Loading...
Plans (259) • LEGEND \Or''' 11430 Southwest Viewmont Lane INV INVERTER&DC DISCONNECT BLUE RAVEN SUB (E) SUBPANEL 72'-3" LC (N) LOAD CENTER 1220 S.630 E STE.430 AMERICAN FORK,UT 84003 AC AC DISCONNECT 800-377-4480 WV W.BLUERAVENSOLAR.COM M UTILITY METER!SERVICE PANEL CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF JBANYONE EXCEPT JUNCTION BOX N BLUERAVENSOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE C COMBINER BOX RECIPIENTS ORGANIZATION, EXCEPT IN CONNEC TION WITH THE SALE AND USE OF THE RESPECTIVE PV PV REVENUE METER EQUIPMENT,WITHOUT THE FRONT OF HOME WRITTEN PERMISSION OF BLUERAVENSOLAR LLC. j FIRE SETBACK 1 \ / ar,/ 1 EMT CONDUIT RUN W W O (TO BE DETERMINED IN FIELD) Ur Z F_ O d' Z D C) < 0i .'0 c PV WIRE STRING Q C7 d- Q W M AC I H C`') 0 (§ C°Z \ / (-11--- OM MSP M I PROPERTY LINE U O 0 ❑ w U U m ❑ - SCALE: 1116"= 1'-0" 0 0' 4' 8' 16' 32' ° 1:1119'-10" a. _ 119'-7" ❑ a 0 ❑ o — — CD RI J `,wwwwzmzzzzmizzziwywrzmizmzzmzzizmzz/mmzmizmiwzzzzzrnmzz, 'C' 0 0 0 ❑ 0 0 0 0 o Z CO a J 0 CU N LLI Nti 0 Et OF a ac a ac a a a JB _c cp W U ROOF ATTACHMENTS SHALL BE SPACED ac a a a ac o 0 a ;v o H NO GREATER THAN 24" ON CENTER IN AZIMUTH:182° kt ac ac a W LT M 1 CO Y ANY DIRECTION WHERE LOCATED PITCH:25° - E U CN WITHIN 3' OF A ROOF EDGE, HIP, EAVE, TSRF:93% MP1 u) — i= OR RIDGE OSSC 3111.5.3 ITEM 3.44 AZIMUTH:182° DRAWING BY PITCH:18° Isaiah Young TSRF:94% DATE May 29, 2018 74'-1 0" PROJECT NUMBER DC SYSTEM SIZE: 13.92 kW DC 51833588 ROOF TYPE: Comp Shingle SHEET NAME (48) Sunmodule Plus SW 290M Black PROPERTY PLAN Enphase IQ6-60-2-US,----INVERTER PAGE NUMBER REVISION PV2 0 LEGEND \le° INV INVERTER 8.DC DISCONNECT BLUE RAVEN N SUB (E) SUBPANEL LC (N) LOAD CENTER 1220 S.630 E STE.430 AMERICAN FORK,UT 84003 AC AC DISCONNECT 800-377-4480 FRONT OF HOME WWW.BLUERAVENSOLAR.COM M UTILITY METER/SERVICE PANEL CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF JB JUNCTION BOX ANYONE EXCEPT BLUERAVENSOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR IN N / PART TO OTHERS OUTSIDE C COMBINER BOX RECIPIENTS ORGANIZATION. EXCEPT IN CONNEC TION WITH THE SALE AND USE OF THE RESPECTIVE PV PV REVENUE METER EQUIPMENT,WITHOUT THE WRITTEN PERMISSION OF ri��i� BLUERAVENSOLAR LLC. d FIRE SETBACK 1 LU � 0x00 SKYLIGHT ❑ EMT CONDUIT RUNO c I (TO BE DETERMINED IN FIELD) 0 Z H O D C6 0 a 1- Z C6 Q ti AC PV WIRE STRING Q 0 c LU p7 IL MSP M i � Ico Z � cD ° I PROPERTY LINE U 0 W O m ❑ — SCALE: 3/32"= 1.