TWINE* Submittal
APR .ft. _
Prepared For: Date:March 26, 2018
Oregon Heating
Customer P.O. Number:
Customer Project Number:
Sold To: Job Number:
Job Name:
Fanno Cr Bridgeport Family Med-Equip
Trane U.S. Inc. is pleased to provide the enclosed submittal for your review and approval.
Product Summary
Qty Product
1 Variable Air Volume Fan Powered Terminal Units
The attached information describes the equipment we propose to
furnish for this project,and is submitted for your approval.
Product performance and submittal data is valid for a period of 6 months
from the date of submittal generation. If six months or more has elapsed
Kyle Wolf between submittal generation and equipment release,the product
Trane performance and submittal data will need to be verified. It is the
7257 SW Kable Lane customer's responsibility to obtain such verification.
Portland, OR 97224-7181
Phone: (503)620-8031
Cell: (503)828-6788
Fax: (503)639-1454
J:IJOBSI124170013131Fanno Cr Bridgeport Family Med-Equip-submittal 01.doc
}
Table Of Contents
Product Summary 1
Variable Air Volume Fan Powered Terminal Units(Item Al)
Tag Data 3
Product Data 3
Mechanical Specifications 4
Unit Dimensions 8
Accessory 9
Field Wiring 10
Fanno Cr Bridgeport Family Med-Equip March 26,2018
Tag Data-Variable Air Volume Fan Powered Terminal Units(Qty: 1)
Item Tag(s) Qty Description Model Number
Al VAV-x 1 VAV Fan Powered Terminal Units VPEF1000R**DD04AD210-L-WWD03021W-00
0
Product Data-Variable Air Volume Fan Powered Terminal Units
Item: Al Qty: 1 Tag(s): VAV-x
Parallel with electric heat
10"(254 mm)
04 super quiet fan
1/2"[13mm]matte faced insulation
Flanged connection
277/60/1 motor voltage
Single speed motor w/SCR
DDC with on/off electric heat control
Standard actuator
Left hand controls connection
Disconnect switch
Power fuse
277 volt, 1 phase
3.0 kilowatt
2 stages of heat-equal increments
24 volt magnetic contactors
Electric heater air flow switch
FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 3 of 11
Others
Fanno Cr Bridgeport Family Med-Equip March 26,2018
Mechanical Specifications-Variable Air Volume Fan Powered Terminal Units
Item:Al Qty: 1 Tag(s): VAV-x
General Unit Information
Casing -The unit casing is 22 gauge galvanized steel. Outlet duct connection is flanged.
Total metal encapsulation of all insulation edges. Hanger Brackets provided. Side access is provided.
Filter-A filter is provided on the plenum inlet.
Agency Listing - UL and Canadian UL listed as environmental air terminal unit. UL Control#9N65. All Trane terminal
units are AHRI 880-98 certified.
General Unit Clearance
Leave a minimum of 36"on control box side of unit for adequate service access.Allow at least 12"on remaining sides for
unit clearance.A minimum of one and one half duct diameters of straight duct work,upstream of the air inlet connection,
should be present for optimum airflow measurement performance. Upstream duct work should be the same diameter as
the primary inlet connection.
Electrical Installation Information
For electrical connections, consult field wiring section &equipment IOM.
IMPORTANT: Field Wiring
Most fan-powered VAV terminal units with electric reheat require a neutral connection from building power, however,
some configurations do not. In order to prevent a building wiring issue once the boxes are installed,the wiring diagrams
and field wiring installation for each unit MUST be checked to determine whether the neutral is required or not required.
1/2" Matte-Faced Insulation
The interior surface of the unit casing is acoustically and thermally lined with 1/2", 1.8 lb/cu. ft composite density glass
fiber with high density facing. The insulation is UL listed and meets NFPA-90A and UL 181 standards.All insulation
options will meet the 25/50 smoke developed and flame spread rating(per ASTM E 84 and UL 723 and CAN/ULC
S102-M88)Meets NFPA-90B. The insulation R-value is 1.9. All cut edges of insulation are completely encapsulated in
metal to prevent erosion.
Air Valve& Fan Description (Parallel)(Series)
The air inlet connection is an 18 gauge galvanized steel cylinder sized to fit standard round duct.A multiple point,
averaging flow sensing ring is provided with balancing taps for measuring airflow within+/-5%of unit cataloged airflow.
Also provided with each unit is a calibration chart indicating airflow versus flow sensor pressure differential.The damper
blade is constructed of a closed cell foam seal mechanically locked between two 22 gauge galvanized steel disks. The
damper blade assembly is connected through a cast zinc stub axle and shaft supported by self lubricating bearings.The
shaft is cast with a damper position indicator.The valve assembly includes a mechanical stop to prevent over stroking.
