Report (109)
s ►�005kt3 S . COSCO Fire Protection RECEIVED JUL 6 Z018 CITY OF TIGARD BUILDING DIVISION OFFICE COPY Fire Pr t o e tl c on Material Clean Water Services New Building "F" O&M Building TI ‘401A FA 4 1 77506 PE 6-28-2018 OREGON , io Ry L . 04' EXPIRATION DATE:12/31/18 COSCO Fire Protection Inc. Job # 24PD5199 2501 SE Columbia Way, Suite 100 Vancouver,WA 98661 Phone: 360-883-6383 Fax: 360-883-6390 Toll Free: 800-983-6383 TABLE OF CONTENTS SECTION #1 -SPRINKLER HEADS A. Viking, quick response, upright, VK300 B. Viking, standard response, pendent, VK302 C. Viking, quick response, dry sidewall, VK178 SECTION#2-VALVES AND BACKFLOW A. Victaulic, check valve, firelock series 717 B. C. AGF, test an drain, model 1011A C. Deringer— 30, Double Check Detector Assembly SECTION #4-SWITCHES & ELECTRICAL A. Potter, water flow switch, model VSR B. Argo, water gauge C. Brecco, electric bell SECTION#5-CALCULATIONSP A. Water Flow B. Hydraulic calculation - 1 C. USGS Ss value = Cp value of 0.51 D. Seismic calculations - 2 Products may be substituted at Cosco's discretion and will be of equivalent quality ....:.. COSCO I Fire Protection 'IPS' ) 17 ,,)„, „t/r), . ..,) Sprinklers COSCO Fire Protection Inc. 2501 SE Columbia Way, Suite 100 Vancouver,WA 98661 Phone:360-883-6383 Fax: 360-883-6390 Toll Free:800-983-6383 December 4, 2013 Sprinkler 51a MICROFAST°AND NIKINGt TECHNICAL DATA MlcrofastHP° QUICK RESPONSE UPRIGHT AND CONVENTIONAL SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com 1. DESCRIPTION Viking Microfast®and MicrofastHP®Quick Response Upright and Conventional(Old Style)Sprinklers are small,thermosensitive,glass-bulb spray sprinklers available in # •' " ` several different finishes,temperature ratings,and K-Factors to meet design require- ments.The special Polyester,Polytetrafluoroethylene(PTFE),and Electroless Nickel PTFE(ENT)coatings can be used in decorative applications where colors are desired. i In addition,these coatings have been investigated for installation in corrosive atmos- ' pheres and are listed/approved as corrosion resistant as indicated in the Approval ( Charts. (Note: FM Global approves the ENT coating as corrosion resistant. FM . :'UI Global has no approval classification for PTFE and Polyester coatings as corrosion resistant.) _ 2. LISTINGS AND APPROVALS ut os cULus Listed: Category VNIV <> FM Approved: Classes 2002 and 2020 NYC Approved: Calendar Number 219-76-SA and MEA 89-92-E, Volume 16 ABS Certified: Certificate 04-HS407984B-PDA VdS VdS Approved: Certificates G4060054, G4060056, G4880046, G4930039, and G4980020 trze LPC Approved: Ref. No. 096e/03, TE30401, and TE30872 CE Certified: Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001, 0832-CPD-2003, 0786-CPD-40131, 0786-CPD-40171, and 0786-CPD-40278 MED Certified: Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008 NOTE: Other International approval certificates are available upon request. Refer to Approval Chart 1 and Design Criteria on pages 51 c-d for cULus Listing requirements, and refer to Approval Chart 2 and Design Criteria on page 51e for FM Approval requirements that must be followed. 3. TECHNICAL DATA Specifications: Viking Technical Data may be found on Available since 1987. The Viking Corporation's Web site at Minimum Operating Pressure: 7 psi (0.5 bar)* http://www.vikinggroupinc.com. Maximum Working Pressure: Sprinklers VK315 and VK340 are rated for The Web site may include a more recent use with water working pressures ranging from the minimum 7 psi (0.5 edition of this Technical Data Page. bar) up to 250 psi (17 bar) for high-pressure systems. High-pressure (HP)sprinklers can be identified by locating "250" stamped on the de- flector.All other Part Nos. not mentioned above are rated to a maximum 175 psi (12 bar)wwp. Factory tested hydrostatically to 500 psi (34.5 bar) Testing: U.S.A. Patent No. 4,831,870 Thread size: Refer to the Approval Charts Nominal K-Factor: Refer to the Approval Charts Glass-bulb fluid temperature rated to-65 °F (-55 °C) Overall Length: Refer to the Approval Charts *cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE Approvals ONLY is 5 psi(0.35 bar). Material Standards: Frame Casting: Brass UNS-C84400 or QM Brass for Sprinklers 12978, 06766B, 07060, and 12281. Brass UNS-C84400 for all other sprinklers. Deflector: Brass UNS-C23000 or Copper UNS-C19500 for Sprinklers 12978, 06764B, and 12281. Copper UNS-C19500 for Sprinklers 066656, 07060, and 14817. Brass UNS-C26000 for all other Sprinklers. Bushing (for Sprinklers 06719B, 06717B, and 12286): Brass UNS-C36000 Bulb: Glass, nominal 3 mm diameter Form No. F_080488 Replaces page 51a-e, dated June 28, 2013. (Changed 06931 to VK3271) Sprinkler 51b December 4, 2013 MICROFAST®AND TECHNICAL DATA MicrofastHP® QUICK RESPONSE UPRIGHT AND CONVENTIONAL SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape Screw: Brass UNS-C36000 Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400 For PTFE Coated Sprinklers: Belleville Spring-Exposed, Screw-Nickel Plated, Pip Cap-PTFE Coated For Polyester Coated Sprinklers: Belleville Spring-Exposed For ENT Coated Sprinklers: Belleville Spring-Exposed, Screw and Pipcap- ENT plated. Ordering Information: (Also refer to the current Viking price list.) Order Microfast°and MicrofastHP®Quick Response Upright and Conventional Sprinklers by first adding the appropriate suffix for the sprinkler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number. Finish Suffix: Brass =A, Chrome = F, White Polyester= M-/W, Black Polyester= M-/B, and Black PTFE = N, ENT= JN Temperature Suffix (°F/°C): 135°/57° =A, 155°/68° = B, 175°179° = D, 200°/93° = E, and 286°/141° = G For example, sprinkler VK300 with a 1/2"thread, Brass finish and a 155 °F/68 °C temperature rating = Part No. 12978AB Available Finishes And Temperature Ratings: Refer to Table 1. Accessories: (Also refer to the "Sprinkler Accessories" section of the Viking data book.) Sprinkler Wrench: Standard Wrench: Part No. 10896W/B (available since 2000) Sprinkler Cabinets: A. Six-head capacity: Part No. 01724A(available since 1971) B. Twelve-head capacity: Part No. 01725A(available since 1971) 4. INSTALLATION Refer to appropriate NFPA Installation Standards. 5. OPERATION During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. 6. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY The Viking Microfast®and MicrofastHP°Quick Response Upright and Conventional Sprinklers are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking's current list price schedule or contact Viking directly. TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES pnn er .. ." a'r. .a ° Classification = .sting', �' n: _. Ordinary 135 °F (57 °C) 100 °F (38 °C) Orange Ordinary 155 °F (68 °C) 100 °F (38 °C) Red Intermediate 175 °F (79 °C) 150 °F (65 °C) Yellow Intermediate 200 °F (93 °C) 150 °F (65 °C) Green High 286 °F (141 °C) 225 °F (107 °C) Blue Sprinkler Finishes: Brass, Chrome, White Polyester, Black Polyester, Black PTFE, and ENT Corrosion-Resistant Coatings3: White Polyester, Black Polyester, and Black PTFE. ENT in all temperature ratings except 135 °F (57 °C) Footnotes The sprinkler temperature rating is stamped on the deflector. 2 Based on NFPA-13.Other limits may apply,depending on fire loading,sprinkler location,and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 3 The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated on pages 51c-e.These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compatible with or suitable for the proposed environment.For automatic sprinklers,the coatings indicated are applied to the exposed exterior surfaces only.Note that the spring is exposed on sprinklers with Polyester, ENT,and PTFE coatings. For ENT coated automatic sprinklers, the waterway is coated. December 4, 2013 Sprinkler 51c NIKINGg MICROFAST®AND TECHNICAL DATA MicrofastHP® QUICK RESPONSE UPRIGHT AND CONVENTIONAL SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 ,.Fax: 269-818-1680 Email: techsvcs@vikingcorp.com .m ..y Approval Chart 7 (UL) fi `s _-_Temperature KEY Microfast®and MicrofastHP°Quick Response �" ++ Finish Al X f-Escutcheon(if applicable) Upright and Conventional Sprinklers Maximum 175 PSI (12 bar)WWP Base Part Thread Size Nominal K-Factor Overall Length Listings and Approvals3 SIN (Refer also to Design Criteria on page 51d.) Number' NPT BSP U.S. metric2 Inches mm cULus4 NYC° VdS LPCB (E Q Upright-Standard Orifice 12978 VK300 1/2" 15 mm 5.6 80.6 2-3/16 56 Al, B4 See Footnote 7. -- -- -- -- 07060 VK345 -- 15 mm 5.6 80.6 2-3/16 56 -- -- A2 A2 B2t2 B275 Conventional-Standard Orifice 06766B VK310 1/2" 15 mm 5.6 80.6 2-3/16 56 A2 A2 -- A2 B212 B275 Upright-Large Orifice 06665B VK350 3/4" -- 8.0 115.2 2-5/16 59 Al, B4 Al A2 A2 B212 -- 14817 VK350 -- 20 mm 8.0 115.2 2-5/16 59 Al, B4 Al A2 A2 B212 -- 06764B16 VK350 1/2" 15 mm 8.0 115.2 2-5/16 59 Al, B4 Al A2 -- A213 -- Conventional-Large Orifice 06768B VK354 3/4" 20 mm 8.0 115.2 2-5/16 59 Al A2 -- A2 B212 -- Upright-Small Orifice" 067176" VK325 1/2" 15 mm 2.8 40.3 2-3/16 56 Al Al -- -- -- -- 067196" VK327 1/2" 15 mm 4.2 57 2-3/16 56 Al Al -- -- -- -- 069311311 VK3271 -- 10 mm 4.2 57 2-3/16 56 -- -- A2 -- C314 -- Maximum 250 PSI(17 bar)WWP Upright-Standard Orifice Base Part Thread Size Nominal K-Factor Overall Length Listings and Approvals3 SIN (Refer also to Design Criteria on page 51d.) Number NPT BSP U.S. metric2 Inches mm cULus4 NYC° VdS LPCB CE C? 12281 VK315 1/2" 15 mm 5.6 80.6 2-3/16 56 Al Al -- -- -- -- Upright-Small Orificet0 1228611 VK340 1/2" 15 mm 2.8 40.3 2-3/16 56 Al Al -- -- -- -- Approved Temperature Ratings Approved Finishes A- 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 1 Brass, Chrome, White Polyesters s, Black Polyesters s, and 286 °F(141°C) Black PTFE5 B- 155 °F (68 °C), 175°F (79 °C), 200 °F (93 °C), and 286 °F (141°C) 2 Brass, Chrome,White Polyesters s,and Black Polyesters C 155 °F (68 °C) 3- Brass and Chrome 4- ENT5 Footnotes 'Base part number is shown.For complete part number,refer to Viking's current price schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0. 'This table shows the listings and approvals available at the time of printing.Check with the manufacturer for any additional approvals. "Listed by Underwriters Laboratories Inc.for use in the U.S.and Canada. 5cULus Listed as corrosion resistant. 6 Other colors are available on request with the same Listings and Approvals as the standard colors. 7 Meets New York City requirements,effective July 1,2008. 8 Accepted for use,City of New York Board of Standards and Appeals,Calendar Number 219-76-SA. 'Accepted for use,City of New York Department of Buildings,MEA 89-92-E,Vol.16. 10 Listings and Approvals limited to Light Hazard Occupancies where allowed by the installation standards being applied, with hydraulically calculated wet systems only. Exception:4.2K sprinklers may be installed on hydraulically calculated dry pipe systems where piping is corrosion resistant or internally galvanized. "The sprinkler orifice is bushed, 12 C E Certified,Standard EN 12259-1,EC-certificate of conformity 0832-CPD-2001 and 0832-CPD-2003. " (E Certified,Standard EN 12259-1,EC-certificate of conformity 0786-CPD-40278. 14 (E Certified,Standard EN 12259-1,EC-certificate of conformity 0786-CPD-40131. 15 Q MED Certified,Standard EN 12259-1,EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008. i6The 1/2"NPT Large Orifice Sprinkler is Listed and Approved for retrofit only Sprinkler 51d December 4, 2013 NIlam' MICROFAST°AND TECHNICAL DATA MicrofastHP° QUICK RESPONSE UPRIGHT AND CONVENTIONAL SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com u:n;, DESIGN CRITERIA- UL k (Also refer to Approval Chart page cULus Listing Requirements: Microfast°and MicrofastHP Quick Response Upright and Conventional Sprinklers are cULus Listed as indicated in Approval Chart 1 for installation in accordance with the latest edition of NFPA 13 for standard spray sprinklers,or old style(conventional)sprinklers. • Designed for use in Light and Ordinary Hazard occupancies (exception:small orifice sprinklers are limited to Light Hazard where allowed by the installation standards being applied, with hydraulically calculated wet systems only). • The sprinkler installation rules contained in NFPA 13 for standard spray upright sprinklers must be followed. For conventional sprinklers, refer to the installation guidelines for old style(conventional)sprinklers. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page QR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accor- dance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. / Protective Wrench Sprinkler Plat ` --- Cap `itl VIKIING ill 90896 Figure 1: Standard Sprinkler Wrench 10896W/B December 4, 2013 Sprinkler 51e NIKI ik 1e ' MICROFAST®AND 4 TECHNICAL DATA MlcrofastHP° QUICK RESPONSE UPRIGHT AND CONVENTIONAL SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Approval Chart 2 (FM) T eratu r. KEY Microfast® ck Response Upright Sprinklers +i r c Al X 4--Escututcheon I if apphcable) ry Maxi; m.175 PSI (12 bar,)/VW Base Part SIN Thread Size Nominal K-Factor Overall Length FM Approvals' Number' NPT BSP U.S. metric2 Inches mm (Refer also to Design Criteria below.) Standard Orifice 12978 VK300 1/2" 15 mm 5.6 80.6 2-3/16 56 A2, B3 07060 VK345 -- 15 mm 5.6 80.6 2-3/16 56 A2 Large Orifice 06665B VK350 3/4" -- 8.0 115.2 2-5/16 59 A2, B3 14817 VK350 -- 20 mm 8.0 115.2 2-5/16 59 A2, B3 06764B7 VK350 1/2" 15 mm 8.0 115.2 2-5/16 59 A2, B3 Small Orifice" 0671766 VK325 1/2" 15 mm 2.8 40.3 2-3/16 56 Al Approved Finishes Approved Temperature Ratings 1 - Brass and Chrome A- 135 °F (57 °C), 155 °F (68 °C), 175 °F(79 °C), 200 °F (93 °C), and 286 °F (141°C) 2 - Brass, Chrome, White Polyesters, and Black B- 155 °F(68 °C), 175 °F (79°C), 200°F (93 °C), and 286 °F(141°C) Polyesters 3 - ENT8 Footnotes 'Base part number is shown. For complete part number, refer to Viking's current price schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0. 