Specifications (2) Vv\s-c2onocl)OSo
% I 02._V2) kYEl 6614/R- AAle---
Project:Arlington D_Biggi Const_Lot 2 Oak Woods Beams ;o_ page
IP- - ' Judith Souers
Location: Beam Nr.01 -Garage Door Header * ;� Suntel Design
Roof Beam 16865 Boones Ferry Rd Suite 201 of
[2015 International Building Code(2012 NDS)] - Lake Oswego,OR 97035
5.5 IN x 11.5 IN x 8.0 FT
#1 -Douglas-Fir-Larch(North)-Dry Use StruCalc Version 9.0.2.5 12/27/2016 3:56:07 PM
Section Adequate By: 125.8%
Controlling Factor: Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.03 IN L/2767
Dead Load 0.03 in
Total Load 0.07 IN L/1401 ___
--t.19 1 2017
Live Load Deflection Criteria: U240 Total Load Deflection Criteria: L/180
REACTIONS A B
CITY OF i'it ;- ° .;
Live Load 1680 lb 1680 lb BUILDINr4 q3 a
Dead Load 1638 lb 1638 lb
Total Load 3318 lb 3318 lb
Bearing Length 0.97 in 0.97 in
BEAM DATA
Span Length 8 ft -- — —
Unbraced Length-Top 7 ft A 8 ftT.
Unbraced Length-Bottom 0 ft
Roof Pitch 12 :12
Roof Duration Factor 1.15 ROOF LOADING
MATERIAL PROPERTIES Side One:
#1 -Douglas-Fir-Larch(North) Roof Live Load: LL= 30 psf
Base Values Adjusted Roof Dead Load: DL= 20 psf
Bending Stress: Fb= 1300 psi Fb'= 1483 psi Tributary Width: TW= 3 ft
Cd=1.15 CI=0.99 CF=1.00 Side Two:
Shear Stress: Fv= 170 psi Fv'= 196 psi Roof Live Load: LL= 30 psf
Cd=1.15 Roof Dead Load: DL= 20 psf
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi Tributary Width: TW= 11 ft
Min.Mod. of Elasticity: E_min= 580 ksi E_min'= 580 ksi
Comp. L to Grain: Fc- L= 625 psi Fc-1'= 625 psi Wall Load: WALL= 0
plf
Controlling Moment: 6635 ftIb SLOPE/PITCH ADJUSTED LENGTHS AND LOADS
4.0 ft from left support Adjusted Beam Length: Ladj= 8 ft
Created by combining all dead and live loads. Beam Self Weight: BSW= 13 plf
Controlling Shear: 3318 lb Beam Uniform Live Load: wL= 420 plf
At support. Beam Uniform Dead Load: wD_adj= 409 plf
Created by combining all dead and live loads. Total Uniform Load: wT= 829 plf
Comparisons with required sections: Req'd Provided
Section Modulus: 53.69 in3 121.23 in3
Area(Shear): 25.46 in2 63.25 in2
Moment of Inertia(deflection): 89.56 in4 697.07 in4
Moment: 6635 ft-lb 14982 ft-lb
Shear: 3318 lb 8244 lb
NOTES
4
Project:Arlington D_Biggi Const_Lot 2 Oak Woods_Beams page
:I — Judith Souers
Location: Beam Nr.02-Ceiling Beam at Foyer Suntel Design /
Multi-Loaded Multi-Span Beam . 16865 Boones Ferry Rd Suite 201 of
[2015 International Building Code(2012 NDS)] :.'..:.- Lake Oswego, OR 97035
6.75 INx10.5INx9.75FT
24F-V4-Visually Graded Western Species-Dry Use StruCalc Version 9.0.2.5 12/27/2016 3:56:07 PM
Section Adequate By: 13.4%
Controlling Factor:Shear
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.17 IN L/687
Dead Load 0.12 in
Total Load 0.29 IN L/404
Live Load Deflection Criteria: L/360 Total Load Deflection Criteria: L/240 1
REACTIONS A B
Live Load 6446 lb 4172 lb
Dead Load 4598 lb 3041 lb ' .
Total Load 11044 lb 7213 lb
Bearing Length 2.52 in 1.64 in
w
BEAM DATA Center
Span Length 9.75 ft
ii
Unbraced Length-Top 1.33 ft -9.75 ft --
Unbraced Length-Bottom 9.75 ft
Live Load Duration Factor 1.00
Camber Adj. Factor 0 UNIFORM LOADS Center
Camber Required 0 Uniform Live Load 70 plf
Notch Depth 0.00 Uniform Dead Load 135 plf
MATERIAL PROPERTIES Beam Self Weight 15 plf
24F-V4-Visually Graded Western Species Total Uniform Load 220 plf
Base Values Adjusted POINT LOADS-CENTER SPAN
Bending Stress: Fb= 2400 psi Controlled by: Load Number One
Fb_cmpr= 1850 psi Fb'= 2398 psi Live Load 2300 lb
Cd=1.00 C1=1.00 Dead Load 1800 lb
Shear Stress: Fv= 265 psi Fv'= 265 psi Location 0.67 ft
Cd=1.00
Modulus of Elasticity: E= 1800 ksi E'= 1800 ksi TRAPEZOIDAL LOADS-CENTER SPAN
Comp.1-to Grain: Fc-1-= 650 psi Fc-1-'= 650 psi Load Number One Two Three
Left Live Load 360 plf 80 plf 570 plf
Controlling Moment: 19789 ft-lb Left Dead Load 135 plf 30 plf 380 plf
4.58 Ft from left support of span 2(Center Span) Right Live Load 360 plf 80 plf 570 plf
Created by combining all dead loads and live loads on span(s)2 Right Dead Load 135 plf 30 plf 380 plf
Controlling Shear: 11045 lb Load Start 0 ft 6 ft 0.67 ft
At left support of span 2(Center Span) Load End 6 ft 9.75 ft 9.75 ft
Created by combining all dead loads and live loads on span(s)2 Load Length 6 ft 3.75 ft 9.08 ft
Comparisons with required sections: Req'd Provided
Section Modulus: 99.02 in3 124.03 in3
Area(Shear): 62.52 in2 70.88 in2
Moment of Inertia(deflection): 386.88 in4 651.16 in4
Moment: 19789 ft-lb 24786 ft-lb
Shear: 11045 lb 12521 lb
NOTES
Project:Arlington D_Biggi Const_Lot 2 Oak Woods Beams { ; page
-- Judith Souers
Location: Beam Nr.03-Roof Beam at Front Porch -j Suntel Design
