Report - ca.5-3 f15)-617 $ 4'4' /41-13 .44.. W VAT T • • 9 • 11 • *10, . . • . • • • # • 9 IL ' • FIRE PROTECTION, INC ,v , . , 1 S.W. Burnham , r ., t'Y 9095 • Tigard, OR 97223 LIDS WASH SQ 9461 SW WASHINGTON SQ RD #A13 TIGARD, OR 97223 FIRE PROTECTION EQUIPMENT SUBMITTAL VICO Worldwide Contacts www,tyco-fire.com Series RFII — 5.6 K-factor "Royal Flush II" Concealed Pendent Sprinklers Quick & Standard Response, Standard Coverage General stallation or finish. The tip of the Pro- tective Cap can be used to mark the DeSCri tion center of the ceiling hole into plaster jp board or ceiling tiles by gently push- '_ The TYCO Series RFII 5.6 K-factor, ing the ceiling product against the Pro- rf "Royal Flush II" Concealed Pendent tective Cap. When ceiling installation is complete, the Protective Cap is re- Sprinklers Quick Response (3-mm V '_ :. bulb) and Standard Response (5-mm moved and the Cover Plate/Retainer Assembly is installed. bulb), are decorative sprinklers featur- i ing a flat cover plate designed to con- As an option,the Series RFII Standard -�r ", , ceal the sprinkler.These sprinklers are Response(5-mm bulb)"Royal Flush II" optimal for architecturally sensitive ar- Concealed Pendent Sprinklers can be eas such as hotel lobbies,office build- fitted with a silicone Air and Dust Seal. • TY3531 (3-mm Bulb) is UL Listed, ings,churches,and restaurants. (Refer to Figure 5.) The Air and Dust C-UL Listed, VdS Approved (Certif Each sprinkler includes a Cover Plate/ Seal is intended for sensitive areas icate No. G4090007), and NYC Ap- Retainer Assembly and a Sprinkler/ where it is desirable to prevent air and proved (MEA 353-01-E) as Quick Support Assembly. separa- dust from the area above the ceiling to PP Cup Y P Response. ble, two-piece assembly design pro- pass through the cover plate. vides the following benefits: • TY3531 (3-mm Bulb) is FM and NOTICE LPCB Approved (Ref. No. 094a/10) • Allows installation of the sprinklers The Series RFII Concealed Pendent Approved as Standard Response. and pressure testing of the fire pro- Sprinklers described herein must be Factory Mutual and LPCB do not tection system prior to installation installed and maintained in compli approve any concealed sprinklers - of a suspended ceiling or applica for quick response. ance with this document and with the tion of the finish coating to a fixed applicable standards of the National • pp TY3551 (5-mm Bulb) is UL Listed, ceiling. Fire Protection Association, in addi- C-UL Listed, FM Approved, LPCB • Permits the removal of suspended tion to the standards of any authori- Approved (Ref. No. 094a/9), and ceiling panels for access to building ties having jurisdiction.Failure to do so NYC Approved (MEA 353-01-E) as service equipment without having may impair the performance of these Standard Response. to first shut down the fire protection devices. A system and remove sprinklers. Approvals for Air and Dust Seal The owner is responsible for maintain UL and C-UL Listed for use with the • Provides for 1/2 inch (12,7 mm) of ing their fire protection system and de- RFII Standard Response Concealed vertical adjustment to allow a mea- vices in proper operating condition. Sprinkler(TY3551). sure of flexibility in determining the The installing contractor or sprinkler length of fixed piping to cut for the manufacturer should be contacted Maximum Working Pressure sprinkler drops. with any questions. are shipped Maximum 250 psi (17,3 bar) by UL, The Series RFII Sprinklers PP C-UL,and NYC with a Disposable Protective Cap.The Sprinkler Protective Cap is temporarily removed p Maximum 175 psi (12,1 bar) by FM, during installation and replaced to help Identification VdS,and LPCB protect the sprinkler during ceiling in- Temperature Rating Number (SIN) 155°F(68°C)Sprinkler with IMPORTANT TY3531 — 3 mm bulb 139°F(59°C)Plate Always refer to Technical Data 200°F(93°C)Sprinkler with Sheet TFP700 for the "INSTALLER TY3551 — 5 mm bulb WARNING" that provides cautions 165°F(74°C)Plate with respect to handling and instal- Technical Discharge Coefficient lation of sprinkler systems and corn- K=5.6 GPM/psi112(80,6 LPM/bar1i2) ponents. Improper handling and in- Data stallation can permanently damage Adjustment a sprinkler system or its components Sprinkler Approvals 1/2 inch(12,7 mm) and cause the sprinkler to fail to Approvals apply only to the service operate in a fire situation or cause it conditions indicated in the Design Cri- Finishes to operate prematurely. teria section. See the Ordering Procedure section. Page 1 of 4 MARCH 2013 TFP181 TFP181 Page 2 of 4 Physical Characteristics 1/2" NPT 4rSEALING Frame Bronze / ASSEMBLY Support Cup Chrome t Plated Steel ,. Guide Pins Stainless Steel FRAME V ' ,Deflector Bronze �— l CAP Compression Screw Brass �� Bulb Glass Cap Bronze or Copper SUPPORT Sealing Assembly Beryllium CUP WITH __________LTI BULB Nickel w/TEFLON ROLL FORMED 11 Cover Plate Brass THREADS Retainer Brass Ejection Spring Stainless Steel 1r R I I COMPRESSION Design \ SCREW GUIDE 1 � Criteria PINS(2) / A r $ The TYCO Series RFII 5.6 K-factor, , DEFLECTOR "Royal