Report (52) . 1�SaI77ri/ 0777 S& 4 tlICQ/Ffre & Building roducts Technical Services: Tel: (800)381-9312/Fax: (800)791-5500 Series TY-FRB — 2,8, 4s2r 5.61 and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage P nklers General tamed when exposed to corrosive at- mospheres. Although corrosion resis- Description tant coated sprinklers have passed the ' standard corrosion tests of the appli- The Tyco® Series TY-FRB, 2.8, 4.2, cable approval .: r" si. not reprreentativeeof�a l possible) or-is w. 5.6,and 8.0 K-factor,Upright and Pen- dent Sprinklers described in this data f rec atmospheres. Consequently, it is rec sheet are quick response - standard ommended that the end user be coverage,decorative 3 mm glass bulb consulted with respect to the suitability ,r.iri type spray sprinklers designed for use of these coatings for any given corro- in light or ordinary hazard,commercial sive environment.The effects of ambi- occupancies such as banks, hotels, ent temperature, concentration of ~ shopping malls, etc. chemicals, and gas/chemical velocity, should be considered, as a minimum, The recessed version of the Series along with the corrosive nature of the TY-FRB Pendent Sprinkler,where ap- chemical to which the sprinklers will be plicable, is intended for use in areas exposed. with a finished ceiling. It uses either a two-piece Style 10 (1/2 inch NPT) or An intermediate level versions of the Style 40(3/4 inch NPT)Recessed s- Series TY-FRB Pendent Sprinklers cutcheonwith 1/2 inch (12,7 mm) are detailed in Technical Data Sheet recessed adjustment or up to 3/4 ich of TFP356,and Sprinkler Guards are de- if (19,1 mm)of total adjustment from the tailed in Technical Data Sheet TFP780 flush pendent position, or a two-piece Style 20(1/2 inch NPT)or Style 30 3/4 WARNINGS ( The Series TY-FRB Sprinklers de-and x ` „ inch NPT) Recessed Escutcheon with scribed herein must be installed and :::1/4 inch (6,4 mm)of recessed adjust- maintained in compliance with this ment or up to 1/2 inch (12,7 mm) of �'"'� total adjustment from the flush pofn- document, as well as with the appl/ca- deat adjustment The jspro- ble standards of the National Fire Pro- dent bytheRecessed adjustmentusre- tection Association, in addition to the duces the accuracy o which the fixed standards of any other authorities hav- pipe drops to the sprinklers must be ing jurisdiction. Failure to do so may Model/Sprinkler p p impair the performance of these de-cutIdentification vices. Corrosion resistant coatings, where The owner is responsible for maintain- a eplicich c bile, r utilized sprinkletole extend ing their fire protection system and de- Numbers that wwould otherwise be ob- vices vices in proper operating condition. TY1131 - Upright 2.8K, 1/2"NPT The installing contractor or sprinkler TY1231 - Pendent 2.8K, 1/2"NPT manufacturer should be contacted TY2131 - IMPORTANT with any questions. TY2231 - Pendent 4.2K, 1/2"NPT TY3131 - Sheet TFP700 for the "INSTALLER Upright 5.6K, 1/2"NPT Always refer to Technical Data TY3231 - Pendent 5.6K, 1/2"NPT WARNING" that provides cautions TY4131 - with respect to handling and instal- TY4231 - Pendent 8.0Kht ,3/4"NPT lation of sprinkler systems and com- TY4831- ponents. Improper handling and in Upright 8.0K, 1/2"NPT ` stallation can permanently damage TY4931- Pendent 8.0K, 1/2"NPT a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 10 AUGUST, 2007 TFP171 Page 2 of 10 TFP171 ESCUTCHEON 7/16"(11,1 mm) STYLE 10 or 20 RECESSED PLATE SEATING 1/2^ NOMINAL ESCUTCHEON SSU* SURFACE MAKE-IN DEFLECTOR NPT IAF 6 :'a?T'1 y.�Tf�. --p -,_______.._____=_-_.. ------ = 7/16" I 4 IIII 1,11r;= NO NA I ' 2-1/4" =, IFNI � I NOMINAL 2 (57,2 mm) ��Ilr � MAKE-IN A' -L 2-3/16" Ir 19/16 (55,6 mm)WRENCH (397 mm) FLATS /%1!ti�� ///fl'ti�� 1/2"NPT SSP DEFLECTOR* 2-7/8"(73,0 mm)DIA. CROSS SECTION PENDENT RECESSED PENDENT UPR__GHT 3-Sealing 4-Bulb 6-Deflector * Temperature rating is indicated on deflector or adjacent to 1-Frame Assembly 5-Compression 7-Bushing orifice seat on frame. 2-BButton Screw FIGURE 1 QUICK RESPONSE SERIES TY-FRB 2.8IGHT(T Y 131) AH ND PENDENT(TY1231)SPRINKLERS U T ESCUTCHEON 7/16"(11,1 mm) STYLE 10 or 20 RECESSED PLATE SEATING 1/2" MAKE-IIN ESCUTCHEON DEFLECTOR SU* SURFACE NPT 6* r Iiii7ln'*� ��\�e� W 5 , �� 7/16" __r I (11,1 mm) I I 4 2-3/16" 1\ NOMINAL (55,6 mm) I�1 � ���: .110, MAKE-IN MAKE-IN 2 1mm I'' I 1�1 2-3/16" V 11/2 (5m) ii WRENCH) FLATS III • NPT 1 *_-- 2-7/8"(73,0 mm)DIA. �1 1/2' SSP DEFLECTOR CROSS SECTION PENDENT RECESSED PENDENT UPRIGHT 3-Sealing 4-Bulb 6-Deflector * Temperature rating is indicated on deflector or adjacent to 1-Frame Assembly 5-Compression orifice seat on frame. 2-BButton Screw FIGURE 2 QUICK RESPONSE SERIES TY-FRB BRIGHT(T 2 Y131)AND PENDENT(TY2231)SPRINKLERS 4.2 U TFP171 Page 3 of 10 ESCUTCHEON 7/16"(11,1 mm) STYLE 10 or 20 PLATE SEATING NOMINAL SURFACE 1/2" RECESSED MAKE-IN ESCUTCHEON NPT SSU* DEFLECTOR G ,_.pit .�. 6* (55,6 mm) A� ��1` 7/16.. ter 5 2-3/16" \---= 1 .___„1111%- ; �� (11,1 mm) �L� NOMINAL ili 1-1/2" id ��� I 1��r MAKE-IN A 4 (38,1 mm) �� 2-3/16" i 2 WRENCH D (55,6 mm) o FLATS — E 3 if SSP DEFLECTOR* 'E 2-7/8"(73,0 mm)DIA. 1/2"NPT 1 PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1-Frame 3-Sealing 2-ButtonramAalin4-Bulb 6-Deflector * Temperature rating is indicated on deflector or adjacent to Y 5-Compression Screw orifice seat on frame. FIGURE QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY3131)AND PENDENT(TY3231)SPRINKLERS 5.6 K-FACTOR, 1/2 INCH NPT ESCUTCHEON 1/2"(12,7 mm) STYLE 30 or 40 PLATE SEATING NOMINAL RECESSED SURFACE 3/4 MAKE-IN ` NPT ESCUTCHEON SSU* DEFLECTOR ------- Ill__ __–.--=------. III 2-5/16" 1/2" (�% 5 (58,716" kill, �� �� (12,7 mm) 1-9/16" I MAKE-IN L 4 (39,7 mm) I� I 2-1/4" A� 2 . WRENCHFLATS _— III (57,2 mm) .MPI SSP DEFLECTOR* 2-7/8"(73,0 mm)DIA. I NPT PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1-Frame 3-Sealing 4-Bulb 2-Buttonram6-Deflector * Assembly 5-Compression Temperature rating is indicated on deflector or adjacent to Screw orifice seat on frame. FIGURE 4 QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY4131)AND PENDENT(TY4231)SPRINKLERS 8.0 K-FACTOR, 3/4 INCH NPT TFP171 Page 4 of 10 7/16"(11,1 mm) SSU* NOMINAL 1/2" MAKE-IN DEFLECTOR NPT * 6 Ilkh! 5 2-3/16"2-1/4" I`, (55,6 mm) I i 4 - i (57,2 mm) -`t'-9/16" WRENCH �' 2 I Ir FLATS t 3 (39,7 mm) __ II SSP* CROSS DEFLECTOR SECTION PENDENT UPRIGHT 3-Sealing 4-Bulb6-Deflector Temperature rating is indicated on deflector or adjacent to 12-Buttonrameorifice seat on frame. 