Roof Beam 16865 Boones Ferry Rd Suite 201 of
[2015 International Building Code(2012 NDS)]
3 ��"Lake Oswego,OR 97035
.5 IN x 9.25 IN x 10.75 FT
#2-Douglas-Fir-Larch(North)-Dry Use StruCalc Version 9.0.2.5 12/27/2016 3:56:07 PM
Section Adequate By: 102.4%
Controlling Factor:Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.07 IN L/1762
Dead Load 0.06 in
Total Load 0.14 IN L/953
Live Load Deflection Criteria: L/240 Total Load Deflection Criteria: L/180
REACTIONS A_
Live Load 484 lb 484 lb
Dead Load 410 lb 410 lb
Total Load 894 lb 894 lb
Bearing Length 0.41 in 0.41 in
BEAM DATA I _
Span Length 10.8 ft — —
A
Unbraced Length-Top 2 ft 10.75 ft
Unbraced Length-Bottom 0 ft A
Roof Pitch 7 :12
Roof Duration Factor 1.15
ROOF LOADING
MATERIAL PROPERTIES Side One:
#2-Douglas-Fir-Larch(North) Roof Live Load: LL= 30 psf
Base Values Adjusted Roof Dead Load: DL= 20 psf
Bending Stress: Fb= 850 psi Fb'= 1169 psi Tributary Width: TW= 1.5 ft
Cd=1.15 C1=1.00 CF=1.20 Side Two:
Shear Stress: Fv= 180 psi Fv'= 207 psi Roof Live Load: LL= 30 psf
Cd=1.15 Roof Dead Load: DL= 20 psf
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi Tributary Width: TW= 1.5 ft
Min. Mod.of Elasticity: Emin= 580 ksi E_min'= 580 ksi
Comp.1 to Grain: Fc- = 625 psi Fc- = 625 psi Wall Load: WALL= 0
plf
Controlling Moment: 2403 ft Ib SLOPE/PITCH ADJUSTED LENGTHS AND LOADS
5.375 ft from left support Adjusted Beam Length: Ladj= 10,75 ft
Created by combining all dead and live loads. Beam Self Weight: BSW= 7 plf
Controlling Shear: 894 lb Beam Uniform Live Load: wL= 90 plf
At support. Beam Uniform Dead Load: wD_adj= 76 plf
Created by combining all dead and live loads. Total Uniform Load: wT= 166 plf
Comparisons with required sections: Req'd Provided
Section Modulus: 24.66 in3 49.91 in3
Area(Shear): 6.48 in2 32.38 in2
Moment of Inertia(deflection): 43.58 in4 230.84 in4
Moment: 2403 ft-lb 4863 ft-lb
Shear: 894 lb 4468 lb
NOTES
page
, Project:Arlington D_Biggi Const_Lot 2 Oak Woods Beams
-- --11Judith Souers
Location:Beam Nr.04-Roof Beam at Entry Suntel Design
Multi-Loaded Multi-Span Beam '71417 16865 Boones Ferry Rd Suite 201 of
[2015 International Building Code(2012 NDS)]
Lake Oswego,OR 97035
3.5 IN x 9.25 IN x 6.0 FT '
#2-Douglas-Fir-Larch(North)-Dry Use StruCalc Version 9.0.2.5 12/27/2016 3:56:08 PM
Section Adequate By: 102.6%
Controlling Factor:Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.02 IN L/3631
Dead Load 0.02 in
Total Load 0.04 IN L/2012
Live Load Deflection Criteria: L/360 Total Load Deflection Criteria: L/240
REACTIONS A
Live Load 805 lb 739 lb
Dead Load 634 lb 646 lb
Total Load 1439 lb 1385 lb TR2
Bearing Length 0.66 in 0.63 in
w
BEAM DATA Center
Span Length 6 ft
Unbraced Length-Top 2 ft s ft
Unbraced Length-Bottom 6 ft
Live Load Duration Factor 1.00
Notch Depth 0.00 UNIFORM LOADS Center
MATERIAL PROPERTIES Uniform Live Load 120 plf
#2-Douglas-Fir-Larch(North) Uniform Dead Load 80 plf
Base Values Adjusted Beam Self Weight 7 plf
Bending Stress: Fb= 850 psi Fb'= 1017 psi Total Uniform Load 207 plf
Cd=1.00 C1=1.00 CF=1.20 POINT LOADS-CENTER SPAN
Shear Stress: Fv= 180 psi Fv'= 180 psi Load Number One
Cd=1.00 Live Load 500 lb
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi Dead Load 425 Ib
Comp. L to Grain: Fc-1= 625 psi Fc- L'= 625 psi Location 1.75 ft
Controlling Moment: 2088 ft-lb TRAPEZOIDAL LOADS-CENTER SPAN
1.86 Ft from left support of span 2(Center Span) Load Number One Two
Created by combining all dead loads and live loads on span(s)2 Left Live Load 45 plf 210 plf
Controlling Shear: 1439 lb Left Dead Load 30 plf 240 plf
At left support of span 2(Center Span) Right Live Load 45 plf 210 plf
Created by combining all dead loads and live loads on span(s)2 Right Dead Load 30 plf 240 plf
Load Start 0 ft 4.83 ft
Comparisons with required sections: Req'd Provided Load End 1.75 ft 6 ft
Section Modulus: 24.64 in3 49.91 in3 Load Length 1.75 ft 1.17 ft
Area(Shear): 11.99 in2 32.38 in2
Moment of Inertia(deflection): 27.54 in4 230.84 in4
Moment: 2088 ft-lb 4230 ft-lb
Shear: 1439 lb 3885 lb
NOTES
Project:Arlington D_Biggi Const_Lot 2 Oak Woods Beams r.° page
liJudith Souers
Location: Beam Nr.05-Roof Beam at Entry Suntel Design
Roof Beam 16865 Boones Ferry Rd Suite 201 of
[2015 International Building Code(2012 NDS)] –Lake Oswego,OR 97035
3.5 INx9.25INx9.0FT
#2-Douglas-Fir-Larch(North)-Dry Use StruCalc Version 9.0.2.5 12/27/2016 3:56:08 PM
Section Adequate By: 127.7%
Controlling Factor:Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.04 IN L/2574
Dead Load 0.04 in
Total Load 0.08 IN L/1282
Live Load Deflection Criteria: L/240 Total Load Deflection Criteria: L/180