Flush II" Concealed Pendent (DROPPED Sprinklers are intended for fire protec- DEFLECTOR i —z r _� � POSITION) tion systems designed in accordance with the standard installation rules rec- ognized by the applicable Listing or SPRINKLER/SUPPORT CUP Approval agency;for example,UL List- ASSEMBLY ing is based on NFPA 13 and VdS Ap- proval is based on the CEA 4001. THREAD INTO I RETAINER For more information on LPCB and SUPPORT \ I WITH THREAD CUP UNTIL \ Q ) DIMPLES VdS Approvals, contact Tyco Fire Pro- MOUNTING tection Products at the following office: SURFACE IS EJECTION Enschede,Netherlands FLUSH WITH SPRING Telephone:31-53-428-4444 CEILING Fax:31-53-428-3377 The Series RFII Concealed Pendent J --- Sprinklers are only listed and approved - with the Series RFII Concealed Cover Plates having a factory applied finish. SOLDER COVER TABS(3) COVER PLATE/RETAINER PLATE NOTICE ASSEMBLY Do not use the Series RFII in applica- FIGURE 1 tions where the air pressure above MODEL RFII CONCEALED SPRINKLER the ceiling is greater than that be- ASSEMBLY low. Down drafts through the Sprin- kler/Support Cup Assembly can delay Installation Do not attempt to compensate for in- sprinkler operation in a fire situation. sufficient adjustment in the Sprinkler The TYCO Series RFII 5.6 K-factor, by under- or over-tightening the Sprin- "Royal Flush II" Concealed Pendent kler/Support Cup Assembly. Re-adjust Operation Sprinklers must be installed in accor- the position of the sprinkler fitting to When exposed to heat from a fire,the dance with this section. suit. Cover Plate, normally soldered to the General Instructions Step 1. Install the sprinkler only in the Retainer at three points, falls away to Do not install an bulb t e s rinkler if pendent position with the center-line expose the Sprinkler/Support Cup y yp p of the sprinkler perpendicular to the Assembly. the bulb is cracked or there is a loss mounting surface. of liquid from the bulb. With the sprin- Step 2.Remove the Protective Cap. The Deflector — supported by the kler held horizontally, a small air bub- Guide Pins — then drops down to its ble should be present. The diameter Step 3. With pipe thread sealant ap- operational position. of the air bubble is approximately 1/16 plied to the pipe threads, hand-tighten inch (1,6 mm)for the 155°F (68°C)and the sprinkler into the sprinkler fitting. The glass bulb contains a fluid that ex- 3/32 inch(2,4 mm)for the 200°F(93°C) Step 4. Wrench tighten the sprinkler ponds when exposed to heat. When temperature ratings. using only the RFII Sprinkler Wrench. the rated temperature is reached, the (Refer to Figure 3.) Apply the RFII fluid expands sufficiently to shatter the A leak-tight 1/2 inch NPT sprinkler joint Sprinkler Wrench to the Sprinkler as glass bulb,activating the sprinkler and should be obtained by applying a min- shown in Figure 3. allowing water to flow. imum to maximum torque of 7 to 14 Step 5. Replace the Protective Cap ft. lbs. (9,5 to 19,0 Nm). Higher levels by pushing it upwards until it bottoms of torque can distort the sprinkler In- out against the Support Cup. (Refer let with consequent leakage or impair- - to Figure 4.)The Protective Cap helps ment of the sprinkler. prevent damage to the Deflector and TFP181 Page 3 of 4 FACE OF CLEARANCE HOLE CLEARANCE ... \SPRINKLER DIAMETER ► HOLE FITTING `I DIMENSION C J SPRINKLER lifirrit IMIIN SUPPORT CUP ASSEMBLY I ,Il1IJ 1104a, r 1 e T 1/2"(12,7 mm) 1 THREADED 1 DADJUSTMENT ly „ ISIFACE OF CEILING, RETAINING RING it r ��----,-/ e MOUNTING �� i SURFACE v tl \ j I n\ I I / FIGURE 4 tDISPOSABLE PROTECTIVE CAP i i Arms during ceiling installation and/or L.- ---J �r_� finish.You can also use the Protective T -~ Cap to locate the center of the clear- 3/16"to 11/16" MANUFACTURER DEFLECTOR COVER PLATE ance hole by gently pushing the ceiling (4,8 to 17,5 mm) PRESET GAP IN DROPPED RETAINER material up against the center point of REFERENCE 3/32"(2,4 mm) POSITION ASSEMBLY the Protective Cap. COVER PLATE COVER PLATE NOTICE -PROFILE DEPTH - DIAMETER - As long as the Protective Cap remains DIMENSION B DIMENSION A in place, the system is considered A:3-1/4 inches(82,6 mm) C:2-3/8 to 2-5/8 inches(60,3 to 66,7 mm) "Out of Service': B:3/16 inches(4,8 mm) D:1-3/4 to 2-1/4 inches(44,5 to 57,2 mm) Step 6.After the ceiling has been com- pleted with the 2-1/2 inch(63,5 mm)di- ameter clearance hole and in prepa- FIGURE 2 ration for installing the Cover Plate/ SERIES CONCEALED SPRINKLER INSTALLATION DIMENSIONS Retainer Assembly, remove and dis- card the Protective Cap.Verify that the Deflector moves up and down freely. If the Sprinkler is damaged and the IIM FRAME j=l,_ Deflector does not move up and down ARM H' freely, replace the entire Sprinkler. Do not attempt to modify or repair a - damaged sprinkler. SUPPORTj Step 7. When installing an Air and CUP (' % IDust Seal,refer to Figure 5;otherwise, I proceed to Step 8. To attach the Air ; i and Dust Seal, verify the angle of the _111111111. ,���i�� outside edge of the seal is oriented I■I ��j ac- cording to Figure 5. Start the edge of - - --- - the Retainer in