-0" Q �' 4' 6' 1 G' N O El La. ❑ o ❑ a) C co AC DISCO WON'T EXCEED 10' o - AWAY FROM THE UTILITY METER ° z EE O a) N LU j 2 5 c N //////////////////////////////////////////////////Y////////////////////////////l//l/A iii a' ❑ L 3 0 ❑ ❑ ❑ ❑ ❑ U I- co co N Ifc Igc Itc Ofc ffc aic I2fc Ifc Iic _ �_ 0 co J B afc efc Ofc Pic Ifc Iffc Inc U) W .— I= I� r- 0 o DRAWING BY OfC afC iffc L2fc fffc a§C o rafc INC JB Isaiah Young DATE MP2 May 29, 2018 AZIMUTH:182° Of° OfC El0 eiC IffC Vic PITCH:25° PROJECT NUMBER DC SYSTEM SIZE: 13.92 kW DC TSRF:93% MP1 51833588 ROOF TYPE: Comp Shingle AZIMUTH:182° SHEET NAME PITCH:18° SITE PLAN (48) Sunmodule Plus SW 290M Black TSRF:94% Enphase IQ6-60-2-US,----INVERTER PAGE NUMBER REVISION PV3 0 PV ARRAY STRUCTURAL CRITERIA ROOF ATTACHMENTS SHALL BE SPACED NO GREATER THAN 24" ON • • PV MODULE PV MODULE COUNT: 48 MODULES CENTER IN ANY DIRECTION WHERE Iron Ridge XR10 PV RAIL LOCATED WITHIN 3'OF A ROOF BLUE # OF ATTACHMENT POINTS: 100 t1VE� EDGE, HIP, EAVE, OR RIDGE OSSC ARRAY AREA: Module Count X 17.51ft2= 840.5ft2 3111.5.3 ITEM 3.44 .+ g N N N 1'-11" 48"MAX."-- ---f ROOF AREA: 3855.7ft2 MAX. 1220 S.630 E STE.430 ARRAY DETAIL, FRONT VIEW AMERICAN FORK,UT 84003 cYo OF ARRAY/ROOF: 21.8% Scale: 3/8" = 1'-0" 800-377-4480 VVVVVV BLUERAVENSOLAR COM ARRAY WEIGHT: Module Count x 50Ibs = 2400.OIbs ROOF TYPE: Comp Shingle DISTRIBUTED LOAD: Array Weight=Array Area = 2.86 lbs/ft2 ROOF FRAMING TYPE: Manufactured Truss CHOEREIN CONTAINED INFORHALL MATION BE RAFTER OR TOP CHORD SIZE: 2x4 USED FOR THE BENEFIT OF POINT LOAD: Array Weight=Attachments =24.Olbslattachment RAFTER OR TOP CHORD SPACING: 24"O.C. Iron Ridge XR10 PV RAIL ANYONE EXCEPT CEILING JOIST OR BOTTOM CHORD SIZE: 2x4 BLUERAVENSOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR IN ASCE 7-10 WIND SPEED: 110 MPH EXPOSURE CATEGORY: C CEILING JOIST OR BOTTOM CHORD SPACING: 24"O.C• PART TO OTHERS OUTSIDE '1' RECIPIENTS ORGANIZATION; SITE E CRITERIA 10"MIN - FlashFoot2 EXCEPT IN CONNEC TION WITH THE GROUND SNOW LOAD: 10 PSF SEISMIC DESIGN CATEGORY: D / '/ SALE AND USE OF THE RESPECTIVE 1'-4" ,lµ-- EQUIPMENT,WITHOUT THE AI OF IRONRIDGE STOPPER SLEEVE IRONRIDGE UNIVERSAL MAX WRITTEN PERMISSION C, 10"MIN - '` BLUERAVENSOLAR LLC. IRONRIDGE UNIVERSAL FASTENING OBJECT 1'-4" 2'-8"MIN App FASTENING OBJECT 1 PV MODULE FRAME PV MODULE FRAME MAX �µ – 3'-10"MAX 18 Z 0 O _�O s IRONRIDGE RAIL IRONRIDGE RAIL z rn g 9 ti 1 .