Plans (30) Ansul wet chemical fire suppression system. Model R-102. 4.5 gal system. Duct: 12"X24" Flow point capacity: 16 Flow points used: 13 3/8" black pipe .-. Fusible links , .mh. 450F --- 2W ' ,a'' I— 1--/I i 12'Type I Hood —__ Single Filter Bank il IAUL 1N INu T - T--1 qu OIi' ft 1N IN 3N IN (11 • g• 4 • 25" 35" 1 N 245 15" 40" _. Ti G r 35" 40" 40" 50" • ^' 8 0 (l1 1 �... 0.4 Remote Pull __-- --_-- O 10'-20' *4 rill — t� from hood. — )1:: r it ' ntri 0 � — — ----- — — -- ,-- - R _ ` 0 4 0 ,` Automatic gas 2-12" Upright 14"x21„ 24"x24" 24"x24" 24"x24" 1 i,, shut off valve. Gyro Broilers Fryer Griddle Radiant Range • y Manual resetting Broiler Z required. -� n tri Fire system drawing .i Front view System shall signal building fire alarm system if present. Wiring by others. Guardian Fire Systems Job: Al-Basha Gyros Notes; Fire system installed in accordance with Ansul PO Box 1555 11705 SW Pacific Hwy STE X design, installation and maintenance manual. Albany OR 97321 Tigard OR 97223 System tested in accordance with UL 300. CCB # 100355 exp 06/18 Date: 01/18 Drawn by: MAF SECTION IV — SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-1 7-1-09 REV.8 SYSTEM DESIGN GENERAL INFORMATION The ANSUL R-102 Restaurant Fire Suppression System may be 1.Nozzles must be located 2-8 in.(5-20 cm)into the center of the used on a number of different types of restaurant cooking appli- duct opening,discharging up.See Figure 1. ances and hood and duct configurations.The design information listed in this section deals with the limitations and parameters of this pre-engineered system.Those individuals responsible for the design of the R-102 system must be trained and hold a current 111 ANSUL certificate in an R-102 training program. The R-102 and the PIRANHA systems use compatible agents and components, therefore, they may be used together for cooking appliance, hood, and duct protection. The primary ANSUL AUTOMAN Release can be either an R-102 or a PIRANHA ANSUL AUTOMAN Release and can actuate up to two additional 111111111111111 R-102 or PIRANHA Regulated Actuators. In systems utilizing a111111111 101 remote release, any combination of the maximum number of regulated actuators can be used. 2-8IN. (5-20cm) • Both systems must actuate simultaneously. t • Each system must be designed and installed per its appropri- FIGURE 1 ate manual. 000173 • Adjacent appliances requiring protection must be protected 2.In installations where a UL listed damper assembly is with the same type of system, either R-102 or PIRANHA, employed, the duct nozzle can be installed beyond the 8 in. unless the center-to-center spacing between the adjacent (20 cm) maximum,to a point just beyond the damper assem- R-102 and PIRANHA nozzles is no less than 36 in.(91.4 cm). bly that will not interfere with the damper.Exceeding the maxi- • When appliances are protected with R-102 nozzles, the hood mum of 8 in.(20 cm) in this way will not void the UL listing of and connecting duct above those appliances cannot be pro- the system. tected with PIRANHA nozzles. 3.Previously listed 3 flow number and 5 flow number duct pro- • Mixing systems in a common plenum is not allowed. tection detailed in earlier published manual, Part No.418087- One of the key elements for restaurant fire protection is a correct 06,can also still by utilized. system design.This section is divided into ten sub-sections:Noz- DUCT SIZES UP TO 50 IN.