Plans (142) BUP2015 00212 - - - ABBREVIATION LEGEND GENERAL DRAWING SYMBOLS LEGEND: ARCHITECTURAL SYMBOLS LEGEND: ELECTRICAL & COMMUNICATIONS SYMBOLS LEGEND: j A EXISTING PARTITION TO REMAIN POWER- SWITCHING AND RECEPTACLES ACT ACOUSTICAL H Q 1 VIEW TITLE VIEW TITLE CEILING TILE HC HOLLOW CORE QTY QUANTITY A-201 SCALE $ NEW WALL-MOUNTED LIGHT SWITCH AFF ABOVE FINISHED HCP HANDICAP(PED) ___________= EXISTING PARTITION TO BE REMOVED ! FLOOR HDW HARDWARE R ALT ALTERNATE HM HOLLOW METAL RB RESILIENT BASE E EXISTING WALL-MOUNTED ELECTRICAL DUPLEX OUTLET TO REMAIN Q ALUM ALUMINUM KN'APPROX APPROXIMATELY) HOR HORIZONTAL REF REFERENCENEW PARTITION ARCH ARCHITECT(URAL) HR HOUR REINF REINFORCE(D) NORTH ARROW NEW WALL-MOUNTED ELECTRICAL DUPLEX OUTLET 10260 W. 4 � HT HEIGHT REQ REQUIRED NORTH j REV REVISION EXISTING/NEW WINDOW FRAMING SYSTEM TO REMAIN D B I NEW WALL-MOUNTED DEDICATED ELECTRICAL DUPLEX OUTLET GREEN URG RD ARD BDDG BUILDING INCL INCLUDE(D) S INSUL INSULATION SAB SOUND GFCI42 BLKG BLOCKING ATTENUATION 1 REFERENCE TO INFORMATION EXISTING DOOR, FRAME, AND HARDWARE TO REMAIN M INT INTERIOR A-201 ENLARGED ELSEWHERE NEW WALL-MOUNTED GROUND FAULT CIRCUIT INTERRUPT ELECTRICAL DUPLEX OUTLET BATES W T AT 42"O.C. A.F.F. T1 AR ' OR 97223 C J Sc SOLID CORE L - - //// \\ Z CM C/L CENTERLINE SF SQUARE FOOT EXISTING DOOR, FRAME, AND HARDWARE TO BE REMOVED 42" W CFCI CONTRACTOR JT JOINT (FEET) 1 1 13 NEW WALL-MOUNTED ELECTRICAL DUPLEX OUTLET AT 42" O.C. A.F.F. VICINITY MAP W CV f FURNISHED, L SIM SMILAR 60 SITE CONTRACTOR SPEC SPECIFICATION 1 1 ELEVATION-SINGLE REFERENCE NEW OR RELOCATED DOOR, FRAME, AND HARDWARE NEW WALL-MOUNTED ELECTRICAL DUPLEX OUTLET AT 60" O.C. A.F.F. INSTALLED LAM LAMINATE SQ SQUARE A101 A101 CJ CONTROL JOINT SQ FT SQUARE FOOT INTERIOR CLG CEILING M (FEET) EXTERIOR REFLECTED CEILING SYMBOLS LEGEND:: WALL CONNECTIONS O CLR CLEAR MAX MAXIMUM STL STEEL 1 1 Z CONC CONCRETE MECH MECHANICAL SUSP SUSPEND(ED) - NEW WALL-MOUNTED DATA RECEPTACLE- QUANTITY LISTED IF GREATER THAN ONE(1) co j CONT CONTINUE, MEP MECHANICAL, SYM SYMMETRICAL 1 A101 1 1 A101 1 ELEVATION-MULTIPLE REFERENCES Q ELECTRICAL,AND EXISTING/NEW SUSPENDED CEILING GRID SYSTEM M CONTINUOUS NEW WALL-MOUNTED DATA/VOICE RECEPTACLE- QUANTITY LISTED IF GREATER THAN 0°" _ W CORR CORRIDOR PLUMBING T 1 1 INTERIOR ONE(1) � a CT CERMIC TILE MEPFP MECHANICAL, EXTERIOR } TEL TELEPHONE N ELECTRICAL, �,�., �,�z����;,P.r:u�. PLUMBING, AND TEMP TEMPERED SIM E EXISTING WALL-MOUNTED DATA/VOICE RECEPTACLE TO REMAIN 1 E EXISTING 2x4 FLUORESCENT LIGHT FIXTURE O i D FIRE PROTECTION TFCI TENANT(CLIENT) SECTION/PLAN DETAIL REFERENCE D r � DIA DIAMETERA1oi MIN MINIMUM FURNISHED, DIM DIMENSION(S) MISC MISCELLANEOUS CONTRACTOR ® RELOCATED 2'x4' FLUORESCENT LIGHT FIXTURE SPECIAL PURPOSE CONNECTION OR PROVISION FOR CONNECTION. SEE KEYED NOTES FOR j MTL METAL INSTALLED 101 ADDITIONAL INFORMATION. n E TFTI TENANT(CLIENT) ROOM NUMBER TAG y ® EXISTING/NEW EXIT SIGN tai EA E NFURNISHED TENANT(CLIENT) FLOOR NUMBER EJ EXPANSION JOINT NIC NOT IN INSTALLED ELEC ELECTRIC(AL) CONTRACT `TOS TOP O _ EQUIPMENT LEGEND: �I NiEARCHITECTURE ELEV ELEVATION NTS NOT TO SCALE STRUCTURE 9098 NORTH EQ EQUAL TOW TOP OF WALLSUFFIX AS REQ D DOOR NUMBER TAG ROOM NUMBER F=====1 REFRIGERATOR(O.F.C.1): 720 OLIVE STREET,SUITE 200 SAINT LOUIS, M063101 EQUIP EQUIPMENT 0 TYP TYPICAL FLOOR NUMBER T 314 206 7100 F 314 231 9801 EXIST EXISTING OC ON CENTERREF PROVIDE ELECTRICAL DUPLEX RECEPTACLE. COORDINATE WITH CODE INFORMATION j CLIENT FOR SPECIFICATION AND ADDITIONAL REQUIREMENTS. EXP EXPANSION OFCI OWNER U I FURNISHED, 9E --- AUTHORITIES HAVING JURISDICTION: TRIGARD, OR COUNTY EXT EXTERIOR UL UNDERWRITERS PARTITION TYPE TAG CONTRACTOR LABORATORIES, SUB-TYPE ---- COPY/PRINTER(O.F.0.1): BUILDING CODE: 2014 OREGON STRUCTURAL SPECIALITY CODE INSTALLED INC. TYPE DESIGNATION F--fir-----, � F , F---1 PROVIDE ONE(1) DUPLEX OUTLET ON DEDICATED CIRCUIT, AND FD FLOOR DRAIN OF01 OWNER � �� ACCESSIBILITY: AMERICANS WITH DISABILITIES ACT UNO UNLESS NOTED ' �� L_-i'I ONE(1) DATA TERMINATION. CONFIRM REQUIREMENTS WITH FURNISHED, OTHERWISE 1 KEYNOTE TAG L-� --J ICC/ANSI Al 17.1, REFERENCED BY BUILDING CODE a FE FIRE OWNER --- CLIENT. EXTINGUISER INSTALLED FIRE PREVENTION: NATIONAL FIRE PROTECTION ASSOCIATION FEC FIRE OH OPPOSITE VM FINISH TAG EXTINGUISHER OH OPPOSITE HAND VERT VERTICAL MECHANICAL: 2014 OREGON MECHANICAL SPECIALITY CODE CABINET OPG OPENING I FIN FINISH(ED) W 1 ELECTRICAL: 2014 OREGON ELECTRIC SPECIALITY CODE FIN FLR FINISHED FLOOR P W/ WITH REVISION CLOUD AND DELTA PLUMBING: 2014 OREGON PLUMBING SPECIALITY CODE FLR FLOOR PLAM PLASTIC W/0 WITHOUT FLUOR FLUORESCENT LAMINATE WC WALL COVERING ENERGY: 2014 OREGON ENERGY EFFICIENCY SPECIALTY CODE FRT FIRE-RETARDANT PT PAINT(ED) WD WOOD I- TREATED PTN PARTITION j G PWD PLYWOOD BUILDING INFORMATION GA GAUGE, GAGE USE GROUPS: B BUSINESS GYP BD GYPSUM BOARD CONSTRUCTION TYPE: 11 STORIES, TYPE IB ASSUMED SPRINKLERED j SEISMIC CATEGORY: I_ D REFER TO CISCA GUIDELINES FOR REQUIREMENTS ARCHITECT OF RECORD: OCCUPANT LOAD: ACTUAL SF: 1,652 SF CALCULATED OCCUPANT LOAD(EMPLOYEES &CUSTOMERS): 17 OCCUPANTS DEVICE LOCATION DIAGRAM GENERAL NOTES: DEVICE LOCATIONS -- ACTUAL SF: WHEN MOUNTING MULTIPLE DEVICES FROM DIFFERENT TRADES IN THE SAME LOCATION(SUCH AS 1,652 SF ACTUAL OCCUPANT LOAD(EMPLOYEES&CUSTOMERS): 6-8 OCCUPANTS ED NOTE: CEILING LIGHTING SWITCHES, THERMOSTATS, ETC.), THEIR ARRANGEMENT SHALL BE IN ACCORDANCE WITH THE C PROVIDE INTERMEDIATE EQ EQ VISUAL ALARM FOLLOWING: � BLOCKING FOR DEVICES AS C� REQUIRED FOR PLACEMENT \ 1. LOCATE DEVICES AS SHOWN ON THE ARCHITECTURAL PLANS, ELEVATIONS OR SECTIONS. PROJECT TEA wl z ROLES, RESPONSIBILITIES, AS DIMENSIONED EDGE OF COLUMN OR 2. MULTIPLE DEVICES MOUNTED ON A SINGLE WALL OR IN THE SAME AREA OF A WALL ARE TO BE • PARTITION, PARTITION- GROUPED TOGETHER AND ARRANGED AS INDICATED HERE. & CONTACT INFO. PHOENIX,ARIZONA MOUNTED EQUIPMENT, 3. WHERE DEVICE LOCATIONS ARE SHOWN ELSEWHERE IN THE ARCHITECTURAL DRAWINGS, THOSE O �. ETC. LOCATIONS ARE TO BE THE BASIS FOR ARRANGING OTHER DEVICES IN THE SAME AREA. ARCHITECT: `9J�, R�� VISUAL ALARM ��� 4. DEVICES,WHETHER SHOWN ON ARCHITECTURAL, ELECTRICAL, MECHANICAL OR OTHER CONTRACTED BY THE CLIENT, RESPOi JSIBLE TO COORDINATE WITH THE CLIENT, THE GENERAL OF DRAWINGS ARE TO BE ARRANGED AND LOCATED AS INDICATED HERE, WITH UNIFORM SPACING CONTRACTOR, SUBCONTRACTORS,AND OTHER CLIENT CONSULTANTS TO ACHIEVE THE CONTRACTED 7-08-15 4" 10" �� I BETWEEN DEVICES AND HORIZONTAL AND VERTICAL ALIGNMENTS AS SHOWN. SCOPE OF WORK `� 5. PRIOR TO INSTALLATION OF DEVICES IN EXPOSED MASONRY OR MATERIALS SUCH AS WOOD ONE ARCHITECTURE ISSUE DATE DESCRIPTION DEVICE PANELS,WALL COVERING OR OTHER NON-PAINTED SURFACES, THE CONTRACTOR SHALL REVIEW 720 OLIVE STREET SUITE 200 DEVICE SWITCH, ST. LOUIS, MO 63101 4/27/2015 LANDLORD REVIEW SET N. � _ _ - ( PROPOSED LOCATIONS WITH THE ARCHITECT TO DETERMINE THE LOCATION OF DEVICES. THERMOSTAT, 6. OBTAIN CLARIFICATION FROM THE ARCHITECT PRIOR TO INSTALLATION WHERE THERE ARE CONTACT: RACHAEL BERRY,314.206.7122, RBERRY ARCTURIS.COM 6/15/2015 BID SET °? F.E., ETC.) QUESTIONS ABOUT CORRECT LOCATIONS OF DEVICES. 