Loading...
Report .r -f/OS�o/7-00// f / U25_S� //�G'7" Bulletin 014 Rev. P cn IIIIN ® Model Fl FR Sues Quick Response0 Reliable Mass Bulb Sprinklers33CD Model Fl FR56 Sprinkler Types RECEIVED ; ,r,} - Standard Spray Upright Standard Spray Pendent Conventional Upright/Pendent JUL ') , i ; .� Vertical Sidewall CITY OF TIGARD , . Horizontal Sidewall - A °- II Model Fl FR56 Recessed Sprit a sp1 'ISIO1' Upright Pendent illkAtiailitir.: Standard Spray Pendent Horizontal Sidewall .. Model Fl FR56 Concealed Sprinkler Types1111 1 _ Standard Spray Pendent ; ' sr ` Model F1 FR42, F1 FRXLH & Fl FR28 Sprinkler `, Types ,:5,4-- Types Standard Spray Upright Vertical Sidewall Horizontal Sidew. Recessed Pendent/F1/F2 Standard Spray Pendent Model Fl FR40 Sprinkler Types Standard Spray Pendent �� Model F1 FR42, F1 FR40, F1 FRXLH & Fl FR28 ,' b , _ " '�9 Recessed Sprinkler Types �� ,, _ Standard Spray Pendent '. . - , . Model Fl FR56LL&Fl FR42LL Low Lead Sprinkle' Recessed Concealed Recessed Types Horizontal Sidewall Pendent Pendent/FP Standard Spray Pendent with less than 0.25% Lead Content Listing &Approvals 'Ali s rte The following organizations provide Listings or Approvals for various Model Fl FR series sprinklers. See the Design and Installation table in this Bulletin for information on XLH Upright XLH Pendent XLH Recessed specific listings and approvals applicable to each sprin Pendant Fl/F2 kler. 1. Underwriters Laboratories Inc. and Certified for Product Description Canada (cULus) in accordance with ANSI/UL199. Reliable Model Fl FR series sprinklers , - 2. FM Approvals (FM) are quick-response automatic sprin- 3. Loss Prevention Certification Board (LPCB) klers with a glass bulb thermal element. ° Vi.°, 4. VdS Schadenverhutung GmbH (VdS) Model F1 FR series sprinklers are Stan 5. Underwriters Laboratories Inc. and Underwriters dard Spray sprinklers, with the excep Laboratories of Canada Certified for Health Effects tion of the Model Fl FR56 Conventional XLH Recessed to NSF/ANSI Standard 61 Annex G (ULH) sprinkler which is an Old-style/Conven- Pendent FP tional sprinkler. 6. EC Certificate: 0786-CPD-40239 (RA1414), 0786 The Model Fl FR Series automatic sprinklers utilize a 3.0 CPD-40251 (RA1425), 0786-CPD-40252 (RA1475) mm frangible glass bulb.These sprinklers have demonstrat- (EC) ed response times in laboratory tests which are five to ten UL Listing Category times faster than standard response sprinklers. This quick Sprinklers,Automatic&Open (VNIV) response enables the Model Fl FR Series sprinklers to apply Quick Response Sprinkler water to a fire faster than standard-response sprinklers of the same temperature rating. The glass bulb consists of an accurately controlled amount of special fluid hermetically sealed inside a precisely man- ufactured glass capsule. This glass bulb is specially con- structed to provide fast thermal response. Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 At normal temperatures, the glass bulb contains the fluid Model F1FR Series sprinklers must be installed with the 4 in both the liquid and vapor phases. The vapor phase can Reliable sprinkler installation wrench identified in the Design be seen as a small bubble. As heat is applied, the liquid and Installation Information table in this Bulletin. Any other expands, forcing the bubble smaller and smaller as the liq- wrench may damage the sprinkler. A leak tight sprinkler joint uid pressure increases. Continued heating forces the liquid can be obtained with a torque of 8 to 18 lb-ft(11 to 24 N-m). to push out against the bulb, causing the glass to shatter, Do not tighten sprinklers over the maximum recommended opening the waterway and allowing the deflector to distrib- installation torque. Exceeding the maximum recommended ute the discharging water. installation torque may cause leakage or impairment of the Model Fl FR Series sprinklers provide a wide range of op- sprinkler. tions where quick-response,glass bulb sprinklers are used: Recessed Sprinklers • Pendent, recessed pendent, upright, horizontal Model Fl FR Series Recessed sprinklers are to be installed sidewall, and vertical sidewall deflectors as shown in Fig. 1, Fig.2,or Fig.3,as applicable to the spe- • K-factors of 2.8 (40 metric), 4.0 (57 metric), 4.2 (60 cific model being installed.The Recessed Escutcheon Data metric), and 5.6 (80 metric) table in the Bulletin identifies the only recessed escutcheons • Flush, recessed, and concealed installations that are permitted to be used with each Model F1FR Series See the Design and Installation Information table in this Recessed sprinkler.The use of any other recessed escutch- Bulletin for information on the approvals and availability of eon will void all approvals and negate all warranties. specific Model F1FR series sprinkler configurations. Concealed Sprinklers Model F1FR Recessed Pendent and Recessed Horizon- Model F1FR Series Concealed Pendent sprinklers are to tal Sidewall sprinklers are required to be used with Reliable be installed as shown in Fig. 4 or Fig. 5, as applicable to the Model F1, F2, or FP recessed escutcheons. See the Re- selected cover plate. Model F1FR56 Concealed Pendent cessed Escutcheon Data table in this Bulletin for listing and and Model Fl FR56LL Concealed Pendent sprinklers have approval information with each specific Model Fl FR series a factory-installed Model CCP cup. A protective cap is in- sprinkler. Model F1 and F2 recessed escutcheons,shown in stalled at the factory that should remain on the sprinkler until Fig. 1 and 3, are a friction fit assembly allowing for 3/4-inch the sprinkler is installed and should then be reinstalled on (19mm) and 1/2-inch (12.7mm)of adjustment, respectively. the sprinkler until the cover plate is installed.The concealed Model FP recessed escutcheons, shown in Fig. 2, provide a sprinkler assemblies are completed by the installation of a 1/2-inch(12.7mm)threaded adjustment. Model CCP push-on/thread-off cover plate assembly. The Model F1FR56 Concealed Pendent and Model F1FR56LL cover plate and sprinkler cup assemblies are joined using Concealed Pendent sprinklers are required to be used with a cover plate skirt with flexible tabs for threaded engage- Model CCP cover plates.A standard profile Model CCP cov- ment. A choice of two Model CCP cover plate assemblies er plate is available that provides up to 1/2-inch(12.7mm)of provides either 1/2-inch (13mm) or 5/8-inch (8mm) of cover cover plate adjustment. In addition,a low profile Model CCP adjustment. Do not install Model F1FR Series Concealed cover plate