3This table shows the FM Approvals available at the time of printing. Check with the manufacturer for any additional approvals. ^ FM Approved as quick response Non-Storage pendent sprinklers. For specific application and installation requirements, reference the latest appli- cable FM Loss Prevention Data Sheets(including Data Sheet 2-0). s Other colors are available on request with the same Approvals as the standard colors. 6 The sprinkler orifice is bushed. 'The 1/2"NPT Large Orifice Sprinkler is Listed and Approved for retrofit only °FM approved as corrosion resistant. i - T IA I A of ®Ap •v a �,) FM Approval Reauirements: The sprinklers indicated in Approval Chart 2 are FM Approved as quick response Non-Storage upright sprinklers as indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets(including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to,but not limited to:minimum water supply requirements,hydraulic design,ceiling slope and obstructions, minimum and maximum allowable spacing,and deflector distance below the ceiling. NOTE:The FM installation guidelines may differ from cULus and/or NFPA criteria. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page QR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac- cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD,VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. December 12, 2013 Sprinkler 41a NIKINIG® ICROFAST®AND TECHNICAL DATA :fil icrofastHP® QUICK RSPONSE PENDENT SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com 1. DESCRIPTION Viking Microfast® and MicrofastHP° Quick Response Pendent Sprinklers are small, thermosensitive, glass-bulb spray sprinklers available in several different finishes and temperature ratings and K-Factors to meet design requirements. The special Polyester,Polytetrafluoroethylene (PTFE), and Electroless Nickel PTFE (ENT) coatings can be used in decorative applications where colors are desired. In ad- l7:::;Isf.N dition, these coatings have been investigated for installation in corrosive atmos- pheres and are listed/approved as corrosion resistant as indicated in the Approval a Charts. (Note: FM Global approves ENT finish as corrosion resistant. FM Global has no approval classification for PTFE and Polyester coatings as corrosion resist- ant.) 2. LISTINGS AND APPROVALS };- ut U5 cULus Listed: Category VNIV„ FM Approved: Classes 2001, 2002, 2015, and 2017pN 1297966666 NYC Approved:Calendar Number 219-76-SA and MEA 89-92-E,Volume 16 ABS Certified: Certificate 04-HS407984C-PDA vds VdS Approved: Certificates G4040095, G4040097, G4060056, G4060057, G4880045, G4930038, and G4980021 r,,,'. LPC Approved: Ref. Nos. 096e/03 and 096e104 (E CE Certified: Standard EN 12259-1, EC-certificates of conformity 0786-CPD-40130, 0786-CPD-40170 and 0786-CPD- 402790832-CPD-2001and 0832-CPD-2003 , MED Certified: Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008 NOTE: Other International approval certificates are available upon request. Refer to Approval Chart 1 and Design Criteria on page 41d for cULus Listing requirements and refer to Approval Chart 2 andDesign Criteria on page 41f for FM Approval requirements that must be followed. 3. TECHNICAL DATA Specifications: Available since 1987. Minimum Operating Pressure: 7psi (0.5 bar)* Viking Technical Data may be found on Maximum Working Pressure: Sprinklers 12282 and 12290 are rated for use with water working pressures ranging from the minimum 7 psi The Viking Corporation's Web site at (0.5 bar) up to 250 psi (17 bar)for high-pressure systems. High-pres- http:/lwww.vikinggroupinc.com. sure (HP) sprinklers can be identified by locating "250" stamped on The Web site may include a more recent the deflector.All other Part Nos. not mentioned above are rated to a edition of this Technical Data Page. maximum 175 psi (12 bar)wwp. Factory tested hydrostatically to 500 psi (34.5 bar) Thread size: Refer to the Approval Charts Nominal K-Factor: Refer to the Approval Charts Glass-bulb fluid temperature rated to-65 °F (-55 °C) Overall Length: Refer to the Approval Charts *cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE Approvals ONLY is 5 psi (0.35 bar). Material Standards: Frame Casting: Brass UNS-C84400 or QM Brass for Sprinklers 12979 and 12282. Brass UNS-C84400 for all other sprinklers. Deflector: Phosphor Bronze UNS-C51000 or Copper UNS-C19500 for Sprinklers 12979, 06666B, and 06765B. Copper UNS- C19500 for Sprinkler 12282. Phosphor Bronze UNS-C51000,Copper UNS-C19500 or Brass UNS-C26000 for Sprinkler 06720B. Brass UNS-C26000 for all other Sprinklers. Bushing (for Sprinklers 06718B, 06720B, and 12290): Brass UNS-C36000 Bulb: Glass, nominal 3 mm diameter Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape Screw: Brass UNS-C36000 Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400 For PTFE Coated Sprinklers: Belleville Spring-Exposed, Screw-Nickel Plated, Pip Cap-PTFE Coated For Polyester Coated Sprinklers: Belleville Spring-Exposed For ENT Coated Sprinklers: Belleville Spring-Exposed, Screw and Pipcap- ENT coated. Form No. F_081296 Replaces page 41a-f, dated December 4, 2013. (Added E-3 Escutcheon) Sprinkler 41b December 12, 2013 N 1 I< N G A MICROFAST®AND TECHNICAL DATA MicrofastHP® QUICK RESPONSE PENDENT SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Ordering Information: (Also refer to the current Viking price list.) Order Microfast°and MicrofastHP°Quick Response Pendent Sprinklers by first adding the appropriate suffix for the sprinkler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number. Finish Suffix: Brass =A, Chrome = F, White Polyester= M-/W, Black Polyester= M-/B, Black PTFE = N, and ENT= JN Temperature Suffix: 135 °F (57 °C) =A, 155 °F (68 °C) = B, 175 °F (79 °C) = D, 200 °F (93 °C) = E, and 286 °F (141 °C) = G For example, sprinkler VK302 with a 1/2"thread, Brass finish and a 155 °F (68 °C)temperature rating = Part No. 12979AB Available Finishes And Temperature Ratings: Refer to Table 1. Accessories: (Also refer to the"Sprinkler Accessories" section of the Viking data book.) Sprinkler Wrenches: A. Standard Wrench: Part No. 10896W/B (available since 2000). B. Wrench for Recessed Pendent Sprinklers: Part No. 16036W/B* (available since 2011) C. Optional Protective Sprinkler Cap Remover/Escutcheon Installer Tool** Part No. 15915 (available since 2010.) *A'/2"ratchet is required(not available from Viking). **Allows use from the floor by attaching a length of 1"diameter CPVC tubing to the tool. Ideal for sprinkler cabinets. Refer to Bulletin F_051808. Sprinkler Cabinets: A. Six-head capacity: Part No. 01724A(available since 1971) B. Twelve-head capacity: Part No. 01725A(available since 1971) 4. INSTALLATION Refer to appropriate NFPA Installation Standards. 5. OPERATION During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. 6. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection,Testing and Maintenance require- = wrench ments. Flat llksm Protective IIS\ /II II\ Protective Sprinkler 7. AVAILABILITY I Sprinkler 1111.- -111111pCap The Viking Microfast®and MicrofastHP®Quick Response Pendent 0 ■ � Shield Sprinklers are available through a network of domestic and international distributors. See The Viking Corporation web site for ' ,_... ring I g!. the closest distributor or contact The Viking Corporation. II'.lwj'_ 8. GUARANTEE For details of warranty, refer to Viking's current list price schedule 6) or contact Viking directly. Figure 1: Standard Sprinkler Wrench 10896W/B December 12, 2013 Sprinkler 41c MICROFAST®AND NIKING** TECHNICAL DATA MicrofastHP® QUICK RESPONSE PENDENT SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com TABLE 1:AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Spri r Temperature .: kler Nominal MaXi, , - :Ment Classification ,mperature Rating' Ceiling Temperature2 Bulb Color Ordinary 135 °F (57 °C) 100 °F (38 °C) Orange Ordinary 155 °F (68 °C) 100 °F (38 °C) Red Intermediate 175 °F (79 °C) 150 °F (65 °C) Yellow Intermediate 200 °F (93 °C) 150 °F (65 °C) Green High 286 °F(141 °C) 225 °F (107 °C) Blue Sprinkler Finishes: Brass, Chrome, White Polyester, Black Polyester, Black PTFE, and ENT Corrosion-Resistant Coatings3: White Polyester, Black Polyester, and Black PTFE. ENT in all temperature ratings except 135 °F (57 °C). Footnotes 'The sprinkler temperature rating is stamped on the deflector. 2 Based on NFPA-13.Other limits may apply,depending on fire loading,sprinkler location,and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 3 The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts.These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are com- patible with or suitable for the proposed environment. For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces only. Note that the spring is exposed on sprinklers with Polyester, PTFE, and ENT coatings. For ENT coated automatic sprinklers,the waterway is coated. 1 I 1 11 L _J 111L—;'—Y115 .i=l!\ I 'J nil. —\ IliL_Jii I `= i Sprinkler Wrench A —- - \ 160nkler � for installing recessed R i;Ii;IIi 1 pendent sprinklers . - . I \= I AWA 1/2' ratchet is required n (not available from Viking). r •� Carefully slide thet f L'_==J_=J I I wrench sideways around the protective II II II cap, ensuring engage— ment with the sprinkler wrench flats. Figure 2: Wrench 16036W/B for Recessed Pendent Sprinklers Sprinkler 41d December 12, 2013 : MICROFAST®AND NEKING TECHNICAL DATA MicrofastHP® QUICK RESPONSE PENDENT SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Approval Chart 1 (UL) Temperature KEY Microfast®and MicrofastHP°Quick Response Pendent Sprinklers +: Finish Maximum 175 PS 1 2 bar)WWF. A1X4-Escutcheon{f applicable) Sprinkler Thread Size Nominal Overall Listings and Approvals' Base SIN K-Factor Length (Refer also to Design Criteria on page 41e.) Part No.' NPT BSP U.S. metric2 Inches mm cULus4 NYC' VdS LPCB CE 0 Standard Orifice 12979 VK302 1/2" 15 mm 5.6 80.6 2-1/4" 57 A1X,B1Y,C4,E4Z A1X,B1Y — -- -- — 18021 VK302 1/2" 15 mm 5.6 80.6 2-1/4" 58 AIX,B1Y AIX,B1Y A2 A2X,B2Y C2X,E2Y" C2X,E2Y14 Large Orifice 06666B VK352 3/4" 20 mm 8.0 115.2 2-3/8" 60 A1X,B1Y,C4,E4Z A1X,B1Y A2 A2X C211 -- 06765B15 VK352 1/2" 15 mm 8.0 115.2 2-3/8" 60 A1X,B1Y,C4,E4Z A1X,B1Y A2 -- A212 -- Small Orifice8 0671869 VK329 1/2" 15 mm 2.8 40.3 2-3/16" 56 A1X,B1Y AIX,B1Y -- -- -- -- 06720B9 VK331 1/2" 15 mm 4.2 57 2-1/4" 58 A1X,B1Y A1X,B1Y -- -- -- -- 06932B VK331 -- 10 mm 4.2 57 2-3/8" 60 -- -- A2 -- G313 -- Maximum 250 PSI(17 bar)WWP Standard Orifice Sprinkler Thread Size Nominal Overall Listings and Approvals' Base SIN K-Factor Length (Refer also to Design Criteria on page 41e.) Part No' NPT BSP U.S. metric2 Inches mm cULus4 NYC" VdS LPCB C f 0 12282 VK317 1/2" 15 mm 5.6 80.6 2-1/4" 58 A1X,B1Y A1X — -- -- -- Maximum 250 PSI (17 bar)WWP Small Orifices 1229010 VK342 1/2" 15 mm 2.8 40.3 2-3/16" 56 A1X,B1Y A1X -- -- -- -- Approved Temperature Ratings A-135°F(57°C),155°F(68°C),175°F(79°C),200°F(93°C),and 286°F(141 °C) Approved Finishes Approved Escutcheons B-135°F(57°C), 155°F(68°C), 175°F(79°C),and 200°F(93 1 - Brass, Chrome, White Polyesters', Black X - Standard surface-mounted escutcheon or the Viking Microfast® Model F-1 Adjustable °C) Polyester6'7,and Black PTFE' Escutcheon C-155°F(68°C),175°F(79°C),200°F(93°C),and 286°F(141 2-Brass,Chrome,White Polyester7,and Black Y - Standard surface-mounted escutcheon or the ° Polyester7 Viking Microfast®Model F-1 Adjustable Escutcheon D-135°F(57°C),155°F(68°C),175°F(79°C),and 286°F(141 3-Brass and Chrome or recessed with the Viking Micromatic®Model E- °C) 4-ENT' 1,E-2,or E-3 Recessed Escutcheon E-155°F(68°C),175°F(79°C),and 200°F(93°C) Z - Standard surface-mounted escutcheon or re- F-155°F(68°C),175°F(79°C),and 286°F(141 °C) cessed with the Viking Micromatic®Model E-1 G-155°F(68°C) Footnotes 1 Base part number is shown.For complete part number,refer to Viking's current price schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0. 3 This table shows the listings and approvals available at the time of printing.Check with the manufacturer for any additional approvals. 4 Listed by Underwriters Laboratories Inc.for use in the U.S.and Canada. 5 Accepted for use,City of New York Board of Standards and Appeals,Calendar Number 219-76-SA. 6 cULus Listed as corrosion resistant. 7 Other colors are available on request with the same Listings and Approvals as the standard colors. 6 Listings and Approvals limited to Light Hazard Occupancies where allowed by the installation standards being applied,with hydraulically calculated wet systems only. Exception:4.2K sprinklers may be installed on hydraulically calculated dry pipe systems where piping is corrosion resistant or internally galvanized. 9 The sprinkler orifice is bushed. "Accepted for use,City of New York Department of Buildings,MEA Number 89-92-E,Vol.16. " CE Certified,Standard EN 12259-1,EC-certificates of conformity 0832-CPD-2001 and 0832-CPD-2003. t2 CE Certified,Standard EN 12259-1,EC-certificate of conformity 0786-CPD-40279. 