Plans (128) O M O JOtO SCOPE OF WORK FIRE ALARM EQUIPMENT SYMBOL LIST WW'd INSTALL A NEW ADDRESSABLE CENTRAL STATION FIRE ALARM SYSTEM WHICH SYMBOL DESCRIPTION PART # ROUGH-IN / NOTE MOUNTING HEIGHT w INCLUDES A FIRE ALARM CONTROL PANEL, CENTRAL STATION OFF-SITE 3 0 REPORTING, SPRINKLER FLOW AND TAMPER VALVE MONITORING, A MANUAL PULL FACP FIRE ALARM CONTROL PANEL NOTIFIER SELF-CONTAINED SURFACE MOUNT 54" TO TOP OF HIGHEST 2 STATION, AND A SMOKE DETECTOR. NFW-50 19"H X 16.65"W X 5.25"D USER FUNCTION AFF 2 • PLEASE PROVIDE �FACI CELLULAR DIALER DSC SELF-CONTAINED SURFACE MOUNT COMPLETED NFPA 72 3G4010-CF 11.5"H X 10"W X 3"D ALIGN WITH OTHER EQUIPMENT RECORD OF IWFI WATER FLOW SWITCH BY OTHERS MONITORED BY NMM-100P COMPLETION AT GENERAL NOTES FINAL INSPECTION I—I TAMPER SWITCH BY OTHERS MONITORED BY NMM-100P ` 11101 ..:illt ADDRESSABLE INPUT MODULE - MINI NOTIFIER NI ® SINGLE GANG ALIGN WITH OTHER EQUIPMENT 1. THE FIRE ALARM SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH NFPA NMM-100P 72 AND NFPA 70, ARTICLE 760, POWER LIMITED SYSTEMS. 2. FIRE ALARM WIRE INSTALLED IN VERTICAL RUNS AND PENETRATING MORE F ADDRESSABLE MANUAL PULL STATION NOTIFIER 4" SQUARE, SINGLE GANG, OR THAN ONE FLOOR SHALL BE RISER RATED. NOT-BG12LX DOUBLE GANG BACK BOX 46" TO CENTER AFF 3. FIRE ALARM WIRE RUN IN DUCTS OR PLENUMS SHALL BE PLENUM RATED. 4. ONLY SYSTEM WIRING CAN BE RUN IN THE SAME CONDUIT. ER 5. A SYSTEM GROUND MUST BE PROVIDED FOR EARTH DETECTION AND �P PHOTOELECTRIC SMOKE DETECTOR NOTI11 (� 00 4" OCT OR SINGLE GANG CEILING MOUNT LIGHTNING PROTECTION DEVICES. 6. DEDICATED BRANCH CIRCUIT(S) AND CONNECTIONS SHALL BE MECHANICALLY GENTEX GENTEX GBBB WEATHER PROOF PROTECTED. AB 24 VOLT WATER FLOW BELL GB6-24 BACK BOX 96" AFF 7. CIRCUIT DISCONNECT MEANS SHALL HAVE A RED MARKING, IDENTIFIED AS "FIRE ALARM CIRCUIT". 8. AUDIBLLEE A ALARMS SHALL CONFORM TO SECTION 18.4.3 PUBLIC MODE OFFICE COPY i tECEIVED (NF9. CENTRAL STATION MONITORING SHALL BE DOCUMENTED UPON COMPLETION l�Y 11 l/ COPY OF THE PROJECT IN ACCORDANCE WITH SECTION 26.6.3 (NFPA 72). MAY 3 2018 10. A RECORD OF COMPLETION SHALL BE PROVIDED TO THE FIELD INSPECTOR _ l'� AT THE ACCEPTANCE TEST INSPECTION IN ACCORDANCE