Report gt-i7 I 3 el 5k,/ 44<s eretra 1::(7 jAN M11865 Jacobs Heating and Air Conditioning Inc. Submittal Packet Summer Creek Apts WO# 50855 TABLE OF CONTENTS Job Name: Summer Creek Apts- Gas Furnace Job No. 50855 Submittal Packet DESCRIPTION Section Tab Carrier ComfortTM Gas Furnace Model: 58STX090-16 GF-1 1 MARS Thermostat Cover Model: 70220 Tstat Guard 2 WEICOBS HEATING&AIR CONDITIONING fIVI, 58STA/STX 4—WAY MULTIPOISE INDUCED—COMBUSTION GAS FURNACE Input Capacities: 45,000 thru 155,000 Btuh Carrier Series 160 turn to the experts Product Data THE CARRIER 58STA/STX GAS FURNACE _ The 58STA/STX 4—way Multipoise Gas Furnaces feature Carrier's ® • a ' QuieTech'" noise reduction system for incredibly quiet induced draft operation. Applications are easy with 4—way multipoise �y ® m design, through-the-furnace downflow venting, 13 different venting options, and designed for easy service access. An inner OO blower door is provided for tighter sealing in sensitive applications. The 58STA/STX furnaces are approved for use with natural or eff propane gas,and the 58STX is approved for use in Low NOx Air Management Districts. PTh STANDARD FEATURES • QuieTech"" noise reduction system • Microprocessor based control center Enhanced diagnostics with LED and reflective sight glass. Stores fault codes during power outages. ® ® Adjustable heating air temperature rise Q � Carrier V ® Adjustable cooling airflow • 4—way Multipoise furnace,13 vent applications • Compact design—only 33-1/3 in.(847 mm)tall • Power Heat"" Igniter • Draft safeguard switch to ensure proper furnace venting • Inner door for tighter sealing • Cabinet air leakage less than 2.0%at 1.0 in.W.C.and cabinet air leakage less than 1.4%at 0.5 in.W.C.when Ok) tested in accordance with ASHRAE standard 193 • HYBRID HEAT®Dual Fuel System compatible N. • All models are chimney friendly when used with _) accessory vent kit • Twinning in Upflow,Downflow and Horizontal Al0247 • Residential installations eligible for consumer financing through the Retail Credit Program MODEL NUMBER NOMENCLATURE 58STA 045 100 08 58STA 4-Way Multipoise 58STX Low NOx version Nominal Cooling Size - - (Airflow at.5 es.p.) 1(400 CFM per 12,000 Btuh) 08-800 CFM 112-1200 CFM 114-1400 CFM 16-1600 CFM Input Capacity 20-2000 CFM 045-44,000 Btuh 110-110,000 Btuh 22-2200 CFM 070-66,000 Btuh 135-132,000 Btuh >090-88,000 Btuh 155-154,000 Btuh Series Number FURNACE COMPONENTS Q INDUCER MOTOR Cl) c0 ASSEMBLY VENT ELBOW to PRESSURE MAIN LIMIT SWITCH SWITCH a L:� ,,� (BEHIND GAS VALVE) ��- _i �� k Vr 775" \4j II °` �� i \)'1,•'//' BLOCKED VENT ►`�\\� i4\\,Jif C SWITCH FLUE COLLECTOR �� BOX _�1'� a� -A A�`. v\` 0 FLAME �`('.'.'i♦'v ` GAS VALVE �' 8 SENSOR 0 I _,t_t ;A i • Jf 1' ii41 i5 0 MANUAL RESET �JI� I GAS MANIFOLD LIMIT SWITCHES ►,Pial ,i1.1 [� • ® l J i o -=(!\II Mil, NI '2`�J HOT SURFACE - IGNITOR I . „I 0=L�---' ' GAS BURNER BLOWER r"T DOOR SAFETY •SWITCH ) -FURNACE ) CONTROL BOARD rr _m o BLOWER AND a , I . • MOTOR 'I m ! I : r o;_ CAPACITOR/ I POWER CHOKE I j ji\I et - r . . A10308 NOTE: The 58STA/STX Furnaces are factory shipped for use with natural gas.These furnaces can be field-converted for propane gas with a factory-authorized and listed accessory conversion kit. 2 DIMENSIONS 5., 1r664 21 IA6 61A 1111 : " 1 wm c 1 0718 0291 I A0:113500'03 1 i 113/16 '2"1 /1$094 57N 11724 --n1Yf6 149.11 w 6 g 6 NRROW n'�n AIR RAW -_w 16161 A 55/0 sT}FF stn nba4 srN '3-1 "4113,!3-a' pr... 19 `1( �. narn r —.