SUBMITTALS
BUILDING DIVISION
DATE 9/21/2017
SUBMITTALS
• AC-1 AND AC-2
t
2615 NW St. Helens Road Portland, Oregon 97210 (503) 220-0855 FAX (503) 220-0260
www.heinz-mech.com
al R-410A Refrigerant
AIRSYS Wall Packaged Units
Equipment Cooling Solution with Integrated Free Cooling, 3kW - 18kW
. _ :is , . = . 7----,-.--%--- -.:-...-..-,--„....
-. y_ 1_: .,'_<-= z
Annual OperatingCost r ::i — r _
4000 tea- .---= -` , :n9,, ---4,--!'-;-,:-i.}"..---,--0-;--_=, =.:- l:,'1;, . ...
..- -- : -r .-... - - ....... .. .... .
M':
30 ''
._,:
$1,000
$tiH _ '-.. .=
_ -_;_ ;.; �'- _ -;r=,ter:
Conve anal Alrsys r• '_ '_
No Eco - Econ off ;.YF. - .S. - '�- F .... 7.,; ';a ;; .;,.w ..
Basedont 'pinenttientload,$O;IU - - - - -.
u
Highest Efficiency for Equipment Rooms
III Integrated variable capacity economizer system with an EER
(btu/kW) as high as 200
III Designed specifically for computer/equipment environments;
cooling capacity heavily shifted toward sensible heat removal
III Top exhaust design allows for more efficient heat removal
while maintaining constant room temperature, significantly
increasing the efficiency of both DX and Free Cooling
■ All units are certified to AHRI390 Standard
Feature Highlights 1 --'"-
Wrap-around Condenser Coil EC Supply Fan Top Exhaust/Bottom Throw Design
Aluminum finned copper coil with wrap- Quieter,more efficient variable speed EC fans Taking advantage of simple physics(hot air
around design allows maximum surface heat are standard on all models providing a highly rises),the top exhaust,bottom throw design
exchange.10 fin per inch spacing minimizes favorable energy efficiency curve when increases the temperature difference across the
collection of dirt and debris. compared to conventional AC fans. heat exchanger and increases overall system
Integrated Free Cooling Economizer Dual Layer Exterior Protection efficiency by as much as 15%when compared
Standard on all units,the highly configurable Galvanized steel exterior coated with an to bottom exhaust systems.
economizer features seamless transitions and additional layer of thermoset polymer
a variable capacity up to 100%rated supply provides two layers of protection against
fan air volume. corrosion. RSYS
Robust Short Cycle Detection Extreme Temperature Range ,
Built-in protection circuit protects the Designed for operation between-30°F and Expert In ICT Cooling
compressor from brownouts and power 127°F ambient temperature.
transfers as short as 0.08s.
,r
Wall Packaged Units Product Specification
f
MODEL NUMBER NOMENCLATURE
1 3 5 7 9
M-OD.13E1 C3DR41 0.230/1/60.AC
2 4 6 8
1 M-OD Product series name:M OD=MOBILECOOL-OUTDOOR:Packaged air conditioner with fresh air free cooling.
2 13 Unit nominal total cooling capacity in kW
3 El Compressor type&qty El=Hermetic scroll compressor qty 1;R1=Rotary compressor qty 1
4 C3 Cabinet size code:There are 4 cabinet sizes:Cl,C2,C3&C4.
Control Configuration: 0=Obit is designed to operate in a Dual control environment(aka Lead/Lag operation)
