Loading...
Plans (76) ,.. NAC EOL VOLTAGE CALCULATION 6 w P ab14,0), / (6. RECEWED CAPITOL ELECTRIC CO., INC. 7�a6o G► � Jed 720 MAY — 2 2007 (503) 255 -9488 Office (503) 255 -1966 Fax CITY OF TIGARD BUILDING DIVISION Job Name: Lincoln Tower Job Address: 10260 SW Greenberg Road Tigard, OR 97223 Job Number: Conductor Wire Guage I 14 Prepared By: Dan Wilson Ohms Per 1000 Ft @ 75 Deg C ( 167 Deg F) I 3.07 I Date: 4/27/2007 Cable Length In Feet (source to end of line) I 213 I Total Circuit Current I 0.285 Nominal System Voltage I 20.4 I Panel Description: Silent Knight 5495 Power Supply Minimum Device Voltage 16 Panel No.: NAC 7.1 Output No.: 1 Point To Point Method EOLv 20.12 Circuit Within Limits ? YES NAC Devices Mfg By: Wheelock End Of Line Method EOLv 20.03 Circuit Within Limits ? YES Load Centering Method EOLv I 20.21 I Circuit Within Limits ? YES Dev Device Location Device Model No. & Description Candella Alarm Distance From Voltage At No. Rating Current Previous Device Device ( Feet ) . ,x.- . � «- - �, c::.' =tx . s " .Aa;.*� .zy-ra° . �', '�� "i� ep rn �rr� b :' �. ���5� „�a: `z,. .�s — 4 .• =n • "` T .'^ -- . . .x k" : S wa ".,,fa' ''''�,";' 3.,..: '• ;,., �' .sn , _ <• r -i�`. I:,w.:• � ;. � 2 a+"�",T 7 ^^4'� z ,��:n ; �'��w F� r's 7 r'G ,'�`t ,p.,!,�.5;, IS TAM '� x�•�' - ;iC;p,_, 5�",, •', �� - �,' . �, = ���eSa �ss�`���xi: '�4 �� �:. � r� ;��.��� `ss�,a__ _��"�` ,r:aw_. �Crc.�° k ,_ ��.xa�. "•.Fs,:,,,�.�, rr� a���i����. _.;�_ a.�dr° .� .. �a 1 EMC, Suite 720 RSS - 24MCW -FW (15) STB WHT 15 Cd 0.060 140 20.16 2 EMC, Suite 720 RSS - 24MCW -FW (75) STB WHT 75 Cd 0.165 12 20.14 3 EMC, Suite 720 RSS - 24MCW -FW (15) STB WHT ' 15 Cd 0.060 61 20.12 . 4 20.12 5 20.12 6 20.12 7 20.12 8 20.12 9 20.12 10 20.12 11 20.12 12 20.12 13 20.12 14 20.12 15 20.12 16 20.12 17 20.12 18 20.12 19 20.12 20 20.12 NAC 07.1 EOLv Calc.xls OUTPUT 1 NAC EXTENDER BATTERY CALCULATIONS CAPITOL ELECTRIC CO., INC. (503) 255 -9488 Office, (503) 255 -1966 Fax JOB NAME: Lincoln Tower ADDRESS: 10260 SW Greenberg Road Tigard, OR 97223 DATE: 4/27/07 PANEL DESCRIPTION: NAC 7.1 PREPARED BY: Dan Wilson DEVICE TOTAL DEVICE TOTAL STANDBY STANDBY ALARM ALARM DEVICE QUANTITY CURRENT CURRENT CURRENT CURRENT NAC EXTENDER `. %)$J � Silent Knight 5495 NAC Panel 1 0.075 0.075 0.175 0.175 CIRCUIT # 1 Suite 720 �b W " :�• - 'n x € '..__: +; �`9>� s �,,,•a r•:e*x_,s;; -1 0.000 � :.•r �" Wheelock RSS - 24MCW -FW 110 Cd Strobe 0.220 0.000 ,������� ;;�.�`�` �; Wheelock RSS - 24MCW -FW 75 Cd Strobe 1 6i 0.165 0.165 Wheelock RSS - 24MCW -FW 30 Cd Strobe a5 0.092 0.000 Wheelock RSS - 24MCW -FW 15 Cd Strobe 2 0.060 0.120 s�:.g a'. ;:...: , 0.000 .: 0.000 I:. 0.000 0.000 =k.`� 5.,. .:3 „•4:r ,i .*',e -Yi"' „ ?,:,e'tii °�'•ei4 Ty":';`� „s .:.;fi °a�.:;. d'.r .r„..vu - :':✓r . �; �:' ~;»�, ��� �� • n' ,��; :: �� � a,. L.. w �s� t, Px aA: ��#, i. f�: �. gr�vw �e�. ;u;�tis , � , ;;...':sA.'sa�:�rr �, 3.,, s: a; TOTAL 0.285 '-^ �a" ��, �. c" s: a°; �W, �M' kv , .:s- '�1�: '�'�'.:i.,s.,i���u3�,SU�^:�� CIRCUIT #2 n ;, wqt?' 5rt «vYiyE; .: > n,. +.e. " _..�'� .'" .,sLn = ,,::v� .x�`,,. , ai. .:£:r •,x�. £u +�'Y�'ri,;i.... ?����^ �.• *F.t're,�i: >�,�j w�m� 0.000 Wheelock RSS - 24MCW -FW 110 Cd Strobe :; IZ4 0.220 0.000 Wheelock RSS - 24MCW -FW 75 Cd Strobe ;aF €;'w`': "Nr 0.165 0.000 Wheelock RSS - 24MCW -FW 30 Cd Strobe r:' ;`• 0.092 0.000 Wheelock RSS - 24MCW -FW 15 Cd Strobe h ;_ft 0.060 0.000 0.000 0.000 0.000 0.000 TOTAL 0.000 .YK•,.. - 4i¢ . w i' ,C '> .