the grooved slot of the 0 7/8"(23 mm) Air and Dust Seal and continue around SQUARE the retainer until the entire Air and Dust Seal is engaged. J-` Step 8. Screw on the Cover Plate/ ALIGN �� Retainer Assembly until the Retainer ARROWS WITH iii" i i \ (shown in Figure 2)or the Air and Dust FRAME ARMS c, Seal (shown in Figure 5) contacts the l�� �I ceiling. Do not continue to screw on i i i the Cover Plate/Retainer Assembly ACCEPTS \, r�� so that it lifts a ceiling panel out of its 0 1/2"SOCKET - normal position. If you cannot engage DRIVE the Cover Plate/Retainer Assembly FIGURE 3 with the Support Cup or you cannot SPRINKLER WRENCH engage the Cover Plate/Retainer As- RFIIsembly sufficiently to contact the ceil- ing, you must reposition the Sprinkler Fitting. TFP181 Page 4 of 4 Care and SUPPORT SPRINKLER FACE OF ORIENT CUP ---_ CEILING SEAL Maintenance BEVEL AS I � 'T SHOWN The TYCO Series RFII 5.6 K-fac- i — 1 I pOLVgTE ��ER ' tor, "Royal Flush II" Concealed Pen ! Milli RETAINER — dent Sprinklers must be maintained ASSEMBLY �� and serviced in accordance with this % Ii ) section. _ _ Before closing a fire protection system E ' - I ; AIR main control valve for maintenance / �'■I iar. ��/ AND DUST . work on the fire protection system that �, 1N1- '_ SEAL it controls, obtain permission to shut •-- ------- �� LIP OF COVER down the affected fire protection sys- RETAINER PLATE tem from the proper authorities and FIGURE 5 notify all personnel who may be affect OPTIONAL AIR AND DUST SEAL FOR SERIES RFII(TY3551) ed by this action. Absence of the Cover Plate/Retainer If you must remove a sprinkler, do not Ordering Assembly can delay sprinkler opera- reinstall it or a replacement without re- tion in a fire situation, installing the Cover Plate/Retainer As- Procedure When properly installed, there is a sembly. If a Cover Plate/Retainer As- nominal 3/32 inch (2,4 mm)air gap be- sembly becomes dislodged during Contact your local distributor for tween the lip of the Cover Plate and the service,replace it immediately. availability. When placing an order, ceiling,as shown in Figure 2. The owner is responsible for the in- indicate the full product name. ection, maintenance o This air gap is necessary for proper their fire protelction s, anystem and devicf Sprinkler/Support Cup Assembly operation of the sprinkler. If the ceil- es in compliance with this document, Specify: Series RFIISIN), ing requires repainting after sprinkler P (specifyendeensure that the new paint as well as with the applicable stan- K=5.6, "Royal Flush II" Pendent Sprin- installation,does not seal off any of the air gap. dards of the National Fire Protection klers (specify) temperature rating and Association(e.g., NFPA 25), in addition (specify)finish, P/N(specify). Do not pull the Cover Plate relative to to the standards of any other authori- the Enclosure.Separation may result. ties having jurisdiction.Contact the in- 155°F(68°C1 200°F(93°C) stalling contractor or sprinkler manu- TY3531 51-792-1-155 51-792-1-200 Sprinklers which are found to be leak- facturer regarding any questions. TY3551 51-790-1-155 51-790-1-200 ing or exhibiting visible signs of corro- sion must be replaced. Automatic sprinkler systems should be Separately Ordered Cover Plate/ Automatic sprinklers must never be inspected,tested,and maintained by a Retainer Assembly: qualified Inspection Service in accor- painted, plated, coated, or other- dance with local requirements and/or Specify: (temperature rating from be- wise altered after leaving the factory. national code. low) Series RFII Concealed Cover _ Modified sprinklers must be replaced. Plate with(finish), P/N(specify). Sprinklers that have been exposed to 139°F(59°C)(a) 165°F(74°C)(b) corrosive products of combustion, but Grey White have not operated,should be replaced (RAL9002) 56-792-0-135 56-792-0-165 if they cannot be completely cleaned Brass 56-792-1-135 56-792-1-165 by wiping the sprinkler with a cloth or Pure White(c) by brushing it with a soft bristle brush. (RAL9010) 56-792-3-135 56-792-3-165 Signal White Care must be exercised to avoid dam- (RAL9003) 56-792-4-135 56-792-4-165 age to the sprinklers - before, during, Jet Black 1 and after installation. Sprinklers dam- (RAL9005) 56-792-6-135 59-792-6-165 aged by dropping, striking, wrench Brushed twist/slippage, or the like, must be re- Chrome 56-792-8-135 56-792-8-165 placed.Also,replace any sprinkler that Chrome 56-792-9-135 56-792-9-165 has a cracked bulb or that has lost Custom 56-792-X-135 56-792-X-165 liquid from its bulb. (Ref. Installation (a) For use with 155°F(68°C)sprinklers. Section.) (b) For use with 200°F(93°C)sprinklers. Exercise care to avoid damage to (c) Eastern Hemisphere sales only. sprinklers before, during, and after in- Sprinkler Wrench stallation.Replace sprinklers damaged Specify:RFII Sprinkler Wrench, by dropping, striking,wrench twisting, P/N 56-000-1-075. wrench slipping, or the like. Also, re- place any sprinkler that has a cracked Air and Dust Seal bulb or that has lost liquid from its Specify:Air and Dust Seal, bulb.