Correspondence (13) t-1Ee g 8'o g7y g//508 4►!.�
CONSOLIDATED FIRE AND RESCUE
.4 `! Washington County Fire District No. 1
' City of Beaverton Fire Department
Y P
; Z 3 ` Tualatin Fire District
`mss, .;ra oA
FIRE MARSHALS OFFICE
August 11, 1988
•
ASI Heating and Air Conditioning
17555 S.W. 65th Avenue
Lake Oswego, Oregon 97035
Re: Washington Federal Savings
16200 S.W. Pacific Hwy.
Gentlemen:
A fire and life safety plan review was conducted on the above captioned
project for compliance with the 1985 editions of the Uniform Building Code
(UBC), Uniform Mechanical Code (UMC). and Uniform Fire Code (UFC) as amended
by Tualatin Rural Fire Protection District's Ordinance 86 -5.
Mechanical plans for the above captioned project are conditionally approved
subject to the following items:
1. Automatic Shutdown: Where handling equipment exceeds 2,000 cfm per
minute, 'automatic shutdown upon detection of smoke shall be installed.
2. Approved Plans on Job Site: One set of approved plans bearing the
stamps of the Tigard Building Department and this office must be
maintained on the project site throughout all phases of construction
and must be made available to building and fire inspectors for
reference during required construction inspections. (UBC Sec. 303)
3. Inspections Required: Inspection and approval of construction by a
representative of this office is required: (a) prior to the cover of
any new framing elements following the installation of all utility
runs which will be concealed within wall and partition cavities; (b)
upon completion of construction and prior to occupancy of the tenant
space. (UBC Sec. 305)
SPECIAL NOTICE:
• DEVIATIONS FROM THE SUBMITTED AND HEREBY CONDITIONALLY APPROVED PLANS DURING
THE COURSE OF CONSTRUCTION, EXCLUSIVE OF THOSE NECESSARY TO COMPLY WITH FIRE
SAFETY REQUIREMENTS AS LISTED HEREIN, ARE PROHIBITED WITHOUT THE WRITTEN
AUTHORIZATION OF THE WASHINGTON COUNTY BUILDING DEPARTMENT AND THIS OFFICE.
4755 S.W. Griffith Drive • P.O. Box 4755 • Beaverton, Oregon 97076 • (503) 5 -2469
ASI Heating and Air Conditioning
August 11, 1988
Page 2
If I can be of any further assistance to you, please feel free to contact me
at 526 -2502.
Sincerely,
Gene Birchill
Deputy Fire Marshal
GB:kw
cc: Tigard Building Department (///
District Inspectors