� 2'-8"MIN - d 0 d' Er W co O... \ 1c: 3'-10"MAX 2 r z Li o ARRAY DETAIL, SIDE VIEW W 0 °' O m 00 Scale: 3/8" = 1-0" - C O DETAIL, END CLAMP FRONT O DETAIL, MID CLAMP FRONT 0 Scale: 6"= 1'-0" Scale: 6"= 1'-0" a Sunmodule Plus SW 290M Black PV MODULE PV MODULE(BEHIND TRIM RAIL) Iron Ridge XR10 PV TRIM RAIL N C Iron Ridge XR10 PV IRONRIDGE al s RAIL g 1,-11" N N - N o i ,MAX. 48"MAX." Z co 0 W (E) ROOF ARRAY DETAIL, FRONT VIEW Q > r N MEMBRANE" Scale: 3/8" = 1 -0" cG N c 4 , I ROOF TYPE: Comp Shingle iz 0 2 0 ROOF FRAMING TYPE: Manufactured Truss Iron Ridge XR10 PV FRAME 0 m 0 RAFTER OR TOP CHORD SIZE: 2x4 z a cn 0 CO RAFTER OR TOP CHORD SPACING: 24"O.C. — LLL > Y CEILING JOIST OR BOTTOM CHORD SIZE: 2x4 0 CO N CEILING JOIST OR BOTTOM CHORD SPACING: 24"0.C. I-- E `t 1 IRONRIDGE CO W H 0 FLASHFOOT FlashFoot2 2.5" MIN. 5,2 - ASSEMBLY DRAWING BY EMBED. Isaiah Young FLASHING --- ‘.............01111111111°.-- , DATE 5/16"STAINLESS STEEL LAG BOLT ',�.;� MODULE 18° May 29, 2018 WITH 2-1/2"MIN. EMBEDMENT WIDTH \ . AND FLAT WASHER ( '44/1PROJECT NUMBER 51833588 (E)BUILDING STRUCTURE ARRAY DETAIL, SIDE VIEW SHEET NAME DETAIL, STANDOFF Scale: 3/8" = 1'-0" EQUIP. DETAIL O , PAGE NUMBER REVISION Scale: 3„ = 1 -O„ PV4 0 • MODULE SPECIFICATIONS Sunmodule Plus SW 290M Black DESIGN LOCATION AND TEMPERATURES CONDUCTOR SIZE CALCULATIONS RATED POWER(STC) 290 W TEMPERATURE DATA SOURCE ASHRAE 0.4%HIGH TEMP MICROINVERTER TO MAX.SHORT CIRCUIT CURRRENT(ISC)= 15.4 A DC MODULE VOC 39.9 V DC STATE Oregon JUNCTION BOX MAX. CURRENT(ISC X1.25)= 19.2 A DC MODULE VMP 31.4 V DC CITY Tigard CONDUCTOR(TC-ER,(90°C))= 12 AWG BLUE RAVEN MODULE IMP 9.33 A DC WEATHER STATION PORTLAND INTERNATIONAL AP CONDUCTOR RATING= 30 A MODULE ISC 9.97 A DC ASHRAE EXTREME LOW TEMP(°C) -6 AMB.TEMP.AMP.CORRECTION= 0.91 VOC CORRECTION(%/°C) -0.31 °C ASHRAE 0.4%HIGH TEMP(°C) 36 ADJUSTED AMP.= 27.3 > 19.2 1220 S.630E STE.430 AMERICAN FORK,UT 84003 VMP CORRECTION(%/°C) -0.44°C JUNCTION BOX TO MAX.SHORT CIRCUIT CURRRENT(ISC)= 15.4 A DC 800-377-4480 SERIES FUSE RATING 25 A DC SYSTEM ELECTRICAL SPECIFICATIONS CR 1 CIR 2 CIR 3 CIR 4 CIR 5 CIR 6 COMBINER BOX MAX.CURRENT(ISC X1.25)= 19.2 A DC WWW.BLUERAVENSOLAR.COM ADJ.MODULE VOC @ ASHRAE LOW TEMP 43.7 V DC NUMBER OF MODULES PER MPPT 16 16 16 CONDUCTOR(THWN-2, (90°C)= 10 AWG CONFIDENTIAL-THE INFORMATION ADJ.MODULE VMP @ ASHRAE 0.4%HIGH TEMP 25.5 V DC DC POWER RATING PER CIRCUIT(STC) 4640 4640 4640 CONDUCTOR RATING= 35 A HEREIN CONTAINED SHALL NOT BE - USED FOR THE BENEFIT OF TOTAL MODULE NUMBER 48 MODULES CONDUIT FILL DERATE= 1 ANYONE EXCEPT BLUERAVENSOLAR NOR SHALL IT MICROINVERTER SPECIFICATIONS Enphase IQ6-60-2-US STC RATING OF ARRAY 13920W DC AMB.TEMP.AMP.CORRECTION= 0.91 BE DISCLOSED IN WHOLE OR IN POWER POINT TRACKING(MPPT)MIN/MAX 22 - 48 V DC AC CURRENT @ MAX POWER POINT(IMP) 15.4 15.4 15.4 ADJUSTED AMP.