Report (87) \-,=,5--A- -,--7,RE .. , NRC F RE CONSULTING NO V 21 dx, Ili 204:16 .4 7511 Greenwood Avenue C1 q , Seattle,WA 98103 �t Phone: 206.789.0165 IIa �� ��� z www.nrofireconsulting.com 4 0 FIRE ALARM SUBMITTAL • B FIT PACIFIC CORPORATE CENTER TENANT IMPROVEMENT 15575 SW SEQUOIA PARKWAY TIGARD, OR NRG Project Number NRG 16-082 NRG Project Manager Sean Pisoni, ET NRG Project Engineer Will Chappell,SET Submittal Version Date Issued for Permit 11.17.2016 s F, w �� py it:oa . ., p. � - Table of Contents NOG FhE CONSULTING BILL OF MATERIALS & COMPONENT SPECIFICATIONS 2 3 4 4 - ^r: / ® ® - : - © & / . : , \ /% ± z » . ' z \ 6 ) eft \\ 4 d\" \ ( / ° 0 \' \ / \ / � / %1\ \ �> �. , � � � \ $ 6�<« > m« �> < »r« e «� 7 � BILL OF MATERIALS FIRE ALARM SUBMITTAL B FIT PACIFIC CORPORATE CENTER TENANT IMPROVEMENT 15575 SW SEQUOIA PARKWAY TIGARD,OR Panel Components Item Model# Part# Quantity Color Mfg Description 1 SK-5700 1 Red Silent Knight Single Loop Addressable Fire Alarm Control System 2 SK-5860R 1 Red Silent Knight Remote Annunciator 3 SK-5495 1 Red Silent Knight Fire Alarm Booster Power Supply,6 Amp 4 SS000690 1 Red Space Age System Record Document Cabinet 5 SK-PHOTO 1 White Silent Knight Intelligent Photoelectric Smoke Sensor 6 SK-DUCT 4* White Silent Knight Intelligent Air Duct Smoke Detector 7 SK-RTS151KEY 4* Silent Knight Remote Test Station with Key Lock 8 SK-PULL-SA 1 Red Silent Knight Intelligent Pull Station-Single Action 9 SK-MONITOR 2 White Silent Knight Intelligent Monitor Module 10 SK-MONITOR-2 1 White Silent Knight Intelligent Dual Monitor Module 11 SK-RELAY 6* White Silent Knight Intelligent Relay Module 12 P2W 6 White System Sensor Multi-Candela Horn/Strobe-Wall Mount 13 SW 10 White System Sensor Multi-Candela Strobe-Wall Mount 14 PC2W 16 White System Sensor Multi-Candela Horn/Strobe-Ceiling Mount 15 SCW 1 White System Sensor Multi-Candela Strobe-Ceiling Mount 16 P2WK 1 White System Sensor Multi-Candela Horn/Strobe,Wall Mount,NEMA-4 17 12V-7AH WKAl2-7.5F2 4 Black Batteries Plus 7 Amp Hour Battery,12VDC* • * Verify Duct Smoke Detector,Remote Test Switch&Addressable Relay requirements and quantities with Mechanical Contractor z R �, ,%r� ori * e y .` r a �` i I a ., ; %. SILENT 5860 Remote Annunciator KNIGHT by Honeywell Bring the power to control an IntelliKnight fire alarm control panel to every • area within your facility. Now you can operate and program your IntelliKnight system from up to eight locations throughout your facility. The 5860 remote annunciator provides the same advanced, easy-to-use interface found on the IntelliKnight panel's built-in annunciator. The 80-character display and ergonomically designed keypad allow for simple and error-free system operation.All operations—including reset, silence, detector status checking, fire drill, and programming—are identical. Access to the system is through a firefighter's key or an access code. For security, a special installation code is needed for programming functions. The 5860 connects to the IntelliKnight panel via the RS-485 system bus. Wire runs can be up to 6000 feet from the panel. For more information about the IntelliKnight system, or to locate your nearest source, please call 1-800-328-0103. Description multiple 5860s Features include an 80-character • RS-485 interface to panel ,-r , backlit LCD providing easy-to- . • Operation and appearance is understand system messages. The identical to 5860 built-in ;l% le',.,, ,� annunciator is ergonomically annunciator . designed with over-sized buttons • On-board piezo sounder audibly ' ,° , for the most frequently used indicates alarms, troubles, and supervisories z � 4 ' . features, like Reset and Silence. � tin In addition to status messages • Five status LEDs for alarm, -: ° In la ed on the LCD, there are supervisory, trouble, silence and Ft displayed AC power conditions q five LEDs for alarm, supervisory, • Wiring lengths up to 6000 ft. from y„ trouble, silence, and AC power the FACP (depending on wire 5860 status. gauge and number of devices on SBUS) Environmental The annunciator is available in gray - UL listed, complies with NFPA 72 Operating Temperature: 32°F– to match virtually any decor and 120°F (0°C–49°C) red for applications where the • CSFM approved Humidity: 10%–93% non- annunciator must stand out. The Electrical Specifications condensing annunciator enclosure can be Operating Voltage: 24 VDC surface or flush mounted.A trim Standby Current: 20 mA max Compatibility ring kit is available for surface Alarm Current: 25 mA The 5860 is compatible is the mounting. following FACP's: Features Wiring Distance: 6,000 max. from • IntelliKnight 5820XL FACP FACP (depending on wire gauge IntelliKnight 5808 FACP • 80-character backlit LCD display and number of devices on the g (4 lines with 20 characters on SBUS) • IntelliKnight 5700 FACP each line) • Tactile and audible feedback Max Per System: 8 Approvals/Listings NFPA 72; UL Listed; - • Accepts user codes or fire Mechanical Specifications CSFM 7170-0559: 135; fighter's key Physical 9.1" W x 7.4" H x 1.5" D • Larger keypad buttons for system (23.1 W x 18.8 H x 3.8 D cm) MEA 429-92-E Vol. IX; reset and silence FM Approved • Install up to eight 5860s per Shipping Weight: 2.8 lbs (1.3 kg) FACP Color • Available in red or light gray 5860R: Red 5860: Gray • Support for simultaneous use of Model 5495 Distributed Power Module Model 5495 Block Diagram Signal Circuit Output Signal 1 Signal 1 Input Distributed Signal 2 Signal Circuit Output Signal 2 Power Input Module 5495 Signal 3 (Optional) Signal 4 120 VAC Aux. Power 1 Trouble Output Local Fire Control (Alternative to notification circuit trouble.) Supervision Current: Input The 5495 supervises a variety of Standby 75 mA voltage range: 9 - 32 VDC ' functions including: Alarm 205 mA Battery charging • Low AC power Auxiliary capacity: 35.0 AH , • Low battery condition power circuit: 1 Ambient temp.: 32° to 120° F • Earth ground fault Notification (0° to 49° C) • Auxiliary output power limit circuits: 4 Mechanical condition Output Dimensions: 12.25" W x 16" H x • EOL supervision trouble or configuration: 2 Class A(Style Z) 3" D (30.88 cm W power limited condition at an 4 Class B (Style Y) x 40.64 cm H x output (1 Class A& 7.62 D cm) When a trouble condition occurs, 2 Class B) Indicator Lights the 5495 creates a trouble condition on the host control signal Amps per AC power on : Green circuits to which it is connected. the output circuit: 3.0 (6.0 amps total) Battery trouble: Yellow 5495 still maintains the