7. WHERE DEVICES ARE INSTALLED WITHOUT THE ARCHITECT'S APPROVAL, OR CONTRARY TO THESE GENERAL CONTRACTOR: 7/7/2015 PERMIT SET WHERE MULTIPLE a ,' ELECTRICAL OR LOCATION GUIDELINES, DEVICES WILL BE RELOCATED PER THESE GUIDELINES AS ACCEPTABLE TO CONTRACTED BY THE CLIENT, RESPuNSIBLE TO COORDINATE WITH THE CLIENT, THE ARCHITECT, MSHB INC SWITCHES OCCUR, o /� ' o COMMUNICATION THE ARCHITECT AT THE GENERAL CONTRACTOR'S EXPENSE. SUBCONTRACTORS,AND OTHER CLIENT CONSULTANTS TO ACHIEVE THE CONTRACTED SCOPE OF WORK r GANG UNDER SINGLE , RECEPTACLE, COVER Revision Schedule COVER PLATE o / o _ _ PLATE, OR JUNCTION DEVIATIONS FROM THE ABOVE PRINCIPLES WITHOUT PRIOR APPROVAL BY THE ARCHITECT SHALL BE BUILDING OWNER/PROPERTY MANAGEMENT: ,�� -1 BOX CORRECTED BY THE INSTALLING CONTRACTOR AT NO EXPENSE TO THE CLIENT.ALL COSTS ASSOCIATED SHORENSTEIN REALTY SERVICES LP No. Date Description SWITCH OR DIMMER WITH THE REMOVAL, RELOCATION,AND REINSTALLATION OF ANY DEVICES SHALL BE THE RESPONSIBILITY 10220 SW GREENBURN ROAD, SUITE 310 FLOOR OF THE GENERAL CONTRACTOR, INCLUDING THE COSTS OF CUTTING, PATCHING, REWIRING, REPAIRING PORTLAND, OR 97223 GIME OP TTIGARD DOOR OR SIDELITE FRAME ,�� OR REPLACING FINISHES, ETC. CONTACT:JAIMA COLEMAN, 503.412.4880 REVIEWED FOR CODE COMPLIANCE Ap�� oxc: DRAWING INDEX rpt : ��u% o%S de ;iI,_2 . CEILING RESTRAINT REQUIREMENTS FOR SEISMIC DESIGN CATEGORY D ARCHITECTURAL Address: 0-7-0 k6 _ _ �� s F�, ,. ,,r. �, .. . .. . . - • •KK_ .. _--_�.- ALL SUSPENDED CEILING SYSTEMS ARE TO BE INSTALLED PER2014 OREGON STRUCTURAL SPECIALITY CODE, CISCA - -..,_ A-001 GENERAL NOTES B . r ate* 4 . _•- =_ ._ GUIDELINES FOR SEISMIC ZONES 3 &4 AND ASCE SECTION 7 REQUIREMENTS. A-201 DEMOLITION PLAN,ARCHITECTURAL PLAN,AND ELEVATIONS A-401 REFLECTED CEILING PLAN F BASIC CONNECTIONS, PERIMETER,AND LATERAL SPLAY BRACING: I FINISH PLAN, AND FINISH LEGEND -;; , SUSPENDED CEILINGS GREATER THAN 144 S.F. SHALL BE BRACED IN ACCORDANCE WITH THE FOLLOWING. A- 1 D L ,� f ` 90 DOOR SCHEDULE/DOOR, FRAME, PARTITION TYPES, AND W.., OFFICE COPY -.i , ... _ S 180 LBS y � � '� � 1. MINIMUM INTERSECTION STRENGTH LIMITS @MAIN TEE/CROSS TEE I INTERIOR DETAILS 2. PROVIDE MIN. 12-GAUGE VERTICAL HANGER WIRE AT 4'-0" O.C. MIN. j L1 - 3. CONNECTION DEVICE FROM VERTICAL WIRE TO STRUCTURE ABOVE MUST SUSTAIN MIN. 100 LBS. - - ♦ �° 4. MAIN TEE CLASSIFICATION TO BE HEAVY DUTY. FURNITURE :E F-201 FURNITURE PLAN ♦ 5. 1 IN 6 MAX. PLUMB OF VERTICAL HANGER WIRES REQUIRED. ♦♦ 6. PROVIDE PERIMETER VERTICAL HANGER WIRES NOT MORE THAN 8" FROM WALL. �' ♦ ti ys � L x 7. MINIMUM CLEARANCE FROM GRID END TO WALL IS 3/4". ' ♦ n NOTE: ♦ 8. PERIMETER CLOSURE(MOLDING)WIDTH MIN. 2" E i ♦ � .. ..., 9. PROVIDE GRID CONNECTION TO PERIMETER ATTACHED ON TWO ADJACENT WALLS. 1. LATERAL FORCE BRACING IS ♦ ; w "` ♦ Ivy 10. TIE PERIMETER TEE ENDS TOGETHER. REQUIRED FOR ALL CEILINGS Key Plan: SnE ♦ 11 WIRES OR RIGID BRACING) WITHIN INTERSECTION AND SPLAYED 90 1 .� ♦ N 2" OF R 1,000 S.F. PROVIDE HORIZONTAL RESTRAINT(SPLAY G W OVER _ ' ♦ ..�; ,�� �� � ��� ,a� ��� � DEGREES APART AT 45 DEGREE ANGLES. 2. BRACING MEMBERS SHALL BE 3 PROVIDE MPRE N POSTS STRUTS AT 12"O.C. IN BOTH DIRECTIONS, STARTING 6' FROM WALL. f �� , ,. .•�� , d ,. . _ ::,,. 12. CO SSIO (STRUTS) RESIGNED TO SUPPORT A10 =;. 13. SPLAY BRACING CONNECTION STRENGTH TO BE MIN. 200 LBS. OR THE DESIGN LOAD,WHICHEVER IS GREATER. MINIMUM LOAD OF 200 PSF. � t 14. PARTITIONS ARE TO BE BRACED INDEPENDENT OF CEILING SPLAY BRACING. 15. IN ADDITION TO REQUIREMENTS NOTED ABOVE, FOR SUSPENDED CEILINGS GREATER THAN 2500 S.F. PROVIDE A STEEL STUD POST 2 500 S.F. E NO. 12 GAUGE SPLAY WIRE , SEISMIC SEPARATION JOINT OR FULL HEIGHT PARTITION DIVIDING CEILINGS INTO AREAS LESS THAN BRACING, SECURE TO BRACING IN PLANE OF w f' 16. PROVIDE RIGID BRACING FOR CEILING PLANE ELEVATION CHANGES. DECK ABOVE - EACH RUNNER. VERT. -- ' ANGLE NOT TO EXCEED 45 p! „� Ii i LIGHT FIXTURE ATTACHMENT. - ;� o , ;;`' DEGREES. SECURE WIRES ll - --- - 1 ALLY ATTACH ALL LIGHT FIXTURES TO CEILING GRID. ATTACHMENTS MUST SUPPORT 100/o OF LIGHT FIXTURE TO STRUCTURE ABOVE f _ - - .M e . MECHANIC - --- . __ - WEIGHT. o _F o UP 2. SURFACE-MOUNTED FIXTURES DO NOT REQUIRE ATTACHMENT TO GRID. d €i 3. SUPPORT PENDANT-HUNG FIXTURES DIRECTLY FROM STRUCTURE WITH 9-GAUGE WIRE OR APPROVED ALTERNATE. PATH A 104 0 0 0 E? _ CITY TIGAR© `% T `: 4. FOR RIGID LAY-IN OR CAN LIGHT FIXTURES WEIGHING LESS THAN 10 LBS PROVIDE(1)WIRE TO STRUCTURE(MAY BE ,,s;,`` `� SLACK). FOR RIGID LAY-IN OR CAN LIGHT FIXTURES WEIGHING FROM 10 TO 56 POUNDS PROVIDE(2) VERTICAL SUPPORT -°- Approved PATH B 124'-2° CROSS TEE y Planning o a o WIRES(MUST BE SLACK). FOR LIGHT FIXTURES GREATER THAN 56 POUNDS PROVIDE DIRECT AND INDEPENDENT S 1 15.2390.00 SUPPORT FROM THE BUILDING STRUCTURE. Date: 7 ( Project Number: ---- Initials: 111 - -------------��------ '� SUSPENSION CEILING GRID : ; LIGHT FIXTURE SUPPLEMENTARY HANGER WIRES: SYSTEM- MAIN TEE BEAM - Sheet Title: �� 1. PROVIDE INTERMEDIATE DUTY MAIN TEES WITH CROSS TEE RATING BELOW 16 LBS/LF. COVER SHEET i O C t 2. PROVIDE HEAVY DUTY MAIN TEES WITH CROSS TEE RATING BELOW 16 LBS/LF. j 3. - HANGER WIRES TO THE SUPPORTING CROSS T I O THREE INCHES OF THE CORNER ° .� ATTACH MIN 12 GAUGE HA EE WITHIN 3-" OF EACH LIGHT FIXTURE. RECEIVED ( B C SEISMIC CATEGORY RY D,E,F) _ �� .'. SERVICE APPLICATIONS: MauUL 16 2 1. ALL MECHANICAL AIR TERMINALS MUST BE POSITIVELY ATTACHED TO THE CEILING GRID. FOR TERMINALS WEIGHING X15 FROM 20 TO 56 POUNDS PROVIDE 2 VERTICAL SUPPORT WIRES MAY BE SLACK.) FOR TERMINALS WEIGHING GREATER CITY OF TIGARD ( ) ( PLANNING/ENGINEERING 21 LIFE SAFETY PLAN THAN 56 POUNDS PROVIDE DIRECT AND INDEPENDENT SUPPORT FROM THE BUILDING STRUCTURE. 16 DETAIL - RCP - LATERAL BRACING A-o0o 1" = 10'-0" 2. SPRINKLER HEADS AND OTHER PENETRATIONS REQUIRE A MIN.2" DIAMETER OPENING OR A SWING JOINT. 00 3. N.T.S. 3. CABLE TRAYS AND ELECTRICAL CONDUIT MUST BE INDEPENDENTLY SUPPORTED AND BRACED. i GENERAL NOTES: DEMOLITION GENERAL NOTES: ARCHITECTURAL GENERAL NOTES: FINISH DESIGN/BUILD M.E.P.F.P. SCOPE CONTRACTOR'S RESPONSIBILITY 1. PROVIDE TEMPORARY BARRICADES AND OTHER FORMS OF PROTECTION AS REQUIRED TO 1. U.N.O.ALL PARTITIONS TO BE PARTITION TYPE P1A. 1. REFER TO PLANS, R.C.P., ELEVATIONS, FINISH SCHEDULE, DOOR SCHEDULE. AND DETAILS FOR 1.1 GENERAL NOTES: PROTECT OWNER'S AND CLIENT'S PERSONNEL AND GENERAL PUBLIC FROM INJURY DUE TO 2. ALL NEW, EXISTING,AND MODIFIED PARTITIONS TO RECEIVE A LEVEL FOUR(4) DRYWALL FINISH INFORMATION AND LOCATIONS. 