= 31.85 > 19.2 PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION, MAXIMUM INPUT VOLTAGE 48 V DC MAX.CURRENT(IMP X 1.25) 19.2 19.2 19.2 EGC MAX.CHANNEL ISC= 19.2 A DC EXCEPT IN CONNEC TION WITH THE SALE AND USE OF THE RESPECTIVE MAXIMUM DC SHORT CIRCUIT CURRENT 15 A DC OCPD CURRENT RATING PER CIRCUIT 20 20 20 CONDUCTOR(THWN-2,(90°C))= 10 AWG EQUIPMENT,WITHOUT THE WRITTEN PERMISSION OF MAXIMUM USABLE DC INPUT POWER 330 W MAX.COMB.ARRAY AC CURRENT(IMP) 46.1 EGC CONDUCTOR RATING= 60 A BLUERAVENSOLAR LLC. MAXIMUM OUTPUT CURRENT 0.96 A AC MAX.ARRAY AC POWER 11520W AC CONDUIT FILL DERATE= 1 AC OVERCURRENT PROTECTION 20 A AMB.TEMP.AMP.CORRECTION= 0.91 W W co MAXIMUM OUTPUT POWER 240 W AC PHOTOVOLATIC MODULE MARKING(NEC 690.52) ADJUSTEDAMP.= 54 6 > 19.2 0 Z H O CEC WEIGHTED EFFICIENCY 97% NOMINAL OPERATING AC VOLTAGE 240 VAC COMBINER BOX TO INVERTER RATED AMPS= 46.1 A AC Z D rn < 0 ti NOMINAL OPERATING AC FREQUENCY 47-68 HZ AC MAIN PV OCPD MAX.CURRENT(RATED AMPS X1.25)= 57.6 A AC < 0 � W M 2 I- l[) I- LI o PHOTOVOLTAIC AC DISCONNECT OUTPUT LABEL(NEC 690.54) MAXIMUM AC POWER 240 VA AC CONDUCTOR(THWN-2,(90°C))= 6 AWG H co Z c) AC OUTPUT CURRENT 46.1 A AC MAXIMUM AC CURRENT 15.4 A AC CONDUCTOR RATING= 65 A W O O Li m NOMINAL AC VOLTAGE 240 V AC MAXIMUM OCPD RATING PER CIRCUIT 20 A AC CONDUIT FILL DEBATE= 1 AMB.TEMP.AMP.CORRECTION= 0.91 O CC ADJUSTED AMP.= 59.15 > 57.6 0_ a) C co J C GROUNDING NOTES STRANDED,AND BARE WHEN EXPOSED, USED TO PROTECT WIRE FROM SHARP EDGES 0 1. A GROUNDING ELECTRODE SYSTEM IN ACCORDANCE WITH[NEC 690-47]AND 10. EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZE ACCORDING TO[NEC 6. PHASE AND NEUTRAL CONDUCTORS SHALL BE DUAL RATED THHN/THWN-2 Z [NEC 250-50]THROUGH[NEC 250-60]SHALL BE PROVIDED. PER NEC, 690.45] AND BE A MINIMUM OF#10AWG WHEN NOT EXPOSED TO DAMAGE(#6AWG INSULATED,90°C RATED,WET AND UV RESISTANT, RATED FOR 600V 0O co W GROUNDING ELECTRODE SYSTEM OF EXISTING BUILDING MAY BE USED AND SHALL BE USED WHEN EXPOSED TO DAMAGE). 