ability to be Notification Ground fault: Yellow activated by the host control. In circuit output: 20.4 to 27.3 VDC addition, the 5495 provides a Form @ 3.0 amps each, Aux trouble: Yellow C trouble relay output as an 4.7 Id1 EOL Output troubles (1-4): Yellow alternative to using the notification resistor required Ordering Information circuit trouble. on each Class B 5495 Distributed Power Module circuit Electrical Specification AC input: 120 VAC at 2 amps No. of inputs 2 Input Output: 24 VDC at 6 amps configuration: 2 Class B or 2 • Class A . SILENT This document is not intended to be used for installation purposes.We try to MADE IN AMERICA yi KNIGHT keep our product information up-to-date and accurate.We cannot cover all specific applications or anticipate all requirements.All specifications are FORM#350395 Rev D subject to change without notice. For more information, contact Silent Knight ©2010 Honeywell International Inc. by Honeywell 12 Clintonville Road, Northford,CT 06472-7161 Phone: (800)328-0103, Fax: (203)484-7118.www.silentknight.com INTELLIKNIGHT ACCESSOR SILENT SK -Photo, SK-Photo-T KNIGHT and • SK-PhotoR by Honeywell Intelligent Photoelectric Smoke Sensors The SK-Photo is a photoelectric smoke detector, the SK-Photo-T is a photoelectric smoke detector with thermal and SK-PhotoR is a photoelectric detector with remote test capability. These plug in smoke detectors, with integral communication, provide features that surpass conventional detectors and are for use with Silent Knight IntelliKnight Fire Alarm Control Panels (FACPs). For more information about the IntelliKnight system, or to locate your nearest source, please call 800-328-0103. Description • Optional remote LED annunciator (System Sensor®PN RA100Z) ��i SK Photo and SK-Photo-T are plug-in Plug-in mounting provides ease ofd f type smoke sensors that combine a installation y; photoelectric sensing chamber with • Tamer- roof feature available on addressable analog communications. p p mountingbases Point ID capability allows each detector's address to be set with rotary • Listed for use in duct applications address switches, providing exact • Rotary address switches for fast detector locations for selective installation maintenance when chamber • UL Listed A, contamination reaches unacceptable • FM Approved levels. % e r�r Specifications SK-Photo and SK-Photo-T have a unique optical sensing chamber that is Physical 6 engineered to sense smoke produced Height: 2.0"(5.0 cm) SK-Photo (Base included) by a wide range of combustion Diameter: 4.1"(10.4 cm) installed in sources. In the SK-Photo-T, dual B501 base electronic thermistors add 135°F (57°C) Installation thermal technology to maximize Electrical detection. Operating Voltage: 15-32 VDC The SK-Photo and SK-Photo-T plug Standby Current: into a compatible IntelliKnight-series The SK-PhotoR is a remote test detector base. The SK-PhotoR is a capable detector for use with the 300 pA @ 24 VDC Maximum remote test capable detector head DNR/DNRW duct smoke detector. (not Alarm Current:6.5 mA @ 24 VDC max included within the DNR (W)duct included) (with LED on) smoke detector. Environmental Operating Temperature Compatibility Features SK-Photo: 32°— 120°F ° ° 0C—49C (0°C 49°C) SK-Photo, and SK-Photo-T are • Sleek, low-profile design SK-Photo-T: 32°— 100°F (0°C—38°C) compatible with the following detector • Base included Humidity: 10%—93% non-condensing bases: Other Ratings B210LP 6" base (included) • Reliable analog communications forB501 2 wire base trouble-free operation SK-Photo-T Thermal: Fixed B224RB Relay base • Age resistant polymer housing temperature set point 135°F (57°C) B224B1 Isolator base • Dual electronic thermistor design on Velocity: 0—4000 fpm (0—20 m/sec) B200SR Sounder base the SK-Photo-T The SK-Photo, SK-Photo-T, and SK- - • Superior EMI resistance for reliability PhotoR are compatible with the • Simple field cleaning for code following IntelliKnight FACPs: compliance 5820XL • Variety of mounting options to meet 5820XL-EVS any application 5808 5700 • Dual LED indicators for 360°visibility 5600 (Rev 2.0 or higher) • Detector transmits signal to indicate maintenance is required Model SK-Photo, SK-Photo-T and SK-PhotoR Intelligent Photoelectric Smoke Sensors Engineering Specifications The contractor shall furnish and install where indicated on the plans, Intelligent photoelectric smoke sensors - Silent Knight SK-Photo or SK-Photo-T with thermal. The combination detector head, and twist-lock base, shall be UL listed and compatible with Silent Knight's IntelliKnight fire control panels. The base shall permit direct interchange with SK-Photo or SK-Photo-T. Base shall be the appropriate twist-lock base part number B210LP (included). The PhotoR is a remote test capable detector for use with DNR(W) duct smoke detectors. (not included). The smoke detector shall have a flashing status LED for visual supervision. When the detector is actuated, the flashing LED will latch on steady. The detector may be reset by actuating the control panel reset switch. The calibration of the detector shall be capable of being selected and measured by the control panel without the need for external test apparatus. The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking feature shall be field selectable as required. The SK-Photo shall automatically perform a functional test of the detector.The test method shall simulate effects of products of combustion in the chamber to ensure testing of detector circuits. SIC IN OUT u,.„ : ` Air,t ,kg . Compatible FACP + — + — RA100Z(Optional) ----.—.111\ ----:.'' --7"14‘ 1111111111111) +1+ AIN II �1+1.(11..,11—•.• �� �i‘iiiir \\ iii, %--.17.....