REACTIONS A
Live Load 473 lb 473 lb
Dead Load 476 lb 476 lb
Total Load 949 lb 949 lb
Bearing Length 0.43 in 0.43 in
BEAM DATA
Span Length 9 ft — —
Unbraced Length-Top 2 ft 9 ft
Unbraced Length-Bottom 0 ft
Roof Pitch 12 :12
Roof Duration Factor 1.15 ROOF LOADING
MATERIAL PROPERTIES Side One:
#2-Douglas-Fir-Larch(North) Roof Live Load: LL= 30 psf
Base Values Adjusted Roof Dead Load: DL= 20 psf
Bending Stress: Fb= 850 psi Fb'= 1169 psi Tributary Width: TW= 2 ft
Cd=1.15 C1=1.00 CF=1.20 Side Two:
Shear Stress: Fv= 180 psi Fv'= 207 psi Roof Live Load: LL= 30 psf
Cd=1.15 Roof Dead Load: DL= 20 psf
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi Tributary Width: TW= 1.5 ft
Min. Mod.of Elasticity: Emin= 580 ksi E_min'= 580 ksi
Comp. L to Grain: Fc--L= 625 psi Fc--- = 625 psi Wall Load: WALL= 0
plf
Controlling Moment: 2135 ft Ib SLOPE/PITCH ADJUSTED LENGTHS AND LOADS
4.5 ft from left support Adjusted Beam Length: Ladj= 9 ft
Created by combining all dead and live loads. Beam Self Weight: BSW= 7 plf
Controlling Shear: 949 lb Beam Uniform Live Load: wL= 105 plf
At support. Beam Uniform Dead Load: wD_adj= 106 plf
Created by combining all dead and live loads. Total Uniform Load: wT= 211 plf
Comparisons with required sections: Rea'd Provided
Section Modulus: 21.92 in3 49.91 in3
Area(Shear): 6.88 in2 32.38 in2
Moment of Inertia(deflection): 32.42 in4 230.84 in4
Moment: 2135 ft-lb 4863 ft-lb
Shear: 949 lb 4468 lb
NOTES
11
Project:Arlington D_Biggi Const_Lot 2 Oak Woods Beams --:-Lt
` Page
41$Judith Souers
Location: Beam Nr.06-Ceiling Beam at Garage j ;, Suntel Design /
Multi-Loaded Multi-Span Beam 16865 Boones Ferry Rd Suite 201 of
[2015 International Building Code(2012 NDS)] -,i, Lake Oswego, OR 97035
5.5 INx21.0INx19.5FT
24F-V4-Visually Graded Western Species-Dry Use StruCalc Version 9.0,2.5 12/27/2016 3:56:08 PM
Section Adequate By:90.7%
Controlling Factor: Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.19 IN L/1263
Dead Load 0.17 in
Total Load 0.36 IN L/655
Live Load Deflection Criteria: U360 Total Load Deflection Criteria: L/240
1
REACTIONS A B
Live Load 4028 lb 4327 lb
Dead Load 3857 lb 3782 Ib
Total Load 7885 lb 8109 lbk�,. '`:
TRa TR1
a., :.: ..
Bearing Length 2.21 in 2.27 in
w
BEAM DATA Center
Span Length 19.5 ft - -
Unbraced Length-Top 1.33 ft -- 19.5 ft-
Unbraced Length-Bottom 19.5 ft
Live Load Duration Factor 1.00
Camber Adj. Factor 1.5 UNIFORM LOADS Center
Camber Required 0.26 Uniform Live Load 270 plf
Notch Depth 0.00 Uniform Dead Load 180 plf
MATERIAL PROPERTIES Beam Self Weight 25 plf
24F-V4-Visually Graded Western Species Total Uniform Load 475 plf
Base Values Adjusted POINT LOADS-CENTER SPAN
Bending Stress: Fb= 2400 psi Controlled by: Load Number One
Fbcmpr= 1850 psi Fb'= 2270 psi Live Load 350 lb
Cd-=/.00 C1=1.00 Cv=0.95 Dead Load 370 lb
Shear Stress: Fv= 265 psi Fv'= 265 psi Location 11.5 ft
Cd=9.00
Modulus of Elasticity: E= 1800 ksi E'= 1800 ksi TRAPEZOIDAL LOADS-CENTER SPAN
Comp.1 to Grain: Fc- L= 650 psi Fc--- = 650 psi Load Number One Two
Left Live Load 170 plf 120 plf
Controlling Moment: 40107 ft-lb Left Dead Load 150 plf 180 plf
10.14 Ft from left support of span 2(Center Span) Right Live Load 170 plf 120 plf
Created by combining all dead loads and live loads on span(s)2 Right Dead Load 150 plf 180 plf
Controlling Shear: -8108 lb Load Start 11.5 ft 0 ft
19.0 Ft from left support of span 2(Center Span) Load End 19.5 ft 11.5 ft
Created by combining all dead loads and live loads on span(s)2 Load Length 8 ft 11.5 ft
Comparisons with required sections: Req'd Provided
Section Modulus: 212.01 in3 404.25 in3
Area(Shear): 45.9 in2 115.5 in2
Moment of Inertia(deflection): 1554.29 in4 4244.63 in4
Moment: 40107 ft-lb 76476 ft-lb
Shear: -8108 lb 20405 lb
NOTES
' page
. Project:Arlington D_Biggi Const_Lot 2 Oak Woods Beamsil
- — '`"Judith Souers
Location:Beam Nr.07-Garage Door Header
Multi Loaded Multi-San Beam l �. Suntel Design
P 16865 Boones Ferry Rd Suite 201 of
[2015 International Building2012 NDS "
Code(2012 )] �.::"-,,,," -'Lake Oswego, OR 97035
5.5 IN x 12.0 IN x 16.5 FT
24F-V4-Visually Graded Western Species-Dry Use StruCalc Version 9.0.2.5 12/27/2016 3:56:08 PM
Section Adequate By: 106.1%
Controlling Factor: Deflection
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.22 IN L/904
Dead Load 0.18 in
Total Load 0.40 IN L/495
Live Load Deflection Criteria: L/360 Total Load Deflection Criteria: L/240
1
REACTIONS A B
Live Load 1322 lb 1791 lb
Dead Load 1060 lb 1526 lb
Total Load 2382 lb 3317 lb
Bearing Length 0.67 in 0.93 in
BEAM DATA Center
Span Length 16.5 ft
i
Unbraced Length-Top 0 ft A 16.5 ft =B