1. INCLUDE IN BASE BID ALL SERVICES, INCLUDING DESIGN, MATERIALS AND INSTALLATION AND 1. ALL NOTES IN THESE DOCUMENTS INSTRUCT THE GENERAL CONTRACTOR OR, AT HIS DISCRETION, SELECTIVE DEMOLITION WORK. FINISH PRIOR TO APPLICATION OF PAINT TO SURFACE TO AVOID PAINT FLASHING. WALL 2. REFER TO PLANS, R.C.P., FINISH LEGEND, AND DETAILS TO VERIFY FINISHES. REFER TO COORDINATION FOR ALL DESIGN/BUILD SERVICES LISTED OR REFERENCED IN THIS SECTION. HIS SELECTED SUBCONTRACTORS. 2. ERECT AND MAINTAIN DUST-PROOF PARTITIONS AND CLOSURES AS REQUIRED TO PREVENT FINISH LEVEL BASED ON GA-214-96"RECOMMENDED LEVELS OF GYPSUM BOARD FINISH." ELEVATIONS FOR ADDITIONAL FINISH INFORMATION OR WHERE MULTIPLE FINISHES ARE 2. REVIEW AND COORDINATE ALL DESIGN/BUILD COMPONENTS WITH ARCHITECT, INCLUDING BUT 2. IT IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO ENSURE ALL SUBCONTRACTORS SPREAD OF DUST OR FUMES TO OCCUPIED PORTIONS OF THE BUILDING. PROTECT REFER TO PARTITION TYPES FOR ADDITIONAL INFORMATION. INDICATED ON PLAN FOR THE SAME WALL. NOT LIMITED TO QUANTITIES, TYPES,AND LOCATIONS OF ALL ELEMENTS. RECEIVE THIS SHEET OF GENERAL NOTES IN ADDITION TO TRADE-SPECIFIC INFORMATION. MECHANICAL SYSTEM AS REQUIRED. 3. U.N.O. PARTITIONS ARE DIMENSIONED TO FACE OF PARTITION. 3. THE FINISH NAME TAKES PRECEDENT OVER THE FINISH PRODUCT NUMBER WHEN ORDERING 3. COORDINATE AND VERIFY NECESSARY FLOOR REINFORCEMENT STEEL AND/OR STRANDED 3. SHOULD THERE BE ANY QUESTIONS REGARDING THE CONTRACT DOCUMENTS, EXISTING 3. CONDUCT SELECTIVE DEMOLITION OPERATIONS AND DEBRIS REMOVAL IN A MANNER TO 4. U.N.O. EDGE OF DOOR TO BE LOCATED 5" OFF PERPENDICULAR WALL. PROVIDE BACK-TO- MATERIALS. CONTACT ARCHITECT WITH DISCREPANCIES BEFORE ORDERING MATERIALS. CABLES WITH FLOOR PENETRATIONS FOR ANY PLUMBING, HVAC, FIRE PROTECTION OR CONDITIONS, AND/OR DESIGN INTENT, OBTAIN CLARIFICATION FROM THE ARCHITECT PRIOR TO BID ENSURE MINIMUM INTERFERENCE WITH ROADS, STREETS, WALKS, AND OTHER ADJACENT BACK OR NESTED STUDS AT BOTH SIDES OF ALL NEW JAMB LOCATIONS. NESTED STUD 4. PATCH AND REPAIR EXISTING FINISHES AS REQUIRED WHERE DEMOLITION OR NEW ELECTRICAL WORK PRIOR TO ANY CONSTRUCTION. G.C. ASSUMES ALL RESPONSIBILITIES AND SUBMITTAL AND/OR PROCEEDING WITH ANY WORK, OR RELATED WORK, IN QUESTION. OCCUPIED OR USED FACILITIES. GAUGE TO MATCH PARTITION TYPE IN WHICH IT OCCURS OR 20-GAUGE, WHICHEVER GAUGE CONSTRUCTION OCCURS. NEW FINISHES TO MATCH EXISTING IN MANUFACTURER, COLOR, LIABILITIES AS A RESULT OF ANY FLOOR PENETRATIONS. COORDINATE WITH CLIENT, BUILDING 4. THESE CONTRACT DOCUMENTS ARE INTENDED TO DESCRIBE ONLY THE SCOPE AND APPEARANCE 4. MAINTAIN FIRE PROTECTION SERVICES DURING SELECTIVE DEMOLITION. IS HEAVIER. FINISH, AND TEXTURE. WHERE MATERIALS ARE NOT AVAILABLE FOR EXACT MATCH, SUBMIT OWNER AND ARCHITECT FOR APPROVAL OF ALL FLOOR PENETRATION LOCATIONS. OF THE REAL PROPERTY IMPROVEMENTS, INCLUDING THE PERFORMANCE AND LEVEL OF QUALITY 5. COVER AND PROTECT EQUIPMENT AND FIXTURES INDICATED"TO REMAIN" FROM SOILAGE OR 5. PROVIDE BLOCKING IN STUD WALLS BEHIND ITEMS SUPPORTED BY WALLS OF SIZES, PROPOSED REPLACEMENT MATERIALS TO ARCHITECT FOR BEFORE PURCHASE OR 4. PROVIDE SEPARATE ELECTRICAL METERING SYSTEM FOR NEW DEVICES UTILIZED SOLELY BY EXPECTED OF ITS COMPONENTS. IT IS INCUMBENT UPON THE CONTRACTOR TO ENSURE THAT ALL DAMAGE. LENGTHS AND HEIGHTS AS REQUIRED. ATTACH BLOCKING TO STUDS WITH TYPE, SIZE, INSTALLATION. THE CLIENT IF REQUIRED BY CLIENT OR BUILDING OWNER. WORK COMPLETED AND MATERIALS INSTALLED BE IN FULL COMPLIANCE,AS A MINIMUM STANDARD, 6. LOCATE, IDENTIFY, STUB OFF,AND DISCONNECT UTILITY SERVICES THAT ARE NOT INDICATED NUMBER AND SPACING OF ANCHORS AS REQUIRED TO PROPERLY SUPPORT LOADS OF 5. MAINTAIN AND PROTECT EXISTING FLOORING AND FINISHES NOTED TO REMAIN FOR DURATION 5. SUBMITTAL OF DESIGN/BUILD DOCUMENTS AS LISTED BELOW IS REQUIRED. G.C. TO OBTAIN WITH ALL APPLICABLE CODES, REGULATIONS, AND ORDINANCES HAVING JURISDICTION. TO REMAIN. ITEMS SUPPORTED. WHERE WOOD BLOCKING IS USED IT IS TO BE FIRE RETARDANT OF CONSTRUCTION. DOCUMENTS FROM SUBCONTRACTORS FOR CLIENT AND ARCHITECT REVIEW WITHIN(3) THREE 5. THOROUGHLY REVIEW THE CONTRACT DOCUMENTS PRIOR TO CONSTRUCTION AND AS 7. PERFORM SELECTIVE DEMOLITION WORK IN A SYSTEMATIC MANNER. TREATED. WHERE METAL IS USED PROVIDE MIN 1/8 INCH THICK PLATE, WELDED, SCREWED 6. PATCH AND REPAIR OR REPLACE ANY EXISTING FINISHES IN BUILDING COMMON AREAS WEEKS OF AWARD OF THIS CONTRACT. SUBMITTALS ARE REQUIRED TO ALLOW CLIENT AND AMENDMENTS MAY BE MADE AS CONSTRUCTION PROCEEDS. NOTIFY THE ARCHITECT OF ANY D 8. WHERE INDICATED ON DRAWINGS AS "SALVAGE AND STORE," CAREFULLY REMOVE INDICATED OR BOLTED TO METAL STUD FRAMING. IF PLATES ARE NOT LOCATED COMPLETELY BEHIND OUTSIDE SCOPE OF WORK IF DAMAGE OCCURS RELATED TO THE CONSTRUCTION OF THE ARCHITECT TO PROVIDE FEEDBACK ON DESIGN SOLUTIONS PRIOR TO PROCUREMENT AND DISCREPANCIES, CONFLICTS, INCONSISTENCIES, ERRORS OR OMISSIONS THAT MAY BE ITEMS, CLEAN, STORE,AND REUSE AS REQUIRED. DELIVER UNUSED ITEMS AT COMPLETION ITEMS SUPPORTED, LET PLATES INTO STUDS OR OTHERWISE CONFIGURE SO THAT THERE SCOPE OF WORK. CONSTRUCTION. NO EXCEPTIONS WILL BE MADE FOR UNSUBMITTED DOCUMENTS, AND ANY DISCOVERED. IN SUCH CASES, OBTAIN CLARIFICATION OR VERIFICATION OF INTENT FROM THE M OF PROJECT TO CLIENT. ARE NO VISIBLE BULGES IN SURFACE OF FINISHED GYPSUM BOARD DUE TO THICKNESS OF 7. ALL INTERIOR FINISHES TO MEET OR EXCEED APPLICABLE CODE REQUIREMENTS, INCLUDING WORK PERFORMED WITHOUT APPROVAL BY SUBMITTAL PROCESS WILL BE CORRECTED BY THE ARCHITECT PRIOR TO PROCEEDING WITH THE WORK. Z CM - 9. WHERE INDICATED ON DRAWINGS AS "SALVAGE AND DELIVER TO OWNER," CAREFULLY REMOVE PLATES BETWEEN STUDS AND GYPSUM BOARD. BUT NOT LIMITED TO FLAME SPREAD AND SMOKE DEVELOPMENT. G.C. OR SUBCONTRACTOR AT NO EXPENSE TO THE CLIENT. 6. VERIFY ALL DIMENSIONS SHOWN ON THE DRAWINGS AT THE PROJECT SITE. NOTIFY ARCHITECT OF INDICATED ITEMS, CLEAN, STORE,AND RETURN TO OWNER. 6. WHERE EXISTING WALLS, PARTITIONS, COLUMNS, FLOORS, BULKHEADS, SURFACES, OR 8. U.N.O.ALL PARTITIONS, EXTERIOR WALLS AND COLUMNS TO RECEIVE PAINT PT-1. 6. REFER TO DOCUMENTS FOR ADDITIONAL INFORMATION. ANY OMISSIONS, DISCREPANCIES,AND/OR CONFLICTS BEFORE PROCEEDING WITH THE WORK. W CM 10. U.N.O. REMOVE ALL EXISTING FLOORING(CARPET TILE, BROADLOOM CARPET, RESILIENT FINISHES ARE REMOVED OR PARTIALLY DEMOLISHED, EACH TRADE IS RESPONSIBLE FOR 9. U.N.O.ALL HOLLOW METAL FRAMES TO RECEIVE PAINT PT-2. REFER TO DOOR SCHEDULE FOR 7. DO NOT SCALE DRAWINGS, DIMENSIONS GOVERN. LARGE SCALE DETAILS GOVERN OVER SMALL W FLOORING, VINYL COMPOSITION TILE, CERAMIC TILE, STONE TILE,ALL BASE, ETC.)WITHIN PATCHING OR REFINISHING OF EXISTING CONSTRUCTION REQUIRED BY THAT TRADE'S ADDITIONAL INFORMATION. 1.2 HEATING,VENTILATION AND AIR CONDITIONING WORK("HVAC" OR"MECHANICAL"): SCALE. SCOPE OF WORK AREA. CLEAN AND PREPARE CONCRETE SLAB FLOOR AREA TO RECEIVE WORK ON THE PROJECT. THIS WORK MUST BE DONE IN A MANNER WHICH WILL ACCEPT 10. U.N.O.ALL METAL DOORS TO RECEIVE PAINT PT-2. REFER TO DOOR SCHEDULE FOR ADDITIONAL HVAC DESIGN/BUILD WORK SHALL INCLUDE, BUT NOT BE LIMITED TO, THE FOLLOWING: 8. DETAILS NOT SHOWN ARE TO BE SIMILAR IN CHARACTER TO THOSE DRAWN. WHERE SPECIFIC NEW FLOORING MATERIALS, INCLUDING REMOVAL OR SEALING OF ANY REMAINING EXISTING NEW FINISHES. INFORMATION. 