Report (106) 5T Med Ht
Project: -Untitled175 &Qp1GGtM 04/11/2018
Prepared By: 10:04AM
Mca \ -
\\q4r'RECEIVED
5T Med Ht MAY 2018
CITY OF TIGARD
Tag Cover Sheet BUILDING DIVISION
Unit Report
Certified Drawing
Performance Report
Unit Feature Sheet
Packaged Rooftop Builder 1.49f Page 1 of 9
Unit Report For 5T Med Ht
Project: —Untitled175 04/11/2018
Prepared By: 10:04AM
Unit Parameters Dimensions (ft. in.) &Weight(lb.)""
Unit Model' 48KCEA06A2A5-0A0A0 Unit Length' 6' 2.375"
Unit Size' 06 (5 Tons) Unit Width- 3' 10.75"
Volts-Phase-Hertz- 208-3-60 Unit Height 3' 5.375"
Heating Type. Gas ••• Total Operating Weight 616 lb
Duct Cfg- Vertical Supply/Vertical Return
Medium Heat Weights and Dimensions are approximate. Weight does
Single Stage Compressor Models not include unit packaging. Approximate dimensions are
provided primarily for shipping purposes.For exact
dimensions and weights,refer to appropriate product
data catalog.
Lines and Filters
Return Air Filter Type. Throwaway
Return Air Filter Quantity. 4
Return Air Filter Size- 16 x 16 x 2
Unit Configuration
Medium Static Option Belt Drive
Al/Cu-Al/Cu
Base Electromechanical Controls
Standard Packaging
Warranty Information
1-Year parts(std.)
5-Year compressor parts(std.)
10-Year heat exchanger-Aluminized(std.)
No optional warranties were selected.
NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.
Ordering Information
Part Number Description Quantity
48KCEA06A2A5-0A0A0 Rooftop Unit 1
Base Unit
Medium Static Option Belt Drive
None
Packaged Rooftop Builder 1.49f Page 2 of 9
Certified Drawing for 5T Med Ht
Project: -Untitled175 04/11/2018
Prepared By: 10:04AM
NOTES: UNITED P.O.005 INOA THIS DOCWFXT IS THE PROPERTY OF CARRIER CORPORATION
1. DIMENSIONS ARE IN INCHES, DIMENSIONS aiik TECHNOLOGIES SYRACUSE.NT AND ES DELI YEAED UHE THE DISCLOSEDSEU CONDITION TNAT THE SOOESSNETXCONSTI NTE PART OF THESE XPERFORMANCEEOR
IN [ I ARE IN MILLIMETERS. UNIT J K (1 PHASE) K (3 PHASE) CARRIER uzn CONTENTS
pp ORATION 3 NOT BE
CONST. USED WITHOUT CARRIER ACCEPTANCE OF CONTRACT.