Unbraced Length-Bottom 16.5 ft
Live Load Duration Factor 1.00
Camber Adj. Factor 1 UNIFORM LOADS Center
Camber Required 0.18 Uniform Live Load 75 plf
Notch Depth 0.00 Uniform Dead Load 50 plf
MATERIAL PROPERTIES Beam Self Weight 14 plf
24F-V4-Visually Graded Western Species Total Uniform Load 139 plf
Base Values Adjusted POINT LOADS-CENTER SPAN
Bending Stress: Fb= 2400 psi Controlled by:
Fb_cmpr= 1850 psi Fb'= 2400 psi Load Number One
Cd=1.00 Live Load 170 lb
Dead Load 150 lb
Shear Stress: Fv= 265 psi Fv'= 265 psi Location 10 ft
Cd=1.00
Modulus of Elasticity: E= 1800 ksi E'= 1800 ksi TRAPEZOIDAL LOADS-CENTER SPAN
Comp. L to Grain: Fc--I-= 650 psi Fc-1'= 650 psi Load Number One Two
Left Live Load 60 plf 170 plf
Controlling Moment: 11855 ft-lb Left Dead Load 40 plf 150 plf
9.9 Ft from left support of span 2(Center Span) Right Live Load 60 plf 170 plf
Created by combining all dead loads and live loads on span(s)2 Right Dead Load 40 plf 150 plf
Controlling Shear: -3317 lb Load Start 0 ft 10 ft
16.0 Ft from left support of span 2(Center Span) Load End 10 ft 16.5 ft
Created by combining all dead loads and live loads on span(s)2 Load Length 10 ft 6.5 ft
Comparisons with required sections: Read Provided
Section Modulus: 59.27 in3 132 in3
Area(Shear): 18.77 in2 66 in2
Moment of Inertia(deflection): 384.19 in4 792 in4
Moment: 11855 ft-lb 26400 ft-lb
Shear: -3317 lb 11660 lb
NOTES
, Project:Arlington D_Biggi Const_Lot 2 Oak Woods Beams
►��";, Page
- — •'Judith Souers
Location: Beam Nr.08-Carrier Beam at Garage j-iw Suntel Design
Multi-Loaded Multi-Span Beam ' 16865 Boones Ferry Rd Suite 201 of
[2015 International Building Code(2012 NDS)]
5.5 IN x 24.0 IN x 20.75 FT .�"Lake Oswego,OR 97035
24F-V4-Visually Graded Western Species-Dry Use StruCalc Version 9.0.2.5 12/27/2016 3:56:09 PM
Section Adequate By:39.4%
Controlling Factor:Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.21 IN L/1195
Dead Load 0.20 in
Total Load 0.41 IN L/610
Live Load Deflection Criteria: L/360 Total Load Deflection Criteria: L/240 1
2
REACTIONS A_
Live Load 8147 lb 3208 lb
Dead Load 7383 lb 3577 lb
Total Load 15530 lb 6785 lb
Bearing Length 4.34 in 1.90 in
BEAM DATA Center
Span Length 20.75 ft ---
Unbraced Length-Top 0 ft -20.75 ft
Unbraced Length-Bottom 20.75 ft
Live Load Duration Factor 1.00
Camber Adj. Factor 1 UNIFORM LOADS Center
Camber Required 0.2 Uniform Live Load 60 plf
Notch Depth 0.00 Uniform Dead Load 40 plf
MATERIAL PROPERTIES Beam Self Weight 29 plf
24F-V4-Visually Graded Western Species Total Uniform Load 129 plf
Base Values Adjusted POINT LOADS-CENTER SPAN
Bending Stress: Fb= 2400 psi Controlled by: Load Number One Two
Fb_cmpr= 1850 psi Fb'= 2226 psi Live Load 4800 lb 4100 lb
Cd=1.00 Cv=0.93 Dead Load 3200 lb 3900 lb
Shear Stress: Fv= 265 psi Fv'= 265 psi Location 5.5 ft 4 ft
Cd=1.00
Modulus of Elasticity: E= 1800 ksi E'= 1800 ksi TRAPEZOIDAL LOADS-CENTER SPAN
Comp.1-to Grain: Fc- = 650 psi Fc-1'= 650 psi Load Number One Two
Left Live Load 360 plf 40 plf
Controlling Moment: 70246 ft-lb Left Dead Load 340 plf 115 plf
5.6 Ft from left support of span 2(Center Span) Right Live Load 360 plf 40 plf
Created by combining all dead loads and live loads on span(s)2 Right Dead Load 340 plf 115 plf
Controlling Shear: 15529 lb Load Start 4 ft 4 ft
At left support of span 2(Center Span) Load End 5.5 ft 20.75 ft
Created by combining all dead loads and live loads on span(s)2 Load Length 1.5 ft 16.75 ft
Comparisons with required sections: Req'd Provided
Section Modulus: 378.65 in3 528 in3
Area(Shear): 87.9 in2 132 in2
Moment of Inertia(deflection): 2491.4 in4 6336 in4
Moment: 70246 ft-lb 97952 ft-lb
Shear: 15529 lb 23320 lb
NOTES
Project:Arlington D_Biggi Const_Lot 2 Oak Woods Beams T d`` page
- ----IJudith Souers
Location: Beam Nr.09-Header at Slider Suntel Design
Combination Roof And Floor Beam .. 16865 Boones Ferry Rd Suite 201 of
[2015 International Building Code(2012 NDS)] -Iii,' ,-Lake Oswego, OR 97035
5.5 IN x 9.5 IN x 6.5 FT
#1 -Douglas-Fir-Larch(North)-Dry Use StruCalc Version 9.0.2.5 12/27/2016 3:56:09 PM
Section Adequate By:22.9%
Controlling Factor:Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.06 IN L/1335
Dead Load 0.04 in
Total Load 0.10 IN L/770
Live Load Deflection Criteria: L/360 Total Load Deflection Criteria: L/240
REACTIONS A B
Live Load 2974 lb 2974 lb
Dead Load 2180 lb 2180 lb
Total Load 5154 lb 5154 lb
Bearing Length 1.50 in 1.50 in
BEAM DATA Center
Span Length 6.5 ft —
Unbraced Length-Top 1.33 ft A 6.5 ft
Roof Pitch 6 :12
Floor Duration Factor 1.00
Roof Duration Factor 1.15 ROOF LOADING
Notch Depth 0.00
Side 1 Side 2