Air valve leakage<1%at 4".
1004SQ Air Valve/Fan Combination Size(Parallel)
10" Inlet designed for up to 1400.0 cfm. Fan is 1350.0 cfm for Std Motor and 1510.0 cfm for ECM Motor.
Fuse
Any electric heat unit with a calculated MCA greater or equal to 30 will have a fan fuse provided.
Motor
Single Speed, direct drive induction, permanent split capacitor type. Thermal overload protection provided. Motors will
be designed specifically for use with an open SCR which is standard. Motors will accommodate anti-backward rotation
at start up. Motor and Fan assembly are isolated from terminal unit.
Electric Heat Coil
Factory provided and mounted. Resistance open-type heater, a disc-type automatic thermal primary safety device and
manual reset load thermal secondary device. Heater element material is nickel-chromium. The heater terminal box is
provided with knockouts for customer power supply. Terminal connections are plated steel with ceramic or phenolic
insulators.All fan-powered units with electric reheat are single-point power connections.
Magnetic Contactor
FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 4 of 11
Others
Fanno Cr Bridgeport Family Med-Equip March 26,2018
An electric heater 24 volt contact for use with Direct Digital Control(D.D.C.)or Analog Electronic VAV Controls.
Transformer
The 50 VA transformer is factory mounted in the fan control box to provide 24 VAC for controls.
SCR-Variable Fan Speed Control Switch
The SCR speed control device allows the operator infinite fan speed adjustment so the fan output may be modified to
achieve exact CFM requirements.
Airflow Switch
An air pressure device designed to disable the heater when the unit fan is off.
Power Fuse
Fuses provided on all energized lines of incoming power to interrupt circuit overcurrent conditions.
Power Disconnect Switch (for VSEF&VPEF)
A factory provided interlocking door disconnect switch located on the electric heater control panel.
Flanged Connection
A rectangular opening on the unit discharge to accept a 90 degree flanged duct work connection.
System Communications
The Controller is designed to send and receive data from a Central Control Panel or other Tracer family products, or a
VariTrac CCP. Current unit status conditions and set points may be monitored and/or edited via this data
communication feature. The network type is a twisted wire pair serial communication.
Set points in Nonvolatile Memory(9 Thru 15)
9. Heating Set point Offset-This determines at what point the 1st. stage of reheat turns on. Expressed in degrees
below cooling set point, only applicable when local thumb wheel is enabled.
10. Zone temperature, auxiliary temperature, and zone set point calibration corrections(+/- 10.0 F).
11. Flow measurement calibration correction(50- 150%).
12. Cooling Set point Low Limit-Applies low limit to programmed occupied cooling set point or zone sensor cooling set
point(30.0 F- 100.0 F).
13. Heating Set point High Limit-Applies high limit to programmed occupied heating set point or zone sensor heating
set point(30.0 F- 100.0 F).
14. RTD/Thermistor-Determines what type of zone temperature sensor will be used.
15. Occupied and Unoccupied Outside Air Requirements-Determines the percent of outdoor air required in the zone
for air quality requirements.
D.D.C. Floating Point Actuator
Trane 3 wire,(open,close,common)26GA when 6-pos amp connector is used for Tracer UC210,W550,or VAV UCM,
otherwise 18GA wires are used. 3.4 VA, 1.7W, 24 VAC, 50/60 Hz. Quarter turn control actuator with linkage release
button.Actuator has a constant drive rate independent of load, a rated torque of 35 in-Ib, a 90-second drive time and is
non-spring return. Travel is terminated by end stops at fully opened and closed positions. An integral magnetic clutch
eliminates motor stall. An integral 3 screw terminal block is provided for field wiring. Operating temperature 32.0 F to
125.0 F.
Additional Status Information(1 thru 8)
In addition to the above set points,the following status information can be transmitted to the Command Control Unit and
Tracer.
1. Active cooling temperature set point.
2. Active heating temperature set point.
3. Current unit primary airflow.
4. Current zone temperature.
5. Re-heat status(On/Off).
6. Auxiliary Air Temperature-Available only if the unit has an auxiliary temperature sensor.
7. Failure Indicators-The U.C.M. will indicate the following:
*Temperature Sensor Failure
*Flow Sensor Failure
*Local Zone Sensor Set point Failure
8. Ventilation Ratio.
FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 5 of 11
Others
Fanno Cr Bridgeport Family Med-Equip March 26,2018
Direct Digital Controller
The microprocessor based terminal unit controller provides accurate, pressure independent control through the use of a
proportional integral control algorithm and direct control technology. The controller monitors zone temperature set
points, zone temperature and its rate of change, and valve airflow, using a differential pressure signal. Optionally, the
controller can monitor either supply duct air temperature or CO2 concentration via appropriate sensors. The controller
and pressure transducer are installed and factory wired in an enclosure with 7/8"knockouts for remote control wiring.A
Trane zone sensor is required.