„„ilr Class A Optional Wiring , Wiring SK-Series Detector Mounting Bases SILENT This document is not intended to be used for installation purposes.We try to MADE IN AMERICA No KNIGHT keep our product information up-to-date and accurate.We cannot cover all specific applications or anticipate all requirements.Ali specifications are FORM#350118 Rev E subject to change without notice.For more information,contact Silent Knight ©2013 Honeywell International Inc. by Honeywell 12 Clintonville Road, Northford,CT 06472-1610 Phone: (800)328-0103, Fax:(203)484-7118. For Technical Support,Please call 800-446-6444. www.silentknight.com Model SK-DUCT Air Duct Smoke Detector Engineering Specifications The air duct smoke detector shall be a SK-Duct photoelectric duct smoke detector. The detector housing shall be UL listed per UL 268A specifically for use in air handling systems. The flexible housing of the duct smoke detector fits both square and rectangular footprints. The detector shall operate at air velocities of 100 ft/min to 4000 ft/min (0.5 m/sec to 20.32 m/sec). The unit shall be capable of providing a trouble signal in the event that the sensor cover is removed or improperly installed. It shall be capable of local testing via magnetic switch or remote testing using the RTS151 KEY remote test station. Terminal connections shall be of the strip and clamp method suitable for 12-18AWG wiring. The unit housing shall be capable of mounting a relay module. Ordering Information SK-Duct Intelligent non-relay duct smoke detector M02-04-00 Test Magnet SK-Photo Addressable Photo Detector P48-21-00 Replacement End Cap for Metal SK-PhotoR Addressable Photo Detector with remote test Sampling Tube capability(included with SK-Duct) APA151 Remote annunciator with piezo alarm SK-Relay Addressable Relay Module, must be added if relay function is required, (fits in housing) Important Notes: Accessoriest •The use of either RTS151 or RTS151KEY requires the DST1 Metal Sampling Tube Duct Width up to 1' installation of an accessory coil, DCOIL, sold separately. DST1.5 Metal Sampling Tube Duct Widths 1'-2' Please refer to the SK-Duct installation instructions for DST3 Metal Sampling Tube Duct Widths 2'—4' more information DST5 Metal Sampling Tube Duct Widths 4'—8' •The RTS151/RTS151KEY test coil circuit requires an DST10 Metal Sampling Tube Duct Widths 8'— 12' external 24VDC power supply which must be UL listed. DH4000E-1 Weatherproof Enclosure ETX Metal Exhaust Tube Duct width 1' RA100Z Remote LED Annunciator Accessory Current Loads at 24 VDC DCOIL Duct accessory coil, required if using with Device Standby Alarm SK-Photo and not SK-PhotoR(included)with RA100Z OmA 12mA Max. SK-Duct RTS151 Magnetic Remote Test station RTS151 OmA 12mA Max. RTS151KEY Key-Activated Remote Test station RTS151 KEY 12mA 12mA Max. SILENT This document is not intended to be used for installation purposes.We try MADE IN AMERICA to keep our product information up-to-date and accurate.We cannot cover tip KNIGHT all specific applications or anticipate all requirements.All specifications are subject to change without notice.For more information,contact Silent FORM#350122 Rev D Knight 12 Clintonville Road, Northford,CT 06472-1610 ©2010 Honeywell International Inc. by Honeywell Phone:(800)328-0103, Fax:(203)484-7118. www.silentknight.com SILENT SK-Pull-SA and SK-Pull-DA KNIGHT • Intelligent Pull Stations by Honeywell The SK-Pull-SA and SK-Pull-DA are a single action or dual action addressable fire alarm pull station for use with Silent Knight's IntelliKnight fire control panel. Extremely easy to operate, the SK-Pull-DA and SK-Pull-SA provide a fast and practical means of manually initiating a fire alarm signal. The IntelliKnight panel recognizes each manual pull station by its specific address saving precious seconds in determining the location of an alarm. For more information about the IntelliKnight system, or to locate you nearest source, please call 1-800-328-0103. Description The SK-Pull-SA is a single action pull station requiring only one motion to activate the station. The SK-Pull-DA is a dual action pull station requiring two motions to active the station. Both pull stations are designed to work with Silent Knight PULL 4, DOWN Intelliknight series fire alarm control panels (FACPs). Features • Installer can open station without causing an alarm condition mi'NT 1 icviUar a ), • Dual-color LED is visible through handle of station blinks a' green to indicate normal operation and remains steady red in an alarm condition SK-Pull-SA • Key operated test and reset lock using lock plate actuator • Key matches compatible FACP locks IR E • Meets the Americans with Disabilities Act Accessibility Guidelines (ADAAG) controls and operating mechanisms I PUSH IN guidelines (Section 4.1.3[13]) *PULL DOWN • Meets ADA requirement for 5 lbs maximum pull force to active • Shell, door, and handle molded from durable LEXAN® SIxr • Reliable analog communications for trouble-free operation • Braille text on station handle SK-Pull-DA • Handle latches in down position and the word Activated Compatibility • appears, clearly indicating the station has been pulled The SK-Pull-SA and SK-Pull-DA are compatible • Rotary address switches for fast installation with the following IntelliKnight FACP's: 5600 • • UL Listed, including UL 38, Standard of Manually Actuated 5700 Signaling System 5808 5820XL 5820XL-EVS 0 - • .-- Model SK-Pull-DA and SK-Pull-SA Intelligent Pull Stations Engineering Specifications The contractor shall furnish and install where indicated on the plans,Addressable Pull Stations, Silent Knight model SK-Pull-SA single action pull station or SK-Pull-DA, dual action pull station. SK-Pull-DA or SK-Pull-SA meet the ADAAG controls and operating mechanisms guidelines, and the ADA requirements for a 5 lb. maximum pull force to activate the pull station. 4 t' 400111,2 ici> Class A Ari * s % Class B Compatible FACP r, III mao''''!,: U t - Z�� / - i0,, / 'sfii # t • la 4/ • Class A Wiring: r...: j, tq `,; Class B Wiring:.._ '� - /-. C„ ,,,,,/:14irt Wiring SK-Pull-SA&SK-Pull-DA Pull Stations Specifications Electrical Physical Operating Voltage: 15-32 VDC Height: 5.5" (14 cm) Average Operating Current(LED flashing): 300 pA Width: 4" (10.2 cm) Wire Gauge: Up to 12 AWG (3.1 mm2) Depth: 5.4 oz. (3.7 cm) Environmental Housing Material: LEXAN polycarbonate resin Operating Temperature 32°— 120°F (0°C—49°C) Bi-Colored LED: Humidity: 10%—93% non-condensing Blinking Green: Normal Steady Red:Alarm Accessories Switch: Single pole, single throw(SPST) normally open (N/O) BG-TR Optional trim ring. switch which closes upon activation of the pull station SB-I/O Surface backbox SILENT This document is not intended to be used for installation purposes.We try MADE IN AMERICA K to keep our product information up-to-date and accurate.We cannot cover NI I\NIGI�T all specific applications or anticipate all requirements.All specifications are FORM#350135 Rev C subject to change without notice. For more information,contact Silent by Honeywell Knight 12 Clintonville Road, Northford, CT 06472-1610 ©2013 Honeywell International Inc. Phone: (800)328-0103, Fax:(203)484-7118. For Technical Support, Please call 800-446-6444. www.silentknight.com 410 SILENT K-Monitor KNIGHT by Honeywell Intelligent Monitor Module The SK-Monitor module provides an interface to contact devices, such