Plans (115) r. RECEIVED FL---R 27 2,108 NOTE: Existing RTU weight with OSA hood cm/ Of 'GAR =648 lbs. New RTU = Unit,economizer �' and adp. Curb=653 lbs. Code allows for BUILDING DIVISION up to 10%additional weight without Rao��CC SS having structural calculations. We are { .0077% heavier in weight. CITY OF TIGARD REVIEWED FOR CODE COMPLIANCE Approved: [2C] OTC: Pr{ Permit #: pl/tz, sc,i z_00 jYd ! 1 Fwul DooK j 1 Ventilation Requirements Adds` s: -?",e7-731,15-- Std "r4-4.41 GM., `* —1 IMC 2015 Chapter 4,Table 403.3.1.1 Suite #: t�� a tSp ce Area Served:1700 sq.ft.=9 Occupants=45 By: Mk V I Date: _�-_zia, ` CFM,delivered by RTU-1 using economizer. Set OSA at 75 CFM,Minimum. Equipment Schedule OFFICE ICE copy TAG RTU-8 Existing RTU Manufacture Carrier Carrier Model Cooling BTUH 48VL-C600905 48NLT-060 56,000 Heating BTUH 90,000 SEER 14 EER 11.5 AFUE 81.0 CFM-Cooling 1750 Voltage 208/230, 3ph MOCP 40 Weight Unit 497 lbs. 616 lbs. Curb 88 lbs. OSA Hood 32 lbs. 12) Ca Location On Roof Accessories:Adaptor ` }��rb/'/ Curb. Note:New S f Notes duct smoke detector. /RB o,, Reof lac' +0 sou4h eAid Of 13ICI3, 11/ Project: Pivot Group Location: 7405 SW Tech Center Dr., Tigard Or. 97223 Sv/i_ 11/0 ROOF {iia N \ .--t--'' Replacement of (1) 5 ton RTU #8 \L\ Scale: 1/8"=1'0° Plan Sheet Drawn By: Date: 2/22/18 IRev. M-1