7.4-WIRE DELTA CONNECTED SYSTEMS HAVE THE PHASE WITH THE HIGHER H > C N BONDED TO AT THE SERVICE ENTRANCE. IF EXISTING SYSTEM IS INACCESSIBLE, 11.GROUNDING AND BONDING CONDUCTORS, IF INSULATED,SHALL BE COLOR VOLTAGE TO GROUND MARKED ORANGE OR IDENTIFIED BY OTHER EFFECTIVE MEANS. N OR INADEQUATE.OR IS ONLY METALLIC WATER PIPING,A SUPPLEMENTAL CODED GREEN(OR MARKED GREEN IF#4 AWG OR LARGER) 8.ALL SOURCE CIRCUITS SHALL HAVE INDIVIDUAL SOURCE CIRCUIT PROTECTION c GROUNDING ELECTRODE WILL BE USED AT THE INVERTER LOCATION 12. ALL CONDUIT BETWEEN THE UTILITY AC DISCONNECT AND THE POINT OF 9.VOLTAGE DROP LIMITED TO 2%FOR DC CIRCUITS AND 3%FOR AC CIRCUITS 0 D U-I 6 CONSISTING OF A UL LISTED 8 FT GROUND ROD WITH ACORN CLAMP. CONNECTION SHALL HAVE GROUNDED BUSHINGS AT BOTH ENDS. 10. NEGATIVE GROUNDED SYSTEMS DC CONDUCTORS SHALL BE COLOR CODED AS O Cl) O (/)2. GROUNDING ELECTRODE CONDUCTORS SHALL BE NO LESS THAN#8 AWG AND 13.SYSTEM GEC SIZED ACCORDING TO[NEC 690.47],[NEC TABLE 250.66], DC FOLLOWS:DC POSITIVE-RED(OR MARKED RED),DC NEGATIVE-GREY(OR MARKED Z LL NO GREATER THAN#6 AWG COPPER AND BONDED TO THE EXISTING GROUNDING SYSTEM GEC SIZED ACCORDING TO[NEC 250.166],MINIMUM#8AWG WHEN GREY) W CO 2 ELECTRODE TO PROVIDE FOR A COMPLETE SYSTEM. INSULATED,#6AWG WHEN EXPOSED TO DAMAGE. 11. POSITIVE GROUNDED SYSTEMS DC CONDUCTORS COLOR CODED: ~ E •1' cm (.),..‘ (y)(3). 3. PV SYSTEM SHALL BE GROUNDED IN ACCORDANCE TO[NEC 250.21],[NEC TABLE 14. EXPOSED NON-CURRENT CARRYING METAL PARTS OF MODULE FRAMES. DC POSITIVE-GREY(OR MARKED GREY),DC NEGATIVE-BLACK(OR MARKED BLACK) W - I- 250.122], AND ALL METAL PARTS OR MODULE FRAMES ACCORDING TO[NEC EQUIPMENTS,AND CONDUCTOR ENCLOSURES SHALL BE GROUNDED IN 12.AC CONDUCTORS>4AWG COLOR CODED OR MARKED: DRAWING BY 690.46]. ACCORDANCE WITH 250.134 OR 250.136(A)REGARDLESS OF VOLTAGE. PHASE A OR L1-BLACK,PHASE B OR L2-RED, PHASE C OR L3-BLUE, NEUTRAL- Isaiah Young 4. MODULE SOURCE CIRCUITS SHALL BE GROUNDED IN ACCORDANCE TO[NEC WHITE/GRAY 690.42]. WIRING&CONDUIT NOTES *USE-2 IS NOT INDOOR RATED BUT PV CABLE IS RATED THWN/THWN-2 AND MAY 5. THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT 1.ALL CONDUIT SIZES AND TYPES,SHALL BE LISTED FOR ITS PURPOSE AND BE USED INSIDE DATE THE REMOVAL OF A MODULE DOES NOT INTERRUPT A GROUNDED CONDUCTOR APPROVED FOR THE SITE APPLICATIONS ""USE-2 IS AVAILABLE AS UV WHITE May 29, 2018 TO ANOTHER MODULE. 2.ALL PV CABLES AND HOMERUN WIRES BE TYPE USE-2,AND SINGLE-CONDUCTOR 13. IF CONDUIT DETERMINED TO BE RAN THROUGH ATTIC IN FIELD THEN CONDUIT WILL 6. EACH MODULE WILL BE GROUNDED USING THE SUPPLIED CONNECTIONS POINTS CABLE LISTED AND IDENTIFIED AS PV WIRE,TYPE TC-ER,OR EQUIVALENT;ROUTED TO BE EITHER EMT,FMC,OR MC CABLE IF DC CURRENT COMPLYING WITH NEC 690.31,NEC PROJECT NUMBER IDENTIFIED IN THE MANUFACTURERS INSTALLATION INSTRUCTIONS. SOURCE CIRCUIT COMBINER BOXES AS REQUIRED 