Report (58) 6,5Acy) - 6a25-- ttiCe Worldwide Fire Protection ( Contacts www.tyco-fire.com Products RAPID RESPONSE Series LFII Residential 4.9 K-factor Concealed Pendent Sprinkler Flat Plate, Wet Pipe and Dry Pipe Systems General The Series LFII Residential Concealed Pendent Sprinklers (TY3596) has Description been designed with heat sensitivity and water distribution characteristics -- TYCO RAPID RESPONSE Series LFII proven to help in the control of residen- Residential 4.9K Concealed Pendent tial fires and to improve the chance for Sprinklers (TY3596) are decorative, occupants to escape or be evacuated. fast response,fusible solder sprinklers The Series LFII Residential Con- designed for use in residential occu- cealed Pendent Sprinklers (TY3596) pancies such as homes, apartments, are shipped with a Disposable Pro- dormitories, ro dormitories,and hotels. tective Cap. The Protective Cap is s ' The cover plate assembly conceals temporarily removed for installation, the sprinkler operating components and then it can be replaced to help above the ceiling.The flat profile of the protect the sprinkler while the ceiling NOTICE cover plate provides the optimum aes is being installed or finished.The tip of theticallyappealing sprinkler design. the Protective Cap can also be used The Series LFII Residential Concealed pp g pto mark the center of the ceiling hole Pendent Sprinklers(TY3596)described In addition, the concealed design of into plaster board, ceiling tiles, etc. herein must be installed and main- the Series LFII Residential Concealed by gently pushing the ceiling product tamed in compliance with this docu- Pe dent Sprinklers(TY3596) provides against the Protective Cap. When the ment and with the applicable standards 1/2 inch(12,7 vertical adjustment. ceiling installation is complete the Pro- of the National Fire Protection Associa- This adjustmentnt provides a measure tective Cap is removed and the Cover tion(NFPA),in addition to the standards flexibi!it,, when cutting fixed sprinkler Plate Assembly installed. of any authorities having jurisdiction. drops. Failure to do so may impair the perfor- The Series LFI! Residential Concealed Dry Pipe System Application mance of these devices. Sprinkiers are intended for use in the The Series LFII Residential Concealed owner is responsible main - approved scenarios: Pendent Sprinklers offers a laboratory Theein theirefire psiblefor system option for designing dry pipe gprotectionY • wet and dry pipe residential sprin- residential sprinkler systems,whereas, and devices in proper operating con- fider systems for one- and two-fam- most residential sprinklers are labora- dition. Contact the installing contrac- i!y dwellings and mobile homes per tory approved for wet systems only. tor or product manufacturer with any NFPA 13D Through extensive testing, it has been questions. • wet and dry pipe residential sprinkler determined that the number of design Sprinkler systems for residential occupancies sprinklers (hydraulic design area) for p up to and including four stories in the Series LFII Residential Concealed height per NFPA 13R Pendent Sprinklers (TY3596) need Identification • wet and dry pipe sprinkler systems not be increased over the number of r thearesidentialryipeportionsinkerf ans design sprinklers (hydraulic design Number (SIN) fooccupancy per NFPA 13 area)as specified for wet pipe sprinkler p y systems,as is accustomed for density/ TY3596 area sprinkler systems designed per NFPA 13. Consequently,the Series LFII Residen- tial Concealed Pendent Sprinklers offer r the features of non-water filled pipe in IMPORTANT addition to not having to increase the Always refer to Technical Data number of design sprinklers(hydraulic Sheet TFP700 for the "INSTALLER design area) for systems designed to WARNING"that provides cautions NFPA 13, 13D, or 13R. with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and installation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 6 FEBRUARY 2015 TFP442 TFP442 Page 2 of 6 BODY 1 g SEALING WRENCH it (1/2"NPT) , ' ASSEMBLY RECESS CAP r I /A—PO—,-.7- r! SPRINKLER �troviiir.