Loading...
Specifications 1u_Gq 4 G Stix -- w\c;1 MEN'S WAREHOUSE HVAC REPLACEMENT 16940 SW 72nd Ave Tigard, Oregon STRUCTURAL CALCULATIONS VLMK Project Number:20180355 Reitmeier Mechanical 19570 SW 90th Court Tualatin,OR 97062 , JCTU/"q 4, <p"P'Or ' 5 �G "NE j37 L ' 56359PE' r 5/23/18 --ORE ry c., 15, - -760N c SPN\' EXPIRES: 6/30/2020 Prepared By: Kelli Slaven,EIT IvivuviK May 23,2018 ENGINEERING + DESIGN Structural Calculations:Men's Warehouse HVAC Replacement DC•1 Project: Men's Warehouse HVAC Replacement Project Number: 20180355 Project Address: 16940 SW 72nd Ave Document: Structural Calculations for Tigard, Oregon Building Permit TABLE OF CONTENTS Design Outline and Criteria DC-1 thru DC-2 Structural Details S-1 thru S-3 Structural Calculations C-1 thru C-8 Reference Documents R-1 thru R-3 DESCRIPTION OF STRUCTURAL SYSTEM This 'Men's Warehouse HVAC Replacement' consists of the replacement of (1) existing 1288 lb roof top unit with a new unit weighing 1588 lbs at the site located at 16940 SW 72nd Ave, Tigard, Oregon. The scope of this calculation is to review gravity loads to the structure and design anchorage of the unit to resist lateral loads. ***LIMITATIONS*** VLMK Engineering + Design was retained in a limited capacity for this project. No responsibility and/or liability is assumed by, nor is any to be assigned to, VLMK Engineering + Design for items beyond that shown in this Structural Calculation Package. G1CAD2018\ O180355\Colculations\20180355 DC.docx 3933 SW Kelly Avenue Portland,OR 97239 tel:503 222.4453 fax:503.248.9263 www.vlmk.com Structural Calculations:Men's Warehouse HVAC Replacement DC-2 CODES 2014 Oregon Structural Specialty Code (Based on the 2012 International Building Code) DESIGN LOADS Live Loads Roof Snow Load Flat Roof Snow Load, Pr 25 psf Dead Loads Roof Roofing 4.0 psf Insulation 1 .5 psf Sheathing 1.8 psf Sub-purlins 1 .2 psf Joists 3.0 psf Girders 1.0 psf Mechanical and Electrical 1 .0 psf Miscellaneous 1 .5 psf Total Roof Load 15.0 psf Additional Loads New Mechanical Unit 1386 lbs Adapter Curb 202 lbs Wind Ultimate Design Wind Speed, Vuif 120 mph Nominal Design Wind Speed, Vaud 93 mph Risk Category II Wind Exposure B Internal Pressure Coefficient GC„; = +1- 0.18 Seismic Location Latitude 45.39738 Longitude -122.74929 Seismic Importance Factor, Ie 1 .0 Risk Category II Mapped Spectral Response Accelerations Su = 0.962 S, = 0.418 Site Class D Spectral Response Coefficients Sds = 0.715 Sdl = 0.441 Seismic Design Category D Component Anchorage Factors a, Rp 1p Q. HVAC Equip 2.5 6.0 1.0 2.5 GNACAD2018\20180355\Calculations\20180355 DC.docx 3933 SW Kelly Avenue Portland,OR 97239 tel:503.222.4453 fax:503.248.9263 