Loading...
Report (21) 6141? P -mac? 919 NE 19th Avee . r Suite 155 4k; ios Portland,OR.97232 503 265 8461 DES I CNI design@eprdesign.com www.eprdesign.com 5.18.17 Attention: Dan Nelson/Senior Plans Examiner RE: BUP2017-00068 and S1T2017-00005 Plan Check Response BUP2017-00068: 1.) Total square footage of building and occupant load provided on Sheet CS. Area and occupant loads of the 3 smoke areas provided on Sheet FLS.1 2.) Com Check form for the building envelope and insulation provided. Lighting and others required will be design build and deferred submittals as discussed over the phone. End of Comments for BUP2017-00068 SIT2017-00005: 1) FDC and new hydrant shown on the Utility Plan Sheet C2. 2) Fire line to stand pipe added to Sheet C2 (delineated with a "FW" line) 3) Hydrant is less than 400'from the NW Corner of the building. See Sheet C2. End of Comments for SIT2017-00005 May 18, 2017 REVISION RE: NEW MEMORY CARE Project Information Building Permit: BUP2017-00068 Construction Type: 5A Address: 11035 SW Hall Occupancy Type: 1-2 Area: 16327 Sq Ft Stories: 2 Name: Brookside Memory Care Sprinklers: Yes The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2014 edition; 2014 Oregon Fire Code. Please respond to conditions below. 1) Provide total square footage and occupant load for building and also broken down for smoke areas. 2) Provide Com Check documents for building envelope insulation and lighting. When responding, provide an itemized letter stating in what way each numbered issue has been addressed in the revision. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfully, Dan Nelson Senior Plans Examiner (503) 718-2436 dann@tigard-or.gov May 18, 2017 RE: NEW MEMORY CARE Project Information Building Permit: SIT2017-00005 Construction Type: 5A Address: 11035 SW Hall Occupancy Type: 1-2 Area: 16327 Sq Ft Stories: 2 Name: Brookside Memory Care Sprinklers: Yes The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2014 edition; 2014 Oregon Fire Code. Please respond to conditions below. 1) Please show location of FDC and hydrants on a scalable plan. 2) Show fire line to stand pipe. 3) Hydrant to be no more than 400' from N/W corner of building. When responding, provide an itemized letter stating in what way each numbered issue has been addressed in the revision. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfully, Dan Nelson Senior Plans Examiner (503) 718-2436 dann@tigard-or.gov 919 NE 19th Ave. Suite 155 DESIGN Portland,OR.97232 503265.8461 design@ep rdesign.corn www.eprdesign.corn Building Permit#:S1T2017-00005 y Address: 11035 SW Hall Blvd.Tigard, Oregon f . q Name: Brookside Memory Care MAY 4 I(i l r' Attention: Dan Nelson,Senior Plans Examiner CITY OF i-I A itat RE: Plan Review Revision Letter Dated 4.27.17 BUILDING ..) VI S) ,t 1.) Fire hydrant locations identified but do not meet the spacing requirements. A new Fire hydrant was added to the Civil Sheets on the property. See sheets C2 and C4. 2.) FPS permit has been applied for and approved. 3.) Hydrant flow test has been provided via email from Tualatin Valley Water District. 4.) FDC and Fire Hydrant shown on the Civil sheets C2 an C4. 5.) Fire line to stand pipe added to plan. See Civil sheet C2. 6.) New Fire hydrant location is closer than 400'to any part of the building and within 150' of the FDC which is located right next to the Fire Vault. End of Response April 27, 2017 RE: NEW MEMORY CARE Project Information Building Permit: SIT2017-00005 Construction Type: 5A Address: 11035 SW Hall Occupancy Type: 1-2 Area: 16327 Sq Ft Stories: 2 Name: Brookside Memory Care Sprinklers: Yes The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2014 edition; 2014 Oregon Fire Code. Please respond to conditions below. 1) Identify fire hydrant locations. 2) Provide FPS permit through the City of Tigard for underground sprinkler lines. 3) Please provide hydrant flow test. 4) Please show location of FDC and hydrants on a scalable plan. 5) Show fire line to stand pipe. 6) Hydrant to be no more than 400' from N/W corner of building. When responding, provide an itemized letter stating in what way each numbered issue has been addressed in the revision. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfully, Dan Nelson Senior Plans Examiner (503) 718-2436 dann@tigard-or.gov