�f i 1bnS !j € 1 ,'.- ma oramw 4 mRascnxw 0LN�I Le=,--•-- — � i 00�� i6 F n'} 5(\,�^�j; ''11�ItGiFf1 �'tM F�JkL FF 777 G. 7 �/ a — 0112C:r P�C.p 113/3 eo4N- — II 03379 . pp5,314 >f6 lA5WVE ®164 pppd 6744+'2 SOCO(PWISWOS .. G45 diM ���G3 HM16 07111 CO 1 I itCn _ 1 epN I 741in09 MX AC005C0Y 323731 214 ---M 6.1 11303400 1:3433I nss21 .E-- p w,3,/: g1DIXgfRWW 30170/3 PUT BOTTOM 3530 09.17 L1 iP 2099 y 2Wei ---+.,...-1 1,1116 ^ p� =[M 11109 6iiOTtT+11s6>Esl NOTES: A10270 1.Two additional 7/8—in.(22 mm)diameter holes are located in the top plate. 2.Minimum return—air openings at furnace,based on metal duct.If flex duct is used,see flex duct manufacturer's recommendations for equivalent diameters. a. For 800 CFM-16—in.(406 mm)round or 14 1/2 x 12—in.(368 x 305 mm)rectangle. b. For 1200 CFM-20—in.(508 mm)round or 14 1/2 x 19 1/2—in.(368 x 495 mm)rectangle. c. For 1600 CFM-22—in.(559 mm)round or 14 1/2 x 22 1/16—in.(368 x 560mm)rectangle. d. For airflow requirements above 1800 CFM,see Air Delivery table in Product Data literature for specific use of single side inlets.The use of both side inlets, a combination of 1 side and the bottom,or the bottom only will ensure adequate return air openings for airflow requirements above 1800 CFM. FURNACE SIZE CABINET WIDTH - OUTLET; OP AND VENT IN f»m BCiTTI '' '' 5SECTtON 5- ; NLET WIDTH SIZE � WItITH WING) � < '` Bif3TTC�A FLUE I k: � � IN(mm) • COLLAR' 045-08 14-3/16 (360) 12-9/16 (319) 9-5/16 (237) 12-11/16 (322) 4 (102) 104 (47) 045-12 14-3/16 (360) 12-9/16 (319) 9-5/16 (237) 12-11/16 (322) 4 (102) 107 (49) 070-08 14-3/16 (360) 12-9/16 (319) 9-5/16 (237) 12-11/16 (322) 4 (102) 111 (50) 070-12 14-3/16 (360) 12-9/16 (319) 9-5/16 (237) 12-11/16 (322) 4 (102) 115 (52) 070-16 17-1/2 (445) 15-7/8 (403) 11-9/16 (294) 16-1/8 (410) 4 (102) 126 (57) 090-14 17-1/2 (445) 15-7/8 (403) 11-9/16 (294) 16-1/8 (410) 4 (102) 127 (58) > 090-16 21 (533) 19-3/8 (492) 13-5/16 (338) 19-1/2 (495) 4 (102) 140 (64) 090-20 21 (533) 19-3/8 (492) 13-5/16 (338) 19-1/2 (495) 4 (102) 146 (66) 110-12 17-1/2 (445) 15-7/8 (403) 11-9/16 (294) 16-1/8 (410) 4 (102) 135 (61) 110-16 21 (533) 19-3/8 (492) 13-5/16 (338) 19-1/2 (495) 4 (102) 146 (66) 110-22 21 (533) 19-3/8 (492) 13-5/16 (338) 19-1/2 (495) 4 (102) 152 (69) 135-16 21 (533) 19-3/8 (492) 13-5/16 (338) 19-1/2 (495) 4 (102)* 149 (68) 135-22 24-1/2 (622) 22-7/8 (581) 15 1/16 (383) 23 (584) 4 (102)* 163 (74) 155-20 24-1/2 (622) 22-7/8 (581) 15-1/16 (383) 23 (584) 4 (102)* 170 (77) *135 and 155 size furnaces require a 5 or 6—in. (127 or 152 mm)vent. Use a vent adapter between furnace and vent stack. See Installation Instructions for complete installation requirements. 