Correspondence (19) Dan Nelson - Albertsons Remodel of Store #565 in Tigard - Mechanical Valuation Figures _ Page 1,
From: "Randy Syphus" <rsyphus@id.tait.com>
To: <dann @tigard- or.gov>
Date: 9/26/2007 1:14:33 PM
Subject: Albertsons Remodel of Store #565 in Tigard - Mechanical Valuation Figures
Dan;
Per your request I am providing the estimated valuation of the scope of the
Mechanical work included in this remodel. The following represents
information I received from our Mechanical Engineering Consultant - DC
Engineering. Should you desire further information, you may contact Tom
Wolgamot, or Travis Miller at (406) 829 -8828.
1. Grease Hood with Ansul System and Exhaust Fan -
$20,000
2. Duct Free split system -
$2,500
3. Reconfiguration of ductwork over the frozen food aisles
(left side of store) - $3,000
4. Mechanical work required for installing the new Generator -
$1,000
Subtotal $26,500
OH&
P 10% $2,650
Total Valuation
$29,150 •
Should you require any further information, I would be happy to accommodate.
Thanks for your timely review of our project.
Randall P. Syphus
Project Manager
Tait & Associates
208 -345 -2428
208 -345 -3757 fax
rsyphus @id.tait.com
•
CC: <bliquin @id.tait.com >, "Thomas, David P. (Boise)'"
<David.Thomas2 @supervalu.com >, "'Briggs, David" <David.Briggs @supervalu.com>
2-9 I` _1
g 25) c00 VA VAT D a�F c2�7
•
... • • • .. •.. •..
: .
• • : • • •• •• •
City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223 •
::
September 26, 2007 •••
.
• RE: MECHANICAL -
: •;
Project Information • • •• • •. . + • • •
• . . . •
• ••• •
Building Permit: MEC2007 -00528 Construction Type: 3 -N
Tenant Name: Albertsons Occupancy Type: M
Address: 16200 SW Pacific Hwy. Occupant Load: 1338
Area: NA Stories: 1
The plan review was performed under the State of Oregon Mechanical Specialty Code
(OMSC) 2007 edition; and the State of Oregon Fire Code (OFC) 2007 edition. The
submitted plans are approved subject to the following.
1. Ductwork shall be supported in accordance with Sheet Metal & Air Conditioning
Contractors National Association, Inc. (SMACNA)
2. Each appliance shall be provided with a shutoff valve separate from the
appliance. The shutoff valve shall be located in the same room and within six feet
of the appliance served. Access shall be provided to the shutoff valve. C409.5
OMSC
3. Equipment and appliances regulated by this code requiring electrical connections
shall have a positive means of disconnect in accordance with the Electrical Code.
301.7 OMSC
4. Permanent equipment supported by the structure, 400 lbs and over, shall have
their attachments designed in accordance with the Building Code. 301.16 OMSC
5. Appliances shall be accessible for inspection, service, repair or replacement
without removal of permanent construction. 306.1 OMSC
6. Manufacturer's installation instructions shall be available on the jobsite at the
time of inspection. 304.1 OMSC
7. Condensate from cooling coils or evaporators shall be collected and discharged
to an approved plumbing fixture or disposal area. 307.1 OMSC
8. Smoke detectors shall be installed in return air systems with a design
capacity greater than 2000 cfm. Upon activation, the smoke detector shall
shut down the air distribution system. Smoke detectors shall be connected
to a fire alarm system and shall activate an audible and visible alarm at a
constantly attended location. 606.2, 606.4 & 606.4.1 OMSC
Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772
• •: • • • • . • . •
. • • • • • • • • . • • • •
• .
. • • • •• •• •
.. • • : • : • •
9. Suspended-type unit heaters shall be supported by non - combustible elgr ent •• • . .
that are desned and constructed to accommodate the weight and d n�rfiik �•. •
loads and shall be sway braced. 920.2 OMSC 9 • • • • • • •
10. Prefabricated refrigeration panels installed in Oregon shall bear one Qrtton; ••� ••: •�• •:.
insignia of compliance located on the exterior side of the panel located rje�r�s•
the door prior to final inspection. • • • • • •
11. Every refrigerant- containing part of every system that is erected on the premises
shall be tested and proved tight after complete installation, and before operation.
Tests shall include both the high and low- pressure sides of each system.
12.A Performance Test shall be conducted upon the type 1 hood at completion and
before final approval of the installation of the ventilation system. The
performance test shall verify the rate of airflow to be in compliance with the
approved plans. 507.17 OMSC
The exhaust and make -up air system shall be electronically interlocked to ensure
that the make -up air is provided whenever the exhaust system is in operation.
508.1 OMSC
An automatic fire suppression system shall be provided to protect the surface of
the heat - processing appliances and the exhaust system serving the appliances.
509.2 OMSC
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp,
shall be maintained on the jobsite. The plans shall be available to the Building Division
inspectors throughout all phases of construction. 106.4.2 OSSC
Premises Identification: Approved numbers or addresses shall be provided for all new
buildings in such a position as to be plainly visible and legible from the street or road
fronting the property.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City
of Tigard in tracking and processing the documents.
Respectfull
0 1 - f 40:00
an Nelson,
Senior Plans Examiner