Report KA.N KA SUBMITTAL TRANSMITTAL
PROJECT NAME: Pac Trust Bldg. 240&241 Upgrade Date: 2/10/2017
PROJECT NUMBER: 4116033-000 Reference Number: 0048
Description HVAC Rev Submittal Package No 0005-230000-1
Transmitted For Review Due Date 2/15/2017
Delivered Via Email Tracking Number
Package Action
Transmitted To: Transmitted By:
Morgan Toth Lindsey Davis
Mackenzie Skanska USA Building Inc.
1515 SE Water Avenue 222 SW Columbia Street, Suite 300
Suite 100 Portland, OR 97201
Portland, OR 97214 Tel: 503 382 0900
Tel: 503.224.9560 Fax: 503 382 0901
Fax: 503.228.1285
Qty Spec Section Register No Type Item Description Item Action
230000 00154-1 Shop Drawing Building 240 Shop Drawing
230000 00155-1 Shop Drawing Building 241 Shop Drawing
230000 00158-1 Product Data Titus Ceiling Diffusers and Grilles
Sheets
Cc: Company Name Contact Name Copies Notes
Remarks
Please see attached submittal.
Thanks,
Lindsey
Signature do" 02/10/201'7 Signed Date
Printed on: 2/10/2017 6West Page 1
Submittal Review
Stamp Notes
SKANSKA USA BUILDING, INC.
This submittal REVIEW shall not be Construed as
a complete check and indicates only that
information presented conforms generally with
Contract Documents, In no case is Subcontractor Skanska notes in blue
or Supplier relieved of full responsibility for
adherence to the Contract Documents and
satisfactory construction of all work. Submitted to SKA to follow up on BACnet controls
Owner, Architect, Engineer for final approval, for heat pumps
Name: .0. Date,02/10/2017
[
]No exception noted [ ]Rejected
[x]Make corrections noted [ }Revise and resubmit
This review is for general conformance with design
concept only. Any deviation from plans or specifications
not clearly noted by the contractor has not been
reviewed. Review shall not constitute a complete check Mackenzie notes in green
of all detailed dimensions or count or serve to relieve the
contractor of contractual responsibility for any error or
deviation from contract requirements.
Group Mackenzie
By: ajs Date: 02/15/2017
PACTRUST
o APPROVED
El APPROVED AS NOTED*
121 REVISE AND RESUBMIT
o REJECTED a li0..c,011,444-nateci in
o FOR INFORMATION ONLY rMackenafview,,,ReVise ad
11.Resubmit on diffusers as not .
This review is only for general conformance of the project and k' '
' general compliance. Corrections or comments made on these
crawmgs during this review do not relieve
ConaactorlSubcontractor from compliancy with the reculrerronts
of the plans and specifications. Contractor is responsible all
1 dimensions and fabrication to he confirmed and correlated at the
lab sae
BY Michael Plummer DATE 2'15/2017
1