3 SPECIFICATIONS UNITSiZEs 045 f)8 70 y RATINGS AND PERFORMANCE Input Btuh* 58STX Upflow;all 44,000 58STA 44,000 66,000 66,000 66,000 88,000 88,000 Nonweatherized ICS 58STX Downflow/ 42,000 42,000 63,000 63,000 63,000 84,000 84,000 Horizontal Output Capacity 58STX Upflow;all 35,000 36,000 53,000 54,000 53,000 71,000 71.000 (Btuh)t 58STA Nonweatherized ICS 58STX Downflow/ 34,000 34,000 51,000 51,000 51,000 68,000 68,000 Horizontal AFUEt 80.0 80.0 80.0 80.0 Certified Temperature Rise Range—°F °C 80'0 80.0 80.0 g ( ) 30-60 20-50 40-70 30-60 25-55 40-70 30-60 (17-33) (11-28) (22-39) (17-33) (14-30) (22-39) (17-33) Certified External Static Pressure Heat/Cool 0.10/0.50 0.10/0.50 0.12/0.50 0.12/0.50 0.12/0.50 0.15/0.50 0.15/0.50 Fx. Airflow CFM Heating 865 1250 720 1195 1350 1300 1505 N Cooling 835 1160 F ELECTRICAL 870 1200 1505 1385 1635 03 Unit Volts—Hertz—Phase 115-60-1 Operating Voltage Range Min-Max Maximum Unit Amps 104-127 5.2 7.2 5.1 7.2 Maximum Wire Length(Measure 1 Way in Ft(M) 49(14.9) 37(11.2) 51 (15.5) 38(11.5) 29(8.8) 32(9.7) 28(8.5) Minimum Wire Size Maximum Fuse or Ckt Bkr Size(Amps)** Transformer(24v) 40va External Control Heating Power Available Cooling Air Conditioning Blower Relay CONTROLS Standard Limit Control Heating Blower Control Solid-State Time Operation Burners(Monoport) 2 2 3 33 Gas Connection Size1111111111.11.11111 4 4 GAS CONTROLS Gas Valve(Redundant) Mfr. White-Rodgers Min.inlet pressure (In.WC.) 4.5(Natural Gas) Max.inlet pressure (In.WC.) 13.6(Natural Gas) Ignition Device Factory-installed orifice Hot Surface BLOWER DATA Direct-Drive Motor HP(PSC) 1/5 1/3 1/5 1/3 1/2 1/3 Motor Full Load Amps 1/2 2.8 5.2 2.8 5.2 RPM(Nominal)-Speeds 7.1 5.2 7.1 1075-3 1075-3 1075-3 1075-3 1075-3 1075-3 1075-3 Blower Wheel Diameter x Width —In.(mm) 10 x 6 10 x 6 10 x 6 10 x 6 11 x 8 10 x 8 10 x 10 * (254 x 152) (254 x 152) (254 x 152) (254 x 152) (279 x 203) (254 x 203) (254 x 254) Gas input ratings are certified for elevations to 2000 ft.(610 M). In USA,For elevations above 2000 ft(610 M),reduce ratings 4 percent for each 1000 ft(305 M)above sea level.Refer to National Fuel Gas Code NFPA 54/ANSI Z223.1-2012 Table F.4 or furnace installation instructions. t Capacity in accordance with U.S.Government DOE test procedures. # Airflow shown is for bottom only return-air supply for the as-shipped speed tap.For air delivery above 1800 CFM,see Air Delivery table for other options.A filter is required for each return-air supply.An airflow reduction of up to 7 percent may occur when using the factory-specified 4-5/16—in.(110 mm)wide, high efficiency media filter. ** Time—delay type is recommended. ICS Isolated Combustion System 4 CARRIER ACCESSORIES ©� rr>nQN 'PARTNO, rr'a5- $017,0P 1 -, , ' 0412 0 0- . 0:10'' 070-a 09O ', We0- , • 11OO ;110. .1*' 135- 135" 155- 0 1t 16 14r !6 20`; ,12: 16 22, Y16' 22 20 FILCABXL0016IIIIIII( 1111111111111111 .: Media Filter Cabinet FILCABXL0020 FILCABXL0024 - FILCCCAR0016 X 111111111111111111 Cartridge Media Filter FILCCCAR0020 X FILCCCAR0024 EXPXXUNV0016 X 11111111111111X EZ Flex Media Filter with End Caps EXPXXUNV0020 X X EXPXXUNV0024 EXPXXFIL0016 - X X Replacement EZ Flex Filter Media EXPXXFIL0020 X I-- EXPXXFIL0024 QKGBFR0401614 FExternal Bottom Return lier RackKGBFR0501617 CO KGBFRO601621 IIiiiiiiii(i : toKGBFR0701624 External Side Return Filter Rack KGAFRp201L KGAWF1306UFRt ©©©©©©©©©© X Unframed Filter 3/4-in.