13 CE Certified,Standard EN 12259-1,EC-certificate of conformity 0786-CPD-40130 and 0786-CPD-40170. 14•MED Certified,Standard EN 12259-1,EC-certificates of conformity 0832-MED-1003 and 0832-MED-1008. "5 The 1/2"NPT Large Orifice Sprinkler is Listed and Approved for retrofit only. December 12, 2013 Sprinkler 41e NIKINGR MICROFAST®AND TECHNICAL DATA MicrofastHP® QUICK RESPONSE PENDENT SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com DES%N CRITERIA- UL _ . ,,, ... (Also refer to Approval Chart 1 on page 41d) cULus Listing Requirements: Microfast®and MicrofastHP®Quick Response Pendent Sprinklers are cULus Listed as indicated in the Approval Chart for installation in accordance with the latest edition of NFPA 13 for standard spray sprinklers. • Designed for use in Light and Ordinary Hazard occupancies (exception:small orifice sprinklers are limited to Light Hazard where allowed by the installation standards being applied, with hydraulically calculated wet systems only). • The sprinkler installation rules contained in NFPA 13 for standard spray pendent sprinklers must be followed. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page QR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accor- dance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. Ceiling Opening Size: 2-5/16" (58.7 mm) minimum 2-1/8" 2-1/2" (63.5 mm) maximum - (54 mm) 1/2' (15 mro) —\ lM=W/ill MI NPT _s 1 �e�9�omo� �s:�°I�OfJAI Ili 1- 4" to 2 1/4" <44,5 mm) 2" 1 1/2" (38,1 mm) 41 mm WA (58mm) (50,8mm) Minimum (41 mm) _ Maximum Installed with a Pendent Sprinkler standard 1/8" surface Installed with a Microfast mounted escutcheon. Model F-1 Adjustable Escutcheon ) Note: At maximum, adapter is exposed 1/2" (12.7 mm) from face of ceiling. Figure 3: Sprinkler VK302 Dimensions with a Standard Escutcheon and the Model F-1 Adjustable Escutcheon 2-1/8" Ceiling Opening Size: 2-1/8" (54 mm) 2-5/16" (58,7 mm) minimum (54 mm) 2-1/2" (63,5 mm) maximum IL. i�iI - M. I 1AIM.11 moor �t:Ilw•w homo(I_ ' 1 3/4" !i! 1-1/8" (28.6 mm) IP 1 1/8" (28.6 mm) Minimum 2" (44,5 mm) I i (50.8 mm) Minimum Maximum __-_ i Maximum ..._ _.... Installed with a Micromatic Model E-1 Recessed Escutcheon Installed with a thread on Model E-2 Recessed Escutcheon Figure 4: Sprinkler VK302 Dimensions with the Model E-1 and E-2 Recessed Escutcheons • • Sprinkler 41fDecember 12, 2013 N11(iNG. MICROFAST®AND TECHNICAL DATA MicrofastHP® QUICK RESPONSE PENDENT SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Approval<�Chart 2 (FM) Tef„perature KEY ' Microfast®Quick Response Pendent Sprinklers 1. Finish Maximum 175 PSI'(12 bar)WWP A1Xf-?'Escutcheon{if applicable)3 i Sprinkler Thread Size Nominal K-Factor Overall Length FM Approvals3 Base Part No.1 SIN NPT BSP U.S. metric2 Inches mm (Refer also to Design Criteria below.) Standard Orifice 12979 VK302 1/2" 15 mm 5.6 80.6 2-1/4" 57 A2X, B2Y,C3, D3Z 18021 VK302 1/2" 15 mm 5.6 80.6 2-1/4" 58 A2X, B2Y Large Orifice 06666B VK352 3/4" 20 mm 8.0 115.2 2-3/8" 60 A2X, B2Y,C3, D3Z 06765B7 VK352 1/2" 15 mm 8.0 115.2 2-3/8" 60 A2X, B2Y,C3, D3Z Small Orifice4 06718B6 VK329 1/2" 15 mm 2.8 40.3 2-3/16" 56 A1X Approved Temperature Ratings Approved Escutcheons A-135°F(57°C), 155°F(68°C), 175°F(79°C), X-Standard surface mounted escutcheon or the Viking 200°F(93°C),and 286°F(141 °C) Approved Finishes Microfast®Model F-1 Adjustable Escutcheon B-135°F(57°C), 155°F(68°C), 175°F(79°C), 1 -Brass and Chrome Y - Standard surface-mounted escutcheon or the and 200°F(93°C) 2 - Brass, Chrome, White Polyesters, and Viking Microfast®Model F-1 Adjustable Escutcheon C-155°F(68°C), 175°F(79°C),200°F(93°C), Black Polyesters or recessed with the Viking Micromatic®Model E-1, and 286°F(141 °C) 3- ENT' E-2,or E-3 Recessed Escutcheon D - 155 °F (68 °C), 175 °F (79 °C), and 200 °F Z-Standard surface-mounted escutcheon or recessed (93°C) with the Viking Micromatic®Model E-1 Footnotes ' Base part number is shown. For complete part number, refer to Viking's current price schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0. 3 This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals. 'FM Approved as quick response control mode standard spray Non-storage sprinklers.For specific application and installation requirements,reference the latest applicable FM Loss Prevention Data Sheets(including Data Sheet 2-0). 5 Other colors are available on request with the same Listings and Approvals as the standard colors. 6 The sprinkler orifice is bushed. 'The 1/2"NPT Large Orifice Sprinkler is Listed and Approved for retrofit only. 8 FM approved as corrosion resistant. DESIGN CRITERIA- FM : (Also refer to Approval Chart 2 above.) u FM Approval Requirements: The sprinklers indicated in Approval Chart 2 are FM Approved as quick response Non-storage standard spray pendent sprinklers as indicated in the FM Approval Guidet. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets(including Data Sheets 2-0 and 8-9).FM Global Loss Prevention Data Sheets contain guidelines relating to,but not limited to:minimum water supply requirements, hydraulic design, ceiling slope and obstructions,minimum and maximum allowable spacing, and deflector distance below the ceiling. NOTE:The FM installation guidelines may differ from cULus and/or NFPA criteria. tSprinklers VK302 and VK352 are also FM Approved as quick response Rack Storage standard spray pendent sprinklers. Refer to technical data page 131a-e for Intermediate Level In-Rack Sprinklers. IMPORTANT:Always refer to Bulletin Form No. F 091699-Care and Handling of Sprinklers.Also refer to page QR1-3 for gen- eral care, installation, and maintenance information.Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. Form No. F_081296 Replaces page 41a-f, dated December 4, 2013. (Added E-3 Escutcheon) Page 1 of 8 NitaiNG, QUICK RESPONSE TECHNICAL DATA DRY HORIZONTAL SIDEWALL SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com 1. DESCRIPTION Viking Quick Response Dry Horizontal Sidewall Sprinklers are thermosensitive spray sprinklers suitable for use in areas subject to freezing. The sprinklers are - _ L designed for dry systems and preaction systems where it is necessary to prevent E_ water or condensation from entering the drop nipple before sprinkler operation. They may also be installed in spaces subject to freezing and supplied from a wet system in an adjacent heated area. (-- Viking Quick Response Dry HSW Sprinklers are available in various finishes I � _ a' and temperature ratings to meet design requirements. The special Polyester and Electroless Nickel PTFE (ENT) coatings have been investigated for installation in corrosive atmospheres and are listed/approved as corrosion resistant as indi- cated in the Approval Charts. (Note: FM Global has no approval classification for �II„IIIIIII�II Polyester coatings as corrosion resistant.) NOTE: When installed in some corrosive environments, the Polyester finish may change color.This natural discoloration over time is not in itself an indi- cation of corrosion and should not be treated as such.All sprinklers installed For Light Hazard Occupancies Only in corrosive environments should be replaced or tested as described in NFPA 25 on a more frequent basis. 2. LISTINGS AND APPROVALS cULus Listed: Category VNIV Ut FM Approved: Classes 2013 and 2015 <> NYC Approved: MEA 89-92-E,Volume 15 Refer to Approval Chart 1 and Design Criteria on page 106c for cULus Listing requirements, and refer to Approval Chart 2 and Design Criteria on page 106d for FM Approval requirements that must be followed. 3. TECHNICAL DATA Specifications: Available since 1993. Minimum Operating Pressure: 7 psi (0.5 bar) Maximum Working Pressure: 175 psi (12 bar). Factory tested pneumatically to 100 psi (6.89 bar) Thread size: 1” NPT or 25 mm BSP Nominal K-Factor: 5.6 U.S. (80.6 metric")for all listed and approved lengths. *Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0. Glass-bulb fluid temperature rated to-65 °F (-55 °C) Covered by the following U.S. Patent numbers: 8,636,075 and 8,376,060 Viking Technical Data may be found on Material Standards: The Viking Corporation's Web site at Frame Casting: Brass UNS-C84400 http://www.vikinggroupinc.com. Deflector: Phosphor Bronze UNS-C51000 The Web site may include a more recent Bulb: Glass, nominal 3 mm diameter edition of this Technical Data Page. Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape Compression Screw: Brass UNS-C36000 Pip Cap: Brass UNS-C31400 or UNS-C31600 Pip Cap Adapter: Brass UNS-C36000 Orifice: Copper UNS-C22000 or UNS-C11000 Tube: ERW Hydraulic Steel Tube Support(Internal): Stainless Steel UNS-S30400 Barrel: Steel Pipe UNS-G10260, Electrodeposited Epoxy Base finish Barrel End and Threads: QM Brass Sleeve (for Adjustable Standard style only): Brass UNS-C26000 or UNS-C26800 Escutcheon Materials: Adjustable Standard Dry Escutcheons: Brass UNS-C26000 or UNS-C26800 Recessed Dry Escutcheons: Cold Rolled Steel UNS-G10080 ENT Coated Adjustable and Recessed Escutcheons: Stainless Steel UNS-S30400 Ordering Information: (Also refer to the current Viking price list.) Order QR Dry HSW Sprinklers by first adding the appropriate suffix for the sprinkler finish,the appropriate suffix for the temperature rating, and then the suffix for the length("A"dimension)to sprinkler base part number.Order in a specific length noted as the"A"dimension.The "A"dimension is the distance from the face of the fitting (tee)to the desired finished surface of the wall in which it is to be installed. Form No. F 031993 Rev 15.1 Page 2 of 8 QUICK RESPONSE NlluNG* TECHNICAL DATA DRY HORIZONTAL SIDEWALL SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings M 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com These sprinklers are listed and approved in lengths from 1-1/2'1',4„o 45-1/2"(38.1 mm to 1,156 mm)for the adjustable standard style, 3"to 47"(76.2 mm to 1,194 mm)for the plain barrel style, and 3- to 47-1/2"(82.5 mm to 1,207 mm)for the adjustable recessed style. Lengths exceeding the standard lengths are available,with no/approv1a3on a."made-to-order"basis: Recessed Dry HSW up to 65- 1/2" (1,664 mm).Adjustable Standard Dry HSW up to 63-1/2" (1,613 mm). Plain Barrel Dry HSW up to 65"(1,651 mm). Contact the manufacturer for more information. Finish Suffix: Brass =A, Chrome = F,White Polyester= M-/W, and ENT= JN Temperature Suffix: 155 °F (68 °C) = B, 175 °F (79 °C) = D, 200 °F (93 °C) = E, 286 °F (141 °C)= G Escutcheon Suffix = Y for the adj. recessed sprinkler with the Model G-1 Escutcheon (no suffix needed for the Model E-1 Escutcheon). NOTE Sprinkler is turned sideways For example, sprinkler VK182 with 1" NPT Threads, a Chrome finish, a 155 for clarity (Refer to Figures 2-7 °F(68°C)temperature rating,the Model G-1 Escutcheon, and"A"length for correct deflector orientation) of 10" = Part No. 08386UFBY10. Protective Available Finishes And Temperature Ratings: Refer to Table 1. Sprinkler Accessories: (Also refer to the"Sprinkler Accessories" section.) Shield Sprinkler Wrenches: • I- A. Standard Wrench: Part No. 07297W/B (available since 1991) ' ;•Ig,I B.Wrench for recessed sprinklers:Part No.07565W/B**(available since 1991) I!, �.' "A'/2'ratchet is required (not available from Viking). I -t ■I Dry Sprinkler Protective Cover: Part No. 15610 i; �� r Replacement Escutcheons: A.Adjustable Standard Dry Escutcheon: Base Part No. 08086F Wrench B. Model E-1 Recessed Dry Escutcheon Cup: Base Part No. 05459A Plat 4. INSTALLATION Refer to appropriate NFPA Installation Standards. 5. OPERATION VIKING 00290 O During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the internal parts to open the water- way.Water flowing through the sprinkler orifice strikes the sprinkler deflector, Figure 1: forming a uniform spray pattern to extinguish or control the fire. 6. INSPECTIONS, TESTS AND MAINTENANCE Standard Sprinkler Wrench 07297W/B Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY The Viking Quick Response Dry Horizontal Sidewall Sprinkler is available through a network of domestic and international distribu- tors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking's current list price schedule or contact Viking directly. -. TABLE 1:AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES • m1 t era rt, • r. e Ordinary 155 °F (68 °C) 100 °F (38 °C) Red Intermediate 175 °F (79 °C) 150 °F (65 °C) Yellow Intermediate 200 °F 93 °C 150 °F 65 °C Green Hi.h 286 °F 141 °C 225 °F 107 °C Blue Sprinkler Finishes: Brass, Chrome, White Polyester, and ENT Corrosion-Resistant Coating3'4: White Polyester and ENT in all temperature ratings Footnotes 'The sprinkler temperature rating is stamped on the deflector. z Based on NFPA-13.Other limits may apply,depending on fire loading,sprinkler location,and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 3 The corrosion-resistant Polyester and ENT coatings have passed the standard corrosion test required by the approving agencies indi- cated in the Approval Charts. These tests cannot and do not represent all possible corrosive environments. Note: These coatings are NOT corrosion proof. Prior to installation,verify through the end-user that the coatings are compatible with or suitable for the proposed environment.Polyester and ENT coatings are applied to the exposed exterior surfaces only. Note that the spring is exposed on sprinklers with Polyester and ENT coatings. 