� I •4r7/" �`'� WRENCHING till t �� r' AREA SADDLE l 1: PUSH WRENCH SUPPORT 1 \ COMPRESSION IN TO ENSURE CUP WITH \ SCREW ENGAGEMENT ROLL FORMED I WITH SPRINKLER THREADS WRENCHING AREA 4 LEVER FIGURE 2 17D S W-TYPE 18 GUIDE .y m I SPRINKLER WRENCH SOLDER LINK ELEMENT GUIDE PIN HOUSING _ _ __ DEFLECTOR E_- _� r_ : (OPERATED DEFLECTOR -- POSITION) SPRINKLER/SUPPORT CUP ASSEMBLY THREAD INTO I I RETAINER SUPPORT I WITH THREAD CUP UNTIL J I DIMPLES MOUNTING \ 0 O SURFACE IS J FLUSH WITH CEILING EJECTION 1 SPRING i� ="' J SOLDER- COVER PLATE/RETAINER COVER TAB ASSEMBLY PLATE FIGURE 1 RAPID RESPONSE SERIES LFII RESIDENTIAL CONCEALED PENDENT SPRINKLER(TY3596) 2-1/2"DIA. SPRINKLER- (63,5 mm) 1/2"(12,7 mm) FACE OF SUPPORT CUP 1/2" THREADED SPRINKLER ASSEMBLY NPT ADJUSTMENT FITTING \— I OPERATED i �i SPRINKLER'----.--... ..,..... " I— 1-7/8"±1/4" PLATE — (47,6 mm COVER Allis ____ ii, — I I I 1/8"GAP 6,4 mm) RETAINER p r �� (3,2 mm) ,____. .. .. .. .. . . , .___ _Ji i L. COVER- SPRINKLER- MOUNTING 7/8 (22'2 mm) I I RETAINER SUPPORT CUP 3/16" _ SURFACE \ 1-1/8"(28,6 mm) __I•���•I_ ASSEMBLY ASSEMBLY (4,8 mm) 3-3/16" DIA. _ DISPOSABLE DEFLECTOR IN (81,0 mm) TIP PROTECTIVE CAP OPERATED POSITION FIGURE 3 RAPID RESPONSE SERIES LFII RESIDENTIAL CONCEALED PENDENT SPRINKLER(TY3596) INSTALLATION DIMENSIONS/PROTECTIVE CAP/ACTIVATED DEFLECTOR TFP442 • Page 3 of 6 Dry Pipe System Water Delivery Technical Design Criteria When using the Series LFII Residen- Data TYCO RAPID RESPONSE Series LFII tial Concealed Pendent Sprinklers Residential Concealed Pendent Sprin- (TY3596)in dry pipe sprinkler systems, Approvals klers(TY3596)are UL and C-UL Listed thee time for water deliverytm must not pp exceed 15 seconds for the most remote UL and C-UL Listed for installation in accordance with this operating sprinkler. NYC Approved under MEA 44-03-E-2NSF section. Certified to NSF/ANSI 61 Obstruction to The TYCO RAPID RESPONSE Series LFII Note: When conditions exist that are Water Distribution Residential Concealed Pendent Sprinklers outside the scope of the provided cri S rinklers are to be located in accor- are only Listed with the Series LFII Con- teria, refer to the Residential Sprinkler with the rules of cealed Cover Plates having a factory-ap- Design Guide TFP490 for the manu- dance twit3D, 13R,te and13 obstructionaarules of plied finish. facturer's recommendations that may NFPA Cover Plates can be ordered by following be acceptable to the authority having le for residential sprinklers as well as with the instructions in the Ordering Procedure jurisdiction. the obstruction criteria described within section. the Technical Data Sheet TFP490. System Types Maximum Working PressurePer the UL Listing, wet pipe and dry Operational Sensitivity 175 psi(12,1 bar) pipe systems may be utilized. Per the The sprinklers are to be installed rela- Discharge Coefficient C-UL Listing, only wet pipe systems tive to the ceiling mounting surface as K=4.9 gpm/psi '(70,6 Ipm/bar1t2) may be utilized. shown in Figure 3. Temperature Rating Refer to Technical Data