2- Assembly 5 Compressioncrew FIGURE 5 QUICK RESPONSE SERIES TY-FRB U RIGHT(T Y4 31)ANP T AND PENDENT(TY4931)SPRINKLERS 8.0 Technical Operation Data The glass Bulb contains a fluid which expands when exposed to heat.When Approvals the rated temperature is reached, the UL and C-UL Listed. fluid expands sufficiently to shatter the FM,LPCB, and NYC Approved. glass Bulb, allowing the sprinkler to (Refer to Table A and B for complete activate and water to flow. approval information including corro- sion resistant status.) Design Maximum Working Pressure Criteria Refer to Table C. Discharge Coefficient ) The Series TY-FRB Pendent and Up- K=2.8 GPM/psi1/2(40,3 LPM/bar1/2 right Sprinklers are intended for fire K=4.2 GPM/psis/2 (60,5 LPM/bars/2j protection systems designed in ac- K=8.0 GPM/psis/2(80,6 L PM/bar12 ordance with the standard installation K=8.0 GPM/psil/2(115,2 LPM/bars/2) rules recognized by the applicable Temperature Ratings Listing or Approval agency (e.g., UL Refer to Table A and B Listing is based on the requirementsvas base NFPA 13, and FM App Sprinkler:iniskes on the requirements of FM's Loss Pre- Recessed Refer Escutcheon:Table A and B. vention Data Sheets ). Only the Style roed,or Brass Plated.lCoated, 10, 20, 30, or 40 Recessed Escutch- eon,Chrome Plated,or as applicable, is to be used for recessed pendent installations. E Physical Characteristics �' Frame Bronze Button Brass/Copper -0 Sealing Assembly 12 Bronze Beryllium Nickel w/Teflont Bulb Glass 22N N Compression Screw Deflector Copper/Bronze a> 0 Bushing (K=2.8) Bronze z a +- TFP171 Page 5 of 10 m•iiim .mm.•m.•.•.•.••••••••m.__ MUNIBULB NATURAL CHROME WHITELIQUID BRASS PLATED T POLYESTER PENDENT ® Orange (TY1231) 155°F/68°C Red and ® Yellow UPRIGHT 200°F/93°C MI (TY1131) 286°F/141°C RECESSED 1112133111 Orange PENDENT COM Red (TY1231)* 175°F/79°C Yellow Figure 6 200°F/93°C RECESSED ® Orange PENDENT Red (TY1231)** ® Yellow Figure 7 200°F/93°C MEMPENDENT Orange Rim (TY2 ® Red andd Yellow UPRIGHT 200°F/93°C EMI (TY2131) 286°F/141°C RECESSED imm ® Orange PENDENT Red (TY2231)* ® Yellow Figure 8 200°F/93°C MI RECESSED ® Orange PENDENT Red (TY2231)** ® Yellow Figure 9 200°F/93°C IMME NOTES: 1.Listed by Underwriters Laboratories, Inc.(UL)as Quick Response Sprinklers. 2.Listed by Underwriters Laboratories, Inc.for use in Canada(C-UL)as Quick Re- sponse Sprinklers. 3.Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprin- klers. 5.Approved by the City of New York under MEA 354-01-E. 7.Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed,the sprin- klers are UL and C-UL Listed as Corrosion Resistant Sprinklers. * Installed with Style 10(1/2"NPT)or Style 40(3/4"NPT)3/4"Total Adjustment Recessed Escutcheon,as applicable. **Installed with Style 20(1/2"NPT)or Style 30(3/4"NPT)1/2"Total Adjustment Recessed Escutcheon,as applicable. ***Frame and Deflector only.Listings and approvals apply to color(Special Order). N/A:Not Available TABLE A LABORATORY LISTINGS AND APPROVALS 2.8 AND 4.2 K-FACTOR SPRINKLERS Page 6 of 10 TFP171 - 11111111111111111111111111111111 LEAD K ® BULB NATURAL CHROME WHITE*** COATED LIQUID BRASS PLATED POLYESTER Orange PENDENT Red 1031011 and (TY3 ® Yellow Mall UPRIGHT 200°F/93°C (TY3131) � ® Orange RECESSED ift42=1 Red PENDENT Yellow (TY3231)* Figure 10 200°F/93°C 11321 IMO Orange RECESSED CiiM Red PENDENT (TY3231)** 175°F/79°C Yellow Figure 11 200°F/93°C MI Immo Orange PENDENT Magna Red (TY4231) Yellow andd UPRIGHT 200F/93°C UZI 8.0 (TY4131) =BEM 314" ®® NPT RECESSED 11=13Orange PENDENT (TY4231)* 175°F/79°C Red Figure 12 200°F/93°C Yellow IESIM Orange RECESSED 155°F/68°C Red PENDENT Yellow (TY4231)** Figure 13 200°F/93°C 11310111011 Orange PENDENT EMI= Red 8.0 (T and ® Yellow 1/2" and NPT UPRIGHT 200°F/93°C MI "4831) 1=3=1 NOTES: as Sprinklers. 1.Listed by Underwriters Laboratories,Inc.(UL)as Underwriters Laboratories,Inc.for use in Canada(C-UL)as Quick Response 2.Approvedsted bySprinklers;however,the 3. by Factory Mutual PreventionResCert CorporationiBoardon (LPCB as Quicke.No.00710Sprinklers. 4.Approved by the rate the thermal sensitivity ftof recessed sprinklers. 007k/04)as Quick Response LPCB does not 5.Approved by the City of New York under MEA 354-01-E.6 Board(LPCB Ref.No.094a/06)as Quick Response Sprinklers.are UL and C-UL Listed as Approved(For details contact Tyco Fire&Building Products,Enschede,Netherlands,Tel.31-53-428-4444/Fax 31-53-428-3377). 8.WVS ppApproved as a 7.Approved by the Loss Prevention Certification roved,the sprinklers are FM Where lResistantt Sprinklers..Where Lead Coated Sprinklers and Lead Coated Sprinklers are t are noted to be FM Listed,thep Corrosionapplicable. Corrosion Resistant Sprinklers. Installed with Style 10 (1/2"( NPT)or Style 30(3/4"NPT)1/2"Total Adjustment Recessed Escutcheon,as applicable. **Installed with Style***Frame and Deflector only.Listings and approvals apply to color(Special Order). N/A:Not Available TABLE B LABORATORY5.6 AND 8.0 K FACTOR SPRINKLERS APPROVALS TFP171 Page 7 of 10 mm••..ii.m.ii••••..•m...••••••••••...m,m.____ K NATURAL CHROME WHITE BRASS PLATED POLYESTER L PENDENT(TY3231) COAATETE D and UPRIGHT(TY3131) RECESSED PENDENT (TY323) 175 PSI(12,1 BAR) PENDENT(TY4231) and UPRIGHT(TY4131) 175 PSI(12,1 BAR) RECESSED PENDENT (TY4231) I PENDENT(TY3231) and 250 PSI(17,2 BAR) UPRIGHT(TY3131) OR 175 PSI(12,1 BAR) RECESSED PENDENT (TY3231) (SEE NOTE 1) MOMMI= PENDENT(TY4231) and 175 PSI(12,1 BAR) 8.0 UPRIGHT(TY4131) MEM 3/4" RECESSED PENDENT NPT (TY4231) 1111111111111 8.0 PENDENT(TY4931) 1/2 and NPT UPRIGHT(TY4831) IIIIMEIIMIM NOTES: 1.The maximum working pressure of 250 psi(17,2 bar)only applies to the Listing by Underwriters Laboratories Inc. (UL);the Listing by Underwriters Laboratories,Inc.for use in Canada(C-UL);and,the Approval by the City of New York. TABLE C,MAXIMUM WORKING PRESSURE tai(13ned4to 26with a8 torqu Nm).eA ofmax10 ito 20mum ft.lbs.of30 the sprinkler into the sprinkler fitting. Installation The Series TY-FRB Sprinklers must ft.lbs.