(19 mm) KGAWF1406UFR 1111511:111111111 X KGAWF1506UFR Flue Extension X X KGAFE0112UPH X X X X X X X X Twinning Kit X X X X X X KGATW0601 HSI X X X X X X X X X Combustible Floor Base X X X X X KGAS80201ALL i X X X X X X X X X X X Downflow Vent Guard X X X KGBVG0101DFG X X X X X X X III Vent Extension Ica X XIIII X X X KGAVE0101DNH X X X X X X X X X X X X X X Chimney Adapter Kit KGACA02014FC X X X ' X X ' X X X X X X KGACA0201SFC Natural-to-propane Conversion Kt* X X X KGBNP50011SP X X X ' X X X X X X X X X Propane-to-Natural Conversion Kit X X KGBPN42011SP X X X X X X X X X Label Kit IIIX X X X KGALB0301KIT X X X X X XIX X X X X X X X LH32D6207 LH32DB202 LH32DB200 LH32DB205 LI-132DB208 Gas Orifice LH32DB078 See Installation Instructions for model, LH32DB076 altitude,and heat value usages. LI-132D8203 LH32DB201 LH32DB206 LH32DB209 LI-132D6210 *Factory-authorized and field installed.Fuel conversion kits are CSA(formerly AGA/CGA)recognized. t Suitable for Side Return Filter Rack X=Accessory S=Standard 6 • CARRIER ACCESSORIES Ac+i ssotles ; ELECTRONIC AIR CLEANER(EAC) Model EACB MECHANICAL AIR CLEANER Models EZXCAB,FILCAB HUMIDIFIER Model HUM HEAT RECOVERY VENTILATOR Model HRV ENERGY RECOVERY VENTILATOR Model ERV UV LIGHTS Model UVL For use with 1-speed Air Conditioner-deg.F/C,Auto Changeover-TP-NAC,TC-NAC THERMOSTAT - For use with 1-speed Heat Pump-deg.F/C,Auto Changeover-TP-NHP,TC-NHP* NON-PROGRAMMABLE For use with 2-speed Air Conditioner-deg.F/C,Auto Changeover-TP-NRH* For use with multi-use/stage configurations-deg.F/C,Auto Changeover/Temperature and Humidity Control-TP-PRHt For use with 1-speed Air Conditioner-deg.F/C,Auto Changeover,7-Day Programmable- TP-PAC For use with 1-speed Heat Pump-deg.F/C,Auto Changeover,7-Day Programmable- X TP-PHP* F- THERMOSTAT - For use with 2-speed Air Conditioner-deg.F/C,Auto Changeover,7-Day Programmable- PROGRAMMABLE TP-PRH* For use with 1-speed Air Conditioner-deg.F/C,5-2 Day Programmable-TP-PAC For use with multi-stage applications-deg.F/C,Auto Changeover,7-Day Programmable-TC-PHP# For multi-use/stage configurations-deg.F/C,Auto Changeover,7-Day Programmable/Temperature and Humidity Control-TP-PRHt Comfort'"Series 3-Zone Kit-ZONECC3ZAC01,ZONECC3ZHP01 ZONING CONTROL 2 Performance"'Series ComfortZone'"II Zoning/Temperature and Humidity Control-ZONECC2KIT01-B 4 Performance-Series ComfortZone'"II Zoning/Temperature and Humidity Control-ZONECC4KIT01-B 8 Performance'"Series ComfortZone'"II Zoning/Temperature and Humidity Control-ZONECC8KIT01-B * Model HP and 2S thermostat must be field converted to air conditioner operation. t Thermidistat Control can be configured for multiple use and staging,it must be configured for each specific application. Dual Fuel thermostat is used with furnace and heat pump application. TYPICAL WIRING SCHEMATIC ---- FIELD 24-V WIRING ---- FIELD 115-,208/230-,460-V WIRING - FACTORY 24-V WIRING - FACTORY 115-V WIRING NOTE 2 FIVE 10 Q Cr) T Y 4 HRMERMOSTAT WIRE Y Y �TERMINALS FIELD-SUPPLIED I I DISCONNECT BLOWER THREE-WIRE _ DOOR HEATING- ' t 208/230-OR SWITCH N -- ___ 460-V --- THREE s�tc• 111 a�r�i PHASE ak_27 IAA 4.0 WH 111.1 -- 01 YGND I r?-1 GND ! -- III •--- 208/230-V AUXILIARY ® I J SINGLE 115-V J-BOX --L I � -_- _,�1 •--- PHASE FIELD-SUPPLIED DISCONNECT CONTROL �)/ NOTE 1 — GNDI BOX © " UN TDENSING 24-V TWO TERMINA WIRE BLOCK FURNACE NOTES: 1. Connect Y-terminal as shown for proper operation. 