•b'. "i2K`M. » ", „M „ � Y(, CIRCUIT # 3 wk a 0.000 Wheelock RSS - 24MCW -FW 110 Cd Strobe si;' 0.220 0.000 Wheelock RSS - 24MCW -FW 75 Cd Strobe ; ,_,' I w 0.165 0.000 Wheelock RSS - 24MCW -FW 30 Cd Strobe rEfwyw 0.092 0.000 Wheelock RSS - 24MCW -FW 15 Cd Strobe ''x x 0.060 0.000 £w 0.000 ,. ,• 0.000 0.000 0.000 � tr +,M^ a; .. :J'r•:3.�: >q - *'aka -;'G „ s �s.� .5. t Via• . TOTAL 0.000 ..`"r -„x �p „`r . "s#_•� ,.. ^w.t= i... t.�.t��,�'.. :��•.o -: rr... r` � �•.. � ;,xw�,� ,a v' „sm„�w'�,r . a e*vrara 2' sRv. ��.r� „s �1,. , .,- e,,.., a�+•:. t�3s _ . _ _ ..., , CIRCUIT #4 wzi4Wt -.: tix' 0.000 Wheelock RSS - 24MCW -FW 110 Cd Strobe > -Ar 0.220 0.000 Wheelock RSS - 24MCW -FW 75 Cd Strobe k ta, 0.165 0.000 Wheelock RSS - 24MCW -FW 30 Cd Strobe_`_ 0.092 0.000 Wheelock RSS - 24MCW -FW 15 Cd Strobe a %` 0.060 0.000 0.000 w - r 0.000 z s 0.000 0.000 v:,. ,... , xa';, �< .t rs'.rr 2 :.y -' ,.n.,' :._ r :s =•, , __av , n .x -� 4 ° y n, m,.;s..m,. TOTAL 0 .000 w ta���� .i��_��•r✓��,a��.'�..����� „'�?,a.�_?�wf,!k+w,.,� ¢`' a�, �w .�� „��"'`''�£;Mc��Y�i�c�����> NAC 07.1 Batt Calc.xls Page 1 of 2 .E V,e, LL t12.PlOGif y .. "�� t ` '`- r q� r + , MO. ` '$ 4 ,yc - T tr 12:1 u, t ` ' m!� 3 Uv �'. ° te a ' . a - e(.: - I . \ }. E'� r y ' , , e. , q -a' �6' r - ^ e g:r`3ks m 9 xs I a '1 yr " 'rT 4 i . m �iSTE�,1� � J - Helping People Take Actions' SERIES RSS & RSSP SINGLE & MULTI - CANDELA STROBES & STROBE PLATES fi NonTli DESCRIPTION . 1 ,. �: I � u Wheelock's patented Series RSS Strobe Appliances and - • 5 � 4} ; . :�� Series RSSP Strobe Plates have lower current draw while ;t t �, N ' a te. maintaining outstanding performance, reliability and cost x - a �• - effectiveness. These versatile a fiances will satisf Lr.%� virtually all requirements for indoor, wall or ceiling mount Series RSS RSS Round applications. Series RSSP • Strobe options for wall mount models include 1575 or -- .. .• - -• _ .- Wheelock's Patented MCW multi - candela strobe with field r ' ' to Mr selectable candela settings of 15/30/75/110cd or the high ., - , intensity MCWH strobe with field selectable 135/185cd. , "� ,� `l Ceiling mount models include the patented MCC multi- - - -- — candela ceiling strobe with field selectable intensities of Multi- Candela Indicator 15/30/75/95cd or the high intensity MCCH strobe with (bottom of Strobe Lens) field selectable 115/1.77cd. Features All models may be synchronized using the Wheelock • Approvals include: UL Standard 1971, New York City SM, DSM Sync Modules or the PS- 12/24 -8CP and (MEA), California State Fire Marshal (CSFM), Factory PS- 12/24 -8MP Power Supplies with Wheelock's Patented Mutual (FM), and Chicago (BFP) See approvals by Sync Protocol. Synchronized strobes can eliminate model in Specifications and Ordering Information possible restrictions on the number of strobes in the field • ADA/NFPA/UFC /ANSI compliant. Meets OSHA 29 of view. Wheelock's synchronized strobes offer an easy Part 1910.165 way to comply with ADA recommendations concerning • Wall mount Multi - Candela models are available photosensitive epilepsy as well as meeting the with Field Selectable Candela Settings of 15/30/ requirements of NFPA 72. 