Special Inspection
FINAL SUMMARY LETTER
Date: February 12, 2018
Job#: T1701603
RECEIVED
City of Tigard FEB 1 2Qj$
13125 SW Hall Blvd
Tigard, OR 97223-8199 CITY OF TIGAiD
3UILDING DIVISION
Attn: Building Division
Re: Project Name: Skyhook Ninja Fitness—Interior Alteration
Address: 12008 SW Garden Place—Tigard, OR
Permit#: BUP2016-00350
Per Chapter 17, Section 1704.1.2 of the International Building Code (IBC), we have performed special inspection of the
following item(s) per our inspection reports only:
Expansion Anchors
The non-compliance (NC) items recorded for each of the above inspection categories, as listed on the non-compliance
report, have been either repaired and re-inspected by CTI for compliance or reviewed and accepted by the engineer of
record for the project in the"As-Built Condition" or through an RFI.
The issuance of this final report is based on the engineer's acceptance of the NC items not specifically re-inspected by
ion of those items
CTI. CTI did not of these individual ittems on the non-compliaional review or nce list. The engineer of beyond
has provided the ections that
generated e
of the non-compliance items and as-built conditions.
All requested inspections and tests were performed and reported according to the requirements of project documents and
to the best of our knowledge, the work was in conformance with the approved plans and specifications, approved change
orders and applicable workmanship, provisions of the State Building Code and Standards, as well as the structural
engineer's design changes, approvals and verbal instructions.
Our construction inspection and testing services were provided and intended to help reduce the risk of construction
defects, deficiencies or omissions that arose during and after construction. Our services do not constitute a warranty or
guarantee of any type. Even with diligent construction monitoring and testing, construction defects, deficiencies or
omissions in the contractor's work may exist. It is the contractor's responsibility to perform their work in accordance with
the approved construction documents.
CTI has provided its professional services with the degree of care and skill currently exercised under similar
circumstances by members of its profession in the same locale. Statements made in our reports are based on technical
judgments and should not be construed to be conclusive representations of fact. Our reports pertain to the material
tested/inspected only.
Updated 11/30/11
P:\Projects\General\2017\T1701603\02-12-18 Final Letter.doc
Date: ,. February 12, 2018
Job#: T1701603
Page 2 of 2
CTI's services did not include responsibilities related to determining, supervising, implementing or controlling the means,
methods, techniques, sequences or procedures of the construction or evaluating or reporting job conditions related to
health, safety or welfare.
Information contained herein is not to be reproduced, except in full, without prior authorization from this office. If there are
further questions regarding this matter please do not hesitate to contact this office.
Respectfully submitted,
CARLSO► -STING I .
E--Ka
-n Shepherd
Project Manager
KS/jng
cc: Cody Knope-Jenkins BIYARO@GMAIL.COM
City of Tigard Building Division—Walter`Chip' Barnett WALTER@TIGARD-OR.GOV
Koble Creative—Terry Amundson TERRY@KOBLECREATIVE.COM
Carlson Testing, Inc.
Incompleted Items List (NCL)
Feb 12,2018
T1701603.
Project Name: SKYHOOK NINJA FITNESS - INTERIOR ALTERATION
Project Address: 12008 SW GARDEN PLACE TIGARD OR
Permit No: BUP2016-00350
P.O.No:
Project Manager: K. SHEPHERD
Item# Insp. Date Item Description Compliance CTI Sign-Off Date
Corrected
1 GP 04/04/2017 SUBMITTAL 5/A2.3 CALLS FOR 3/8" X 3" TITEN HD ACCEPTABLE PER ENGINEER STEVEN W. LEACH 02/12/2018
ANCHORS WITH 2 %" EMBEDMENT. INSTALLERS USED %" X OF RECORD LETTER DATED
5-%Z" ITW RED HEAD WEDGE ANCHORS. 07/14/17 AND LOAD
TESTING PERFORMED BY CTI
REPRESENTATIVE ON
08/17/17.
2 GP 04/04/2017 PORTION OF ANCHORS PROTRUDING FROM TOP OF ACCEPTABLE PER ENGINEER STEVEN W. LEACH 02/12/2018
CONCRETE RANGES FROM 1-%" TO 2-%" . TOPS OF SOME OF RECORD LETTER DATED
ANCHORS HAVE BEEN CUT OFF. NO WAY TO VERIFY EMBED 07/14/17 AND LOAD
DEPTH. TESTING PERFORMED BY CTI
REPRESENTATIVE ON
08/17/17.
CC:CODY KNOPE-JENKINS
CITY OF TIGARD BUILDING DIVISION - WALTER 'CHIP' BARNETT
KOBLE CREATIVE - TERRY AMUNDSON
Page: 1
�I I11203
QW D Y Structural • Civil Engineers
July 14, 2017
Skyhook Ninja Fitness
12008 SW Garden Place
Tigard, OR 97223
Attn: Cody Knope-Jenkins
Re: Trampoline Anchor Testing Recommendations
12008 SW Garden Place,Tigard, OR
Dear Cody,
At your request, WDY has prepared the following recommendations for testing the trampoline concrete
anchors at the subject site. We understand that anchors were installed without special inspection and
some anchors did not achieve full embedment. Our recommendations are based on 1.5 times the cracked
concrete design capacity of the 3/8" diameter x 3" Titen HD anchors noted on the project drawings,
assuming a minimum 5" concrete slab on grade with a minimum 2,500 psi 28 day concrete compressive
strength (modified to allowable strength levels). Anchor testing shall be performed by an independent
testing agency retained by you or your company.
Testing Recommendations:
Tension test load: 1,250 pounds. Acceptance criteria—anchor maintains test load for 1 minute.
1. Test all anchors that have had the top of the anchor cut off or anchor length above the slab that
would indicate incomplete embedment.
2. Test 10% of remaining anchors. Notify engineer after first failed anchor in this group and load at
failure before continuing.
3. If any of the 10%fail—test an additional 10%.
4. If any of the second 10%fail—test all remaining anchors.
5. Prepare a report of findings, including identifying anchors tested, anchors that fail the test (if any)
and load at failure.
Limitations:
WDY has not analyzed the trampoline system. The recommendations contained herein are based solely
on the capacity of the anchors specified on the project drawings dated Rev no. 1, 02.10.2017. WDY is not
responsible for the design of the trampoline system or trampoline anchorage.
Please contract our office if you have any questions or if we can be of any further assistance.
WDY, INC.
Dale DiLoreto, P.E., S.E.
Cell: (503)970-1039
cc: Koble Creative—Attn:Terry Amundson
\\WDY-DC011Projects\2017\17156 Skyhook NinjalDocument\17156 Testing Memo.doc