MATERIAL PROPERTIES Roof Live Load RLL= 30 psf 30 psf
#1 -Douglas-Fir-Larch(North) Roof Dead Load RDL= 20 psf 20 psf
Base Values Adjusted Roof Tributary Width RTW= 17 ft 2.5 ft
Bending Stress: Fb= 1300 psi Fb'= 1493 psi
Cd=1.15 CI=1.00 CF=1.00 FLOOR LOADING
Shear Stress: Fv= 170 psi Fv'= 196 psi Side 1 Side 2
Cd=1.15 Floor Live Load FLL= 40 psf 40 psf
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi Floor Dead Load FDL= 15 psf 15 psf
Min. Mod.of Elasticity: E_min= 580 ksi E_min'= 580 ksi Floor Tributary Width FTW= 8.3 ft 0 ft
Comp.-L to Grain: Fc--L= 625 psi Fc-1'= 625 psi
Wall Load WALL= 100 plf
Controlling Moment: 8375 ft-lb BEAM LOADING
3.25 ft from left support Roof Uniform Live Load: wL-roof= 585 plf
Created by combining all dead and live loads. Roof Uniform Dead Load: wD-roof= 436 plf
Controlling Shear: 5154 lb Floor Uniform Live Load: wL-floor= 330 plf
At support. Floor Uniform Dead Load: wD-floor= 124 plf
Created by combining all dead and live loads. Beam Self Weight: BSW- 11 plf
Combined Uniform Live Load: wL= 915 plf
Comparisons with required sections: Read Provided Combined Uniform Dead Load: wD= 671 plf
Section Modulus: 67.3 in3 82.73 in3 Combined Uniform Total Load: wT= 1586 plf
Area(Shear). 39.55 in2 52.25 in2 Controlling Total Design Load: wT-cont= 1586 plf
Moment of Inertia(deflection): 122,47 in4 392.96 in4
Moment: 8375 ft-lb 10295 ft-lb
Shear: 5154 lb 6810 lb
NOTES
• Project:Arlington D_Biggi Const_Lot 2 Oak Woods Beams page
,- ,,, `Judith Souers
Location: Beam Nr. 10-Header at Great Room ,r;; ' Suntel Design
Multi-Span Floor Beam 16865 Boones Ferry Rd Suite 201 of
[2015 International BuildingCode 2012 NDS)] "
( � - -Lake Oswego,OR 97035
5.5 IN x 9.5 IN x 5.5 FT
#1 -Douglas-Fir-Larch(North)-Dry Use StruCalc Version 9.0.2.5 12/27/2016 3:56:09 PM
Section Adequate By:20.8%
Controlling Factor:Shear
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.03 IN L/2389
Dead Load 0.02 in
Total Load 0.04 IN L/1484
Live Load Deflection Criteria: U360 Total Load Deflection Criteria: L/240
REACTIONS A_
Live Load 3021 lb 1549 lb
Dead Load 1882 lb 900 lb
Total Load 4903 lb 2449 lb
Bearing Length 1.43 in 0.71 in
BEAM DATA Center
Span Length 5.5 ft - ---
Unbraced Length-Top 1.33 ft 5.5 ft - -=B
Unbraced Length-Bottom 5.5 ft
Floor Duration Factor 1.00
Notch Depth 0.00 FLOOR LOADING Center
MATERIAL PROPERTIES Floor Live Load FLL= 40 psf
#1 -Douglas-Fir-Larch(North) Floor Dead Load FDL= 15 psf
Base Values Adjusted Floor Tributary Width Side One TW1 = 0 ft
Bending Stress: Fb= 1300 psi Fb'= 1299 psi Floor Tributary Width Side Two TW2= 8.5 ft
Cd=1.00 C1=1.00 CF=1.00 Wall Load WALL= 40 plf
Shear Stress: Fv= 170 psi Fv'= 170 psi
Cd=1.00 POINT LOADS-CENTER SPAN
Load Number One
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi Live Load 2700 lb
Min.Mod.of Elasticity: E_min= 580 ksi Emin'= 580 ksi
_ Dead Load 1800 Ib
Comp.1 to Grain: Fc---= 625 psi Fc-1'= 625 psi Location 1.25 ft
Controlling Moment: 5720 ft-lb BEAM LOADING Center
1.26 Ft from left support of span 2(Center Span) Reduced Floor Live Load 40 psf
Created by combining all dead loads and live loads on span(s)2 Total Live Load 340 plf
Controlling Shear: 4903 lb Total Dead Load 168 plf
At left support of span 2(Center Span) Beam Self Weight 11 plf
Created by combining all dead loads and live loads on span(s)2 Total Load 519 plf
Comparisons with required sections: Reed Provided
Section Modulus: 52.86 in3 82.73 in3
Area(Shear): 43.27 in2 52.25 in2
Moment of Inertia(deflection): 63.57 in4 392.96 in4
Moment: 5720 ft-lb 8954 ft-lb
Shear: 4903 lb 5922 lb
NOTES
Project:Arlington D_Biggi Const_Lot 2 Oak Woods_Beams { page
"Judith Souers
Location: Beam Nr. 11 Header at Great Rom /
('its; Suntel Design
Multi-Loaded Multi-Span Beam .,' 16865 Boones Ferry Rd Suite 201 of
[2015 International Building Code(2012 NDS)]
Lake Oswego, OR 97035
3.5 IN x 11.25 IN x 5.5 FT �-:�^�-�. -
#2 Douglas-Fir-Larch(North) Dry Use StruCalc Version 9.0.2.5 12/27/2016 3:56:09 PM
Section Adequate By: 11.0%
Controlling Factor: Shear
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.02 IN L/3117
Dead Load 0.01 in
Total Load 0.03 IN L/1952
Live Load Deflection Criteria: L/360 Total Load Deflection Criteria: L/240
1
REACTIONS A B
Live Load 2609 lb 1354 lb
Dead Load 1649 lb 771 lb
Total Load 4258 Ib 2125 Ib 'MI
Bearing Length 1.95 in 0.97 in
w
BEAM DATA Center
Span Length 5.5 ft - _ir
Unbraced Length-Top 1.33 ft A -5.5 ft
Unbraced Length-Bottom 5.5 ft B
Live Load Duration Factor 1.00
Notch Depth 0.00 UNIFORM LOADS Center
MATERIAL PROPERTIES Uniform Live Load 340 plf
#2-Douglas-Fir-Larch(North) Uniform Dead Load 130 plf