(Refer to the Installation section.) P/N 56-908-1-001. GLOBAL HEADQUARTERS 1 1400 Pennbrook Parkway,Lansdale,PA 19446 Telephone+1-215-362-0700 - Copyright©2013 Tyco Fire Products,LP. All rights reserved. Vico TEFLON is trademark of The DuPont Corporation. tijco Worldwide w.tyco-fire.com Fire Protection Contacts Products Series TY-FRB, 5.6 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage • General NOTICE The TYCO Series TY-FRB Sprinklers "'. " - Description described herein must be installed and maintained in compliance with this doc- The TYCO Series TY-FRB,5.6 K-factor, ument, as well as with the applicable # Upright(TY313) and Pendent(TY323) standards of the National Fire Protec- Sprinklers described in this data sheet tion Association,in addition to the stan- k. `" are quick response,standard coverage, dards of any other authorities having decorative 3 mm glass bulb-type spray jurisdiction.Failure to do so may impair nu sprinklers designed for use in light or the performance of these devices. `mow ordinary hazard,commercial occupan- cies such as banks, hotels,and shop- The owner is responsible for maintain- _ ping malls. ing their fire protection system and devices in proper operating condition. The recessed version of the Series TY- The installing contractor or sprinkler FRB Pendent Sprinkler,where applica- manufacturer should be contacted with ble, is intended for use in areas with a any questions. finished ceiling.This recessed pendent sprinkler uses one of the following: Sprinkler • A two-piece Style 15 Recessed 7 r Escutcheon with recessed adjust- Identification ment up to 5/8 inch (15,9 mm)from the flush pendent position. Number (SIN) "" ,_ • A two-piece Style 20 Recessed Escutcheon with recessed adjust- TY313 Upright 5.6K, 1/2"NPT A. ,'„ ment up to 1/2 inch (12,7 mm)from TY323 Pendent 5.6K, 1/2"NPT ` the flush pendent position. - The adjustment provided by the Technical Rating Recessed Escutcheon reduces the TeTemperaturep a accuracy to which the fixed pipe drops Data 155°F(68°C) °C) to the sprinklers must be cut. 175°F(79°C) Intermediate level versions of Series Approvals 200°F(93°C) TY-FRB Sprinklers are described in UL and C-UL Listed 286°F(141°C) Technical Data Sheet TFP357. Sprin- FM, LPCB,and VdS Approved kler guards and shields are described CE Certified Finishes in Technical Data Sheet TFP780. Sprinklers with Polyester Finish are UL Sprinkler: Refer to Table A and C-UL Listed as Corrosion-Resis- Recessed Escutcheon:White Coated, tant Sprinklers. Chrome Plated,or Brass Plated Maximum Working Pressure Physical Characteristics 175 psi(12.1 bar) Frame Bronze 250 psi(17.2 bar)" Button Brass/Copper °The maximum working pressure of 250 psi Sealing Assembly Stainless IMPORTANT (17.2 bar)only applies to the listing by Un- Steel w/TEFLON Always refer to Technical Data derwriters Laboratories,Inc.(UL). Bulb Glass Sheet TFP700 for the "INSTALLER Discharge Coefficient Compression Screw Bronze WARNING"that provides cautions K=5.6 GPM/psis/2(80,6 LPM/bar1/2) Deflector Bronze with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and installation can permanently dam- age a sprinkler system or its compo- nents and cause the sprinkler to fail _ to operate in a fire situation or cause it to operate prematurely. Page 1 of 4 FEBRUARY 2014 TFP172 TFP172 Page 2 of 4 Components: *Temperature rating is ** Pipe thread connections per ISO 7-1 1 Frame 4 Bulb indicated on Deflector. can be provided on special request. 2 - Button 5 - Compression STYLE 15 or 20 3 - Sealing Screw ESCUTCHEON PLATE 1/2" 7/16"(11,1 mm) RECESSED Assembly 6 - Deflector* DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE-IN ESCUTCHEON * 1 6 .,r/___.... I 1 5 =I 7/16" R (11,1 mm) opil ��1 c 4 ` NOMINAL 2" �� I I MAKE-IN (50,8 mm) I �, simiwissimr 2 r i i el 2 1-3/8" I lir ii el (50,8 mm) 1 (34,9 mm) 3 Ifr 1 —� WRENCH 1 1 / I - FLATS t 1/2" NPT** DEFLECTOR* 2-7/8"(73,0 mm)DIA. . - CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT FIGURE 1 SERIES TY-FRB UPRIGHT(7Y313)AND PENDENT(TY323)SPRINKLERS 5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE L, Operation Installation The glass bulb contains a fluid which The TYCO Series TY-FRB,5.6 K-factor, RECESS expands when exposed to heat.When Upright(TY313)and Pendent(TY323) (USE ONLY the rated temperature is reached, the Sprinklers must be installed in accor- END"A) fluid expands sufficiently to shatter the dance with this section. / WRENCH glass bulb, allowing the sprinkler to General Instructions FIGURE 2 activate and water to flow. Do not install any bulb-type sprinkler if W-TYPE 6 the bulb is cracked or there is a loss SPRINKLER WRENCH Design of liquid from the bulb.With the sprin- kler held horizontally, a small air bub- Criteria ble should be present. The diameter WRENCH of the air bubble is approximately 1/16 RECESS The TYCO Series TY-FRB,5.6 K-factor, inch (1,6 mm)for the 135°F(57°C)and Upright(TY313)and Pendent(TY323) 3/32 inch(2,4 mm)for the 286°F(141°C) ��� Sprinklers are intended for fire protec- temperature ratings. _ tion systems designed in accordance Or with the standard installation rules rec- ognized by the applicable Listing or should be obtained by applying amin- Approval agency(such as, UL Listing mum to maximum torque of 7 to 14 is based on the requirements of NFPA ft.