Portland General Electric Company
N
r.
0+4.7 n � PGE
10/18/16
CONTACT: Ken Nii. ' <
PHONE: 503-969-7419
•
CUSTOMER NAME: Red Rock
ADDRESS: 12115 SW 70th Ave Bldg C
SDPM/ENGR: C Jewett WR: M2177604
PHONE:
3-PHASE SECONDARY LINE-LINE FAULT CURRENT (RMS)
TRANSFORMER DATA
PAD MOUNT? YES
XFMR Impedance (%): 5.32 % 3-PH SUBMERSI YES
TRANSFORMER SIZE: 1000 KVA
XFMR? NO
Secondary VOLTAGE (L to L): 480 v WYE OH BANK? NO
VAULT--> VAULT ( or Pole --> Pole) SECONDARY
Secondary Wire LENGTH: 0 Feet WIRE SIZE
Number of SECONDARY RUNS: 1 Run(s) of:
Secondary WIRE Resistance R: 0.0180 Ohms/1000'
Secondary WIRE Reactance X: 0.0258 Ohms/1000'
VAULT ( or Pole) --> PANEL SECONDARY (or Svc Drop
Service Wire LENGTH: 40 Feet WIRE SIZE
Number of Service RUNS: 5 Run(s) of: 1350 AL XLP
Service WIRE Resistance R: 0.0600 Ohms/1000'
Service WIRE Reactance X: 0.0520 Ohms/1000'
MAXIMUM FAULT CURRENT*: 21,495 Amps
*Maximum fault current based upon transformers/conductors sized for 100% of electrical panel rating.
Based on a panel size of: 1200 Amps
To Print This Page: "Ctrl M"and choose"Print 3-Phase Data'
: ` :=, ':fir.,- -;' 2 '.
4
Portland General Electric Company
MAR 2 7 2131'6 (PGE
r>N 10/18/16
CONTACT. Ken
PHONE: 503-969-7419 .
CUSTOMER NAME: Red Rock
ADDRESS: 12115 SW 70th Ave Bldg C
� r
SDPM/ENGR: C Jewett WR: M2177604
' PHONE:
3-PHASE SECONDARY LINE-LINE FAULT CURRENT (RMS)
TRANSFORMER DATA PAD MOUNT? YES
XFMR Impedance (%): 5.32 % 3-PH SUBMERSI YES
TRANSFORMER SIZE: 1000 KVA XFMR? NO
Secondary VOLTAGE (L to L): 480 v WYE OH BANK? NO
VAULT--> VAULT ( or Pole --> Pole) SECONDARY
Secondary Wire LENGTH: 0 Feet WIRE SIZE
Number of SECONDARY RUNS: 1 Run(s) of:
Secondary WIRE Resistance R: 0.0180 Ohms/1000'
Secondary WIRE Reactance X: 0.0258 Ohms/1000'
VAULT ( or Pole) --> PANEL SECONDARY (or Svc Drop)
Service Wire LENGTH: 40 Feet WIRE SIZE
Number of Service RUNS: 5 Run(s) of: 350 AL XLP
Service WIRE Resistance R: 0.0600 Ohms/1000'
Service WIRE Reactance X: 0.0520 Ohms/1000'
MAXIMUM FAULT CURRENT*: 21,495 Amps
*Maximum fault current based upon transformers/conductors sized for 100% of electrical panel rating. .£
} Based on a panel size of: 1200 Amps
To Print This Page: "Ctrl M"and choose"Print 3-Phase Data"