Loading...
Plans (50) -- -1. .. •... COSCO RECE IVED •:••••••: OCT 2520 • • •• • • Fire Protectior, ' DI VISION FIRE PROTECTION SYSTEMS Submittal Brochure FOR: Albertson's #565 16200 SW Pacific Hwy. Tigard, OR. COSCO PROJECT NUMBER 24PS -7026 CONTRACT WITH: CFC 5775 Jean Road Suite# 105 Lake Oswego, OR. 97035 ,- ,. . Bulletin 155 Rev.0 ... ® Model F1 -30 CO 300 psi (20,7 bar) Rated 0 Standard Response cri cri Sprinklers Model F1 -300 Standard Response Sprinkler Sprinkler Types • Upright • Pendent • Recessed Pendent Listings & Approvals , - _ 1. Listed by Underwriters Laboratories, Inc. and Certified for Canada (cULus) Upright 2. NYC MEA 258 -93 -E UL Listing Category Sprinklers, Automatic & Open (VNIV) 4 Product Description Reliable Models F1 -300 Upright, Pendent and Recessed Pendent Sprinklers are high pressure rated automatic sprinklers which can handle a maximum 4:,-,..- � • service pressure of 300 psi (20,7 bar). The Model F1 -300 glass bulb sprinkler combines durability with the attractive low profile of a decorative Pendent sprinkler. Whether installed on exposed piping or below an office ceiling, it is functional and attractive. The Model Fl Recessed Escutcheon provides convenient adjustment for Model F1 -300 Sprinklers. The _.: two-piece construction makes field installation an easy :�: and rapid task. This also allows ceiling panels to later be removed without shutting down the fire protection' system, thus facilitating maintenance of above ceiling ' "'(. services. The Models F1 -300 Upright, Pendent and Recessed --' Pendent automatic sprinklers are standard response sprinklers which utilize a 5.0mm frangible glass bulb. The glass bulb contains an accurately controlled amount of Recessed Pendent special fluid hermetically sealed inside. The other sprinkler parts are made of brass, copper or beryllium nickel. At normal temperatures, the glass bulb contains fluid in both the liquid and vapor phases. The vapor phase can be seen as a small bubble. As heat is applied, the Application liquid expands, forcing the bubble smaller and smaller as pP the liquid pressure increases. Continued heating forces The most common applications for Model F1 -300 the liquid to push out against the bulb, causing the glass sprinklers will be in fire protection systems for high rise to shatter, opening the waterway and allowing the buildings or where the pressure entering the sprinkler deflector to distribute the discharging water. system is in excess of 175 psi (12 bar). The use of these The temperature rating of the sprinkler is identified by sprinklers will provide opportunity to reduce or eliminate the color of the glass bulb. the need for pressure reducing valves. The Reliable Automatic Sprinkler Co., Inc. 525 North MacQuesten Parkway, Mount Vernon, New York 10552 Model F1 -300 Upright and Pendent Sprinklers Installation Wrench: Model D Sprinkler Wrench Installation Data: - Nominal K Factor Sprinkler Sprinkler Nominal Thread Sprinkler Identification Type Orifice Size Size US Metric Height Number (SIN) 1/2" (15mm) 1/2" NPT (R1/2) _ 5.6 80 2.2" (56mm) R5525 Upright ,/ 2 " (20mm) 3 /4" NPT (R 8.0 115 2.4" (61mm) R5522 3 'h" (15mm) ' /2" NPT (RY2) 5.6 80 2.2" (56mm) R5515 Pendent 172" (20mm) 3 4" NPT (R 8.0 115 2.4" (61mm) R5512 _ ' -- air 1,„ , ' ) 1:\ el ,...........___,,_:i„, ,;.,,,,„,„.7.v._:,.,. r ‘N. 1 - Upright Pendent Model F1 - 300 Recessed Pendent Sprinkler Installation Wrench: Model GFR1 Sprinkler Wrench Installation Data: Sprinkler Nominal Orifice Nominal K Factor Sprinkler Type Size Thread Size US Metric Sprinkler Height Number (SIN) Recessed 'h" (15mm) ' /2" NPT (R1/2) 5.6 80 2.2 "(56mm) R5515 Pendent ' / "(20mm) 3 /4" NPT (R 8.0 115 2.4 "(61mm) R5512 .