www.vlmk.com EXISTING 2x6 SUB-PURLINS AT 2'-0"O.C.,TYPICAL z z c a J - J N (y X X N - N M (v� w TYP® w E)4x12 (E)63/4x371/2 GLULAM GIRDER x x- NEW HVAC UNIT TO BEAR ON EXISTING FRAMING ON ALL SIDES z w w z (WEIGHT=1588#) cc E)4x12 \ o a 0 N N X X N N M (h W A ENLARGED FRAMING PLAN S-2 1/4"= MEN'S WAREHOUSE HVAC 201"803°55 055/18 16940 SW 72ND AVE KRS JCS VL M KENGINEERING TIGARD,OREGON °""N `"""`°+ DESIGN ENLARGED FRAMING PLAN S-2 3933 SW Kelly Avenue Portland,Oregon 97239 I tel:503.222.4453 I fax:503.248.9263 I www.vlmk.com s"sEr'w UNIT CASING UNIT BASE AND BASE RAIL SECURE ANCHOR TO UNIT WITH(4)#12 x 1" A. TEK SCREWS r-� I SECURE ANCHOR TO CURB 16 GAUGE x 4"x REQ'D WITH(4)#12 x 1"TEK ANCHOR,(4)TOTAL,(1) SCREWS,TYPICAL EACH CORNER ON LONG SIDES OF UNIT HVAC UNIT ADAPTER CURB SECURE HVAC UNIT ADAPTER CURB TO EXISTING CURB WITH MINIMUM 111, (4)#12 x 1 1/2"TEK SCREWS EACH ''� CORNER AND AT 12"O.C.AT SIDES, I TYPICAL SHIM ADAPTER CURB AS REQ'D HMiiiiI EXISTING UNIT FOR TIGHT FIT.SECURE SHIMS, 1/4" MOUNTING CURB AND GREATER,WITH ADDITIONAL (APPROX 14"HEIGHT) • SCREWS PRIOR TO PLACING CURB EXISTING ROOFING--\ _ / J / /// / / i / // / / / // // i// /Z/// / / I Nr. EXISTING ROOF SHEATHING AO /r EXISTING FRAMING VERIFY THAT EXISTING CURB IS FASTENED TO PER PLAN EXISTING SUPPORT FRAMING WITH A#14 SCREW MINIMUM,WITH 2"EMBED IN SUPPORT FRAMING, AT EACH CORNER AND AT 24"O.C., EACH SIDE.IF ANCHORAGE DOES NOT EXIST, PROVIDE SIMPSON'LTP4'OR'A35'CLIPS AT EACH CORNER AND AT 48"O.C.EACH SIDE FROM THE INSIDE OF THE CURB TO THE EXISTING ROOF FRAMING 0 HVAC CURB DETAIL 1 1/2"=1'-0" VI MEN'S WAREHOUSE HVAC 20180355 05/18 16940 SW 72ND AVE KRS JCS L M K TIGARD,OREGON °" " E E° ENGINEERING + uESIGN HVAC CURB DETAILS-3 SW Kelly Avenue Portland,Oregon 97239 I tel:503.2224453 I fax:503.248.9263 I www.vlmk.com SHEET H° Project Title: Men's Warehouse HVAC Engineer: KRS Project ID: 20180355 Project Descr: C-2 Printed:23 MAY 2018,8:43AM File=G:IACAD2018120180355\CalculahonstMen"s Warehouse HVAC.ec6 Wood Beam ENERCALCINC.1983-2017,BuUd:10.17.12.10,Ver:10.17.12.10 Lic,# KW-06002728 Licensee:VLMK CONSULTING ENGINEERS Description: Existing GL Purlin CODE REFERENCES Calculations per NDS 2015, IBC 2015,CBC 2016,ASCE 7-10 Load Combination Set:ASCE 7-10 Material Properties Analysis Method: Allowable Stress Design Fb+ 2,400.0 psi E:Modulus of Elasticity Load Combination ASCE 7-10 Fb- 1,850.0 psi Ebend-xx 1,800.0 ksi Fc-Prll 1,650.0 psi Eminbend-xx 950.0 ksi Wood Species : DF/DF Fc-Perp 650.0 psi Ebend-yy 1,600.0 ksi Wood Grade :24F-V4 Fv 265.0 psi Eminbend-yy 850.0 ksi Ft 1,100.0 psi Density 31.20 pcf Beam Bracing : Beam is Fully Braced against lateral-torsional buckling