Sheet TFP485 Sprinkler Spacing 160°F(71°C)Sprinkler with about the use of residential sprinklers in The minimum spacing between sprin- 139°F(59°C)Cover Plate residential dry pipe systems. klers is 8 feet (2,4 m). The maximum Vertical Adjustment spacing between sprinklers cannot Ceiling 1/2 inch(12,7 mm) Typesexceed the length of the coverage area Smooth flat horizontal, or beamed, or hydraulically sloped, in accordance with the 2013 (Ref. Table A or B) being ydraulicall y Refer to Ordering Procedure section. Edition of NFPA 13D, 13R, or 13 as calculated(e.g.,maximum 12 feet for a Physical Characteristics applicable. 12 ft.x 12 ft.coverage area, or 20 feet Body Brass for a 20 ft.x 20 ft.coverage area). Cap Bronze Hydraulic Design The Series LFII must not be used Saddle Brass (NFPA 13D and 13R) in applications where the air pres- Sealing Assembly Beryllium Nickel For systems designed to NFPA 13D sure above the ceiling is greater than w/TEFLON or NFPA 13R, the minimum required that below. Down drafts through the Soldered Link Halves Nickel sprinkler flow rates are given in Support Cup could delay sprinkler Lever Bronze Tables A and B as a function of tern- Compression Screw Brass perature rating and the maximum operation in a fire situation. Deflector Copper or allowable coverage areas. The Brass sprinkler flow rate is the minimum Guide Pin Housing Bronze required discharge from each of the Guide Pins Stainless Steel total number of"design sprinklers" as or Bronze specified in NFPA 13D or NFPA 13R. Support Cup Steel The number of "design sprinklers" Cover Plate Copper specified in NFPA 13D and 13R for wet Retainer Brass pipe systems is to be applied when Cover Plate designing dry pipe systems. Ejection Spring Stainless Steel Hydraulic Design Operation (NFPA 13) For systems designed to NFPA 13,the When exposed to heat from a fire, the number of design sprinklers is to be Cover Plate,which is normally soldered the four most hydraulically demanding to the Support Cup at three points,falls sprinklers.The minimum required dis- away to expose the sprinkler assembly. charge from each of the four sprinklers At this point the Deflector supported by is to be the greater of the following: the Arms drops down to its operated • the flow rates given in Tables A and position. The fusible link of the sprin- B as a function of temperature rat- kler assembly is comprised of two link ing and the maximum allowable cov- halves that are soldered together with erage area a thin layer of solder. When the rated • a minimum discharge of 4. temperature is reached, the solder 0.1 gpm/ft.2 over the design area melts and the two link halves separate comprised of the four (4) most th„ allowing the sprinkler to activate and hydraulically demanding sprinklers flow water. for actual coverage areas protected by the four(4)sprinklers The number of design sprinklers speci- fied in NFPA 13 for wet pipe systems is to be applied when designing dry pipe systems. TFP442 - Page 4 of 6 A WET PIPE SYSTEM Minimum Flow and Residual Pressure" Maximum Maximum Coverage Spacing Ordinary Temp.Rating Minimum Area 160°F(71°C) Ft.x Ft. Ft. Deflector to Installation Spacing (m x m) (m) Flow Pressure Ceiling Type Ft. gpm psi (m) (Ipm) (bar) 12 x 12 12 13 7.0 Smooth (3,7 x 3,7) (3,7) (49,2) (0,48) Ceilings 7/8 to 1-1/8 14 x 14 14 13 7.0 inches (4,3 x 4,3) (4,3) (49,2) (0,48) Beamed 16 x 16 16 13 7.0 Ceilings per 8 (4,9 x 4,9) (4,9) (49,2) (0,48) NFPA 13D or Concealed (2,4) 13R,or 13. Installed in 18 x 18 18 17 12.0 beam (5,5 x 5,5) (5,5) (64,3) (0,83) 7/8 to 1-1/8 inches below 20 x 20 20 20 16.7 bottom of (6,1 x 6,1) (6,1) (75,7) (1,15) beam Notes: 1. For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. 