Loading...
Report (32) M$$r?ol‘ - 00L-/9 , 13 .3o s J Auy iii-/ T C T E N G I N E E R l N G 180 Nickerson St INC Suite 302 Seattle,WA 98109 (206)285-4512(V) (206)285-0618(F) asolomon@ctengineering.com BULLETIN Date: August 28,2017 Number:CT-08 Project#: 16043 Project Name: River Terrace MF` Attached: None Subject: Lots 171 & 174—Simpson Strong-Wall foundations Drawings Affected: Description/Action: • This bulletin provides response to RFI, design clarifications and/or variation requests for the`River Terrace MF' project located in Tigard, Oregon. Based on our review of the plans and the construction photographs provided by Polygon, it's our recommendation that the cracked concrete stem walls for the Simpson Strong-Walls be epoxy injected to provide proper concrete cover for the anchor rods. No fix/repair is required for the anchor rod connections to the concrete footing as, per the information we received from Polygon, it's our understanding that the anchor rods have proper embedment&concrete cover into the footings. c,p PRp 4 474\„\GIN4its AREGfi9&� `�% 22. ch' �4FS T. GRA 08/28/2017 CALL WITH ANY OUESTIONS Issued by: Arnold R.Solomon =Date: Aug.28.2017 Distribution: `✓ Contact Information: Sam Scott Polygon Northwest Company Alexia Fukui Milbrandt Architects S:116043 River Terrace(Areas 1&2)\Bulletins116043 2017.08.28 CT08_Lots 171 &174-Simpson Strong-Wall foundations.doc Structural Engineers