D(1.3) D(0.12)S(0.2) b 8 b 3.5x21 411,.1 Span=30.0ft F Applied Loads Service loads entered.Load Factors will be applied for calculations. Beam self weight calculated and added to loads Uniform Load: D=0.0150, S=0.0250 ksf, Tributary Width=8.0 ft,(Roof Trib) Point Load: D=1.30 k @ 7.50 ft,(HVAC Unit) DESIGN SUMMARY Design OK Maximum Bending Stress Ratio = 0.764 1 Maximum Shear Stress Ratio = 0.366 : 1 Section used for this span 3.5x21 Section used for this span 3.5x21 fb:Actual = 1,997.61 psi fv:Actual = 111.47 psi FB:Allowable = 2,616.24 psi Fv:Allowable = 304.75 psi Load Combination +D+S Load Combination +D+S Location of maximum on span = 14.015ft Location of maximum on span = 0.000 ft Span#where maximum occurs = Span#1 Span#where maximum occurs = Span#1 Maximum Deflection Max Downward Transient Deflection 0.754 in Ratio= 477>=360 Max Upward Transient Deflection 0.000 in Ratio= 0<360 Max Downward Total Deflection 1.447 in Ratio= 248>=180 Max Upward Total Deflection 0.000 in Ratio= 0<180 Vertical Reactions Support notation:Far left is#1 Values in KIPS Load Combination Support 1 Support 2 Overall MAXimum 6.014 5.364 Overall MINimum 3.000 3.000 D Only 3.014 2.364 +D+S 6.014 5.364 +D+0.750S 5.264 4.614 +0.60D 1.808 1.418 S Only 3.000 3.000 Project Title: Men's Warehouse HVAC Engineer: KRS Project ID: 20180355 Project Descr: C-3 Printed 23 MAY 2018,8:48AM Wood Beam File=G:IACAD20181201803551Caiculations\Men's Warehouse HVAC.ec6 ENERCALC,INC.1983-2017,Bu0d:10.17.12.10 Ver:10.17.12.10 Lic.#:KW-06002728 Licensee:VLMK CONSULTING ENGINEERS Description: Existing 4x12 End Beam CODE REFERENCES Calculations per NDS 2015, IBC 2015, CBC 2016,ASCE 7-10 Load Combination Set:ASCE 7-10 Material Properties Analysis Method: Allowable Stress Design Fb+ 675.0 psi E:Modulus of Elasticity Load Combination ASCE 7-10 Fb- 675.0 psi Ebend-xx 1,100.0 ksi Fc-PrIl 500.0 psi Eminbend-xx 400.0 ksi Wood Species : Hem Fir Fc-Perp 405.0 psi Wood Grade :No.2 Fv 140.0 psi Ft 350.0 psi Density 26.830 pcf Beam Bracing : Beam is Fully Braced against lateral-torsional buckling D(0.03)S(0.05) b sr e b b D(� b 2)b b b • • 4x12 Span=8.0 ft Applied Loads Service loads entered.Load Factors will be applied for calculations. Load for Span Number 1 Uniform Load: D=0.20 klft,Extent=3.50-->>8.0 ft, Tributary Width=1.0 ft,(HVAC Unit) Uniform Load: D=0.0150, S=0.0250 ksf, Tributary Width=2.0 ft,(Roof Trib) DESIGN SUMMARY Design OK Maximum Bending Stress Ratio = 0.397: 1 Maximum Shear Stress Ratio = 0.209 : 1 Section used for this span 4x12 Section used for this span 4x12 fb:Actual = 271.34 psi fv:Actual 21.03 psi FB:Allowable = 683.10 psi Fv:Allowable = 100.80 psi Load Combination +D+S Load