Base Values Adjusted Beam Self Weight 8 plf
Bending Stress: Fb= 850 psi Fb'= 933 psi Total Uniform Load 478 plf
Cd=9.00 C1=1.00 CF=1.10 POINT LOADS-CENTER SPAN
Shear Stress: Fv= 180 psi Fv'= 180 psi Load Number One
Cd=1.00 Live Load 1375 Ib
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi Dead Load 880 Ib
Min. Mod.of Elasticity: E_ _min= 580 ksi Emin'= 580 ksi Location 1.33 ft
Comp.1 to Grain: Fc-1= 625 psi Fc-1-'= 625 psi
TRAPEZOIDAL LOADS-CENTER SPAN
Controlling Moment: 4355 ft-lb Load Number One Two
1.38 Ft from left support of span 2(Center Span) Left Live Load 540 plf 0 plf
Created by combining all dead loads and live loads on span(s)2 Left Dead Load 460 plf 40 plf
Controlling Shear: 4258 lb Right Live Load 540 plf 0 plf
At left support of span 2(Center Span) Right Dead Load 460 plf 40 plf
Created by combining all dead loads and live loads on span(s)2 Load Start 0 ft 1.33 ft
Load End 1.33 ft 5.5 ft
Comparisons with required sections: Rea'd Provided Load Length 1.33 ft 4.17 ft
Section Modulus: 56.01 in3 73.83 in3
Area(Shear): 35.48 in2 39.38 in2
Moment of Inertia(deflection): 51.07 in4 415.28 in4
Moment: 4355 ft-lb 5740 ft-lb
Shear: 4258 lb 4725 lb
NOTES
page
• Project:Arlington D_Biggi Const_Lot 2 Oak Woods Beams ►'
- ——~ Judith Souers
Location: Beam Nr. 12-Header to Garager Suntel Design
Multi-Loaded Multi-Span Beam A.C.—rNiCh16865 Boones Ferry Rd Suite 201 of
[2015 International Building Code(2012 NDS)] --.Lake Oswego, OR 97035
5.5 INx11.5INx3.0FT
#1 -Douglas-Fir-Larch(North)-Dry Use StruCalc Version 9.0.2.5 12/27/2016 3:56:10 PM
Section Adequate By:33.7%
Controlling Factor:Shear
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.00 IN L/MAX
Dead Load 0.00 in
Total Load 0.00 IN L/MAX
Live Load Deflection Criteria: L/360 Total Load Deflection Criteria: L/240
REACTIONS A_
Live Load 3145 lb 395 lb
Dead Load 2217 lb 383 lb
Total Load 5362 lb 778 lb
Bearing Length 1.56 in 0.23 in
BEAM DATA Center
Span Length 3 ft --
Unbraced Length-Top 0 ft - 3f
Unbraced Length-Bottom 3 ft
Live Load Duration Factor 1.00
Notch Depth 0.00 UNIFORM LOADS Center
MATERIAL PROPERTIES Uniform Live Load 80 plf
#1 -Douglas-Fir-Larch(North) Uniform Dead Load 120 plf
Base Values Adjusted Beam Self Weight 13 plf
Bending Stress: Fb= 1300 psi Fb'= 1300 psi Total Uniform Load 213 plf
Cd=1.00 CF=1.00 POINT LOADS-CENTER SPAN
Shear Stress: Fv= 170 psi Fv'= 170 psi Load Number One
Cd=1.00 Live Load 3300 lb
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi Dead Load 2200 lb
Comp.--to Grain: Fc- = 625 psi Fc-1'= 625 psi Location 0.25 ft
Controlling Moment: 1330 ft-lb
0.27 Ft from left support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Controlling Shear: 5362 lb
At left support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Comparisons with required sections: Rea'd Provided
Section Modulus: 12.28 in3 121.23 in3
Area(Shear): 47.31 in2 63.25 in2
Moment of Inertia(deflection): 7.24 in4 697.07 in4
Moment: 1330 ft-lb 13133 ft-lb
Shear: 5362 lb 7168 lb
NOTES
P
Project:Arlington D_Biggi Const_Lot 2 Oak Woods Beams -#; page
Judith Souers
Location: Beam Nr. 13-Header at Utility ,r;, Suntel Design /
Roof Beam 16865 Boones Ferry Rd Suite 201 of
2015 International BuildingCode 2012 NDS)] `- .. .,
( -;,, -Lake Oswego, OR 97035
5.5 IN x 9.5IN x 3.0 FT
#1 -Douglas-Fir-Larch(North)-Dry Use StruCalc Version 9.0.2.5 12/27/2016 3:56:10 PM
Section Adequate By:24.0%
Controlling Factor:Shear
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.01 IN L/5493
Dead Load 0.00 in
Total Load 0.01 IN L/3292
Live Load Deflection Criteria: L/240 Total Load Deflection Criteria: L/180
REACTIONS A B
Live Load 3290 lb 1690 lb
Dead Load 2200 lb 1134 lb
Total Load 5490 lb 2824 lb 1
Bearing Length 1.60 in 0.82 in
BEAM DATA
Span Length 3 ft *
-- — =--
Unbraced Length-Top 2 ft 3 ft
Unbraced Length-Bottom 0 ft
Roof Pitch 6 :12
Roof Duration Factor 1.15 ROOF LOADING
MATERIAL PROPERTIES Side One:
#1 -Douglas-Fir-Larch(North) Roof Live Load: LL= 30 psf
Base Values Adjusted Roof Dead Load: DL= 15 psf
Bending Stress: Fb= 1300 psi Fb'= 1492 psi Tributary Width. TW= 1 ft
Cd=1.15 CI=1.00 CF=1.00 Side Two:
Shear Stress: Fv= 170 psi Fv'= 196 psi Roof Live Load: LL= 30 psf
Cd=1.15 Roof Dead Load: DL= 15 psf
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi Tributary Width: TW= 1 ft
Comp.L to Grain: Fc-L= 625 psi Fc-L'= 625 psi
Point Live Load LL= 4800 lb
Controlling Moment: 5386 ft-lb Point Dead Load DL= 3200 lb
1.5 ft from left support Point Load Location @ 1 ft
Created by combining all dead and live loads.
Controlling Shear: 5490 lb Wall Load: WALL= 0 plf
At support.
