Report (101) /2457 y2017-007-31
MORTIER ANG STRUCTURAL
ENGINEERS BUILDING DESIGN • FIRE PROTECTION
hi CODE CONSULTANT• PLAN CHECKING
1355 OAK STREET,STE#200 CONSTRUCTION INSPECTION
EUGENE,OREGON 97401
PHONE: (541)484-9080
July 25, 2017
Terra Firma—Karen Hill
7910 SW Hunziker St.
Tigard, OR 97223
RE: 11560 SW 91St Avenue,Tigard,OR 97223 - WO 21175
As requested,special inspection of the installation of Terra Firma helical piers was conducted on July 20,
2017.The repair involved placement of 10 helical piers as shown on the plans from this office dated
6/13/2017.The helical piers were installed beyond the minimum installation pressure of 700 psi (Pengo
RS-7) and the minimum depth of 8 feet. Each pier installation is acceptable regarding project
requirements.
TABLE 1—HELICAL PIER DRIVE LOG DETAILS
Plan Pier Number Installation Depth(feet) Installation Pressure(psi)
1 15 1200
2 15 1100
3 15 1200
4 15 1100
5 15 1200
6 15 1100
7 15 1200
8 15 1000
9 20 1100
10 15 1200
The provided special inspection has been performed to meet the requirements of current building code
and does not establish a guarantee of the contractor's work. It is the responsibility of the contractor to
perform the work in accordance with the provided structural drawings and the specifications of
Foundation Supportworks.
Thank you for the opportunity to be of service. If you have any questions or concerns regarding this
report,feel free to let us know. 8.24.17