(40,7 Nm)of torque is to be used Step 3. Tighten the sprinkler into the be installed in accordance with the fol- fo install sprinklers with 3/4 NPT con- sprinkler fitting using only the W-Type lowing instructions: nections. Higher levels of torque may 6 Sprinkler Wrench (Ref. Figure 14). distort the sprinkler inlet and cause With reference to Figures 1, 2, 3, 4, NOTES leakage or impairment of the sprinkler. and 5,the W-Type 6 Sprinkler Wrench is to Do not install any bulb type sprinkler if Do not attempt to make-up for insuffi- flats be applied to the sprinkler wrench cient adjustment in the escutcheon The Series TY-FRB Recessed Pen- the bulb is cracked or there is a loss of plate by under-or over-tightening the dent Sprinklers must be installed in liquid from the bulb. With the sprinkler he/d horizontally, a small air bubble sprinkler. Readjust the position of the accordance with the following instruc- shouldbe present. The diameter of the sprinkler fitting to suit. air bubble is approximately 1/16 inch tions. (1,6air 1mo inch The Series TY-FRB Pendent and Up- Step A. After installing the Style 10. mm) for the for 5e 57°C to 3/32 right Sprinklers must be installed in 20, 30,or 40 Mounting Plate,as appli- ch (2,4 temperature ratings. accordance with the followinginstruc- tions. cable, over the sprinkler threads and A leak fight 1/2 inch NPTsprinklerjoint Step 1. Pendent sprinklers are to be with pipe thread sealant applied to the should be obtained with a torque of 7 pipe threads, hand tighten the sprin- to 14 ft./bs. (9,5 to 19,0 Nm).A maxi- installed in the pendent position, and kler into the sprinkler fitting. mum of21 ft. lbs. Nm) mxupright sprinklers are to be installed in mayuo used to install sprinklers with the upright position. Step leB. Tighten the sprinkler nithe intoT the 1/2 NPT connections.A leak tight 3/4 Step 2. With pipe thread sealant ap_ sprinkler fitting using only W-Type inch NPT sprinkler joint should be ob- plied to the pipe threads, hand tighten 7 Recessed eces 4,theSpW-Type reference to Figuinkler Wrench re 1, Figure 15 2, 3, and 4, the WTyp7 Recessed TFP171 Page 8 of 10 _ 2-7/8"DIA. 2-7/8"DIA. (73,0 mm) 1/2"(12,7 mm) (73,0 mm) 3/4"(19,1 mm) 1/2±1/8" 12" 12, mm) 518±114" 114"(6,4 mm) (12,7±3,2 mm) 2-1/4"DIA. (1 FACE mm) (57'2 DIA. ►{ FACE OF (57,2 mm) MOUNTING (57,2 mm) I MOUNTING SPRINKLER PLATE FACE OF PLATE FITTING SPRINKLER 118" FITTING •� (3.1 m"') 118" Wirma - ,1! MOUNTINGMOUNTING SURFACE SURFACE RIES 1-5/16"(33,3 mm) TY-FRB 13/16"(20,6 mm) 1-5/16"(33,3 mm) CLOSURE SERIES TY-FRB 1-1/16"(27,0 mm) CLOSURE SERIES FIGURE 7 FIGURE 6 SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 1/2RB INCH OADJUSTMENT WITH TWO-PIECE 10 INCH ADJUSTMENT STYLE 20 RECESSED ESCUTCHEON STYLE 10 RECESSED ESCUTCHEONNH2.8 K-FACTOR, 1/2 INCH NPT 2.8 K-FACTOR, 1/2 INCH NPT 2-7/8"DIA. 2-7/8"DIA. mm) 112"(12,7 mm) (73,0 mm) 3/4"(19,1 mm) 1/2±1/8" 114"(6,4 mm) 5/8±1/4" 114"(6,4 mm) (12,7±3,2 mm) 2-1/4"DIA. (15,9±6,4 mm) 2-1/4"DIA. (57,2 mm) MOUNTING (57,2 mm) MOUNTING FACE OF PLATE FACE OF PLATE SPRINKLER SPRINKLER FITTING 1/8" FITTING 1/8" .. (3,1/8" NI " � � MOUNTING , �■ MOUNTING SURFACE ___•-__ SERIES 1-114"(31,8 mm 1-114"(31,8 mm SURFACE SERIES CLOSURE TY-FRB 1"(25,4 mm) CLOSURE TY-FRB 314"(19,1 mm) FIGURE 9 FIGURE 8 SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 1/2RB INCH OADJUSTMENT WITH TWO-PIECE STYLE E10RECESSEDH ESCUTCHEONOTAL ADJUSTMENT STYLE.2 20 RECESSED D CU NPT ESCUTCHEON STYE 2 K ACTOR, 1/2 INCH NPT theSprinkler prinWrench is to applied to itcontrols,perm re ssionction tosh tdownstem that the fledaltered sprinklers m s ebe trreplacedl the sprinkler wrench flats. affected fire protection system must be Sprinklers that have been exposed to Step C. After the ceiling has been in- obtained from the proper authorities corrosive products of combustion, but stalled or the finish coat has been ap- and all personnel who may be affected ifhave enoly operated, be cohould muldtbe rpl aced plied,slide on the Style 10,20, 30,or by this action must be notified. by wiping cannot sprinkler completely withta cloth cleaned 0 Closure overu the os TY-FRB by brushing it with a soft bristle brush. Sprinkler and push the Closure over The owner must assure that the sprin objects; otherwise, non-operation in Care e to the sprinklers eree before,d to id d d dam- the Mounting Plate until its flange klers are not used for hanging ofany comes in contact with the ceiling. the event of a fire or inadvertent opera- age after installa . Sprinklers dam, tion may result. aged by dropping, striking, wrench Care and Absence of an escutcheon, which is twist/slippage, or the like, must be re- Maintenance used to cover a clearance hole, may placed. Also, replace any sprinkler delay the time to sprinkler operation in that has a cracked bulb that has lost The Series TY-FRB Sprinklers must a fire situation. liquid from its bulb. (Ref. Installation be maintained and serviced in accord- Sprinklers that are found to be leaking Section). ance with the following instructions: or exhibiting visible signs of corrosion Frequent visual inspections are rec- must be replaced. ommended to be initially performed for NOTES Automatic sprinklers must never be corrosion resistant coated sprinklers, Before con a fire valve for maintenatnce painted, plated, coated or otherwise after the installation has been com- main con TFP171 Page 9of10 2-7/8"DIA. " 5/8±1/4" (73,0 mm) "DIA. 3/4 (19,1 mm) (15549±1/4.m) 15,9±6,4 mm) 1/2±1/8" (732-7/8,0 mm) 2-1/4"DIA. 1/4"(6,4 mm) 1/2"(12,7 mm) FACE OF (57,2 mm (12,7±3,2 mm) 2-1/4"DIA. 1/4"(6,4 mm) SPRINKLER MOUNTING FACE OF (57,2 mm) FITTING PLATE SPRINKLER MOUNTING 1/8" FITTING PLATE (3,2 8" I 1/8" I did_ l,�M.____ 4. (3,2 mm) , _i T______v___ _. MOUNTING R, 741,,..