250.118(10). DISCONNECTING MEANS SHALL COMPLY WITH 690.13 AND 690.15 51833588 7. ENCLOSURES SHALL BE PROPERLY PREPARED WITH REMOVAL OF PAINT/FINISH 3.ALL CONDUCTORS AND OCPD SIZES AND TYPES SPECIFIED ACCORDING TO[NEC 14.CONDUIT RAN THROUGH ATTIC WILL BE AT LEAST 18"BELOW ROOF SURFACE AS APPROPRIATE WHEN GROUNDING EQUIPMENT WITH TERMINATION 690.8] FOR MULTIPLE CONDUCTORS COMPLYING WITH NEC 230.6(4)AND SECURED NO GREATER THAN 6'APART PER NEC SHEET NAME GROUNDING LUGS. 4.ALL PV DC CONDUCTORS IN CONDUIT EXPOSED TO SUNLIGHT SHALL BE 330.30(B). ELEC. CALCS. 8. GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE,AND DERATED ACCORDING TO[NEC TABLE 310.15(B)(2)(a), NEC TABLE 310.15(B)(3)(a), GROUNDING DEVISES EXPOSED TO THE ELEMENTS SHALL BE RATED FOR DIRECT &NEC 310.15(B)(3)(c)] PAGE NUMBER REVISION BURIAL. 5. EXPOSED ROOF PV DC CONDUCTORS SHALL BE USE-2,90°C RATED,WET AND UV PV6 0 9. GROUNDING AND BONDING CONDUCTORS SHALL BE COPPER,SOLID OR RESISTANT,AND UL LISTED RATED FOR 600V,UV RATED SPIRAL WRAP SHALL BE CAUTION BLUE RAVEN POWER TO THIS BUILDING IS ALSO SUPPLIED FROM ROOF MOUNTED 1220S 630E STE 430 SOLAR ARRAYS WITH SAFETY DISCONNECTS AS SHOWN: AMERICAN FORK UT 84003 800-377-4480 WWW.BLUERAVENSOLAR.COM CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF N MAIN DISTRIBUTION ANYONE EXCEPT BLUERAVENSOLAR NOR SHALL IT FRONT OF HOME / UTILITY DISCONNECT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION, EXCEPT IN CONNEC TION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT,WITHOUT THE WRITTEN PERMISSION OF BLUERAVENSOLARLLC. co o jA111400 RAPID SHUTDOWN AC a0 DISCONNECT SWITCH z v co < M 000® � F cO ~ moo CCCICCCCCCm CCCCCCC U O p co =CC= CC CCCCCCe u U 0 m rOBOO o `� a PV ARRAY 11430 Southwest Viewmont Lane, Tigard, Oregon 97223 Ct 0 Z E DIRECTORY 0 N W PERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION OFQ N THE SERVICE DISCONNECTING MEANS AND THE PHOTOVOLTAIC cu SYSTEM DISCONNECTING. p w o WHERE THE INVERTERS ARE REMOTELY LOCATED FROM EACH Z o o co OTHER, A DIRECTORY I SHALL BE INSTALLED AT EACH DC PV w o j ct N SYSTEM DISCONNECTING MEANS, AT EACH AC DISCONNECTING �— E � �' MEANS, AND AT THE MAIN SERVICE DISCONNECTING MEANS Cl) W r SHOWING THE LOCATION OF ALL AC AND DC PV SYSTEM DRAWING BY DISCONNECTING MEANS IN THE BUILDING. Isaiah Young ALTERNATE POWER SOURCE PLACARD SHALL BE PLASTIC ENGRAVE DATE IN CONTRASTING COLOR TO THE PLAQUE. THIS PLAQUE WILL BE May 29, 2018 ATTACHED USING AN APPROVED METHOD. IF EXPOSED TO PROJECT NUMBER SUNLIGHT, IT