5.18.17
Attention: Dan Nelson/Senior Plans Examiner
RE: BUP2017-00068 and S1T2017-00005
Plan Check Response
BUP2017-00068:
1.) Total square footage of building and occupant load provided on Sheet CS. Area and occupant
loads of the 3 smoke areas provided on Sheet FLS.1
2.) Com Check form for the building envelope and insulation provided. Lighting and others required
will be design build and deferred submittals as discussed over the phone.
End of Comments for BUP2017-00068
SIT2017-00005:
1) FDC and new hydrant shown on the Utility Plan Sheet C2.
2) Fire line to stand pipe added to Sheet C2 (delineated with a "FW" line)
3) Hydrant is less than 400'from the NW Corner of the building. See Sheet C2.
End of Comments for SIT2017-00005
May 18, 2017 REVISION
RE: NEW MEMORY CARE
Project Information
Building Permit: BUP2017-00068 Construction Type: 5A
Address: 11035 SW Hall Occupancy Type: 1-2
Area: 16327 Sq Ft Stories: 2
Name: Brookside Memory Care Sprinklers: Yes
The plan review was performed under the State of Oregon Structural Specialty Code
(OSSC) 2014 edition; 2014 Oregon Fire Code. Please respond to conditions below.
1) Provide total square footage and occupant load for building and also broken
down for smoke areas.
2) Provide Com Check documents for building envelope insulation and lighting.
When responding, provide an itemized letter stating in what way each numbered
issue has been addressed in the revision.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City
of Tigard in tracking and processing the documents.
Respectfully,
Dan Nelson
Senior Plans Examiner
(503) 718-2436
dann@tigard-or.gov
May 18, 2017
RE: NEW MEMORY CARE
Project Information
Building Permit: SIT2017-00005 Construction Type: 5A
Address: 11035 SW Hall Occupancy Type: 1-2
Area: 16327 Sq Ft Stories: 2
Name: Brookside Memory Care Sprinklers: Yes
The plan review was performed under the State of Oregon Structural Specialty Code
(OSSC) 2014 edition; 2014 Oregon Fire Code. Please respond to conditions below.
1) Please show location of FDC and hydrants on a scalable plan.
2) Show fire line to stand pipe.
3) Hydrant to be no more than 400' from N/W corner of building.
When responding, provide an itemized letter stating in what way each numbered
issue has been addressed in the revision.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City
of Tigard in tracking and processing the documents.
Respectfully,
Dan Nelson
Senior Plans Examiner
(503) 718-2436
dann@tigard-or.gov
919 NE 19th Ave.
Suite 155
DESIGN Portland,OR.97232
503265.8461
design@ep rdesign.corn
www.eprdesign.corn
Building Permit#:S1T2017-00005 y
Address: 11035 SW Hall Blvd.Tigard, Oregon f . q
Name: Brookside Memory Care
MAY 4 I(i l r'
Attention: Dan Nelson,Senior Plans Examiner CITY OF i-I A
itat
RE: Plan Review Revision Letter Dated 4.27.17 BUILDING ..) VI S) ,t
1.) Fire hydrant locations identified but do not meet the spacing requirements. A new Fire hydrant
was added to the Civil Sheets on the property. See sheets C2 and C4.
2.) FPS permit has been applied for and approved.
3.) Hydrant flow test has been provided via email from Tualatin Valley Water District.
4.) FDC and Fire Hydrant shown on the Civil sheets C2 an C4.
5.) Fire line to stand pipe added to plan. See Civil sheet C2.
6.) New Fire hydrant location is closer than 400'to any part of the building and within 150' of the
FDC which is located right next to the Fire Vault.
End of Response
April 27, 2017
RE: NEW MEMORY CARE
Project Information
Building Permit: SIT2017-00005 Construction Type: 5A
Address: 11035 SW Hall Occupancy Type: 1-2
Area: 16327 Sq Ft Stories: 2
Name: Brookside Memory Care Sprinklers: Yes
The plan review was performed under the State of Oregon Structural Specialty Code
(OSSC) 2014 edition; 2014 Oregon Fire Code. Please respond to conditions below.
1) Identify fire hydrant locations.
2) Provide FPS permit through the City of Tigard for underground sprinkler lines.
3) Please provide hydrant flow test.
4) Please show location of FDC and hydrants on a scalable plan.
5) Show fire line to stand pipe.
6) Hydrant to be no more than 400' from N/W corner of building.
When responding, provide an itemized letter stating in what way each numbered
issue has been addressed in the revision.