WITH CITY OF TIGARD SECTION 14.6.2.4 (NFPA 72). CITY OF TIGARD 0 REVIE v I FOR CODE COMPLIANCE BUILDING DIVISION Q Approved: I m • OTC: I 1 f I Permit#: F P5.I p r .A-ono Li'7 W Address: 73'�c�.S kA, 1l u r h mow, ii,d W Suite#: Q) - 1- FIRE ALARM OPERATIONAL MATRIX $ Dater —j SYSTEM OUTPUTS = ( SITE �1 0 2 °� Pio, ���P°� �O��P� M sk �P 5� �P �� Q N I ..\T : ® �Ry. Pay �Q� G�i� ���� g�� 1< i N- J till ROgO �2C� GFS ••C° �y o� 4,, \� G ° �� X00 00`O I O ��' / G �Q�° PGQ ��°� FPGQoc" c0 c• �t, 5 0� V- > a LLI 11 rfx no, P Q`� oma{°Q� P s` 5Q LI- .9.40 cP N U' 5 5 Q i P e,5 0N� QS 3, JP 4,P4 GF, Gni, 5 CI r HII- SYSTEM INPUTS .P��P� °J °J °Q�°Q� C, G, C, �.„�.\\� 4c2 REVIEWED/APPROVED: i P P '6 '�' C. C' P P P 5 5 0 NOTES: PULL STATION • • • • SMOKE DETECTOR • • • • I '--- / s SPRINKLER FLOW SWITCH • • • • • BEN BREIT-4460LEA DWG REV./DATE QsiSS SPRINKLER TAMPER SWITCH • • 0 04/24/18 d COMMUNICATOR TROUBLE • • 1 05/03/18 - 7=LDG 2 11,F, 0/_ �, LOSS OF AC POWER AT FACP • • / ,�� OPEN CIRCUIT • • DRAWN BY / DISCONNECTION OF BATTERIES • • TME I-- dill III'' 1�IICHECKED BY'. ��I III GROUND FAULT • • BJB ,hill illllll, FILE NAME.FA.dwg PRESS SIGNAL SILENCE KEY • • PRESS RESET KEY • DRAWING#: FA-1 ORIG.SHEET SIZE:11"x 17" #OF DWGS IN SET: SHEET 1 OF 4 BATTERY CALCULATIONS #mo NOTIFIER NFW-50 °`° moo Ww" PART # DESCRIPTION QTY STANDBY STANDBY TOTAL ALARM ALARM TOTAL ADDRESS SCHEDULE g Y NFW-50 MAIN CIRCUIT BOARD 1 0.1200 0.1200 0.2000 0.2000 i NOT-BG12LX PULL STATION ADDR 1 0.0003 0.0003 0.0003 0.0003 ADDRESS DEVICE LOCATION / AREA NP-100 PHOTOELECT ADDR HEAD 1 0.0003 0.0003 0.0065 0.0065 D-01 PHOTO SMOKE DETECTOR BY FACP NMM-100P MINI MONITOR MODULE 4 0.0004 0.0016 0.0050 0.0200 M-02 MONITOR COMM TROUBLE BY FACP GB6-24 FIRE ALARM BELL 1 0.0000 0.0000 0.1000 0.1000 M-03 PULL MANUAL PULL STATION BY WF/TS d STANDBY TOTAL 0.1222 ALARM TOTAL 0.2268 M-04 FLOW WATER FLOW I%, *CALCULATIONS BASED ON 24 HR STANDBY TIME & 5 MIN ALARM TIME* M-05 TAMPER TAMPER SWITCH M-O6 TAMPER DOUBLE CHECK VALVEI AMPS (A) X TIME (H) = AMP-HRS (AH) 20% DERATE l` IllSTANDBY 0.1222 X 24 _ = 2.9328 - A-07 SPARE SPARE A-08 SPARE SPARE o ALARM 0.2268 X 0.0833 = 0.0189 - A-09 SPARE SPARE TOTAL AH = 2.9517 3.5420 1111111-I 1111 A-10 SPARE SPARE BATTERIES TO BE INSTALLED: 7.0 AH *** SPARE CONTINUES *** A-50 SPARE SPARE D- DETECTOR M- MODULE A- SPARE !" ,, V 13 -J W 2 W FIRE ALARM RISER DIAGRAM W F- (TYPICAL) Q `>" D-01 M-02 M-03 M-04 M-05 M-06 = V 0. VD III VD 4ID CDSLC ao 18/2C FPLR B� co IFACI WF ITS) ITS)BY OTHERS Vo 2 rI M Q IEOLIRe EOL_ EOL e IEOLIRe _ N- J 47k 47kn e 47k 47kn Q FACP = 0 D Et 0Q u) o W D cCu- N Q NOTE: NAC 1 PROGRAMMED AS r 1 11L SPECIAL AUX POWER SLC 1 DWG REV./DATE SLC NOTIFIER 0 04/24/18 18/2C FPLR NFW-50 2 SPARE EOL.4.7kn FACP e 1 05/03/18 DM RJ I W/INTEGRAL • RJI DACT 14/2C FPLR IAC NOTIFICATION CIRCUIT SCHEDULE DRAWN BY: VOLTAGE DROP CALCULATIONS TME 120VAC DEDICATED CHECKED BY CKT # DEVICE LOCATION / AREA CIRCUIT TOTAL WIRE WIRE VOLT VOLT ACCEPTED VOLT BJB ORIGIN AMPS DIST SIZE DROP AT EOL DROP DROP % FILE NAME: N-1 WATERFLOW BELL AT FDC FACP 0.100 25 14 0.02 20.38 YES 0.08% FA. wg NG N-2 SPARE SPARE FACP 0.000 0 14 0.00, 20.40 YES 0.00% DRAW *****END-OF-LINE METHOD OF CALCULATION FA-2 ORIG.SHEET SIZE:11"x 17" #OF DWGS IN SET SHEET 2 OF 4 00 aro •m r — p O m O o L%°'-'2- Y n I FA-1 lir VV All. All. III rII �� II :t mi i ...._ _ lit% II 1111 FA-3 II II 11 r 1 %% i0OVEALLFLOO � PLA\ _ 16' 32'SCALE: 1/16"=1'-0" J FIRE WATER STUB /�► SANITARY STUB\ Y.1 • ADA RAMP I W W ROLL UP DOOR ROLL UP DOOR Ce '�(//••�� M vJ V/ O iy � LL 2 2MNQ Q = � J = Cl o Q ELEC/MECH/ liN0 W N ROOF ACCESS ABOVE RISER o Q LL N () FACPI D-01 0LL FAC AIM>M-02 -Y' DWG REV./DATE DOC 0 04/24/18 _ 1 05/03/18 WF CD M-04 TS CD M-05 ❑F M-03 TS 4ID M-06 DRAWN BY: TME CHECKED BY: BJB FILE NAME: FA.dwg % 2 E\ L A G E D PLA\ 8' 16' DRAW NG# FA-3 „, / SCALE: 1/8"=1'-0" ORIG.SHEET SIZE 11'k 17" #OF DWGS IN SET: SHEET 3 OF 4 000 VL O. VLOo > m 6 Leo Lj wN go w 5 1111146 FROM FACP TO NEXT DEVICE OR OR PREVIOUS DEVICE �'� _��u TO FACP FOR , � �_ k OPTIONAL CLASS A ° 11114 SLC IN /� V - SLC +,wzc] , ui " SLC OUT il la 411 SLC SLC OL,anC) SLC + 1 111111111 it cs...c.)