Override Commands
The following override commands may be received by the Unit Control Module(U.C.M.)from the Tracer System.
Parallel Unit Fan Energization
As the zone temperature reaches the heating set point, the microprocessor controls airflow to the heating temperature
set point and energizes the auxiliary fan when necessary. At or below the heating set point, reheat is energized. The
heating minimum airflow set point is factory set,field adjustable, and is separate from the cooling minimum set point.
Parallel unit fan energization is a function of primary airflow or zone temperature.
1. Primary Airflow-The fan energizes when primary airflow drops below the fan set point airflow.The fan automatically
starts when the zone temperature drops to the heating temperature set point.
2. Zone Temperature-The fan energizes when the zone temperature drops to a selectable number of degrees above
the heating temperature set point.
Control Mode, Action, &Offset(1 thru 12)
1. Control Mode-The U.C.M. Control Mode may be edited from occupied to unoccupied to accommodate night
setback/setup.
2. Control Action-The Control Action may be edited from cooling to heating, changing the primary air damper to a
heating source. This will accommodate a cooling/heating changeover system.
3. Control Offset-Enabling Control Offset will increase the cooling temperature set point and decrease the heating
temperature set point by a control offset value stored at the U.C.M. This function facilitates demand limiting in the
occupied mode.
4. Drive damper fully open.
5. Drive damper fully closed.
6. Drive damper to maximum airflow set point.
7. Drive damper to minimum airflow set point.
8. Disable unit fan.
9. Disable unit heat.
10. Reset-Enabling the reset function forces the controller and the flow sensor to recalibrate.
11. Programmable hot water valve drive time.
12. Programmable air valve drive time.
Following Unit Set points
The following unit set points reside in the U.C.M. in nonvolatile memory. These set points are editable from the
Command Unit or Tracer via the communications link.
Set points in Nonvolatile Memory(1 thru 8)
1. Occupied cooling temperature set point 60.0 F-80.0 F.
2. Occupied heating temperature set point 60.0 F-80.0 F.
3. Unoccupied cooling temperature set point 60.0 F- 100.0 F.
4. Unoccupied heating temperature set point 30.0 F- 100.0 F.
5. Minimum cooling flow set point(0, 10- 100%of unit equivalent cataloged airflow).
6. Minimum heating flow set point(0, 10- 100%of unit equivalent cataloged airflow).
7. Maximum flow set point(0,10- 100%of unit equivalent cataloged airflow).
8. Fan Control Offset-This determines at what operating point the fan in a parallel fan powered unit is energized.This
can be specified as a function of temperature, degrees above heating set point, or primary airflow. 0.0 F- 10.0 F or 0,
10- 100%of unit equivalent cataloged airflow).
Set points in Nonvolatile Memory(16 thru 21)
16. Series Fan Configuration-allows option of series fan powered box to shut off fan and close air valve when unit is
unoccupied. Fan will operate in unoccupied mode if reheat is active.
17. Heating set point low limit.
18. Cooling set point high limit.
19. Local heating flow set point enable/disable&set point.
20. Auxiliary analog input mode select for either auxiliary temperature sensor or CO2 detector.
21. Binary input mode select for either generic or occupancy detector.
FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 6 of 11
Others
Fenno Cr Bridgeport Family Med-Equip March 26,2018
Additional Status Information (9 thru 12)
9. Fan Status(on/off)
10. Calibration Status(calibrating/not-calibrating)
11. BIP state
12. CO2 Concentration-available only if the unit has an auxiliary CO2 sensor. This mode and auxiliary air temperature
are mutually exclusive.
DDC Sequence of Operation
The unit controller continuously monitors the zone temperature against its set point and varies the primary airflow as
required to meet zone set points. Airflow is limited by minimum and maximum airflow set points.
DDC Controls Option DD04, DD14, DD44& DD74
Basic Operation: On/Off Staged Electric Heat(Normally Open Outputs)(DDC/UCM)
(Parallel Units)
A voltage signal from the zone sensor indicates the zone temperature is used by the unit controller to determine an error
from the set point. This error, as well as primary flow differential pressure, is used to determine damper position within
minimum and maximum cooling airflow set points. As the zone temperature drops to the heating set point, primary
airflow is controlled to minimum heating flow set point. The fan operation is intermittent in both modes. Staged electric
heat is energized.
FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 7 of 11
Others
Fanno Cr Bridgeport Family Med-Equip March 26,2018
Unit Dimensions-Variable Air Volume Fan Powered Terminal Units
Item: Al Qty: 1 Tag(s):VAV-x
Unit Size VPEF1004SQ
Nominal 10"Dia.x 4"Depth
1111011*.4000111110„–
Valve Size&Depth
Nominal 04SQ Fan7.......4...4N'N.
Fan Size
Filter Size 16"x20 x1"(QTY1)
s�
TOP VIEW
20"
"la-10"1
0
z AIRFLOW NOTES:
16 1/2" o 1.Allow a minimum 6"plenum inlet clearance
cn
\II for un-ducted installations.
2.Filter is secured in filter frame located in unit inlet.
32 1/2" 3.For Motor access,remove bottom screws on
hanger brackets to slide panel as shown in drawing.
rn
xi
4.See Installation Documents for exact hanger
z
bracket location.
22" D
p ❑ 5.Air valve centered between top&bottom panel.
x V 6.Heating coil un-insulated. External insulation may
HEATER be field supplied and installed as required.
6" 7.All high&low voltage controls have same-side
PANEL SLIDES NEC jumpback clearance.
AIRFLOW FOR MOTOR ACCESS 8.Allow 48"of straight duct downstream of
DISCHARGE OUTLET unit before first runout and inside of the duct should
be equal discharge size.
9.Terminal box access door is side hinged.Allow for
clearance.
' 10.A 4 wire power supply required for 480\3&575\3
5" l� 40" a single point connection units.
ICi
16" 17 /2„
Approximate 114.0 Ib
Dry Weight
Weights reflected may vary
20" ±5.0 lb based upon options
DISCHARGE VIEW selected.
FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 8 of 11
Others
Fanno Cr Bridgeport Family Med-Equip March 26,2018
Accessory-Variable Air Volume Fan Powered Terminal Units
Item:Al Qty: 1 Tag(s): VAV-x
Notes:
1.When attenuator is required, add inlet attenuator pressure
to discharge static pressure for final fan performance.
VPCF and VPEF maximum
Minimum
1-row coil maximum
-•-•- -•-•-• 2-row coil maximum
Pa in.wg Parallel 04SQ—PSC
199 0.80 .
5'-,
174 0.70 \ ~.�,
\ \
150 0.60 >�
112
C y\
125 0.50 'E.. `\ \
NLI 100 0.40 $�,.;
` \ `
s 75 0.30 � ; ..
y.12
�; \
50 0.20 •. `t
25 0.10
200 400 600 800 1000 1200 1400 1600 Cfm
94 189 283 378 472 566 661 755 Us
Airflow
FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 9 of 11
Others
Fanno Cr Bridgeport Family Med-Equip March 26,2018
Field Wiring -Variable Air Volume Fan Powered Terminal Units
Item: Al Qty: 1 Tag(s): VAV-x
277 Volt 1 Phase
L1 N
I I
7_
I I
I I
I I
I I T
Heater
Control
Wiring
/c WARNING
HAZARDOUS VOLTAGE!
DISCONNECT ALL ELECTRIC POWER
INCLUDING REMOTE DISCONNECTS
BEFORE SERVICING.
FAILURE TO DISCONNECT POWER
BEFORE SERVICING CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH
A\ CAUTION
USE COPPER CONDUCTORS ONLY!
UNIT TERMINALS ARE NOT DESIGNED Customer Notes:
TO ACCEPT OTHER TYPES OF 1. Factory installed.
CONDUCTORS.
FAILURE TO DO SO MAY CAUSE — — — — Optional or installed by others.
DAMAGE TO THE EQUIPMENT.
FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 10 of 11
Others
1
Fanno Cr Bridgeport Family Med-Equip March 26,2018
Field Wiring -Variable Air Volume Fan Powered Terminal Units
Item: Al Qty: 1 Tag(s): VAV-x
HEATER
TERMINAL DAMPER
BOX WIRING ACTUATOR FAN CONTROL
7—____A______\ WIRING BOX—W^IRIN—G r
___A. \ / \ TBi-1 TB2-B TB3-3 TB3-1
TEI1-2 TB2-5 TB3-2
2ND STG HEAT 0000000
> w
11 10 7 6 3 2 1
i = = w O DIGITAL DISPLAY ZONE SENSOR
1STSTG HEAT O O W/COMM.JACK
m REMOTE MMD.