1. MEET WITH CLIENT TO ESTABLISH CLIENT'S REQUIREMENTS. DIMENSIONS, DETAILS OR DESIGN INTENT CANNOT BE DETERMINED, OBTAIN CLARIFICATION FROM i ADHESIVE AS REQUIRED, PATCHING CRACKS, AND LEVELING OF FLOOR TO MEET REQUIRED 7. PREPARE EXISTING FLOOR SLABS FOR INSTALLATION OF SPECIFIED FLOOR FINISHES. 11. U.N.O.ALL PAINTED SURFACES TO RECEIVE A MINIMUM OF ONE (1) PRIMER COAT AND THEN 2. COMPUTE COOLING AND HEATING LOADS FOR THE PROJECT. THE ARCHITECT BEFORE PROCEEDING WITH THE WORK. TOLERANCES FOR SCHEDULED FINISHES. PERFORM MOISTURE TESTING ON FLOOR TO PREPARE EXISTING FLOOR SLABS TO BE SMOOTH AND LEVEL BEFORE INSTALLATION OF TWO(2) FINISH PAINT COATS. TINT PRIMER COAT PER MANUFACTURER'S SPECIFICATIONS. 3. VERIFY EXISTING MECHANICAL ZONES AND DETERMINE NEW ZONING REQUIREMENTS. 9. PERFORM ALL WORK IN CONFORMANCE WITH APPLICABLE WRITTEN CODES, ORDINANCES, LAWS, DETERMINE IF EXTENSIVE FLOOR PREP IS REQUIRED. FINISH FLOOR MATERIALS, WITH MAXIMUM DEVIATION OF 1/4" IN 10'-0". NO FLOOR 12. U.N.O.ALL PARTITIONS RECEIVING PAINT PT-3 TO RECEIVE A LEVEL FIVE(5) FINISH PRIOR TO COORDINATE ZONING WITH CLIENT AND OWNER. RULES, REGULATIONS AND REQUIREMENTS OF AUTHORITIES HAVING JURISDICTION. IF THE O 11. AS INDICATED ON PLANS, REMOVE EXISTING PARTITIONS, PANELS, SHELVING, CASEWORK, PREPARATION ALLOWANCES WILL BE ACCEPTED. G.C.AND HIS SUBCONTRACTORS TO PRIME AND FINISH COATS TO AVOID PAINT FLASHING. ADDITIONAL FINISH COATS WILL BE 4. DESIGN HVAC DISTRIBUTION AND CONTROL SYSTEM TO PROVIDE ADEQUATE COOLING AND CONTRACTOR PERFORMS OR PROCEEDS IN A MANNER CONTRARY TO ANY SUCH REQUIREMENTS Z ,� GLASS, ETC. VISUALLY INSPECT EXISTING FLOOR SLAB CONDITIONS TO ENSURE PROPER FLOOR REQUIRED. HEATING IN ACCORDANCE WITH ASHRAE STANDARDS. EQUIPMENT,AIR DISTRIBUTION, ETC. THE CONTRACTOR ASSUMES FULL RESPONSIBILITY THEREFORE AND SHALL BEAR COSTS N Q 12. U.N.O. REMOVE ALL EXISTING WALL COVERINGS WITHIN THE SCOPE OF WORK FROM WALLS PREPARATION IS INCLUDED IN PROPOSAL. 13. U.N.O.ALL GLASS IN DOORS AND SIDELITES TO BE GLASS GL-1. SHALL BE CAREFULLY DESIGNED FOR NOISE ISOLATION. RESULTING FROM NONCOMPLIANCE OR VIOLATION, INCLUDING COSTS ASSOCIATED WITH REPAIRING, AND PARTITIONS INDICATED TO REMAIN. PREPARE SURFACES TO ACCEPT NEW FINISHES. 8. PROVIDE 6" METAL STUDS AT ALL PARTITIONS WHERE NEW PLUMBING WASTE OR VENT 14. U.N.O.ALL WOOD DOORS AND TRIM TO RECEIVE STAIN ST-1. REFER TO DOOR SCHEDULE FOR 5. PROVIDE BUILDING STANDARD THERMOSTATS. PROVIDE LOCATION PLAN TO ARCHITECT FOR REPLACING OR OTHERWISE BRINGING THE WORK INTO CONFORMANCE. BRING TO THE ARCHITECT'S m Q 13. REMOVE ALL WALL-MOUNTED TACKBOARDS,WHITEBOARDS, FABRIC-WRAPPED PANELS, ETC. LINES ARE LOCATED. ADDITIONAL INFORMATION. REVIEW AND APPROVAL PRIOR TO INSTALLATION. FINISH TO MATCH EXISTING BUILDING ATTENTION ANY CONDITIONS REPRESENTED IN THE CONTRACT DOCUMENTS THAT ARE NOT IN IN ALL ROOMS IN SCOPE OF WORK. 9. COORDINATE QUANTITY AND LOCATION OF ALL ELECTRICAL AND COMMUNICATIONS 15. INSTALL ALL FLOORING PER MANUFACTURER'S RECOMMENDATIONS AND ACCEPTED INDUSTRY STANDARD. CONFORMANCE WITH APPLICABLE REQUIREMENTS. 14. WHERE WALLS OR PARTITIONS ARE TO BE REMOVED, REMOVE OR RELOCATE ALL EXISTING CONNECTIONS REQUIRED FOR ALL EQUIPMENT. REFER TO EQUIPMENT LEGEND FOR PRACTICES, INCLUDING BUT NOT LIMITED TO MOISTURE TESTING, FLOOR PREPARATION, 6. COORDINATE DESIGN WITH OTHER DESIGN/BUILD DISCIPLINES INVOLVED IN PROJECT. 10. BUILDING ACCESSIBILITY IS DESIGNED AND SHALL BE IBC, ANSI 117.1 2003 AND ADAAG WHICHEVER N ELECTRICAL WIRING, DATA CABLING, TELEPHONE LINES, CABLE LINES, SATELLITE LINES, ADDITIONAL ELECTRICAL AND COMMUNICATIONS REQUIREMENTS AT EQUIPMENT INSTALLATION METHOD, AND ADHESIVES. VERIFY WITH ALL MANUFACTURERS AND SUPPLIERS 7. SUBMIT HVAC DESIGN DOCUMENTS PREPARED BY A LICENSED MECHANICAL ENGINEER, STANDARD PROVIDES THE GREATEST DEGREE OF ACCESSIBILITY FOR ANY GIVEN BUILDING O CONDUIT,WIRE MOLD, RECEPTACLES AND SWITCH BOXES, ETC. LOCATED WITHIN DEMOLISHED LOCATIONS. PRIOR TO INSTALLATION. INCLUDING COOLING AND HEATING LOAD COMPUTATIONS, DISTRIBUTION SYSTEM DRAWINGS ELEMENT. r PORTIONS. 10. PROVIDE BUILDING STANDARD FIRE EXTINGUISHERS, REFER TO ARCHITECTURAL PLANS 16. U.N.O.ALL FLOORING TRANSITIONS TO BEGIN AT CENTERLINE UNDER DOOR. REFER TO SHOWING DUCT AND DIFFUSER LOCATIONS, FAN LOCATIONS AND SIZES, DEVICE AND 11. PERFORM ALL WORK IN CONFORMANCE WITH ALL BUILDING OWNER REQUIREMENTS, INCLUDING BUT 15. REMOVE ELECTRICAL TERMINATIONS, BOXES, CONDUIT,AND WIRING BACK TO SOURCE FOR QUANTITY AND LOCATIONS. TRANSITION DETAILS FOR ALL FLOORING CHANGES. EQUIPMENT SPECIFICATIONS AND CATALOG DATA AND THERMOSTAT LOCATIONS TO CLIENT, NOT LIMITED TO WORK HOURS, CONSTRUCTION PROCEDURES, MATERIAL DELIVERY AND STORAGE, PANEL. 11. REFER TO DESIGN/BUILD M.E.P.F.P. NOTES AND DESIGN/BUILD ELECTRICAL, MECHANICAL, 17. U.N.O.ALL RESILIENT BASE TO BE RESILIENT BASE RB-1,4"STRAIGHT AT CARPET AND 4"COVE AT GENERAL CONTRACTOR AND ARCHITECT FOR REVIEW PRIOR TO PROCUREMENT OR ELEVATOR AND RESTROOM ACCESS, PERSONAL CONDUCT, ETC. CONTACT OWNER FOR 16. CONFIRM SCOPE OF REMOVAL REQUIRED FOR EXISTING DATA AND PHONE CABLING WITH PLUMBING, AND FIRE PROTECTION DOCUMENTATION FOR ADDITIONAL INFORMATION. HARD SURFACE FLOORING. INSTALLATION. REQUIREMENTS, BUILDING OWNER AND CLIENT. 12. REUSE DOORS, FRAMES AND HARDWARE SALVAGED FROM PREVIOUS SCOPE. 18. ALL SWITCH AND OUTLET COVERPLATES TO BE WHITE. 8. OBTAIN BUILDING PERMIT AND INSPECTIONS AS REQUIRED BY AUTHORITY HAVING 12. PRODUCE AND DISTRIBUTE TO CONSTRUCTION TEAM A CONSTRUCTION SCHEDULE AT FIRST 17. U.N.O.ALL EXISTING WINDOW TREATMENTS IN SCOPE OF WORK AREA TO REMAIN. REPAIR OR CONTRACTOR TO SURVEY DOORS AND FRAMES TO DETERMINE WHICH ARE OF BEST JURISDICTION. CONSTRUCTION MEETING. SCHEDULE TO IDENTIFY MAJOR MILESTONES AND BE BROKEN DOWN BY REPLACE ANY DAMAGED BLINDS WITH BUILDING STANDARD MANUFACTURER, STYLE, CONDITION AND APPROPRIATE FOR SCHEDULED LOCATION. U.N.O.ALL PAINTED SURFACES TO RECEIVE THE FOLLOWING FINISHES: 9. INSTALL SYSTEM IN ACCORDANCE WITH DESIGN DOCUMENTS. TRADE. AT FIRST CONSTRUCTION MEETING, IDENTIFY AND INFORM CONSTRUCTION TEAM OF ALL FUNCTION, MOUNTING METHOD, AND COLOR. 13. ALL MATERIALS AND COMPONENTS OF FIRE-RATED ASSEMBLIES SHALL BE APPROVED BY GYP. BD.VERTICAL WALL SURFACES- EGGSHELL(SATIN) 10. BALANCE THE MECHANICAL SYSTEM. BALANCING SHALL BE PERFORMED BY A CERTIFIED CRITICAL PATH ITEMS, CRITICAL SEQUENCING AND DEADLINES,AND DATE OF SUBSTANTIAL ARCHITECTURE 18. U.N.O. REMOVE ALL EXISTING FLOOR OUTLETS AND ASSOCIATED WIRING, CABLING AND U.L. OR OTHER RECOGNIZED STANDARD FOR USE IN SUCH ASSEMBLIES, MAINTAIN ON GYP. BD. CEILINGS, SOFFITS, BULKHEADS-FLAT BALANCING TECHNICIAN. SUBMIT BALANCING REPORT TO OWNER. COMPLETION. � `� � � �° CONDUIT AND REPAIR FLOOR, MAINTAINING REQUIRED FLOOR ASSEMBLY RATING, TO BE PROJECT SITE A COPY OF THE APPLICABLE EDITION OF THE UL FIRE RESISTANCE METAL SURFACES-SEMI-GLOSS 11. PROVIDE ELECTRONIC AS-BUILT DRAWINGS TO ARCHITECT AND OWNER. 