(127 cm) zle Placement Requirements,Tank Quantity Requirements, Actu- PERIMETER/16 IN.(41 cm)DIAMETER ation and Expellant Gas Line Requirements, Distribution Piping Requirements, Detection System Requirements,Manual Pull Sta- • One 1W nozzle(Part No.419336)=one flow number tion Requirements, Mechanical Gas Valve Requirements, Electri- 50 in.(127 cm)perimeter maximum cal Gas Valve Requirements,Electrical Switch Requirements,and Pressure Switch Requirements. Each of these sections must be • 16 in.(41 cm)diameter maximum completed before attempting any installation. System design sketches should be made of all aspects of design for reference DUCT SIZES UP TO 100 IN.(254 cm) during installation. PERIMETER/32 IN.(81.3 cm) DIAMETER NOZZLE PLACEMENT REQUIREMENTS • One 2W Nozzle(Part No.419337)=two flow numbers This section gives guidelines for nozzle type, positioning, and • 100 in.(254 cm)perimeter maximum quantity for duct,plenum,and individual appliance protection.This . 32 in.(81.3 cm)diameter maximum section must be completed before determining tank quantity and piping requirements. The chart below shows the maximum protection available from each duct nozzle. Duct Protection—Single Nozzle Part 3.0 Gallon 1.5 Gallon All duct protection is UL listed without limitation of maximum duct Description No. System System length (unlimited length).This includes all varieties of ductworks 2W Nozzle 419337 Maximum Maximum both horizontal and vertical including ducts that run at angles to 100 in.(254 cm) 100 in. the horizontal and ducts with directional bends. (254 cm) Perimeter Perimeter The R-102 system uses different duct nozzles depending on the 1W Nozzle 419336 Maximum Maximum size of duct being protected. 50 in.(127 cm) 50 in.(127 cm) Perimeter Perimeter SECTION IV — SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-5 7-1-09 REV.5 Plenum Protection The R-102 system uses the 1W Nozzle(Part No.419336)or the ili 1N Nozzle(Part No.419335)for plenum protection.The 1W noz- zle tip is stamped with 1W and the 1N nozzle tip is stamped with 20 IN.(51 cm) 4, MAXIMUM 1 N, indicating they are one-flow nozzles and must be counted as one flow number each.When protecting a plenum chamber, the } entire chamber must be protected regardless of filter length. 1 IN.(2.5 cm) =- .- - MINIMUM VERTICAL PROTECTION—GENERAL r-- '1W NOZZLE — PART NO. 419336 — SINGLE AND"V" BANK 'PROTECTION 71 20 IN.(51 cm) One 1W nozzle will protect 4 linear feet (1.2 m) of plenum.The +MAXIMUM maximum distance from the end of the hood to the first and last nozzle must be no more than 2 ft(0.6 m).After the first nozzle,any • t additional nozzles must be positioned at a maximum of 4 ft(1.2 m) ,' , 1 IN.(2.5 cm) apart down the entire length of the plenum.The plenum width must • MINIMUM not exceed 4 ft(1.2 m).(The 1W nozzle can be used on single or V. V-bank filter arrangements.)See Figure 6. FIGURE 7 2 FT(0.6 m) 000199 MAXIMUM ... Option 2:The 1W nozzle must be placed perpendicular, 8-12 in. 4 FT(1.2 m) MAXIMUM (20-30 cm)from the face of the filter and angled to the 4 FT(1.2 m) ......----------1.\,4 FT(1.2 m) center of the filter.The nozzle tipmust be within 2 in. 2 FT MAXIMUM )MAXIMUM • / MAXIMUM (5 cm) from the perpendicular center line of the filter. r �� ,/ See Figure 8. �'�' 1IN. 0 cm) MAXIMUM ::. 8 IN.