SHALL BE UV RESISTANT. ALL PLAQUES AND SIGNAGE 51833588 WILL BE INSTALLED AS REQUIRED BY THE NEC. [NEC 690.56(B)&(C)] [NEC 705.10]. SHEET NAME PLACARD PAGE NUMBER REVISION PV10 0 4lAtrr'''' BLUE RAVEN Enphase IQ 6 and IQ 6+ Microinverters Enphase Microinverters 1220 S.630 E STE.430 AMERICAN FORK,UT 84003 INPUT DATA(DC) 1Q6-60-2-US / 106-60-6-US IQ6PLUS-72-2-US I 106PLUS:72-6-US Commonly used module pairings' 195 W-330 W+ 235 W-400 W+ - 800-377-4480 Module compatibility 60-cell PV modules only 60-cell and 72-cell PV modules VVWW BLUERAVENSOLAR COM Maximum input DC voltage 48V 62 V CONFIDENTIAL-THE INFORMATION Peak power tracking voltage 27 V 37 V 27 V-45 V HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF Operating range 16 V-48V 16V-62 V The high-powered smart grid ready ANYONE EXCEPT Enphase Enphase IQ 6 Micro"and Enphase IQ 6+Micro- Min/Max start voltage 22 V/48 V 22 V 162 V Max DC short circuit current(module Ise) 15 A 15 A BLUERAVENSOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE IQ6 and IQ 6+ dramatically simplify the installation process while Overvoltage class DC port II II RECIPIENTS ORGANIZATION. achieving the highest efficiency for module-level DC port beCkfeed under single fault OA 04 EXCEPT IN CONNEC TION WITH THE Microinverters power electronics, PV array configuration 1 x 1 ungrounded array:No additioA nal DC side protectibranch on required; SALE AND USE OF THE RESPECTIVE AC side protection requires max 20per circuit EQUIPMENT.WITHOUT THE WRITTEN PERMISSION OF Part of the Enphase IQ System,the IQ 6 and OUTPUT DATA(AC) IQ 6 Microinverter 106+Micrainverter BLUERAVENSOLAR LLC Peak output power 240 VA 290 VA IQ 6+Micro integrate seamlessly with the Enphase Maximum continuous output power 230 VA 280 VA L >- O L 2 IQ Envoy",Enphase Q Aggregator",Enphase IQ Nominal(Iii•L)voltage/range° 240 V/211-264 V 208V/183-229 V 240 V/211-264 V 208 V/183-229V in LU 1 "..5 Battery ,and the Enphase Enlighten'monitoring Maximum continuous output current 096A 111 A 117A 135A 0 .5._ F._ c6 0 Nominal frequency 6014z 6014z < 0 N. and analysis software, Z a) < (i) 1 - Extended frequency range 47•68 Hz 47-68 Hz < 0 I. Z C2. The IQ 6 and IQ 6+Micro extend the reliability Power factor at rated power 1.0 1.0 2 1-- Lo I— LU c..) m Maximuunits per 20 A(L-L)branch circuit 16(240 VAC) 13(240 VAC) standards set forth by previous generations andE-- 0 m 0 co 14(208 VAC) 11(208 VAC) (—) 0 CK undergo over a million hours of power-on testing, Overvoltege class AC port 01 ID ll.J ° enabling Enphase to provide an industry-leading AC port backfeed under single fault 0 A 0 A 0 D warranty of up to 25 years, Power factor(adjustable) 0.7 leading..,0/7 lagging 01 leading_.0.7 lagging EFFICIENCY @240 V @208 V @240 V @208 V . , . . . ... , • CEC weighted efficiency 970% 970% 970% 97.0% MECHANICAL DATA Easy to Install Ambient temperature range 40°C to+65°C Lightweight and simple Relative humidity range 4%to 100%(condensing) I • improved two-wire cabling th • Connector type Dimensions(WxHxD) MC4(-2-US)or Amphenol H4 UTX(-5-US) Faster installation wi 219 mm x 191 mm x 37,9 rnm(without bracket) Built-in rapid shutdown compliant(NEC 2014&2017) Weight 1.29 kg(2.84 lbs) . . Cooling Natural convection-No fans Productive and Reliable, Approved for wet locations Yes . Pollution degree P03 • Optimized for high powered 60-cell and Enclosure Class II double insulated 72-cell*modules Environmental category/UV exposure rating NEMA Type 6/outdoor • More than a million hours of testing FEATURES • Class II double-insulated enclosure Communication Power line ' I • UL listed Monitoring Enlighten Manager and MyEnlighten monitoring options Compatible with Eraphaselp Envoy Disconnecting means The AC and DC connectors have been evaluated and approved by W..for use as the load break Smart Grid Ready disconnect required by NEC 690, Compliance CA Rule 21(UL 1741-SA) • Complies with fixed power factor,voltage and UL 62109-1,UL1741/IEEE1547,FCC Part 15 Class 8, ICES-0003 Class 8, frequency ride-through requirements CAN/CSA-C22.2 NO.1071-01 Remotely updates to respond to changing This product is UL Listed as PV Rapid Shut Down Equipment and conforms with NEC-2014 and • grid requirements NEC-2017 section 690.12 and C22.1-2015 Rule 64-218 Rapid Shutdown of PV Systems,for AC and DC conductors,when installed according manufacturer's instructions. • Configurable for varying grid profiles • Meets CA Rule 21 (UL 1741-5A) 1.No enforced DC/AC ratio.See the compatibility calculator at enphaSe,com/en-us/support/rnodule-compatibility. 41) 2.Nominal voltage range can be extended beyond nominal if required by the utility. CERT FIFT. *The ID 64 Micro is required to support 72-cell modules To learn more about Enphase offerings,visit enphase.com ' e ENPHASE SO 2018 Eng gage Energy AU rights reserved AU erode-narks or brands used are the property of Enpdase Eriergy,tar ENPHASE. To learn more about Enphase offerings,visit enphase.com 44..." . '2018 01 1 0 So, SHEET NAME DATA SHEET PAGE NUMBER REVISION DS 0