2. Requirement is based on minimum flow in gpm(Ipm)from each sprinkler.The associated residual pressures are calcul^ted using the nominal K-factor.Refer to Hydraulic Design under the Design Criteria section. 3. For NFPA 13 residential applications,the greater of 0.1 gpm/ft.°over the design area or the flow in accordance with the criteria in this table must be used. TABLE A WET PIPE SYSTEM SERIES LFII RESIDENTIAL 4.9 K-FACTOR FLAT PLATE CONCEALED PENDENT SPRINKLER(TY3596) NFPA 13D, 13R,AND 13 HYDRAULIC DESIGN CRITERIA DRY PIPE SYSTEM Minimum Flow and Residual Pressure 2.3 Maximum Maximum Coverage Spacing Ordinary Temp.Rating Minimum Area' 160°F(71°C) Ft.x Ft. Ft. Deflector to Installation Spacing (m x m) (m) Flow Pressure Ceiling Type Ft. gpm psi (m) (Ipm) (bar) 12 x 12 12 13 7.0 Smooth (3,7 x 3,7) (3,7) (49,2) (0,48) Ceilings 7/8 to 1-1/8 14 x 14 14 14 8.2 inches (4,3 x 4,3) (4,3) (53,0) (0,57) Beamed 16 x 16 16 15 9.4 Ceilings per 8 NFPA(4,9 x 4,9) (4,9) (56,8) (0,65) 13R,o3D3 rr Concealed (2 4) Installed in 18 x 18 18 18 13.5 beam (5,5 x 5,5) (5,5) (68,1) (0,93) 7/8 to 1-1/8 inches below 20 x 20 20 21 18.4 bottom of (6,1 x 6,1) (6,1) (79,5) (1,27) beam r Notes: 1. For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. 2. Requirement is based on minimum flow in gpm(Ipm)from each sprinkler.The associated residual pressures are calculated using the nominal K-factor.Refer to Hydraulic Design under the Design Criteria section. 4.. 3. For NFPA 13 residential applications,the greater of 0.1 gpm/ft°over the design area or the flow in accordance with the criteria in this table must be used. TABLE B DRY PIPE SYSTEM RAPID RESPONSE SERIES LFII RESIDENTIAL 4.9 K-FACTOR FLAT PLATE CONCEALED PENDENT(TY3596) NFPA 13D, 13R,AND 13 HYDRAULIC DESIGN CRITERIA TFP442 • Page 5 of 6 Step 6. Screw on the Cover Plate Care must be exercised to avoid Installation Assembly until its flange comes in damage before,during,and after instal- TYCO RAPID RESPONSE Series LFII contact with the ceiling. lation. Sprinklers damaged by drop- Residential Concealed Pendent Sprin- Do not continue to screw on the Cover ping, striking, wrench twist/slippage, klers (TY3596) must be installed in Plate Assembly such that it lifts a or the like, must be replaced. accordance with this section. ceiling panel out of its normal position. The owner is responsible for the General Instructions If the Cover Plate Assembly cannot inspection,testing,and maintenance of a to the fusible Link Assemblybe engaged with the Mounting Cup their fire protection system and devices Damage or the Cover Plate Assemblycannot in compliance with this document, as during installation can be avoided by well as with the applicable standards handling the sprinkler by the support be engaged sufficiently to contact the of the National Fire Protection Asso- cup only(i.e.,do not apply pressure to ceiling, the Sprinkler Fitting must be dation (e.g., NFPA 25), in addition to the fusible Link Assembly). repositioned. the standards of any other authorities A 1/2 inch NPT sprinkler joint should be having jurisdiction.Contact the install obtained with a minimum to maximum Care and ing contractor or product manufacturer torque of 7 to 14 lbs.-ft.