--- 1 r/4 NW 1:44 1579..1 r ,5/ ON - ---- (i92 .'J !_ — a i; r ��- d, L - ,• X ,/J• BID2CYA r . ' `37e y t tMa wet ` y ncnrsr SPAM2(a UfSMM 8055 �r , n 13/10 I \‘,.,,. � K 3 /f- /((S7+VINT . = j =J.B�„• J l ra r y„J i i v A L III vs-_f f 155r00,A 1 27/3P at „xoo+a ,22^J (" When installed directly into a tee, the escutcheon adjustment will be reduced. 2. . Installation Finishes (1) Model F1-300 Sprinklers are standard response Standard Finishes: sprinklers intended for installation as specified in NFPA 13. Sprinkler Escutcheon They must be installed with the Model D Sprinkler Wrench Bronze Brass ' specifically designed by Reliable for use with these Chrome Plated Chrome Plated sprinklers. White Polyester Coated White Painted Model F1 -300 Recessed Pendent Sprinklers are to be Special Application Finishes: installed with a maximum recess of 3 /4" (19mm). The Sprinkler Escutcheon Model Fl Escutcheon illustrated is the only recessed Bright Brass (2) Bright Brass escutcheon to be used with Model F1 -300 Pendent Black Plated Black Plated Sprinklers. The use of any other recessed escutcheon will Black Paint Black Paint void all approvals and negate all warranties. Off White Off White When installing Model F1 -300 Recessed Pendent Satin Chrome, Satin Chrome I Sprinklers, use the Model GFR1 Sprinkler Wrench. Any Wax Sol ted " "" other type of wrench may damage these sprinklers. Wax Over Lead " "" Glass bulb sprinklers have orange bulb protectors to n, Other colors and finishes are available on special order. minimize bulb damage during shipping, handling and Consult factory for details. installation. REMOVE THIS PROTECTION AT THE TIME ( 200 °F (93 °C) Maximum. THE SPRINKLER SYSTEM IS PLACED IN SERVICE FOR (3) 155°F (68 °C) to 200 °F (93 °C) Rating Only. FIRE PROTECTION. Removal of the protectors before this ("212°F (100 °C) brown wax may be used on 286 °F (141 °C) time may leave the bulb vulnerable to damage. RASCO ex when maximum ceiling temperatures do not wrenches are designed to install sprinklers when covers excc d 150 °F (66°C). are in place. REMOVE PROTECTORS BY UNDOING THE CLASP BY HAND. DO NOT USE TOOLS TO REMOVE THE PROTECTORS. Ordering Information Maintenance 1. Sprinkler Pendent and Recessed 1. Sprinkler Model The Model F1 -300 Upright, 2. Sprinkler Type Pendent Sprinklers should be inspected quarterly and 3. Orifice Size the sprinkler system maintained in accordance with 4. Deflector Type • NFPA 25. Do not clean sprinklers with soap and water, 5. Temperature Rating ammonia or any other cleaning fluid. Remove any 6. S prinkler Finish - sprinkler that has been painted (other that factory 7. Escutcheon Finish (where applicable) applied) or damaged in any way. A stock of, spare sprinklers should be maintained to allow quick - replacement of damaged of operated sprinklers. Prior to Note: When Model F1 -300 Recessed Pendent sprinklers are installation, sprinklers should be maintained in the original ordered, the sprinklers and escutcheons are packaged cartons and packaging until used to minimize the separately. potential for damage to sprinklers that would cause improper operation or non - operation. Standard Temperature Ratings Sprinkler Maximum Ambient Classification Temperature Temp. Bulb °F °C °F °C Color Ordinary 135 57 100 38 Orange Ordinary 155 68 100 38 Red Intermediate 175 79 150 66 Yellow Intermediate 