as security contacts, waterflow switches, or pull stations. For more information about the IntelliKnight system, or to locate you nearest source, please call 1-800-328-0103. Description The SK-Monitor is an addressable monitor module for use with Silent Knight IntelliKnight series fire alarm control :; panels (FACPs). The SK-Monitor is intended for use in f q intelligent, two-wire systems, where individual address of ���. � ,�t � , each module is selected using the built-in rotary switches. . ro ,, `'V� The SK-Monitor supports Class A supervised or Class B supervised wiring to the load device. Conventional 4-wire �,, smoke detectors can be monitored for alarm and trouble i; ' * �� r,, ' conditions. - ., , ,4 " Features " • Single contact monitor *70 • Support for Class A and Class B wiring a, , , • Fully supervised % • Panel controlled status LED that.flashes green in normal state and is solid red in alarm • Attractive ivory cover plate SK-Monitor • Rotary address switches for fast installation • SEMS screws for easy wiring Specifications • UL Listed Physical Installation Height: 4.5" (11.4 cm) The SK-Monitor mounts directly into a 4" square electrical Width: 4" (10.2 cm) box. The box must have a minimum depth of 2-1/8".A Depth: 1.25" (3 cm) surface mount electrical box (System Sensor® PN Shipping Weight: 6.3 oz (196 g) SMB500) is available from Silent Knight. Electrical Compatibility Operating Voltage: 15— 32 VDC The SK-Monitor is compatible with the following Current Draw (LED on): 5.0 mA max IntelliKnight FACP's: Operating Current (LED flashing): 375 pA 5700 5808 5820XL 5820XL-EVS , - Model SK-Monitor Intelligent Monitor Module TO NEXT 44 1-9 DELI€ ,� CA"K.- °<c°, R�- ,_sc-` 4'I x a r�r�L ars 7 ' PREVIOUS DEVICE yi ANY NUMBER OF IL LIBTBJ CONTACT r--, MODULE na 1 CLOSURE DEINCES MAYBE a I.DO NOT MIX . DOMIEOT MODULES TO LISTED C NIPA71 E FRE AtARM1IMT{RTMD,SUPERIVISESRY,OR V 8 • Q iI CONTROL PI41+EL8 DALY SECLRRY❑P ICER ONTI E SME IADOL#E: i • R j 41 I *,� , IV 47K EDL 11 b 1 h8/8F1A1 UhE CRCIdT Pig EtA-47K 11' 7 . Ti1�PD614N4 tI • 711VIE3TEL}PdYR S ;,..♦1 IS FECOMENDED PIITATP4D DEVICE CREW*gDc NFPA BTYLE B PO4#VER UMTED:46tµA Max.A 11 VOC WAX INSTALLC TE DIILIFE DE VICEH PER ALL WRING SHOWN E BLPEFht�APE POWER LIMITED MANUFACTURERS INSTALLATION INSTRUCTIONS. 2-Wire Initiating Circuit Configuration, NFPA Style B TO NEXT FROM PANEL OR DEVICE 4'411.41.s 46 wr IF s.f ti!• /+rrr �.f+�•..wt+# PREVIOUS DEVICE MONITOR t ANY NUMBER OF LL.LIS I ED CONTACT MODULE CLOSURE DEVICES MAY BE USED DO NOT MIX $$ • $y OZWNECT MODULES TO LISTED COMPATIBLE FRE ALARM INTIATING,SUPERVISORY,OR p����0 • cs • N(3TEER CONTROL R NEL.&ONLY SECURITY DEVICES ON THE SAME MODULE. .. - Uii • +` iro t51� is N. I �;- SIGNAL LANE CJ.6DU?T_I�BLC} EOL RESISTOR I6 I I ,' 32 VOC MAX. �*° * SHIELDED-TWISTED PAIR INTERNALAT S Ii®A IS REOOMENDED TERMINALS 8 SS b L-r Li INSTALL CONTACT CLOSURE DEVICES PER ALL WIRING SHOWN IS SUPERVISED AM)POWER UNITED MANUFAC1 UTIETTS ISTALLATION INSTRUCTIONS. 4-Wire Initiating Circuit Configuration, NFPA Style D Standby Current: Environmental 400 pA max @ 24 VDC (one communication every 5 Operating Temperature: 32°F— 120°F (0°C—49°C) sec with 47K EOL) Humidity: 10%— 93% non-condensing 550 SIA max @ 24 VDC (one communication every 5 sec with EOL <1K) Ordering Information 5.5 mA(with LED latched on) SK-Monitor Monitoring Module LED Current: 5.5 mA(with LED latched on)End-of-Line Resistance: 47K S2 Accessories Initiating Device Circuit Wiring Resistance: 1,500 f2 max SMB500 4" Square Surface Mount Electrical Box SLC Loop Resistance: 40 0 max. SILENT This document is not intended to be used for installation purposes.We try to MADE IN AMERICA 4% KNIGHT keep our product information up-to-date and accurate.We cannot cover all specific applications or anticipate all requirements.All specifications are subject to change without notice. For more information,contact Silent Knight FORM#350131 Rev D by Honeywell 12 Clintonville Road,Northford, CT 06472-1610 Phone:(800)328-0103, ©2013 Honeywell International Inc. Fax:(203)484-7118. For Technical Support,Please call 8200-446-6444. www.silentknight.com • Model SK-Monitor-2 Intelligent Dual Monitor Module To Next Device + 4 n n M Te E.4.4 o ° 06)CO:TY Compatible FACP Two Initiating Device Circuits NFPA Style B Power Limited 230 NA Max @ 12 VDC Max SLC •. MI 0 O Cf 1J AsS W Nt!..a, cop TB E01---- ---- .. t CSE n ESE (41(TO.04". '. 11 ao ° 0 U U Wiring SK-Monitor-2 Modules Specifications End-of-Line Resistance:47K S2 Physical Max IDC wiring resistance: 1,50052 Height:4.5" H x 4"W x 1.25" D SLC Line Loop Resistance:4052 max. Shipping Weight: 6.3 oz (196 g) Environmental Electrical Operating Temperature: 32°F— 120°F (0°C—49°C) Operating Voltage: 15—32 VDC Humidity: 10%—93% non-condensing Current Draw(LED on): 6.4 mA max Accessories Operating Current(LED flashing): 750 pA SMB500 4"Square Surface Mount Electrical Box This document is not intended to be used for installation purposes.We try MADE IN AMERICA SILENT to keep our product information up-to-date and accurate.We cannot cover KNIGH' all specific applications or anticipate all requirements.All specifications are subject to change without notice.For more information,contact Silent FORM#350124 Rev C 1r, Knight 12 Clintonville Road, Northford,CT 06472-1610 ©2013 Honeywell International Inc. by Honeywell Phone:(800)328-0103, Fax: (203)484-7118. For Tehnical Support,Please call 800-446-6444. www.silentknight.com Model SK-Relay Intelligent Relay Module To Next Device – 44 If Any Wiring to Terminals 3–9 is Not Power + Limited,the CB500 Barrier is Required.The CB500 Includes a Non-Power Limited Label, n n Which Must Be Placed Over the Power Limited ICIZ, O 0 O Terminal Information on the Name Plate Label. Relay Common 2 `° 9 •T, °Cr—, Normally Closed 2 i a ;6 + Normally Open 2 i; 7 „'* 2 ,“r Relay Common 1 a :`”` a – From Compatible FACP a1� 11° + or Previous Device Normally Closed 1 1; a =, 4X €. Module Does Not Supervise ° Normally Open 1 Controlled Circuits U U Wiring the SK-Relay Module Specifications Ordering Information Physical SK-Relay Relay Module 4.675" H x 4.275" W x 1.4" D Shipping Weight: 6.3 oz (196 g) Accessories Environmental SMB500 4" Square Surface Mount Electrical Box Operating Temperature: 32°F– 120°F (0°C–49°C) CB500 Module Barrier Humidity: 10% – 93% non-condensing Electrical Operating Voltage: 15–32 VDC Relay Contact Ratings End-of-Line Resistance: Not used 3.0A @ 30 VDC resistive SLC Standby&Alarm Current: .255mA max @ 24 