6 R410 Refrigerant: R410=R410a.
7 230/1/60: `AC Power source 230/1/60 i 208/230V Single Phase 60Hz AC Power Source
8 AC Supply Fan configuration: DC=DC EC fan;AC=AC EC fan. (EC=Electronically commutated variable speed fan)
9 Special code: Utilized to designate unit customization(nonstandard configuration)
COOLING CAPACITY
Cooling Mode Full Compressor(1)(2) Free Cooling(2) Free Cooling(2)(3)
Outdoor 95"F 70"F <50"F
Temp
Total Sensible Sensible
NominalSensible Capacity
Capacity Capacity EER ' EER Capacity EER
Model Tonnage Btu(kW) '; Btu(kW) Btu(kW) Btu(kW)
AC Supply Fan
3R1C1DR410.230/1/60.AC 1 12200(3.6) 10500(3.1) 10.1 12600(3.7) 70.0 10500(3.1) 375
5R1C1DR410.230/1/60.AC 1.5 18000(5.3) 15600(4.6) 10.0 14700(4.3) 43.2 15600(4.6) 216
7E1C2DR410.230/1/60.AC 2 27600(8.1) 24200(7.1) 10.2 26200(7.6) 29.1 24200(7.1) 182
M 9E1C2DR410.230/1/60.AC 2.5 32400(9.5) 29600(8.7) 10.2 30400(8.9) 33.8 29600(8.7) 199
OD 13E1C3DR410.230/1/60.AC 3.5 46000(13.5) 40900(12.0) 10.0 32500(9.6) 36.1 40900(12.0) 151
48E1C4DR410 23tt/1/64C-1 a 61 00(17.9) 56200(16 5) ',id:6 48200(141 26.8 56200(16 5j 125
18E1C4DR410.230/3/60.AC 5 60000 (17.6) 52600(15.4) 10.0 48200(14.1) 26.8 52600(15.4) 127
18E1C4DR410.460/3/60.AC 5 61000(17.9) 53200(15.6) 10.0 48200(14.1) 26.8 53200(15.6) 127
DC Supply Fan
9E1C2DR410.230/1/60.DC 2.5 31000(9.1) 27200(8.0) 10.2 24500(7.2) 51.0 27200(8.0) 243
M-
3.5 3.5 46000(13.5) 39500(11.6) 10.1 36300(10.6) 37.8 39500(11.6) 190
OD
13E1C3DR410.230/3/60.DC 3.5 47500(13.9) 39200(11.5) 10.0 36700(10.8) 38.2 39200(11.5) 193
(1)Total Capacity and EER rated according to AHRI Standard 390
(2)All data based on 80°F return temperature.Free Cooling Capacity based on Lead/Lag Configuration
(3)Free Cooling Capacity reduced to match 100%DX Capacity
Contact:AIRSYS North America Phone:(855)874-5380 Page 2 of 4
Email:ASNSupport@air-sys.com Web:www.airsysnorthamerica.com Rev 2.6.1 01/2017
•
Wall Packaged Units Product Specification
ECHNICAL DATA
Compressor Evaporator Fan Condenser Fan Electric Heater(1) Refrigerant Noise(2)
Current Current Air Current Air kW Current Indoor Outdoor
(A) (A) Volume (A) Volume Def/(Opt'l) (A) lbs. (dBA) (dBA)
Model (CFM) (3) (CFM)
AC Supply Fan
3131C1DR410.230/1/60.AC 4.2 0.8 600 1.2 2050 1.5/(2.4) 6 6.5/10.4 3.3 50 60
5R1C1DR410.230/1/60.AC 6.7 1.1 6 700 1.2 2050 1.5/(2.4) 6 6.5/10.4 4.2 50 60
7E1C2DR410.230/1/60.AC 9.3 2.9 1250 1.2 2200 5/(2.4) 21.7/10.4 6.2 50 60
Ni.. 9E1C2DR410.230/1/60.AC 10.5 2.9 1450 2.7 3700 5/(2.4) 21.7/10.4 6.8 56 61
OD 13E1C3DR410.230/1/60.AC 16.5 2.9 1550 2.7 6 3700 5 21.7 8.2 56 61
8E1C4DR410230/1/60.AC 21 3 5 8 '437-12300 ,..',!,,,,„.8.,3 4500 , 5, 21.7 i 11.0 55 •,,r 60
18E1C4DR410.230/3/60.AC 12.6 5.8 2300 3.8 4500 5 12.6 11.7 55 60
18E1C4DR410.460/3/60.AC 6.3 5.8 2300 3.8 4500 5 6.3 14.5 55 60
DC Supply Fan
9E1C2DR410.230/1/60.DC 10.8 10.0 1170 2.7 3700 5/(2.4) 21.7/10.4 6.8 56 61
M 13E1C3DR410.230/1/60.DC 16.5 20.0 1730 2.7 3700 5 21.7 8.2 56 6 61
OD
13E1C3DR410.230/3/60.DC 11.0 22.0 1750 2.7 3700 5 12.6 8.2 56 61
(1) Optional
(2) Ambient Temperature=95"F,6.5ft away from unit in open space
(3) Measured with 2"pleated filter standard on all models
ELECTRICAL RATINGS ,.