Created by combining all dead and live loads. SLOPE/PITCH ADJUSTED LENGTHS AND LOADS
Adjusted Beam Length: Ladj= 3 ft
Beam Self Weight: BSW= 11 plf
Comparisons with required sections: Req'd Provided Beam Uniform Live Load: wL= 60 plf
Section Modulus: 43.3 in3 82.73 in3 Beam Uniform Dead Load: wD_adj= 45 plf
Area(Shear): 42.13 in2 52.25 in2 Total Uniform Load: wT= 105 plf
Moment of Inertia(deflection): 21.49 in4 392.96 in4
Moment: 5386 ft-lb 10289 ft-lb
Shear: 5490 lb 6810 lb
NOTES
Project:Arlington D_Biggi Const_Lot 2 Oak Woods Beams ,r,:' page
-----40Judith Souers
Location: Beam Nr. 14-Roof Beam at Covered Patio Suntel Design
Roof Beam 16865 Boones Ferry Rd Suite 201 of
[2015 International Building Code(2012 NDS)] ""'
- -°Lake Oswego, OR 97035
3.5 IN x 9.25 IN x 10.0 FT
#2-Douglas-Fir-Larch(North)-Dry Use StruCalc Version 9.0.2.5 12/27/2016 3:56:10 PM
Section Adequate By: 11.0%
Controlling Factor:Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.14 IN L/876
Dead Load 0.08 in
Total Load 0.21 IN L/562
Live Load Deflection Criteria: L/240 Total Load Deflection Criteria: L/180
REACTIONS A
Live Load 1125 lb 1125 lb
Dead Load 627 lb 627 lb
Total Load 1752 lb 1752 lb
Bearing Length 0.80 in 0.80 in
BEAM DATA
Span Length 10 ft -
Unbraced Length-Top 2 ft A 10 ft
Unbraced Length-Bottom 0 ft
Roof Pitch 4 :12
Roof Duration Factor 1.15 ROOF LOADING
MATERIAL PROPERTIES Side One:
#2-Douglas-Fir-Larch(North) Roof Live Load: LL= 30 psf
Base Values Adjusted Roof Dead Load: DL= 15 psf
Bending Stress: Fb= 850 psi Fb'= 1169 psi Tributary Width: TW= 1.5 ft
Cd=1.15 C1=1.00 CF=1.20 Side Two:
Shear Stress: Fv= 180 psi Fv'= 207 psi Roof Live Load: LL= 30 psf
Cd=1.15 Roof Dead Load: DL= 15 psf
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi Tributary Width: TW= 6 ft
Comp. L to Grain: Fc- = 625 psi Fc--L'= 625 psi
Wall Load: WALL= 0
Controlling Moment: 4381 ft-lb plf
5.0 ft from left support SLOPE/PITCH ADJUSTED LENGTHS AND LOADS
Created by combining all dead and live loads. Adjusted Beam Length: Ladj= 10 ft
Controlling Shear: 1752 lb Beam Self Weight: BSW= 7 plf
At support. Beam Uniform Live Load: wL= 225 plf
Created by combining all dead and live loads. Beam Uniform Dead Load: wD_adj= 125 plf
Comparisons with required sections: Read Provided
Total Uniform Load: wT= 350 plf
Section Modulus: 44.97 in3 49.91 in3
Area(Shear): 12.7 in2 32.38 in2
Moment of Inertia(deflection): 73.91 in4 230.84 in4
Moment: 4381 ft-lb 4863 ft-lb
Shear: 1752 lb 4468 lb
NOTES
• Project Arlington D_Biggi Const_Lot 2 Oak Woods Beams . page
p- —- - Judith Souers
Location:Ceiling Joist at Study/Br Suntel Design
Floor Joist r* 16865 Boones Ferry Rd Suite 201 of
[2015 International Building Code(2012 NDS)] - Lake Oswego, OR 97035
(2) 1.5 INx11.25INx16.75FT(15,8+ 1 )@ 16 O.C.
#2-Douglas-Fir-Larch(North)-Dry Use StruCalc Version 9.0.2.5 12/27/2016 3:56:10 PM
Section Adequate By:44.9%
Controlling Factor: Deflection
CAUTIONS
Properly connect sheathing to double joists/rafters or fully laminate to transfer diaphragm forces.
DEFLECTIONS Center RJghl LOADING DIAGRAM
Live Load 0.17 IN L/1114 -0.03 IN 2L/724
Dead Load 0.07 in -0.01 in
Total Load 0.24 IN L/776 -0.05 IN 2L/522
Live Load Deflection Criteria: L/480 Total Load Deflection Criteria: L/360
REACTIONS A
Live Load 765 lb 530 lb
Dead Load 424 lb 364 lb
Total Load 1189 lb 894 lb 1
Bearing Length 0.63 in 0.48 in
SUPPORT LOADS A_
Live Load 574 plf 398 plf l —
Dead Load 318 plf 273 plf A 15.75 ft t
A
Total Load 892 plf 671 plf
MATERIAL PROPERTIES
#2-Douglas-Fir-Larch(North) JOIST DATA Center Right
Base Values Adjusted Span Length 15.75 ft 1 ft
Bending Stress: Fb= 850 psi Fb'= 978 psi Unbraced Length-Top 0 ft 0 ft
Cd=1.00 CF=1.00 Cr=1.15 Unbraced Length-Bottom 0 ft 0 ft
Shear Stress: Fv= 180 psi Fv'= 180 psi Floor sheathing applied to top of joists-top of joists fully braced.
Cd=1.00 Floor Duration Factor 1.00
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi JOIST LOADING
Min. Mod. of Elasticity: E min= 580 ksi E_min = 580 ksi Uniform Floor Loading Center Right
Comp. to Grain: Fc- = 625 psi Fc- = 625 psi
Live Load LL= 40 psf 40 psf
Controlling Moment: 3063 ft-lb Dead Load DL= 15 psf 15 psf
Total Load TL= 55 psf 55 psf
6.46 Ft from left support of span 2(Center Span) TL Adj.For Joist Spacing wT= 73.3 plf 73.3 plf
Created by combining all dead loads and live loads on span(s)2 wall Loading
Controlling Shear: 1189 lb Wall One
At left support of span 2(Center Span) Live Load(1 to Joists): L1 = 300 plf 0 plf
Created by combining all dead loads and live loads on span(s)2 Dead Load( L to Joists)D1 = 240 plf 100 plf
Load Location X1 = 2.17 ft 1 ft
Comparisons with required sections: Req'd Provided
Section Modulus: 37.61 in3 63.28 in3
Area(Shear): 9.91 in2 33.75 in2
Moment of Inertia(deflection): 245.6 in4 355.96 in4
Moment: 3063 ft-lb 5155 ft-lb
Shear: 1189 lb 4050 lb
NOTES
•
Project:Arlington D_Biggi Const_Lot 2 Oak Woods_Beams page
-
— loJudith Souers
Location:Girder Truss-Calc Only 'f Suntel Design
Multi-Loaded Multi-Span Beam 16865 Bone
Ferry Rd Suite 201 of
[2015 International Building Code(2012 NDS)]
�'Lake Oswego,OR 97035
5.125 IN x 10.5 IN x 33.75 FT
24F-V4-Visually Graded Western Species-Dry Use StruCalc Version 9.0.2.5 12/27/2016 3:56:10 PM
Section Inadequate By:228.8%
Controlling Factor: Deflection/Depth Required 15.61 In.