(20 cm) IIII\ �/ j1IIii MINIMUM ` NOLE TIPMUST BE WITHINFIGURE 6THIS AREA 000197 When protecting plenums with the 1W nozzle.two options of cov- erage are available: FIGURE 8 000200 Option 1:The 1W nozzle must be on the center line of the single or "V" bank filter and positioned within 1-20 in. HORIZONTAL PROTECTION—OPTION 1 (2.5-51 cm) above the top edge of the filter. See 1N NOZZLE—PART NO.419335—SINGLE BANK PROTECTION Figure 7. One 111 nozzle will protect 10 linear feet(3.1 rn)of single filter bank plenum.The nozzle(s) must be mounted in the plenum, 2 to 4 in. (5 to 10 cm)from the face of the fitter, centered between the filter height dimension,and aimed down the length.The nozzle must be positioned 0-6 in.(0-15 cm)from the end of the hood to the tip of the nozzle.See Figure 9. 2—AIN. 10FT.(3.1m) (6—10 cm) MAXIMUM . t 000201 li°1*10 Al I �� 000202 FIGURE 9 SECTION IV — SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-9 4-1-06 REV.8 Fryer—Single Nozzle Protection (Continued) Maximum Area Dimensions—Single Nozzle Fryer Protection (Continued) Max.Size Max.Size Overall Type of Nozzle Height Nozzle Frypot Only With Dripboard Nozzle Above Top of Fryer Location 19.5 in.x 19 in. 19.5 in.x 25 3/8 in. 290 13 in.to 16 in. See Figure 17 (50 cm x 48 cm) (50 cm x 65 cm) (33 to 41 cm) 19.5 in.x 19 in. 19.5 in.x 25 3/8 in. 3N See Figure See Figure 18 (50cmx48cm) (50cmx65cm) 18 . 0-18 in.x 18 in. 18 in.x 27 3/4 in. 3N 25 in.to 35 in. See Figure 19 • (46 cm x 46 cm) (46 cm x 70.5 cm) (64 cm to 89 cm) A` , -'r , I `r i I ^Y 1i � I I I 1 it t I '" ' f I; TOP OF FRYER11111114110111° %11 ...t...,--- ' 1 J ; .44100,- Allit FRYER WITHOUT DRIPBOARD FRYER WITH DRIPBOARD \ �JN' F \g pNT\ �' 90Nr ` 290 NOZZLE TIP POSITIONED OVER THE MIDPOINT OF THE HAZARD AREA t 3 IN. (7.6 cm)FROM THE MIDPOINT ALONG THE LONGEST SIDE OF THE HAZARD AND t 1 RIGHT-TO-LEFT 000008 IN.(2,5 cm)FROM THE MIDPOINT ALONG THE SHORTEST SIDE OF THE HAZARD AND 00001C CENTERLINE AIMED AT THE MIDPOINT OF THE COOKING AREA. FRYER WITHOUT DRIPBOARD FRYER WITH DRIPBOARD FIGURE 17 NOTE: 3N NOZZLE TIP MUST BE LOCATED WITHIN THE PERIMETER OF THE SURFACE 002286 AREA WITHIN THE FRONT HALF OF THE FRY POT AND AIMED AT THE CENTER. FIGURE 19 34 IN.(86 cm)MAXIMUM DIAGONAL DISTANCE BETWEEN NOZZLE AND CENTER OF HAZARD AREA s—`--T ..�_=1\ r. "� s �>-?.. ..= y < l 'I 21 in.(53 cm) I MINIMUM k� I `�',.1.'' i VERTICAL 11�- t I NOZZLE HEIGHT I ► V ...41111011100... I IL441740:0701 %Of" • FRYER WITHOUT DRIPBOARD FRYER WITH DRIPBOARD 3N NOZZLE TIP POSITIONED ANYWHERE ALONG OR WITHIN PERIMETER OF COOKING SURFACE AND AIMED TO THE CENTER OF THE COOKING AREA. FIGURE 18 002287 SECTION IV — SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-14 REV.6 7-1-09 ►Range Protection 245(2-Flow)Nozzle—High Proximity Application • ^COOKING—t No Obstructions AREA ► 40 in.to 50 in.(102 cm to 127 cm)above the cooking surface. This high proximity application uses the 245 nozzle, Part No. 419340. `� The nozzle tip is stamped with 245 indicating this is a two-flow ` COOKING nozzle and must be counted as two flow numbers. 245NOZZLE LOCATIONCENTERTIP / AREA OF J , ►One 245 nozzle will protect a maximum cooking area of 672 in.2 COOKING SURFACEOR / ►(4335 cm2)with a maximum longest dimension of 28 in.(71 cm). 11 3/8 IN.(29 cm) �\ �` MAXIMUM FROM \� When using this nozzle for range protection, the nozzle must CENTERLINE OF NOZZLE be pointed verticallydown andpositioned as shown in Figures TOU CENTER OF ANY 9 BURNER GRATE 29 and 30. 