„.0, MOUNTING 1�' SURFACE - 1 _-;_ SURFACE CLOSURE SERIES 1-1/4"(31,8 mm) TY-FRB 3/4"(19,1 mm) CLOSURE SERIES 1-1/4"(31,8 mm) TY-FRB FIGURE 10 1"(25,4 mm) SERIES TY-FRBRECESSED PENDENT FIGURE 11 WITH TWO-PIECE 3/4 INCH ADJUSTMENT SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 5.6 K-FACTOR, 1/2 INCH NPT 5.6 K-FACTOR, 1/2 INCH NPT 2-7/8"DIA. 5/8±1/4" (73,0 mm) 3/4"(19,1 mm) 2-7/8"DIA. (15,9±6,4 mm) 2-1/4"DIA. 1/4"(6,4 mm) 1/2±1/8" (73,0 mm) 1/2"(12,7 mm) (12,7±3,2 mm ) 2-1/4"DIA. 1/4"(6,4 mm) FACE OF (57'2 mm) SPRINKLER MOUNTING FACE OF (57,2 mm) FITTING PLATE SPRINKLER MOUNTING 1/8" FITTING PLATE �'�II (3,2 mm) n Iear, 1/8" 32 Fil MOUNTING IMM1ll l'r'e 1 MOUNTING VIzr o -E- SURFACE -_-_ SURFACE • CLOSURE SERIES 1-5/16"(33,3 mm) TY-FRB CLOSURE SERIES 1-5/16"(33,3 mm) 13/16"(20,6 mm) TY-FRB FIGURE 12 1-1/16"(27,0 mm) SERIES TY-FRB RECESSED PENDENT FIGURE 13 WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT SER/EP TY-FRB 1/2 RECESSED PENDENT T STYLE 40 RECESSED ESCUTCHEON WITH STYLEE/ECRC INCH TOTAL ADJUSTMENT 8.0 K-FACTOR, 3/4 INCH NPT 30 RECESSED ESCUTCHEON 8.0 K-FACTOR,3/4 INCH NPT pleted,to verify the integrity of the cor- rosion resistant coating. Thereafter, WRENCH annual inspections per NFPA 25 ' RECESS should suffice; however, instead of in- specting from the floor level,a randomjia WRENCH RECESS sampling of close-up visual inspec- (END"A"USED FOR r tions should be made, so as to better ^ 1/2"NPT MODELS) determine the exact sprinkler condi- tion and the long term integrity of the %corrosion resistant coating, as it may WRENCH RECESS be affected by the corrosive conditions (END"B"USED FOR O E present. 3/4"NPT MODELS) PUSH WRENCH IN TO ENSURE ENGAGEMET The owner is responsible for the in- FIGURE 14 WITH SPRINKLER spection, testing, and maintenance of W-TYPE 6 SPRINKLER WRENCHING AREA their fire protection system and de- WRENCH FIGURE 15 vices in compliance with this docu- WRENCH FIGURE 15 ment, as well as with the applicable W--TYPE 7 RECESSED standards of the National Fire Protec- facturer should be contacted relative SPRINKLER WRENCH tion Association (e.g., NFPA 25), in to any questions. addition to the standards of any other It is recommended that automatic authorities havingen- sprinklersystems p Inspection Service in accordance with stalling contractr�orlsprinklerTmanu- tested and maintained byla qualified local requirements and/or national codes. Page 10 of 10 TFP171 P/N 57 - XXX - X - XXX TEMPERATURE RATING MODEL/SIN SPRINKLER 135 330 1211=12111 TY1131 NM 155 OM 331 2.8K PENDENT(1/2"NPT) TY1231 _ 11 EINNI _ WHITE POLYESTER 175 175°F/79°C 340 TY2131 341 4.2K PENDENT(1/2"NPT) TY2231 © WHITE(RAL9010)* 200 200°F/93°C 3701126=111TY3131 CHROME PLATED 286 286°F/141°C TY3231 IIILEAD COATED 371 5.6K PENDENT(1/2"NPT) 390 8.0K UPRIGHT(3/4"NPT) TY4131 *Eastern Hemisphere sales only. 391 8.0K PENDENT(3/4"NPT) TY4231 360 8.0K UPRIGHT(1/2"NPT) TY4831* 361 8.0K PENDENT(1/2"NPT) TY4931* TABLE D PART NUMBER SELECTION SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS In no event shall TFBP be liable, in prdering Limited contract, tort, strict liability or under any other legal theory, for incidental, procedure Warranty indirect,special or consequential dam- ages,including but not limited to labor placing an order, the Products manufactured by Tyco Fire& charges, regardless of whether TFBP Whenfull name. Refer indicate the Price Building Products (TFBP) are war- was informed about the possibility of List for product completealisting Re a to Part ranted solely to the original Buyer for such damages, in no event shall bers. Num- ten(10)years against defects in mate- TFBP's liabilityexceed an amount rial and workmanship when paid for equal to the sales price. Contact your local distributor for avail- and properly installed and maintained _• _ -, • „ under normal use and service. This , - I . , Sprinkler• Assemblies with NPT warranty will expire ten (10) years • , , .r - TFBP. No , ., - Thread Connections: from date of shipment by • ��_ ..'I'► . Specify: (Specify Model/SIN), Quick warranty is given for products or corn- tic alar ouroose. Response, (specify K-factor), (specify ponents manufacturedywby companies temperature rating), Series TY-FRB not affiliated by ownership with TFBP This limited warranty sets forth the ex- (specify or Upright)Sprinkler or for products and components which clusive remedy for claims based on withpe(specifyiPendent typeof finish or coating), have been subject to misuse,improper failure of or defect in products,materi- (specify trom Table D). installation, corrosion, or which have als or components,whether the claim not been installed, maintained, modi- is made in contract, tort, strict liability fled or repaired in accordance with ap- or any other legal theory. Reccessedtd Escu Escutcheon: plor 40) Re- standards Standards the National the This warranty will apply to the full ex- tent permitted by law.The invalidity,in cessed Escutcheon with(specify*)fin- Havingstandards of Association,tr and/or the portion othis ish,es P/N (specify*). grds is any other Authoritieslsfound whole or part, of any p Jurisdiction. Materials warranty will not affect the remainder. *Refer to Technical Data Sheet TFP770. by TFBP to be defective shall be either repaired or replaced, at TFBP's sole Wrench: e nklr option. TFBP neither assumes, nor Sprinkler r ePe 6 Sprinkler Wrench, authorizes any person to assume for it, P/N 56-000-6-387. any other obligation in connection with the sale of products or parts of prod- ucts. W-Type TFBP shall not be responsible for P/N 56-850-4-001. sprinkler system design errors or inac- curate or incomplete information sup- plied by Buyer or Buyer's repre- sentatives. TYCO FIRE&BUILDING PRODUCTS,451 North Cannon Avenue,Lansdale,Pennsylvania 19446 VicFlexTM Sprinkler Fittings Series AH1, AH2 and AH4 Braided Flexible Hose Assemblies 10.85✓at ul 10.85• • Brackets: Style AB1 for suspended and hard-lid ceilings, allows Flexinstallation before ceiling tiles in place P Style AB2 for hard-lid ceilings, allows for vertical sprinkler adjustment " Style AB4 for hard-lid ceilings with hat furring channel Approvals/Listings: systems, allows for vertical sprinkler adjustment pprovals/Listings: Style AB7 for suspended ceilings and hard-lid ceilings FM us vds ILPC61 Style AB7 Adjustable for suspended and hard-lid ceilings LISTED G412024 1041-01 e�vlct�ullc P�ael+cdtion 10.01 hr more aetails. Style AB8 for hard-lid ceilings (regionally available) SStyle AB9 for hard-lid ceilings with hat furring channel roduct Description: grid systems Style AB10 for Armstrong®TechZone'"ceilings VicFlex sprinkler fittings provide sprinkler installation on suspended ceiling grids, wood or metal stud/joist or hat furring channel hard-lid ceilings utilizing a flexible, stainless steel hose and steel bracket assembly. Refer to the Installation Manual for all applicable ASTM ceiling material and installation standards. System Components • Hoses: Series AH1 Braided Hose Series AH2 Braided Hose - Series AH4 Braided Hose Assembly lengths: 31, 36,48, 60, 72790, 914, 1220, 1525, 1830mm. Note: length includes branch-line nipple and 5.757140mm straight reducer. • Sprinkler Reducers: l and 3/4"/15 and 20 mm sprinkler connections and 5.757140mm, 97230mm, 137330mm straight lengths and short, long 90° elbows. Note: The short 90°elbow is typically used with concealed sprinklers while the long 90°elbow is typically used in the installation of recessed pendent sprinklers. • Branch Connections: 1"/25mm NPT or BSPT branch line nipples for attaching to rigid pipe. 3/4720mm NPT or BSPT available for VdS. Job/Owner Engineer System No. Spec Section Location --- — Paragraph Contractor — — — — Approved Submitted By Date Date victaulic.com I VicFlex Sprinkler Fittings I AH1 I AH2 I AH4 I Publication 10.85 10.85 5839 Rev V Updated 11/2014 ©2014 Victaulic Company.All rights reserved. 1ictaujic° • victaulic.cam I VicFlex Sprinkler Fittings I AH1 I AH2 I AH4 I Publication 10.85 Technical Specifications: Material Specifications: Maximum Working Temperature: 225°F/107°C • Series AH1 Maximum Working Pressure: Flexible Hose:300-series Stainless Steel • 200 psi/1375 kPa (FM Approval) Collar/Weld Fitting:300-series Stainless Steel • 175 psi/1206 kPa (cULus Listed -Series AH2 only) Gasket Seal:Victaulic EPDM • 1600 kPa/232 psi (VdS/LPCB Approved) Isolation Ring: Nylon Connections: To branch line (inlet)via 1"/25.4 mm NPT or BSPT male Nut and Nipple:Carbon Steel, Zinc Plated thread Reducers(1/2 or 3/4'): Carbon Steel, Zinc-Plated OR To branch line (inlet)via 3/x"/20 mm BSPT male thread • Series AH2 (VdS only) Flexible Hose:300-series Stainless Steel To sprinkler head (outlet)via 1/2" or 3/4715 mm or 20 mm NPT or BSPT female thread Collar/Weld Fitting:300-series Stainless Steel Minimum Bend Radius: Gasket Seal:Victaulic EPDM • 7"/178 mm (FM Approval) Isolation Ring: Nylon • 2"/51 mm (cULus Listed -Series AH2 only) Carbon Steel, Zinc Plated • 3"/76.2 mm (cULus Listed -Series AH1 only) Nut and Nipple: • 3776.2 mm (VdS/LPCB Approved) Reducers(1/2 or 3/4'): Carbon Steel, Zinc-Plated Maximum Allowable Sprinkler K-Factors: • Series AH4 • FM (1/2"/15mm reducer) K5.6/8,1 (S.I.) Flexible Hose:300 series Stainless Steel (3/a"/20mm reducer) K14.0/20,2 (S.I.) • cULus(1715mm reducer) K8.0/11,5(S.I.) Collar/Weld Fitting: 300-series Stainless Steel (3/4"/20mm reducer) K14.0/20,2 (S.I.) •VdS/LPCB (1"/15mm reducer) K5.6/8,1 (S.l.) Gasket Seal: EPDM per ASTM D2000 (3/4"/20mm reducer) K8.0/11,5(S.I.) Isolation Ring: N/A Nut and Nipple:Carbon Steel, Zinc-Plated Reducers(l or 3/4"): Carbon Steel, Zinc-Plated • Brackets: Carbon Steel, Zinc-Plated 10.85 5839 Rev V Updated 11/2014 ©2014 Victaulic Company.All rights reserved. ictaulid victaulic.cam • victaulic.com I VicFlex Sprinkler Fittings I AH1 I AH2 I AH4 I Publication 10.85 ®us FRICTION LOSS DATA: LISTS -Series AH2 Braided Hose with Straight 5.75"Reducers -Style AB1 and AB10 Brackets Series AH2 Hose Length of Stainless Steel Equivalent Length Maximum Number of of 1733.7mm 90°Bends at 2751mmFlexible Hose Outlet Size Sch.40 Pipe(C=120) Bend Radius inches inches/type feet/meters 31 a '/z/Straight 16/4.9 3/4/Straight 4 � --17/5.2 36 /z"/Straight 4 - 21/6.4 3/a"/Straight — -� 5 23/7.0 48 1/2"/Straightraight I — 5 - —— L_.- 32/9.8 1._ _ 8 3/4"/Straight .__... 37/11.3 Yz/Strai ht 8 60 __-..9_.._.._ 46/14.0 3/4'/Strai ht -__-- 10 � 2-- _--- ---- 46/14.0 1 /z"/Strait ht 55/16.8 10 72 f --- 12 3/a"/Straight 53/16.2 — 12 Series AH2 Braided Hose Equivalent Length Design Guide Equivalent length values at various numbers of 90 degree bends at 2751mm center line bend radius Length of Stainless 1 Steel Flexible Outlet 1 2 3 14 5 6 7 8 9 3 11 12 Hose Size Bend Bends Bends I Bends Bends Bends Bends ! Bends Bends Bends Bends Bends inches inches '/z" ' 8.5/2.6 1 11.0/3.4 13.0/4.0 H6.0/4 9 N.A N.A N.A N A_. - 31 3/4' 10.0/3.0 12.5/3.8 14.0/4.3 17.0/5.2 N.A N.A-�— I N.A N.A N A N A NA 36 Yz' 13.5/4.1 16.0/4.9 18.0/5.5 4 19.0/5.8 21.0/6.4 - N.A N.A N.A N.A N.A NN.A .A 3/a' 14.0/4.3 17.0/5.2 19.5/5.9 ' 20.0/6 1 23.0/7 0 N.A N A -"- N A ' - NA N.A N.A N.A N.A '� 15.5/4.7 17 0/5.2 19 5/5.9 20.0/6 1 21.0/6 4 22.0/6 7 28.0/8.5 32.0/9.8 N.A * N.A N.A 48 17.0/5.2 19.0/5.8 21.5/6.6 24.5/7.5 26.0/7.9 27.0/8.2 30.0/9.1 37.0/11.3 N.A 1 N.A N.A '/zN.A 60 " 4 21.5/6.6 24.0/7.3 27.0/8.2 28.5/8.7 30.0/9.1 31.0/9.4 37.0/11.3 42.0/12.8 44.0/13.4 46.0/14.0 N.A N.A -__3/4" 23.0/7.0 24.0/7.3 28.0/8.5 1 29.5/9.0 30.5/9.3 31.0/9.4 38.0/11.6 42.0/12.8 44.0/13.4 46.0/14.01 N.A 1 N.A 72 - '/z" 30.0/9.1 32.0/9.8 36.5/11.1 137.5/11.4 40.5/12.5 41.0/12.8 42.0/12.8146.0/14.0 49.0/14.9. 52.0/15.8 154.0/16.5 55.0/16.8 3/4" 1 32.0/9.8 32.5/9.9 .35.0/m7;35.5/10.8 40.0/12.3 40.5/12.3 41.0/12.5 146.0/14.0 50.0/15.2 51.0/15.5]52.0/15.8 53.0/16.21 Note:Values for use with 5.75"straight reducers. How to use this Design Guide: 1 For some systems,it may be advantageous for the designer to calculate the system hydraulics using shorter equivalent lengths associated with fewer than the maximum allowable number of bends.In this case,the designer may select a design number of bends for the job and use the associated equivalent length from the design guide to determine the system hydraulics. 