(9,5 to 19,0 Nm) . with any questions. Higher levels of torque may distort the Maintenance The owner must assure that the sprin- sprinkler inlet with consequent leakage TYCO RAPID RESPONSE Series LFII klers are not used for hanging any or impairment of the sprinkler. Residential Concealed Pendent Sprin- objects and that the sprinklers are only Do not attempt to compensatemust be maintained cleaned by means of gently dusting for klers e (TY3596) insufficient adjustment in the Cover and serviced in accordance with this with a feather duster; ctherwise, non- Plate / Retainer Assembly by under- section. operation in the event of a fire or inad- or over-tightening the Sprinkler. Read- vertent operation may result. just the position of the sprinkler fitting Before closing a fire protection system to suit. main control valve for maintenance Automatic sprinkler systems should be work on the fire protection system inspected,tested,and maintained by a Step 1. The sprinkler must only be which it controls, permission to shut qualified Inspection Service in accor- installed in the pendent position and down the affected fire protection dance with local requirements and/or with the centerline of the sprinkler per- system must be obtained from the national codes. pendicular to the mounting surface. proper authorities and all personnel Step 2. Remove the Protective Cap. who may be affected by this action must be notified. Step 3. With pipe thread sealant Absence of a Cover Plate may delay the applied to the pipe threads, and using sprinkler operation in a fire situation. the W-Type 18 Wrench shown in Figure 2, install and tighten the Sprinkler / When properly installed, there is a Support Cup Assembly into the fitting. nominal 1/8 inch (3,2 mm) air gap The W-Type 18 Wrench will accept a between the lip of the Cover Plate and 1/2 inch ratchet drive. the ceiling, as shown in Figure 3.This Step 4.Replace the Protective Cap by air gap is necessary for proper opera pushing it upwards until it bottoms out tion of the sprinkler by allowing heat against the Support Cup. The Protec flow from a fire to pass below and tive Cap helps prevent damage to the above the Cover Plate to help assure Deflector and Guide Pins during ceiling appropriate release of the Cover Plate installation and/or during application of in a fire situation. If the ceiling is to be the finish coating of the ceiling. It may repainted after the installation of the also be used to locate the center of the Sprinkler, care must be exercised to clearance hole by gently pushing the ensure that the new paint does not seal ceiling material against the center point off any of the air gap. of the Cap. Factory painted Cover Plates must not Note:As long as the protective Cap be repainted.They should be replaced, remains in place, the system is consid if necessary, by factory painted ered to be "Out Of Service." units. Non-factory applied paint may adversely delay or prevent sprinkler Step 5. After the ceiling has been operation in the event of a fire. completed with the 2-1/2 inch(63 mm) Do not pull the Cover Plate relative to diameter clearance hole and in prep the Enclosure.Separation may result. aration for installing the Cover Plate a Assembly,remove and discard the Pro- Sprinklers which are found to be tective Cap,and verify that the Deflec- leaking or exhibiting visible signs of i. tor moves up and down freely. corrosion must be replaced. If the sprinkler has been damaged and Automatic sprinklers must never be the Deflector does not move up and painted, plated, coated, or otherwise down freely,replace the entire sprinkler altered after leaving the factory. Modi- assembly.Do not attempt to modify or fied or over heated sprinklers must be repair a damaged sprinkler. replaced. TFP442 Page 6 of 6 Limited Ordering Warranty Procedure