O
OPTIONAL FIELD INSTALLED
L DIGITAL DISPLAY ZONE SENSOR J
R-FAN
BR r TB2-6 TB3-1
O Y
TB2-5 TB3-2
1113-3LL 24VAC BL
rc > o
1m
—F� 00100
rijw J1 0000001 d0 — 2( x)1(-) ,3 2 1
ACT ~12 PRESSURE ZONE SENSOR
BIP GND 245 W/COMM.JACK
TRANSDUCER REMOTE MTD.
ADDRESS D.D.C.\U.C.M. 3 < 1(
SWITCH CONTROL BOARD — R /+
OPTIONAL FIELD
LILILIIJLILI BK VOUT L INSTALLED ZONE SENSOR J
LILILILIUUI E— o 0
r
1 kg 1
Cl 3
i 80
OIL �'7 y N R VEL GRN F m v� gyp- �SC 7' I 24V (TB1-1)24V
I-II O—O— ��r� ❑ ❑ F� 4 �rA� e�5_ CO2 i (TB3-6)GND
ZONE GND SET A/CO2 GND SENSOR GND 0
OUT V_(TB3-5)A/CO2
OPTIONAL FIELD INSTALLED
L -CO2 SENSOR
D.D.C.\U.C.M. r 1
O O CONTROL BOX OPTIONAL BL
FACTORY
INSTALLEDY
WIRELESS
WIRES
SHIELDED TWISTED PAIR OPTIONAL FACTORY INSTALLED rTBaS r TB3-B -I
COMMUNICATIONS WIRING WIRELESS I I Y I
r , 24VAC l B
R(.0-0.____(TBI-1)24VAC I
O(COMMONL—-(TB4-DRIP mF I
GRSNCCONTACf_(T01-1)24VAC
BKSRETURNL__(TBI-2)0ND OPTIONAL GND 24V
V -NOT CONNECTED L 1:3,AUX TEMP SENSOR J W550 Boats'
J
OPTIONAL FIELD INSTALLED L
L OCCUPANCY SENSOR _I
NOTE:
1. FACTORY WIRING
FIELD WIRING
— — OPTIONAL OR ALTERNATE WIRING WARNING
2. 1/4"QUICK CONNECT REQUIRED FOR ALL FIELD CONNECTIONS. HAZARDOUS VOLTAGE!
<7 ZONE SENSOR TERMINALS 1(-)AND 2(+)REQUIRE SHIELDED TWISTED PAIR WIRING FOR DISCONNECT ALL ELECTRIC POWER
COMMUNICATIONS JACK EQUIPPED ZONE SENSOR OPTION. INCLUDING REMOTE DISCONNECTS
BEFORE SERVICING.
4. I NO ADDITIONAL WIRING REQUIRED FOR NIGHT SETBACK OVERRIDE(ON/CANCEL). FAILURE TO DISCONNECT POWER
THE OPTIONAL BINARY INPUT CONNECTS BETWEEN TB4-1(BIP)AND 24VAC(HOT)FROM BEFORE SERVICING CAN CAUSE
TRANSFORMER. INPUT CAN BE RECONFIGURED AS AN OCCUPANCY INPUT VIA THE COMMUNICATIONS SEVERE PERSONAL INJTURY OR DEATH
INTERFACE. /°
/\ CAU I ION
6. I AS SHIPPED,THE AUX INPUT IS CONFIGURED AS AN AUX TEMP INPUT.THE AUX INPUT CAN BE USE COPPER CONDUCTORS ONLY!
RECONFIGURED AS A CO2 SENSOR INPUT VIA THE COMMUNICATIONS INTERFACE.
UNIT TERMINALS ARE NOT DESIGNED
S TERMINAL NOT TO BE USED WITH VARITRANE. TO ACCEPT OTHER TYPES OF
CONDUCTORS.
8. I ZONE SENSOR TERMINALS BAND 7 REQUIRE SHIELDED TWISTED PAIR
WIRING FOR OPTIONAL USE OF COMMUNICATIONS JACK. FAILURE TO DO SO MAY CAUSE
DAMAGE TO THE EQUIPMENT.
FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 11 of 11
Others
i FAcPO�r
�' 2_QG�'M FV 05-11VK1
Adjustable Airflow for
VENTILATION N
Maximum Performance
Specification Submittal Data/ Panasonic Ventilation Fan
Description
Customizable Ventilation Fan shall be low sone ceiling mount rated for continuous 4" or 6" duct
run.Fan shall be ENERGY STAR®rated and certified by the Home Ventilating Institute
(HVI).Evaluated by Underwriters Laboratories and conform to both UL and cUL safety
standards.