DEFLECTIONS Center LOADING DIAGRAM
Live Load 3.05 IN L/133
Dead Load 2.50 in
Total Load 5.55 IN L/73
Live Load Deflection Criteria: U360 Total Load Deflection Criteria: L/240
REACTIONS A_
Live Load 2271 lb 1262 lb
Dead Load 1804 lb 1057 lb
Total Load 4075 lb 2319 lb
Bearing Length 1.22 in 0.70 ini
BEAM DATA
Center
Span Length 33.75 ft --
Unbraced Length-Top 0 ft A 33.75 ft---
Unbraced
-Unbraced Length-Bottom 33.75 ft
Live Load Duration Factor 1.00
Camber Adj. Factor 1 UNIFORM LOADS Center
Camber Required 2.5 Uniform Live Load 0 plf
Notch Depth 0.00 Uniform Dead Load 0 plf
MATERIAL PROPERTIES Beam Self Weight 12 plf
24F-V4-Visually Graded Western Species Total Uniform Load 12 plf
Base Values Adjusted TRAPEZOIDAL LOADS-CENTER SPAN
Bending Stress: Fb= 2400 psi Controlled by: Load Number One Two
Fb_cmpr= 1850 psi Fb'= 2320 psi Left Live Load 195 plf 60 plf
Cd=1.00 Cv=0.97 Left Dead Load 140 plf 40 plf
Shear Stress. Fv= 265 psi Fv'= 265 psi Right Live Load 195 plf 60 plf
Cd=1.00 Right Dead Load 140 plf 40 plf
Modulus of Elasticity: E= 1800 ksi E'= 1800 ksi Load Start 0 ft 11.17 ft
Min. Mod.of Elasticity: E_min= 930 ksi E_min'= 930 ksi Load End 11.17 ft 33.75 ft
Comp.J-to Grain: Fc-1= 650 psi Fc-1'= 650 psi Load Length 11.17 ft 22.58 ft
Controlling Moment: 24057 ft-lb
12.83 Ft from left support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Controlling Shear: 4075 lb
At left support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Comparisons with required sections: Reqs Provided
Section Modulus: 124.46 in3 94.17 in3
Area(Shear): 23.07 in2 53.81 in2
Moment of Inertia(deflection): 1625.52 in4 494.4 in4
Moment: 24057 ft-lb 18203 ft-lb
Shear: 4075 lb 9507 lb
NOTES
4. Project:Arlington D_Biggi Const_Lot 2 Oak Woods_Beams ! page
Location:post at beam#2
- Judith Souers
Column Suntel Design
16865 Boones Ferry Rd Suite 201 of
[2015 International Building Code(2012 NDS)] . Y,; Lake Oswego,OR 97035
3.5 x 6.0 x 9.0 FT
Comb#1-DF-L3-Visually Graded Western Species-Dry Use StruCalc Version 9.0.2.5 12/27/2016 3:56:11 PM
Section Adequate By: 16.8%
VERTICAL REACTIONS LOADING DIAGRAM
Live Load: Vert-LL-Rxn= 6500 lb
Dead Load: Vert-DL-Rxn= 4641 lb
Total Load: Vert-TL-Rxn= 11141 lb
COLUMN DATA
Total Column Length: 9 ft
Unbraced Length(X-Axis)Lx: 9 ft 7
Unbraced Length(Y-Axis)Ly: 9 ft
Column End Condtion-K(e): 1
Axial Load Duration Factor 1.00
COLUMN PROPERTIES
Comb#1-DF-L3-Visually Graded Western Species
Base Values Adjusted
Compressive Stress: Fc= 1550 psi Fc'= 637 psi
Cd=1.00 Cp=0.41
Bending Stress(X-X Axis): Fbx= 0 psi Fbx'= 1250 psi
Cd=1.00 9 ft
Bending Stress(Y-Y Axis): Fby= 1000 psi Fby'= 1070 psi
Cd=1.00 Cf=1.07
Modulus of Elasticity: E= 1500 ksi E'= 1500 ksi
Column Section(X-X Axis): dx= 6 in
Column Section(Y-Y Axis): dy= 3,5 in
Area: A= 21 in2
Section Modulus(X-X Axis): Sx= 21 in3
Section Modulus(Y-Y Axis): Sy= 12.25 in3
Slenderness Ratio: Lex/dx= 18 -
Ley/dy= 30.86
A
Column Calculations(Controlling Case Only):
Controlling Load Case:Axial Total Load Only(L+D) AXIAL LOADING
Actual Compressive Stress: Fc= 531 psi Live Load: PL= 6500 lb
Allowable Compressive Stress: Fc'= 637 psi Dead Load: PD= 4600 lb
Eccentricity Moment(X-X Axis): Mx-ex= 0 ft-lb Column Self Weight: CSW= 41 lb
Eccentricity Moment(Y-Y Axis): My-ey= 0 ft-lb Total Load: PT= 11141 lb
Moment Due to Lateral Loads(X-X Axis): Mx= 0 ft-lb
Moment Due to Lateral Loads(Y-Y Axis): My= 0 ft-lb
Bending Stress Lateral Loads Only(X-X Axis): Fbx= 0 psi
Allowable Bending Stress(X-X Axis): Fbx'= 1250 psi
Bending Stress Lateral Loads Only(Y-Y Axis): Fby= 0 psi
Allowable Bending Stress(Y-Y Axis): Fby'= 1070 psi
Combined Stress Factor: CSF= 0.83
NOTES