0.9A @ 110 VDC resistive VDC (one communication every 5 sec with LED 0.9A @ 125 VAC resistive enabled) 0.5A @ 125 VAC inductive (PF = .35) 0.7A @ 75 VAC inductive (PF = .35) SILENT This document is not intended to be used for installation purposes.We try to keep ;;;•;;; KNIGHT our product information up-to-date and accurate.We cannot cover all specific +. NI applications or anticipate all requirements.All specifications are subject to change without notice. For more information,contact Silent Knight 12 Clintonville Road, by Honeywell Northford,CT 06472-1610 Phone: (800)328-0103, Fax: (203)484-7118. For Technical Support, Please Call 800-446-6444. www.silentknight.com Asembled in USA SpectrAlert Advance Specifications Architect/Engineer Specifications General SpectrAlert Advance horns,strobes,and horn strobes shall mount to a standard 4 x 4 x 11/2-inch back box,4-inch octagon back box,or • double-gang back box.Two-wire products shall also mount to a single-gang 2 x 4 x 17/8-inch back box.A universal mounting plate shall be used for mounting ceiling and wall products.The notification appliance circuit wiring shall terminate at the universal mounting plate. Also,SpectrAlert Advance products,when used with the Sync•Circuit°' Module accessory,shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts.When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts;24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full- wave rectified unfiltered power supply.Strobes and horn strobes shall have field-selectable candela settings including 15, 15/75,30,75,95, 110, 115, 135, 150, 177,and 185. Strobe The strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Horn Strobe Combination The horn strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and UL 464 and shall be approved for fire protective service.The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system.The horn shall have three audibility options and an option to switch between a temporal three pattern and a non-temporal(continuous)pattern.These options are set by a multiple position switch.On four-wire products,the strobe shall be powered independently of the sounder.The horn on horn strobe models shall operate on a coded or non-coded power supply. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service.The module shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three.Also,while operating the strobes,the module shall silence the horns on horn strobe models over a single pair of wires.The module shall mount to a 411/16 x 411/16 x 21/8-inch back box.The module shall also control two Style Y(class B)circuits or one Style Z(class A)circuit.The module shall synchronize multiple zones.Daisy chaining two or more synchronization modules together will synchronize all the zones they control.The module shall not operate on a coded power supply. Physical/Electrical Specifications. Standard Operating Temperature 32°F to 120°F(0°C to 49°C) Humidity Range 10 to 93%non-condensing Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR' Operating Voltage Rangel 8 to 17.5 V(12 V nominal)or 16 to 33 V(24 V nominal) Operating Voltage Range MDL3 Sync Module 8.5 to 17.5 V(12 V nominal)or 16.5 to 33 V(24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG Wall-Mount Dimensions(including lens) 5.6"L x 4.7"W x 2.5"D(142 mm L x 119 mm W x 64 mm D) Horn Dimensions 5.6"L x 4.7"W x 1.3"D(142 mm L x 119 mm W x 33 mm D) Wall-Mount Trim Ring Dimensions(sold as a 5 pack)(TR-HS) 5.7"L x 4.8"W x 0.35"D(145 mm L x 122 mm W x 9 mm D) Notes: 1.Full Wave Rectified(FWR)voltage is a non-regulated,time-varying power source that is used on some power supply and panel outputs. 2.P.S,PC,and SC products will operate at 12 V nominal only for 15 and 15/75 cd. UL Current Draw Data UL Max.Strobe Current Draw(mA RMS) UL Max.Horn Current Draw(mA RMS) 8-17.5 Volts 16-33 Volts 8-17.5 Volts 16-33 Volts Candela DC FWR DC FWR Sound Pattern dB DC FWR DC FWR • Standard 15 123 128 66 71 Temporal High 57 55 69 75 Candela 15/75 142 148 77 81 Temporal Medium 44 49 58 69 Range 30 NA NA 94 96 Temporal Low 38 44 44 48 75 NA NA 158 153 Non-temporal High 57 56 69 75 95 NA NA 181 176 Non-temporal Medium 42 50 60 69 110 NA NA 202 195 Non-temporal Low 41 44 50 50 115 NA NA 210 205 Coded High 57 55 69 75 High 135 NA NA 228 207 Coded Medium 44 51 56 69 Candela 150 NA NA 246 220 Coded Low 40 46 52 50 Range 177 NA NA 281 251 185 NA NA 286 258 UL Max.Current Draw(mA RMS),2-Wire Horn Strobe,Standard Candela Range(15-115 cd) 8-17.5 Volts 16-33 Volts DC Input 15 15/75 15 15175 30 75 95 110 115 Temporal High 137 147 79 90 107 176 194 212 218 Temporal Medium 132 144 69 80 97 157 182 201 210 Temporal Low 132 143 66 77 93 154 179 198 207 Non-Temporal High 141 152 91 100 116 176 201 221 229 Non-Temporal Medium 133 145 75 85 102 163 187 207 216 Non-Temporal Low 131 144 68 79 96 156 182 201 210 FWR Input Temporal High 136 155 88 97 112 168 190 210 218 ' Temporal Medium 129 152 78 88 103 160 184 202 206 Temporal Low 129 151 76 86 101 160 184 194 201 Non-Temporal High 142 161 103 112 126 181 203 221 229 Non-Temporal Medium 134 155 85 95 110 166 189 208 216 Non-Temporal Low 132 154 80 90 105 161 184 202 211 UL Max.Current Draw(mA RMS),2-Wire Horn Strobe,High Candela Range(135-185 cd) 16-33 Volts 16-33 Volts DC Input 135 150 177 185 FWR Input 135 150 177 185 Temporal High 245 259 290 2.97 Temporal High 215 231 • 258 265 Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258 Temporal Low 232 251 282 292 Temporal Low 207 221 248 256 Non-Temporal High 255 270 303 309 Non-Temporal High 233 248 275 281 Non-Temporal Medium 242 259 293 299 Non-Temporal Medium 219 232 262 267 Non-Temporal Low 238 254 291 295 Non-Temporal Low 214 229 256 262 Horn Tones and Sound Output Data Horn and Horn Strobe Output(dBA) 8-17.5 16-33 24-Volt Nominal Switch Volts Volts Reverberant Anechoic Position Sound Pattern dB DC FWR DC FWR DC FWR DC FWR 1 Temporal High 78 78 84 84 88 88 99 98 2 Temporal Medium 75 75 80 80 86 86 96 96 3 Temporal Low 71 71 76 76 83 80 94 89 4 Non-Temporal High 82 82 88 88 93 92 100 100 5 Non-Temporal Medium 78 78 85 85 90 90 98 98 6 Non-Temporal Low 73 74 81 81 88 84 96 92 7t Coded High 82 82 88 88 93 92 101 101 8r Coded Medium 78 78 85 85 90 90 97 98 9r Coded Low 74 75 81 81 88 85 96 92 Settings 7,8,and 9 are not available on 2-wire horn strobes. SpectrAlert Advance Dimensions 4.7" 2.5 CO/Of POWr 1 11111 r=1=3111MIME==p In ...i t II 5.6" ,' J'- � G� ill irl�� Wall-mount horn strobes SpectrAlert Advance Ordering Information Model Description Model