75/110cd or 135/185cd. Single Candela models are available in 1575cd Wheelock's Series RSS Strobes employ a Patented • Ceiling mount Multi- Candela models are Integral Strobe Mounting Plate that can be mounted to a available with field selectable candela settings of single gang, double gang, 4" square, 100mm European 15/30/75/95cd or 115/177cd. (Round or Square) backboxes or the SHBB surface backbox. If the flush • Strobes produce 1 flash per second over the backbox has side or top space between it and the finished regulated voltage range wall, the NATP (Notification Appliance Trimplate) may be • 12 and 24 VDC models with wide UL "Regulated used. It provides an additional .65" of trim for the Appliance. Voltage" using filtered (DC) or unfiltered VRMS input An attractive cover plate is provided for a clean, finished voltage appearance on all models. • Synchronize using Wheelock's sync modules or power supplies with built -in sync protocol The Series RSSP Multi - Candela Strobe Plates area cost • Fast installation with IN /OUT screw terminals using - effective way to retrofit required wall strobe appliances to #12 to #18 AWG wire bells, horns, chimes, multitones or speakers and easily • mounts to standard 4" backboxes or for surface mount use with Wheelock's SBL2 surface backbox. For Weatherproof Series RSS See Datatsheet S9004 • Copyright 2004 Wheelock, Inc. All rights reserved. • NOTE: All CAUTIONS and WARNINGS are identified by the symbol A. All warnings are printed in bold capital letters. A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND /OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS. General Notes • Strobes are designed to flash at 1 flash per second minimum over the Regulated Voltage Range. Note that NFPA -72 specifies a flash rate of ,1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second. • 'All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971. • Series RSS & RSSP Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32° F to 120° F (0° C to 49° C) and maximum humidity of 93% (± 2 %). • "Regulated Voltage Range" is -the newest terminology used by UL to identify the voltage range. Prior to this change, UL used the terminology "Listed Voltage Range ". Table 1: Average RMS Current* RSS /RSSP RSS /RSSP - Wall Mount RSS - Ceiling Mount 24VDC 241575W 24MCW 24MCWH 24MCC 24MCCH Models - 1575cd 15cd 30cd 75cd 110cd 135cd 185cd 15cd 30cd 75cd 95cd 115cd 177cd 24 vdc 0.060 0.041 0.063 0.109 0.140 0.195 0.270 0.045 0.070 0.119 0.159 0.195 0.270 • UL max* 0.090 0.060 0.092 0.165 0.220 0.300 0.420 0.065 0.105 0.189 0.249 0.300 0.420 RSS /RSSP RSS /RSSP * RMS current ratings are per UL average RMS method. UL max current 24VDC Wall Mount rating is the maximum RMS current within the listed voltage range (16 -33v Models 121575W for 24v units). For strobes the UL max current is usually at the minimum 12 vdc 0.152 listed voltage (16v for 24v units). For audibles the max current is usually at the maximum listed voltage (33v for 24v units). For unfiltered FWR ratings, UL max* 0.255 see installation instructions. Table 2: Audibles /Speakers for RSSP Strobe Plate • Product Series Multitone Appliances AMT, MT Horns AH, NH, HS Motor Bells MB- G6 /G10 Speakers ET- 1010/1080, E70, ET70 Chimes CH70 • • AWARNING: CONTACT WHEELOCK FOR THE CURRENT "INSTALLATION INSTRUCTIONS" AND "GENERAL INFORMATION" SHEET (P82380) ON THESE PRODUCTS. THESE DOCUMENTS UNDERGO PERIODIC CHANGES. IT IS IMPORTANT THAT'YOU HAVE CURRENT INFORMATION ON THESE PRODUCTS. THESE MATERIALS CONTAIN IMPORTANT INFORMATION THAT SHOULD BE READ PRIOR TO SPECIFYING OR INSTALLING THESE PRODUCTS, INCLUDING: • TOTAL CURRENT REQUIRED