For warranty terms and conditions,visit Contact your local distributor for www.tyco-fire.com. availability. When placing an order, indicate the full product name and part number(P/N). Sprinkler Assemblies Specify: Series LFII (TY3596) 4.9K Residential Concealed Pendent Sprin- kler without Cover Plate Assembly, P/N 51-112-1-160 Cover Plate Assemblies Specify: Cover Plate Assembly with (specify) finish for the Series LFII (TY3596) 4.9K Residential Concealed Pendent Sprinkler, P/N (specify): Ivory(RAL1015) P/N 56-202-0-135 Beige(PAL1001) P/N 56-202-2-135 Pure White'(RAL9010) P/N 56-202-3-135 Signal White**(RAL9003) P/N 56-202-4-135 Grey White(RAL9002) P/N 56-202-5-135 Brown(RAL8028) P/N 56-202-6-135 Black(RAL9005) P/N 56-202-7-135 Brushed Brass P/N 56-202-8-135 Brushed Chrome P/N 56-202-9-135 Custom Paint P/N 56-202-X-135 Eastern Hemisphere sales only **Previously known as Bright White Note: All Custom Cover Plates are painted using Sherwin Williams Interior Latex Paint. Contact Tyco Customer Service with any questions related to custom orders. Sprinkler Wrench Specify: W-Type 18 Sprinkler Wrench, P/N 56-000-1-265 r GLOBAL HEADQUARTERS 11400 Pennbrook Parkway,Lansdale,PA 194461 Telephone+1-215-362-0700 Copyright©2015 Tyco Fire Products,LP. All rights reserved. t'"'ffco TEFLON is trademark of The DuPont Corporation. Fire Protection Products sok._ MALLEABLE IRON & CAST-IRON-FITTINGS 0.4 Malleable Iron Face Bushing N 0 V 8 ?_017 El FIGURE 385 (:I t �` }w Unit Weight Face Bushing I€! r)r� "y Black Galy. • ,,:NPS „ ,,,4 . y NP ..ice. "OW ibtk .. ..k9 .. lbs 3/e 10 0.08 0.04 - - 3/a 20 1/2 15 0.06 0.03 0.06 0.03 1/2 15 0.16 0.07 0.16 0.07 • 1 25 3/a 20 0.10 0.05 0.10 0.05 1/2 15 0.30 0.14 - - 11/4 32 3/a 20 0.27 0.12 - - 1 25 0.19 0.09 0.19 0.09 '/z 15 0.40 0.18 - - 1'/z 40 3/4 20 0.39 0.18 - - 1 25 0.33 0.15 - - 11/4 32 0.16 0.07 0.16 0.07 1 25 0.65 0.29 0.65 0.29 2 50 11/4 32 0.53 0.24 0.53 0.24 _ 11/2 40 0.40 0.18 0.40 0.18 11/4 32 1.10 0.50 - - 21/2 65 2 50 0.40 0.18 0.40 0.18 3 80 2'/z 65 0.99 0.45 - - Note:See following page for malleable iron pressure-temperature ratings. Cast Iron Face Bushing I I FIGURE 385 Unit Weight Size Black Face Bushing NPS ON- , }P .DAt lbs kg ., 3 80 2 50 13.30 6.03 2152 65 2.55 1.16 4 100 3 80 19.20 8.71 According to specifications,hex bushings and cored plugs should be used with 150#malleable iron and 125#cast iron.Solid plugs and face bushings are recommended for use with 250#and 300#fittings. Note:See page 3 for cast iron pressure-temperature ratngs. PROJECT INFORMATION APPROVAL STAMP Project: Approved Address: ['Approved as noted Contractor: ['Not approved Engineer: Remarks: Submittal Date: Notes 1: Notes 2: PF-11.16 iv- MALLEABLE IRON FITTINGS «<Q�� !+!' 4 ' / ' '. ' y/ s,'` ^.ux/tii// � i�r j ;: // , F�`� ' '''/moi, r -� �s" kip' C" f ` 45 \m € _ vi Malleable Iron Threaded Pipe Unions Malleable Iron Threaded Fittings Pressure -Temperature Ratings _ Pressure -Temperature Ratings Pressure Pressure Temperature Class 150 Class 250 Class 300 Class 300 Temperature Class 150 Sizes Y4"-1" Sizes 1 Y4"-2" Sizes 2'h"-3" Ft"} Of' psi'',,,g„,bar '''psi..: , bOr., ps"r........,,.,618.1 -20° -28.9° ° (6-25 mm) (32-51 mm) (64 76 mm) to to 300 20.7 500 34.5 600 41.4 ...t F) ( '' psi bar ...; psi' bat,t- 'PSI bar, -'pst %Gar 150° 65.6° -20° -28.9° 200° 93.3° 265 18.3 455 31.4 550 37.9 15to 0° 65.6°to 300 20.7 2,000 137.9 1,500 103.4 1,000 68.9 250° 121.1° 225 15.5 405 27.9 505 34.8 200° 93.3 265 18.3 1,785 123.1 1,350 93.1 910 62.7 300° 148.9° 185 12.8 360 24.8 460 31.7 250° 121.1 225 15.5 1,575 108.6 1,200 82.7 