Description Wall Horn Strobes Wall Strobes(cont.) P2R 2-Wire Horn Strobe,Standard cd,Red SRN Strobe,High cd,Red P2R-P 2-Wire Horn Strobe,Standard cd,Red,Plain SRH-P Strobe,High cd,Red,Plain P2R-SP 2-Wire Horn Strobe,Standard cd,Red,"FUEGO" SRH-SP Strobe,High cd, Red, "FUEGO" P2RH 2-Wire Horn Strobe, High cd,Red 0 SW Strobe,Standard cd White P2RH-P 2-Wire Horn Strobe,High cd, Red,Plain SW-P Strobe,Standard cd,White,Plain P2W'^ 2-Wire Horn Strobe,Standard cd,White SWH Strobe, High cd,White P2W-P 2-Wire Horn Strobe,Standard cd,White,Plain SWH-P Strobe, High cd,White,Plain P2WH 2-Wire Horn Strobe,High cd,White Horns P2WH-P 2-Wire Horn Strobe,High cd,White,Plain HR Horn,Red P4R 4-Wire Horn Strobe,Standard cd,Red HW Horn,White P4R-P 4-Wire Horn Strobe,Standard cd,Red,Plain Accessories P4RH 4-Wire Horn Strobe,High cd,Red TR-HS Trim Ring,Wall,Red P4W 4-Wire Horn Strobe,Standard cd,White SBBR Indoor Surface Mount Back Box,Red Wail Strobes SBBW Indoor Surface Mount Back Box,White SR Strobe,Standard cd,Red SR-P Strobe,Standard cd,Red,Plain SR-SP Strobe,Standard cd,Red, "FUEGO" Notes: All-P models have a plain housing(no"FIRE"marking on cover) All-SP models have"FUEGO"marking on cover "Standard cd"refers to strobes that include 15,15/75,30,75,95,110,and 115 candela settings. "High cd"refers to strobes that include 135.150,177,and 185 candela settings. *Th, SYSTEIVI 3825 Ohio Avenue•St.Charles, IL 60174 ©2014 system sensor. Phone:800-SENSOR2•Fax:630-377-6495 Product specifications subject to chanoe wiJaut notice vis systemsens«.com .. SENSOR' for current product information,including the latest versos of his data sheet. www.systemsensor.com AOS10201•1/14 SpectrAlert Advance Specifications Architect/Engineer Specifications'' General SpectrAlert Advance strobes and horn strobes shall mount to a standard 4 x 4 x 11/-inch back box,4-inch octagon back box,or double- gang back box.Two-wire products shall also mount to a single-gang 2 x 4 x 17/8-inch back box.A universal mounting plate shall be used for mounting ceiling and wall products.The notification appliance circuit wiring shall terminate at the universal mounting plate.Also,SpectrAlert Advance products,when used with the Sync•Circuit""Module accessory,shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts.When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 9 and 17.5 volts;24-volt-rated notification appliance circuit outputs shall operate between 17 and 33 volts. Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply.Strobes and horn strobes shall have field-selectable candela settings including 15, 15/75,30,75,95, 110, 115, 135, 150, 177,and 185. Strobe The strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Horn Strobe Combination The horn strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and UL 464 and shall be approved for fire protective service.The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system.The horn shall have three audibility options and an option to switch between a temporal three pattern and a non-temporal(continuous)pattern.These options are set by a multiple position switch.On four-wire products,the strobe shall be powered independently of the sounder.The horn on horn strobe models shall operate on a coded or non-coded power supply. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL listed to UL 464 and shall be approved for fire protective service.The module shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three.Also,while operating the strobes.the module shall silence the horns on horn strobe models over a single pair of wires.The module shall mount to a 411./16 x 411/16 x 21/8-inch back box.The module shall also control two Style Y(class B)circuits or one Style Z(class A)circuit.The module shall synchronize multiple zones.Daisy chaining two or more synchronization modules together will synchronize all the zones they control.The module shall not operate on a coded power supply. Physical/Electrical Specifications Standard Operating Temperature 32°F to 120°F(0°C to 49°C) Humidity Range 10 to 93%non-condensing Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR1 Operating Voltage Rangel 8 to 17.5 V(12 V nominal)or 16 to 33 V(24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG Ceiling-Mount Dimensions(including lens) 6.8"diameter x 2.5"high(173 mm diameter x 64 mm high) Ceiling-Mount Back Box Skirt Dimensions(BBSC-2,BBSCW-2) 7.1"diameter x 2.2"high(180 mm diameter x 57 mm high) Ceiling-Mount Trim Ring Dimensions(sold as a 5 pack)(TRC-HS, 6.9"diameter x 0.35"high(175 mm diameter x 9 mm high) TRCW-HS) Notes: 1.Full Wave Rectified(FWR)voltage is a non-regulated,time-varying power source that is used on some power supply and panel outputs. 2.P,5,PC,and SC products will operate at 12 V nominal only for 15 and 15/75 cd. AVDS00501 UL Current Draw Data UL Max.Strobe Current Draw(mA RMS) 8-17.5 Volts 16-33 Volts Candela DC FWR DC FWR • Standard Candela Range 15 123 128 66 71 15/75 142 148 77 81 30 NA NA 94 96 • 75 NA NA 158 153 95 NA NA 181 176 110 NA NA 202 195 115 NA NA 210 205 High 135 NA NA 228 207 Candela Range 150 NA NA 246 220 177 NA NA 281 251 185 NA NA 286 258 UL Max.Current Draw(mA RMS),2-Wire Horn Strobe,Standard Candela Range(15-116 cd) 8-17.5 Volts 16-33 Volts DC Input 15 15175 15 15/75 30 75 95 110 115 Temporal High 137 147 79 90 107 176 194 212 218 Temporal Medium 132 144 69 80 97 157 182 201 210 Temporal Low 132 143 66 77 93 154 179 198 207 Non-Temporal High 141 152 91 100 116 176 201 221 229 Non-Temporal Medium 133 145 75 85 102 163 187 207 216 Non-Temporal Low 131 144 68 79 96 156 182 201 210 FWR Input Temporal High 136 155 88 97 112 168 190 210 218 • Temporal Medium 129 152 78 88 103 160 184 202 206 Temporal Low 129 151 76 86 101 160 184 194 201 Non-Temporal High 142 161 103 112 126 181 203 221 229 Non-Temporal Medium 134 155 85 95 110 166 189 208 216 Non-Temporal Low 132 154 80 90 105 161 184 202 211 UL Max.Current Draw(mA RMS),2-Wire Horn Strobe,High Candela Range(135-185 cd) 16-33 Volts 16-33 Volts DC Input 135 150 177 185 FWR Input 135 150 177 185 Temporal High 245 259 290 297 Temporal High 215 231 258 265 Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258 Temporal Low 232 251 282 292 Temporal Low 207 221 248 256 Non-Temporal High 255 270 303 309 Non-Temporal High 233 248 275 281 Non-Temporal Medium 242 259 293 299 Non-Temporal Medium 219 232 262 267 Non-temporal Low 238 254 291 295 Non-Temporal Low 214 229 256 262 Horn Strobe Tones and Sound Output Data Horn Strobe Output(dBA) 8-17.5 16-33 24-Volt Nominal Switch Volts Volts Reverberant Anechoic Position Sound Pattern dB DC FWR DC FWR DC FWR DC FWR 1 Temporal High 78 78 84 84 88 88 99 98 2 Temporal Medium 74 74 80 80 86 86 96 96 3 Temporal Low 71 73 76 76 83 80 94 89 4 Non-Temporal High 82 82 88 88 93 92 100 100 5 Non-Temporal Medium 78 78 85 85 90 90 98 98 6 Non-Temporal Low 75 75 81 81 88 84 96 92 7t Coded High 82 82 88 88 93 92 101 101 81 Coded Medium 78 78 85 85 90 90 97 98 9t Coded Low 75 75 81 81 88 85 96 92 tsettings 7,8,arid 9 are not available on 2-wire horn strobes. AVDS00501 SpectrAlert Advance Dimensions 7.1" 14-2.251 6.8" /' Dia. I Dia. 7 P P . 