-lbs. (9,5 to 19,0 Nm). Higher levels 13, and FM Approval is based on the of torque can distort the sprinkler Inlet requirements of FM's Loss Prevention with consequent leakage or impairment PUSH WRENCH Data Sheets).Only the Style 15 or Style of the sprinkler. IN TO ENSURE 20 Recessed Escutcheon is to be used Do not attempt to compensate for ENGAGEMENT for recessed pendent installations. insufficient adjustment in the Escutch- WITH SPRINKLER eon Plate by under-or over-tightening WRENCHING AREA the sprinkler. Re-adjust the position of FIGURE 3 the sprinkler fitting to suit. W-TYPE 7 RECESSED SPRINKLER WRENCH Upright and Pendent Sprinklers The Series TY-FRB Upright and Pen- dent Sprinklers must be installed in accordance with the following instructions. Step 1.Install Pendent sprinklers in the pendent position. Install upright sprin- klers in the upright position. Step 2. With pipe-thread sealant applied to the pipe threads, hand- tighten the sprinkler into the sprinkler fitting. TFP772 Page 3 of 4 Step 3.Tighten the sprinkler into the 2-7/8" DIA. sprinkler fitting using only the W-Type - (73,0 mm) - 6 Sprinkler Wrench(Figure 2).With ref- erence to Figure 1,apply the W-Type 6 2-1/4" DIA. Sprinkler Wrench to the wrench flats. FACE OF — (57,2 mm) — Torque sprinklers 7 to 14 ft.-lbs.(9,5 to SPRINKLER 19,0 Nm). FITTING 5/8"(15,9 mm) Recessed Pendent Sprinklers 1 \ i FLUSH _1 The Series TY-FRB Recessed Pendent 3/8±5/16" / '� I 1 I Sprinklers must be installed in accor- (9,5±7,9 mm) dance with the following instructions. } / J� Step A.After installing the Style 15 or MOUNTING 71 �•–' 1/8 I Style 20 Mounting Plate over the sprin- SURFACE (3,2 mm) kler threads, and with pipe-thread "— I _ sealant applied to the pipe threads, CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) hand-tighten the sprinkler into the TY-FRB PLATE 3/4"(19,1 mm) sprinkler fitting. FIGURE 4 Step B.Tighten the sprinkler into the SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323) sprinkler fitting using only the W-Type WITH TWO PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15 7 Recessed Sprinkler Wrench (Figure RECESSED ESCUTCHEON 3).With reference to Figure 1,apply the W-Type 7 Recessed Sprinkler Wrench to the sprinkler wrench flats. Torque 2-7/8" DIA. sprinklers 7 to 14 ft.-lbs. (9,5 to 19,0 (73,0 mm) Nm). FACE OF "2.1/4DIA. SPRINKLER —_ Step C.After ceiling installation and fin- FITTING (57,2 mm) ishing, slide on the Style 15 or Style 20 Closure over the Series TY-FRB Sprin- 5/16±1/4" 1/2"(12,7 mm) kler and push the Closure over the (7,9±6,4 mm) Mounting Plate until its flange comes in + EN FLUSH contact with the ceiling. 1` `L` 1 . , Care and f j MOUNTING 1/8" ] Maintenance SURFACE ----- The (3,2 mm) The TYCO Series TY-FRB,5.6 K-factor, Upright(TY313) and Pendent(TY323) CLOSURE SERIES MOUNTING 1-3/8"(34 ,9 mm) Sprinklers must be maintained and ser- TY-FRB PLATE 7/8'(22,2 mm) viced in accordance with this section. FIGURE 5 Before closing a fire protection system SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323) main control valve for maintenance WITH TWO PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 work on the fire protection system RECESSED ESCUTCHEON that it controls, obtain permission to shut down the affected fire protection Modified sprinklers must be replaced. standards of any other authorities hav- systems from the proper authorities Sprinklers that have been exposed to ing jurisdiction. Contact the installing and notify all personnel who may be corrosive products of combustion,but contractor or sprinkler manufacturer affected by this action. have not operated,should be replaced regarding any questions. if they cannot be completely cleaned Absence of the outer piece of an by wiping the sprinkler with a cloth or Automatic sprinkler systems are rec- escutcheon, which is used to cover ommended to be inspected, tested, a clearance hole, can delay sprinkler by brushing it with a soft bristle brush. and maintained by a qualified Inspec- operation in a fire situation. Care must be exercised to avoid dam- tion Service in accordance with local The owner must assure that the sprin age to the sprinklers before,during,and requirements and/or national codes. klers are not used for hanging any after installation. Sprinklers damaged str , wrench twist/ objects and that the sprinklers are only slibppaopgeping,or like,ikmust be replaced. cleaned by means of gently dusting Also, replace any sprinkler that has a with a feather duster;otherwise, non cracked bulb or that has lost liquid from operation in the event of a fire or inad- its bulb.