245 NOZZLE TIP LOCATION COOKING CENTERLINE OF COOKING SURFACE AREA i245 NOZZLE TIP _LO COOKING 127. 1LOCATION CENTER OF AREA f I (127 cm)MAXIMUM COOKING SURFACE OR HEIGHT 11 3/8 IN.(29 cm) OF 245 MAXIMUM FROM `,_ I NOZZLE CENTERLINE OF NOZZLE TIP TO CENTER OF ANY 000766 BURNER GRATE 40 IN. MINIMUM MINIMUM FIGURE 30 HEIGHT OF 245 NOZZLE i TIP I i ( 000236 0 0�Ly0 0 I` 1 FIGURE 29 NOTICE Four burner grates shown in Figure 30.For sin- gle or double burner grates, locate nozzle at center of cooking surface or 11 3/8 in.(29 cm) maximum from nozzle centerline to center of any burner grate. SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-18 REV.7 7-1-09 ►Griddle Protection 1N(1-Flow)Nozzle-High Proximity ►Griddle Protection 290(2-Flow)Nozzle-High Proximity Application ►Application The R-102 system uses four different nozzles for the protection of Option 1 -Nozzle Center Located griddles. One of the applications requires a 1-flow nozzle and P.30 in.to 50 in.(76 cm to 127 cm)above the cooking surface. three of the applications require a 2-flow nozzle. This high proximity application uses the 290 nozzle, Part No. High Proximity Application:35 in.to 40 in.(89 to 102 cm)above 419342. the cooking surface. The nozzle tip is stamped with 290 indicating this is a 2-flow noz- This high proximity application uses the 1N nozzle, Part No. zle and must be counted as,two flow numbers. 419335. ►One 290 nozzle will protect a maximum cooking area of 720 in.2 The nozzle tip is stamped with 1N indicating this is a one-flow noz- ► (4645 cm2)with a maximum dimension of 30 in.(76 cm). zle and must be counted as one flow number. When using this nozzle for high proximity applications,the nozzle One 1N nozzle will protect a maximum cooking area of 1080 in.2 must be positioned within 1 in.(2.5 cm)of the center of the cook- (6968 cm2)with the maximum longest side of 36 in.(91 cm). P.ing surface and pointed vertically down.See Figure 41 and 42. When using this nozzle for griddle protection,the nozzle must be CENTER LINE OF GRIDDLE positioned along the cooking surface perimeter to a maximum of SURFACE x 1 IN.(2 cm)IN 2 in.(5 cm)inside the perimeter,and aimed to the midpoint of the ANY DIRECTION cooking surface.See Figure 39 and 40. 1 I NOTICE I When usingthistype ofgriddleprotection,only50 IN. I I (127 cm) 5 flow numbers are allowed on a 1.5 gal(5.7 L) I MAXIMUM system and only 11 flow numbers are allowed I I HEIGHT on a 3 gal(11.4 L)system. 1 I OF 290 NOZZLE TIP I I 30 IN. I I (76 cm) t .— i N MINIMUM HEIGHT r—t--MIDPOINT OF—�-----1 I I OF 290 I COOKING SURFACE ! _. 1 NOZZLE i I TIP I j I I I -{- I 1 II t r I I t 1N NOZZLE LOCATED ALONG COOKING SURFACE EDGE ANY SIDE OF GRIDDLE SURFACE ► FIGURE 41 000244 WITHIN 0-2 IN.(0-5 cm)OF COOKING SURFACE EDGE.NOZZLE MUST BE AIMED AT MIDPOINT OF COOKING COOKING SURFACE. - AREA NOZZLE 1 IN.(2 cm) FIGURE 39 LOCATION MAXIMUM 00024, MEM I ffil 1 NOZZLE LOCATION t 1 ' 0-2IN.(0-5 cm) ) INSIDE PERIMETER ! 40!N. --11.- Lr- OF COOKING SURFACE I ( (102 cm) ( , I MAXIMUM r, ........ COOKING I j//35 i HEIGHT 1.-.i ,/ AREA OF1N NOZZLE TIP .(2cm) NN.