0 ic:, i/ (7 .r__ __,,._ PM , i lot c r, 2.5 „, !., 0 4.---,---- 4,--, \' ' di Ceiling-mount horn strobes Ceiling back box skirt • SpectrAlert Advance Ordering Information Model Description Model Description Ceiling Horn Strobes Ceiling Strobes PC2R* 2-Wire Horn Strobe,Standard cd,Red SCR Strobe,Standard cd,Red PC2RH 2-Wire Horn Strobe, High cd,Red SCRH Strobe,High cd, Red PC2W*fi 2-Wire Horn Strobe,Standard cd,White SCW* Strobe;Standard cd,White PC2WH* 2-Wire Horn Strobe,High cd,White SCWH Strobe,High cd,White PC4R 4-Wire Horn Strobe,Standard cd,Red Accessories PC4RH 4-Wire Horn Strobe, High cd,Red BBSC-2 Back Box Skirt,Ceiling,Red PC4W 4-Wire Horn Strobe,Standard cd,White Back Box Skirt,Ceiling,White TRC-HS Trim Ring,Ceiling, Red TRCW- Trim Ring,Ceiling,White HS Notes: *Add"-P"to model number for plain housing(no"FIRE"marking on cover),e.g.,P2R-P. t Add'-SP"to model number for"FUEGO"marking on cover,e.g.,P2R-SP. t"Standard cd"refers to strobes that include 15,15/75,30,75.95,110.and 115 candela settings."High cd"refers to strobes that include 135,150,177.and 185 candela settings. S/E� ©2012 Sysiem Sensor. ` '_`+ ` 3825 Ohio Avenue•St.Charles, IL 60174 Productspec�ticationssubjecttohanoewatroutnotice.Vistsystemsensoccom 1_..\�"y`) ,5. ' Phone:800-SENSO R2•Fax:630-377-6495 for current product intorrrahon,including the latest version of this data sheet. AVDS00507•3/12 SpectrAlert Advance Outdoor Horn, Strobe, and Horn Strobe Specifications Architect/Engineer Specifications General SpectrAlert Advance outdoor horns,strobes,and horn strobes shall mount to a weatherproof back box.A universal mounting plate shall be used for mounting ceiling and wall products.The notification appliance circuit wiring shall terminate at the universal mounting plate. Also,SpectrAlert Advance products,when used with the Sync•Circuit° Module accessory,shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts.When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 9 and 17.5 volts;24-volt-rated notification appliance circuit outputs shall operate between 17 and 33 volts.Outdoor SpectrAlert Advance products shall operate between-40 and 151 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply.Strobes and horn strobes shall have field-selectable candela settings including 15, 15/75,30,75,95, 110, 115, 135, 150, 177,and 185. Strobe The strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system.The strobe must be installed with its weatherproof back box in order to remain outdoor approved per UL.The strobe shall be suitable for use in wet environments. Horn Strobe Combination The horn strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and UL 464 and shall be approved for fire protective service.The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system.The horn shall have three audibility options and an option to switch between a temporal three pattern and a non-temporal(continuous)pattern.These options shall be set by a multiple position switch. On four-wire products,the strobe shall be powered independently of the sounder.The horn or horn strobe models shall operate on a coded or non-coded power supply.The horn strobe must be installed with its weatherproof back box in order to remain outdoor approved per UL. The horn strobe shall be suitable for use in wet environments. Physical/Electrical Specifications • Operating Temperature -40°F to 151°F(-40°C to 66°C) Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR; - Operating Voltage Rangel 8 to 17.5 V(12 V nominal)or 16 to 33 V(24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG Wall-Mount Dimensions(including lens) 5.6"L x 4.7"W x 2.5"D(142 mm L x 119 mm W x 64 mm D) Horn Dimensions 5.6"L x 4.7"W x 1.3"D(142 ram L x 119 mm W x 33 rnrn D) Wall-Mount Weatherproof Back Box Dimensions(SA-WBB) 5.7"L x 5.1"W x 2.0"D(145 mm L x 130 mm W x 51 mm D) Notes: 1.Full Wave Rectified(FWR)voltage is a non-regulated,time-varying power source that is used on some power supply and panel outputs. 2.P,5,PC,and SC products will operate at 12 V nominal only for 15 and 15/75 cd. AVDS01201 UL Current Draw Data UL Max.Strobe Current Draw(mA RMS) : UL Max.Horn Current Draw(mA RMS) 8-17.5 Volts 16-33 Volts 8-17.5 Volts 16-33 Volts Candela DC FWR DC FWR Sound Pattern dB DC FWR DC FWR • Standard 15 123 128 66 71 Temporal High 57 55 69 75 Candela 15/75 142 148 77 81 Temporal Medium 44 49 58 69 Range 30 NA NA 94 96 Temporal Low 38 44 44 48 ' 75 NA NA 158 153 Non-Temporal High 57 56 69 75 95 NA NA 181 176 Non-Temporal Medium 42 50 60 69 110 NA NA 202 195 Non-Temporal Low 41 44 50 50 115 NA NA 210 205 Coded High 57 55 69 75 High 135 NA NA 228 207 Coded Medium 44 51 56 69 Candela 150 NA NA 246 220 Coded Low 40 46 52 50 Range 177 NA NA 281 251 185 NA NA 286 258 UL Max.Current Draw(mA RMS),2-Wire Horn Strobe,Standard Candela Range(15-115 cd) 8-17.5 Volts 16-33 Volts DC Input 15 15/75 15 15/75 30 75 95 110 115 Temporal High 137 147 79 90 107 176 194 212 218 Temporal Medium 132 144 69 80 97 157 182 201 210 Temporal Low 132 143 66 77 93 154 179 198 207 Non-Temporal High 141 152 91 100 116 176 201 221 229 Non-Temporal Medium 133 145 75 85 102 163 187 207 216 Non-Temporal Low 131 144 68 79 96 156 182 201 210 FWR Input Temporal High 136 155 88 97 112 168 190 210 218 • Temporal Medium 129 152 78 88 103 160 184 202 206 Temporal Low 129 151 76 86 101 160 184 194 201 Non-Temporal High 142 161 103 112 126 181 203 221 229 • Non-Temporal Medium 134 155 85 95 110 166 189 208 216 Non-Temporal Low 132 154 80 90 105 161 184 202 211 UL Max.Current Draw(mA RMS),2-Wire Horn Strobe,High Candela Range(135-185 cd) 16-33 Volts 16-33 Volts DC Input 135 150 177 185 FWR Input 135 150 177 185 Temporal High 245 259 290 297 Temporal High 215 231 258 265 Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258 Temporal Low 232 251 282 292 Temporal Low 207 221 248 256 Non-Temporal High 255 270 303 309 Non-Temporal High 233 248 275 281 