Combination D Only Location of maximum on span = 4.555ft Location of maximum on span = 7.066 ft Span#where maximum occurs = Span#1 Span#where maximum occurs = Span#1 Maximum Deflection Max Downward Transient Deflection 0.011 in Ratio= 8988>=360 Max Upward Transient Deflection 0.000 in Ratio= 0<360 i Max Downward Total Deflection 0.043 in Ratio= 2245>=180 Max Upward Total Deflection 0.000 in Ratio= 0<180 Vertical Reactions Support notation:Far left is#1 Values in KIPS Load Combination Support 1 Support 2 Overall MAXimum 0.573 0.967 Overall MINimum 0.200 0.200 D Only 0.373 0.767 +D+S 0.573 0.967 +D+0.750S 0.523 0.917 +0.60D 0.224 0.460 S Only 0.200 0.200 Project Title: Men's Warehouse HVAC Engineer: KRS Project ID: 20180355 Project Descr: C-4 Printed.23 MAY 20'8,8:53AM File=G:IACAD2018l201803551Calculatians\Men's Warehouse HVAC.ec6 Wood Beam ENERCALC,INC.1983-2017,Build:10.17,12.10,Ver:10.17.12:10 Lic.#:KW-06002728 Licensee:VLMK CONSULTING ENGINEERS Description: Existing(2)2x6 Edge Support CODE REFERENCES Calculations per NDS 2015, IBC 2015,CBC 2016,ASCE 7-10 Load Combination Set:ASCE 7-10 Material Properties Analysis Method: Allowable Stress Design Fb+ 900 psi E:Modulus of Elasticity Load Combination ASCE 7-10 Fb- 900 psi Ebend-xx 1600 ksi Fc-PrIl 1350 psi Eminbend-xx 580 ksi Wood Species : Douglas Fir-Larch Fc-Perp 625 psi Wood Grade :No.2 Fv 180 psi Ft 575 psi Density 31.2 pcf Beam Bracing : Beam is Fully Braced against lateral-torsional buckling D(0.1 15) a o D(0.015)°S(0.025) b 5 5 5 5 -2x6 2 Span=7.0ft F Applied Loads Service loads entered.Load Factors will be applied for calculations. Uniform Load: D=0.0150, S=0.0250, Tributary Width=1.0 ft,(Roof Trib) Uniform Load: D=0.1150, Tributary Width=1.0 ft,(HVAC Unit) DESIGN SUMMARY Design OK Section used for this span 2-2x6 Section used for this span 2-2x6 Maximum BendinoStress Ratio 0.60a 1 Maximum Shear Stress Ratio 0.224 : 1 fb:Actual = 631.74 psi fv:Actual = 36.23 psi FB:Allowable = 1,053.00 psi Fv:Allowable = 162.00 psi Load Combination D Only Load Combination D Only Location of maximum on span = 3.500ft Location of maximum on span = 6.566 ft Span#where maximum occurs = Span#1 Span#where maximum occurs = Span#1 Maximum Deflection Max Downward Transient Deflection 0.020 in Ratio= 4115>=360 Max Upward Transient Deflection 0.000 in Ratio= 0<360 Max Downward Total Deflection 0.127 in Ratio= 663>=180 Max Upward Total Deflection 0.000 in Ratio= 0<180 - 1 Vertical Reactions Support notation:Far left is#1 Values in KIPS Load Combination Support 1 Support 2 Overall MAXimum 0.543 0.543 Overall MINimum 0.088 0.088 D Only 0.455 0.455 +D+S 0.543 0.543 +D+0.750S 0.521 0.521 +0.60D 0.273 0.273 S