ELECT.HEAT 1.5 KW 2.4kW 5 KW
AC 48VDC AC 48VDC AC 48VDC
Model MCA I MFS MCA I MFS MCA I MFS MCA , MFS MCA I MFS MCA I ,MFS
AC Supply Fan
3R1C1DR410.230/1/60.AC. 10 15 -- -- 15 20 -- -- -- -- -- --
5R1C1DR410.230/1/60.AC 11 15 -- -- 15 20 -- -- -- -- -- --
7E1C2DR410.230/1/60.AC -- -- -- -- 17 25 -- -- 31 35 -- --
M_ 9E1CZDR410.230/1/60.Ac -- -- -- -- -- -- -- 31 35 -
OD'' 13E1c3DR410.230/1/60.AC' -- -- -- -- -- -- -- -- 32 40 -- --
z. 37 18�14O411230/1/60.AC r . .ti . ,
18E1C4DR410.230/3/60.AC -- -- -- -- -- -- -- -- 28 40 -- --
18E1C4DR410.460/3/60.AC -- -- -- -- -- -- -- -- 18 25 -- --
DC Supply Fan
9E1C2DR410.230/1/60.DC -- -- -- -- 18 30 7 10 _ 28 35 7 10
M 13E1C3DR410.230/1/60.DC -- -- -- -- -- -- -- -- 28 40 14 20
OD - -
13E1C3DR410.230/3/60.DC -- -- -- -- -- -- -- -- 17 25 14 20
*MCA=Minimum Circuit Ampacity(Wire Size Amps) MFS=Maximum Fuse Size or HACR circuit breaker
FILTER SIZES
Cabinet Size Filter Qty Nominal Size(in) Exact Size(in)
Cl 1 16x16x2 15%x15'/:x134
C2 1 25x18x2 24%x171,4x13/4
C3 2 16x16x2 15%x15%x1%
r ,„ . . .. 20X 16x 25. x 1%%. . :.,.
Contact:AIRSYS North America Phone:(855)874-5380 Page 3 of 4 _
Email:ASNSupport@air-sys.com Web:www.airsysnorthamerica.com Rev 2.6.1 01/2017
,
Wall Packaged Units Product Specification
UNIT DIMENSIONS
a
RETURN AIR
-...--11•M . affight,-Ir!!!-110111111.1 \ Mb.----.01111111111
P y • ‘,,.
............ \ . 4^
iiiiiiiiiiii
3#W
[f1.38')ia wring
=MIL.,
1a-41Z
[00:47')
11111111.
in
W II D B
CONDENSER DISCHARGE SUPPLY Al C
Cabinet Size Cl C2 C3 C4
Unit of measurement mm in mm in '" mm in mm in
Width W 700 27.6 1010 39.8 1160 45.7 mi.„1360 t, : , 'S3, .KS,
Depth D 620 24.4 700 27.6 700 27.6 ,704S a 12-t ..
Height H 1930 76.0 2130 83.9 2130 _ 83.9 SS 21'370 N' ,.
A` 200 7.9 268 10.6 268 10.6 . . ; 2 ; O _,. ,
Supply B 450 17.7 708 27.9 759 29.9 884 7
C 300 11.8 356 14.0 356 14.0 ::.356 '.,_. ir'14.0
Return B 450 17.7 708 27.9 759 29.9 ..: .;880_ ,...FII 344.7. ,,<'
E 1000 39.4 1104 43.5 1104 43.5 ,.3104! ,. ,x. .43.5, ,::
F 133 5.2 101 4.0 101 4.0 111-4., -1r-2-4.0 ,._._
G 660 26.0 970 38.2 1120 44.1 ,,...71.-:-,26,-.;...!, '.,-.5„.I', 52:,£ .
I 350 13.8 400 15.8 400 15.8 400 F ,,,:z--X'-::8:t1113
J 226 8.9 178 7.0 178 7.0 1. 6 _.` 4 _;.
K 101 4.0 101 4.0 101 4.0 .,01.01SS„ ,4.01 =;
1 87 3.4 87 3.4 112 4.4 .,-: 112. '',1;'.. S 4.4£, ..'"
M 80 3.2 _ 80 3.2 80 3.2 5' 0 r .„ F 'K.32.