825 56.9 350° 176.7° 150 10.3 315 21.7 415 28.6 300° 148.9 185 12.8 1,360 93.8 1,050 72.4 735 50.7 ° 110 7.6 270 18.6 370 25.5 3500 176.7 150 10.3 1,150 79.3 900 62.1 650 44.8 400° 204.4 450° 232.2° 75 5.2 225 15.5 325 22.4 500° 260.0° - - 180 12.4 280 19.3 400° 204.4 - - 935 64.5 750 51.7 560 38.6 550° 287.8° - - 130 9.0 230 15.9 450° 232.2 - - 725 50.0 600 41.4 475 32.8 Note:Unions with Copper or Copper Alloy seats are not intended for use where temperature exceeds 500° 260.0 - - 510 35.2 450 31.0 385 26.5 450°F 550° 287.8 - - 300 20.7 300 20.7 300 20.7 C US ® Anvil Class 150/300 Malleable Iron Fittings conform to ASME APPROVED B16.3 and Unions conform to ASME 816.39. For Listings/Approval Details and Limitations,visit our website at ALL ELBOWS&TEES 3/e"(10 DN)and LARGER ARE 100%GAS TESTED AT www.anvilintl.com or contact an Anvil Sales Representative. A MINIMUM OF 100 PSI.(6.9 bar) Standards and Specifications Dimensions Material Galvanizing* Thread Pressure Rating 81 ‘• ..,; ...., MALLEABLE''.IRQI ''... IT" NGS ... . .. ......r. ,.:�\ l i4;of .:..�.....,, Class 150/PN 20 ASME B16.3 ASTM A 197 ASTM A-153 ASME B1 20.1 ASME B16.3 ` Class 300/PN 50 ASME B16.3 ASTM A 197 ASTM A 153 ASME B1 20.1 ASME B16.3 LLEA�LE IRON(JNIONS ASTM A-197 ASTM A-153 ASME B1 20.1 ASME B16.39 Class 150/PN 20 ASME B16.39 Class 250 ASME B16.39 ASTM A-197 ASTM A-153 ASME B1 20.1 ASME B16.39 Class 300/PN 50 ASME B16.39 ASTM A-197 ASTM A-153 ASME B1 20.1 ASME B16.39 ASTM B 633.Type I,SC 4,may be supplied as alternate zinc coating per applicable ASME B16 product standard. PF-11.16 0 CAST IRON FITTINGS (Q1niv! w 4f,bi,., 4, / f?.i. .....:...."... ..- 7. ....,, ,;-0,.$.;i:.-'1::'''4'.!.-..,.?...,!....z..•;.,\ if .... - ----' 7'..:-''.'..:,...,=::;?."-kV7,4 .16 ,' ' '...,:•'-'",N, .......,,'.,f.: .. '''\ :,,N,,,,,,, .:,i.,,, i.. , mak,., 3 _ ,, ,.. , i - ' / ,'� ,,rem" k. a , . .'.:'.-:.:.'-..'. ••::-... . . 'tl.-t,,,f.;:..:-:7-,...!':::l:,--.'yf:':':lt.!EE,;;;;41,ti..,j,s...,„„!ii, :-._ 7:-..„•••••• i - ' :. .0,..,\, ' .::31i,,: ".4k, • . "-i,-,-1,0MIKW-ailliiiir SIP-- .,:,.=..,-,,,,.....,,....:„...,1"'----. ,..,..--:-. --' .- ''''--;'''t,'- ,.........-.=. -1::' - ' ' .4reitii2143*'<4.1, *,*1 \ \ C '"----...' �' "ems "�3 t•y ° .vim,,,,::: ��, Anvil standard and extra heavy cast iron threaded fittings Cast Iron Threaded Fittings are manufactured in accordance with ASME B16.4.Plugs and Pressure -Temperature Ratings bushings are manufactured in accordance with ASME B16.14. Temperature Pressure NOTE:Figure 367 Concentric Reducers do not meet the overall length o Class 125 Class 250 requirement of ASME B16.4. All other dimensions are in compliance. �_E"t ....... .1a�1; tt�' gar fir%,��,,'''°"'�bar 20°to 150° -28 9 to 65.6 175 12.1 400 27.6 200° 93.3 165 11.4 370 25.5 1)1. 250° 121.1 150 10.3 340 23.4 C a US APPROVED 300° 148.9 140 9.7 310 21.4 For Listings/Approval Details and Limitations,visit our website at 350° 176.7 125 8.6 300 20.7 www.anvilintl.com or contact an Anvil Sales Representative. 400° 204.4 - - 250 17.2 Standards and Specifications Dimensions Material Galvanizing Thread Pressure Rating BAST tltt3N TREl7EL1 �`�'TI�!(GS, ., Class 125 ASME B16.4 ASTM A 126(A) ASTM A 153 ASME 61.20.1 ASME 616.4 Class 250 ASME B16 4 ASTM A 126(A) ASTM A 153 ASME 61 201 ASME 616.4 - CASJTRQN PLUGS A j B ' HI i'/ ASME B16.14 ASTM A-126(A) ASTM A-153 ASME 81.20.1 ASME 616.14 'ASTM B 633.Type I,SC 4,may be supplied as alternate zinc coating per applicable ASME B16 product standard. PF-11.16 MALLEABLE IRON & CAST IRON FITTINGS• General Assembly of Threaded Fittings 1) Inspect both male and female components prior to assembly. • Threads should be free from mechanical damage,dirt,chips and excess cutting oil. • Clean or replace components as necessary. 