13. PRIOR TO THE START OF CONSTRUCTION, G.C.AND ALL SUBCONTRACTORS TO CONFIRM ALL FLUSH AND CONTINUOUS WITH ADJACENT FLOOR SURFACE, AS REQUIRED FOR NEW FINISH. DIRECTORY AND OTHER FIRE RESISTIVE STANDARDS REFERENCED IN THE CONTRACT WOOD SURFACES-SEMI-GLOSS 12. REFER TO DOCUMENTS FOR ADDITIONAL INFORMATION. MATERIALS AND FINISHES WITHIN SCOPE OF WORK ARE AVAILABLE IN SUFFICIENT QUANTITY AND 720 OLIVE STREET,SUITE 200 SAINT LOUIS, M063101 19. REMOVE ALL EXISTING INTERIOR BUILDING SIGNAGE IN SCOPE OF WORK, INCLUDING BUT NOT DOCUMENTS FOR USE BY INSPECTORS AT TIMES OF INSPECTION. CONCRETE MASONRY UNIT-EGGSHELL WITHIN THE REQUIRED TIMEFRAME ESTABLISHED IN THE CONSTRUCTION SCHEDULE. G.C. TO T 314 206 7100 F 314 231 9801 LIMITED TO, ROOM SIGNAGE, DOOR SIGNAGE, ETC. 14. PROVIDE THROUGH PENETRATION FIRESTOP SYSTEMS FOR ALL ITEMS PENETRATING FIRE- 1.3 ELECTRICAL WORK: INFORM CLIENT AND ARCHITECT OF ANY MATERIALS OR FINISHES THAT ARE NOT IN STOCK, WILL NOT 20. HAZARDOUS MATERIALS: CLIENT ACCEPTS SOLE RESPONSIBILITY FOR COMPLIANCE WITH ALL RATED ASSEMBLIES. PENETRATIONS TO BE DESIGNED, TESTED,AND FIRE-RESISTANCE ELECTRICAL DESIGN/BUILD WORK SHALL INCLUDE, BUT NOT BE LIMITED TO, THE FOLLOWING: BE AVAILABLE IN TIME TO MEET THE CONSTRUCTION SCHEDULE REQUIREMENTS, OR WHERE THE FEDERAL, STATE,AND LOCAL LAWS RELATING TO THE ENVIRONMENT, INCLUDING BUT NOT RATED TO RESIST FOR A PRESCRIBED PERIOD OF TIME THE SPREAD OF FIRE THROUGH 1. MEET WITH CLIENT TO ESTABLISH CLIENT'S REQUIREMENTS. SUBCONTRACTOR OR SUPPLIER IS UNABLE OR UNWILLING TO COMMIT TO THE CONSTRUCTION LIMITED TO THE NATIONAL EMISSIONS STANDARDS FOR HAZARDOUS AIR POLLUTANTS AND PENETRATIONS. PROVIDE UL-LISTED ASSEMBLIES AS REQUIRED. 2. DESIGN A COMPLETE LIGHTING AND CONTROL SYSTEM INCORPORATING THE REQUIREMENTS SCHEDULE. THE OCCUPATIONAL SAFETY AND HEALTH ACT. THE ARCHITECT AND ARCHITECT'S 15. REFER TO FURNITURE/ELECTRICAL/COMMUNICATIONS REFERENCE DRAWINGS FOR SHOWN ON THE DRAWINGS. 14. PROVIDE STRUCTURAL TESTS AND SPECIAL INSPECTIONS AS REQUIRED BY CODE, CONSULTANTS SHALL HAVE NO RESPONSIBILITY FOR THE DISCOVERY, PRESENCE, HANDLING, ADDITIONAL ELECTRICAL, COMMUNICATIONS, AND FURNITURE INFORMATION. 3. ALL FIXTURES TO BE AS SPECIFIED ON DESIGN/BUILD DOCUMENTS. PREPARE COMPLETE 15. CONTRACTOR TO MAINTAIN, ONSITE,A COPY OF THE APPLICABLE EDITION OF THE UL FIRE REMOVAL, OR DISPOSAL OF OR EXPOSURE OF PERSONS TO HAZARDOUS MATERIALS IN ANY 16. PROVIDE AND INSTALL ADA COMPLIANT BUILDING STANDARD FIRE EXTINGUISHERS AS DESIGN SPECIFICATION AND SUBMIT TO ARCHITECT FOR REVIEW. RESISTANCE DIRECTORY OF USE BY INSPECTOR AT TIME OF INSPECTION. FORM AT THE PROJECT SITE, INCLUDING BUT NOT LIMITED TO ASBESTOS,ASBESTOS REQUIRED BY AND IN ACCORDANCE WITH NFPA LIFE SAFETY CODE AND LOCAL BUILDING 4. PROVIDE REQUIRED LIFE SAFETY LIGHTING, INCLUDING BUT NOT LIMITED TO EMERGENCY 16. CONTRACTOR TO PARTICIPATE IN WEEKLY PROGRESS UPDATE CONFERENCE CALLS AND PROVIDE PRODUCTS, POLYCHLORINATED BIPHENYL(PCB) OR OTHER TOXIC SUBSTANCES. FIRE SAFETY CODE AND REGULATIONS. CONFIRM QUANTITY AND LOCATION WITH EGRESS LIGHTING AND ILLUMINATED EXIT SIGNAGE, IN ACCORDANCE WITH ALL CODE PHOTOS AS OUTLINED IN PROVIDED BID DOCUMENT. 21. PROVIDE BY-PASS CONNECTIONS AS NECESSARY TO MAINTAIN CONTINUITY OF SERVICE TO AUTHORITY HAVING JURISDICTION PRIOR TO ORDERING. REQUIREMENTS, OCCUPIED AREA OF THE BUILDING 5. PREPARE SWITCHING CONTROL DESIGN INCORPORATING ARCHITECT'S DESIGN AND SUBMIT TO DEFINITION OF TERMS: 22. REVIEW/COORDINATE SCHEDULE OF WORK TO BE DEMOLISHED WITH BUILDING MANAGEMENT ARCHITECT FOR REVIEW. TO LIMIT INTERRUPTIONS OF OWNER AND OTHER TENANT OCCUPIED SPACES. 6. PROVIDE DEVICES AND PLATES, AS NOTED ON DOCUMENTS. 1. THE WORD"CLIENT"AS USED IN THESE DOCUMENTS REFERS TO THE ENTITY WHO HAS CONTRACTED 23. WHERE EXISTING WALLS, BULKHEADS OR FINISHES ARE REMOVED OR PARTIALLY DEMOLISHED, GENERAL NOTES: REFLECTED CEILING PLAN 7. WHERE SPECIFIC LAMPS ARE NOT SHOWN, PROVIDE LAMPS MOST SUITABLE FOR THE THE ARCHITECT TO PERFORM PROFESSIONAL SERVICES ON THIS PROJECT. EACH TRADE SHALL BE RESPONSIBLE FOR PATCHING OR REFINISHING OF EXISTING APPLICATION AND SUBMIT TO ARCHITECT FOR APPROVAL. 2. THE WORD"PROJECT"AS USED IN THESE DOCUMENTS REFERS TO THE SCOPE OF WORK DESCRIBED IN CONSTRUCTION REQUIRED BY THAT TRADES WORK ON THE PROJECT. THIS WORK MUST BE 1. REVIEW CEILING LAYOUT AS SHOWN AND NOTIFY ARCHITECT OF ANY CONFLICTS WITH 8. AT PROJECT COMPLETION, CLEAN ALL LIGHT FIXTURES. THESE DOCUMENTS. DONE IN A MANNER WHICH WILL ACCEPT NEW FINISHES. STRUCTURAL, ELECTRICAL, MECHANICAL, PIPEWORK, FIRE PROTECTION SYSTEMS, ETC. 9. DESIGN A POWER SUPPLY SYSTEM INCORPORATING REQUIREMENTS SHOWN ON ARCHITECT'S 3. THE WORDS"CONTRACTOR", "GENERAL CONTRACTOR",AND"G.C."AS USED IN THESE DOCUMENTS BEFORE PROCEEDING WITH CONSTRUCTION. DRAWINGS AND IN ACCORDANCE WITH ALL CODE REQUIREMENTS. REFER TO THE GENERAL CONTRACTOR SELECTED BY THE CLIENT TO PERFORM THE WORK DESCRIBED 2. U.N.O. LIGHTING LOCATIONS TAKE PRECEDENCE OVER ALL OTHER CEILING ELEMENTS. 10. COORDINATE ALL ELECTRICAL REQUIREMENTS WITH OTHER SYSTEMS- INCLUDING BUT NOT IN THESE DOCUMENTS.ALL NOTES IN THESE DOCUMENTS INSTRUCT THE GENERAL CONTRACTOR. MECHANICAL, PLUMBING,AND FIRE PROTECTION WORK MUST ACCOMMODATE LOCATIONS AND LIMITED TO HVAC, FIRE PROTECTION, PLUMBING, COMMUNICATIONS, AND SECURITY SYSTEMS. 4. THE WORD"ARCHITECT"AS USED IN THESE DOCUMENTS REFERS TO THE ARCHITECT OF RECORD FOR CLEARANCES FOR ALL NEW AND EXISTING LIGHT FIXTURES, G.C. IS RESPONSIBLE TO COORDINATE POWER AVAILABILITY, LOCATION, EXISTING RESTRICTIONS AND OTHER THIS PROJECT, ONE ARCHITECTURE. COORDINATE WITH ALL TRADES. REQUIREMENTS WITH OWNER. 5. THE WORDS"CONSTRUCTION TEAM" REFER TO ALL PARTIES INVOLVED IN THE CONSTRUCTION PHASE, 3. IDENTIFY AND COORDINATE LOCATIONS FOR ALL CEILING ELEMENTS INCLUDING LIGHTING, 11. COORDINATE ALL BUILDING SECURITY REQUIREMENTS WITH OWNER AND CLIENT. INCLUDING BUT NOT LIMITED TO: THE CLIENT AND THEIR CONSULTANTS;THE GENERAL CONTRACTOR AND MECHANICAL DIFFUSERS, RETURN AIR GRILLES, FIRE PROTECTION DEVICES,ACCESS PANELS, 12. DEVELOP COMPLETE ELECTRICAL DESIGN AND INSTALLATION DRAWINGS PREPARED BY A ALL SUBCONTRACTORS; AND THE ARCHITECT. EXIT SIGNS,AUDIOVISUAL EQUIPMENT, SECURITY DEVICES, ETC.WITH ARCHITECT BEFORE LICENSED ELECTRICAL ENGINEER AND SUBMIT FOR ARCHITECT'S REVIEW. 6. THE WORD"ALIGN"AS USED IN THESE DOCUMENTS SUPERSEDES ANY DIMENSIONAL INFORMATION INSTALLATION. 13. DESIGN AND INSTALL BUILDING FIRE ALARM SYSTEM COMPLIANT WITH ALL APPLICABLE CODE INDICATED. IF DISCREPANCIES OCCUR, NOTIFY ARCHITECT IMMEDIATELY. 