Only 0.088 0.088 1 Men's Warehouse VVLMK Project:HVAC Job#: 20180355 By: KRS Date: 5/18 Sneer#: C-5 ENGINEERING+DESIGN HVAC Anchorage Design: Loading: Unit Weight: 1386 lbs Curb Weight: 202 lbs Unit Length: 7'-4" Unit Width: 4'-11.5" Unit Height: 4'-1.5" SDS= 0.715g Vu11= 120 mph From Wind Spreadsheet: Ph= 41.7 psf Pv= 32.9 psf From Anchorage Spreadsheet: LSD= 425 lbs (Per corner) VASD = 319 lbs Anchorage: A UNIT CASING UNIT BASE AND BASE RAIL Check#10 x 1/2" TEK Screws: SECURE ANCHOR TO UNIT WRH(4)#10 x 1/2" TEK SCREWS Ta„GW = 388 Ib/screw WISECUREANCHOR TO CURB Vallow = 475 lb/screw (ICC-ESR-3223) I WITH(4)#10 x 1/2”TEK J SCREWS,TYPICAL x4 per corner 16 GAUGE STEEL'CANFAB' HVAC UNIT ADAPTER CURB OR EQUAL ANCHOR,(4) 1900lb T and 1552 Ib V TOTAL,(1)EACH CORNER ON LONG SIDES OF UNIT > 425 lbs OK SECURE HVAC UNIT TO EXISTING CURB WITH MINIMUM TER B INMUM (4)#10 x 1/2"TEK SCREWS EACH CORNER AND AT 12"O.C.AT SIDES, Check#14 Wood Screws: TYPICAL Shear Capacity: MOUNTNUCR � MOUNTNG CURB (APPROX 14'HEIGHT) NDS Table 11L - 163 lb (ASD) EXISTING ROOF SHEATHING x min 20 total = 3260 lbs EXISTING ROOFING AIAL > (4 corners)x319 lbs ��dg`-` �� = 1276 lbs OK for Shear VERIFY THAT G CURB IS FASTENED TO EXISTING SUPPORT UFRAMING WITH A#14 SCREW / 1't MINIMUM AT EACH CORNER AND AT 24"O.C., EXISTING FRAMING Tension Capacity: EACH SIDE.IF ANCHORAGE DOES NOT EXIST, PER PLAN PROVIDE SIMPSON LTP4 OR'A35 CLIPS AT NDS Table 11.26 - 172 Ib/inch (ASD) FROM THE NSIDE OF THE COURB TAO THE E x2" = 344 lbs/ screw EXISTING ROOF FRAMING x min 4 per side = 1376 lbs > (2 corners per side)x 425 lbs = 850 lbs OK for Tension 3933 SW Kelly Avenue Portland,OR 97239 iel: 503.222.4453 fax 503.248.9263 www.vlmk,cam VVLMK project: Men's Warehouse Job#: 20180355 By: KRS Date: 5/18 sheet#: C-6 ENGINEERING + DESIGN v3.00-Software Copyright 2015 VLMK Consulting Engineers. All Rights Reserved. Mechanical Unit Anchorage Design Based on the 2012 International Building Code and ASCE 7-10 DESIGN INPUT Seismic Parameters: 1x Spy = 0.715 g Design Spectral Response Acceleration • S2 = 1.0 Overstrength Factor [ASCE7 12.2-1 or 15.4-1] 3 a - CG Ap = 2.5 [ASCE7 13.5-1 or 13.6-1] `.1-'-*CR Y -r- Rp = 6.0. [ASCE7 13.5-1 or 13.6-1] Ycg Ip = 1.00 [ASCE7 13.1.3] • 1 2 • - z = 25 ft Attachment height from base of structure u h = 25 ft Average roof height of structure from base xcg I PLAN VIEW Wind Parameters: PHORIZ. = 41.7. psf Design Wind Pressure (psf), 1.0W PUPLIFr = 32.9 . psf Design Wind Pressure (psf), 1.0W crG Mechanical Unit Parameters: Wp = 1,588 lbs Total Weight zcg X = 88.0 in Base Dimension (max) ' ' Y = 59:5 in Base Dimension (min) SIDE VIEW Z = 49.5; in Height of Unit Zcurb = 34.0in