Non-Temporal Medium 242 259 293 299 Non-Temporal Medium 219 232 262 267 Non-Temporal Low 238 254 291 295 Non-Temporal Low 214 229 256 262 Candela Derating Horn Tones and Sound Output Data For K series products used at low temperatures,listed Horn and Horn Strobe Output((IRA) candela ratings must be reduced in accordance with 8-17.5 16-33 24-Volt Nominal this table. Volts Volts Reverberant Anechoic Strobe Output(cd) Switch Sound Position Pattern dB DC FWR DC FWR DC FWR DC FWR Listed Candela Candela rating at—40°F 1 Temporal High 78 78 84 84 88 88 99 98 15 2 Temporal Medium 74 74 80 80 86 86 96 96 15/75 Do not use below 32°F 3 Temporal Low 71 73 76 76 83 80 94 89 30 4 Non- High 75 44 Temporal 82 82 88 88 93 92 100 100 95 70 5 Non- Medium • 110 110 Temporal 78 78 85 85 90 90 98 98 115 115 6 Non- Low 75 75 81 81 88 84 96 92 135 135 Temporal • 150 150 7r Coded High 82 82 88 88 93 92 101 101 177 177 8t Coded Medium 78 78 85 85 90 90 97 98 185 185 9t Coded Low 75 75 81 81 88 85 96 92 Settings 7,8,and 9 are not available on 2-wire horn strobe. AVDS01201 SpectrAlert Advance Diagrams r_4.7" 2.5" 1 5.6" I MD— KS. 0 - Wall-Mount Horn Strobes Wall Plastic Weatherproof Back Box ° UP l *i) 4. Wall-Mount Horn Strobe with Plastic Weatherproof Back Box SpectrAlert Advance Ordering Information Model Description Wall Horn Strobes P2RK't 2-Wire Horn Strobe,Standard cd,Red, Outdoor(includes plastic weatherproof back box) P2RHK*t 2-Wire Horn Strobe,High cd,Red,Outdoor(includes plastic weatherproof back box) P2WK"t 2-Wire Horn Strobe,Standard cd,White,Outdoor(includes plastic weatherproof back box) P2WHK*t 2-Wire Horn Strobe, High cd,White,Outdoor(includes plastic weatherproof back box) P4RKt 4-Wire Horn Strobe,Standard cd,Red,Outdoor(includes plastic weatherproof back box) P4WK 4-Wire Horn Strobe,Standard cd,White,Outdoor(includes plastic weatherproof back box) P2RHK-120 2-Wire Horn Strobe,High cd,Red,Outdoor, 120 V(includes plastic weatherproof back box) Wall Strobes SRK't Strobe,Standard cd,Red,Outdoor(includes plastic weatherproof back box) SRHK*t Strobe,High cd, Red,Outdoor(includes plastic weatherproof back box) SWK`t Strobe,Standard cd,White,Outdoor(includes plastic weatherproof back box) SWHK`S Strobe,High cd,White,Outdoor(includes plastic weatherproof back box) Horns HRKt Horn, Red,Outdoor(includes plastic weatherproof back box) Accessories SA-WBB Red,Metal Weatherproof Back Box SA-WBBW White,Metal Weatherproof Back Box Notes: • *Add"-P"to model number for plain housing(no"FIRE"marking on cover),e.g.,P2RK-P. t Add"-R"to model number for weatherproof replacement device(no back box included),only for use with weatherproof outdoor flush mounting plate,WTP and WTPW. "Standard cd"refers to strobes that include 15,15/75,30,75,95,110,and 115 candela settings."High cd"refers to strobes that include 135,150,177,and 185 candela settings.\ 1 When replacing standard outdoor units both the device and back box must be replaced.ilk TE ©2012 System Sensor. Y 3825 Ohio Avenue•St.Charles, IL 60174 vroductspecircaeonssubjecttochangewiu�outnotice.vistsystemsensa.com for current product information,including the latest version of this data sheet. Phone:800-SENSOR2•Fax:630-377-6495 Avos01201•3;12 .,.1..,. ,�,.,,,,,,,..,.,, 111111�1111/SON/L' 0 t Shelf Life&Storage Discharge Characteristics -- 10014.0 I I I I I I I 1 I 1 Change sary not Ambient Temperature 20°C(68°F) o 100%of capacity 13.0 - •a _ is required. _ LI; 80 r-- --__- 5°C ':''," Charging before �i C g' use is necessary 12.0 -- (41°F)- i„ to help recover 0 _ full capacity. co -- a) 603 11.0 `` _` Charge may fal to restore full To 0 35 Z' 40°C 30°C 20°C ' capacity.Do not c 10.0 0.70 - - c.t 40 (104°F) (86°F) (68°F) ` let batteries reach E 1.4 ea r this state. `m 3.5 cc,t. 0� I I 1- 9.0 Final U 0 2 4 6 8 10 12 14 16 18 20 Voltage 7.0 Standing Period(Months) 8.0 , 1 I 14 1.2 2.4 6 12 24 36 48 1 2 4 6 8 10 20 4 0 Discharge Time vs. Discharge Current I i min • I- h ►I Discharge Time 20 15 \ 10 \\ Life Characteristics in Stand-By Use \ Ambient Temperature 20°C(68'F) IM 5 Final 0 100 F E VoltageY ;" ,s d 2 iZ 10.5V VA •' 80 10.2V \ 0 60 o + 1 \ Float Charging Voltage 6 0 40 2.25-2.30 V/Cell 9.6V \\ 30 \ o 20 m _ c \ 0 8 9.OV 0 1 2 3 4 10 \ 40°C(104°F) - 20°C (68°F) Years 0°C (32°F) 5 8.1V I Life Characteristics in Cyclic Use 0.35 0.70 1.4 3.5 7.0 14 120 Discharge Current(A) 100 'I Charging 80 At Cycle Applications:Limit initial current to 2.1A.Charge until battery voltage co (under charge)reaches 14.4 to 14.7 volts at 68°F(20°C).Hold at 14.4 to 14.7 R 60 Discharge Discharge Discharge volts until current drops to under 70mA.Battery is fully charged under these Depth 100% Depth 501. Depth 30i conditions,and charger should be disconnected or switched to"float"voltage. 0 40 e 1.Discharge Current 0.2C(Final Voltage 1.7V/Cell) "Float"or"Stand-By"Service:Hold battery across constant voltage source of m 20 2.Charge Current:0.1C I I I 13.5 to 13.8 volts continuously.When held at this voltage,the battery will seek its tY 3.Ambient Temperature:20°C to 25°C(68°F to 77°F) own current level and maintain itself in a fully charged condition. 0 I I I 0 200 400 600 800 1000 1200 Note:Due to the self-discharge characteristics of this type of battery,it is Number of Cycles imperative that they be charged within 6 months of storage,otherwise permanent loss of capacity might occur as a result of sulfation. Chargers Further Information Power-Sonic offers a wide range of chargers suitable for batteries up to 100AH. Please refer to our website www.power-sonic.com for a complete range of useful Please refer to the Charger Selection Guide in our specification sheets for"C-Series downloads,such as product catalogs,material safety data sheets(MSDS),ISO Sv tch Mode Chargers"and"Transformer Type A and F Series".Please contact our certification,etc.. Technical department for advice if you have difficulty in locating suitable models. Contact Information www.power-sonic.com DOMESTIC SALES CUSTOMER SERVICE TECHNICAL SUPPORT INTERNATIONAL SALES Tel:+1-619-661-2020 Tel:+1-619-661-2030 Tel:+1-619-661-2020 Tel:+1-650-364-5001 Fax:+1-619-661-3650 Fax:+1-619-661-3648 Fax:+1-619-661-3648 Fax:+1-650-366-3662 national-sales@powersonic.com customerservice@power-sonic.com support@power-sonic.com intemational-sales@power-sonic.com CORPORATE OFFICE • 7550 Panasonic Way • San Diego,CA 92154 • USA •Tel:+1-619-661-2020 • Fax:+1-619-661-3650 0211 1M ©2011.Power-Sonic Corporation.All rights reserved.At trademarks are the property of their respective owners.