Loading...
Report (101) /2457 y2017-007-31 MORTIER ANG STRUCTURAL ENGINEERS BUILDING DESIGN • FIRE PROTECTION hi CODE CONSULTANT• PLAN CHECKING 1355 OAK STREET,STE#200 CONSTRUCTION INSPECTION EUGENE,OREGON 97401 PHONE: (541)484-9080 July 25, 2017 Terra Firma—Karen Hill 7910 SW Hunziker St. Tigard, OR 97223 RE: 11560 SW 91St Avenue,Tigard,OR 97223 - WO 21175 As requested,special inspection of the installation of Terra Firma helical piers was conducted on July 20, 2017.The repair involved placement of 10 helical piers as shown on the plans from this office dated 6/13/2017.The helical piers were installed beyond the minimum installation pressure of 700 psi (Pengo RS-7) and the minimum depth of 8 feet. Each pier installation is acceptable regarding project requirements. TABLE 1—HELICAL PIER DRIVE LOG DETAILS Plan Pier Number Installation Depth(feet) Installation Pressure(psi) 1 15 1200 2 15 1100 3 15 1200 4 15 1100 5 15 1200 6 15 1100 7 15 1200 8 15 1000 9 20 1100 10 15 1200 The provided special inspection has been performed to meet the requirements of current building code and does not establish a guarantee of the contractor's work. It is the responsibility of the contractor to perform the work in accordance with the provided structural drawings and the specifications of Foundation Supportworks. Thank you for the opportunity to be of service. If you have any questions or concerns regarding this report,feel free to let us know. 8.24.17 PRO , `fiToya(@a mortiereng. Sincerely, ,6-•°•.) � � Cflm" 9 3 � Royal Mortier, PE 2017.08•24 lei 1 5:51:30-07'00' Royal Mortier, P.E. "pt 9 I