• NAC EXTENDER BATTERY CALCULATIONS
CAPITOL ELECTRIC CO• , INC.
(503) 255 -9488 Office, (503) 255 -1966 Fax -';\ Ll; •
JOB NAME: Lincoln Tower
ADDRESS: 10260 SW Greenberg Road Tigard, OR 97223 DATE: 3/15/1'1
PANEL DESCRIPTION: NAC 8.1 PREPARED BY: Dan Wilson
DEVICE TOTAL DEVICE TOTAL
STANDBY STANDBY ALARM ALARM
DEVICE QUANTITY CURRENT CURRENT CURRENT CURRENT
NAC EXTENDER
Silent Knight 5495 -7 NAC Panel 1 0.075 0.075 0.175 0.175
CIRCUIT # 1 Suite 800
0.000
Wheelock RSS - 24MCC -FW 115 Cd Strobe 0.300 0.000
Wheelock RSS - 24MCC -FW 95 Cd Strobe 0.249 0.000
Wheelock RSS - 24MCC -FW 75 Cd Strobe 2 0.189 0.378
Wheelock RSS - 24MCC -FW 30 Cd Strobe 7 0.105 0.735
Wheelock RSS - 24MCC -FW 15 Cd Strobe 3 0.065 0.195
Wheelock RSS - 24MCW -FW 110 Cd Strobe 1 0.220 0.220
0.000
0.000
TOTAL 1.528
CIRCUIT # 2 Suite 800
0.000
Wheelock RSS - 24MCC -FW 115 Cd Strobe 1 0.300 0.300
Wheelock RSS - 24MCC -FW 95 Cd Strobe 2 0.249 0.498
Wheelock RSS - 24MCC -FW 75 Cd Strobe 1 0.189 0.189
Wheelock RSS - 24MCC -FW 30 Cd Strobe 0.105 0.000
Wheelock RSS - 24MCC -FW 15 Cd Strobe 2 0.065 0.130
0.000
0.000
0.000
TOTAL 1.117
CIRCUIT # 3 Floor 8 Building Core
0.000
Wheelock RSS - 24MCW -FW 15 Cd Strobe 2 0.060 0.120
E60- 24MCW -FW 15 Cd SPKR STB, Ceiling 2 0.065 0.130
0.000
0.000
0.000
0.000
0.000
0.000
TOTAL 0.250
CIRCUIT # 4
0.000
0.000
0.000
0.000
• 0.000
0.000
0.000
0.000
0.000
TOTAL 0.000
NAC 08.1 Batt Calc.xls Page 1 of 2
•
J' . NAC EXTENDER BATTERY CALCULATIONS
•
CAPITOL ELECTRIC CO., INC.
(503) 255 -9488 Office, (503) 255 -1966 Fax
JOB NAME: Lincoln Tower
ADDRESS: 10260 SW Greenberg Road Tigard, OR 97223 DATE: 3/15/11
PANEL DESCRIPTION: NAC 8.1 PREPARED BY: Dan Wilson
DEVICE TOTAL DEVICE TOTAL
STANDBY STANDBY ALARM ALARM
DEVICE QUANTITY CURRENT CURRENT CURRENT CURRENT
AUXILIARY DEVICES
0.000 0.000
0.000 0.000
0.000 0.000 ,
TOTAL 0.000
• STANDBY TOTAL CURRENT: I 0.075 •
STANDBY HOURS: • 24 • .
STANDBY AMP HOURS: 1.800 NAC DEVICE CURRENT I • 2.895
ALARM TOTAL CURRENT: I 3.070
ALARM MINUTES: 5
ALARM AMP HOURS: 0.256
TOTAL CALCULATED AMP HOURS 2.056
APPLIED SAFETY FACTOR 1.15
MINIMUM AMP HOURS REQURED 2.364
SELECTED BATTERY SIZE. • 1 2 EACH 12 VOLT, 7 AMP HOUR BATTERIES
•
NAC 08.1 Batt Caic.xls Page 2 of 2
NAC EOL VOLTAGE CALCULATION
• CAPITOL ELECTRIC CO., INC.