4. NOTIFY ARCHITECT OF ANY REQUIREMENTS FOR ACCESS PANELS NOT SHOWN ON REQUIREMENTS. COORDINATE REQUIREMENTS WITH BUILDING OWNER. 7. THE WORD"PROVIDE"AS USED IN THESE DOCUMENTS MEANS FURNISH AND INSTALL. DOCUMENTS BEFORE PROCEEDING WITH CONSTRUCTION. 14. PROVIDE BUILDING STANDARD FIRE STROBES THAT COMPLY WITH CODE REQUIREMENTS. 8. THE WORDS"NOT IN CONTRACT"AND"N.1.C."AS USED IN THESE DOCUMENTS REFER TO WORK OR 5. ALL EXPOSED CEILING EDGES TO BE FINISHED. PROVIDE LOCATION PLAN TO ARCHITECT FOR REVIEW AND APPROVAL PRIOR TO INSTALLATION. EQUIPMENT PROVIDED OUTSIDE THE CONTRACT SCOPE REPRESENTED IN THESE DOCUMENTS. THE 6. IN AREAS WHERE DEMOLITION OCCURS AND THE ADJACENT SUSPENDED ACOUSTICAL CEILING 15. OBTAIN BUILDING PERMIT AND INSPECTIONS AS REQUIRED BY AUTHORITY HAVING CONTRACTOR SHALL COORDINATE HIS WORK WITH ALL PARTIES FURNISHING AND/OR INSTALLING N.I.C. ARCHITECT OF RECORD: SYSTEM IS INDICATED TO REMAIN, PATCH EXISTING ACOUSTICAL CEILING GRID TO MATCH JURISDICTION. ITEMS AND COOPERATE TO AFFECT THE IMPLEMENTATION OF SUCH WORK OR INSTALLATION. EXISTING CEILING GRID HEIGHT, STYLE AND ORIENTATION. 16. FIELD VERIFY EXISTING CONDITIONS AND REVIEW WITH ARCHITECT PRIOR TO DESIGNING AND 9. THE WORD"CLEAR"AS USED IN THESE DOCUMENTS SHALL MEAN THAT THE CONDITION IS NOT 7. COORDINATE AND VERIFY LOCATION OF LIGHT SWITCHES, THERMOSTATS, FIRE ALARMS, ETC. INSTALLING SYSTEM OR FIXTURES. NOTIFY ARCHITECT OF ANY DISCREPANCIES OR CONFLICTS ADJUSTABLE WITHOUT THE APPROVAL OF THE ARCHITECT. CLEAR DIMENSIONS ARE TYPICALLY TO WITH ARCHITECT BEFORE INSTALLATION. REFER TO DEVICE LOCATION DIAGRAM. PRIOR TO COMMENCEMENT OF CONSTRUCTION. FINISH FACE OF MAJOR SURFACE. COORDINATE REQUIREMENTS FOR CONVECTORS(BASE BOARD 8. ELECTRICAL CONTRACTOR TO COORDINATE SWITCHING AND DIMMING REQUIREMENTS WITH 17. INSTALL THE SYSTEM IN ACCORDANCE WITH THE DESIGN/BUILD DOCUMENTS. HEATERS) OR OTHER PROTRUSIONS WITH ARCHITECT. ARCHITECT. 18. REFER TO DOCUMENTS FOR ADDITIONAL INFORMATION. 10. THE WORD"MAXI MUM"AS USED IN THESE DOCUMENTS SHALL MEAN THE CONDITION IS SLIGHTLY DA 9. U.N.O. LIGHTING IN EACH ROOM TO BE SWITCHED FROM ONE LOCATION WITHIN THAT ROOM. 19. PROVIDE ELECTRONIC AS-BUILT DRAWINGS TO ARCHITECT AND CLIENT. ADJUSTABLE BUT MAY NOT VARY TO A DIMENSION OR QUANTITY GREATER THAN THAT SHOWN WITHOUT c.�`t f 10. U.N.O.ALL LIGHT FIXTURE TYPES WITHIN EACH ROOM OR OPEN OFFICE AREA TO BE SWITCHED APPROVAL OF THE ARCHITECT. C?~ STI S S"): SEPARATELY. GANG ALL LIGHT SWITCHES IN EACH ROOM UNDER A SINGLE COVERPLATE. 1_4 TELECOMMUNICATIONS AND DATA COMMUNICATIONS WORK("COMMUNICATION11. THE WORD"MINIMUM"AS USED IN THESE DOCUMENTS SHALL MEAN THE CONDITION IS SLIGHTLY 11. CLEAN AND/OR REPAIR AND RELAMP ALL EXISTING LIGHT FIXTURES TO REMAIN AS NEEDED TO COMMUNICATIONS DESIGN/BUILD WORK SHALL INCLUDE, BUT NOT BE LIMITED TO, THE FOLLOWING: ADJUSTABLE BUT MAY NOT VARY TO A DIMENSION OR QUANTITY LESS THAN THAT SHOWN WITHOUT PERFORM AS NEW. 1. MEET WITH CLIENT TO ESTABLISH CLIENT'S REQUIREMENTS. APPROVAL OF THE ARCHITECT. • 12. U.N.O. INSTALL LINEAR DIFFUSERS IN ALL GYP. BD.AND A.C.T. CEILINGS. 2. CLIENT TO PROVIDE WRITTEN SCOPE DOCUMENTS &SPECIFICATIONS. 12, THE WORD"TYPICAL"AS USED IN THESE DOCUMENTS SHALL MEAN THE CONDITION OR DIMENSION IS THE PHOENIX,ARIZONA 13. U.N.O.ALL SPRINKLER HEADS IN GYP. BD.AND A.C.T. CEILINGS TO MATCH BUILDING STANDARD. 3. DESIGN AND PROVIDE A TELECOMMUNICATIONS AND DATA COMMUNICATIONS NETWORK, SAME OR REPRESENTATIVE FOR SIMILAR CONDITIONS THROUGHOUT. ,� p CONFIRM TYPE PRIOR TO ORDER. CENTER ALL SPRINKLER HEADS IN A.C.T.WITH A MAXIMUM 3" INCLUDING CABLING AND SERVICE TO BUILDING, AS REQUIRED BY CLIENT. REFER TO F-SERIES 13. THE SYMBOL"+/-"AS USED IN THESE DOCUMENTS SHALL MEAN THE DIMENSION OR QUANTITY IS OF C30DEVIATION. DRAWINGS FOR ADDITIONAL INFORMATION. ADJUSTABLE TO ACCOMMODATE ACTUAL CONDITIONS. IF ACTUAL DIMENSION VARIES BY MORE THAN 1" 14. REFER TO DESIGN/BUILD DRAWINGS FOR ADDITIONAL INFORMATION. 4. OBTAIN BUILDING PERMIT AND INSPECTIONS AS REQUIRED BY AUTHORITY HAVING FROM DIMENSION NOTED AS"+/-", INFORM ARCHITECT BEFORE PROCEEDING. 7-08-15 15. REFER TO DESIGN/BUILD ELECTRICAL DRAWINGS FOR EMERGENCY EGRESS LIGHTING JURISDICTION. QUANTITY AND LOCATION. EXIT SIGNAGE IS SHOWN IN PLANS ONLY TO IDENTIFY PATHS OF 5. FIELD VERIFY EXISTING CONDITIONS AND REVIEW WITH ARCHITECT PRIOR TO DESIGNING AND EGRESS. INSTALLING SYSTEM OR FIXTURES. NOTIFY ARCHITECT OF ANY DISCREPANCIES OR CONFLICTS SUBMITTALS ISSUE DATE DESCRIPTION PRIOR TO COMMENCEMENT OF CONSTRUCTION. 4/27/2015 LANDLORD REVIEW SET 6. REFER TO DOCUMENTS FOR ADDITIONAL REQUIREMENTS. 1. SUBMIT ALL SUBCONTRACTOR SHOP DRAWINGS AND SUBMITTALS TO ARCHITECT FOR APPROVAL 6/15/2015 BID SET 7. PROVIDE ELECTRONIC AS-BUILT DRAWINGS TO ARCHITECT AND CLIENT. BEFORE FABRICATION OR INSTALLATION OF ANY ITEMS. 2. SUPPLY AN ELECTRONIC COPY OF ALL SHOP DRAWINGS AND SUBMITTALS AND 5 MATERIAL SAMPLES 7/7/2015 PERMIT SET 1.4 FIRE PROTECTION WORK: FIRE PROTECTION DESIGN/BUILD WORK SHALL INCLUDE, BUT NOT BE LIMITED T0, THE FOLLOWING: (WHERE APPROPRIATE):ARCHITECT, GENERAL CONTRACTOR, SUBCONTRACTOR, FIELD COPY,ANDCLIENT. 1. MEET WITH CLIENT TO ESTABLISH CLIENT'S REQUIREMENTS. 3. REQUIRED SHOP DRAWING SUBMITTALS INCLUDE, BUT ARE NOT LIMITED TO: MILLWORK, H.V.A.C., Revision Schedule .2. DESIGN ALL SYSTEMS IN ACCORDANCE WITH NFPA-LIFE SAFETY CODE AND IN ACCORDANCE PLUMBING, ELECTRICAL, GLASS AND GLAZING, DOOR HARDWARE,ALL ITEMS ON FINISH LEGEND, 2'X2' WITH LOCAL BUILDING AND FIRE SAFETY CODES AND REGULATIONS CURRENTLY IN FORCE. WALL FINISH SAMPLE, PAINTING AND WALLCOVERING. No. Date Description 3. COORDINATE WORK WITH EXISTING AND PROPOSED ARCHITECTURAL, HVAC AND ELECTRICAL 4. CONTRACT DOCUMENTS SHALL NOT BE REPRODUCED AS THE BASIS FOR REQUIRED SUBMITTALS INSTALLATIONS. REVIEW LOCATIONS AND DESIGN OF ACCESS PANELS,VALVES, CONTROLS UNLESS PRIOR WRITTEN PERMISSION HAS BEEN OBTAINED FROM THE ARCHITECT. AND SIGNS WITH CLIENT AND ARCHITECT. 5. SUBMITTALS CONTAINING CONTRACT DOCUMENTS OR PORTIONS OF CONTRACT DOCUMENTS WILL BE 4. OBTAIN BUILDING PERMIT AND INSPECTIONS AS REQUIRED BY AUTHORITY HAVING REJECTED AND RETURNED TO THE CONTRACTOR WITHOUT ACTION OR COMMENT, AND ARE NOT TO BE JURISDICTION. USED FOR PROCUREMENT, FABRICATION OR INSTALLATION OF ANY WORK IN THE PROJECT. 5. INSTALL WORK, IN ACCORDANCE WITH DESIGN DOCUMENTS, TEST SYSTEM AND OBTAIN NECESSARY CODE INSPECTIONS&APPROVALS. 6. REFER TO DOCUMENTS FOR ADDITIONAL REQUIREMENTS. 7. PROVIDE ELECTRONIC AS-BUILT DRAWINGS TO ARCHITECT AND CLIENT WITH ALL CABLING AND EXISTING CONDITIONS AND CHANGE ORDERS TERMINATIONS LABELED, 1. EXISTING CONDITIONS SHOWN ON THESE DRAWINGS ARE BASED UPON BASE BUILDING OR OTHER CONSTRUCTION DOCUMENTS MADE AVAILABLE TO THE ARCHITECT BY THE OWNER. UNLESS OTHERWISE NOTED,AS-BUILT ARCHITECTURAL CONDITIONS HAVE BEEN PARTIALLY FIELD VERIFIED AND MAY VARY FROM THOSE SHOWN. 