2. Some thermostats require a"C"terminal connection as shown. 3. If any of the original wire,as supplied,must be replaced,use same type or equivalent wire. A02186 7 r 1 L �J 1 IR• - 11 •0 \ X SEE NOTES:1,2,4,7,8,9 SEE NOTES:1,2,3,4,7,8,9 SEE NOTES:1,2,4,5,7,8,9 UPFLOW UPFLOW < A02058 A02059 DOWNFLOW A02061 i . co to • 1 €: /;: F �7 (� t .^9j - 1 '-':----t"--. `',e -- 11"11.1111111.11'.. t_r' Jam \"�. J I � 1 Q• v_ e _ ii e e� F / .tT J> .z. as SEE NOTES:1,2,3,4,5,7,8,9 SEE NOTES:1,2,3,4,5,7,8,9 SEE NOTES:1,2,4,5,6,7,8,9 DOWNFLOW DOWNFLOW DOWNFLOW A02060 A02063 A02062 Venting Notes 1. For common vent,vent connector sizing and vent material:United States,latest edition of the National Fuel Gas Code(NFGC),ANSI Z223.1/NFPA 54. 2. Immediately increase to 5-in.(127 mm)vent connector outside furnace casing when 5-in.(127 mm)vent connector required,refer to Note 1. 3. Side outlet vent for upflow and downflow installations must use Type B vent immediately after exiting the furnace, except when Downflow Vent Guard is used in downflow position. 4. Type B vent where required,refer to Note 1. 5. 4—in.(102 mm)single wall vent must be used inside furnace casing and the Downflow Vent Guard Kit. 6. Accessory Downflow Vent Guard Kit required in downflow installations with bottom vent configuration. 7. Chimney Adapter Kit required for exterior masonry chimney applications. Refer to Chimney Adapter Kits for sizing and complete application details. 8. Secure vent connector to furnace elbow with(2)corrosion-resistant sheet metal screws,space approximately 180° apart. 9. Secure all other single wall vent connector joints with(3)corrosion-resistant screws spaced approximately 120° apart. Secure Type B vent connectors per vent connector manufacturer's recommendations. 8 is • • . 7, SEE NOTES 1,2,4,5,7,8,9 — ,— — - _ HORIZONTAL RIGHT SEE NOTES 1,2,4,5,7,8,9_ . A02068 HORIZONTAL RIGHT A02070 I, J ,•:/".;;'—'r cn P a 1— cn co I a in SEE NOTES 1,2,4,7,8,9 HORIZONTAL RIGHT A02069 1 liA • SEE NOTES 1,2,4,7,8,9 SEE NOTES 1,2,4,5,7,8,9 HORIZONTAL LEFT HORIZONTAL LEFT A02064 A02065 i 1 4 '' i,=`�> • 0 ...., . , , yJ ..., SEE NOTES 1,2,4,5,7,8,9 SEE NOTES 1,2,4,5,7,8,9 HORIZONTAL LEFT HORIZONTAL LEFT A02066 A02067 9 • AIR DELIVERY— CFM (With Filter) ' U N40,E RETURN ArR �R1AL St4T)G PRESSURE{t1t 1f 0) , 0.1 _ o2' j4ja," 04.' 05 0. ;07: 0.9 ti , High 045-08 Bottom or 1035 995 945 895 835 770 675 565 390 195 Side(s) Med—High 865 830 790 745 690 625 545 440 250 195 Med—Low 760 720 680 635 580 520 445 345 220 195 Bottom or High 1440 1375 1305 ! 1240 1160 1070 975 870 730 560 045-12 Side(s) Med—High 1360 1300 1240 1175 1115 1040 950 850 725 575 Med—Low 1250 1210 1160 1100 1040 965 885 790 670 520 Bottom or High 1 1030 1005 ' 965 925 070-08 870 810 740 645 465 280 Side(s) Med—High 835 815 790 755 710 660 590 480 325 205 Med—Low 725 700 675 635 595 545 460 350 250 -- Bottom or High 1425 1375 1 1320 1265 1200 1125 1035 940 830 655 070-12 Side(s) Med—High 1320 1280 1 1240 1205 1140 1075 995 905 790 620 Med—Low 1200 1175 I 1145 1105 1050 990 920 840 725 555 070-16 Bottom or Med—Low 1355 1700 , 1635 1570 1505 1435 1350 1260 1160 1055 Side(s) — High 1755 O Med High i 1550 1520 1475 1430 1375 1310 1240 1155 1070 970 -- 1340 1310 1280 1240 1190 1125 1060 975 890 High 1605 �. Bottom or 1570 1535 1465 1385 1285 1175 1055 895 645 090-14 Q Side(s) Med—High 1470 1445 1410 1380 1300 1220 1115 990 830 600 Med—Low 1310 1295 1265 1230 1195 1120 1025 915 710 565 Bottomcn High 1940 1880 1805 1720 1635 1540 1425 1290 1090 830 c0 090-16 Side(s) Med—High 1740 1700 ' 1650 1590 1525 1440 1335 1195 1010 820 Med—Low 1505 ! 