(69 cm) XIMUM / / I MINIMUM I HEIGHT EDGE I 1 OF 1N OF V i I NOZZLE TIP CENTER OF GRIDDLE SURFACE OR A ICOOKING l MAXIMUM DIMENSION OF 20.6 IN. SURFACE —e`er) (52 cm)FROM NOZZLE CENTERLINE TO FURTHEST CORNER OF GRIDDLE FIGURE 42 —_� I. oo42 4 FIGURE 40 I. 000243 SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-23 7-1-09 REV.8 Overhead Chain Broiler Protection (Continued) Example No.1 -Internal broiler size is 24 in. long x 20 in.wide 'Salamander Broiler Protection-1F(1-Flow)Nozzle Overhead (61 x 51 cm), with an opening of 16 in. x 16 in. A salamander broiler with a maximum hazard area(internal broil- (40.6 x 40.6 cm). er chamber) of 15 in.(38 cm)deep x 31 in. (79 cm)wide can be To determine minimum opening size, multiply the protected using a 1F nozzle, Part No. 419333.The nozzle tip is internal length and the internal width by 0.6: stamped with 1F, indicating that this is a one-flow nozzle. Length of opening-24 in.x 0.6=14.4 in. The single 1F nozzle must be located directly in line with the cen- (61 cm x 0.6=36.6 cm) ter of the broiler opening,8 in.(20 cm)to 12 in.(30 cm)in front of Width of opening-20 in.x 0.6= 12.0 in. the broiler and 12 in.(30 cm)to 18 in.(46 cm)above the top of the (51 cm x 0.6=30.5 cm) broiler.The nozzle must be aimed at the center of the top broiler opening when the grate is located in the middle position.The noz- The minimum allowable opening for overhead protec- zle must be orientated so the nozzle tip flats are parallel with the tion would be 14.4 in.x 12.0 in.(36.6 x 30.5 cm). grate left to right centerline.See Figure 57b. This example would be acceptable for overhead pro- NOZZLE 1 F NOZZLE--►# LOCATION ZONE tection. 6 IN. :S (PART NO. (15 cm) Example No.2-Internal broiler size is 30 in. long x 24 in.wide 4193 t '• a IN.(20 cm) (76 x 61 cm) with an opening of 22 in. x 12 in. jiii "4 +-"} (56 x 30 cm). (10 12IN.c \\ (10 cm) (30 cm) To determine minimum opening size, multiply internal ��• ®, \\\\\\ length and internal width by 0.6: a j ' .l 101.' Length of opening-30 in.x 0.6=18.0 in. 'WWI 01,.11M►r474111r,1ie �yyy7•�I (76 cmx0.6=45.7cm) ®i'I e.i' Width of opening-24 in.x 0.6=14.4 in. AIM AT CENTER OF THE AIM AT CENTER OF THE TOP (61 cm x 0.6=36.6 cm) TOP BROILER OPENING BROILER OPENING WHEN THE WHEN THE GRATE IS GRATE IS LOCATED IN THE Minimum allowable opening for overhead protection LOCATED IN THE MIDDLE POSITIONAIM AT CENTER would be 18 in.x 14.4 in.(45.7 x 36.6 cm). MIDDLE POSITION OF BROILER OPENING Because this broiler has an opening of 22 in.x 12 in., FIGURE 576 008426 the 12 in.width is below the minimum allowable cal- culated dimension of 14.4 in.(36.6 cm)and therefore Salamander Broiler Protection-1N(1-Flow)Nozzle Local would not be acceptable for overhead protection. A salamander broiler with a maximum hazard area(internal broil- ,.Salamander Broiler Protection er chamber)of 15 in.(38 cm)deep x 31 in. (79 cm)wide can be The R-102 system uses three different nozzle locations for sala protected using a 1N nozzle, Part No.419335.The nozzle tip is mender broiler protection.All of the design options require a one stamped with iN,indicating that this is a one-flow nozzle. flow nozzle. The single 1N nozzle must be located above the grate on either vertical edge of the broiler opening.The nozzle must be aimed at Salamander Broiler Protection-iN(1-Flow)Nozzle Overhead the center of the grates.See Figure 57c. A salamander broiler with a maximum hazard area(internal broil- er chamber)of 16 in.(41 cm) deep x 29 in.(74 cm)wide can be ` protected using a 1N nozzle, Part No. 419335.The nozzle tip is .1 ►stamped with 1N, indicating that this is a one-flow nozzle. The single 1N nozzle must be located directly in line with either (I vertical edge of the broiler opening,6 in.