Plans B Anik MADDEN&BAUGHMAN F F P, I N G . I N C: April 12, 2018 RECEID Mr. Mark Schick 2018 ARM Property Management CITY OF TIGARD PO Box 25030 Portland,Portland, Oregon ON RE: Rooftop Unit Structural Engineering Calculations Pacific Plaza, SW Hall and 99E, Tigard, Oregon Mr. Schick, Attached please find structural calculations pages for the anchorage of the rooftop unit replacement on the roof of the building located at Pacific Plaza in Tigard, Oregon, as shown on the attached details and dated April 12, 2018. Design is based on the requirements of the 2014 Oregon Structural Specialty Code. Sincerely, Jerome A. Madden, PE, SE PROFL- Principal '\\-\\ s OFFICE COPY 19386 j\p„,,,,,_ a CITY OF TIGARD OREGON REVIEWED FOR CODE COMPLIANCE • • 22 X901 Approved: F�OfiE A. 0,0\>� OTC: [ } EXPIRES 12-31-18 Permit #: javaTi Address: y i q �}[l S t f� :1r:c 1.4 rM'S) Suite #: By: Date: , a,3_ ) The attached calculations represent design for gravity and lateral loads as determined by the applicable building code. To the extent the design is based on information provided by the client or others, Madden & Baughman Engineering, Inc. has relied on such information and assumes that it is accurate. Madden & Baughman Engineering, Inc. shall have no liability with respect to means and methods of construction. The engineering reflects the finished product and no consideration has been made for temporary conditions that may exist during construction (such as loads induced during erection, shoring, etc.), which are entirely the responsibility of the contractor. Madden & Baughman Engineering, Inc.is and shall remain the owner of the calculations. Unauthorized use of these calculations is prohibited including but not limited to making changes to this project or use on other projects. 15 s;w 2r.1 ..c•u: iril,:50 :rtl:rd „'2{w . 5:341 323..7,1 Project: Pacific Plaza By:JAM Sheet No. tirMADDEN&BAUGHMAN Location:Tigard,Oregon ENG '' NEE RING , INC g g Date:04/11/18 Client:Arm property management Revised: Job No. Portland,OR Subject: Rootop Unit Date: Seismic Criteria for Non Structural Components: Risk Category= II Soil Site Class= D Seismic Design Category= D IP 1.00 Per Section 13.1.3(references are to ASCE 7-10 UNO) Ss 1 g Per USGS Si= 0.4 g Per USGS SMs= 1.10 Per USGS 5M1= 0.70 Per USGS SDs= 0.733 SDI= 0.467 z/h= 0.0 Roof W1= 802 lbs Roof Top Unit(Max) Wel= 399 lbs Seismic Weight(0.6-0.14SD5)D Section 13.3 Fp 0.4apSD5Wp(1+2(z/h)) (Eqn.13.3-1) (Rp/lp) Max FP 1.6S051pWp (Eqn.13.3-2) Min FP 0.3SDslpWp (Eqn.13.3-3) Mechanical Unit Mechanical Unit Vertical Seismic Component ap= 2.5 Table 13.6-1 Fp, 0.147 Wp 0.2*SDs*Wp RP 6.0 Table 13.6-1 FP 0.122 Wp Max FP 1.173 Wp Min FP 0.220 Wp O= 1 (not anchored to concrete) Design Fp 0.220 we F1= 176 lbs (Ultimate) Load per attachment: W= 47 in Width(Min.) H= 44 in Height(Max) H1= 26 in Assumed height to center of gravity(0.6*H1) M= -4715 lb-in Overturning Moment Vscrew 22 lbs Shear per holdown Tgross= -100 lbs Maximum Total uplift/tension Tholdown= -50 lbs Max.uplift per holdown Tend screw -13 lbs 2 H2.5A ea.End Vend screw= 44 lbs 2 H2.5A ea.End