(503) 255 -9488 Office
(503) 255 -1966 Fax
Job Name: Lincoln Tower
Job Address: 10260 SW Greenberg Road Tigard, OR 97223
Job Number: Conductor Wire Guage I 14 I
Prepared By: Dan Wilson Ohms Per 1000 Ft @ 75 Deg C ( 167 Deg F) I 3.07 I
Date: 3/15/2011
Cable Length In Feet (source to end of line) I 493 I
Total Circuit Current I 1.528 I
Nominal System Voltage I 20.4 I
Panel Description: Silent Knight 5495 -7 Power Supply Minimum Device Voltage I 16 I
- Panel No.: NAC 8.1
Output No.: 1 Point To Point Method EOLv I 18.00
Circuit Within Limits ? YES
NAC Devices Mfg By: Wheelock
End Of Line Method EOLv I 15.77 I
Circuit Within Limits ? NO
Load Centering Method EOLv I 18.09 I
Circuit Within Limits ? YES
Dev Device Location Device Model No. & Description Candella Alarm Distance From Voltage At
No. Rating Current Previous Device Device
( Feet )
1 SUITE 800 RSS - 24MCC -FW (30) STB WHT 30 Cd 0.105 33 20.09
2 SUITE 800 RSS - 24MCC -FW (30) STB WHT 30 Cd 0.105 33 19.80
3 SUITE 800 RSS - 24MCC -FW (75) STB WHT 75 Cd 0.189 42 19.46
4 SUITE 800 RSS - 24MCC -FW (30) STB WHT 30 Cd 0.105 33 19.23
5 SUITE 800 RSS - 24MCC -FW (75) STB WHT 75 Cd 0.189 45 18.95
6 SUITE 800 RSS - 24MCC -FW (30) STB WHT 30 Cd 0.105 36 18.77
7 SUITE 800 RSS - 24MCC -FW (30) STB WHT 30 Cd 0.105 31 18.63
8 SUITE 800 RSS - 24MCC -FW (15) STB WHT 15 Cd 0.065 33 18.50
9 SUITE 800 RSS - 24MCC -FW (15) STB WHT 15 Cd 0.065 43 18.35
10 SUITE 800 RSS - 24MCC -FW (30) STB WHT 30 Cd 0.105 34 18.25
11 SUITE 800 RSS - 24MCC -FW (15) STB WHT 15 Cd 0.065 48 18.13
12 SUITE 800 RSS - 24MCC -FW (30) STB WHT 30 Cd 0.105 33 18.07
13 SUITE 800 RSS- 24MCW -FW (110) STB WHT 110 Cd 0.220 49 18.00
14 18.00
15 18.00
16 18.00
17 18.00
18 18.00
19 18.00
20 18.00
NAC 08.1 EOLv Calc.xls OUTPUT 1
• n[w rug � 4 [r [[
. ( f?
L a ' ° ° td
ffrtz vv :K__IL { C__.
, __SYSI EMS__ .�. ---
Helping People Take Actions"
SERIES RSS & RSSP SINGLE
& MULTI - CANDELA STROBES
& STROBE PLATES
DESCRIPTION _ n �\
Wheelock's patented Series RSS Strobe Appliances and ( � "r
l_ ._T
Series RSSP Strobe Plates have lower current draw while `� r� _4'
i� �:�
maintaining outstanding performance, reliability and cost ti
effectiveness. These versatile appliances will satisfy , _ F e..
virtually all requirements for indoor, wall or ceiling mount Series RSS RSS Round
applications. Series RSSP
Strobe options for wall mount models include 1575 or - -. — ;--- •
•
Wheelock's Patented MCW multi candela strobe with field r.
selectable candela settings of 15/30/75/110cd or the high 1 -.-
is 3 0 _
intensity MCWH strobe with field selectable 135/185cd. r, — ' 110 l ' i
Ceiling mount models include the patented MCC multi -
candela ceiling strobe with field selectable intensities of Multi - Candela Indicator
15/30/75/95cd or the high intensity MCCH strobe with (bottom of Strobe Lens)
field selectable 115/177cd. Features
All models may be synchronized using the Wheelock • Approvals include: UL Standard 1971, New York City
SM, DSM Sync Modules or the PS- 12/24 -8CP and (MEA), California State Fire Marshal (CSFM), Factory
PS- 12/24 -8MP Power Supplies with Wheelock's Patented Mutual (FM), and Chicago (BFP) See approvals by
Sync Protocol. Synchronized strobes can eliminate model in Specifications and Ordering Information
possible restrictions on the number of strobes in the field • ADA/NFPA/UFC /ANSI compliant. Meets OSHA 29
of view. Wheelock's synchronized strobes offer an easy Part 1910.165
way to comply with ADA recommendations concerning • Wall mount Multi - Candela models are available
photosensitive epilepsy as well as meeting the with Field Selectable Candela Settings of 15/30/
requirements of NFPA 72. • 75/110cd or 135/185cd. Single.Candela models
are available in 1575cd
Wheelock's Series RSS Strobes employ •a Patented • Ceiling mount Multi - Candela models are
Integral Strobe Mounting Plate that can be mounted to a available with field selectable candela settings of
single gang, double gang, 4" square, 100mm European 15/30/75/95cd or 115/177cd. (Round or Square)
backboxes or the SHBB surface backbox. If the flush • Strobes produce 1 flash per second over the
backbox has side or top space between it and the finished regulated voltage range
wall, the NATP (Notification Appliance Trimplate) may be • 12 and 24 VDC models with wide UL "Regulated
t used. It provides an additional .65" of trim for the Appliance. Voltage •using filtered (DC) or unfiltered VRMS input
An attractive cover plate is provided for a clean; finished voltage
appearance on all models. • Synchronize using Wheelock's sync modules or power
supplies with built -in sync protocol
The Series RSSP Multi - Candela Strobe Plates are a cost • Fast installation with IN /OUT screw terminals using
effective way to retrofit required wall strobe appliances to #12 to #18 AWG wire
bells, horns, chimes, multitones or speakers and easily
mounts to standard 4" backboxes or for surface mount
use with Wheelock's SBL2 surface backbox.