Motor/Blower: �Y\,
•Enclosed DC brushless motor technology rated for continuous run.
•Fan ventilation rates shall be manually adjustable for 50-80-110 CFM. &. ;
•Power rating shall be 120 volts and 60 Hz. A�
•Fan shall be UL listed for tub/shower enclosure when used with a GFCI protected
circuit and used in insulated ceiling(TYPE I.C.).
•Fan equipped with a thermal cutoff fuse 4 I1
•Removable,permanently lubricated,plug-in motor. •
Housing: / z
•Rust proof paint,galvanized steel body. \ `�
•Integrated dual 4"or 6"diameter duct adapter.
•Built-in metal flange provides blocking for penetrations through drywall as an Air
Barrier,and assists with the decrease in leakage in the Building Envelope during
blower door testing.\
•Built in backdraft damper.
•Articulating and expandable installation bracket up to 24".
Grille: l
•Attractive design using Poly Pro material.
•Attaches directly to housing with torsion springs. \
•Includes a motion sensor cap for use as a cover when motion sensor
Plug'n PIayTM module has not been selected.
Warranty:
•ALL Parts:3 Years from original purchase date.
DC Motor:6 Years from original purchase date.
Architectural Specifications: FV-05-11VK1
Customizable Ventilation Fan shall be ceiling mount, ENERGY STAR®rated type with
built-in speed selector. Select from 50/80/110 CFM and no more than <0.3 sone as
certified by the Home Ventilating Institute(HVI)at 0.1 w.g.with no less than 53/82/113
CFM and no more than 0.3/0.4/0.8 sones at .25 w.g. Power Consumption shall be Performance Curve 4"or 6"duct
no greater than 3.5/5.5/9.8 watts at 0.1 w.g. and 15.1/15.3/11.5 watts at 0.25 w.g. 080 ----------
ENERGY STAR® rated with efficiency of no less than 15.1/15.3/11.5 CFM/watt at
0.1 w.g. and than 8.1/8.4/7.2 CFM/watt at 0.25 w.g. The motor shall be enclosed 1 0.70
with brushless DC motor engineered to run continuously. DC motor speed shall §
o.so C
automatically increase when the fan senses static pressure to maintain selected CFM. IIe — DFM
Power rating shall be 120v/60Hz. Duct diameter shall be no less than 4", inclusive o.so _, —90CFM
of an integrated dual 4" or 6" duct adapter. Plug 'N PIayTM modules provide up —aocFM
to three additional features. Select from Multi-Speed with Time Delay, Condensation 040 —s�FM
Sensor, LED Night Light and Motion Sensor. Fan shall be UL and cUL listed for tub/ '°CFM
shower enclosure when used with a GFCI protected circuit.Fan can be used to comply .ao
rani
-30CFM
with ASHRAE 62.2,LEED,ENERGY STAR®IAP,EarthCraft,California Title-24 and WA _u
Ventilation Code.
0.20 =wow0 10
DC Motor Technology:
y� 7 F40� When fan senses static pressure,its speed is automatically increased to °°°0 20 40 60 80 100 120
DC ensure that the desired CFM is not compromised,which allows the fan
Fto perform as rated.
cyNO
Model Quantity Comments Project:
Location:
Architect:
Engineer:
Contractor:
Submitted by:
Date:
For complete Installation Instructions visit us.panasonic.com/ventfans
SUBMITTAL
Job Title: Bridgeport Family Medical TI
Elevation: (ft) 108
Date: 3/29/2018
Submitted By: Jeff Fohr
JOHNSON AIR PRODUCTS
2220 SE 9TH AVENUE
PO BOX 15098
PORTLAND, OR 97293
US
Phone: (503)234-5071
Fax: (503)233-0451
Email Address: jfohr@johnsonair.com
[ GREENHECK
Building Value in Air.
P.O. Box 410 Schofield, WI 54476 (715)359-6171 FAX(715)355-2399 www.greenheck.com
Generated by:jfohr@johnsonair.com
CAPS 4.25.1969 O:\ChrisHessick\Bridgeport Family Medical Tl.gfcj Page 1 of 4
LGREENHECK Printed Date: 3/29/2018
Job: Bridgeport Family Medical TI
Building Value in Air. Mark: Louver Anodize Finish
Model: ESD-202
ESD-202 2 in. Frame
APPLICATION & DESIGN
ESD-202 is a weather louver designed to protect air intake and exhaust openings in building exterior walls. Design incorporates a drainable head
member and stationary horizontal blades to channel water to the jambs which guides the water through vertical downspouts for escape at the sill.The
ESD-202 is an extremely efficient louver with AMCA LICENSED PERFORMANCE DATA enabling designers to select and apply with confidence.