BY ALL APPLIANCES CONNECTED TO SYSTEM SECONDARY POWER SOURCES. • FUSE RATINGS ON NOTIFICATION APPLIANCE CIRCUITS TO HANDLE PEAK CURRENTS FROM ALL APPLIANCES ON THOSE CIRCUITS. • ADDING, REPLACING OR CHANGING APPLIANCES OR CHANGING CANDELA SETTINGS WILL AFFECT CURRENT DRAW. RECALCULATE CURRENT DRAW TO INSURE THAT THE TOTAL AVERAGE CURRENT AND TOTAL PEAK REQUIRED BY ALL APPLIANCES DO NOT EXCEED THE RATED CAPACITY OF THE POWER SOURCE OR FUSES. • COMPOSITE FLASH RATE FROM MULTIPLE STROBES WITHIN A PERSON'S FIELD OF VIEW. • THE VOLTAGE APPLIED TO THESE PRODUCTS MUST BE WITHIN THEIR "REGULATED VOLTAGE RANGE ". • INSTALLATION OF 110 CANDELA STROBE PRODUCTS IN SLEEPING AREAS. • INSTALLATION IN OFFICE AREAS AND OTHER SPECIFICATION AND INSTALLATION ISSUES. • USE STROBES ONLY ON CIRCUITS WITH CONTINUOUSLY APPLIED OPERATING VOLTAGE. DO NOT USE STROBES ON CODED OR INTERRUPTED CIRCUITS IN WHICH THE APPLIED VOLTAGE IS CYCLED ON AND OFF AS THE STROBES MAY NOT FLASH. • FAILURE TO COMPLY WITH THE INSTALLATION INSTRUCTIONS OR GENERAL INFORMATION SHEETS COULD RESULT IN IMPROPER INSTALLATION, APPLICATION, AND /OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS. • CONDUCTOR SIZE (AWG), LENGTH AND AMPACITY SHOULD BE TAKEN INTO CONSIDERATION PRIOR TO DESIGN AND INSTALLATION OF THESE PRODUCTS, PARTICULARLY IN RETROFIT INSTALLATIONS. ..:err cr •,' 4WI;r�:t,.'" 'rN- :� t •.... ,,.. U 111P iCG�( (� ,, - �r :r�Y- •�,`' i �, �*%` : �+ �?f €,� = =� r^� - `= n �j � \ l 3 ` � � � � .rte k � f".? - •���t�., �. f�r.it< Msge m I ADA :': . . .. Helping People Take Action'� SERIES E SPEAKERS & SPEAKER • STROBES � ' Description J Wheelock's Series E Low Profile Speakers Speaker and S eaker { " " ^ Strobes are designed for high efficiency sound output, with ,:i?cr,"d " <' ' dual voltage (25/70 VRMS) capability and field selectable taps FIRE,; . from 1/8 to 2 watts. The low profile design incorporates a speaker mounting plate for faster and easier installation. Each SERIES E70 SERIES E90 model has a built -in level adjustment feature and an aesthetic Speaker Strobe Speaker two (2) screw grille cover. The Series E Speaker Strobe models incorporate the Low a Current draw Series RSS Strobes. k ` , Strobe options for wall mount models include 1575 or Wheelock's patented MCW multi - candela strobe with field Multi - Candela Indicator selectable candela settings of 15/30/75/110cd or the high - intensity MCWH strobe with field selectable 135/185cd. (bottom of Strobe Lens) Features Ceiling mount models are available in Wheelock's patented • Approvals include: UL Standard 1971, UL Standard MCC multi - candela ceiling strobe with field selectable 1480, New York City (MEA), California State Fire intensities of 15/30/75/95cd or the high intensity MCCH strobe Marshal (CSFM), Factory Mutual (FM) and Chicago with field selectable 115/177cd. (BFP) See approvals by model in Specifications and Series E Speakers and Speaker Strobes provide high audio Ordering Information output with clear audibility and are designed to meet the critical • ADA/NFPA/ANSI compliant needs of the life safety industry for effective emergency voice • Complies with OSHA 29 Part 1910.165 communications, tone signaling and visible signaling to alert • Wall mount models are available with Field the hearing impaired. Selectable Candela Settings of 15/30/75/110cd or 135/185cd (Multi - Candela models), or 1575cd The strobe portion of all Series E Speaker Strobes may be (Single Candela model) synchronized when used in conjunction with the Wheelock • Ceiling mount models are available with field SM, DSM Sync Modules or Wheelock's PS- 12/24 -8CP and selectable candela settings of 15/30/75195cd or • PS- 12/24 -8MP Power Supplies with Patented Sync Protocol. 