2. PRIOR-TO SUBMITTING THE CONSTRUCTION BID, THE CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD VERIFYING ALL EXISTING CONDITIONS AND ANY CRITICAL DIMENSIONS ASSOCIATED WITH THE PROPOSED WORK. THE CONTRACTOR SHALL CONFIRM THAT ALL WORK OUTLINED WITHIN THESE DOCUMENTS MAY BE ACCOMPLISHED AS SHOWN, PRIOR TO THE COMPLETION OF THE BIDDING PROCESS,AND SHALL NOTIFY BOTH THE ARCHITECT AND THE BUILDING OWNER OF ANY CONDITIONS ENCOUNTERED WHICH MAY EFFECT BUILDING CODE COMPLIANCE, LIFE SAFETY AND ASSURANCE OF A CERTIFICATE OF OCCUPANCY, THE TIMELY COMPLETION FOR THE PROJECT OR ESTABLISHED BUDGET OF SUCH WORK. 3. NO ADDITIONAL FUNDS WILL BE APPROVED FOR WORK OMITTED FROM THE CONSTRUCTION BID DUE TO LACK OF VERIFICATION BY THE CONTRACTOR, EXCEPT AS OTHERWISE APPROVED BY THE OWNER i FOR WORK ASSOCIATED WITH"HIDDEN" CONDITIONS NOT ACCESSIBLE PRIOR TO CONSTRUCTION. Key Plan: SFE •J _ Project Number: 15.2390.00 Sheet Title: GENERAL NOTES k KEYED NOTES: DEMOLITION _.PI ; 1. EXISTING FIRE EXTINGUISHER TO REMAIN AT THIS LOCATION.VERIFY IN GOOD WORKING ORDER. i , 2. U.N.O. EXISTING CEILING GRID TO REMAIN THROUGHOUT. PROTECT FROM DAMAGE. PATCH/REPAIR AS NEEDED AND REPLACE ANY DAMAGED OR STAINED TILES. SEE RCP ON A-401 ` FOR ADDITIONAL INFORMATION. I 3. REMOVE AND STORE DOOR AND FRAME AT THIS LOCATION FOR RE-USE. PROTECT FROM DAMAGE. RETURN ANY UN-USED DOORS/FRAMES TO OWNER. 4. EXISTING IT CLOSET AND EQUIPMENT TO REMAIN. PROTECT FROM DAMAGE. 5. EXISTING BREAKROOM MILLWORK, PLUMBING,AND APPLIANCES TO REMAIN. PROTECT FROM DAMAGE AND VERIFY IN GOOD WORKING ORDER. \ w M - - - - - - - - - — — 3 - - - - - -- O - - - - - - - 3. C_♦ W CYN W � _ 2 � N � i4 720 OLIVE STREET, SUITE 200 SAINT LOUIS, MO 63101 T 314 206 7100 F 314 231 9801 � u . ��Ak - 1I t I I I I I ! I E I ! I I I ! w I I 1 1 1 1 1 1 t 1 I ! I I I ft- m 4 I ! I I I I I II UP�-- O I F.E. O n S, 1 DEMOLITION PLAN A 201 1/411 — 11-011 ARCHITECT OF RECORD: DA Z I O KEYED NOTES: PLAN 'sTIN 1. PROVIDE BLOCKING FOR T.V.'S. CENTER TV ON WALL. REFER TO FURNITURE/DATA PLAN AND DEVICE DIAGRAM 16/F-201 FOR ADDITIONAL INFORMATION. PHOENIX RELOCATED DOOR AND FRAME AT THIS LOCATION. t11 ARIZONA ADD A DOOR LIGHT KIT AT THIS LOCATION. MATCH DOOR TYPE B ON A-901. - OF 0 104 N 103 102 7-08-15 ISSUE DATE DESCRIPTION r . 4/27/2015 LANDLORD REVIEW SET 3 6/15/2015 BID SET Y ALIGN ALIGN 2'-0" 6" 2'-0" 6" � 7/7/2015 PERMIT SET � � O OtjO 1 105 O O1 Revision Schedule O � No. Date Description 1 06/30/15 1 BULLETIN 1 s 105 ' 101 <Y� N 4 4 _ 101-101, 28'-5112" y O 01 ALIGN , 1 ,07 � .. Key Plan: WE N 106 107 ALIGN m : -- ------------- w -__ w y 1 I i I I I I I I l 100 €= r_ a.�_ ROOM SCHEDULE � ; IItIlI Number Name Project Number: 15.2390.00 100 ENTRY/WAITING I I I c I w. F.E. 101 OPEN OFFICE Sheet Title: € I E o ---- -- !--E-_--I--�_-- O - 100 "' 102 PRIVATE OFFICE DEMOLITION PLAN,ARCHITECTURAL 103 PRIVATE OFFICE PLAN,AND ELEVATIONS 104 PRIVATE OFFICE 105 CONFERENCE ROOM 106 IT CLOSET 107 WORK/BREAK ROOM �, 21 ARCHITECTURAL PLAN A-201 1/411 = 1'-0" y s. KEYED NOTES: CEILING Z � 1. EXISTING CEILING GRID AND TILES TO REMAIN. PATCH/REPAIR AS NEEDED AND REPLACE DAMAGED OR STAINED TILES. Q 2. U.N.O., EXISTING LIGHT FIXTURES TO REMAIN. VERIFY IN GOOD WORKING R R R v R 1 I ORDER. I 3. RELOCATE EXISTING 2X4 LIGHT FIXTURE AT THIS LOCATION. VERIFY IN GOOD WORKING ORDER. 104 103 102 4. PROVIDE FIXTURE ON NIGHT LIGHT CIRCUIT. 5. NEW EXIT SIGN AT THIS LOCATION. USE SPEC LITHONIA#LHQM-S-W-3-R. 6. IF NOT EXISTING, PROVIDE AND INSTALL NEW EMERGENCY WALL LIGHT. COORDINATE WITH ELECTRICAL CONTRACTOR AND FIRE MARSHAL FOR FINAL COUNT AND LOCATION. USE SPEC, LITHONIA#ELM2 Y R R R "'0110 N f W 6 3 ?,5 TYP. R R R O R Z .� m O � 105 j Y N N C'3 E E E R TYP. 101 ._ 106 E ' 720 OLIVE STREET, SUITE 200 SAINT LOUIS, MO 63101 1 T 314 206 7100 F 314 231 9801 F R R E M 107 a 6 E E R 100 Li-- ----------------- --—T- O E E s 3 <...__ --- ----- — ----L- JO r n -46 l k REFLECTED CEILING PLAN A-401 1/4 = 1 -0 . ARCHITECT OF RECORD. DA TI C 1. G.C. TO PROVIDE AND INSTALL TRANSITION STRIP BY JOHNSONITE OR PHOENIX,ARIZONA APPROVED EQUAL: COLOR TO MATCH RB-1. SEE DETAILS 8/A-901 FOR MORE t jl INFORMATION. a 2. TOUCH UP ANY SCRATCHES AND MARKS ON EXISTING DOORS TO LIKE NEW OF 00 104 103 102 CONDITION. 7-08-15 CPT-1 CPT-1 CPT-1 RB-1 RB-1 RB_1 ISSUE DATE DESCRIPTION 4/27/2015 LANDLORD REVIEW SET a' 6/15/2015 BID SET FINISH LEGEND 7/7/2015 PERMIT SET � y O O O CARPET PAINT CPT-1 MFG:J&J INVISION PT-1 MFG: GLIDDEN PAINTS Revision Schedule PATTERN: CORRUGATED, MODULAR COLOR: WHITE WHISPER COLOR: 501 MIRROR NO.44YY 84/042 No. Date Description SIZE:24"X 24" ORDER NO. A0051 w TYPE: CARPET TILE (FIELD) F BACKING: NEXUS BACKING PT-2 y - INSTALLATION: QUARTER TURN MFG: GLIDDEN PAINTS COLOR: NOBLE GRAY NOTE:ALL CARPETING MATERIAL TO BE NO.30BB 10/019 PROVIDED BY TENANT. CONTRACTOR TO ORDER N0. A2002 PROVIDE FOR RECEIPT AND INSTALLATION. (H.M. DOOR FRAMES) 105 PT-3 MFG:SHERWIN WILLIAMS CPT-1 CPT-1 RESILIENT FLOORING COLOR: NAVAL NO. SW 6244F RB_1 RB-1 VCT-1 MFG: MANNINGTON (RECEPTION ACCENT) COLLECTION: ASSURANCE SQUARED STYLE: 16403 ICOLOR: BISQUE p- SIZE: 18"X 18" STAIN ST-1 STAIN MATCH TO EXISTING DOORS RESILIENT BASE AND TRIM RB-1 MFG: JOHNSONITE GLASS STYLE NAME: MILLWORK REVEAL PROFILE ,. SIZE 4" GL-1 1/4"TEMPERED GLASS v, COLOR: 63-BURNT UMBER b I yT � 106 Key Plan: sr� i RB-1 rn y ' v I I I ! I t I k I I I CC IE ROOM SCHEDULE Number Name Project Number: 15.2390.00 i --': i 100 ENTRY/WAITING Sheet Title: 102 PRIVATE OFFICE REFLECTED CEILING PLAN, FINISH PLAN, 101 OPEN OFFICE AND FINISH LEGEND Q o 0 0 ® �. 103 PRIVATE OFFICE 104 PRIVATE OFFICE t. _. 105 CONFERENCE ROOM 106 IT CLOSET 107 WORK/BREAK ROOM ., 21 FINISH PLAN A-401 1/4 = 1 -0 I DOOR SCHEDULE-NEW Door Frame Hardware Number Type Width Height Finish Type Frame Finish Group Remarks First Floor 100 EXIST T-0" 7 -0" EXTG EXTG PT-2 EXTG 102 RELOC T-0" T-0" ST-1 RELOC PT-2 1 103 RELOC T-0" T-0- ST1 RELOC _ PT-2 ' 1 104 RELOC T-0" T-0" ST1 RELOC PT-2 1 ADD GLASS LIGHT KIT TO MATCH DOOR TYPE B 105 B T-0" T-0" ST1 1 P1-2 1 WOOD SPECIES TO MATCH EXISTING 106 EXIST 3'-0" T-0" ' ST-1 EXTG PT-2 EXTG 107 A 3'-0" T-0" ST-1 1 PT-2 2 WOOD SPECIES TO MATCH EXISTING r� W GENERAL NOTES" DOOR, FRAME, & HARDWARE Z 1. FIELD VERIFY ACCURACY OF ALL CONDITIONS AND NOTIFY ARCHITECT OF ANY DISCREPANCIES. N 2. REPAIR FINISH ON ALL EXISTING DOORS TO REMAIN WITHIN SCOPE OF WORK, INCLUDING FILLING, SANDING, STAINING,AND/OR REFINISHING AS REQUIRED TO RETURN DOOR TO AS NEW APPEARANCE W h 3. ALL MEANS OF EGRESS DOORS SHALL BE READILY OPENABLE FROM THE SIDE WHICH EGRESS IS TO BE MADE WITHOUT THE USE OF A SPECIAL KEY OR SPECIAL KNOWLEDGE OR SPECIAL EFFORT, 4. DOOR OPERATING DEVICES SHALL BE CAPABLE OF OPERATION WITH ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING,TIGHT PINCHING OR TWISTING OF THE WRIST. ALL DOORS SHALL HAVE ADA COMPLIANT LEVER HANDLES UNLESS NOTED OTHERWISE. �✓ 5. CONTRACTOR TO COORDINATE KEYING WITH PROPERTY MANAGER AND TENANT. ALL SPECIAL LOCKING ARRANGEMENTS TO COMPLY WITH APPLICABLE BUILDING CODE REQUIREMENTS.THE TENANT ENTRY DOORS SHALL BE PLACED ON A BUILDING SUB-MASTER. FOUR COPIES OF THE BUILDING SUB MASTER SHOULD BE SUPPLIED TO THE TENANT.ALL OFFICE DOORS SHOULD BE KEYED INDIVIDUALLY.ENTRY&EXIT, CONFERENCE ROOM,AND UTILITY DOORS Z SHOULD REMAIN ON THE BUILDING SUBMASTER,WHERE THE SAME KEY THAT WORKS AN INDIVIDUAL'S OFFICE ALSO WORKS THESE DOORS.THE IT ROOM SHOULD BE KEYED INDIVIDUALLY WHERE ONLY CERTAIN PEOPLE COULD ACCESS THIS SPACE. 