PRODUCT DETAILS
Frame: 2 in.x 0.063 in.Frame Thickness Internal View ;.
Frame Type: Channel
Blades: 0.063 in.Fixed Blade Thickness III
Material: Aluminum
Sizing: Actual Ili
Shape: Rectangular I li
Construction: Mechanically Fastened
Ili
OPTIONS &ACCESSORIES Ili
Finish: Anodize,Standard TBS -4----
�I
Bird Screen: 0.75 in.x 0.05 in.,Flat Expanded Aluminum,Internal, i
Mill Finish II
Warranty: 1 Yr(Standard)Product Warranty 11
1 Yr(Standard)Finish Warranty
II
SUMMARY
ID# TAG QTY. W(in.) H(in.) FREE AREA FREE AREA SECT.WIDE SECT.HIGH SHIP SECT.
(ft2) (%)
- * 1-1 1 36 18.5 1.56 33.7 1 1 1
Total Louver Qty: 1 Total Weight(Ib): 9 Louver Area(ft2): 5
Total Ship Sect.: 1
"Weight shown is an estimate only based on the default base product configuration without options or accessories.
Larger openings may require field assembly of multiple louver panels to make up the overall opening size.Individual louver panels are designed to withstand windloads up to a maximum of 25
PSF(size and configuration dependent).Design,materials and installation of structural reinforcement required to adequately support large sections or multiple section assemblies within a large
opening are not provided by Greenheck.Unless specifically indicated,the following are NOT included in the quote provided:structural steel, installation hardware(anchors,angle clips,
continuous angles,shims,fasteners,inserts,backer rod and sealant),field measuring and/or installation,miscellaneous flashing,trim or enclosures,blank off panels,mullion covers or mullion
hardware,hinged frames or removable subframes,custom birddnsect screen,3-coat,metallic and/or exotic paint finishes,bituminous paints for unlike metals,any applicable taxes,stamped and
sealed structural calculations seismic calculations or job specific engineered submittal drawings.
Generated by:jfohr@johnsonair.com
CAPS 4.25.1969 O:\ChrisHessick\Bridgeport Family Medical Tl.gfcj Page 2 of 4
L GREENHECKPrinted Date: 3/29/2018
Job: Bridgeport Family Medical TI
Building Value in Air. Mark: Louver Anodize Finish
Model: ESD-202
Louvers Product Limited Warranty
Thank you for purchasing Greenheck louvers.Greenheck warrants this equipment to be free from defect in material and workmanship for a period of 1
year from the date of product shipment.Any units or parts,which prove defective during the warranty period,will be repaired or replaced at our option
when returned to our factory,transportation prepaid.Unless agreed upon otherwise Greenheck will not be held responsible for costs associated with
removal or installation of product(s).
The legal remedies described in this Limited Warranty are the sole exclusive remedy of Customer.This limited warranty will be void if payment from
Customer is not received within a commercially reasonable time frame.GREENHECK MAKES NO OTHER WARRANTY,EITHER EXPRESS OR
IMPLIED,REGARDING ITS PRODUCTS,OR ITS SELECTION AND APPLICATION,INCLUDING,BUT NOT LIMITED TO,COMPLIANCE WITH
BUILDING CODES,SAFETY CODES,LAWS,MERCHANTABILITY OR FITNESS OR A PARTICULAR PURPOSE.This limited warranty is extended
solely to the Customer.It is nontransferable and non-assignable,and the Customer shall not permit or authorize its employees,agents,representatives
or customers to claim,represent or imply that this limited warranty extends or is available to anyone other than the Customer.
In the event of material breach by the Customer of any of the conditions of this warranty,Greenheck shall have no liability for and product failure claims.
Failure to pay Greenheck in full for original services will automatically make this warranty null and void.
Greenheck will not be held liable for incidental or consequential damages of any kind. The limited warranty of product(s)replaced or repaired under this
limited warranty shall be limited to the remainder of the original warranty period. Greenheck reserves the right to reasonable field access to diagnose
and repair any product alleged to be defective. This limited warranty may not be modified by anyone and may not be changed by such things as
purchase order forms or acceptance forms,unless otherwise agreed upon by Greenheck.
This limited warranty is provided in lieu of any other warranty requirements or obligations,including,but not limited to,those within project specifications.
All notices and claims given under or pursuant to this agreement shall be in writing and sent by certified or registered mail,postage prepaid,return
receipt requested to: Greenheck,Attn: Louver Sales,525 Western Road,Schofield,WI 54476.