(Ref. Installation Section.) vertent operation may result. Sprinklers which are found to be leak- The owner is responsible for the ing or exhibiting visible signs of corro- inspection,testing,and maintenance of sion must be replaced. their fire protection system and devices in compliance with this document, as Automatic sprinklers must never be well as with the applicable standards painted, plated, coated, or other- of the National Fire Protection Associa- wise altered after leaving the factory. tion (e.g., NFPA 25), in addition to the TFP172 Page 4 of 4 P/N* 77 - XXX - X - XXX SPRINKLER TEMPERATURE FINISH RATINGS SIN 1 NATURAL BRASS 135 135°F(57°C) 370 5.6K UPRIGHT(1/2"NPT) TY313 3 PURE WHITE(RAL9010)**POLYESTER 155 155°F(68°C) 371 5.6K PENDENT(1/2"NPT) TY323 4 SIGNAL WHITE(RAL9003)POLYESTER 175 175°F(79°C) Use suffix"I"for ISO 7-1 connection; 9 CHROME PLATED 200 200°F(93°C) for example,77-370-4-175-I "Eastern Hemisphere sales only 286 286°F(141°C) TABLE A SERIES TY-FRB UPRIGHT AND PENDENT SPRINKLERS PART NUMBER SELECTION Limited Ordering Warranty Procedure For warranty terms and conditions,visit Contact your local distributor for avail- www.tyco-fire.com. ability.When placing an order,indicate the full product name and Part Num- ber(P/N). Sprinkler Assemblies with NPT Thread Connections Specify:Series TY-FRB Upright or Pen- . dent(specify)Sprinkler, SIN (specify), K=5.6,Quick Response, (specify)tem- perature rating, (specify) finish, P/N (specify,refer to Table A). Recessed Escutcheon Specify:Style 15 Recessed Escutcheon with(specify*)finish,P/N (specify*) Specify: Style 20 Recessed Escutch- eon with(specify*)finish,P/N(specify*) *Refer to Technical Data Sheet TFP770 Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387 Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001 GLOBAL HEADQUARTERS 1 1400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright©2014 Tyco Fire Products,LP. All rights reserved. t//'o TEFLON is trademark of The DuPont Corporation. "f Fire Protection Products Eddythread 40 A Lightweight Schedule 40 Replacement Pipe That Has a Corrosion Resistance Ratio of 1.0 Bull Moose Tube Company has been making pipe for a long time and is recognized as a producer of quality pipe products. Eddythread 40 is designed with the same thoroughness as our other fine pipe products and now our customers have an option to buy a carefully designed replacement for Schedule 40 that: • Has a Corrosion Resistance Ratio of 1.0 • Has a Pressure Rating of 300 psi • Is Lighter Weight Than Schedule 40 • Is Approved by Factory Mutual and Listed by Underwriters Laboratories • Is Produced in Accordance to ASTM A-135 and A-795 • Can be Used With Standard Schedule 40 Threaded Fittings, Couplings and Valves • Is Produced From Steel With Excellent Properties of Strength and Threadability • Can be Used in Wet, Dry, Preaction, and Deluge Type Sprinkler Systems* • Offers Lower Freight Costs EDDYTHREAD 40 SPECIFICATIONS .IsioitioNA1r 12E(E I , (in) BUNDLE SIZE 1 1.461 1.083 70 1 1/4 2.070 1.418 51 1 1/2 2.547 1.654 44 2 3.308 2.123 30 CORROSION RESISTANCE RATIOS NOMINALSCHEDULE E 1 1.00 1.00 1 1/4 1.00 1.00 1 1/2 1.00 1.00 2 1.00 1.00 *Eddythread 40 can be hot dipped galvanized to meet FM's requirement for dry systems $( 46 1819 Clarkson Road For additional information, C �L us Chesterfield,MO 63017 contact your salesperson today at �� (800)325 4467 (800)325-4467 or(636)537-2600 LISTED 1 f BULL MoosE TUE COMPe►niv FAX:(636)537-2645 in the USA,or from Canada CJ www.bullmoosetube.com call(800)882-4666 411> A CAPATO company e-mail:sales(bullmoosetube.com APPROVED All information contained herein is accurate as known at the time of publication. Bull Moose Tube reserves the right to change product specifications without notice and without incurring obligation. 8/08 ... • •Ductile Iron Threaded Fitton s ..... . . ,.... ... . ... • . ..._........ ..., .... ., .. ...... ..,.._ .. . . . .. ....v. . h ��. , ,. ,rt;# §fit ar t ' t+,# ity • • yam ; { �, � I I_I ( ) 41,) b ® 1+ex 1 41. r � %, ,r, ,w: $ ., �.. .:5 °'� .. 7t w4.+ RU:2#rii,1,,,u x,"#w= ", 2 .w.. H .3 ,. korl, Ductile Iron Threaded Fittings S F ,tifications • > branded ductile iron threaded fittings are UL Listed and FM Approved at 500 psi • Rated to 300 WSP ckILus • Ductile iron castings conform to ASTM A536 LISTED • Fitting dimensions conform to ASME B16.3 • Bushings and plugs conform to ASME B16.14 444t:;° ' • Fittings are 100% air tested APPROVED • NPT threads on all fittings conform to ASME B1.20.1 • Independent lab verification that fittings meet applicable chemical&physical properties • Manufacturing facilities are ISO 9001:2008 and ISO 14001 rrTemperature Working Pressure, Nonshock psiG Degrees F , 300#Class Threaded Fittings -20 to 100 500 >. 500 200 480 250t. 4r del , ' Wit: 300 440 350420 400 400 '1a �x � 40 500 360 349,teiA '.. 600 320 650 t, 4.4 k00 SCI. ` Ductile Iron Fittings-Class 300 UL/FM . I rWS:ai C US 4> APPROVED Fig. 35E 3-90°Elbow LISTED IlkA Size A Packing , Weight in Part Number in Inner Master lb II___',44a1!2 35E 3004 1.13 100 200 0.2 1 3/4 35E3006 ! t1.31 70 140 0,3 1 5 A 1 35E 3010 1.50 40 80 0.5 I l 17,1/4 `35E3012 1.75 25 50 :„ ` 0.8 1-1/2 35E 3014 1.94 18 36 1.1 '2Y; 35E 3020 2.2 10 .20 1.8';h 2-1/2 35E 3024 2.70 4 8 3.2 Fig. 35RE3-90°Reducing Elbow B Size �_ kr. BPacking Weight < > in Part Number in in Inner Master Ib Iii®• 3/4 x 1/2 358E3006004 1.20 1.22 80 160 0.3 Il'X 1/2 35RE3010004 1.26 1.36 70 r140 ' 0.4 k. IA 1 x 3/4 35RE3010006 1.38 1.45 50 100 0.4 111 I!i 1-1C4 x1J2 �,35RE3012004 1.34 x. 1.53 - 1 '35 70.,. 