200 93 150 66 Green High "' 286 141 225 107 Blue • m Not available for recessed sprinklers 3. • - Reliable...For Complete Protection Reliable offers a wide selection of sprinkler components. Following are some of the many precision -made Reliable products that guard life and property from fire around the clock. • Automatic sprinklers • Deluge valves • Flush automatic sprinklers • Detector check valves • Recessed automatic sprinklers • Check valves • Concealed automatic sprinklers • Supertrol electrical system • Adjustable automatic sprinklers • Sprinkler emergency cabinets • Dry automatic sprinklers • Sprinkler wrenches • Intermediate level sprinklers • Sprinkler escutcheons and guards • Open sprinklers • Inspectors test connections • Spray nozzles • Sight drains • Alarm valves • Ball drips and drum drips • Retard chambers • Control valve seals • Dry pipe valves • Air maintenance devices • Accelerators for dry pipe valves • Air compressors • Mechanical sprinkler alarms • Pressure gauges • Electrical sprinkler alarm switches • Identification signs • Water flow detectors • Fire department connections The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 80 years, and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries. Manufactured by The Reliable Automatic Sprinkler Co., Inc. Paper Hi — elab'd (800) 431 -1588 Sales Offices (800) 848 -6051 Sales Fax (914) 668-3470 Corporate Offices Revision lines indicate updated or new data. www.reliablesprinkler.com Internet Address EG Printed in USA 8/04 P/N 9999970169 2-pcAdjustable Sprinkler Escutcheon Description Installation Specs: The two -piece adjustable Proper installation of the sprinkler escutcheon (can- sprinkler escutcheon can be opy) has been designed accomplished with tools ordi- Type:2 -pc Adjustable w/ to provide an aesthetically narily found on the job site. weep hole pleasing concealment of the The installer must make sure sprinkler piping, servicing that the reducing coupling Standard threads: the individual sprinkler head. on the drop nipple does not 1/2" or 3/4" IPS exceed 2" outside diameter. The sprinkler escutcheon The face of the coupling Material: (canopy) has a full 2" of must extend at least 1.85" .020" cold rolled steel field adjustment, making it but not more than 2.85" past possible to accommodate the finished ceiling. Turn the Standard finishes: minor irregularities in ceil- escutcheon cup onto the Chrome ing to sprinkler head loca- sprinkler threads then install Bass tion. This assures complete the sprinkler into the reduc- %Iw concealment of the ceiling ing coupling using the manu- • w ite penetration allowing only facturers sprinkler installa- Dep 1. the sprinkler to be ex- tion instructions. After the Min. 2" posed. Additionally the skirt finished ceiling is installed, Max. 3" is manufactured with two push the skirt over the cup Base coverage: raised reliefs allowing for so that it is flush against the 3.5" increased friction between ceiling. Upon system active- the two parts when installed. tion, leaks can be detected This sprinkler escutcheon by observing accumulation (canopy) is available in two of moisture at the "weep" standard thread sizes and hole. For questions: four standard finishes. 