By proceeding to use our products and services on your project,you accept the terms of these limited warranties.
Generated by:jfohr@johnsonair.com
CAPS 4.25.1969 O:\ChrisHessick\Bridgeport Family Medical Tl.gfcj Page 3 of 4
L'GREENHECKPrinted Date: 3/29/2018
Job: Bridgeport Family Medical TI
Building Value in Air. Mark: Louver Anodize Finish
Model: ESD-202
Louvers Architectural Finish Limited Warranty
Class I Anodize (215-R1 Clear,Champagne, Light Bronze, Medium Bronze, Dark Bronze, Extra Dark Bronze or
Black Anodize)
Greenheck warrants the finish of Class I anodize for a period of 5 years from the date of product shipment when applied
to aluminum louvers or aluminum architectural products. Greenheck warrants that for 5 years after the date of product
shipment the applied finish:
A) Will resist cracking, crazing, flaking or blistering.
B) Will not chalk in excess of ASTM D-4214-89 number 8 rating, determined by The procedure outlined in
ASTM D-4214-89 specification test.
C) Will not change color more than five(5) Delta-E Hunter units(square root of the sum of square Delta E,
Delta A and Delta B)as determined by ASTM method D-2244.
Any units or parts,which prove defective during the warranty period,will be repaired or replaced at our option when
returned to the factory, transportation prepaid. Unless agreed upon otherwise Greenheck will not be held responsible for
costs associated with installation or removal of product(s).
Greenheck limited warranties are not applicable when failure is caused by events that cannot be controlled by Greenheck.
These include, but are not limited to, Acts of God, fire or other casualty or physical damage; Government restrictions;Acts
of aggression; Harmful fumes or foreign substances in the atmosphere; Improper storage or packaging of the parts prior
to installation; Product failure due to improper usage and/or application; Failure to provide reasonable and routine
maintenance and/or improper maintenance, including, but not limited to the use of chemical cleaning agents not in
accordance with AAMA recommendations or failure to use a systematic maintenance cleaning program in areas of high
salt concentration; Corrosive atmosphere found in the interior of buildings,which effect the interior surface of material;
Standing or ponding water on the metal; Excessive building movements; Work performed or materials supplied by others;
Improper treatment of finished material; Corrosion of the metal substrate; Incompatibility between materials, including, but
not limited to, Galvanic corrosion due to contact with adjacent dissimilar metals such as stainless steel; Damage to the
painted metal occasioned by moisture or other contamination detrimental to the finish because of improper storage of the
finished metal prior to installation as outlined in AAMA Publication 10, "Care and handling of Architectural Aluminum From
Shop to Site."
The legal remedies described in this Limited Warranty are the sole exclusive remedy of Customer. This limited warranty
will be void if payment from Customer is not received within a commercially reasonable time frame. GREENHECK
MAKES NO OTHER WARRANTY, EITHER EXPRESS OR IMPLIED, REGARDING ITS PRODUCTS, OR ITS
SELECTION AND APPLICATION, INCLUDING, BUT NOT LIMITED TO, COMPLIANCE WITH BUILDING CODES,
SAFETY CODES, LAWS, MERCHANTABILITY OR FITNESS OR A PARTICULAR PURPOSE. This limited warranty is
extended solely to the Customer. It is nontransferable and non-assignable, and the Customer shall not permit or
authorize its employees, agents, representatives or customers to claim, represent or imply that this limited warranty
extends or is available to anyone other than the Customer.
In the event of material breach by the Customer of any of the conditions of this warranty, Greenheck shall have no liability
for and product failure claims.
Failure to pay Greenheck in full for original services will automatically make this warranty null and void.
Greenheck will not be held liable for incidental or consequential damages of any kind. The limited warranty of product(s)
replaced or repaired under this limited warranty shall be limited to the remainder of the original warranty period.
Greenheck reserves the right to reasonable field access to diagnose and repair any product alleged to be defective. This
limited warranty may not be modified by anyone and may not be changed by such things as purchase order forms or
acceptance forms, unless otherwise agreed upon by Greenheck.
This limited warranty is provided in lieu of any other warranty requirements or obligations, including, but not limited to,
those within project specifications.
All notices and claims given under or pursuant to this agreement shall be in writing and sent by certified or registered mail,
postage prepaid, return receipt requested to: Greenheck,Attn: Louver Sales, 525 Western Road, Schofield,WI 54476.
By proceeding to use our products and services on your project,you accept the terms of these limited warranties.
Generated by:jfohr@johnsonair.com
CAPS 4.25.1969 O:\ChrisHessick\Bridgeport Family Medical TI.gfcj Page 4 of 4