0.5 1-1/4 x 3/4 35RE3012006 1.45 1.63 35 70 0.6 1-1/4x 1 ,, 35R6b12010 x .X, , 1.58„ 1,0;.r30 _`0.n.. 1-1/2 x 1/2 35RE3014004 1.52 1.75 30 60 0.6 „.1,1:-'11/2)c 3/4 350E3014006 X 5 ,2 ,fit{m 5.ww" 25 ` 50 h`'0 7' 1-1/2 x 1 35RE3014010 1.65 1.80 20 40 0.8 11/2 34' `1/4 ".35RE3b1,,4it':. 1.82 1.86. <r2,.. 18 30 ,1.0 2 x 1/2 35RE3020004 1.60 1.97 18 36 1.0 2,,,x 3/47 35E1E3020006 :,,!1,60'-'4 1,97. 4§,,,,,,,,,,,!. k06 ;' 1.0 2 x 1 35RE3020010 1.73 2.02 16 32 1.2 ) 3. rx'2 0-1/4 30E3020012 1.90 2.10 1.,1-i ' 4 1.3 i I 2 x 1-1/2 35RE3020014 2.02 2.16 10 20 1.5 12-1/2X`1 1/2 35RE3024014 2.16-7;',1,-;„„ 2.51 , 64, i'-' .2 1': 2-1/2 x 2 35RE3024020 2.39 2.60 6 12 2.5 Fig. 35F 3-45°Elbow Size A Packing Weight Part Number,r ''°1 q in ;# in. Inner ,; Master lb 4' . • 1/2 35F 3004 0.88 150 300 0.2 3/4 ''.''-g.._3006 '' 8 80 w ' 0.3 t �® 1 35F 3010 1.13 40 80 0.5 1-1(4 35F O. dt`$: 1.29 4,.„4.7:::7,125 50' 4.7 ,... I IA 1-1/2 35F 3014 1.44 20 40 1.0 I_I 2 eta 36F3020 16.9 10 20 `1.6' 2-1/2 35F 3024 1.95 4 8 2.7 Fig. 35T 3- Tee Size A Packing - Weight Part Number ins. in " Inner Master '; lb MI 1/2 351 3004 1.13 80 160 0.3 3/4 35T 3006 =" 1.31 30 66:i'; •:,••:, 0.5 ' II �I 1 35T 3010 1 50 25 50 0.7 °..• 1-1/4 35T_3012 7,75 ,:10 20' 1.1 A I A 1-1/2 351 3014 1.94 10 20 1.5 ' :t2 ` , 35T 3020 2.25 6 x; >12` 2.4, 2-1/2 35T 3024 2.70 4 8 4.3 111 SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com Ductile Iron Fittings-Class 300 UL/FM g QUALrrt C ID)US 411> APPROVED • A Fig. 35CP3 -Straight Coupling with Ribs usTEo Size A Packing -:',i," Weight " Part Number i inn Inner Master Ib 1/2 35CP3004 1.38 200 400 0.1 ;3/4 35CP3006 1.63 100 200., . . 0.2 1 35CP3010 1.75 60 120 0.4 i>1/4 35CP301,2 ,,; .- 2.00 .^^>35-, X70 7 0.5. 1-1/2 35CP3014 2.19 2550 0.7 2 £%{ 35CP3020 1_ x.62 , '15 30 1.2r 2-1/2 35CP3024 3.00 9 18 2.2 Fig. 35RC3 -Hex Reducing Coupling Size ` Part Number A • -. Packing Weight (j\ in ,Inner - Master Ib• A1 x 1/2 35RC3010004 1.69 80 160 0.3 "i,3i;3/4 3,5RC3010Q0fr" .,1,69. : 60x1:,' i-,„': 120J,...,7„ 0.4 1-1/4 x 3/4 35RC3012006 2.06 40 80 0.6 2 x-1�oot hex) 35R302ó010 r''' -...;.,...„2,814,„ 20'; 40, "1.0 Fig. 35HB3 -Hex Bushing Size �. .A` ,,ri Packing 4 , Weight l'', i '%Part Number , ;in Q h Inner Master ",` lb h$ B 1 x 1/2 35HB3010004 1.06 180 360 0.2 �i1 x 3/ --;38H886-166'68': ,-- 1.06 ',A"' A 180 ' `' $;360 ,;^:. . 0.1 i 1 �A 1-1/4 x 1 r 35HB3012010 1.19 90 180 0.2 1-1/21 1 " 35HB3014010 1,2Snnnn, . . X75 - < 1150 0, (�` IIP 1-1/2 x 1-1/4 35H B3014012 1.25 75 150 0.3 { # 3' 2x1 ` -" 35HB3020010A„ .. 1.58AA. ..,AAA* kz 80 06 .4 2 x 1-1/4 35HB3020012 1.38 40 80 0.6 I2-z 1-1/2 z. 35HB3020014, 1.38,. 40AA •, 80 '. --,'''6.6 II Fig. 35SP3 Square Head Plug Size .x til Packing "� Weighte �Part Number �_ ,'�` in , A , in Inner . Master lb 1.4r21 1/2 35SP3004 0.94 600 1200 0.07 TIT A ,44.3/4 ,x x, 3 SP3906 r 1.1 , 350r ,,„„„ `760 A. 0.1 1 35SP3010 1.25 200 400 0.1 1- 2 37 100 ,` 0.3 -1/4 . 365P3012r ;5 , 1-1/2 35SP3014 1.44 80 160 0.4 2 3SP 020 51.'0.=w # :5;45-5' ,'90 41."''' 60 Fig. 35U 3-Union with Brass Seat A A Packing' ;r ` Weight > f'Size s Part Number .. Pull in ,an in Inner =Master Ib 35U 3010 2.19 20 40 1.0 _ 1 1-1/2 35U 3012 7 2.62 x;'15 nn- 30 : 1.2 1-1/2 35U 3014 2.62 10 20 1.7 �� 2 � 35Lh3020 3.12 6 , 12 2.4 113 SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com .1 Ductile Iron Fittings- Class 300 UL/FM 1 QIIAL I Pi * . C el US 41> APPROVED - Fig. 35X 3— Cross USTED � 4I�� Size A Packing Weight _ Part Number —��/' JA in . in Inner Master lb I 1 35X 3010 1.50 20 40 0 9 Y" 1 1-1/4 35X.3012 N 1.75 1224 ,:- 1.4 I II I 11I 1-1/2 35X 3014 1 94 8 16 1.8 * NI( Jq 2 35X" 3020 2.25` 6 12 2.6 H c B Fig. 35RX3—Reducing Cross __ ` Size Part Number A B Packing Weight ■■! in � in , -In Inner Master lb 1 1/4 x 1 35RX3012010 1 67 1.58 15 30 1.2 -i I q 35RX302 1-1/21 4410 1.80 s; , `1.66" 2 r''24 1.4 t' 0010 2.02 1.73 8 16 2.0 o!r 1 n; Fig. 35C 3—Cap Size `` Part Number A Packing Weight ® in' , in ., Inner Master lb 1/2 350 3004 0.87 300 600 0.1 ¢. 1 a JA 31/4 35C 3006 , s°0.97` 200 .. =4"00 0 qtr K tom" �� 1 350 3010 1.16 110 220 0.2 1-1/4 °'>ef- 350,.p012 f,r.. ' 1.28 .,;.. .70, ,, 140 , ,0.4,, .f f, 1-1/2 35C 3014 1.33 50 100 0 5 ?; 35C#00214;: 1.45 �,2.. e 50 0.8 2-1/2 35C 3024 1.70 18 36 1.6 ;',MI ' 1 Fig. 35BC3—Beam Clamp Size A Packing ' ' .Weight AI ��� . Part Number: in 3 Innern = Master lb _ �; 3/8 35BC3003 0.75 100 200 0 3 ®i'' •1 '80 - 60 f:� ' 0.5 "�"'"112 4`. 