48KC 04 33 3/8 14 7/8 14 7/8
2. CENTER OF GRAVITY 1847] [377] [3771 CONNECTION SIZES
48KC 05 33 3/8 14 1/8 18 5/8
3. 01118.DIRECTION OF AIR FLOW [8411 [3771 [4721 A 1 3/8" [351 DIA FIELD POWER SUPPLY HOLE
48KC 06 41 3/8 14 7/8 18 5/8 B 2' [50) DIG POWER SUPPLY KNOCKOUT
[1051] [377] [472]
C 1 3/4" [511 DIA GAUGE ACCESS PLUG
D 7/8' [22] DIA FIELD CONTROL WIRING HOLE
33-3/8
18487 E 3/4"-14 NPT CONDENSATE DRAIN
F 1/2"-14 NPT GAS CONNECTION
•
+ G 2 1/2 ' [64]DIA POWER SUPPLY KNOCK-OUT
32-1/4 i ECONOMIZER HOOD
[818] (OPTIONAL) 16
[406]
FILTER ACCESS PANEL
•
(TOOL-LESS) COMP. THRU-THE-BASE CHART
• ACCESS CONDENSER ` THESE HOLES REQUIRED FOR USE
'PANEL I COIL � NIA . X . • CRBTMPWROD1A01, 003A01
5~ THREADED WIRE REO'D HOLE
R COIL
•
ACCINDESS PANEL I ,a "
W CONDUITISIZE USE ACC. 7/B°[22A 21
_ w _� _ ^ ^- 25-5/8 10-7/8 X 172" 2/V 7/8" [22.2]
RETURN AIR [2177 RETURN Y . 3/4' 1001,003) POWER 1 1/8" [28.41
�[�I����-����jy� qq •I11�P+\111,11` /JJAIR ISO (003) 1/2"FPT GAS 1 3/16" [30.0]
[1117] \\\ �����// r �� I 1
\ %//// 11 FOR"THRU-TAE-BASEPAN' FACTORY OPTION,
BACK ANDLE 161/8 .. FITTINGS FOR ONLY 0,1, 1 Z ARE PROVIDED
TYP '�� E ALT. N SELECT EITHER 3/4"OR 1/2'
CURB I ` 'W CONDENSATE - 17-3/4 •
Af FOR POWER, DEPENDING ON WIRE SIZE
WIDTH 'X DRAIN OPENING [4517
Y IN BASEPAN 29-3/8 10011 PROVIDES 3/4'FPT THRU CURB
SUPPLY 26-1/2 FLANGE A FITTING.
145918 2 AIR [6137 [747] AIAPLY
16-118 14-1/4 12-114 _ •.• , + -
[111] [363] [312] i SEE THRU THE . 6-i/4
+ ! BASE CHART �JJy,4 [1511 y '•-
lr E ��3-3/8
12-1/8 [B5]
25 LUE • [3071
[636] 4 HOOD 18-1/2 --
f K [100] TOP 14701
d-s/8 10-1/2
[1181 [265] 1-1/4
[32]
• ELECTRICAL 0 }
= j DISCONNECT � I
LOCATION [-ill
CONDENSER -- CONTROLBO% INDOOR BLOWER E STD.COIL = I -- ACCESSPANELACCESS CONDENSATE ILTER
DRAIN
I OPTIONALC =_ _ - I [6381II OUTSIDE
FACTORY 16-3/4 RETURN
�- 19-1/2 OPTIONAL- [427] AIR
INSTALLED I-- FACTORY = r 11-3/8 I AIR
CONVENIENCE [494] (( F HANDLE SUPPLY AIR p''
OUTLET , INSTALLED [289] •
DISCONNECT + Y 21-1/4
L Ii it 6-5/8 .-_- s _ 0-L [5391
8:.= "€ 1.:� (1681 00 I I �1: : 00 sive
nss] _ I
3-3/4 HANDLE' -8-3/8 -�
[951 46-3/4 -. 30-1/8 [213] [169]] [177] 6
[1181] [764] [152]
74-3/8 26-7/8
[1888] [6821 BAROMETRIC
31-1/4 RELIEF
LEFT [7931 FLOW
FRONT SUPPLY
AIR At
RETURN
RIGHT
SHEET DATE SUPEACEDFS 48KC 04-06 SINGLE ZONE ELECTRICAL REV
IOF2 09-16-14 , - COOLING WITH GAS HEAT 48KC 000281
Packaged Rooftop Builder 1.49f Page 3 of 9
Certified Drawing for 5T Med Ht
Project: -Untitled175 04/11/2018
Prepared By: 10:04AM
UNITED P.O.DOR 4000 IRIS DOCUMENT IS THE PROPERTY OP CARRIER CORPORATION SUMMON OF THESE DRAWINGS OR DOCUMENTS
�6X[y
TECHNOLOGIES SIRACtl51 NI AND IS OEI10(010 OP01 THE EIMESS CONDI1101 IXA0 THE DOES NOT COf 10100 PART PERPORMANCE OR
STD. UNIT CORNER CORNER CORNER CORNER AR/ CARRIER 11221 CONTEXTS NIEE NOI RE 00051001.pl USEO NlinplT dIR[ER ACCEPTANCE Of C0Nna1.