is also available that provides up to 5/16-inch Pendent sprinklers in ceilings which have positive pressure (8.0mm) of cover plate adjustment. See the Design and In- in the space above. stallation Information and Listed and Approved Temperature Model F1FR Series Concealed Pendent sprinklers require a Ratings tables in this Bulletin for further information on ap- 2-5/8-inch (67mm) diameter hole to be cut in the ceiling. The proved cover plate options. Model RC1 wrench is used to engage the sprinkler wrenching Application surfaces and to install the sprinkler in the fitting. Remove the Model Fl FR Series sprinklers are intended for use in protective cap to install the sprinkler,then reinstall the protective accordance with NFPA 13, FM Property Loss Prevention cap until the cover plate is installed. When inserting or remov- Data Sheets, and the requirements of the Authority Hay- ing the wrench from the sprinkler/cup assembly,care should be ing Jurisdiction. Care must be exercised that the k-factor, taken to prevent damage to the sprinkler. Do not wrench any temperature rating, deflector style, and sprinkler type are other part of the sprinkler/cup assembly. Installation is com- in accordance with the requirements of the applicable pleted by removing the protective cap from the sprinkler and design and installation standards. In addition, Model pushing the cover plate onto the cup. Final adjustment is made Fl FR Series sprinklers must be used in accordance with by hand turning the cover plate until the skirt flange makes full their listings and approvals, as well as the information contact with the ceiling.Cover plate removal requires turning the provided in this Bulletin, cover plate in the counter clockwise direction.After installation, Installation inspect all sprinklers to ensure that there is a gap between the Glass bulb sprinklers have orange bulb protectors or pro- cover plate and ceiling and that the four cup slots are open and tective caps to minimize bulb damage during shipping,han- free from any air flow impediment to the space above. dling and installation. Reliable sprinkler installation wrench- Concealed cover plate/cup assemblies are listed only for es are designed to install sprinklers with bulb protectors in use with specific sprinklers.The use of any concealed cover place.Remove the bulb protector at the time when the sprin- plate/cup assembly other than the Reliable Model CCP with kler system is placed in service for fire protection. Removal Model F1FR56 Concealed Pendent and Model F1FR56LL of the bulb protector before this time may leave the bulb vul- Concealed Pendent sprinklers or the use of the Model CCP nerable to damage. Remove bulb protectors by undoing the Concealed cover plate assembly on any sprinkler with clasp by hand. Do not use tools to remove bulb protectors. which it is not specifically listed my prevent good fire pro- tection and will void all guarantees, warranties, listings and approvals. 2. 