2) Application of thread sealant • Use a thread sealant that is fast drying,sets-up to a semi hard condition and is vibration resistant.Alternately,an anaerobic sealant may be utilized. • Thoroughly mix the thread sealant prior to application. • Apply a thick even coat to the male threads only.Best application is achieved with a brush stiff enough to force sealant down to the root of the threads. 3) Joint Makeup • For sizes up to and including 2"pipe,wrench tight makeup is considered three full turns past handtight.Handtight engagement for 1/2'through 2"thread varies from 41/2 turns to 5 turns. • For 21/2"through 4"sizes,wrench tight makeup is considered two full turns past handtight.Handtight engagement for 21/2" through 4"thread varies from 51/2 turns to 63/4 turns. .4 PF-6.13 Eddyth read 40 A Lightweight Schedule 40 Replacement Pipe That Has a Corrosion Resistance Ratio of 1.0 Bull Moose Tube Company has been making pipe for a long time and is recognized as a producer of quality pipe products. Eddythread 40 is designed with the same thoroughness as our other fine pipe products and now our customers have an option to buy a carefully designed replacement for Schedule 40 that: • Has a Corrosion Resistance Ratio of 1.0 • Has a Pressure Rating of 300 psi • Is Lighter Weight Than Schedule 40 ttV 8 0(112 • Is Approved by Factory Mutual and Listed by Underwriters Laboratories • Is Produced in Accordance to ASTM A-135 and A-795 J!l • Can be Used With Standard Schedule 40 Threaded Fittings, Couplings and Valves • Is Produced From Steel With Excellent Properties of Strength and Threadability • Can be Used in Wet, Dry, Preaction, and Deluge Type Sprinkler Systems* • Offers Lower Freight Costs EDDYTHREAD 40 SPECIFICATIONS 1 1.461 1.083 70 1 1/4 2.070 1.418 51 11/2 2.547 1,654 44 2 3.308 2.123 30 CORROSION RESISTANCE RATIOS NOMINAL PIPE SCHEDULE 40 EDDYTHREAD 4 1 1.00 1.00 1 1/4 1.00 1.00 1 1/2 1.00 1.00 2 1.00 1.00 *Eddythread 40 can be hot dipped galvanized to meet FM's requirement for dry systems 1819 Clarkson Road For additional information, /� Chesterfield, MO 63017 contact your salesperson today at C®US 1( BULL MOOSE TUESE COnnp.4nrY (800)325-4467 (800)325-4467 or(636)537-2600 LISTED -, CJ FAX:(636)537-2645 in the USA,or from Canada www.bullmoosetube.com call(800)882-4666 A LPARO)company e-mail:sales@bullmoosetube.com APPROVED All information contained herein is accurate as known at the time of publication. Bull Moose Tube reserves the right to change product specifications without notice and without incurring obligation. 8/08 La1CFez: t ',AV 8 2017 3t ,'z ° ' h LaMMOWNiiiMMO „r,,, \ / Nor / , \t/A.,-, � �"` # .... e, .\,"'""""'t.� I r fi' « E� i .r_ - 4 aWr1111MIM�M� € fF �X. , - £ gip.. tj'. .t OVININWINMINIt 1111111111 ' 0two/ ,\t O PREP R 4f '—j , i NE: R /IRE 4 ., I:s2 I & FIR,INC. .N ' -\ r S S i c\' _,°Frt / fry CVS Health ol 0 O / 0 C 1 7358 SW Durham RD. � itv Portland, OR 97224 0 0 R F I I Concealed Sprinkler heads SE GRE TORA i 0 ' f 4 i , ,, Ildf Will will be relocating 1 - 1—,-1 i 0 sprinkler head due to light 0 I I I r' fixture location change / and changing out 18 , ._._ n n . a n n — standard response / ! k- � // sprinkler heads to quick \ CITY OP TIGARD response concealed LFII REVIEWED FOR CO COMPLIANCE sprinkler heads. • 'Ai / Approved. t °°. T OTC: [ I Permit#: `-lam` c C7 (7 Address: Suite#: , � ���i� Date: I(/�-4 BY: OFFICE COPY