2 It is possible that the actual installed condition of some of the flexible drops may have more bends than the designer selected.When this happens,the design guide may be used to find equivalent lengths based on the actual installed number of bends for particular sprinkler installations.The system hydraulics can be recalculated using actual equivalent lengths to verify the performance of the system. 10.85 5839 Rev V Updated 11/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 3 ictaulic, victaulic.com I VicFlex Sprinkler Fittings I AH1 I AH2 I AH4 I Publication 10.85 C®Us FRICTION LOSS DATA: -Series AH1 Braided Hose with Straight 5.75"Reducers LISTED -Style AB1 and AB10 Brackets Series AH1 Hose Maximum Equivalent Length Number of StaLength of j of 1'733.7mm 90°Bends at 3°/76.2mm Flexible Steelosj Sch.40 Pipe(C=120) Bend Radius Flexible Hose � Outlet Size inches/type feet/meters _-- inches + � �/z — 8/15 —_-_--- _ ---- "/Strai ht 52 3 —__ 31 3-- 55/16.8 4 63/19.2 4 �/i'/Straight 36 I3/4"/Straight ht -.-- 66/20.1 —.._.... 9 — 78/23.8 4 r/z/Strai.ht - 80/24.4 48 4 '/a"/Straight 4 __-----.__ __ -88/26.8 _.. 1/2"/Straight i-- 90/27.4 60 L 3/a'/Strai ht — — ig-- 112/34.1 — --t 5 Yz°/Straight __— ? 5 72 i_ ----- 3/a"/Straight 118/36.0----- - _-------'------------- Series AH1 Braided Hose Equivalent Length Design Guide Equivalent length values at various numbers of 90 degree bends at 3"/75mm center line bend radius Length of+! Stainless) Steel Flexible Outlet 1 2 3 4 5 Hose ; Size Bend Bends Bends Bends Bends inches inches 1/2N.A N.A " 32 42 ...._._52 31 33 4 55 N.A N.A /2 33 43 53 63 N.A. 36 3/4' 36 46 56 66 N.A 1" 46 57 68 78 N.A 48 3/4, 51 60 71 80 N.A " 56 67 77 _.. 88 N.A 60 60 h_-.____— 58 69 80 90 N.A -— -4-• y2" ...- 69 79 91 102 112 72 I 33/a_ —73 — 84 95 106 118 Note:Values for use with 5.75"straight reducers. How to use this Design Guide: 1 For some systems,it may be advantageous for the designer to calculate the system hydraulics using shorter equivalent lengths associated with fewer than the maximum allowable number of bends.In this case,the designer may select a design number of bends for the job and use the associated equivalent length from the design guide to determine the system hydraulics. ble drops may ve more ends n 2 It is guide mayy be used toafindal equivalennt lengths based on the actualn of some of the iinstalled numberofof bends for particular spe anker installationr selected.s.The hen system hydraulics is happens,thecan design recalculated using actual equivalent lengths to verify the performance of the system. 10.85 5839 Rev V Updated 11/2014 ©2014 Victaulic Company.All rights reserved. jCtdU�iC victaulic.com 4 victaulic.com I VicFlex Sprinkler Fittings I AH1 I AH2 I AH4 I Publication 10.85 FM FRICTION LOSS DATA: ------ ------ —____ , -Series AH1,AH2 and AH4 Braided Hose -Various brackets specific to hose Series_AI11 Hose Series AH2 Hose __ Series AH4 Hose For use with Style AB1,AB2, For use with Style AB1,AB2, j AB4,AB7,AB7 Adj.,AB8,AB9 AB4,AB7,AB7 Adj.,AB8,AB9 For use with Style AB1,AB7,AB8, and AB10 VicFlex Brackets and AB10 VicFlex Brackets Length of T__._ .--___--- _and AB9 VicFlex Brackets Stainless Maximum .._-- Equivalent I Number of Length of 90°Bends at Maximum Maximum Steel Equivalent Number j Equivalent Number Length of of 90°Bends at I Length of of 90°Bends at Flexible Sprinkler Outlet 1733.7mm j 77178mm Bend 1733.7mm Hose* K-Factor Size Sch.40 Pipe I Radius 71733.7mm 7'%178mm Sch.40 Pipe Bend Radius Sch.40 Pipe Bend Radius inches Imperial/S.I. inches/type feet/meters feet/meters feet/meters 31 5.6/8.1 _'/z"/Straight 53.8/16.4 �_.. 2 ( 23.5/7.1 Yz"/90"Elbow 53.8/16.4 2 j 20.6/6.3 36 5.6/81 ''/z'/Straight 63.7/19.4 23/7.0 217/6.6 2 27.8/8.5 _ 'h'/90°Elbow 2 29.7/9.0_ 63.1/192 -.4 2 _ 27.7/8.42 '/z'/Strai.ht __. __-------...._.-- _ _29.8/9.0 5.6/8.1 87.9/26.8 I 38.2/11.6 h"/90°Elbow 85.8/26.1 i 3 _27.5/8.3 48 37.4/11.4 3 3 60 "/Strai ht 112.2/34.1 i • 29.2/8.9 5.6/8.1 @ 42.4/12.9 'h'/90"Elbow 108.4/33.0 4 4 4 _ 35.7/10.3 - 72 1/2"/Straight 136.5/41.6 43/13.1 372/11.3 5.6/8 1 Yz"/90 Elbow 13 4 46.6/142 131.1/39.9 45 9/14.0 4 - 48.5/14.7 31 8.0/11 5 34'/Straight 44.4/13.5 -_47 5/14.5 20.7/6.3 3/a"/90°Elbow 2 13.3/4.-- 47.6/14.5 2 2 36 8.0/11 5 3/a"/Straipht 55.6/16.9 20.5/6.2 — g /a/90°Elbow 57.5/17 5 2 25.0/7.6 - 2 I 21.7/6.6 3 ., 3_. 24.6/7.5 8 2 48 8.0/11 5 /a/Straight 82.8/_25 2 f 22 4/6.8 I 3 35.5/10.8_._. � 3/a'/90°Elbow 81.7/24 9 I 3 ; 21.2/6.4 34.7/10.63 3/4'/Strai ht 110.1/33.5 - --22.2/6.7---- 60 8.0/11.5 g 39.6/12.1 3/4'/90°Elbow 4 27.9/8.5 - 105.9/32.2 I 40.1/12.2 44 72 8.0/11.5 3/473!!!!!9_11t_ 137.3/41.8 fi _ 28.9/8.8 43.5/13.2 3/a"90°Elbow 130.2/39.7 i 4 38 8/11.8 - 45.2/13.7 -- 4 4 _ 31 11.2/16 1 -3�4,/Straight 45.5/13.8 17.8/5.4 39.4/12.0 '/"/90°Elbow 47.1/14.3 2 2 16.4/5.0 36 11.2/16.1 3/a"/Straight ---- 18/5.52 66.3/20 2 19 9/6.1 3/a"/90"Elbow --- ----.--; 2 22.2/6.7 -- ------- 57.5/17.5 2 21.7/6.6 48 11.2/16.1 3/a"/Strai.ht 82.7/25.2 22.1/6.7 24.2/7.4 2 3/a"/90°Elbow 3 32.9/10.0 82.8/25.2 3 28.5/8.7 _ 32.1/9.8 60 11.2/16.1 3/a"/Straigh5 109.1/33.2 29.9/9.1 3 J q 36.8/11.2 3/a/90 Elbow 108.1/32 9 4 j_ - 34.7/10.5 3 37.1/11.3 30. 4 3/a"/Strai.ht 135.5/41.3 30 3/9 2 72 11 2/16.1 40.5/12.3 /a'/90°Elbow 133.4/40.6 i 4 38.6/117 41.9/12.7 31 14.0/20.2 3/a"/Strai.ht 44.3/13.5 - ------ 38.6/11.7 4 3/a"/90°Elbow46.4/14.12 14.9/4.5 16.3/5.0 —15.5/4.72 2 2 3/a"/Strai•ht 19.9/6.1 36 14.0/20.2 55.5/16.9 - 19.4/5.9 3/a"/90°Elbow 56.7/17.3 2 21.8/6.7 19.6/5.9 2 48 14.0/20.2 3/a/Straight 83.0/25 3 24.2/7 4 2 3/a'/90°Elbow 82.1/25 0 • 3 30 3/9.2 3 28.3/8.6 60 140/20.2 3/a'/Strai.ht 29.5/8.9 3 3 �_-_110.4/33 6 33.9/10.3 29.9/9.1 /a/90°Elbow 107.5/32.7 4 f 4 34.9/10.6 34.1/10.4 3/a/Straight 137 9/42.0 _-- ------'- 30.3/9 2 - 72 14.0/20.2 4 37.5/11.4 4 3/a/90°Elbow 132.8/40.4 4 41.5/12 6 _ 4 FM Notes: 38.6/11.7 Series AH1,AH2 and AH4 have been tested and Approved by FM Global for use in wet,dry and preaction systems per NFPA 13,13R,and 13D and FM data sheets 2-0,2-5,and 2-8.FM 1637 and Vds standards for safety include,but are not limited to,pressure cycling,corrosion resistance,flow characterisitics,vibration resistance,leakage,mechanical and hydrostatic strength. Differences in equivalent lengths are due to varying test methods,per FM 1637 and VdS standards.Refer to these standards for additional information regarding friction loss test methods. EXAMPLE:A 48-inch hose installed with two 30°bends and two 90°bends at a 7-inch bend radius is permitted and considered equivalent to the data in the table shown above.In this example,the total number of degrees is 240°,which is less than the allowable 270°. 