Height of Curb, where occurs Load Combinations: Xc9 = 29.5 in Center of Gravity Seismic: Wind: Ycg = 34.3 in Center of Gravity (0.9-.2SDS)D + QE 0.9D + 1.0W Zcg = 203 in Center of Gravity (excluding curb) (0.6-.14SDS)D + 0.752E 0.6D + 0.6W ANALYSIS Base Shear: (Load applied to all (4) anchors/corners together) Seismic: l F,, = 0.4aR"SDS p Cl+2 h))I= 568 lbs <_1.6SDSIpWp = 1817 lbs OK "7 " >_0.3SDSIpWp = 341 lbs OK Base Shear, QV„E = 568 lbs Seismic, QE Wind: Vuw = 2128 lbs Wind, 1.0W Vu,BASE = 2128 lbs Wind = 1277 (ASD) Anchor Shear: (Load applied to each anchor/corner) Seismic: Design Eccentricity = 5% Anchor: dx dx^2 dy dy^2 ex = 15.975 in ey = -2.7875 in 1 29.5 870.25 34.25 1173.1 Mx_x = 9069 in-lbs My-y = -1582 in-lbs 2 58.5 3422.3 34.25 1173.1 Y Direction X Direction 3 29.5 870.25 25.25 637.56 V1,3 = 173 lbs V1,2 = 127 lbs 4 58.5 3422.3 25.25 637.56 V2,4 = 204 lbs V3,4 = 131 lbs 8585 3621.25 Wind: V1,2,3,4 = 532 lbs Max Vu,ANCHOR = 532 lbs Wind = 319 (ASD) Overturning/Uplift: (Load applied to each anchor/corner) Seismic: Mot = 30798 lb-in Seismic, QE Net Tension: Tx* = 564 lbs Mres,x = 35462 lb-in Seismic, SIE Ty* = 742 lbs ,r; Mres,v = 30353 lb-in Seismic, QE ‘iii Mot = 88838 lb-in Wind, 1.0W Max T,,,ANCHOR* = 742 lbs , lind F Mres,x = 42161 lb-in Wind, 1.0W = 425 (ASD).. Mres,y = 36087 lb-in Wind, 1.0W *Negative(-)values indicate there is no net uplift 3933 SW Kelly Avenue('ortlurd,OR 97239 lel. 503.222.4453 fax: 503.248.9263 www.vlmk.com VVLMK Project Men's Warehouse Job u: 20180355 BY KRS Date: 5/18 Sheet u: C-7 ENGINEERING • DESIGN v3.00-Software Copyright 2015 VLMK Consulting Engineers. All Rights Reserved. Wind Loads on Rooftop Structures and Equipment Based on the 2012 International Building Code and ASCE 7-10, 29.5.1 pC`' TYPICAL SCREEN WALL a' �...,' '> TYPICAL MECHANICAL UNIT H h DESIGN INPUT B = 170 ft Horizontal Dimension of Building Measured Normal to the Wind Direction h = 25 ft Mean Roof Height of Building (Eave Height if Roof Angle < 10) Height = 4.00 ft Height of Rooftop Structure or Equipment Width = 5.00 ft Width of Rooftop Structure or Equipment, Perpendicular to Wind Depth = 3.00 ft Depth of Rooftop Structure or Equipment, Parallel to Wind H = 29.0 ft Height to Top of Structure or Equipment Vuit = 120 mph Ultimate Wind Speed 3-Second Gust [Figures 26.5-1A, B, &C] B Exposure Category [Section 26.7.3] zg = 1200 ft Nominal Height of Atmospheric Boundary Layer [Table 26.9-1] a = 7.0 3-Second Gust-Speed Power Law Exponent [Table 26.9-1] KZ = 0.701 Velocity Pressure Exposure Coefficient [Table 29.3-1] Kn = 1.00 Topographic Factor [Figure 26.8-1] Kd = 0.85 Wind Directionality Factor [Table 26.6-1] ANALYSIS qZ = 