UNIT WEIGHT WEIGHT(AI WEIGHT(81 WEIGHT ICI WEIGHT IDI
C.G. HEIGHT (00150ATI01111 OtITTENCONSENT.
LBS. KG. LBS. KG. LBS. KG. LBS. KG. LEIS. KG. X I 2
48KC 04 490 222 120 54 111 50 125 56 135 61 35 3/4[9081 24 3/4[6281 18 7/8[4191
48KC 05 544 246 130 58 126 57 142 64 146 66 36 3/4[9331 24 3/4[6281 18 7/8[4791
48KC 06 597 270 141 64 156 10 158 11 142 64 39 1/8[9931 23 1/2[5971 20 1/8[5111
N STANDARD UNIT WEIGHT IS WITH LOW GAS HEAT AND WITHOUT PACKAGING.
FOR OTHER OPTIONS AND ACCESSORIES, REFER TO THE PRODUCT DATA CATALOG.
CORNER A CORNER B
1 -- - -••••R
-
0
T I .Iii, ll�� I .
,
9
CORNER D - - CORNER C
X
TOP
I• .. •
111111
2
1H.:
I---I
ij 00 •=i l• •I: : 00
FRONT
SHEET DATE SUPERCEOES 48KC 04-06 SINGLE ZONE ELECTRICAL REV
2OF 2 09-16-14 - COOLING WITH GAS HEAT 48KC000281 _
Packaged Rooftop Builder 1.49f Page 4 of 9
•
.r
Certified Drawing for 5T Med Ht
Project: -Untitled175 04/11/2018
Prepared By: 10:04AM
Service Clearance
C
� - D411
-V
� fd�
CH337
LOCATION DIMENSION CONDITION
43-in(1219 mm) •Unit disconnect is mounted on panel
A 18-in(457 mm) •No disconnect,convenience outlet option
•Recommended service clearance
12-in(305 mm) •Minimum clearance
42-in(1067 mm) -Surface behind servicer is grounded(e.g.,metal,masonry wall)
B 36-in(914 mm) -Surface behind servicer is electrically non-conductive(e.g.,wood,fiberglass)
Special •Check for sources of flue products within 10-ft.of unit fresh air intake hood'.
36-in(914 mm) •Side condensate drain is used
18-in(457 mm) •Minimum clearance
48-10(1219 mm) •No flue discharge accessory installed,surface's combustible material
42-in(1067 mm) •Surface behind servicer is grounded(e.g.,metal,masonry wall,another unit)
D 36-in(914 mm) •Surface behind servicer is electrically non-conductive(e.g.,wood,fiberglass)
Special •Check for adjacent units or building fresh air Intakes within 10-ft.of this unit's
flue outlet
NOTE:Unit not designed to have overhead obstruction.Contact Application Engineering for guidance on any
application planning overhead obstruction or vertical clearances.