1505 , 1480 , 1440 1375 1300 1190 1045 890 740 High g 2405 2310 ' 2220 2130 2025 1920 1790 1660 1530 1350 Bottom Only Med—High 2170 2110 2040 ' 1970 1895 1785 1675 1565 1420 1260 Med—Low 1920 1875 ' 1835 1780 1715 1630 1535 1420 1275 1135 Both Sides or 1 High 2530 2450 2365 2270 2165 2065 1940 1805 1670 1505 090-20 Side&Bottom Med—High 2230 2170 2110 2050 1985 1890 1780 1660 1525 1360 Med—Low 1895 1890 1845 1815 1755 1685 1600 1480 1350 1180 High 2475 2395 2300 2200 2090 1985 1865 1730 1585 1425 1Side Only Med—High ! 2105 2145 2070 2010 1940 1845 1735 1620 1475 1325 Med—Low 1850 1860 ' 1810 1770 1715 1650 1555 1445 1310 1150 Bottom or High 1600 1550 i 1490 ' 1425 1355 1260 1135 990 785 530 110-12 Side(s) Med—High 1475 1435 ! 1395 1335 1285 1185 1070 890 725 450 Med—Low ' 1315 1295 1265 i 1220 1155 1080 985 810 675 440 Bottom or High 1980 1915 1835 1750 1655 1495 1365 1185 965 700 110-16 Side(s) Med—High 1745 1710 1650 1560 1450 1340 1205 1090 865 605 Med—Low 1530 1515 I 1470 1400 1310 1215 1095 990 830 670 High 2485 2415 T 2340 2255 2160 2080 1950 1840 1720 1565 Bottom Only Med—High 2135 2100 2060 2000 1930 1860 1765 1670 1555 1425 Med—Low 18551840 1815 1775 1725 1675 1600 1510 1405 1290 Bottom Sides High ' 55 1 2285 2190 2090 165 1850 : 1705 1535 110-22 or 1 Side&Bot- Med High 2140 2100 2050 1990 1935 1865 1760 1670 1545 1410 torn Med—Low 1855 1840 ! 1815 ! 1775 1725 1675 1600 1510 1405 1290 High i 2495 j 2440 2370 l 2290 2205 2120 2015 19101 Side OnlyMed—High 20301775 i1625 A filter is re wired for each return—air inlet Airflow- o pertormance i 2025 2000 1950 1905 1850 1750 1660 1555 : 1425 Med—low -- i 1735 1725 1695 1650 1595 1535 1455 1335 I 1230 * 4ncluded 3/4-in.(19 mm)washable filter media such as contained in factory-authorized ac- cessory filter rack.To determine airflow performance without this filter,assume an additional 0.1 In.W.C.available external static pressure. --Indicates unstable operating conditions. 10 t INSTALLATION '= GUIDE SPECIFICATIONS Gas Furnace Casing 58STA/STX Casing shall be of .030 in. (.76) thickness minimum, General pre—painted steel. SYSTEM DESCRIPTION Inducer Motor Furnish a Inducer motor shall be soft mounted to reduce vibration fixed capacity gas—fired transmission. furnace for use with natural gas or propane (factory Draft Safeguard Switch authorized conversion kit required for propane); furnish cold air return plenum. Draft Safeguard Switch (blocked vent safeguard) shall QUALITY ASSURANCE be factory installed to reduce the possibility of vent gas infiltration due to a blocked or restricted vent pipe. Unit will be designed, tested and constructed to the current ANSI Z 21.47/CSA 2.3 design standard for Heat Exchangers gas—fired central furnaces. Heat exchangers shall be a 4-Pass 20 gage aluminized Unit will be 3rd party certified by CSA