0.00256KZKZtKdVutt2 [Equation 29.3-1] qz = 22.0 psf Velocity Pressure at Ultimate Level GCr = 1.9 Horizontal: Force Increase &Gust Factor [Section 29.5.1] GCr = 1.5 Vertical-Uplift: Force Increase & Gust Factor [Section 29.5.1] Af = 20 sf Area of Structure Normal to the Wind Direction (Horizontal face) Ar = 15 sf Area of Structure Perpendicular to the Wind Direction (Vertical face) B*h = 4250 sf Building Area Normal to the Wind Direction Fh = gh(GCr)Af [Equation 29.5-2] '♦ Fh = 834 lbs Horizontal Design Wind Force (Ult., 1.0W) Ph = 41.7 psf Horizontal Design Wind Pressure (Ult., 1.OW) Fv = gh(GC r)Ar [Equailor 29€0] 1 F„ = 494 lbs Vertical (Uplift) Design Wind Force (Ult., 1.0W) Pv = 32.9 psf Vertical (Uplift) Design Wind Pressure (Ult., 1.0W) 3933 SW Kelly Avenue Portland,OR 97239 tel. 503.222.4453 fax: 503.248.9263 www.vlmk.ron Unit Report For 12.5T R-1 Project: -Untitled177 05/0 /2018 Prepared By: 01:48PM Unit Parameters Dimensions(ft.in.)&Weight(lb.)*** Unit Model. 48TCFD14A3A6-6UOGO Unit Length. 7'4.125" Unit Size• 14(12.5 Tons) Unit Width. 4'11.5" Volts-Phase-Hertz. 460-3-60 Unit Height. 4' 1.375" Heating Type. Gas *** Total Operating Weight. 1386 lb Duct Cfg• Vertical Supply/Vertical Return High Heat *** Weights and Dimensions are approximate. Weight does Round Tube Plate Fin Coils not include unit packaging. Approximate dimensions are provided primarily for shipping purposes.For exact dimensions and weights,refer to appropriate product data catalog. Lines and Filters Gas Line Size• 3/4 Condensate Drain Line Size- 3/4 Return Air Filter Type. Throwaway Return Air Filter Quantity 4 Return Air Filter Size- 20 x 20 x 2 Unit Configuration High Static Option (Belt Drive) Al/Cu-Al/Cu Electromechanical Controls w/W7220 Econo Controller Temp Ultra Low Leak Economizer w/Baro Relief Standard Packaging 2-Speed indoor fan motor controlled by VFD Warranty Information 1-Year parts(std.) 5-Year compressor parts(std.) 10-Year heat exchanger-Aluminized(std.) 15-Year heat exchanger-Stainless Steel(std.) No optional warranties were selected. NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods. Ordering Information Part Number Description Quantity 48TCFD14A3A6-6UOGO Rooftop Unit 1 Base Unit High Static Option(Belt Drive) Ultra Low leak Temp Econo X with baro relief,W7220 control. Meets Calf.Title 24 FDD&Leak Rates 2 Speed Fan Controller (VFD) Accessories CRPWREXH023A01 Power Exhaust System 1 Packaged Rooftop Builder 1.49h Page 2 of 10 Certified Drawing for 12.5T Project: --Untitled177 R-2 05/01/2018 Prepared By: 01:48PM UNITED P 0 BOX 5858 5 WCUMEMI IS INE PROPERTY OF CARR]FR CORPoRAIIOM SUBMISSION OF T ESE ORAW[x0$OF OOCU E r5 TECHNOLOGIES SYRACUSE.NI