N 1800 70.9 1999 78.7 1999 78.7 19 -1t: 781:4, 1
O 1815 71.5 2017 79.4 2017 79.4 2017,,n i 79,4. ,U
UNIT WEIGHT
13E1C3. 13E1C3.
Size 3R1C1 5R1C1 7E1.C2" 9E1C2' 18E1C4
xx.AC xx.DC
lbs. 355 370 515 530 616 635 ` 2},,
kg 161 168 234 240 279 288 , 2y.
Contact:AIRSYS North America Phone:(855)874-5380 Page 4 of 4
Email:ASNSupport@air-sys.com Web:www.airsysnorthamerica.com Rev 2.6.1 01/2017
AIRSYS Lead/Lag Controller (ASLLC.2A ASLLC.2A.48)
For AIRSYS Wall Packaged Units
Product Overview
F. Microprocessor based controller with automatic
changeover between lead and lag unit to balance system
run time and provide redundant operation for electronic
equipment rooms.
F- Dynamic free cooling setpoints and fan speed to match
the exact heat load throughout the day, thereby
maximizing free cooling time and system efficiency.
;, Seamless changeover between free cooling, partial free
cooling, and mechanical cooling.
::• '�" 'IIflit ' a o s ward confI t lc • used t
o ler(AsLLC} -naxim + vailabi = •#
NRS A €ior P be tween the lead
ill rtoar.�
--- fa-"''Work
. �- , _ of bo _ ,the backup
• ea. a s e etotake• thallt
Feature Highlights =
Customizable Operation System Step Test Rugged Construction
More than 200 configurable parameters allow Step-by-step testing mode allows anyone to Industrial controller with surge protection of
complete flexibility of system operation and easily and systematically verify all major HVAC up to 3000V.Polymer layered steel frame
alarm reporting.Advanced settings are passcode functions on both lead and lag units in 5-10 provides corrosion resistance for large range
protected. minutes. of operating environment.
Remote Monitor/Control Self-Diagnostics and Log Storage
Dry contact outputs available for major alarms. Self-diagnostics with 30+alarms to clearly
Default serial card allows for remote monitoring indicate component in need of attention.Up
and control of system performance and alarms to 200 alarm log entries are stored with time A I RS'V'S
through RS485(MODBUS).Optional Ethernet stamp for diagnostics and preventive
Expert In module allows communication through HTML, maintenance. ICT oIn
SNMP and TCP/IP protocols.
AIRSYS LEAD LAG CONTROLLER (ASLLC.2A ( ASLLC.2A.48) Product Specification
Technical Data
y.,, .• .,_ �. "� , . {. �• .� �h �. gym. ,
Compatible with all AC fan WPU Compatible with all WPU
(WPU Model:M-OD.xxxx.AC)
Model Number ASLLC.2A ASLLC.2A.48
Power Input 120/230VAC 120/230VAC and/or 48VDC
Certification UL/CSA/CEUL/CSA/CE
Max Current 0.5A 0.5A
Height 580 rim/22,8 in 580 mm/22.8 in
Width 410 mm/16.1.in 410mm/16.1in
Depth 140nim/5.5in _ 140mm/5.5in
Weight 12.3 kg/27 lbs 12.3 kg/27 lbs
Options
Web Card
This Ethernet module replaces the standard RS485 MODBUS module
for remote monitoring and control.This card comes with built-in real-
time HTML monitor/control interface with at-a-glance system
performance and alarms, SNMP trap/inform, BACNet TCP/IP,
MODBUS TCP/IP, automatic data logging, and remote software
upgrade.
Custom Cat-5 Wiring Bundle
The optional Cat-5 wiring bundle allows quick and easy field wiring from
the lead/lag controller to the outdoor units. Installation cost can be
reduced by minimizing field wiring time and wiring errors. Each bundle
includes(4)Outdoor-rated Cat-5 cables. Each cable is a different color
helping to ensure correct wiring. Bundles available in 20'or 40' lengths.
PGD Display
This larger optional 128*32 user interface replaces the standard 3
digit PLD display, allowing easier access for new users and at-a-glance
monitoring and diagnostics for experienced users.This display is plug-
and-play, and backward compatible with existing ASLLC with
modification to mounting only.
Contact:Airsys North America Phone:(855)874-5380 Page 2 of 2
Email:ASNsupport@air-sys.com Web:www.airsysnorthamerica.com Rev 2.1
8/2017