(15 Cm)to 12 in.(30 cm) \ in front of the broiler,and O in.to 12 in.(30 cm)above the top of the broiler.The nozzle must be aimed at the center of the broiler ►opening.See Figure 57a. �� 4. �` VERTICAL EDGE [ijj�`� OF BROILER .iii`.�� OPENING 1N NOZZLE Ls. (PART NO.419335) NOZZLE 1N NOZZLE AIMED ,µ,,,''4---LOCATION ZONE AT CENTER OF 121N GRATES (3o cm) r: 6 IN.(15 cm) FIGURE 57c ► 008428 V---** / t \ :4.: _.__._.__ y.__ (15cm) .A'_ -- _ SIC I . ----_--- AIM AT CENTER ' AIM AT CENTER OF BROILER OF BROILER OPENING OPENING FIGURE 57a 008426 SECTION IV — SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-24 REV.7 7-1-09 ►Upright Broiler Protection Gas-RadiantfElectric Char-Broiler Protection The R-102 system uses two 1/2N Nozzles(Part No.419334)for all The R-102 system uses the 1N nozzle, (Part No.419335)for gas- ►upright broiler protection.The nozzle tip is stamped 1/2N, indicat- radiant/electric char-broiler protection. ing that this is a half-flow nozzle.A pair of these nozzles will equal The nozzle tip on the 1N nozzle is stamped with a 1 N, indicating one flow number. that this is a one-flow nozzle and must be counted as one flow Two 1/2N nozzles will protect a maximum hazard area (internal number. broiler chamber)of 30 in.x 32.5 in.(76 cm x 82.5 cm).These noz- One IN nozzle will protect a hazard with a maximum length of ►zles must always be used in pairs on an upright broiler.One noz- 36 in. (91 cm) and a total cooking area which does not exceed zle must be positioned above the grate and pointed at the back .864 in.2 (5574 cm2). The nozzle tip must be located 15 to opposite corner of the broiler chamber.The second nozzle must 40 in.(38 to 102 cm) above the hazard surface.When using this be pointed down into the center of the drip pan through the open nozzle for gas-radiant/electric char-broiler protection, the nozzle ►slot.See Figure 58. must be positioned anywhere along or within the perimeter of the ` UPRIGHT BROILERmaximum cooking area and shall be aimed at the center of the .cooking surface.See Figure-59. BROILER CHAMBER COOKING AREA � IIMMI f-_ I COOKING4—'1.24 AREA( 00026 _ DRIP PAN ' §R \ t /fl i I MAXIMUMcm) FRONT VIEW , SIDE VIEW I ` I I \\` I/ 15 IN.(38 cm) I I I I ` ` t / i MINIMUM 000252 1�� MIIIIMIIMIIIIIIMOIIIIIIIIIM 000257 ► FIGURE 58 I ■ . FIGURE 59 SECTION IV — SYSTEM DESIGN ► UL EX3470 ULC EX3470 Page 4-52 REV.4 7-1-09 DISTRIBUTION PIPING REQUIREMENTS(Continued) START OF LAST BRANCH LINE Distribution Piping Requirements—1.5 Gallon SystemSTART OF FIRST DUCT, PLENUM, AND APPLIANCE PROTECTION BRANCH LINE \t 1.This option allows for duct protection, plenum protection, ► appliance protection, or any combination. However, only one SUPPLY R • (1)duct nozzle may be used,either a 1W or a 2W, nozzle. LINE TEE \ TOTAL LENGTH MUST NOT ► 2.All distribution piping, supply and branch, must be 3/8 in. EXCEED 6 FT Schedule 40 black iron, chrome-plated,or stainless steel. ( , (2.4 m) • 3.Each 1.5 gallon tank allows a maximum of five flow numbers,* ► 4.The pipe length between the start of the first branch line and the start of the last branch line must not exceed 8 ft(2.4 m). When the supply line is split, the combined length of both START OF LAST legs of the supply line (start of first branch line to start of last 4 BRANCH LINE branch line)must not exceed 8 ft(2.4 m).See Figure 111. V START OF FIRST P. BRANCH LINE 5.The combined length of all branch lines must not exceed 22 ft ► FIGURE 111 000784 (6.7 m).See Figure 112. • 6.The requirements of the following table must not be exceeded: 1w NOZZLE .f---1N NOZZLE KO , iN N (BRANCH LINES IN BOLD) COMBINED LENGTH MUST NOT EXCEED 22 FT.