AMO[S 555 1858/U UPON THE EXPRESS CONDITION[NAE tHE ROES NUT CONSTSTUOE PART PERFORMSNCE OR OUTDOOR STD. UNIT CORNER CORNER CORNER CORNER CARRIER 13221 COxlExrs WIIC MOT eE RMsaosco 58 us[R WIIHou[cARRI ER EPTANCE OF CONTRACT. C G CORPORAi)OX'S IA I1 iCx COXSEX r. UNIT COIL WEIGHTY.. WEIGHT(A/ WEIGHT (B) WEIGHT(CI WEIGHT ID) TYPE LBS. KG. LBS. KG. LBS. KG. LBS. KG. LBS. KG. X Y Z 48TC-014 NCHX 1116 506 297 135 157 71 229 104 434 197 29 1/2[7497 34 1/4 [8701 20 1/4 15141 MWW STANDARD UNIT WEIGHT IS WITH LOW GAS HEAT AND WITHOUT PACKAGING. 48TC-D14 RTPF 1167 530 349 159 167 76 211 96 440 200 31 3/8[7977 34 3/4 [883] 21 7/8 1556] FOR OTHER OPTIONS AND ACCESSORIES, REFER TO THE PRODUCT DATA CATALOG. ROPE -ROUND TUBE, PLATE FIN (COPPER/ALUM) MCRX -RICROCHANNEL (ALUM/ALUM) CORNER A CORNER B ((111Clh ;ll►►ll►)ii)►)ill) • • CORNER D •— CORNER C X _ TOP A. 1 I O I = R O O 'O. =O : : o o FRONT SHEET RATE SUPERCEOSS 48TC-14 SINGLE ZONE ELECTRICAL RE' 2OF2 10-04-10 08-30-10 COOLING WITH GAS HEAT 48TM501441 G Packaged Rooftop Builder 1.49h Page 4 of 10 NOTES: DIMENSIONED AND TOLERENCED PER ANSI YI4SID1982 REVISIONS MATERIAL:18 ga.GAL STEEL REV. ECO# DESCRIPTION DATE R-3 'ED 1 1/2"ADDED TO EXISTING CURB O.D_ Attn" 1 INITIAL DRAWING 5/5/08 00 1"DUCT INSULATION (R VALUE 3.85) 2 608 UPDATED DRAWING TO MATCH KIT CURB 6/7/2014 EH GASKET PROVIDED WITH CURB Tag: • Approval: SUPPLY AIR 441 15/16" - 17 9/16" RETURN AIR 410 11'.1141:/t ....\,.., ...gigo,t. . 4#0.1t1 .....f., ::,,,, , 33 1/4" `. s 36 114" s INSULATED EXISTING CURB LAYOUT ' 1 COVER I 92 1/2" I „.,:---...-- 58 1/2” 41 5/16" SUPPLY RETURN 27 1/16" FC _ 1 --s- 2 1/4" 813/4" 1 f-271/16" 537/16" \ 7 �—30 1/4" - t 5" 20" 20" 1 1. I II 94" I L I 60" 1 THIS DRAWING&THE INFORMATION CONTAINED APPROVALS DATE CURB SHOWN IS CDI STANDARD CONFIGURATION CDI RESERVES THE RIGHT TO CHANGE THEREIN IS THE CONFIDENTIAL.PROPRIETARY mTT Le NAME: INFORMATION OF CRYSTAL DISTRIBUTION INC., """"" Ehanson 6/7/2014 1-2016-4005 LAYOUT WITHOUT NOTIFICATION.IF CURB IS NEEDED IN A DIFFERENT CONFIGURATION &MAY NOT BE USED OR REPRODUCED K WITHOUT THE APPROVAL OF CRYSTAL DISTRIBUTION.INC. a"' CDI MUST BE NOTIFIED PRIOR TO PLACING AN ORDER. ALL RIGHTS RESERVED MMEMSH NS ARE AS FOLLOWS:1.00In[25A0 mm] *VERIFY EXISTING CURB OD .11� APPROXIMATE OPERATIONAL HEIGHT OF CDI ADAPTER IS 3"LESS THAN OVERALL CURB HEIGHT 'NOTE ANY RETURN OPENINGS r, CordaAt us@ CURB WEIGHT(Las.) F<°L 'NOTE ANY CHANGES =,.,;: .!� I,a'WWW.cdicurbs.com • 2 SHOWN. 'CALL WITH ANY QUESTIONS �.:!--7":.:::::".= or 201.27 I B� 'FAX BACK IF DRAWING IS OK AS IS 4}Ea II:!--7":.:::::".=.M"W= 1-888-2347001 ....:: 1:24 ET: 1 °F 2 S:\DRAWINGS(NEW)\CURB ADAPTER\3D\2000(Lennox)\