115/177cd (Multi - candela models) Wheelock's synchronized strobes offer an easy way to comply • Strobes produce 1 flash per second over the regulated with ADA recommendations concerning photosensitive voltage range epilepsy: • 24 VDC with wide UL "Regulated Voltage" Series E Speaker Strobes are UL Listed for indoor use under using filtered DC or unfiltered VRMS input voltage • Standard 1971 (Signaling Devices for the Hearing- Impaired) Synchronize with Wheelock SM, DSM or Wheelock and Standard 1480 (Speaker Appliances), and use a Xenon PS 12/24 8CP and PS 12/24 8MP Power Supply with flashtube with solid state circuitry enclosed in a rugged Lexan® built-in sync protocol • lens to provide maximum reliability for effective visual signaling. Field selectable taps for 25 or 70 VRMS operation All inputs are supervised and employ IN /OUT wiring terminals from 1/8 watt up to 2 watts • for fast installation using #12 to #18 AWG wiring. High efficiency design for maximum output at minimum wattage across a frequency range of 400 to Color options for the Series E Speakers and Speaker Strobes 4000 HZ are red, white and nickel plated. • Fast installation with IN /OUT screw terminals using #1.2 to #1 8 AWG wires Copyright 2004 Wheelock Inc. All rights reserved. r • j , NOTE: All CAUTIONS and WARNINGS are identified by the symbol A. All warnings are printed in bold capital letters. A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND /OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS. General Notes: • Strobes are designed to flash at 1 flash per second minimum over their "Regulated Voltage Range ". Note that NFPA -72 specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second. • All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971. • Series E Speaker Strobes and Series E Speakers are listed under UL Standard 1971 for indoor use with a temperature range of 32 °F to 120 °F (0 °C to 49 °C) and maximum humidity of 85 %. • "Regulated Voltage Range" is the newest terminology used by UL to identify the voltage range. Prior to this change UL used the terminology "Listed Voltage Range ". Table 1: Average RMS Current E70 Strobe Current - Wall Mount E90 Strobe Current - Ceiling Mount E70/E90 Speaker 241575W 24MCW 24MCWH 24MCC 24MCCH Strobes 1575cd 15cd 30cd 75cd 110cd 135cd 185cd 15cd 30cd 75cd 95cd 115cd 177cd 24 vdc 0.060 0.041 0.063 0.109 0.140 0.195 0.270 0.045 0.070 0.119 0.159 0.195 0.270 UL max` 0.090 0.060 0.092 0.165 0.220 0.300 .0420 0.065 0.105 0.189 0.249 0.300 0.420 * Table 2: E70/E90 UL Reverbant dBA @ 10 Feet" RMS current ratings are per UL average RMS method. UL max current rating is the maximum watts 1/8 1/4 1/2 1 2 RMS current within the listed voltage range (16 -33v for 24v units). For strobes the UL max current is • E Speaker 78.1 80.8 83.8 86.0 88.8 usually at the minimum listed voltage (16v for 24v E Speaker Strobe 77.5 80.4 83.2 85.7 87.8 units). For audibles the max current is usually at the maximum listed voltage (33v for 24v units). For ` "dBA ratings are based on testing under UL Standard 1480. unfiltered FWR ratings, see installation instructions.