_.1, TO NEXTDEVICE TO NEXT DEVICE OR OR TO FACP FOR TO FACP FOR OPTIONAL CLASS A CLASS Xj...... SLC — � SLC — SLC — 6 SLC — FROMM FACP SLC IN SLC OUT FROMMRFACP SLC IN SLC OUT PREVIOUS DEVICE TYPICALOR ,arzc) (TYPICAL MC) PREVIOUS DEVICE (TYPICAL,enc) (TYPICAL 18/2C) SLC + • SLC + SLC + . SLC + CAUTIONDO NOT LOOP WIRE UNDER TERMINAL 1 OR 2 MONITOR MODULE MONITOR MODULE BREAK WIRE RUN TO PROVIDE IN SUPERVISION OF CONNECTIONS. SEE ADDRESS SCHEDULE FOR Alp 8 ,e- 52�I�\ ADDRESS 21 A 8 9 CORRESPONDING MODULE. 7 g g QQ 7 g g BASE-B2101P 6 /1 6 7 J SET DIAL(S)ACCORDINGLY. \ 'C�� ADDRESS CI� LOOP10 4 lip PHOTO SMOKE DETECTOR 2 y J HEAT DETECTOR TENSONES 0 0 'TENS LOOP ONES • • . • • - • • • (-W(+) (+) (-) OSMOKE/HEAT BASE YELLOW VIOLET RED `BLACK / YELLOW VIOLET RED BLACK SCALE: NTS FLOW CR TAMPER SNATCH TYPICAL,a-zc 1 \ J TYPICAL,anC PLACED HERE;NOTE EOLR \ \ TYPICAL 18/2C \- J TY !� LOCATION ON EACH. -\ / TAMPER SWITCH ` \.. TYPICAL,anc \ /^ - PADDLE FLOW SWITCH \ v NC NC •NC NC• PAM-2 c C NJ J WHITE C -- BLUE S•C C• EL 4K0 EOL ,an / •OV-) OR N0_No-' GREY YELLOW / •NO NO / -A24V@0.015 A NC S • , W PLACE EOLR AS SHOWN PLACE EOLR AS SHOWN RED FOR TAMPER SWITCH FOR PADDLE FLOW SNATCH �•i12V@O.015A NO• ORANGE ***FOR USE WITH FLOW SWITCH**" FROM FACP SLC , , SIXTO NEXT DEVICE (MTVO �` FACP AUX I OR SLC IN SLC OUT OR PREVIOUS DEVICE (TYPICAL,enc) (TYPICAL,enc) TO FACP FOR SW + SLC + OPTIONAL CLASS A //� e + 24VDC cENTEx 24voc \ v, TYPICAL 18nC POWER FLOW BELL \ TYPICAL 1.0 0 - OUT GB6-24 l \r.^ CY 0 `-) O O (-) CAUTION. / '[...1.1 O BLACK IN BLACK(OUT) nnI I ( 1 DO NOT LOOP WIRE UNDER I I e e e e e m o e e a e e e e e e e e 00550 SAFE OFF TERMINAL 1 OR 2. I I c CO TYPICAL 18. g-jt UNUSED BREAK WIRE RUN TO PROVIDE 1 Z d A Op 9 -0 v -0 C 0 U N w t O CC)) O A C CV CONDUCTORS 17 L F 2 2 F x 2 a ; -I -I ,n Q N SUPERVISION OF CONNECTIONS. O O C- 0 % N 4 t + 2 2 < I r (+) 0 0 (+) 11- I REDDSC-3G4010CF ,7, DSC-3G4010CF Q I' CA RED(IN) (OUT) D CC 1 2 3 4POWER SUPPLY PCMa IS OPTIONAL BECAUSE TERMINAL BLOCKS = DIAL TONE IS NOT i S7PoP OAU - GENERATED WHEN CELL �. • SIGNAL IS LOST W Q W FLOW BELL/TAMPER SWITCH MONITOR _ _ 3 COMM TROUBLE MONITORiII 0 i:O SCALE: NTS SCALE: NTS D �� r DWG REV.)DATE 0 04/24/18 0 0 1 05/03/18 • DRAWN BY: n TME �/ CHECKED BY: PULL STATION BJB FILE NAME ®PULL STATION FA.dWg 4 SCALE: NTS DRAW NG#: FA-4 ORIG.SHEET SIZE 11"x 17" #OF DWGS IN SET: SHEET 4 OF 4