For Weatherproof Series RSS See Datatsheet S9004
Copyright 2004 Wheelock, Inc. All rights reserved.
•
•
•
•
•
•
•
•
•
NOTE: All CAUTIONS and WARNINGS are identified by the symbol n. All warnings are printed in bold capit letters.
A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING,
SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN
IMPROPER APPLICATION, INSTALLATION AND /OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN
PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS.
General Notes
• Strobes are designed to flash at 1 flash per second minimum over the Regulated Voltage Range. Note that NFPA -72 specifies a flash rate of
1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second.
• All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971.
• Series RSS & RSSP Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32° F to 120° F (0° C to
49° C) and maximum humidity of 93% (± 2 %).
• "Regulated Voltage Range" is the newest terminology used by UL to identify the voltage range. Prior to this change, UL used the
terminology "Listed Voltage Range ".
Table 1: Average RMS Current*
RSSIRSSP RSSIRSSP - Wall Mount RSS - Ceiling Mount
24VDC 241575W 24MCW 24MCWH 24MCC 24MCCH
Models 1575cd 15cd 30cd 75cd 110cd 135cd 185cd 15cd 30cd 75cd 95cd 115cd 177cd
24 vdc 0.060 0.041 0.063 0.109 0.140 0.195 0.270 0.045 0.070 0.119 0.159 0.195 0.270
UL max* 0.090 0.060 0.092 0.165 0.220 0.300 0.420 0.065 0.105 0.189 0.249 0.300 0.420
•
•
RSSIRSSP RSS /RSSP * RMS current ratings are per UL average RMS method. UL max current
• 24VDC Wall Mount rating is the maximum RMS current within the listed voltage range (16 -33v
Models 121575W for 24v units). For strobes the UL max current is usually at the minimum
• 12 vdc 0.152 listed voltage (16v for 24v units). For audibles the max current is usually at
the maximum listed voltage (33v for 24v units). -For unfiltered FWR ratings,
UL max" 0.255 see installation instructions.
Table 2: AudibleslSpeakers for RSSP Strobe Plate
•
Product Series
Multitone Appliances AMT, MT
Horns AH, NH, HS
Motor Bells MB- G6 /G10
•
Speakers ET- 1010/1080, E70, E170
Chimes CH70
•
•
A WARNING: CONTACT WHEELOCK FOR THE CURRENT "INSTALLATION INSTRUCTIONS" AND "GENERAL INFORMATION" SHEET (P82380) ON THESE
PRODUCTS. THESE DOCUMENTS UNDERGO PERIODIC CHANGES. IT. IS IMPORTANT THAT YOU HAVE CURRENT INFORMATION ON THESE PRODUCTS.
THESE MATERIALS CONTAIN IMPORTANT INFORMATION THAT SHOULD BE READ PRIOR TO SPECIFYING OR INSTALLING THESE PRODUCTS, INCLUDING:
• TOTAL CURRENT REQUIRED BY ALL APPLIANCES CONNECTED TO SYSTEM SECONDARY POWER SOURCES.
• FUSE RATINGS ON NOTIFICATION APPLIANCE CIRCUITS TO HANDLE PEAK CURRENTS FROM ALL APPLIANCES ON THOSE CIRCUITS.
• ADDING, REPLACING OR CHANGING APPLIANCES OR CHANGING CANDELA SETTINGS WILL AFFECT CURRENT DRAW. RECALCULATE CURRENT
DRAW TO INSURE THAT THE TOTAL AVERAGE CURRENT AND TOTAL PEAK REQUIRED BY ALL APPLIANCES DO NOT EXCEED THE RATED CAPACITY
OF THE POWER SOURCE OR FUSES.
• COMPOSITE FLASH RATE FROM MULTIPLE STROBES WITHIN A PERSON'S FIELD OF VIEW.
• THE VOLTAGE APPLIED TO THESE PRODUCTS MUST BE WITHIN THEIR "REGULATED VOLTAGE RANGE'.
• INSTALLATION OF 110 CANDELA STROBE PRODUCTS IN SLEEPING AREAS.
• INSTALLATION IN OFFICE AREAS AND OTHER SPECIFICATION AND INSTALLATION ISSUES.
• USE STROBES ONLY ON CIRCUITS WITH CONTINUOUSLY APPLIED OPERATING VOLTAGE. DO NOT USE STROBES ON CODED OR
INTERRUPTED CIRCUITS IN WHICH THE APPLIED VOLTAGE IS CYCLED ON AND OFF AS THE STROBES MAY NOT FLASH.
• FAILURE TO COMPLY WITH THE INSTALLATION INSTRUCTIONS OR GENERAL INFORMATION SHEETS COULD RESULT IN IMPROPER
INSTALLATION, APPLICATION, AND /OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY
DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS.
• CONDUCTOR SIZE (AWG), LENGTH AND AMPACITY SHOULD BE TAKEN INTO CONSIDERATION PRIOR TO DESIGN AND INSTALLATION OF THESE
PRODUCTS, PARTICULARLY IN RETROFIT INSTALLATIONS.
•