4 When installed in some corrosive environments,the Polyester finish may change color.This natural discoloration over time is not in itself an indication of corrosion and should not be treated as such.All sprinklers installed in corrosive environments should be replaced or tested as described in NFPA 25 on a more frequent basis. Form No. F_031993 Rev 15.1 Page 3 of 8 NiiciNGT37, QUICK RESPONSE TECHNICAL DATA DRY HORIZONTAL SIDEWALL SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com ,- **Note A 1/2" ratchet is required Sprinkler Wrench Part (Not available from Viking). No. 07565W/BNw for installing recessed dry sprinklers. .----- ----I -I,I' N .___t ----- 'L 1 I Step 1 Carefully slide the Step 2: Press the wrench onto wrench sideways around the the sprinkler wrench flats and deflector and protective , turn slightly to ensure engage- _Ashield as shown. \ cent with the wrench flats. Figure 2: Wrench 07565W/B for Adjustable Recessed Dry Horizontal Sidewall Sprinklers For "A" Dimension, 1. Determine the distance from the face of 11111111111111111111111111111111111111111E Deflector at NOTE: the tee to the finished face of the wall, T Minimum Distance To locate the deflector 2. Round to the nearest 1/2" (12.7 mm) between Finished Ceiling From Wall at the minimum distance 1-1/2' (38.1 mm) and 45-1/2' (1,156 mm). from the wall, with no adjustment available, NOTE: The deflector will extend approximately Finished Wall M k order the standard dry 4-1/8" (104.8 mm) from the wall pwith 2' +/- 4' (102 mm) Minimum �•�I horizontal sidewall sprink- 1' (25.4 mm) horizontal adjustment available. 6' (152 mm) MaximumE ler V (25.4 mm) shorter A3-1/8" -than the "A' Dimension. (79.4 rim) ���������.� Deflector at NOTE: i I'�Ii l��i I L �� 3-1/16" Maximum Distance To locate the deflector �� ���i _.-_ 07,8 mm) From Wall at the maximum distance �S from the wall, with no Ill adjustment available, --*,���� I \ ,� '-i order the standard dry 111 \ 5/8' (15.9 mm) horizontal sidewall sprink- Minimum wall o peninler 1' (25.4 mm) longer P 9 5-1/8' than the 'A' Dimension. _ diameter: 1-3/4" (44,5 mm). I Sleeve diameter: (130.2 mm) Maximum wall opening 1-1/2' (38.1 mm). diameter: 2-1/4" (57 mm). 13/16' Sleeve finish matches x May be allowed up to 18' (457 mm) for certain (20.6 mm) finish of escutcheon. FM installations. Refer to the appropriate installation standards, including NFPA 13 and/or FM Loss Prevention Data Sheet 2-0. Figure 3: Adjustable Standard Dry Horizontal Sidewall Sprinkler IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIE IIlllllllllllllllllllllllllllllllllllME Illlllllllllllllllllllllllllllllllllll M Illlllllllllllllllllllllllllllllllllll M MHllllllllllllllllllllllllllllllll ME Slot— Deflector — — _ — Slot Push and Rotate Oa11 �a�I�1 illi .-_ •II U1_0111 Sleeve I STEP 1: Align the slot In STEP 2, Push the rounded STEP 3: Pull the escutcheon STEP 4: Push and rotate STEP 5: To minimize the escutcheon with the end of the slot against -the away from the near edge -the escutcheon onto the visibility of the slot horizontal surface of near edge of the deflector. of the deflector. Move the sleeve. in the escutcheon, the deflector as shown. Push the far side of the near side of the escut- position the slot escutcheon past the deflec- cheon over the deflector. at the -top of the tor, toward the sleeve. sprinkler sleeve. Figure 4: Adjustable Standard Escutcheon Installation Form No. F_031993 Rev 15.1 • Page 4 of 8 Nit(ING® QUICK RESPONSE TECHNICAL DATA DRY HORIZONTAL SIDEWALL SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Approval Chart 1 (UL) TFmshemperatureal Quick Response Dry Horizontal Sidewall Sprinklers 1KEY For Light Hazard Occupancies Only A1X+-Escutcheon ft applicable) Maximum 1 SI (12 b f9" U P Sprinkler Base Thread Size NominalOrder Length Listings and Approvals4 Part No.' SIN Style K-Factor2 Increment (Refer also to Design Criteria on page 106e.) NPT BSP U.S. metric' Inches mm cULuss NYCE VdS LPCB (f 0 08384U Adjustable 1" -- 5.6 80.6 1/2" 12.7 Al,A5 Al -- -- -- -- 16458U VK178 Standard -- 25 mm -- 80.6 1/2" 12.7 Al,A5 -- 08386U Adjustable 1" -- 5.6 80.6 1/4" 6.35 B2, B6 B2 -- -- -- -- VK182 16454U Recessed -- 25 mm -- 80.6 1/4" 6.35 B2, B6 -- -- -- -- -- 08388U 1" -- 5.6 80.6 1/2" 12.7 A3 A4 -- -- -- -- 16456U VK174 Plain Barrel -- 25 mm -- 80.6 1/2" 12.7 A3 -- Approved Finishes and "A" Dimensions 1* - Chrome, or White Polyester' sprinkler with a Chrome, Brass, or White Polyester Sleeve and Escutcheon with"A"dimensions 1-1/2"to 45-1/2"(38.1 mm to 1,156 mm) Approved Temperature Ratings 2* - Chrome, or White Polyester' with "A" dimensions 3-1/4" to 47-1/2" (82.5 mm to 1,207 A- 155 °F (68 °C), 175 °F (79°C), 200 °F mm) (93 °C), and 286 °F(141 °C) 3-Chrome, Brass,White Polyester',or ENT'with"A"dimensions 3"to 47"(76.2 mm to 1,194 mm) B - 155 °F (68 °C), 175 °F (79 °C), and 4-Chrome or Brass with"A"dimensions 3"to 47" (76.2 mm to 1,194 mm) 200°F(93 °C) 5- ENT'sprinkler with an ENT'Sleeve and Escutcheon with"A"dimensions 1-1/2"to 45-1/2" (38.1 mm to 1,156 mm) 6- ENT'with "A" dimensions 3-1/4" to 47-1/2" (82.5 mm to 1,207 mm) *Brass Finish is listed and approved but not standard offering,lead times of 6-8 weeks required. (Matching Brass escutcheons are not available.) Footnotes ' Part number shown is the base part number. For complete part number, refer to current Viking price list schedule. 2 K-Factor applies for standard lengths("A" Dimensions indicated above). Metric K-factor shown is for use when pressure is measured in bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0. °This chart shows the listings and approvals available at the time of printing.Other approvals may be in process.Check with the manufacturer for any additional approvals. 5 Listed by Underwriter's Laboratories for use in the U.S.and Canada for Light Hazard occupancies only. 6 Accepted for use,City of New York Department of Buildings, MEA Number 89-92-E,Vol. 15. 'cULus Listed as corrosion resistant. DESIGN CRITERIA- UL kat. (Also refer to Approval Chart 1 above) <s NOTE:When using CPVC fittings with Viking dry sprinklers,use only new Nibco Model 5012-S-Bl tees.When selecting other CPVC fittings, contact Viking Technical Services. cULus Listing Requirements: Quick Response Dry Horizontal Sidewall Sprinklers are cULus Listed as indicated in Approval Chart 1 for installation in accordance with the latest edi- tion of NFPA 13 for standard spray sprinklers. • Limited to Light Hazard occupancies only. • Protection areas and maximum spacing shall be in accordance with the tables provided in NFPA 13. • Minimum spacing allowed is 6 ft. (1.8 m). • Deflector must be positioned between 4"and 6" (102 mm and 152 mm) below the ceiling. Keep the top of the deflector oriented parallel with the ceiling. • Locate no less than 4"(102 mm)from end walls. • Maximum distance from end walls shall be no more than one-half of the allowable distance between sprinklers.The distance shall be measured perpendicular to the wall. • The sprinkler installation and obstruction rules contained in NFPA 13 for sidewall standard spray sprinklers must be followed. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page DRY1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB,APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. Form No. F_031993 Rev 15.1 Page 5 of 8 QUICK RESPONSE TECHNICAL DATA DRY HORIZONTAL SIDEWALL SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Approval Chart 2 (FM) Temperature KEY Quick Response Dry Horizontal Sidewall Sprinklers �;Finish 1X4—Escutcheon(if applicable) For Light Hazard Occupancies Only ,24iv Maxi 175 PSI (12 bar)WWP x3k _ Sprinkler Base SIN Style Thread Size Nominal K-Factor2 Order Length Increment FM Approvals4 Part No.1 NPT BSP U.S. metric' Inches mm (Refer also to Design Criteria below.) 08384U 1" -- 5.6 80.6 1/2" 12.7 Al VK178 Adjustable Standard 16458U -- 25 mm -- 80.6 1/2" 12.7 Al 08386U 1" -- 5.6 80.6 1/4" 6.35 B2 VK182 Adjustable Recessed 16454U -- 25 mm -- 80.6 1/4" 6.35 B2 08388U 1" -- 5.6 80.6 1/2" 12.7 A3 VK174 Plain Barrel 16456U -- 25 mm -- 80.6 1/2" 12.7 A3 Approved Finishes and "A" Dimensions 1*- Bright Brass, Chrome,White Polyester,or ENT'with "A"dimensions 1-1/2"to 45-1/2" (38.1 Approved Temperature Ratings mm to 1,156 mm) 5 A 155°F (68 °C), 175°F(79 °C), 200°F (93 °C), and 2*- Bright Brass,Chrome,White Polyester,or ENT with "A"dimensions 3-1/4"to 47-1/2" (82.5 mm to 1,207 mm) 286°F(141 °C) 3 - Brass, Bright Brass, Chrome,White Polyester, or ENT'"A"dimensions 3"to 47" (76.2 mm to B-155°F(68°C), 175°F(79 °C), and 200°F(93°C) 1,194 mm) `Brass Finish is listed and approved but not standard offering,lead times of 6-8 weeks required. (Matching Brass escutcheons are not available.) Footnotes 1 Part number shown is the base part number. For complete part number, refer to current Viking price list schedule. 2 K-Factor applies for standard lengths ("A" Dimensions indicated above). 3 Metric K-factor shown is for use when pressure is measured in bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0. 4 This chart shows the FM Approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional approvals. 5 FM approved as corrosion resistant. :-§ t DESIGN RITERIA- FM (Also refer to Approval Chart 2 above.) NOTE:When using CPVC fittings with Viking dry sprinklers, use only new Nibco Model 5012-S-Bl tees.When selecting other CPVC fittings, contact Viking Technical Services. FM Approval Reauirements: The Dry HSW Sprinklers in the Approval Chart above are FM Approved as quick response Non-storage standard spray sprinklers as indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets(including 2-0)and Technical Advisory Bulletins. FM Global Loss Prevention Data Sheets and Technical Advisory Bulletins contain guidelines relating to, but not limited to:minimum water supply requirements,hydraulic design,ceiling slope and obstructions,minimum and maximum allowable spacing,and deflec- tor distance below the ceiling. NOTE:The FM installation guidelines may differ from cULus and/or NFPA criteria. IMPORTANT:Always refer to Bulletin Form No. F_091699-Care and Handling of Sprinklers.Also refer to page DRY1-3 for general care, installation, and maintenance information.Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data,the appropriate standards of NFPA, FM Global, LPCB,APSAD,VdS or other simi- lar organizations,and also with the provisions of governmental codes, ordinances, and standards,whenever applicable. Form No. F_031993 Rev 15.1 Page 6 of 8 QUICK RESPONSE TECHNICAL DATA DRY HORIZONTAL SIDEWALL SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email:techsvcs@vikingcorp.com For "A" Dimension 1. Determine the distance from the face of the tee to the face of the finished wall, 11111111111111111E 2. Round to the nearest 1/4" (6.35 mm) between 3-1/4' (83 mm) and 47-1/2' (1,207 mm). Ceiling NOTE; The sprinkler will be recessed approximately Wall 5/16" (7.9 mm) with 5/8" (16 mm) horizontal adjustment available, 4" (102 mm) Minimum A 6" (152 mm) Maximum* I ' �° 1 il ( 5/8" (16 mm) 1111 f " =-*4 f 3-1/16 E_I,r��r r (77.8 mm) / I I ii I Minimum wall opening: I 2-1/8" (54 mm) diameter. I I Maximum wall opening: 2-1/2" (63.5 mm) diameter. I _ Available Adjustment 1-23/32" (43.7 mm) Minimum * May be allowed up to 18" (457 mm) for certain 2-11/32" (59.5 mm) Maximum FM installations, Refer to the appropriate installation standards, including NFPA 13 and/or FM Loss 5/16" (7.9 mm) Outward Adjustment Prevention Data Sheet 2-0. 5/16' (7.9 mm) Inward Adjustment Figure 5: Adjustable Recessed Dry Horizontal Sidewall Sprinkler with the Model E-1 Escutcheon Side outlet of Tee turned to ' 011)-" �� req'd angle for ��I Int For 'A' Dimension, slope of ceiling 1' 11,1 1. Measure B Dimension from centerline of the face of the tee to the horizontal centerline Matt, ,'/ of the wall opening. Adjustable-, �� Adapter ,ir ,�� 2. Measure C Dimension from the centerline of Ring the Face of the tee to the finished wall II ( q 3. Calculate 'A' Dimension using, A = '\/B2+ C2 ■■1 NOTE,A Dimension will provide approximately 1/4' of adjustment In either direction. Depth, 1-1/16' (27 mm) 1/ 3.2 rilI Adjustable I(Hs m) ile„......, - ,,, '/—Ceiling Outer Cup ���,,',,,� F 'I /4 Deflector distance , u,H ,, tr_ 74 6' (102 to 152 mm) 266 mm) (102 mm) J� - below the ceiling.* 4' Minimum wall opening When measuring for 2-5/8' (66 mm) diameter. the 'A' Dimension, Maximum wall opening, the exact deflector 3 3/4° (95 mm) diameter, ��Wall distance below the ceiling must be known. C * May be allowed up to 18' (457 mm) 1-t/16' Lfor certain FM installations. Refer to (27 mm) the appropriate installation standards, including NFPA 13 and/or FM Loss Prevention Data Sheet 2-0, Figure 6: Adjustable Recessed Dry Horizontal Sidewall Sprinkler with the Model G-1 Escutcheon Form No. F_031993 Rev 15.1 Page 7 of 8 Niturc QUICK RESPONSE TECHNICAL DATA DRY HORIZONTAL SIDEWALL SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com For "A" Dimension 111111111111111111111: 1. Determine the distance from the face of • -the tee to the base of the sprinkler. Ceiling 2. Round to next highest 1/2" (12.7 mm) increment, between 3" (76.2 mm) and Wall 47" (1,194 mm). 