Report (99) DIGREENHECK Ct u(x,, S�,> ()0, 1(._ #L\cc:_), Printed Date: 8/28/2013
Job: Arjae 8-28-13
Building Value in Air. Mark: EF-1
CCjVr
—15.625— --14.875--
_ Model: SP-B150 �� AUG 4 2016
4.5 13.25 ri Ceiling Exhaust Fan B�,//�D� 71(
NG Dt
I Standard Construction Features:
r: 1(1)--- .
--I- 1 -Corrosion resistant galvanized steel scroll and housing-White designer non-
yellowing grille-Round outlet duct collar with integral backdraft damper-Single
inlet forward curved wheel-Plug type disconnect-Adjustable mounting brackets
Options &Accessories:
UL/cUL 507 Listed-Electric Fan
06 - 11.5— Designer Grille
13.875Round Duct Connection
—1 - 1.25 Polypropylene Wheel Material
MOUNTING I
BRACKET =-_-, _
1
Dimensional
Quantity 1
Weight w/o Acc's(Ib) 10
Weight w/Acc's(Ib) 10
Performance "
Requested Volume(CFM) 100 �._
0.9 `,,
Actual Volume(CFM) 149
External SP(in.wg) 0.25 c
Total SP(in.wg) 0.552 c
Fan RPM 1050 2 0.6 e 1
Watts(W) 150
Amps(A) 1.7
Elevation(ft) 203
Airstream Temp.(F) 70 tei
m
k .a' t
Air Density(ft3) 0.074
Q°<' Syster . * ' , `
Motor
Motor Mounted Yes 0 20 40 60 80 100 120 140 160
Watts(W) 150 Volume(CFM)
V/C/P 115/60/1 Operating Bhp point
Q Operating point at Total SP
Enclosure ODP Operating point at External SP
NEC FLA*(Amps) NA " Fan curve
_ _ _System curve
_ __a-- Brake horsepower curve
Notes: i
CIMCAll dimensions shown are in units of in.. c mo ;i"
'FLA is approximate and will vary slightly with the motor. '%
LwA-A weighted sound power level,based on ANSI S1.4 1 .,,,
Sound Power by Octave Band dBA-A weighed sound pressure level,based on 11.5 dB f/
attenuation per Octave band at 5.0 ft @€a. s°./
j Soundd Sones-calculated using AMCA 301 at 5.0 ft ' '`'% rt�1o.1
Data 62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones AMCA certified ratings seal applies to sone ratings only.
Inlet 55 62 56 57 57 50 44 39 60 45 3.6
I �eS
CAPS 4.12.1236 G:\Job Data Files\Michael M\Arjae 8-28-13.gfcj Page 2 of 5
OGREENHECK Printed Date: 8/28/2013
Job: Arjae 8-28-13
Building Value in Air. Mark: EF-1
Round Duct Connector
Model: RDC
Standard Construction Features:
-Constructed of Polypropylene - Replaces the square discharge duct connector and damper using the
existing mounting holes
,-,,, Semi Mos=
,�.0, Screw holes
1,.
,...40 11. j
ire Ar, ' :0:
( )
•
ytt
i.00„0"000/00000lts .
:1S111:111711111e1170: 6
11111t0„\..,...,. ,,,",00"."' AO'
41101111fr'
d
k
Notes:All dimensions shown are in units of in.
CAPS 4.12.1236 G:\Job Data Files\Michael M\Arjae 8-28-13.gfcj Page 3 of 5