SPECIAL INSPECTION—FINAL SUMMARY LETTER
November 3, 2017
Mr. Mark Van Domelen
City of Tigard, Building Department
13125 SW Hall Blvd.
Tigard, OR 97223
RE: Schultz Residence Underpinning
8493 SW Bonaventure Ln.
Tigard, OR 97224
Permit# MST2017-00395
Dear Mr. Van Domelen,
This letter certifies that we have performed special inspection of the referenced project, in accordance with
Chapter 17 of the International Building Code. Special inspection has been performed on (4) helical piers
and (4)helical ground anchor, as shown on the permit documents.
On Nov. 3rd 2017, a representative of i.e.Structural observed the installation of(4)Foundation Supportwork
Incorporated model HP288 helical piers, as shown on structural drawings. All helical piers reached or
exceeded the specified installation pressure and the minimum penetration depth specified on structural
drawings. Load testing was performed on piers (1) and (3) in accordance with ASTM method D1143(Quick
Method), and passed the creep acceptance criteria. i.e. Structural has reviewed the installation logs of the
remaining piers and confirmed them to be acceptable.
Special inspections have been provided to meet the requirements of the building code and do not constitute
a guarantee of the installed work. It is the responsibility of the contractor to execute the work in accordance
with the structural drawings.