4" (102 mm) Minimum 6" (152 rim) Maximum( A 2-3/16" (51 mm) 5/8" (16 mm) 1111�i111111 xs‘i .I • Outside diameter: 1-5/16" (33.4 mm). (Same as 1" Do not exceed 6" (152 mm). (25 mm) Schedule 40 pipe. Do not recess wrench boss. w May be allowed up to 18" (457 mm) For certain FM installations. Refer to the appropriate installation standards, including NFPA 13 and/or FM Loss Prevention Data Sheet 2-0. Figure 7: Quick Response Plain Barrel Dry Horizontal Sidewall Sprinkler Top View- Dry HSW Sprinkler Side View- Sprinkler Cover 15610 NOTE: Shown with an Adjustable Standard Dry HSW Sprinkler. The protective cover may also be used with the Adjustable Recessed Press the cover together or Plain Barrel style Dry HSW Sprinkler. until it snaps closed. - it ho After the sprinkler is installed, carefully place the cover over J the dry sprinkler as shown. NOTE: Remove the sprinkler clip and cover before placing the system in service! Figure 8: Dry Horizontal Sidewall Sprinkler Cover Part Number 15610(shown with an Adjustable Standard Dry HSW Sprinkler) (Optional for temporary use with Viking Dry HSW Sprinklers until finish work is completed around the sprinkler.) Form No. F_031993 Rev 15.1 Page 8 of 8 QUICK RESPONSE NIKING TECHNICAL DATA DRY HORIZONTAL SIDEWALL SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com 1 (130,2 mm)5-1/8' Seal the clearance space around the sprinkler barrel to avoid Maximum leakage of air into the protected area and consequent formation of condensate around the sprinkler frame, which could inhibit - operation or cause premature operation. Refer to Figuree10. OM i �, If humidity and temperature „I I NOTE: To locate the differential causes condensation liII = Deflector nt > deflector at the on the exposed dry sprinkler lilt = Maximum Distance barrel, consider wrapping the IIII - - _ From Walt maximum distance from exposed barrel with insulation, the wall, with no --`' foam insulating tape, or equivalent, �I ll 13/16' Ceilingadjustment available, IIII (20,6 mm) order the standard Install the 1' NPT threaded iill 4' (102 mm) Minimum dry horizontal side II wall sprinkler 1" end of the dry sidewall sprink- I 6' (152 mm) Maximum* ii:: 1 longer than the 'A' ler into the 1' NPT outlet of iilii _ Sleeve finish dimension. a malleable iron tee fitting per ii„I„ii , I matches ANSI B 16.3 (Class 150) or cast " "' escutcheoniron t6reaCed tee fitting per ,-\��;� m___ ' I_ __ — 3-1/16' Up to 2' (50.8 mm) ANSI 16.4 (Class 125) only. } (77 8 mm) adjustment Is available. \ !I r MI 5/8'J Minimum wall opening: ;;ii L\ (15.9 mm) I 3-1/8' diameter: 1-3/4' (44.5 mm)____ mm)— Maximum wall opening (Exposed ii ii Minimum diameter: 2-1/4' (57 mm), Barrel) " 1-1/2' NOTE: To locate the (38.1 mm) 11 1 deflector at the diameter Exposed Barrel— _ minimum distance from Ambient Ambient Temperature Outer , -. ( the wall, with no Temperature 40'F/4'C50'F/10°C�60'F/16°C Surface - 2 adjustment available, of Protected Exposed Minimum Barrel of the Wall ■ order the standard Areae at the P Ili dryhorizontal side- Discharge End Length■*■ Face of the Tee to the Outer wall sprinkler 1" of the Sprinkler Deflector nt Surface of the Wall Mlnlmum Distance shorter than the In.(mm) In.(mm) In.(mm) From Wall 'A" dimension. 40°F (4'C) 0 0 0 30°F (-1°C) 0 0 0 *May be allowed up to 18" (457 mm) for certain FM 20'F (-7°C) 4 (100) 0 0 installations. Refer to the appropriate installation standards, 10°F (-12'C) 8 (203) 1 (254) 0 including NFPA 13 and/or FM Loss Prevention Data Sheet 2-0. 0°F (-18°C) 12 (305) 3 (76) 0 **The protected area refers to the area below the ceiling, -l0°F (-23°C)14 (356) 4 (102) 1 (25.4) The ambient temperature is the temperature at the discharge end of the sprinkler. -20'F (-29°C)14 (356) 6 (152) 3 (76) For protected area temperatures that occur between the -30°F (-34°C)16 (406)8 (203)4 (102) values listed, use the next cooler temperature. -40°F (-40°C)18 (457)8 (203)4 (102) ***The minimum required barrel length is not the same as the 'A' dimension. -50°F (-46°C)20 (508)10 (254)6 (152) Refer to Figures 3, 5, and 7 for the 'A' dimension. -60'F (-51°C)20 (508)10 (254)6 (152) Exposed minimum barrel lengths are inclusive up to 30 mph wind velocities. Figure 9: Dry Horizontal Sidwall Sprinkler Required Minimum Barrel Length Based on Ambient Temperature in the Protected Area (Adjustable Standard Dry HSW Sprinkler is Shown) Seal (or equivalent ` Seal method) N IL �!� _ i,i,,l IG 1 If .,J il Ili .i s ss Is 7 Clearance Opening Insulated \ Insulated N ' Wall Wall Dry Sprinkler Seal on the Exterior of the Wall Dry Sprinkler Seal Within the Wall Figure 10: Dry Sprinkler Seal(Adjustable Standard Dry HSW Sprinkler is Shown) Form No. F_031993 Rev 15.1 :.r•.+; COSCO .sr� '•"•.F Fire Protection Valves Backflow COSCO Fire Protection Inc. 2501 SE Columbia Way, Suite 100 Vancouver,WA 98661 Phone:360-883-6383 Fax: 360-883-6390 Toll Free: 800-983-6383 I � . heck V. Pvee g l)s ® VdS LPCB SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS SERIES 717—cULus, FM, VdS, LPCB SERIES 717H HIGH PRESSURE—cULus, FM,VdS, LPCB The FireLock Series 717 Check Valve and Series 717H High Pressure Check Valves are CAD- designed for hydrodynamic efficiency and available in 2"/50mm—3"/80mm(Series 717H)and 2t /z"/65 mm 12"/300 mm(Series 717)sizes. *IOW Series 717H valves are cULus Listed and FM Approved for service up to 365 psi/2517 kPa.See chart below for approved services for the Series 717 valves. In both valve designs,the single-disc mechanism incorporates a spring-assisted feature for non- slamming operation.This spring-assisted,single-disc design achieves a leak-free seal with as little as 5ft/1.5m of head.Series 717 and 717H FireLock Check Valves can be installed either Series 717 vertically(flow upwards only)or horizontally.A cast flow arrow indicator is provided to assist with (4—127100—300mm) proper valve orientation. Both valves include upstream and downstream pressure taps. Each ,. valve is factory-tested to the rated working pressure.For systems requiring a Riser Check option, ;,, ". refer to publication 10.09. Grooved ends allow fast,easy installation with just two Victaulic couplings or the valve may be mounted to flanged(ANSI CL.150)equipment using either to Victaulic Style 741 Vic-Flange®or111111 Style 744 FireLock flange adapters on either end. Series 717H High Pressure Check Valve (2—3"/50—80mm) Approval/Listing Service Pressures Series 717H Size cULus FM LPCB Vds 2750 mm up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa 2W/65 mm up to 365psi/2517 kPa up to 365 ps12517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa 76.1 mm up to 365 psi/2517 kPa up to 365 ps12517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa 3780 mm up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa 47100mm n/a n/a n/a n/a 57125 mm rVa n/a n/a n/a 139.7 mm n/a n/a n/a n/a 67150 mm n/a n/a n/a n/a 165.1 mm n/a n/a n/a n/a 87200mm n/a n/a n/a n/a 107250 mm n/a n/a n/a n/a 127300mm n/a n/a n/a n/a Approval/Listing Service Pressures Series 717 Size 2750 mm n/a n/a n/a n/a 21/2765 mm up to 250 ps11725 kPa n/a up to 365 psi/2517 kPa n/a 76.1 mm up to 250 psi/1725 kPa n/a up to 365 psi/2517 kPa up to 16bar/232 psi 3780 mm up to 250 psV1725 kPa n/a up to 365 psi/2517 kPa up to 16bar/232 psi 47100 mm up to 350 psi/2413 kPa up to 350 psi/2413 kPa up to 365 psi/2517 kPa up to 16bar/232 psi 5"/125 mm up to 250 psi/1725 kPa up to 250 psi/1725 kPa up to 365 psi/2517 kPa n/a 139 7 mm up to 250 psi/1725 kPa up to 250 psi/1725 kPa up to 365 psi/2517 kPa up to 16bar/232 psi 67150 mm up to 350 ps 2413 kPa up to 350 psi/2413 kPa up to 365 psi/2517 kPa up to 16bar/232 psi 165.1 mm up to 2SOpsi/1725 kPa up to 250 psi/1725 kPa up to 365 psi/2517kPa n/a 87200 mm up to 350 ps 2413 kPa up to 350 psi/2413 kPa up to 348 psi/2400 kPa up to 16bar/232 psi 107250 mm up to 250 psV1725 kPa up to 250 psi/1725 kPa up to 1725 kPa/250 psi n/a 127300 mm up to 250 psV1725 kPa up to 250 psi/1725 kPa up to 1725 kPa/250 psi n/a JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date Approved Date WWW.VICTAULIC.COM _ IPS CARBON STEEL PIPE- FIRE PROTECTION VALVES 10.08 FireLock® Check Valves SERIES 717-cULus, FM, VdS, LPCB SERIES 717H HIGH PRESSURE-cULus, FM,VdS, LPCB DIMENSIONS-Series 717 Approx. ,_A_,..., r B )1 Size Dimensions-Inches/millimeters Wgt.Ea.Actual Nominal Outside Ill T Size Diameter W Inches Inches E to E mmLbs. M m A B C D E J K P R kg TYPICAL 2'h-3"/65-80 MM 21/2 2.875 3.88 4.26 3.57 _ _ _ _ 3.6 65 73.0 99 108 91 1.6 761 mm 3.000 3.88 4.26 3.57 - - 3.6 el it; c A 76.1 99 108 91 1.6 R 3 3.500 4.25 5.06 4.17 ._i 4.5 80 88.9 108 129 106 - - - 2.0 0 i 4 4.500 9.63 6.00 3.88 2.75 3.50 2.00 4.50 3.50 3.35 20.0 +" 4 100 114.3 245 152 99 70 89 51 14 89 85 91 D E 5 141.3 1030 6.80 _ 417 2.15 5.88 1 4.08 3.98 27.0 k-K > ��"" 125 141.3 267 _ 173 114 106 55 149 ! 104 101 12.3 I B� -)I J 14- 0 139.7 mm 5.500 10.50 6.80 4.50 _ 417 2.15 5.88 4.08 3.98 27.0 Y2"NPT Upstream Drain 139.7 267 173 114 106 55 149 104 101 12.3 12) 'h"NPT Downstream Drain 6 1 6.625 11.50 8.00 5.00 _ 4.50 2.38 6.67 4.73 3.89 38.0 3 2"NPT(Drain Optional) 150 168.3 292 203 127 114 61 169 120 99 17.2 TYPICAL 4-87100-200 MM 165.1 mm 6500 1130 1 8.00 5.00 _ 4.50 2.38 657 4/3 , 3.89 38.0 I 165.1 292 203 127 114 61 L 169 120 I 99 17.2 8 8.625 I 14.00 9.88 6.06 5.05 5.65 215 8.85 5.65 I 5.75 ' 64.0 l A 200 219.1 356 251 154 128 144 55 225 144 1 146 , 29.0 ��' T 1 4 10 10.750 17.00 . 12.00 7.09 5.96 6.69 2.15 10.92 1 6.73 1 _ 100.0 I-.. -' P l� 250 273.0 432 305 180 151 170 55 1 2777 1 171 45.4 Onil -1": D 12 12.750 19.50 14.00 8.06 6.91 I.._ 7.64 j 2.51 12.81 � 7.73 140.0 I I D E 300 323.9 495 356 205 176 194 64 925 196 63.5 LKSI p ' I0 -,-B J14- 0 F01 /2"NPT Upstream Drain ©1/2"NPT Downstream Drain TYPICAL 10-127250-300 MM • DIMENSIONS -Series 717H Approx. Size Dimensions-Inches/millimeters Wgt.Ea. A -B i :' ( )' Lbs. lir �� 1111 y ;AN'',r 2 8.66 646 3.23 148 3.02 2.80 4.25 10.7 IIMIIIIIII y V yir 60 3 219.8 1641 82.1 375 76.7 71.0 - - 108.0 49 73 38 0 76 3 1 84.1 42.2 86 4 85 9 41 3 J 6 8 .3 e- E 76,1 mm 9.37 6.94 3.31 1.66 3.40 3.38 - 4.38 13.8 238.0 176.3 84.1 42.2 86 4 85 9 3 111.3 6.3 TYPICAL 2"/60.3 mm 3"/88.9 mm 3 9.62 744 353 191 3.65 338 l _ 4.63 . 20.0 88.9 j 244.3 189.0 89.7 48.5 92.7 85.9 - - 117.6 9.1 www.victaulic.com - f. __ _. _. iPS CARBON STEEL PIPE- FIRE PROTECTION VALVES 1 0.08 r r,® :` "a lues SERIES 717—cULus, FM, VdS, LPCB SERIES 717H HIGH PRESSURE—cULus, FM,VdS, LPCB MATERIAL SPECIFICATIONS Body: Ductile Iron conforming to ASTM A-536,grade 65-45-12. Ductile iron conforming to ASTM A-395,grade 65-45-15, is available upon special request. Body Coating:Series 717H Body: Black Paint Series 717H Endface: Electroless Nickel Series 717(2' —3"): PPS Coating Series 717(4—12"): Black Paint Body Seat:Series 7171-1—Nitrile 0-ring installed into an electroless nickel plated endface Series 717(21/2—3"): PPS Coated ductile iron Series 717(4—12"):Welded Nickel Disc Seal or Coating: • Grade"T"Nitrile(Series 717H ONLY) Nitrile(Orange color code).Temperature range—20°F to+180°F/-29°C to+82°C. Recommended for petroleum products,air with oil vapors,vegetable and mineral oils within the specified temperature range;except hot,dry air over+140°F/+60°C and water over+150°F/+66°C. NOT RECOMMENDED FOR HOT WATER SERVICES. • Grade"E" EPDM(Series 717 ONLY) EPDM (green color code).Temperature range-30"F to+230"F/-34"C to+110"C. Recommended for cold and hot water service within the specified temperature range plus a variety of dilute acids, oil-free air and many chemical services. NOT RECOMMENDED FOR PETROLUEM SERVICES. * Services listed are General Service Recommendations only. It should be noted that there are services for which these gaskets are not recommended. Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service recommendations and for a listing of services which are not recommended. Discs: • Series 717H (2—3750—80 mm):CF8M Cast Stainless Steel • Series 717(2' —3"):Aluminum bronze with elastomer seal • Series 717(4—127100—300 mm) Elastomer-coated ductile iron Shaft: • Series 717H (2—3"/50-80mm): Brass • Series 717(21—3"):Type 416 Stainless Steel • Series 717(4—127100—300 mm)Type 316 Stainless Steel Spring:All sizes Type 302/403 Stainless Steel Shaft Plug: • Series 717H(2—3750—80 mm):Type 416 Stainless Steel • Series 717(2'/2—12"/65—300 mm):Carbon steel zinc plated Pipe Plug: • Series 717H (2—3750—80mm):carbon steel zinc plated • Series 717(4—127100—300 mm):Carbon steel zinc plated www.victaulic.com IPS CARBON STEEL PIPE- FIRE PROTECTION VALVES 10.08 FireLock® Check Valves SERIES 717—cULus, FM,VdS, LPCB SERIES 717H HIGH PRESSURE—cULus, FM,VdS, LPCB FLOW CHARACTERISTICS The charts below express the flow of water at 60"F/16"C through valve. S717H/717HR 10 ycF � R OJ ye�� A o z 1 N LU CC a 0.1 10 100 1000 FLOW RATE-G.P.M. S717H/717HR 100.00 tn 10.00 ��c� `' �e N N W K a 1.00 100 1000 10000 FLOW RATE(Litres/Min) www.victaulic.com ___■_ IPS CARBON STEEL PIPE- FIRE PROTECTION VALVES 10.08 FireLor ! 'her ' _, !ves SERIES 717—cULus, FM, VdS, LPCB SERIES 717H HIGH PRESSURE—cULus, FM,VdS, LPCB FLOW CHARACTERISTICS The charts below express the flow of water at 60"F/16"C through valve. 5717/717R 10 F� II A F oF F �cF �cF F pF n, �h o c„ p0 0 1 N 4:3.A h <oi Rei ^O A -. W - / OC I N V) OV9AV 0.1 10 100 1000 10000 100000 FLOW RATE-G.P.M. S717/717R 100.00 m a FF F FF FF FF FF of FF N ^� OF Op gyp, �� Op N OO OJ 10.00 ,v _cp 'ti ti ; ry: 9 V) N N W CL CL 1.00 � 10.00 100 1000 10000 100000 FLOW RATE(Litres/Min) www.victaulic.com - _::,, . . - : 0.08 SERIES 717—cULus, FM, VdS, LPCB SERIES 717H HIGH PRESSURE—cULus, FM,VdS, LPCB INSTALLATION Series 717 and Series 717H Check Valves can be installed either vertically(flow up only)or horizontally (with hinge on top)-making sure the flow arrow matches the flow direction through the pipeline. Reference should always be made to the 1-100 Victaulic Field Installation Handbook for the product you are installing.Handbooks are included with each shipment of Victaulic products for complete installation and assembly data,and are available in PDF format on our website at www.victaulic.com. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. • NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. For complete contact information,visit www.victaulic.com MODEL 1011 , ,.;:,v:,i 1,,:,,, in' ,,n'nnn :,:—:,:; •An',47:1 7,..,:,3 ::,.,,i:- ',,, , ....:,.., --- ,,,,„ ' - , , , ,,:.,.&.,,,:: A • TAi N . ..- ,T,- -,,,,,,, ,- ,' :74*''''', -:.'V..5,-. .,* ,:14yf;;I'li. '44i;I:4 '''''',,'' , ,;!7:', ',„: :1" 1. '40}. ° �... r is i 1! i U'M r j ..i i m � . S USA PATENT AND OTHER PATENTS PENDING ❑ The AGF Manufacturing Inc. Model 1011 Matches All The Features And Benefits Of Our Model 1000 by Providing Both The Test Function And The Express Prain Function In A Multistory Installation,With The Added Feature Of An Integral Model 7000 Pressure Relief Valve With Drainage Piping. ❑ Available In A Full Range Of Sizes From 3/4"To 2", NPT & BSPT,With All Specifiable Orifice Sizes 3/8", x/16", 1/2" 17/32",5/8" (ELO), & 3/4" (ESFR). ❑ The Model 1011 Complies With The Requirements Of NFPA 13, 138 & 13D,Which Stipulate A Pressure Relief Valve Be Installed On All Gridded Systems And Downstream Of All Pressure Reducing Valves. ❑ The Model 1011 IsA Single Handle Ball Valve That lsLig htweightAnd Compact,Which Includes A Ta m p er Resistant Test Orifice, Integral Ta m per Resistant Sight G lass, A n d Is 300 PSI Rated. ❑ The Included UL/FM Model 7000 Pressure Relief Valve Features A Flushing Handle And Is Factory Set At 175 PSI, Other Pressure Settings Are Also Available. Li Designed To Relieve Excess System Pressure Caused By Surges OrTe m perature Changes As Well As Solve The Difficult Problem Of Providing The Relief Valve With A Drainage-Piping Outlet. ❑ The Unit Comes Shipped In A Semi-Assembled State With The Relief Valve And The Bypass Drain Ports Plug ged.This Is Done To Ease Pressure Testing The System. butourNew qutoc ('* visit us AO ��� on the Internet J/e G at o, 8/01 www.testandrain.com' MODEL 1011 A � ® MODEL 1011 (UL LISTED/FM APPROVED) BRONZE BALL VALVE MODEL 7000 (UL LISTED/FM APPROVED) PRESSURE RELIEF VALVE , TESTAN DRAIN FACTORY SET AT 175 PSI WITH OTHER SETTINGS AVAILABLE. FRONT VIEW - MODEL 1011 PLAN VIEW INLET A j A ► 100111, 0n11 / ■ DRAIN �1 �- D-- - 'IN _ ; . ,,,, - � - CJ H o• O O *.,1=�1 TO DRAIN ? . p G `; :--=.:--7--. ..IIIIIII0 . 1 Eu From the February 1 , 1999 Edition of NFPA 13: Chapter 4-1.2 Requires ALL GRIDDED SYSTEMS be provided with a relief valves Chapter 5-14.1.2.3 Requires a relief valve be installed downstream of all pressure-reducing valves ORIFICE SIZES AVAILABLE -3/8, 7/16, 1/2, 17/32, ELO(5/8)', ESFR(3/4)' DIMENSIONS- INCHES OVERALL LENGTH 101 1 1011 SIZE A B C D E F G H MATERIAL LIST 3/4" 7 9/16" 1 1/2" 2 3/16" 3 5/8" 3 3/8" 1 13/16" 4 9/n" 6 3/8" 191.30mm 37.58mm 55.65mm 93.23mm 85.88mm 45.30mm 117.12mm 162.42mm PART: MATERIAL: 1 " 7 9/16" 1 1/2" 2 3/16" 3 5/8„ 3 3/8" 1 13/16" 4 9/16" 6 3/8 191.30mm 37.58mm 55.65mm 93.23mm 85.88mm 45.30mm 117.12mm 162.42mm HANDLE STEEL 1/4" 15/ 11/16" 9/ 1/ 5/ 15/ 9/ 1/ STEM ROD BRASS 1 ] 1B 1 2 16" 4 4" 3 16" 1 1fi" 5 16" 5 2" BALL C.P.BRONZE 201mm 42.70mm 65.36mm 108.36mm 82.84mm 50.89mm 141.39mm 192.28mm BODY BRONZE " 5 1 /211 2826168 m6m 1 45 50/16" 3 m m 81.50/m'm 127mm" 99.18mm/ 66.97mm 206.63 m11m 2 33. 7/8" VALVE SEAT.60m m INDICATOR PLATE STEEL REGNATED TEFLON 2" 8 15/16" 1 13/16" 3 1/4" 5 1/15" 3 7/8' 2 5/8" 8 1/4" 10 7/8„ RELIEFVALVE BRONZE 226.68mm 45.50mm 81.50mm 127mm 99.18mm 66.97mm 206.63mm 273.60mm BYPASSTITBINGS BRAS$ BYPASS TUBING NYLOBRAID *Availa ble on 11/4"to 2"size units only. 2"ELO/ESFRIIS UL LISTED&FM APPROVED .; ivELO/ESFRIS UL LISTED x r UL LISTING EX4019(N)&EX4533(N) AGF MANUFACTURING COMPANY JOB NAME: 100 Quaker Lane - ARCHITECT: Malvern,PA 19355 USA Telephone:(610)240-4900 _ ,.-,..--,:s.-.--.- ENGINEER: Fax:(610)240-4906 www.testandrain.com MADE IN U.S.A. CONTRACTOR: 80 Deringer3fl DCDA BDIRECT ACKFLOW Double Check Detector Assembly The Deringer 30 Double Check Detector Assembly prevents non-health hazard pollutants from entering a potable water supply system when backpressure 0 ,! , T .. .. _ and/or backsiphonage conditions occur. Usedii . . primarily on fire sprinkler systems when monitoring of .... .. , . . w. V .. unathorized water use is required. R ' Sizes: 21/2", 3", 4", 6", 8" h . T Working Pressure: 10-175psi(0.7-12.1 bar) I Temperature Range: 33°-140°F(1°-60°C) C �► '* " A End Connections -IPS Groove for Steel Pipe: AWWA C606 HORIZONTAL ` ii* Ts - Flange Adapters: ANSI B16.1 Class 125 For Regulatory Approval Status Visit - , ° Lead Free: 0.25%Maximum by Weight www.backflowdirectapprovals.com - Lead Free Bronze CuFt or Gallons1 DCDA II Single Bypass Componets Bypass Meter Check Bypass Integral Shut-Off Valves Indoor/Outdoor Application Prewired t e Supervisory ., *. * ` Switches 100%Stainless Steel Housing m ,, '' i Silicone Elastomer Dual Ae#ionTe Check Modules '� f" e<.,"� � � � "k � �,""' Check Discs •Poppet Action at Low Flow t, I C. t Fy., •Swing Action at High Flow : # -- ' " IRS Grooved Gx4.> ., - . I Ends Tamper Resistent '' Test Cocks • ' * °—. Flange Adapters Available Engineerr igS, ecificath, The Deringer 30 Double Check Detector Assembly shall utilize two independent Dual Action Check modules and two integral resiliently seated shut-off valves all of which shall be contained within a single rigid valve housing constructed entirely of 304 stainless steel. Both integral shutoff valves shall include pre-wired supervisory tamper switches contained within a weatherproof actuator housing approved for both indoor and outdoor use. Dual Action Check modules shall operate as a"poppet style"check under low flow conditions, operate as a"swing style"check under high flow conditions and utilize replaceable silicone elastomer sealing discs. Assembly test cocks shall be handle-less and operate via a tamper resistant actuator.Assembly shall have a single full access service port and cover with an "inline" replaceable elastomer seal. The bypass assembly shall include a meter registering either gallons or cubic feet, a single check valve and required test cocks. Assembly shall be serviceable without special tools and approved for both horizontal and vertical applications. Job Name: Contractor: Job Location: Approval: Engineer: Contractor's P.O. No: Approval: Representative: Backflow Direct,LIC • 3290 Monier Circle* Rancho Cordova *California •95742 * United States of America Phone: 916-760-4524 Website: www.backflowdirect.cotn . 'lowPerfo , once ' (lptrn) 379 75/ ;i t:9 3 2' 7r?r . 1,-'r, 18 ® ®® ®® 4 10 y. 3 1° 8 55 c0 —raid -.''°'''' _..001.11111.1°" 1111111111=1111111=111.11111111111111111111111111111 °P2- Y0 0 100 200 300 400 500 600 700 800 C. - Rated Flow A - UL Tested 0 - 15 fps) Rate of Flow (gpm) qac{; ental(.,,t-- -' Dccren.cmg Flo, (WOn 1574 "1'=r 1a 6.056 75? 9085 16 - in 7 14 � 8„ 96 a 12 . 83 6"(x) , 69 m 10 - 8 �- 55 r N 4 - L - 28 P- 2 14 a. 0 _ tkP 0 400 800 1200 1600 2000 2400 :peddle ntatIan&agency ti- characteristics avatlable on website Rate of Flow(gpm) Measures S, " S' } i ir . — Sc ti H t :,,, ,- HtWIN : . Ec L W -' Size Ht Hb L Ec D H W Weight Sc in Harrin mm in mm in mm in mm in mm in mm in mm lbs kg NPT �/ _.. ._. n 2 /2 65 7.1 180 2.9 74 18.7 475 2% 65 0.0 0 10.0 254 11.0 279 47 21 W 3 80 7.4 188 2.9 74 18.7 475 3 80 0.0 0 10.3 262 11.0 279 49 22 'A" 4 100 7.9 201 3,1 79 18.7 475 4 100 0.2 5 11,0 279 11.0 279 51 23 1/" 6 150 .7 221 4.8 122 28.4 721 6 150 1.0 25 13.5 343 13.8 351 131 59 "Vi' 8 8 200 10.4 264 5.4 137 30.7 780 8 200 1.8 46 15.8 401 13.8 351 150 68 1A" Valve Housing: 304 Stainless Steel SOV Bearings: Teflon/Bronze Check Springs: 17-7 Stainless Steel Valve Cover: 304 Stainless Steel Non Wetted Bolts: Grade 8 Zinc Plated Check Pins: 17-7/18-8 Stainless Steel SOV Disks: EPDM/304SS Wetted Fasteners: 18-8 Stainless Steel Check Seats: Noryl Polymer(NSF) SOV Shafts: 304 Stainless Steel All Check Disks: Silicone(NSF) 0-Rings: Buna-N(NSF) Bypass Spring: 302 Stainless Steel Bypass Components:Lead Free Bronze Bypass Internals:ABS Polymer(NSF) Backlit-to Direct. LLC' • 3190 Monier Circle• Rancho Cot Elov a•California •95742 • United Slates of America Phone: 916-760-4524 \\ebsite: w Na w.backllow direct.com COSCO Fire Protection Fire Prole(Iion oral I i/t Safety Specialists Supervisory COSCO Fire Protection Inc. 2501 SE Columbia Way, Suite 100 Vancouver,WA 98661 Phone:360-883-6383 Fax: 360-883-6390 Toll Free: 800-983-6383 VSR POTTER VANE TYPE WATERFLOW The Symbol of Protection ALARM SWITCH WITH RETARD UL,CUL and CSFM Listed,FM Approved,LPCBApproved,For CE Marked(EN12259-5)/VdS Approved model use VSR-EU r ` Service Pressure: 450 PSI(31 BAR)-UL _ - Flow Sensitivity Range for Signal: 4-10 GPM(15-38 LPM)-UL Maximum Surge: 18 FPS(5.5 m/s) Contact Ratings: Two sets of SPDT(Form C) 10.0 Amps at 125/250VAC 2.0 Amps at 30VDC Resistive 10 mAmps min.at 24VDC Conduit Entrances: Two knockouts provided for 1/2"conduit. Individual switch compartments suitable for dissimilar voltages. Environmental Specifications: • NEMA 4/IP54 Rated Enclosure suitable for indoor or outdoor use with factory installed gasket and die-cast housing when used with appropriate conduit fitting. • Temperature Range: 40°F-120°F,(4.5°C-49°C)-UL • Non-corrosive sleeve factory installed in saddle. Service Use: Automatic Sprinkler NFPA-13 Specifications subject to change without notice. One or two family dwelling NFPA-13D Ordering Information Residential occupancy up to four stories NFPA-13R Nominal Pipe Size Model Part Number National Fire Alarm Code NFPA-72 2" DN50 VSR-2 1144402 1' , 2 1/2" DN65 VSR-2 1/2 1144425 ROI G 3" DN80 VSR-3 1144403 • Installation must be performed by qualified personnel and in 3 1/2" - VSR-3 1/2 1144435 accordance with all national and local codes and ordinances. • Shock hazard.Disconnect power source before servicing.Serious 4" DN100 VSR-4 1144404 injury or death could result. 5" - VSR-5 1144405 • Risk of explosion.Not for use in hazardous locations.Serious 6" DN150 VSR-6 1144406 injury or death could result. 8" DN200 VSR-8 1144408 Optional: Cover Tamper Switch Kit,stock no.0090148 CAUTION Replaceable Components:Retard/Switch Assembly,stock no. 1029030 Waterflow switches that are monitoring wet pipe sprinkler systems shall not be used as the sole initiating device to discharge AFFF, deluge, or chemical suppression systems. Waterflow switches used for this application may result in unintended discharges caused by surges, trapped air,or short retard times. General Information Enclosure The Model VSR is a vane type waterflow switch for use on wet sprinkler The VSR switches and retard device are enclosed in a general purpose, systems. It is UL Listed and FM Approved for use on steel pipe; die-cast housing. The cover is held in place with two tamper resistant schedules 10 through 40,sizes 2"thru 8" (50 mm thru 200 mm).LPC screws which require a special key for removal. A field installable approved sizes are 2" thru 8" (50 mm thru 200 mm). See Ordering cover tamper switch is available as an option which may be used Information chart. to indicate unauthorized removal of the cover. See bulletin number The VSR may also be used as a sectional waterfiow detector on large 5401103 for installation instructions of this switch. systems.The VSR contains two single pole,double throw,snap action switches and an adjustable,instantly recycling pneumatic retard. The switches are actuated when a flow of 10 GPM(38 LPM)or more occurs downstream of the device. The flow condition must exist for a period of time necessary to overcome the selected retard period. Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 866-956-1211/Canada 888-882-1833 • www.pottersignal.com PRINTED IN USA MFG.