Packaged Rooftop Builder 1.49f Page 5 of 9
Performance Summary For 5T Med Ht
Project: --Untitled175 04/11/2018
Prepared By: 10:04AM
Part Number:48KCEAO6A2A5-0A0A0
ARI SEER. 14.10
Base Unit Dimensions
Unit Length. 74.4 in
Unit Width 46.8 in
Unit Height. 41.4 in
Operating Weight
Base Unit Weight. 597 lb
Medium Heat. 9 lb
Medium Static Option Belt Drive. 10 lb
Total Operating Weight. 616 lb
Unit
Unit Voltage-Phase-Hertz. 208-3-60
Air Discharge. Vertical
Fan Drive Type. Belt
Actual Airflow 2000 CFM
Site Altitude. 0 ft
Cooling Performance
Condenser Entering Air DB. 95.0 F
Evaporator Entering Air DB- 80.0 F
Evaporator Entering Air WB- 67.0 F
Entering Air Enthalpy 31.44 BTU/lb
Evaporator Leaving Air DB. 58.6 F
Evaporator Leaving Air WB. 57.3 F
Evaporator Leaving Air Enthalpy 24.57 BTU/lb
Gross Cooling Capacity 61.84 MBH
Gross Sensible Capacity 46.23 MBH
Compressor Power Input. 5.19 kW
Coil Bypass Factor 0.058
Heating Performance
Heating Airflow 2000 CFM
Entering Air Temp- 70.0 F
Leaving Air Temp. 113.1 F
Gas Heating Input Capacity 115.0 MBH
Gas Heating Output Capacity 0.0/93.0 MBH
Temperature Rise. 43.1 F
Thermal Efficiency(%)• 81.0
Supply Fan
External Static Pressure. 0.75 in wg
Fan RPM- 1303
Fan Power 1.34 BHP
NOTE. Selected IFM RPM Range: 1035-1466
Electrical Data
Voltage Range- 187 -253
Compressor#1 RLA. 15.9
Compressor#1 LRA 110
Outdoor Fan Motor Qty 1
Outdoor Fan FLA(ea). 1.4
Indoor Fan Motor Type. MED
Indoor Fan Motor FLA- 8.4
Combustion Fan Motor FLA(ea). 0.48
Power Supply MCA- 30
Packaged Rooftop Builder 1.49f Page 6 of 9
t
Performance Summary For 5T Med Ht
Project: -Untitled175 04/11/2018
Prepared By: 10:04AM
Power Supply MOCP(Fuse or HACR). 45
Disconnect Size FLA. 30
Disconnect Size LRA. 185
Electrical Convenience Outlet None
UNIT(s)INSTALLATION LOCATION
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage
Acoustics
Sound Power Levels, db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz 88.1 87.6 87.5
125 Hz 83.2 80.2 82.5
250 Hz 76.3 67.4 76.1
500 Hz 71.9 64.5 73.6
1000 Hz 68.5 63.8 71.3
2000 Hz 62.9 57.9 67.1
4000 Hz 64.7 53.8 64.1
8000 Hz 60.4 46.6 60.0
A-Weighted 75.3 69.8 77.0
Advanced Acoustics
4,1
kik
144
1
Advanced Accoustics Parameters
1. Unit height above ground 30.0 ft
2. Horizontal distance from unit to receiver 50.0 ft
3. Receiver height above ground- 5.7 ft
4. Height of obstruction 0.0 ft
5. Horizontal distance from obstruction to receiver 0.0 ft
6. Horizontal distance from unit to obstruction 0.0 ft
Detailed Acoustics Information
Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall
A 87.5 82.5 76.1 73.6 71.3 67.1 64.1 60.0 89.2 Lw
B 61.3 66.4 67.5 70.4 71.3 68.3 65.1 58.9 76.7 LwA
C 55.1 50.1 43.7 41.2 38.9 34.7 31.7 27.6 56.8 Lp
D 28.9 34.0 35.1 38.0 38.9 35.9 32.7 26.5 44.3 LpA
Legend
Packaged Rooftop Builder 1.49f Page 7 of 9
t
Performance Summary For 5T Med Ht
Project: —Untitled175 04/11/2018
Prepared By: 10:04AM
A Sound Power Levels at Unit's Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA
C Sound Pressure Levels at Specific Distance from Unit, Lp
D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA
Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI
Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed
that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical
estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be
appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate
an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an
Acoustical Engineer or a person with sound prediction expertise should be consulted.
FanCurve
20 \ .- _— 1500RPNI 1700RPM �`,
1900RPM
t 21I'
18
N
16 ,
1�
614 .ssBHP-
12
N - v
= 900RPM
cod
(n 700RPM \
vv 2.00B' �\
500RPM 1.50BHP<
— ''
0.756HP 1 00BHP '
— illiii41161116.- \ \
co 03 CE CE 12 15 18 21 24 27 3) 33
Airflcw(CFM-thousands)
RPM=1303 BHP=1.34 MaximumRPM=2100 MaximumBHP=2.90
Note:Please contact applicationengineering for selections outsidethe shaded region.