1 800 344 -1822 or fax 1 800 344 -3775 © Fire Protection Products, Inc 1989 -2007 ® AUTOMA SPRINKLERS SERIES A o FIRE SPRINKLER DRY TYPE CORPORATION PENDENT RECESSED PENDENT DESCRIPTION AND OPERATION The Globe GL Series Dry Type Pendent Sprinkler is designed for use in special applications such as freezing environments and conditions ota where sediment or foreign materials might accumulate in ordinary drop t nipples. The Globe GL Series Dry Type Pendent Sprinkler utilizes a frangible 4' glass ampule sprinkler. At the ampules rated temperature, the sprinkler` opens releasing the bulb seat, causing the inner tube assembly to move, _ , allowing spring assembly to pivot alongside the inner tube. At this time ,,, water flows through the sprinkler and is distributed by the deflector, in an ME approved discharge pattern. 1 The heart of Globe's GL Series sprinkler proven actuating assembly is M ' a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature SURFA il E SLEEVE the internal pressure within the ampule exceeds the strength of the glass MOUN & SKIRT causing the glass to shatter. This results in water discharge which is distributed in an approved pattern. ) TECHNICAL DATA it. 1 I . '` • See reverse side for Approvals and Specifications. • Temperature Ratings - 135 °F (57°C) 155 °F (68°C) 175 °F (79 °C),� 200 °F (93 °C), 286 °F (141 ° C). , , • Water Working Pressure Rating - 175 psi (12 Bars). • Factory tested hydrostatically to 500 psi (34 Bars).: , ir. • Maximum low temperature glass bulb rating is -67 °F (- 55 °C). _ . _ ._ . • Frame - bronze • Deflector - brass • Screw - brass t ■ • Bulb seat - brass • Spring - teflon coated nickel alloy I' -T- • Retainer - brass • Pin - stainless steel • Torsion spring - stainless stee • Bulb - glass with glycerin solution, 5mm • Orifice insert - brass F • 3/4" or 1" NPT • Outer tube - galvanized steel pipe • Inner tube - stainless steel EXTENDED RECESSED • SPRINKLER TEMPERATURE RATING /CLASSIFICATION and COLOR CODING CLASSIFICATION AVAILABLE SPRINKLER BULB COLOR N.F.P.A. MAXIMUM TEMPERATURES CEILING TEMPERATURE ORDINARY( 135 °F /155 °F 57°C/68 °C ORANGE/RED 100 °F 38 °C INTFRMFn , 175 °F 1200 °F 79 °C /93 °C YELLOW /GREEN 150 °F 66 °C HIGH 286 °F 141 °C BLUE 225 °F 107°C 4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658 989 - 846 -4583 • FAX 989 - 846 -9231 APRIL 2007 A -90 BULLETIN GL5679, REV. #10 A UTOMATIC SPRINKLERS GL SERIES SPECIFICATIONS NOMINAL ••K° FACTOR THREAD SIZE LENGTH FINISHES Factory Bronze 5.6 (80 metric) 3/4" or 1" NPT cULus riable to Satin Chrome'. Bright Chrome White Polyester Black Polyester 8.1 (116 metric) 1" NPT FM Variable to Lead Coated' 38" Wax Coated' Wax oler Lead' NOTE: 'Finishes available on special order, Metric conversions are approximate - Wax Coating cULus listed up to 200 °F cULus listed corrosion resistant: Polyester must be specified on order. APPROVALS STYLE SIN MODEL K FACTOR THREAD 135°F 165°F 176°F • 200°F • 286•F cULus • FM NYC • DOB SIZE 57°C 88•C 79°C 93°C 141•C MEA 101 •2•E GL5679 5.8 1" NPT X X X X X X X X PENDENT GL5680 5.8. 3/4' NPT X X X X X X - X GL8179 8.1 1° NPT X X X X X X - X 0L5679 5.6 1 °NPT X X X X X X X X RECESSED GL5680 5.6 3/4" NPT X X X X X X - X PENDENT GL8179 8.1 1 "NPT X X X X X X - X NOTE Listed for all hazards • Dry Recessed Pendent - FM Approved 155°F and 200°F only. • Dry Pendent • FM Approved 155"F, zao•F, and tea• only. IMPORTANT INSTALLATION DATA CROSS SECTIONS Globe GL Series Dry Pendent sprinklers should be installed in accordance with the requirements set forth in NFPA 13. "' ',� :,t: „ ° ,.