h i r Installat Manual FB- IOM -1.0 7 -27 -06
Fan Powered Terminals VAV Term in&- - °c - ov 7 /D
/6 a $1,-) Rd � J
Receiving inspection The diameter of the inlet duct "p" in low voltage controls from the side of the
Inches must be equal to the listed size of unit, and line voltage motor controls or
After unpacking the terminal, check it for the terminal; e.g. a duct that actually electric heat section (if so equipped)
shipping damage. If any shipping measures 8 inches must be fitted to a from the rear or discharge of the unit. ,
damage is found, report it Immediately size 8 terminal. The inlet collar of the
to the delivering carrier. Store units in a terminal is made 1/8" smaller than listed For bottom access panel removal, 3"
size in order to fit inside the duct (see minimum vertical clearance below the
clean dry location and do not stack more (
than four high. Figure 1). unit is required, plus sufficient horizontal
clearance to slide the access panel clear
Caution: Do not use the inlet collar, Important: Do not insert duct work of the bottom of the unit. Horizontal
damper shaft, flow sensor or air inside the inlet collar of the clearance is dependent on access panel
tubing as a handle to lift or move assembly. dimensions as indicated on product
assembly. Damage to the unit or submittals.
controls may result. Inlet duct should be Installed in
accordance with SMACNA guidelines. For low voltage control enclosure
Before installation, remove fan packing Rectangular discharge opening is access, a minimum of 18" is
and all foreign material from the unit. designed for flanged duct connections. recommended. Specific control
Check the blower wheel for free rotation. Fasten and seal by method prescribed enclosure location is indicated on
In the Job specification. product submittals. Panel for low voltage
enclosures are removable (not hinged).
Supporting the Assembly If single -point electronic velocity sensor For line voltage motor controls or electric
is used, 3 to 5 Inlet duct diameters of heat control access, a minimum of 36"
Suspend the unit from the building straight duct should be provided at the should ba provided to allow full opening
terminal inlet, of hinged access doors. Specific location
structure in a horizontal plane with the is indicated on product submittals.
access panels facing downward.
Minimum Access Important: These recommendations
Do not obstruct the access panels do not preclude NEC or local codes
with support channels or straps. that may be applicable, which are
Fan Powered terminals require sufficient
One inch Ion sheet metal screws can clearance to service the fan blower the responsibility of the installing
g assembly and internal actuator (if so contractor.
be used to penetrate the casing (see
Figure 1). Use the support method equipped) from the bottom of the unit,
prescribed for the rectangular duct on
the job specifications. Unit may be =4-' /0 ''' Straps
equipped with optional hanging brackets
(see Figure 2). Hanger rod up to 7/16" ( C re w S / & &/- Si7O?
diameter may be used.
Note: If equipped with pneumatic .-
controls, or unit is parallel fan type — - _L. l
(Model TOP or FLP), the terminal must Discharge `1 l 41 Air
be mounted right side up. It must be I _# Flow
level within ±10 degrees of horizontal, '
both parallel to the air flow and at the Access Panel
right angle of air flow. The control side of (Entire Bottom Is
the terminal is labeled with an arrow Figure 1. Removeable)
indicating UP.
Hanger Rod
Duct Connections i Optional
Hanger
Slip each inlet duct over the Inlet collar Bracket
of the terminal. Fasten and seal the
connection by the method prescribed by
the job specification. i t ifii
Discharge 11 11, 4 Air Flow
•
Figure 2.