10.85 5839 Rev V Updated 11/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 5 NIctauliicr victaulic.cam I VicFlex Sprinkler Fittings I AH1 I AH2 I AH4 I Publication 10.85 - ® FRICTION LOSS DATA: -Series AH1,AH2 and AH4 Braided Hose -Style AB1,AB2,AB4,AB7,AB7 Adj.,AB8,AB9,and AB10 Brackets Series AH1 Hose Series AH2 Hose Series AH4 Hose 1 Equivalent Length of Equivalent Length of Equivalent Length of steel pipe according to steel pipe according to steel pipe according to EN 10255 DN 20 EN 10255 DN 25 EN 10255 DN 25 Maximum Number (26,9 x 2,65)and (33,7 x 3,25)and (33,7 x 3,25)and of 90°Bends at Outlet relating to a flow relating to a flow relating to a flow 3"/76.2m uam Bend Steele StainlessSize velocity of 5 m/s velocity of 5 m/s velocity of 5 m/s Rad Flexible xibblle HHose I mm/inches meters/feet meters/feet meters/feet mm/inches i- _tYPe_ _.-.__. - - — — i 15mm/'/z"/Strai•ht5.5/18.0 5.5/18.0 3 4.0/12.9 -_ 790/31 I 20 mm/3/4"/Strai•ht 3 15mm/1h /Strawht 4.6/150 6.4/21.0 6.4/21.0 915/36 20 mm/'/a"/Strai ht ---- --� 3 -- - 8.5/27.9 220-4 8.5/27.9 1-- 6.1/20.0 6,1/200 2222__-2222-- 1220/48 I 20 mm/'/4"/Strai ht.__ 4 15mm/1h"/Straight 7.6/25.0 10.7/35.1 10.7/35.1 1525/60 20 mm/3/4"/Strai•ht • —2222 �— 12.8/42 0 4 L_ 15mm/1/z"/Strai,ht 9.2/30.0 12.8/42.0 1830/72 1 20 mm/3/4"/Stratght ----------------- VdS Ceiling Manufacturers List AB1,AB2,AB7,AB10 AB4/9 ABS 1.AMF1.Hilti 2.Armstrong No specific approval 2.Knauf 3.Chicago Metallic 2.Lafarge 4.DiplingDrl4.Lindner 5.Geipel 5.Rigips 6.Geipel 7.Gema-Armstrong 8.Hilti 9.Knauf 10.Lafarge 11.Linder 12.Odenwald 13.Richter 14.Rigips 15.Rockfon Pagos 16.Suckow&Fischer 17.USG Donn LPCB FRICTION LOSS DATA: -Series AH2 Braided Hose -Style AB1 Bracket — --_---------" -"--� Series AH2 Hose j Series AH2 Hose Equivalent Length Equivalent Length of steel pipe of steel pipe Length of according to EN Maximum according to Maximum 10255 DN 25 of Stainless of EN 10255 DN 20 Number of Stainless j (33,7 x DN and Number at St Steel Steel relating to a flow 90°Bends a Steel i (26,9 x 2,65)and 90°Bends at Flexible Outlet FlexibleHoei et relating to a flow 3"nd iu Hose Size velocity of 5 m/s Bend Radius Hose j Size velocity of 5 m/s Bend Radius mm/inches mm/inches/type meters/feet mm/inches mm/inches/type a meters/feet 22 -----_ 15mm/1h"/90°Elbow 14.4/47.2 2 15mm/1/2:11_Strai ht 2 790/31 20 mm/Y4'/90°Elbow .2 790/31 — . h 12.65/41.5 20 mm/3/4'/Strai•ht 15mm/1 "/90°Elbow 14.3/46.9 3 915/36 20mm/Yz'/Straight 14.8/48.6 20 mm/3/4 /90°Elbow _—_--_ _ --- 915/36 _ 3 3 20 mm/3/a'/Straight ____--- --2222-- 15mm/1/z'/90°Elbow 15.3/50.2 1220/48 b 3 15mm/1 "/Strai ht 15/49.2 _ 20 mm/3/4'/90°Elbo - 1220/48 20 mm/3/4"/Strai•ht 15mm/1/z"/90°Elbow 16.0/52.5 3 h 15mm/1h"/Strai ht I 3 1525/60 20 mm/3/a"/90°Elbow 1525/60 15.3/50.2 __ I 20 mm/3/4"/ .19.1 ht - 15mm/1/z"/90 Elbow 17,1/56.1 -- 3 1830/72 t 15mm/Yz'/Straight 17.5/57.4 3 20 mm/'/a /90 Elbow 1830/72 �20mm/3/4"/Straht --- — — — __ -=22 22-2222-- \iCt:aUliCr 10.85 5839 Rev V Updated 11/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com e victaulic.cam I VicFlex Sprinkler Fittings I AH1 I AH2 I AH4 I Publication 10.85 Product Details-Series AH1 Braided Hose — — Series AH2 Braided Hose Series AH4 Braided Hose Item Description 1 Flexible Hose 4 O p 2 Q p Isolation Ring(Series AH1 and AH2 only)_ �imuliiiiilii iiii ul imiiill3 Gasket _ if�ll 5 Nut �. A Branch Line NJ��Ie g 6 Braid Collar/Weld Fitting Hose Length Dimensions 8 Sleeve(AH2 Only) ----__..__ Hose Length A i.._.____- B inches inches mm inches __---. mm mm 31/790 25.25 31/790 36/915 T 31.25 36/915 48/1220 1 _ 42.25 48/1220 60/1525 54.25 60/1525 72/1830-- --_ --- 66.25 72/1830 Standard I IIIIDl illillellIIIIl lilll I'IiIIII,hi/I I ull�l idlnidi Ihlh Im4oll 5.757140 mm straight reducer Optional Ili punyillIlloom vii I1ii III1'1111 11111i19111d1�ll'ililiillll�I� 6 un�la a lohdhlluli�� 9.07229 mm straight reducer lifillilfmrin CH III 4111111i f IL — r 13.0"/330 mm straight reducer 2.62'! 2.62"/ —° 665 mm 66.5 mm 11111 T iMilk I 4.83"/ 630"/122.7 mm 160.0 mmEff N MAN MIN Short 90°elbow reducer Long 90°elbow reducer Note:The Short 90°elbow reducer is typically used with concealed sprinklers while the longer 90 elbow is typically used in the installation of recessed pendent sprinklers. • 10.85 5839 Rev V Updated 11/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 7 ctaulIC° victaulic.com I VicFlex Sprinkler Fittings I AH1 I AH2 I AH4 I Publication 10.85 VicFlex Brackets Style AB1 ID . • Suspended Ceilings .,•-frti 1 • Hard-Lid Ceilings(FM Only) . I Item III- Description 12 1 24"/6p1a tOema tme do ri_4B8e"/e12.21c9e mntmerSBqraucakreetBar* 11 I," C @ *Both sizes FM/VdS/LPCB approved,cULus listed tl'," ,. is 1;1/ Style AB2 t) • Hard-Lid Ceilings 9 Item 4 Description 4,01 \• ,,,,,,lo .. ,, :1;11'...t.'"Ii7' --;III1-:-I--...2-- 1 ' 24"/610mm or 48"/1219mm S.uare Be._ 2 ' Patent-Pendin9 adjustable Center bracket 0 4 1 0 or 3 ' End Bracket — *Both sizes FM/VdS approved. Note: 1/22"/4mm hex key required for adjustment 0 . ,1* •14 to • Style AB4t .. • Hard-Lid Ceilings with Hat furring channel f grid system 1 -7- Item 1 1 —I- Description I' "•••.., - 24"/610mm or 48"/1219mm Square Bar* -I '•4 2 i pet_ 3 I End Bracket for Hat Furrin.Channel p Both sizes FM/VdS approved. 4ki•,_,-6- Note:5h2"/4mm hex key required for adjustment 1 C .:31 11 1> 1 ic . . 