�."; �°.. «�„ �__ .. vs -� ' These sprinklers are to be installed using a pipe wrench applied ttss ' n«°` — 'ACC a - to the outer tube. When this is not possible, the proper sprinkler I «` `' R _ ^'i. "? r- c " head wrench may be used with extreme care for lengths up to approximately 18 ". Excessive force may distort the frame thus �r• ;„ °o0 destroying the unit. I I °< . For further important installation data, please refer to our ' ` .t ". "'°' Dry Sprinkler Caution Sheet. ` ` " °� : 1 Q . ORDERING INFORMATION Ali W.. ,,:. - - j U I, «, °w SPECIFY EXTENDED PENDENT PENDENT •Quantity • Model Number •Style • Orifice • Temperature • Finishes desired ""°.N."0,:: ss` ,v a s•• 2 ^; ; .. , • Quantity - Wrenches - P/N 333010 �� " ' °' , c s: " ' Y • Quantity - Recessed Wrenches - P/N 337014 ^ i –j !!! .m . . j r, • Quantity - Protective Caps - P/N 327109 -CAP (Friction Fit = 1 = -- • Recessed) • Escutcheons desired ..•' m " A " Dimension - Distance from face of fitting to the finished ', « ..� _,�� , ceiling line regardless of escutcheon used L T i GGLOBE WARRANTY i f' P • : °" Globe agrees to repair or replace any of its own manufac- «,, ' := a , « ". 1,,R1 I 1 tured products found to be defective in material or workmanship for a period of one year from date of shipment. RECESSED PENDENT SLEEVE & SKIRT PENDENT For specific details of our warranty please refer to Price List Terms and Conditions of Sale (Our Price List). LOBE ° FIRE SPRINKLER 4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658 CORPORATION 989 - 846 -4583 FAX 989 - 846 -9231 1- 800 - 248 -0278 www.globesprinkler.com APRIL 2007 PRINTED U.S.A. BULLETIN GL5679, REV. #10 Allied Schedule 10 dr. Schedule 40 Sprinkler Pipe - Allied Tube and Conduit - Tyco Electrical and M... Page 1 of 1 • i a1Iied Industry Leaders in Electrical and Metal Products TUBE & CONDUFT Allied and T co Overview Em.lo ees Literature & Technical S.ecifications Contact Us Site Map Products Home > Industries Served > Steel Tube and Pipe > Sprinkler Pipe > Allied Schedule 10 & Schedule 40 • industries Served Allied Schedule 10 & Schedule 40 Sprinkler Pipe Related Products: Automotive ! . Electrical Raceways E — ' BLT6 - Siach Li;ntwaii Metal Construction +� fhreadahie Pipe Perimeter Security Rolled Shapes & Angles �:. .. i Sign Support f I i -r Steel e & Pipe ; 1 F: - Fence Framework , °`�,�. / r x I - Mechanical Tubing } ;_n` " t . • . The original black lacquer • - upr,nkler Pipe coated threadable lightwall - Welded Pipe Fittings Allied Schedule 10 & schedule 40 Sprinkler Pipe pipe with exceptional hydraulics and economy. • Services Mole Alternative to Sch-40 pipe for branch line use, generically known as "lightwall threadable pipe." Manufactured to ASTM A -135 Sizes 1" - 2" Other Sprinkler Pipe Pages: with clean black, moisture resistant coating. Dyna Thread& Dyna Flow® Allier§ Spunkier Pipe CD XLr Galvanized Pipe Benefit: When you specify Allied Schedule 10 and Schedule 40 ( ^ BLT&) - Black Lightwall sprinkler pipe you get a UL listed and FM approved product. Our , ,:. i s Threadable Pipe Schedule 10 and Schedule 40 pipe passes through the same thorough � svli[:Arrkrwt�� I r.!I■ed Schedule 10 and Schedule lab testing as our other listed pipe products, and receive periodic mill Y, . inspections from both UL and FM agents to ensure consistent quality. • A5F II Coating Request Your t,epv Today Sprinkler Pipe Spec. CD Approvals: Schedule 10 and Schedule 40 pipe are in compliance with ASTM A - 135, and NFPA 13. Both pipe products have a working pressure rating of 300 psi maximum. • Ainerrcan Fire Sprinkler Association `. OZ) 44* National Fire Sprinkler APPROVED Association National rim Protection Association Order with Ease Allied Schedule 10 /Schedule 40 is available nationally through our network of distributors, providing convenient ordering and flexible delivery options. For order inquiries, please contact Roberta Lund at , n 0 (800) 882 -5543, ext. 2097, or via email at rlund@alliedtube.com. For full specifications and detailed information, download Schedule ' 10/Schedule 40 brochure. n , .