SC-SystemCurve RP-RatedPoint
Packaged Rooftop Builder 1.49f Page 8 of 9
Unit Feature Sheet for 5T Med Ht
Project: -Untitled175 04/11/2018
Prepared By: 10:04AM
(i." Carrier )
WeatherMakee — 48KC
PACKAGED ROOFTOP GAS HEATING/ELECTRIC COOLING UNITS-14 SEER
345 TONS
STANDARD FEATURES INCLUDE:
L411k4 •PLIP311(R-410A)HFC refrigerant
.A.--"--111 4:att •Meets and exceeds AS HRAE 90,1 energy efficiency levels
TlIATT2.! I iiriii • Scroll compressors with internal line bfeak and ove;Toad protectioiiriwtwitigjiuiin
L ,
• Single-stage cooling capacity control
•SEERS up to 14.0,EERS up to 12.0
' '.'.,•••• •Acutrol-"refrigerant metering system
- A 'FL-Z-4 • Exclusive non-corrosive composite condensate pan in accordance With
AS I-IRAE Standard 52,sloping design,side Dice nterchmln
• Standard cooling operation up to 115=F(4C C)a nd down to 40 F(4=C)
- down to 25 F(-4 C)with winter start lot
• Pre-panted ext.eriorpartels and primer-coated interior pa nets tested to
500 haws salt spray protection
• Fully insulated cabinet
• Exclusive IGC solid-state co ntrol for on-board diagnostics with LED
error code designation burnercontnal logic and energy saving indoor
fan motor delay
•Lowf*Ox models that meet California AlirCuatity Management m-onInduced draftgas heat combustion design
cord5 Radii ndant gas vaives with LI p to two stages of heating
• Low pressure and high pressure switch protected.
MAINTENANCE FEATURES:
•Access panels with easy grip handles
• Innovative easy starting,no-strip screws on unit access panels
•Two-inch disposable return airfilters and Taal-less filter access door
WEATHERMAKER SERIES • Direct Drrve—ECM indoormotor is standard with optional belt drive
systems
WeatherMak Cr 4ake (14-SEER) units are one-piece gas •Tel. lel board facilitating simple safety circuit troubleshooting and
heating. electric cooling units that are pre-wired and charged simplified control box arrangement
with Puron(R-410)refrigerant. They are factory tested in both • Exclusive IGC solid-state control for on-board diagnostics with LED
heating and cooling modes,and rated in accordance virith AHRI error code desgnation,burnercontrot logic and energy saving indoor
Standards 210/240. WeatherMaker units are designed in fan motor delay.
accordance with UL Standard 1995. and listed by the
INSTALLATION FEATURES:
Underwriters'Laboratories.
•Thru-the-bottorn power entry cape b ddy
• Single point gas and electric connections
• Full perimeter base rad with built-rn rigging adapters and fork slots
Approved and certified by: • Fetd convertible from vertical to hen=ntal airflow
STANDARD WARRANTY:
AVENamiifiEL
• 10-yea r heat exchanger—15-yearsta less steel option
•
5-yearcompressor
mad mix... • 1-year parts
c
Patin4US.
• Many optional upgrades aiso available
row.fve V00.0.1.
V10111:04,11..MO**
ogf,does, ka. OPTIONS INCLUDE BUT ARE NOT LIMITED TO:
• P re mie rUnir and RTU Open Multi Protocol DDC Controls
• Supply and Return Air Smoke Detectors,high static motois
• Louvered condenser me guards
• Disconnect switch and convenience outlet options
Stainless• Steel heat exchange-Topton
• Corrosion resistant coil coating.
Certified to ISO 9001 • High static rrotor options
• Patented Hunech-tbZee adaptive dehumidiftoation system.This option
also includes Motormaster I controls
• I-tinged access panels
• Integrated economise rsystend Standard and Ultra Low Leak versions
For a complete list of options and accessories referto the Product Data
Catalog forth*unit
Packaged Rooftop Builder 1.49f Page 9 of 9