10.85 5839 Rev V Updated 11/2014 ©2014 Victaulic Company.All rights reserved. ctaulact ViCulic.com 8 \i th • victaulic.com I VicFlex Sprinkler Fittings I AH1 I AH2 I AH4 I Publication 10.85 VicFlex Brackets Style AB7 • Suspended Ceilings le • Hard-Lid Ceilings Item ' Description '' Egi- 24"/610mm or 48/1219mm Square Bar* -- 2 3 Patented 1-Bee"Center Bracket — _ End Bracket *Both sizes FM/VdS approved. ;4�N` . Style AB7 Adjustable • Suspended Ceilings © ..i • Hard-Lid Ceilings Item Description , 1 700mm or 1400mm Square Bar* r Patented 1-Bee"Center Bracket 3 j End Bracket(adjustable) Both sizes FM and VDS approved. ii-' O Style AB8 , • Hard-Lid Ceilings © °\� v�. � 6 Item Description 1 700mm or 1400mm Square Bar* 2 Patented 1-Bee'®Center Bracket 3 ---- End Bracket(adjustable) *Both sizes FM/VdS approved. Si` O Style AB9 OD • Hard-Lid ceilings with Hat furring channel grid system © \+ Item I � ► � Description I 1 24"/610mm or 48"/1219mm Square Bar* 2 iPatented 1-Bee"Center Bracket 3 I End Bracket for Hat Furrin�Channel �, Both sizes FM/VdS approved. i =�y O Style AB10 4 • Suspended ceilings � ,► •Armstrong®TechZone'" © �\ © � O �item Description ? 6'/152mm Square Bar* y��� 1 . L Patented 1-Bee"Center Bracket i 3___I_______ End Bracket `-X *FM/VdS approved,cULus listed. 10.85 5839 Rev V Updated 11/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 9 Jctauljc° victaulic.com I VicFlex Sprinkler Fittings I AH1 I AH2 I AH4 I Publication 10.85 Braided Hose Assembly Suspended Ceiling Grid with Recessed Sprinkler -Clearances above ceiling tile at various center-line bend radii /---I i L. Hose Clearance Chart A __-- —___ --_._.__—_— —_ / See char Dimension inches/mm —— 4/100 5/125 6/150 7/175 I •IIT• Minimum Bend 2/50 3/80 A It" Bracket assembly Radius R" —_ ! See styleAel Minimum"A" 10.75/273 11.75/298.511 12.75/324 13.75/349 14.75/375 15.75/400 1■ _ J I-1 1t! 4.4 1,IIi I j 113 mm / \! 't'k 1/e/16 mm tki II ical ! /"I -tip li = ceiling the!i 1 ip�l 17'/43 mm i niI 1• 11 •! Typical ceiling god %At�Dii9, �I,'` ,1%��'l9���� 15 ���%/". In ceiling face See note 24"/610 mm or 4871219 mm on Center V2707 3/4"/19 MM MAX.RECESS V2707 3/4"/19mm Max.Recess Suspended Ceiling Grid with 90°Elbow(Long) 1I�III�I I I Bracket assembly I _„_,_,-• Style AB1 I ,,�1r 11 Hose Clearance Chart i Iii I - =s _ - see chart i{ q 4°/ inches/ sI I 3 mm 1; j Dimension mm \! }{ _ E.— 6mm 11 I 8/200 �' A Min. i e1/16 mle !,I! II�I'! 17"/43 mm ��'y I•�'RI � Note: Style AB1 and Series AH2 figures shown. Ty 1alceilinm 4t,, I,._ �l ������� Variations of ceiling grids, sprinkler heads, brackets, r,. Finished and hoses are permitted but may result in clearance See note e,ling face 24°/610 mm or 48"/1219 mm on Center differences from the figures above. V2707 3/"/19mm Max.Recess 10.85 5839 Rev V Updated 11/2014 ©2014 Victaulic Company.All rights rriCtaluliC�'esserved. victaulic.c0m • victaulic.com I VicFlex Sprinkler Fittings I AH1 I AH2 I AH4 I Publication 10.85 Series AQB Braided Hose Assembly — --- Suspended Ceiling Grid with Hat Furring Channel Hose Clearance Chart Dimension inches/mm 7 / Minimum Bend Radius"R" 2/50 3/80 i 4/100 5/125 6/150 7/175 % R ee Chart Minimum A 10.3/262 111.3/287 12.3/313 13.3/338 14.3/363.5 15.3/389 riii n 1 / See chart 1 ,ILII — V. ��� Ile) III[ S ]7 99 mm r 1 ` \ ee Note a. .I . � rota V ` s; :3` + 1g .1' IVA V27081/2"/12.7mm Max. Recess Suspended Ceiling Grid with 90°Elbow(Short) 'l �♦lllllsHose Clearance Chart inches/ CO Dimension mm 1 "' • A Min. 8/200 i a / I r�_io I / n 99 mm See Chart \ se NoteIII Note: Style AB9 and Series AH2 figures shown. I f/ I ,I•IIS.' i'-' 7,"* I• - V Variations of ceiling grids, sprinkler heads, brackets, rr 1� and hoses are permitted but may result in clearance \ !`II,� ' differences from the figures above. \ V38021/2"/12.7mm Max.Recess 10.85 5839 Rev V Updated 11/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 11 ✓CtauliC' • victaulic.com I VicFlex Sprinkler Fittings I AH1 I AH2 I AH4 I Publication 10.85 Flexible Hose In-Plane Bend Characteristics ONE BEND TWO BENDS zX zX i Minimum Minimum - - Minimum I bend radius ' bend radius bend radius Minimum I OR OR bend radius I``90° —_`\ 1 Minimum l Minimum bend radius Minimum bend radius bend radius 1 Minimum , bend radius \N---_, \ Minimum bend radius Note:For out-of-plane(three-dimensional)bends care must be taken to avoid imparting torsional stress on the hose Model Number Correlation �04vt z�. T AquaFlex®Designation � � �$ �KK. . VicFlexi - - s ,,, ' !„ � Designation 1, Series AH4 Outlet j Series AQB Series AFB It is the responsibility of the system designer Hose Size j HOS Hose • Assembly inches Assembly Assembly to verify suitability of 300-series stainless steel - — ,/2 AQB31HLD AFB31HLD flexible hose for use with the intended fluid AH4-31 3/4 AQB31TLD AF631TLD media within the piping system and external y2 AQB36HLD AFB36HLD AH4-36environments. 3/4 AQB36TLD AFB36TLD 1/2 AQ648HLD AF648HLD__.. • The effect of chemical composition, pH level, AH4-48 3/4 AQB48TLD AFB48TLD operating temperature,chloride level,oxygen 1/2 _ ; AQB6OHLD AFB6OHLD level,and flow rate on 300-series stainless steel AH4-60 � _ 3/4_ AQB6OTLD AFB6OTLD flexible hose must be evaluated by the material y2 AQB72HLD _AFB72HLDspecifier to confirm system life will be AH4-72 /4 AQB72TLD AFB72TLD — acceptable for the intended service. Failure to follow these instructions could cause product failure,resulting in serious personal injury and/or property damage. ----- - —— Note InstallationThis IR-VICFLEX-AB7,1 oral-VICFLEX- AB8 for the product you are iins allling.Handbooks are to be nstalled shall iaccordance with ccurrent Victaulic in tallation/assemblyinstructions.by Victaulic or to Victaulic specificatons.All products included with each shipment of Victaulic products for complete installation and assembly Victaulic reserves the right to change product specifications,designs and standard data,and are available in PDF format on our website at www.victaulic.com. equipment without notice and without incurring obligations. Trademarks Warranty Refer to the Warranty section of the current Price List or contact Victaulic for details. Victaulic and VicFlex are registered trademarks of Victaulic Company. 10.85 5839 Rev V Updated 11/2014 ©2014 Victaulic Company.All rights reserved. ‘iCt9UliC victaulic.com 12