to the current steel of fold—and—crimp sectional design when applied ANSI Z 21.47/CSA 2.3 design standard for gas—fired operating under negative pressure. central furnaces. Controls Unit will carry the CSA Blue Star® label. Control shall include a micro—processor based integrated electronic control board with at least 11 service Unit efficiency testing will be performed per the current DOE test procedure as listed in the Federal Register. flashing H troubleshooting codes displayed via enhanced LED diagnostic light on the control, a self—test feature that co Unit will be certified for capacity and efficiency and checks all major functions of the furnace within one listed in the latest AHRI Consumer's Directory of Q minute, and a non—volatile memory replaceable U) Certified Efficiency Ratings. Unit shall carry the current Federal Trade Commission automotive—type circuit protection fuse. Multiple co operational settings available including, separate blower Energy Guide efficiency label. DELIVERY,STORAGE AND HANDLING speeds for heating, cooling and continuous fan. Unit shall be shipped as singles Continuous fan speed may be adjusted from the storedUand handled peri g unit manufacturer's only thermostat. Cooling airflow will be selectable between 350 recommendations. or 400 CFM per ton of air conditioning. WARRANTY(for inclusion by specifying engineer) OPERATING CHARACTERISTICS Warranty certificate available upon request. Heating Capacity shall be Btuh input; Products Btuh output capacity. Fuel Gas Efficiency shall be 80% AFUE. Air delivery EQUIPMENT shall be CFM minimum at 0.50 In. W.C. Components shall include: slow—opening gas valve to external static pressure. reduce ignition noise, regulate gas flow, with electric Dimensions shall be: depth in. mm ; switch gas shut—off; flame proving sensor, hot surface width(ciht (mm);halheight in. (win) igniter, pressure switch assembly, flame rollout switch, A/C coil only).nHeight shall be in. (mm) with blower and inducer assembly, 40va transformer; ea and in. (mm) overall with low—voltage (heating) (heating/cooling) thermostat. plenum. Blower Wheel and Blower Motor ELECTRICAL REQUIREMENTS Galvanized blower wheel shall be centrifugal type, Electrical supply shall be 115 volts, 60 Hz, statically and dynamically balanced. Blower motor of PSC be gle—phase (nom maxi Minimum wrre size shall type shall be permanently lubricated with sealed bearings, AWG; maximum fuse size or circuit breaker of hp, and shall be multiple—speed direct drive. shall be Amps. Blower motor shall be soft mounted to the blower scroll to SPECIAL FEATURES reduce vibration transmission. Refer to section of the product data sheet identifying Filters accessories and descriptions for specific features and Furnace may have reusable—type filters. Filter shall be available enhancements. in.high efficiencym Mea(x) Filter is available asAnmm). accessory anoptio Media Filter. 13 X H N c Copyright 2017 Carrier Corp.• 7310 W.Morris St.