•; r. ; f : ;' • : r s ,, .., , , r Download Schedule 1 O /Schedule �Li Brochure Learn more in our Library of Literati r < technical Specifications. Visit l ycc l ire Products for fire sprinkler products. • Home Products Industries Served Services Careers Retail Contact Site Map Allied Tube & Conduit 16100 S. Lathrop Avenue Harvey, IL 60426 -6021 Tel 800 -882 -5543 All Material Copyright ®1994 -2006 Allied Tube & Conduit. All rights reserved. web design by mir Internet marketing l search engine optimization by seo logic http : / /www.alliedtube.com/steel -tube- pipe /sprinkler- pipe /schedule- 10 -40.asp 10/24/2007 TDLCO . , . ..... V i www tolco.cotln a land of NIBCD' _ e Revision 3/1/2007 Fig. 200 - "Trimline" Adjustable Band Hanger C ODS LISTED Size Range — 1/2" thru 8" pipe 4> Material — Carbon Steel, Mil. Galvanized to G90 specifications Function — For fire sprinkler and other general piping 44: 2_ purposes. Knurled swivel nut design permits hanger /; - '" adjustment after installation. �; " �! " .rA ) ` '% J Features — = i � , " • (1/2" thru 2 ") Flared edges ease installation for + ( . + all pipe types and protect CPVC plastic pipe from i /j i s ;; j� abrasion. Captured design keeps adjusting nut J , ' from separating with hanger. Hanger is easily R ' ' ; e I ; i I, installed around pipe. '% �' , j A • (21/2 thru 8 ") Spring tension on nut holds it A I ; ' `. ( ; securely in hanger before installation. Adjusting ( i i( _ / ' , I �' "` nut is easily removed. J C/ ,.! Approvals — Underwriters' Laboratories listed (1/2" „.• ' � � thru 8 ") in the USA (UL) and Canada (cUL) for steel 1 „! and CPVC plastic pipe and Factory Mutual Engineering r . - I,./ Approved (3/4" thru 8 "). Conforms to Federal 1/2 THRU 2 INCH PIPE / 2 1/2 THRU 8 INCH PIPE Specifications WW -H -171 E, Type 10 and Manufacturers Standardization Society SP -69, Type 10. Maximum Temperature — 650 °F {t; Finish — Mil. Galvanized. For Stainless Steel materi- - als, order TOLCOTM Fig. 200WON. ! 1 r IA ' O By — Fi gure number and pipe size , ' �/ • l; /, ,� i 1 1 , �. Dimensions • Weights Pipe Rod Size Max. Rec. Approx. Size Inch Metric A B Load Lbs. Wt. /100 1/2 3/8 8mm or 10mm 3 2% 400 11 3/4 3/8 8mm or 10mm 31 21/2 400 11 1 3/8 8mm or 10mm 3% 2% 400 12 11/4 3/8 8mm or 10mm 33 2 400 13 11/2 3/8 8mm or 10mm 3 2 %/e 400 14 2 3/8 8mm or 10mm 4 3 400 15 21 3/8 10mm 5% 41/4 600 27 3 3/8 10mm 5 4 600 29 3 3/8 10mm 7% 5 600 34 4 3/8 10mm 7% 5 1000 35 5 1/2 12mm 91 6 1250 66 6 1/2 12mm 10 63/4 1250 73 • 8 1/2 12mm 13 8 1250 136 OFFICE/MANUFACTURING FACILITY • 1376 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330 90 CUSTOMER SERVICE • 800.786.5266 www.fofco.com GST - Wood Sammy Page 1 of 4 • ••,,• .•y > TLUa, Rod AUK '"so , .