0 Technical Data: Sensitivity: Quick-response Thread Size: 1/2-inch NPT standard; ISO 7-R1/2 optional Maximum Working Pressure: 175 psi (12 bar) - 100% Factory tested hydrostatically to 500 psi (34.5 bar) SIN RA1425, RA1414 & RA1435 cULus listed for 250 psi (17 bar) Design and Installation Information Nominal Nominal Nominal K-factor Orifice Deflector/ Sprinkler Installation Listings Approval Model Diameter Orientation Height Wrench SIN and Notes US Metric inches mm inches mm Approvals Pendent 2.25 57 Dor W2 RA1411 cULus 2 F1FR28 2.8 40 3/8 10 Recessed Pendent 2.25 57 GFR2 RA1411 cULus 2 Upright 2.25 57 Dor W2 RA1421 cULus 1,2 F1FR40 4.0 57 3/8 10 Pendent 2.25 57 Dor W2 RA1418 VdS Recessed Pendent 2.25 57 GFR2 RA1418 VdS Pendent 2.25 57 Dor W2 RA1413 cULus 2 F1FR42 4.2 60 7/16 10 Recessed Pendent 2.25 57 GFR2 RA1413 cULus 2 Upright 2.25 57 Dor W2 RA1423 cULus 1,2 F1FR42LL 4.2 60 7/16 10 Pendent 2.25 57 D or W2 RA1410 cULus, ULH Recessed Pendent 2,25 57 GFR2 RA1410 cULus, ULH F1FRXLH Pendent 2.25 57 Dor W2 RA1413 cULus 2 (F1FR42 4.2 60 7/16 10 Recessed Pendent 2.25 57 GFR2 RA1413 cULus 2 with Pintle) Upright 2.25 57 D or W2 RA1423 cULus 1,2 Pendent 2.25 57 Dor W2 RA1414 cULus, FM, 1,2,3,4 LPCB,VdS, EC Recessed Pendent 2.25 57 GFR2 RA1414 cULus, FM, 1,2,3,4 LPCB,VdS, EC F1FR56 5.6 80 1/2 15 Concealed Pendent 2.25 57 RC1 RA1414 cULus,VdS,EC 5,6 Upright 2.25 57 D or W2 RA1425 cULus, FM, 1,2,3,4 LPCB,VdS, EC "Conventional 2.25 57 D or W2 RA1475 LPCB,VdS, EC 4 (Pendent or Upright)" Pendent 2.25 57 D or W2 RA1415 cULus, ULH 1 F1FR56LL 5.6 80 1/2 15 Recessed Pendent 2.25 57 GFR2 RA1415 cULus, ULH Concealed Pendent 2.25 57 RC1 RA1415 cULus, ULH 6 Horizontal Sidewall 2.63 67 D or W2 RA1435 cULus, FM 1,2,3,7 F1FR56 5.6 80 1/2 15 Recessed Horizontal 2.63 67 GFR2 RA1435 cULus, FM 8 Sidewall F1FR56 5.6 80 1/2 15 Vertical Sidewall 2.25 57 Dor W2 RA1485 cULus, FM, 1,2,3,9 (Pendent or Upright) LPCB "1 cULus Listed Corrosion Resistant sprinkler when ordered with available Polyester coating. (7.)cULus Listed Corrosion Resistant sprinkler when ordered with available Electroless Nickel PTFE plating. 31 Available with FM approved Polyester coating in black or white. 0)Available with LPCB and VdS approved Polyester coating. (5)VdS and EC approvals of the F1FR56 Concealed Pendent sprinkler are for 155°F(68°C)temperature rated sprinklers only.VdS approved sprin- klers must use Norbulb brand glass bulbs with the 1/2-inch(12.7mm)adjustment Model CCP cover plate only. (6)Model F1FR56 Concealed Pendent and Model F1FR56LL Concealed Pendent sprinklers must be used with Reliable Model CCP cover plates, available as either standard depth with 1/2-inch(12.7mm)of adjustment or low profile with 5/16-inch(8.0 mm)of adjustment. 17'cULus Listing of the F1FR56 Horizontal Sidewall sprinkler is for Light and Ordinary Hazard occupancies only. FM Approval of the F1FR56 Hori- zontal Sidewall sprinkler is for Light Hazard occupancies only. m cULus Listing and FM Approval of the F1FR56 Recessed Horizontal Sidewall sprinkler is for Light Hazard occupancies only. (6)The F1FR56 Vertical Sidewall sprinkler is listed and approved for use only in Light Hazard occupancies. Minimum to maximum deflector to ceil- ing distance shall be 4 inches to 12 inches(102mm to 305mm).LPCB approval of the Fl FR56 Vertical Sidewall sprinkler is for installation in the Pendent position only. 3. t Listed and Approved Temperature Ratings Ordinary Temp. Intermediate Temp. High Temp. Classification Classification Classification Deflector/ 100°F(38°C)Max.Ambient 150°F(65°C) Max.Ambient 