• Indianapolis,IN 46231 Edition Date: 10/17 Catalog No:58ST-12PD Manufacturer reserves the right to change,at any time,specifications and designs without notice and without obligations. Replaces: 58ST-11 PD 14 ' . Unt013 • , MARS Designer Series- MARS Elite Series - Plastic Base Plastic Cover And Base MARS offers a broad selection of MARS offers a broad selection of thermostat guards.Popular thermostat guards.Popular models models available include metal, available include metal,clear clear plastic and opaque plastic plastic and opaque plastic designs.MARS thermostat designs.MARS thermostat guards are ideal for protecting guards are ideal for protecting thermostats in schools,industrial thermostats in schools,industrial plants institutions,public facilities plants institutions,public facilities and other areas where and other areas where unauthorized tampering could be unauthorized tampering could be a problem.These attractive units a problem.These attractive units feature a rugged,light weight feature a rugged,light weight and compact design.All units and compact design.All units supplied with key.Extra keys are 70236,4007;, 70217 supplied with key.Extra keys are 7020! available.Order part#70236 for 70236 available.Order part#70236 for the BTG thermostat guard key. the BTG thermostat guard key. r '" ::-,7'-',:rile..:-T1,44; $ Solid 8 5 21/8 '' „! •. ' Solid 4 3/4 4112 2 314 - ' , Ring 8 5 21/8 r-..,...,,,,,,,,,,t,...,,,,„,„,..........„„„„„„„,„...:„.„„„,.............„,,.......„.„..„,::::,............„_ (........ ........................................... ...._......„....„,.....„,,,,,...„......„,„:„.„...„„,,,,, -„,,.....„,,,,,-*-i 70201 BTG-EK clear plastic cover Solid 1 12 70217 '41';';' ''';':-G-DK clear plastic Dual 1 12 70236 F336,extra key for all BTG guards 1 1 70236 F336,extra key for all BTG guards 1 1 MARS Classic Series - MARS Universal Series Plastic Base MARS offers a broad selection of MARS offers a broad selection of thermostat guards.Popular thermostat guards.Popular models available include metal,clear models available include metal, plastic and opaque plastic clear plastic and opaque plastic designs.MARS thermostat designs.MARS thermostat guards are ideal for protecting guards are ideal for protecting Z thermostats in schools,industrial thermostats in schools,industrial plants institutions,public facilities plants institutions,public facilities and other areas where and other areas where ; 0 Ilmo unauthorized tampering could be unauthorized tampering could be 14 a problem.These attractive units t a problem.These attractive units ,_f rr� feature a 70220 feature a rugged,light weight :7„,,,,,. 70205 rugged,light weight and compact design.All units J ' and compact design.All units supplied with key.Extra keys are ACC supplied with key.Extra keys are pP y impi available.Order part for available.Order part#70236 for the BTG thermostat guard key. 0the BTG thermostat guard key .� r Solid 6114 5 5/8 3 3/16 ;? Ring 61/4 5 518 3 3/16 W 74224 4M , 70x36 702005. BTG-K clear plastic cover Dual 1 12 i0 70236 F336,extra key for all BTG guards 1 1 "St IZ `. Thermostat Guard Bases W Solid 9 5/16 5 5/8 3 9116 CO Ring 9 5/16 5 5/8 3 9116 - thailBase Solid 8 5 9/16 3 5/8 Ring 8 59/16 3518 >','70220 BTG-UK2 clear plastic Dual 1 12 70223 BTG-UM metal Solid 1 12 70224 BTG-UWM metal Ring 1 12 Solid Daae Rrng Base ':.10236• ., F336,extra key for all BTG guards 1 1 Toll Free(800)445-4155 •• Fax(631)348-7160 •• www.marsdelivers.com "",' 7