-.4tiAr! 6 y ' •w _ Home ; Up j _Dektite Retro Socket Video I GST - Wood Sammy SWG - Wood SW f DST - Steel Sammy SWDR - Steel SW ;,ST - Concrete Sammy SWC - Concrete SW SS Wood j SS Steel I Sheetrock Hurricane I Ceiling Screws Pole Tool Samm y Assortment Sammy Saddle Sammy Xpress I Sammy Swivel Head - -- - -__ - I � -- - - - - -- -- - - - - -= - - -- - -- -- - -- - - -- - - -= - - - -- -- - -- - - All - thread Rod Anchoring Systems Wood Sammy - Self drilling & self - tapping into wood "mom' °`un ' Ito �,�nr di,;. � . WOOD • 1/4" Rod • Vertical Mount Use #14 Nut Driver (Item #100) Item Part # Model Rod Shank Shank No Size Diameter Length 21 8002957 GST 100 1/4 -20 1/4 1 #14 22 8003957 GST 200 1/4 -20 1/4 2 Item #100 PN 8113910 23 8004957 GST 300 1/4 -20 1/4 3 WOOD • 3/8" Rod • Vertical Mount Use #14 Nut Driver (Item #100) Minimum Wood Thickness 1.5 UL/FM http:// www.sammysuperscrew.com/GST.htm 10/24/2007 GST - Wood Sammy Page 2 of 4 inches Pipe Item Rod Shk Shk UL FM Size Actual No Part # Model Size Diam Len Test Test inches Pullout Load Load (Ib) (Ib) ' 10 8006957 GST .75 3/8- 16 1 /4 3 /4 564# - 6 Ply Q. 11 8007957 GST 3/8- 1 /4 1 300 CPVC 210# - 7 / 16 OSB 10 16 1 -1/2 670# - 3 /4 "Ply �. 12 8008957 GST 3/8- 1 /4 2 850 1475 2'/214 1760# -Fir #14 20 16 Item #100 ®. 27 8009925 25 -380 16 GST 3/8- 3/8 2 /z 1500 4 2113# - Fir G3801. 3/8- 1 /4 PN 8113910 30 8010957 16 3 1500 1475 4/4 2060# - Fir 403 8011925 GST 3/8- 1 /4 4 2180# - Fir 40 16 14 8012925 GST 3/8- 1 /4 6 2230# - Fir 60 16 Click on ® symbol to link direct to UL Online Certification Click on symbol to link direct to FM Global Loss Prevention Data Sheet 1 -2. WOOD • 1/2" Rod • Vertical Mount Use #14SW Nut Driver (Item #101) Item Part Rod Shank Shank Actual Note: #14SW must be used No # Model Size Diameter Length Pullout for screws with 1 /2" cap. 8 8013925 GST 2 1 /z - 13 1 /4 2 1760# - Fir 06 8014925 GST 2.5 -380 1 /2 - 13 3/8 2 2113# - Fir 15 8015925 GST 3 '/2 - 13 1 /4 3 2275# - Fir 16 8016925 GST 4 * '/2 - 13 1 /4 4 2180# - Fir #14SW Item #101 17 8017925 GST 6 * '/2 - 13 1 /4 6 2230# - Fir PN 8114910 * Contact ITW Buildex for availability and lead time Legend Factory Mutal Approved 0. UL- listed . Box quantity 25. Standard box quantity 125, except where so indicated. Factory Mutual and UL listed approvals - pdf http: // www.sammysuperscrew.com /GST.htm 10/24/2007 GST -, Wood Sammy Page 3 of 4 Link to DOWNLOADS including: Product Catalog, engineering (CAD) drawings, list of FM approvals, ICC Evaluation Service, Miami Dade Online Certification and UL test reports. U RTICAL MOUNT.pdf Installation Diagrams Composite Joist Not rocath.e r eomledwldlh ( tr! Sammy ism ' Sammy rit It id - ,� � Vtand .�,� ., klet F L9 r 8 r Sammy- a 8 lhegrrock `" Consult truss manufacturer for �! Ceiba recommended installation point. See Special Notes Installation per NFPA 13 • ., All installations must be performed with appropriate nut drivers to comply with warranty. Installation Instructions Wood Sammy (GST) • Wood Sidewinder (SWG) Self drilling & self - tapping into wood See Figures 1- 4 (vertical) and 11 -14 Step 3 (horizontal) of detailed installation Position drill and begin installation: instructions for more diagrams and illustrations. a. for installing GST, drill should be in a vertical position; Step 1 „ b. for installing SWG drill should be in a Insert the appropriate nut driver into a 3/8 or horizontal position at a right angle to 1 /2 portable drill: the structural member. a. use #14 Nut Driver for GST for 3/8" Step 4 and 1 /a�� rod; When the nut driver spins freely on the cap of the screw installation is complete. b. use #14SW Nut Driver for SWG, and for GST for 1 /z" rod. Step 5 • Screw is now ready to receive 1 /4 ", 3/8 ", 1 /2" `Step 2 or metric all thread rod or bolt stock. Insert the screw into the nut driver. Now you are ready to install the screw. • Must be installed with appropriate nut driver to comply with warranty. • Eye protection should be worn at all times when installing this product. http:// www.sammysuperscrew.com/GST.htm 10/24/2007