#5401146-REV L PAGE 1 OF 4 3/09 VSR P POTTER VANE TYPE WATERFLOW e The Symbol of Protection ALARM SWITCH WITH RETARD Installation (see Fig. 1) These devices may be mounted on horizontal or vertical pipe. On horizontal pipe they shall be installed on the top side of the pipe where they will be accessible. The device should not be installed within 6" (15 cm)of a fitting which changes the direction of the waterflow or within 24" (60 cm)of a valve or drain. NOTE:Do not leave cover off for an extended period of time. Drain the system and drill a hole in the pipe using a hole saw in a slow speed drill (see Fig. 1). Clean the inside pipe of all growth or other material for a distance equal to the pipe diameter on either side of the hole.Roll the vane so that it may be inserted into the hole;do not bend or crease it.Insert the vane so that the arrow on the saddle points in the direction of the waterflow.Take care not to damage the non-corrosive bushing in the saddle.The bushing should fit inside the hole in the pipe. Install the saddle strap and tighten nuts alternately to required torque (see the chart in Fig. 1).The vane must not rub the inside of the pipe or bind in any way. A CAUTION Do not trim the paddle.Failure to follow these instructions may prevent the device from operating and will void the warranty. Fig.1 Retard Adjustment ! DO NOT LEAVE COVER OFF FOR a/ AN EXTENDED PERIOD OF TIME The delay can be adjusted by rotating the retard adjustment knob from �1 ' � 0 to the max setting(60-90 seconds).The time delay should be set at °--->5 ���� !; the minimum required to prevent false alarms �� II \I : \� �1 '��� �� ' TIGHTEN NUTS 1 ,��� f_ I �II1- ALTERNATELY ` oP v_ / CAUTION 44I� ;;>• Hole must be drilled perpendicular to the pipe and vertically centered. Viiiiiii::::4001t, Refer to the Compatible Pipe/Installation Requirements chart for size. Correct Incorrect MOUNT ON PIPE SO I ----p - 0- -(-3--- ARROW ON SADDLE If rniligiffa-471 POINTS IN DIRECTION - -� Y IW00P''' OF WATERFLOW 0 a.M 1a1 ROLL PADDLE IN I� ..,:11I OPPOSITE DIRECTION ADAPTER "\ ADAPTER DIRECTION OF OF WATERFLOW WATERFLOW 11 jte-i p•1 , I V'4110 '4 -*;1\ \ ' 4111j1 (Flowing water activates 20mm±2mm MAX. device in one direction only.) DN50 ONLY ,� USE(2)5180162 ADAPTERS AS SHOWN ABOVE DWG. 1146-It DWGit 1146 IF Compatible Pipe/Installation Requirements Model Nominal Pipe Nominal Pipe Pipe Wall Thickness Hole Size U-Bolt Nuts Size O.D. Schedule 10(UL) Schedule 40(UL) BS-1387(LPC) DN(VDS) Torque inch mm inch mm inch mm inch mm inch mm inch mm inch mm ft-lb n-m VSR-2 2 DN50 2.375 60.3 0.109 2.77 0.154 3.91 0.142 3.6 0.091 2.3 VSR-2 1/2 2.5 - 2.875 73.0 0.120 3.05 0.203 5.16 - - - - 1.25+.125/-.062 33.0+2.0 VSR-2 1/2 - DN65 3.000 76.1 - - - - 0.142 3.6 0.102 2.6 VSR-3 3 DN80 3.500 88.9 0.120 3.05 0.216 5.49 0.157 4.0 0.114 2.9 VSR-3 1/2 3.5 - 4.000 101.6 0.120 3.05 0.226 5.74 - - - - 20 27 VSR-4 4 DN100 4.500 114.3 0.120 3.05 0.237 6.02 0.177 4.5 0.126 3.2 2.00±.125 50.8+2.0 VSR-5 5 - 5.563 141.3 0.134 3.40 0.258 6.55 - - - - VSR-6 6 DN150 6.625 168.3 0.134 3.40 0.280 7.11 0.197 5.0 0.157 4.0 VSR-8 8 DN200 8.625 219.1 0.148 3.76 0.322 8.18 0.248 6.3 0.177 4.5 NOTE:For copper or plastic pipe use Model VSR-CF. PRINTED IN USA MFG.#5401146-REV L PAGE 2 OF 4 3/09 P PJTTERVSR VANE TYPE WATERFLOW ® The Symbol of Protection ALARM SWITCH WITH RETARD Fig.2 Fig.3 Fig.4 Switch Terminal Connections Clamping To remove knockouts:Place screwdriver at Break out thin section of cover when Plate Terminal inside edge of knockouts,not in the center. wiring both switches from one conduit 111 entrance. 4 �� t tif 4140 �I I f00��G �' �.�� .-.-=---_,,, -� 00 mc.gn4e le -1-- _ �:' ! AWARNING. r. ' ` �1 �/ An uninsulated section of a single conductor should not be looped -\\J <r 11 .'1' around the terminal and serve as two separate connections. The g _ \�,,I� �� wire must be severed,thereby providing supervision of the _ connection in the event that the wire become dislodged from under NOTICE ,�//` the terminal. Failure to sever the wire may render the device Do not drill into the base as this creates 1`.� DWG 1146-I, inoperable risking severe property damage and loss of life. metal shavings which can create Do not strip wire beyond 3/8"of length or expose an uninsulated electrical hazards and damage the APO conductor beyond the edge of the terminal block.When using device.Drilling voids the warranty. stranded wire,capture all strands under the clamping plate. Fig.5 Typical Electrical Connections Notes: 11 - ' �. II POWER SOURCEh± SUITABLE FORBELL 1. The Model VSR has two switches,one can be used to operate acentral = iiii ' ',station,proprietary or remote signaling unit,while the other contact = 11.illil ` _ �;`�.., EILn_is used to operate a local audible or visual annunciator. '= iii-II. 1111= ten■ n�11MB �ii�i.; VSR P POTT VANE TYPE WATERFLOW The Symbol of Protection ALARM SWITCH WITH RETARD Maintenance Inspect detectors monthly. If leaks are found, replace the detector. The VSR waterflow switch should provide years of trouble-free service. The retard and switch assembly are easily field replaceable.In the unlikely event that either component does not perform properly,please order replacement retard switch assembly stock#1029030(see Fig.6).There is no maintenance required,only periodic testing and inspection. Retard/Switch Assembly Replacement(See Fig.6) NOTICE The Retard/Switch Assembly is field-replaceable without draining the system or removing the waterflow switch from the pipe 1. Make sure the fire alarm zone or circuit connected to the waterflow switch is bypassed or otherwise taken out of service. 2. Disconnect the power source for local bell(if applicable). 3. Identify and remove all wires from the waterfiow switch. 4. Remove the(2)mounting screws holding retard/switch assembly to the base.Do not remove the(2)retard housing screws. 5. Remove the retard assembly by lifting it straight up over the tripstem. 6. Install the new retard assembly.Make sure the locating pins on the retard/switch assembly fit into the locating pin bosses on the base. 7. Re-install the(2)original mounting screws. 8. Reconnect all wires.Perform a flow test and place the system back in service. Fig.6 REMOVE(2)ORIGINAL MOUNTING SCREWS HOLDING RETARD/SWITCH ASSEMBLY TO BASE BREAKOUTTHIN SECTION OF COVER WHEN WIRING BOTH SWITCHES FROM ONE CONDUIT ENTRANCE. (2)ORIGINAL MOUNTING � CREWS RETARD/SWITCH ASSEMBLY ---.....1.01111111111- er• � Ea.: OII ,- t,r (2)LOCATING PINS I , (2)LOCATING DO NOT REMOVE � \ ��•_%� /�� BOSSES IN BASE (2)RETARD HOUSING `j SCREWS � ::ill� BAS 44"r14110/4111°'-- Sala DWG#1146-10 Removal of Waterfow Switch • To prevent accidental water damage,all control valves should be shut tight and the system completely drained before waterflow detectors are removed or replaced. • Turn off electrical power to the detector,then disconnect wiring. • Loosen nuts and remove U-bolts. • Gently lift the saddle far enough to get your fingers under it. With your fingers,roll the vane so it will fit through the hole while continuing to lift the waterfiow detector saddle. • Lift detector clear of pipe. PRINTED IN USA MFG.#5401146-REV L PAGE 4 OF 4 3/09 • QL ' data sheet A R G C 0 GUARANTEED Fire Sprinkler Pressure Gauges 125 is iTS2� 0-300 psi water 100 75 141�5 r;=` y 0-300 psi air so 50 zs 775 0-300 psi air/water 30[ \11101440.0}29•, ,_. • GE* Application: Fluid medium which does not clog connection port or corrode copper alloy. - " Specifically designed for the fire sprinkler industry. Size: 4"(100 mm) Accuracy ±3/2/3%of span- 11/2"(ASME B40.1 Grade B) Working Range Steady:3/4 of full scale value Fluctuating:2/3 of full scale value Short time:full scale value Approvals Operating Temperature UL listed (UL-393) Ambient:-40°F to 140°F(-40°C to 60°C) FM approved Media: max. 140°F(+60°C) Temperature Error Standard Scale Additional error when temperature changes from reference temperature of 68°F PSI (20°C)+0.4%for every 18°F(10°C)rising or falling. Percentage of span. Window Standard Features Acrylic, ultrasonically welded to case Connection Material:copper alloy Standard Series •Type 110.10sp Lower mount(LM)-not available for 11/2"size 1/4" NPT limited to wrench flat area Bourdon Tube: Material:copper alloy C-type Order Options Movement: Copper alloy, silicone dampened water Dia:White plastic with stop pin-black&red lettering air/water Pointer: Black aluminum air Case: Black polycarbonate The information contained herein is produced in good faith and is believed to be reliable but is for guidance only.ARGCO and its agents cannot assume liability or responsibility for results obtained in the use of its product by persons whose methods are outside or beyond our control. It is the user's responsibility to determine the suitability of any of the products, methods of use,or preparation prior to use, mentioned in our literature. It is the user's responsibility to observe and adapt such precautions as may be advisable for the protection of personnel and property in the handling and use of any of our products. FOR MORE INFORMATION CALL ARGCO AT 1-800-854-1015 OR LOG ONTO WWW.ARGCO.COM An s s Electrical w; ja s€ Bells - Electric UL Approved. Features four wire, 120 and 24 volt red enamel heavy steel gong. Indoor and outdoor installation. c Yir, 4 Part No. Description Box Qty Box Case Case Weight Qty Weight ELAB12006 6" 120 V 1 3.3# 20 68# ELAB12010 10" 120 V 1 4.4# 10 47# ELAB2406 6" 24 V 1 3.3# 20 68# ELAB2410 10" 24 V 1 4.4# 10 47# Back Boxes Weatherproof. For use in attaching electric bells to walls. Part No. Description Case Case Qty Weight ELBBB BELL BACK BOX w/GASKET AND SCREWS 50 33# www.breccocorp.com Email: sales@breccocorp.com PAGE: EL-1 :::::::: COSCO :••••. Fire Protection Vire i'roaeci o;i ,. La .`,afelt' Specialists Calculations COSCO Fire Protection Inc. 2501 SE Columbia Way, Suite 100 Vancouver,WA 98661 Phone:360-883-6383 Fax: 360-883-6390 Toll Free: 800-983-6383 W YAT T FIRE PROTECTION, INC. 9095 S.W. Burnham Tigard, OR 97223 Fire Hydrant Fire Flow PROJECT Durham & Hall Flow ADDRESS SW Durham & Hall near CWS treatment plant CROSS STREET FLOW HYDRANT North end of Hall LOCATION STATIC 98 PITOT RESIDUAL 22 GPM 1764 GPM AT 20 PSI 3494 4" pitot flowed calculated per NFPA 291 DATED 06.07.18 MONITOR HYDRANT South end of Hall & Durham LOCATION STATIC 98 RESIDUAL 76 DATED 06.07.18 WITNESS WITNESSED BY TITLE ORGANIZATION City of Tigard Public Works SIGNATURE PERFORMED BY Mike Sayti r Hydraulic Summary IlJob Number:24PD5199-Clean Water services ' f 7. - Report Description:Light Hazard(1) Job Job Number Design Engineer 24PD5199 Tim Carpenter Job Name: State Codification/Lieensa Number Clean Water Services 67508 Address I AHJ 16060 SW 85th Ave. City of Tigard Address 2 Job Sib/Building Tigard,OR 97223 Address 3 Drawing Name ' Clean Water-FP-1-Building F Piping Plan.cad System Remote Area(s) Most Demanding Sprinkler Data Occupancy Job Suffix 5.6 K-Factor 14.82 at 7.000 Light Hazard Clean Water services Hose Allowance At Source Density Area of Application 100.00 0.10gpm/ft2 1500ft2(Actual 1158ft2) Additional Hose Supplies Number Of Sprinklers Calculated Coverage Per Speeder Node Flow(gpml 14 145f2 ,444e(1,,,,,,g4,0: .., / /7 ir."<(/\'\ P 17 77506 PE 6-28-2018 OREGON Total Hose Streams 9 O� 100.00 "F ti 10 ti0(Pte, System Flow Demand Total Water Required(Including Hose Allowance) r,pY 0 s�" 232.68 332.68L Maximum Pressure Unbalance In Loops o.000 EXPIRATION DATE:12/31/18 Maximum Velocity Above Ground 20.43 between nodes 9 and 10 Maximum Velocity Under Ground 5.34 between nodes 4 and 5 Volume capacity of Wet Pipes Volume capacity of Dry Pipes 399.82ga1 Supplies Hose Flow Static Residual Flow Available Total Demand Required Safety Margin Node Name (gpm) (psi) (psi) °@ (gpm) 1 (psi) @ (gpm) (psi) (psi) 1 Water Supply 100.00 98.000 76.000 1764.00 96.995 332.68 52.103 44.892 Contractor Contractor Number Contact Name Contact True 24PC0190 Tim Carpenter Design/PM Name of Contractor. Phone Extension Cosco Fire Protection 360-883-6383 Address I FAX 2501 SE Columbia Way#100 360-883-6390 Address 2 Heil Vancouver,WA 98661 tcarpenter@coscofire.com — Address Web-Site www.coscofire.com [M©M.E.P.CAD,Inc. r; ,AutoSPRINK 2018 v14.0.3.0 6/9/2018 3:47:12PM Page 1 Hy t raulic Graph,' Job Number:24PD5199-Clean Water services Report Description:Light Hazard(1) Water Supply at Node 1 100 -Static Pressure 98.000 90 80 1764.00 @ 76.000 70 60 'a =- 232.681@ 52.103 50 332.68 with hose streams w _ a` 40 30 -System demand curve 20 10 0 -H- I 1w11u1 111111111 111111111 111111111 1 1 1 1 1 1 1 1 1 11 i i 1 1 i i 1 X 1 1 1 1 1 1 1 1 I I I I I I I I I I I I I t I I I I 350 700 1050 1400 1750 2100 2450 2800 3150 3500 Water flow,gpm Hydraulic Graph Water Supply at Node 1 Static.Pressure 98.000 Residual:Pressure 76.000 @ 1764.00 Available Pressure at Time of Test 96.995 @ 332.68 System Demand 52.103 @ 232.68 System Demand(Including Hose Allowance at Source) 52.103 @ 332.68 ik,©M.E.P.CAD,Inc. AutoSPRINK 2018 v14.0.3.0 6/9/2018 3:47:14PM Page 2 illSummary Of Outflowing Devices ` Job Number:24PD5199-Clean Water services Report Description:Light Hazard(1) Actual Flow Minimum Flow K-Factor Pressure Device (gpm) (gpm) (K) (psi) Sprinkler 100 20.77 14.47 5.6 13.750 Sprinkler 101 20.46 14.47 5.6 13.344 Sprinkler 102 17.79 14.47 5.6 10.093 Sprinkler 103 16.46 14.47 5.6 8.634 Sprinkler 104 15.72 14.47 5.6 7.878 Sprinkler 105 17.23 14.47 5.6 9.468 Sprinkler 106 15.43 14.47 5.6 7.593 Sprinkler 107 15.20 14.47 5.6 7.369 Sprinkler 108 17.09 14.47 5.6 9.308 Sprinkler 109 15.79 14.47 5.6 7.949 Sprinkler 110 14.95 14.47 5.6 7.127 Sprinkler 111 15.07 14.47 5.6 7.241 Sprinkler 112 14.82 14.47 5.6 7.000 Sprinkler 206 15.93 14.47 5.6 8.088 ca Most Demanding Sprinkler Data ({,©M.E.P.CAD,Inc. di AutoSPRINK 2018 v14.0.3.0 6/9/2018 3:47:15PM Page 3 mi, Node Analysis 1 Job Number:24PD5199-Clean Water services % Report Description:Light Hazard(1) Node Elevation(Foot) Fittings Pressure(psi) Discharge(gpm) 1 -5'-0 S 52.103 232.68 _ 100 15-4% Spr(-13.750) 13.750 20.77 101 15'-7'/z Spr(-13.344) 13.344 20.46 102 15'-1'/z Spr(-10.093) 10.093 17.79 103 15'-4'/z Spr(-8.634) 8.634 16.46 104 15'-7% Spr(-7.878) 7.878 15.72 105 15'-1'/z Spr(-9.468) 9.468 17.23 106 15'-10'% Spr(-7.593) 7.593 15.43 107 15-7% Spr(-7.369) 7.369 15.20 108 15'-1'% Spr(-9.308) 9.308 17.09 109 15-4'/z Spr(-7.949) 7.949 15.79 110 15-10 Spr(-7.127) 7.127 14.95 111 15-7% Spr(-7.241) 7.241 15.07 112 15'-10 Spr(-7.000) 7.000 14.82 206 15'-4'% Spr(-8.088) 8.088 15.93 2 -5'-0 E(30'-6%) 52.068 3 -5-0 E(22'-1) 52.044 4 -5-0 E(16'-8%) 51.825 5 -5-0 50.707 6 1'-1'/z 47.772 7 15'-3 P0(7.-5) 9.684 8 14'-0% P0(7.-5) 12.139 9 2'-11 40.132 10 14'-0% PO(T-5) 16.454 11 15'-3 P0(7.-5) 10.327 12 14'-0% P0(7'-5) 12.900 13 15-3 P0(7.