(6.7 m) ► FIGURE 112 000785 Duct Plenum Appliance Requirements Supply Branch Line Branch Line Branch Line Pipe Size 3/8 in. 3/8 in. 3/8 in. 3/8 in. Maximum Length 40 ft 6 ft 4 ft 10 ft (12.2 m) (1.8 m) (1.2 m) (3 m) Maximum Rise 6 ft 4 ft 2 ft 2 ft (1.8 m) (1.2 m) (0.6 m) (0.6 m) Maximum 90°Elbow 9 4 4 6 Maximum Tees 1 1 2 3 Maximum Flow Numbers 5* 2 2 3 •Exceptions: 1.Six(6)flow numbers are allowed when a duct branch line is the last branch line on the piping network and no 1N nozzles are used to protect woks or griddles. 2.Six(6)flow numbers are allowed when six(6)1N nozzles are used and none of the nozzles are used to protect woks,griddles,ranges,and salamanders. NOTE:Only five(5)flow numbers are allowed if a 1N nozzle is used for wok,griddle,range,or salamander protection. 3.Six(6)flow numbers are allowed when only two(2)3N nozzles are used, SECTION IV — SYSTEM DESIGN • UL EX3470 ULC EX3470 Page 4-53 7-1-09 REV.4 DISTRIBUTION PIPING REQUIREMENTS(Continued) Distribution Piping Requirements—3.0 Gallon System 1. The maximum length between the start of the first branch line SUPPLY�' and the start of the last branch line must not exceed 24 ft ' TEE (7.3 m).When the supply line is split, the combined total of , both legs of the supply line (from the start of the first branch 41ilit V. .. line to the start of the last branch line) must not exceed 24 ft d ' • (7.3 m).See Figure 113. .../ 000266 COMBINED LENGTH OF \ 2. The total length of all branch lines must not exceed 36 ft a BOTH LEGS OF SUPPLY • (10.9 m).See Figure 113. LINE MUST NOT 3 BRANCH LINES EXCEED 24 FT(7.3 m) 3. Use a 3/8 in,union to connect the tank adaptor to the 3/8 in. supply line. 4. A maximum of two nozzles are allowed per duct branch line. 1N NOZZLE 5. The requirements of the following table must not be exceeded: 2W NOZZLE.�. 1N NOZZLE lig 230 NOZZLE ` 245 NOZZLE 1.2N NOZZLE (BRANCH LINE IN BOLD) COMBINED LENGTH MUST 000so2 NOT EXCEED 36 FT(10.9 m) FIGURE 113 Duct Plenum Appliance Requirements Supply Line Branch Line Branch Line • Branch Line Pipe Size 3/8 in. 3/8 in. 3/8 in. 3/8 in. Maximum Length 40 ft 8 ft 4 ft 12 ft (12.2 m) (2.4 m) (1.2 m) (3.7 m) Maximum Rise E ft 4 ft 2 ft 2 ft (1.8 m) (1.2 m) (0.6 m) (0.6 m) Maximum 90° 9 4 4 6 Elbows Maximum Tees 1 2 2 4 Maximum Flow 11" 4 2 4 Numbers 'Exceptions: 1.Twelve(12)flow numbers are allowed in any one tank for duct and plenum protection only. 2.Twelve(12)flow numbers are allowed with any one tank using only two-flow appliance nozzles. 3.Twelve(12)flow numbers are allowed with any one tank using only three-flow appliance nozzles. Special Instructions: 1.Twelve(12)flow numbers are allowed when four(4)Dean Industries GTI Gas Fryers are protected at low proximity as shown in Figure 66 on Page 4-32.The discharge piping must r. be as shown in Figure 67 on Page 4-32. 2.For certain McDonald's applications,11.6 flow numbers are allowed when using a combination of one(1)2W duct nozzle,one(1)1/2N electrostatic precipitator nozzle, one(1)1N plenum nozzle,and four(4)two-flow appliance nozzles.Contact ANSUL Applications Engineering Department for additional information.