Plans (115) r.
RECEIVED
FL---R 27 2,108 NOTE: Existing RTU weight with OSA hood
cm/ Of 'GAR =648 lbs. New RTU = Unit,economizer
�' and adp. Curb=653 lbs. Code allows for
BUILDING
DIVISION up to 10%additional weight without
Rao��CC SS having structural calculations. We are
{ .0077% heavier in weight.
CITY OF TIGARD
REVIEWED FOR CODE COMPLIANCE
Approved: [2C]
OTC: Pr{
Permit #: pl/tz, sc,i z_00 jYd ! 1 Fwul DooK j 1 Ventilation Requirements
Adds` s: -?",e7-731,15-- Std "r4-4.41 GM., `* —1 IMC 2015 Chapter 4,Table 403.3.1.1
Suite #: t�� a tSp ce Area Served:1700 sq.ft.=9 Occupants=45
By: Mk V I Date: _�-_zia, ` CFM,delivered by RTU-1 using economizer.
Set OSA at 75 CFM,Minimum.
Equipment Schedule
OFFICE ICE copy TAG RTU-8 Existing RTU
Manufacture Carrier Carrier
Model
Cooling BTUH
48VL-C600905 48NLT-060
56,000
Heating BTUH 90,000
SEER 14
EER 11.5
AFUE 81.0
CFM-Cooling 1750
Voltage 208/230, 3ph
MOCP 40
Weight Unit 497 lbs. 616 lbs.
Curb 88 lbs. OSA Hood 32 lbs.
12) Ca
Location On Roof
Accessories:Adaptor
` }��rb/'/ Curb. Note:New
S f Notes duct smoke detector.
/RB
o,, Reof lac' +0 sou4h eAid
Of 13ICI3, 11/
Project: Pivot Group
Location: 7405 SW Tech Center Dr., Tigard Or. 97223 Sv/i_ 11/0
ROOF {iia N
\ .--t--''
Replacement of (1) 5 ton RTU #8
\L\
Scale: 1/8"=1'0° Plan Sheet
Drawn By: Date: 2/22/18 IRev. M-1