6. U.N.O.ALL HARDWARE COMPONENTS TO BE SATIN CHROME FINISH#626. m Q 1D 7. ALL WOOD DOORS SHALL BE WD-1.REFER TO FINISH LEGEND FOR ADDITIONAL INFORMATION. 8. FIELD VERIFY ALL DOOR SIZES PRIOR TO FABRICATION AND INSTALLATION. 9. PROVIDE(1) COAT HOOK ON OFFICE SIDE OF DOOR AND INSIDE OF RESTROOM DOORS WHEN APPLICABLE.CONFIRM MOUNTING LOCATION WITH TENANT. CM 10. ALL DOORS 7'-6"HIGH OR TALLER TO RECEIVE TWO(2)PAIR OF HINGES.ALL DOORS LESS THAN 7'-6"HIGH TO RECEIVE ONE AND A HALF(1-1/2)PAIR OF . HINGES. � T 11. ALL HARDWARE AND ASSEMBLIES IN RATED OPENINGS TO COMPLY WITH REQUIRED OPENING ASSEMBLY RATING. 12- DOOR OPERATING DEVICES AND ANY SPECIAL LOCKING ARRANGEMENTS TO COMPLY WITH ALL ENFORCED BUILDING CODES,ICC/ANSI 117.1,AND ALL LOCAL,STATE,AND NATIONAL ACCESSIBILITY REQUIREMENTS. 13. ALL EQUIPMENT TO BE INSTALLED SUCH THAT EMERGENCY MEANS OF EGRESS DOORS EQUIPPED WITH MAGNETIC LOCKS, PUSH BUTTONS COMBINATION LOCKS OR OTHER SPECIAL LOCKING DEVICES SHALL, IN THE EVENT OF AN EMERGENCY,AUTOMATICALLY RELEASE AND OPEN IN ACCORDANCE WITH ENFORCED BUILDING CODE REQUIREMENTS. 14. U.N.O. PAINT ALL EXISTING AND NEW HOLLOW METAL DOOR FRAMES PT-2. 15. REFER TO FINISH LEGEND.FOR ADDITIONAL DOOR,FRAME,AND HARDWARE FINISH INFORMATION. ONE ARCHITECTURE 16. ALL NEW DOGS TO DECEIVE FACTORY FINISH TO MATCH EXISTING DOORS 17. DOORS SHALL HAVE A SMOOTH, UNINTERRUPTED SURFACE ON LOWER 10 INCHES. 18. IF A DOOR HAS A CLOSER,THE SWEEP PERIOD OF THE CLOSER SHALL BE ADJUSTED SO THAT FROM AN OPEN POSITION OF 70 DEGREES.THE DOOR 720 OLIVE STREET,Sura 200 SAINT LOUIS,MO 63101 SHOULD TAKE AT LEAST 3 SECONDS TO MOVE TO AS POINT OF 3 INCHES FROM THE LATCH MEASURED TO THE LEADING EDGE OF THE DOORS. T 314 206 7100 F 314 231 9801 DOOR HARDWARE GROUP LEGEND: GROUP L PRIVATE OFFICE/CONFERENCE ROOM HARDWARE: 3 HINGES 1 LEVER LOCKSET WITH ENTRY FUNCTION 3 DOOR SILENCERS 1 FLOOR MOUNTED DOOR STOP 1 COAT HOOK GROUP 2: BREAK ROOM/WORKROOM HARDWARE: 3 HINGES 1 1 LEVER HANDLE WITH PASSAGE SET 3 DOOR SILENCERS 1 FLOOR MOUNTED DOOR STOP 2" RE: SCHED. 2" SEE PLAN RE:SCHED, RE:SCHED. 21 EA-19101 SCHEDULED 6" 6" A RESILIENT FLOOR s C� ONE-PIECE VINYL TRANSITION WD-1 GLA STRIP BY JOHNSONITE OR APPROVED EQUAL,TYP. GL-1 Y LU WD-1 � 21 ARCHITECT OF RECORD: SCHEDULED CARPET 0 5 A-901 a 11 _ ui u.i o LLi � A 901 FLOAT FLOOR AS a ?> - REQUIRED FOR SMOOTH TRANSITION Q D� (1/8"PER 12"MAX.) A B ewj� �CONCRETE SLABSOLID CORE WOOD SOLID CORE WOODWITH FULL LITE HOLLOW METAL WOOD BLOCKING PHMIX,ARIZONA„ 5/8"GYP.BOARD 14 DOOR TYPES 15 FRAME TYPES WINDOW TYPES RETURN AT HEAD 12 TRANSITION - RESILIENT FLOOR TO CARPET A-�1 1/4" _ '-a" A-9�1 �/4" _ ��-o" v4" = 1}-0" of o J-MOULD, BOTH SIDES A-901 3" _ 1 1_019 7-08-15 1"X 2" STEEL GLAZING CHANNEL ISSUE DATE DESCRIPTION A-901 4/27/2015 LANDLORD REVIEW SET �� ECS 6/15/2015 BID SET 7/7/2015 PERMIT SET METAL COWER BEAD, u. 0'-01/4" TYP. Revision Schedule > CLEAR SEALANT BOTH SIDES No. Date Description GLA a GLASS CENTERED ON 1 06130/15 BULLETIN 1 PARTITION,GL-1 � Lu a W �: SCHEDULED PARTITION BEYOND Cl) d- 1"X1"STEEL GLAZING CHANNEL - 5/8"GYP.BOARD SCHEDULED FLOOR 3 5/8"Mit.STUDS 1s DETAIL - GLASS SIDELIGHT 17 DETAIL @ JAMB AT SIDELIGHT GLAZING A-901 3" = 1'-0" A-901 3" = 1'-0" — STRUCTURE ABOVE Key Plan: 6"LONG 20 GA.STUD TRACK AT DECK AND BOTH SIDES OF CEILING _' BRACE WALL TO STRUCTURE fi ld ABOVE AT 48"O.C.MAX ONr". ALTERNATING SIDES OF WALL HEAD JAMB y ...'A...--4 _ 3-112" SOUND ATTENUATION BATT i` INSULATION TO 24 MIN EACH SIDE OF s WALL RE: SCHEDULE - SCHEDULED CEILING(RE: RCP). SPLIT EXISTING CEILING TILES AS REQUIRED SCHEDULED PARTITION TO ACCOMMODATE BRACING r! 5/8"GYPSUM BOARD EACH SIDE OF 'I KM.FRAME ; 3.5/8"25 GA. METAL STUDS a�116" O.C. Project Number: 15.2390.00 v SCHEDULED DOOR 3-1/2"SOUND ATTENUATION BATT `n INSULATION ui Sheet Title: FINISH FLOOR&BASE(RE:FINISH DOOR SCHEDULE/DOOR, FRAME, SCHEDULE) EACH SIDE PARTITION TYPES,AND INTERIOR DERAILS 1A 47/8" PARTITION TO CEILING 901 21 DETAIL - H.M. DOOR FRAME 22 DETAIL - PARTITION TYPES A Wl 3"= V-0" t9 1 1 1/2" = 1'-0" " KEYED NOTES: FURNITURE f E = r E `E 1. PROVIDE DUPLEX AND CTV CONNECTION AT THIS LOCATION FOR WALL MOUNTED FLAT SCREEN. SEE LOW VOLTAGE SCOPE DOCUMENT FOR - 102 E E ADDITIONAL INFORMATION E Ems' , =: E 2. PROVIDE DUPLEX, CTV, AND HDMI CONNECTION AT THIS LOCATION FOR WALL �; -- r E N SEE LOW VOLTAGE ^, E - MOUNTED FLAT SCREEN AND COMPUTER CONNECT E E ' SCOPE DOCUMENT FOR ADDITIONAL INFORMATION. E� 3. PROVIDE DATACOMM RECESSED LOW VOLTAGE MEDIA PLATE#45-0041 WH FOR — 103 E DEVICES SHOWN AT 60"A.F.F. q ( 4. IF NOT EXISTING, NEW SWITCH LOCATION. COORDINATE WITH ELECTRICAL E — CTV SUBCONTRACTOR FOR EXACT LOCATION. 104 E� M 5. RELOCATED FURNITURE BY FURNITURE VENDOR. W LU s N 4 4 4 O O O r NOTE: RE) � y POWER AND DATA LOCATIONS PER DESIGN INTENT. RE-USE EXISTING OUTLETS/DATA PORTS AND SWITCHES WHEN POSSIBLE, co _ + + �_ E� E Z .� �E W E E r 0 E r V E �E if x 105 v - _N ;# a " ONE R : E _ M. STREET,SUITE 200 SAINT LOUIS,MO 63101 r-- T 314 206 7100 F 314 231 9801 ^, E i i' I D E ---- 3 E E 106 5 107 E a w r xA9 w 4 --------------- E E E E + + E E = I 101 LI: u e € I t I ( I I € E� I t I � I i U I I , E ; I I I t I ------------ E --- - I ( I t I — ---E I wow 17 lot a 1 FURNITURE PLAN ARCHITECT OF RECORD: F-201 1/411 = 1'-0" D STI , c� I I I I I I PHOENIX,ARIZONA rill IPROVIDE 2X FRT WOOD tla� I I I I I �BLOCKING AS REQUIRED FOR ��F ©�,�MONITOR BRACKET SUPPORT,SECURELY SCREW BLOCKING TO MTL. STUDS 7-08-15 I I I I I I RECESSED DATACOMM ' ' ' ' I ' I I I I I I ISSUE DATE DESCRIPTION ELECTRICAL AND DATA I I I I OUTLET i i iIi i i 4/27/2015 LANDLORD REVIEW SET I I I I 6/15/2015 BID SET I i l i i i 7/7/2015 PERMIT SET I I I I I I I I I I I I i I I I I I Revision Schedule o i i i i i i No. Date Description I I I I I I � I I I I I I 1 I III I I I I I I I MOUNT CLIENT-PROVIDED 42"-60" EQ EQ i i i i FLAT SCREEN TELEVISION ON MONITOR BRACKET. MOUNT AND TV TO BE HUNG BY LOW VOLTAGE = 1 1 CONTRACTOR. I I I I I I if) I I I I I I METAL STUDS 16"O.C. I I I I I I I I I I i I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I 16 DEVICE LOCATION DIAGRAM - WALL-MOUNTED TV F-201 3/4" = 1'-0" Key Plan: SITE ROOM SCHEDULE Number Name Project Number: 15.2390.00 Sheet Title: 100 ENTRY/WAITING FURNITURE PLAN 101 OPEN OFFICE 102 PRIVATE OFFICE 103 PRIVATE OFFICE 104 PRIVATE OFFICE 105 CONFERENCE ROOM 106 IT CLOSET 107 WORK/BREAK ROOM