-5) 9.520 14 14'-0'% P0(7'-5) 11.944 k{,©M.E.P.CAD,Inc. ,i6 AutoSPRINK 2018 v14.0.3.0 6/9/2018 3:47:16PM Page 4 11Hydraulic Analysis 7 Job Number:24PD5199-Clean Water services Report Description:Light Hazard(1) Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq.Length Summary Upstream Total Length w Route 1 BL 1.4420 14.82 2.91 120 0.015862 9'-11/2 Pf 0.145 112 15'-10 14.82 5.6 7.000 Sprinkler Pe 0.096 111 15'-7'% 7.241 9.-1% Pv BL 1.4420 29.88 5.87 120 0.058087 10'-4 Pf 0.600 111 15'-7'% 15.07 5.6 7.241 Sprinkler Pe 0.108 109 15'-41/2 7.949 10'-4 Pv BL 1.4420 45.67 8.97 120 0.127314 4'-6Yz Pf 1.524 109 16-4% 15.79 5.6 7.949 Sprinkler, 7'-5 Pe 0.048 13 15'-3 9.520 P0(7.-5) 11-11'/2 Pv BL 1.4420 62.76 12.33 120 0.229188 0'-10'/2 Pf 1.900 13 15'-3 17.09 9.520 Flow(q)from Route 4 7'-5 Pe 0.523 14 14'-0'/2 11.944 P0(7'-5) 8'-3% Pv CM 2.1570 62.76 5.51 120 0.032248 6'-0'% Pf 0.195 14 14'-0'% 11.944 Pe 8 14'-0'% 12.139 6'-0'/z Pv CM 2.1570 126.07 11.07 120 0.117198 6'-6 Pf 0.762 8 14'-0% 63.31 12.139 Flow(q)from Route 2 Pe 12 14'-0'% 12.900 6-6 Pv CM 2.1570 191.46 16.81 120 0.253898 14'-0 Pf 3.553 12 14'-0'% 65.39 12.900 Flow(q)from Route 3 Pe 10 14'-0'% 16.454 14'-0 Pv CM 2.1570 232.68 20.43 120 0.364184 39'-5'% Pf 18.848 10 14'-0% 41.22 16.454 Flow(q)from Route 7 12'-31/2 Pe 4.830 9 2'-11 40.132 2fE(6'-2),f(-0.000) 51'-9 Pv DY 2.4690 232.68 15.59 120 0.188622 0'-0 Pf 6.863 9 2'-11 40.132 Pe 0.777 6 1-1% 47.772 BFP(-6.863) 0'-0 Pv UG 4.2600 232.68 5.24 150 0.008763 12'-0 Pf 0.279 6 1'-1'% 47.772 19'-10'% Pe 2.655 5 -5'-0 50.707 E(19'-10%) 31-101/2 Pv UG 4.2200 232.68 5.34 140 0.010424 77'-2 Pf 1.118 5 -5'-0 50.707 30'-1'% Pe 4 -5'-0 51.825 2EE(6'-8%),E(16'-8%) 107'-3% Pv UG 6.2800 232.68 2.41 140 0.001504 75'-0 Pf 0.219 4 -5'-0 51.825 70'-11 Pe 3 -5'-0 52.044 GV(4'-8%),3E(22'-1) 145'-11 Pv UG 8.3900 232.68 1.35 140 0.000367 35'-0 Pf 0.024 3 5'-0 52.044 30'-6'% Pe 2 -5'-0 52.068 E(30'-6%) 65'-6'% Pv UG 6.2800 232.68 2.41 140 0.001504 23'-0 Pf 0.035 2 -5'-0 52.068 Pe 1 -5'-0 52.103 Water Supply 23'-0 Pv 100.00 Hose Allowance At Source 1 332.68 el Route 2 BL 1.4420 14.95 2.94 120 0.016127 9'-1% Pf 0.147 110 15'-10 14.95 5.6 7.127 Sprinkler Pe 0.096 107 15'-7'% 7.369 9'-1'% Pv BL 1.4420 30.15 5.92 120 0.059050 10'-4 Pf 0.610 107 15'-7'% 15.20 5.6 7.369 Sprinkler Pe 0.108 206 15'-4'% 8.088 10'-4 Pv BL 1.4420 46.08 9.05 120 0.129406 4'-6%2 Pf 1.549 206 15'-4% 15.93 5.6 8.088 Sprinkler, 7'-5 Pe 0.048 7 15'-3 9.684 PO(T-5) 11-11% Pv BL 1.4420 63.31 12.44 120 0.232917 0'-101/2 Pf 1.931 7 15'-3 17.23 9.684 Flow(q)from Route 5 7'-5 Pe 0.523 8 14'-0'% 12.139 PO(T-5) 8'-3'% Pv QII Route 3 BL 1.4420 15.43 3.03 120 0.017100 10'-4 Pf 0.177 106 15'-10'% 15.43 5.6 7.593 Sprinkler Pe 0.108 104 15'-7'% 7.878 10'-4 Pv BL 1.4420 31.15 6.12 120 0.062712 10'-4 Pf 0.648 104 15'-7% 15.72 5.6 7.878 Sprinkler Pe 0.108 103 15'-4'% 8.634 10'-4 Pv k,©M.E.P.CAD,Inc. ilk AutoSPRINK 2018 v14.0.3.0 6/9/2018 3:47:18PM Page 5 111 Hydraulic Analysis II Job Number 24PD5199-Clean Water services Report Description:Light Hazard(1) Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq.Length Summary Upstream Total Length BL 1.4420 47.60 9.35 120 0.137446 4'-6'/ Pf 1.645 103 15'-4'/ 16.46 5.6 8.634 Sprinkler, 7'-5 Pe 0.048 11 15'-3 10.327 P0(7-5) 11'-11'/2 Pv BL 1.4420 65.39 12.85 120 0.247314 0'-101.4 Pf 2.050 11 15'-3 17.79 10.327 Flow(q)from Route 6 7'-5 Pe 0.523 12 14'-0'% 12.900 P0(7-5) 8'-3% Pv Q Route 4 BL 1.4420 17.09 3.36 120 0.020646 5'-9'% Pf 0.273 108 15'-1'% 17.09 5.6 9.308 Sprinkler, 7-5 Pe -0.061 13 15'-3 9.520 PO(7-5) 13'-3 Pv Q Route 5 BL 1.4420 17.23 3.39 120 0.020973 5'-9'% Pf 0.278 I 105 15'-1% 17.23 5.6 9.468 Sprinkler, 7'-5 Pe -0.061 7 15'-3 9.684 PO(7-5) 13'-3 Pv Q Route 6 BL 1.4420 17.79 3.50 120 0.022252 5'-9'% Pf 0.294 102 15'-1% 17.79 5.6 10.093 Sprinkler, 7-5 Pe -0.061 11 15'-3 10.327 P0(7-5) 13'-3 Pv Q Route 7 BL 1.4420 20.46 4.02 120 0.028808 10'-4 Pf 0.298 101 15'-7% 20.46 5.6 13.344 Sprinkler Pe 0.108 100 15'-4'% 13.750 10'-4 Pv BL 1.4420 41.22 8.10 120 0.105309 5'-4'% Pf 2.133 100 15'-4'% 20.77 5.6 13.750 Sprinkler, 14'-10'% Pe 0.571 10 14'-0'% 16.454 2P0(7'-5) 20'-3 Pv Equivalent Pipe Lengths of Valves and Fittings(C=120 only) d = Value Multiplier Actual Inside Diameter 4.87 Value Of C 100 130 140 150 Schedule 40 Steel Pipe Inside Diameter =Factor MultiplyingFactor ( P ) 0.713 1.16 1.33 1.51 &©M.E.P.CAD,Inc. lifi AutoSPRINK 2018 v14.0.3.0 6/9/2018 3:47:18PM Page 6 lig_HYdraulic Analysis Job Number:24PD5199-Clean Water services Report Description:Light Hazard(1) Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq.Length Summary Upstream Total Length Pipe Type Legend Units Legend Fittings Legend AO Arm-Over Diameter Inch ALV Alarm Valve BL Branch Line Elevation Foot AngV Angle Valve CM Cross MainFlow gpm b Bushing DN Drain BaIV Ball Valve DR Drop Discharge gpm BFP Backflow Preventer DY Dynamic Velocity fps BV Butterfly Valve FM Feed Main Pressure psi C Cross Flow Turn 90° FR Feed Riser Length Foot cplg Coupling MS Miscellaneous Friction Loss psi/Foot Cr Cross Run OR Outrigger HWC Hazen-Williams Constant CV Check Valve RN Riser Nipple Pt Total pressure at a point in a pipe DeIV Deluge Valve SP Sprig DPV Dry Pipe Valve ST Stand Pipe Pn Normal pressure at a point in a pipe E 90°Elbow UG Underground Pf Pressure loss due to friction between points EE 45°Elbow Pe Pressure due to elevation difference between indicated Eel 11W Elbow points Ee2 22W Elbow Pv Velocity pressure at a point in a pipe f Flow Device fd Flex Drop FDC Fire Department Connection fE 90°FireLock(TM)Elbow fEE 45°FireLock(TM)Elbow flg Flange FN Floating Node fT FireLock(TM)Tee g Gauge GIoV Globe Valve GV Gate Valve Ho Hose Hose Hose HV Hose Valve Hyd Hydrant LtE Long Turn Elbow mecT Mechanical Tee Noz Nozzle P1 Pump In P2 Pump Out PIV Post Indicating Valve PO Pipe Outlet PRV Pressure Reducing Valve PrV Pressure Relief Valve red Reducer/Adapter S Supply sCV Swing Check Valve Spr Sprinkler St Strainer T Tee Flow Turn 90° Tr Tee Run U Union WirF Wirsbo WMV Water Meter Valve Z Cap ©M.E.P.CAD,Inc. g AutoSPRINK 2018 v14.0.3.0 6/9/2018 3:47:18PM Page 7 MUMS Design Maps Summary Report User-Specified Input Report Title Clean Water Services Fri May 25, 2018 18:25:27 UTC Building Code Reference Document ASCE 7-10 Standard (which utilizes USGS hazard data available in 2008) Site Coordinates 45.44789°N, 122.76916°W Site Soil Classification Site Class D - "Stiff Soil" Risk Category I/II/III ortland1 Beaverton _1J = . � °"_ - .' Tigar�Ui 1 , IC ;Lake,psivego ' t ppgg iI II AV Tut x - USGS-Provided Output 0.981 Ss = Cpof0.51 SS = 0.981 g SMS = 1.087 g SEs = 0.724 g Per NFPA 13, 2013 Table 9.3.5.9.3 Sl = 0.425 g SMI = 0.670 g SEI = 0.446 g _ For information on how the SS and S1 values above have been calculated from probabilistic (risk-targeted) and deterministic ground motions in the direction of maximum horizontal response, please return to the application and select the"2009 NEI-IRP"building code reference document. AMCiK Response Spectrum Design Response Spectrum 01 I.Itr ,....... _ 000 0.72 0.&4 0.36 I Sc VJ 040 r 132 u 33 ci.31 __ ule. 11 ODE 15.170 000 01:0 o.3) o.i0 nfn 7'I) 1.00 LA") 140 IX+1 134. 201 n10 0:23 0.40 014) 0E0 1.AX 1.35 1.40 1 184 2D0 Period,T Vie! Period,T(seri For PGAM,TL, CRS, and CR1 values, please view the detailed report. Although this information is a product of the U.S. Geological Survey,we provide no warranty,expressed or implied,as to the accuracy of the data contained therein.This tool is not a substitute for technical subject-matter knowledge. TOLBraceTM Seismic Calculations Cosco Fire Protection Project Address: Clean Water Services- F Building -AT.1 111 2501 SE Columbia Way#100 Vancouver,WA 98661 16060 SW 85th Ave. 360-883-6383 RnMarrngamsimbl+an4Jvnrfe Tigard, OR 97223 Job#PD 5199 Calculations based on 2013 NFPA Pamphlet#13 Brace Information TOLCOTM Brace Components Maximum Spacing 2'0"(0.61 m) TOLCOTM Component Fig. Number Adjusted Load Maximum Brace Length 7 0" (2.13 m) Fig. 1001 Clamp 1425 lbs(646 kg) Bracing Material 1"Sch.40 Fig.980 Universal Swivel 1425 lbs(646 kg) Angle from Vertical 45° Min. *Calculation Based on CONCENTRIC Loading *Please Note:These calculations are for TOLCOTM components only.Use of any other components voids these calculations and the listing of the assembly. Least Rad.of Gyration 0.42"(11 mm) Assembly Detail L/R Value 200 TOLCO FIG. 980 Max Horizontal Load 1310 lbs (594 kg) UNIVERSAL SWAY BRACE ATTACHMENT Force Factor(Cp) 0.51 STEEL PIPE OA" 4" Fastener Information Fastener Orientation , NFPAType E • �, f ,, f , . Maximum Load 400 lbs(181 kg) d _ e / •• Diameter 1/2in. " TOLCO FIG. 1001 Length 4-1/2in. FAST CLAMP 44 • Type Lag-Screw Brace Identification on Plans #101 Lateral Orientation of Brace Lateral Size and Type of Pipe ' ! LTotai Length Total Calculated Load 2"Sch.10 Steel Pipe(50.8 mm) /� ':moi.• pQ�G O� 2ft(0.6 m) 4 lbs(2 kg) 2"Sch.10 Steel Pipe(50.8 mm) y 928.5ft(8.7 m) 61 lbs(28 kg) 11.25"Sch.10 Steel Pipe(31.75 mm) 7750G PC 6-28-2018 98.5ft(30 m) 127 lbs(58 kg) OREGON co Y L p EXPIRATION DATE:12/31/18 1 Percentage added for Fittings and Sprinklers 15% 29 lbs(13.16 kg) Total Adjusted Load of all pipe within Zone of Influence 221 lbs(100 kg) {TOLBraceTM Version 8) Use of TOLBrace"4 is subject to terms and conditions per the end user license agreement TOLBraceTM Seismic Calculations Clean Water Services- F Building Job#PD 5199 16060 SW 85th Ave. Es Fbwvnn3 8nsiness dwuk Brace Identification #101 Lateral Brace Type(Per NFPA#13) NFPA Type E Braced Pipe 2" Sch.10 Steel Pipe Spacing of Brace 2'0" (0.61 m) Orientation of Brace Lateral Bracing Material 1" Sch.40 Maximum Brace Length 7'0" (2.13 m) Slenderness Ratio used for Load Calculation 200 True Angle of Brace for Calculation 45° Type of Fastener 1/2in.x 4-1/2in. Lag-Screw Length of Fastener 4-1/2in. Summary of Pipe within Zone of Influence 2"Sch.10 Steel Pipe(50.8 mm) 2ft(0.6 m) 2"Sch.10 Steel Pipe(50.8 mm) 28.5ft(8.7 m) 1.25"Sch.10 Steel Pipe(31.75 mm) 98.5ft(30 m) G-Factor Used 0.51 Allowance for Heads and Fittings 15% Conclusions Total Adjusted Load of Pipe in Zone of Influence 221 lbs(100 kg) Material Capacity 1310 lbs(594 kg) Fastener Capacity 400 lbs(181 kg) Fig. 1001 Clamp 1425 lbs(646 kg) Fig.980 Universal Swivel 1425 lbs(646 kg) Structural Member Attach to Roof Glu-Lam Beam Calculations prepared by Tim Carpenter *The description of the Structural Member is for informational purposes only. TOLBrace''software calculates the brace assembly only,not the structure it is attached to. Calculated with TOLBrace'"8 Visit us at www.tolco.com TOLBraceTM Seismic Calculations Cosco Fire Protection Project Address: Clean Water Services-F Building 2501 SE Columbia Way#100 Vancouver,WA 98661 F1 16060 SW 85th Ave. 360-883-6383 PawvringEneirnsstMarldorzic Tigard, OR 97223 Job#PD 5199 Calculations based on 2013 NFPA Pamphlet#13 Brace Information TOLCOTM Brace Components Maximum Spacing 2'0"(0.61 m) TOLCOTM Component Fig. Number Adjusted Load Maximum Brace Length 7'0"(2.13 m) Fig.4LA Clamp 707 lbs(321 kg) Bracing Material 1"Sch.40 Fig.980 Universal Swivel 1425 lbs(646 kg) 45° Min. `Calculation Based on CONCENTRIC Loading Angle from Vertical *Please Note:These calculations are for TOLCOTM'components only. Use of any other components voids these calculations and the listing of the assembly. Least Rad.of Gyration 0.42"(11 mm) Assembly Detail L/R Value 200 Max Horizontal Load 1310 lbs(594 kg) _. "Tni SALSwAY-_--_ 4 t:.. Force Factor(Cp) 0.51 .pAMATTACMIEM ;4�gj Fastener Information '"c",:-`.41%1A, MACE AT1ApHMEN Fastener Orientation NFPA Type E 8 Maximum Load 400 lbs(181 kg) ___ g) 'i t 4.# % © Diameter 1/2in. " PO 4tA Length 4-1/2in. " ts' `".n- Type Lag-Screw Brace Identification on Plans #201 Longitudinal Orientation of Brace Longitudinal i Size and Type of Pipe !� L. = Total Length Total Calculated Load 2"Sch.10 Steel Pipe(50.8 mm) ,b� l 2ft(0.6 m) 4 lbs(2 kg) 77506 PE j 2"Sch.10 Steel Pipe(50.8 mm) 6-28-2018 28.5ft(8.7 m) 61 lbs(28 kg) OREGON v co EXPIRATION DATE:12/31/18 Percentage added for Fittings and Sprinklers 15% 10 lbs(4.54 kg) Total Adjusted Load of all pipe within Zone of Influence 75 lbs(34 kg) (TOLBrace"""Version 81 Use of TOLBraceM is subject to terms and conditions per the end user license agreement { TOLBraceT" Seismic Calculations Clean Water Services- F Building Job#PD 5199 16060 SW 85th Ave. �, oN Dov vr3n7 Bas messWc4dw ds Brace Identification #201 Longitudinal Brace Type(Per NFPA#13) NFPA Type E Braced Pipe 2" Sch.10 Steel Pipe Spacing of Brace 2'0" (0.61 m) Orientation of Brace Longitudinal Bracing Material 1"Sch.40 Maximum Brace Length 7'0" (2.13 m) Slenderness Ratio used for Load Calculation 200 True Angle of Brace for Calculation 45° Type of Fastener 1/2in.x 4-1/2in. Lag-Screw Length of Fastener 4-1/2in. Summary of Pipe within Zone of Influence 2"Sch.10 Steel Pipe(50.8 mm) 2ft(0.6 m) 2"Sch.10 Steel Pipe(50.8 mm) 28.5ft(8.7 m) G-Factor Used 0.51 Allowance for Heads and Fittings 15% Conclusions Total Adjusted Load of Pipe in Zone of Influence 75 lbs(34 kg) Material Capacity 1310 lbs(594 kg) Fastener Capacity 400 lbs(181 kg) Fig.4LA Clamp 707 lbs(321 kg) Fig.980 Universal Swivel 1425 lbs (646 kg) Structural Member Attach to Roof Glu-Lam Beam Calculations prepared by Tim Carpenter *The description of the Structural Member is for informational purposes only. TOLBrace''software calculates the brace assembly only,not the structure it is attached to. Calculated with TOLBrace'8 Visit us at www.tolco.com