35BC3004V .:;0.7a r. • SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com 114 Pipe Hangers Fig.200- "Trimline"Adjustable Band Hanger (B-Line Fig.B317ONF) ®TOLco . Fig.200F- "Trimline" Adjustable Band Hanger with Felt Lining (B-Line Fig.B317ONFF) cCus - Fig.200C- "Trimline" Adjustable Band Hanger with Plastic Coated (B-Line Fig.B317ONFC) US-TED Fig.200S - "Trimline" Adjustable Band Hanger with Non-Captured Nut Size Range: Fig.200 - 1/2" (15mm)thru 8" (200mm)pipe Material: Steel, Pre-Galvanized to G90 specifications ,, ' Function: For fire sprinkler and other general piping purposes. Knurled ,---, V" swivel nut design permits hanger adjustment after installation. ' Features: • (1/2" (15mm)thru 2" (50mm)) Flared edges ease installation for all pipe `'' ' / types and protect CPVC plastic pipe from abrasion. Captured design �, 11 " keeps adjusting nut from separating with hanger. Hanger is easily B �' installed around pipe. A For hanger with non-captured nut order Fig. 200S. I ; • (21/2" (65mm)thru 8" (2oomm)) Spring tension on nut holds it securely in ‘ - hanger before installation.Adjusting nut is easily removed. Approvals: Underwriters Laboratories listed (1/2" (15mm)thru 8" (200mm)) Fig.200-1/2.200-s/4 in the USA(UL)and Canada(cUL)for steel and CPVC plastic pipe and Fig.200-1 to 200-2 Fig.200-21/2 to 200-8 Factory Mutual Engineering Approved (FM) (3/4" (20mm)thru 8" (2oomm)). Conforms to Federal Specifications WW-H-171 E&A-A-1192A,Type 10 and Manufacturers Standardization Society ANSI/MSS SP-69&SP-58, Type 10. Maximum Temperature: 650°F(343°C) , Finish: Pre-Galvanized. Stainless Steel • ` f materials will be supplied with (2) hex nuts '. in place of a knurl nut. • - Order By: Figure number and pipe size . , • Designed to meet or exceed requirements of 4• FMDS2-0. • . . Fig.200 6 Fig.200C Fig.200F Pipe Size Rod Size A B Approx.Wt./100 Part No. in. 1mm) in. (mm) in. (mm) lbs. (kg) ' 2001/2 1/2" 115) 3/e"-16 31/e" (79.4) 25/8° (66.7) 11 (5.0) 1_ 200-3/4 3/4' (20) 3/8"-16 31/8" (79.4) 21/2" (63.5) 11 (5.0) 200-1 1" 1251 3/8"-16 33/e" (85.7) 25/8" (66.7) 12 (5.51 200-11/4 11/4" (32) 3/E"-16 33/4" (94.0) 27/8" (73.0) 13 (5.9) 200-11/2 11/2" (40) 3/8"-16 32/8" (98.4) 22/8" (73.0) 14 (6.4) : + 2004 2" 150) 3/8"-16 41/2" (1143) 3" (763) 15 15.9) 20041/2 21/2" 165) 3/8"-16 55/8" (142.9) 41/8" (104.7) 27 (123) ' 200-3 3" (75) 3/8"-16 51/8" (149.1) 4" (101.6) 29 (13.3) Fig.200S 200-31/2 31/2" 190) 3/8"-16 73/8" 1187.3) 51/4' (133.3) 34 (15.6) 200-4 4" (100) 3/8"-16 73/s" (187.3) 5" 1127.0) 35 (16.0) 200-5 5" (125) 1/2"-13 91/8" (231.8) 61/4" 1158.7) 66 (30.2) 200-6 6" (150) 1/2"-13 101/8" (257.2) 63/4" 1171.4) 73 (33.4) 200-8 8" (200) 1/2"-13 131/8" (333.4) 83/4" (222.2) 136 (62.3) - All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. , B-Line Fire Protection Solutions 21 by E' '1•N Threaded Accessories y B3205 -Threaded Rod (right-hand threads - both ends) (TOLco Fig.103) B3205L-Threaded Rod (right& left hand threads) / TL l Size Range: 3/8"-16 thru 3"-4 rod Specify Length � l��l' Material: Steel Function: Recommended for use as a hanger support in hanger assemblies. • TL �� Rod is threaded on both ends with right hand threads of the length shown.Also lll'll1)l A available with left and right hand threads-specify Fig.B3205L when ordering. V' Thread Size Maximum Temperature: 750°F(399°C) Finish: Plain.Contact B-Line for alternative finishes and materials. Order By: Part number, rod size,length and finish Standard Design Load Thread Size Thread Length TL 650°F(343°C) 750°F(399°C) Part No. A in. (mm) Lbs. (kN) Lbs. (kN) 83205-3/4x'L':'`_:` 3/8"-16 21/2" (63.5) 730 (3.25) 572 (2.54) 03205-112 x'124 1/2"-13 21/2" (63.5) 1350 (6.00) 1057 (4.70) 83205-5/8 x'L'."' 5/8"-11 21/2" (63.5) 2160 (9.61) 1692 (7.52) B3205-3/4,x I',: 3/4"-10 3" (76.2) 3230 (14.37) 2530 (11.25) B32051/8 x'L' 7/e"-9 31/2" (88.9) 4480 (19.93) 3508 (15.60) B3205-1'X'L';' 1"-8 4" (101.6) 5900 (26.24) 4620 (20.55) B3205-11/e x'L' 11/8"-7 41/2" (114.3) 7450 (33.14) 5830 (25.93) B3205-11/4-x'L' 11/4"-7 5" (127.0) 9500 (42.25) 7440 (33.09) B3205-11/2 x'L' 11/2"-6 6" (152.4) 13800 (61.38) 10807 (48.07) 03205-15/4 x'L' :'`` 13/4"-5 7" (177.8) 18600 (82.73) 14566 (64.79) B3205-2 x'L' 2"4/2 8" (2032) 24600 (109.42) 19625 (87.29) B3205-21/4 x'L' '' 21/4"-41/2 9" (228.6) 32300 (143.67) 25295 (112.51) 83205-2112 x'L' „r' 21/2"-4 10" (254.0) 39800 (177.03) 31169 (138.64) B3205-23/4 x'L' 23/4"-4 11" (279.4) 49400 (219.73) 38687 (172.08) B3205-3 x'L' ,s 3"-4 12" (304.8) 60100 (267.32) 47066 (209.35) ATR - All Threaded Rod 120" (3.05m) Lengths (TOLCO Fig.100) Fig.99 -All Threaded Rod Cut To Length �� �`�D ,;moi; .4 111111111111 �1, \"111111111111 Size Range: 3/8"-16 thru 11/2"-6 rod in 120"(3.05m)lengths or cut to length �hD�l� Material: Steel 1�1�� H vd Maximum Temperature: 750°F(399°C) a o Finish: Plain.Contact B-Line for alternative finishes and materials. s u Order By: Part number,rod diameter and finish a Part No.-Size x Length Threads Recommended Load Approx.WtJ100 Ft. ATR Fig.99 Per Inch Lbs. (kN) Lbs. (kg) ATR 1/4"x 120 99-114,,x length 20 240 (1.07) 12 (5.44) ATR 3/s"x 120 99-3/s"x length 16 730 (3.24) 29 (13.15) ATR1/2"x 120 99-1/2"x length 13 1350 (6.00) 53 (24.04) ATR 5/a"x 120 99-5/a"x length 11 2160 (9.60)` 89 (40.37) Pt,3/4"x 120 =, ,,99-3J4"x length 10 3230 (14.37) 123 (55.79) ATR 7/e"x 120 99-7/a"x length 9 4480 (19.93) 170 (77.11) „ ATR 1"x 120 , 99.1"x length 8 5900 (26.24) 225 (102.06) - All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. B-Line Pipe Hangers&Supports 236 Revised 4/28/2014 by • vETM