225°F(107°C)Max. r-m,. Ambient Temp. Model Orientation 135°F(57°C)Temp. p155°F(68°C) 175°F(79°C) 200°F(93°C) 86°F(141°C)Temp. Temp. Rating Temp. Rating Temp. Ratin• Temp.Rating Rating Orange Bulb Red Bulb Yellow Bulb r:- a ' Blue Bulb Pendent cULus F1FR28 Recessed Pendent cULus -- Upright cULus F1 FR40 Pendent VdS Recessed Pendent VdS Pendent cULus F1FR42 Recessed Pendent cULus -- Upright cULus F1FR42LL Pendent -- cULus, ULH Recessed Pendent -- cULus, ULH Pendent cULus F1FRXLH Recessed Pendent cULus -- Upright cULus Pendent cULus, FM, LPCB,VdS, EC Recessed Pendent cULus, FM, LPCB,VdS, EC -- F1FR56 Concealed Pendent" cULus cULus,VdS,EC cULus -- Upright cULus, FM, LPCB,VdS, EC "Conventional LPCB,VdS, EC (Pendent or Upright)" Pendent -- cULus,ULH -- F1FR56LL Recessed Pendent -- cULus, ULH -- Concealed Pendent" -- cULus,ULH -- _ Horizontal Sidewall cULus,FM F1FR56 Recessed Horizontal cULus, FM Sidewall F1FR56 Vertical Sidewall(Pen cULus, FM, LPCB dent or Upright) Model Fl FR56 Concealed Pendent and Fl FR56LL Concealed Pendent sprinklers must be used with Reliable Model CCP cover plates. For Ordinary Temperature Classification sprinklers use a 135°F (57°C) temperature rated cover plate. For Intermediate Temperature Classification sprinklers use a 165°F (74°C) temperature rated cover plate. Recessed Escutcheon Data Listed and Approved Recessed Escutcheons Deflector/ Model F1 Model F2 Model FP Model Orientation (Fig.1 &3) (Fig. 1 &3) (Fig.2) SIN 3/4-inch(19mm) 1/2-inch(12.7mm) 1/2-inch(12.7mm) adjustment adjustment adjustment F1FR28 Recessed Pendent cULus cULus cULus RA1411 F1FR40 Recessed Pendent VdS VdS VdS RA1418 F1FR42 Recessed Pendent cULus cULus cULus RA1413 F1FR42LL Recessed Pendent cULus, ULH cULus, ULH cULus, ULH RA1410 F1FR42XLH Recessed Pendent cULus cULus cULus RA1413 F1FR56 Recessed Pendent cULus, LPCB,VdS, cULus, FM, LPCB, cULus,VdS, EC RA1414 EC VdS,EC F1FR56LL Recessed Pendent cULus,ULH cULus, ULH cULus, ULH RA1415 F1FR56 Recessed Horizontal Sidewall cULus cULus,FM cULus RA1435 4. A. I 2 1/4"HOLE DIA. [57.2mm] ---I"- 1 15/16"D/A [49.2mm] ----" L- _--1 F -=i==i-i If v 1"X 1/2" REDUCER TURN COLLAR UNTIL TIGHT AGAINST SPRINKLER I WRENCH BOSS / FACE OF FITTING p— \ I 6 TO FACE OF CEILING DIMENSION II II F1 ESCUTCHEON SII C -- p AT MAXIMUM RECESS = 1[25.4mm] �� L J AT MINIMUM RECESS = 3/8[9.5mm] r F1 ESCUTCHEON , MM. F2 ESCUTCHEON 3/4[19mm] ADJUSTMENT /AT MAXIMUM RECESS = 3/4'[19mm] F2 ESCUTCHEON jJI` ®��� �Iyy 1r AT MINIMUM RECESS = 3/8[9.5mm] ADJUSTMENT O -, r., �� Z./7///A I 16 ' F7 ESCUTCHEON '�� 1/a" AT MAXIMUM RECESS = 7/8[22.2mm] 0 [3.2mm] /T MINIMUMHEONESS = 1-5/87-41.3mm] \,V V AT MAXIMUM RECESS = 1-1/87-28.6mm] ' �� , AT MINIMUM RECESS = 1-5/8[41.3mm] 2 27/32"DIA. [72.2mm] Fig. 1 Model F1 FR56,F1 FR56LL,F1 FR42,F1 FR40,Fl FR42LL,F1 FRXLH&F1 FR28 Recessed Pendent sprinkler with Model F1 or F2 escutcheon r L ____ _ -- m II I 1" X 1/2" REDUCER 2 5/8" DIA. [66.7mm] HOLE IN CEILING 2 5/16" DIA. [58.7mm] CUP 11-H11-,L a -1 CEILING ��— 1111.' — FACE OF FITTING I i i�'��� ��� � TO FACE OF CEILING �\ � IR� fili' DIMENSION — iii{ t AT MAXIMUM RECESS = 1-1/2[38mm] 1 1 AT MINIMUM RECESS = 1[25.4mm] • I 1%%` i :i AT MAXIMUM RECESS = 9/16[14.3mm] %2[12.7mm] I '`�, � AT MINIMUM RECESS = 1[25.4mm] ADJUSTMENT • 3 1/4" DIA. f [82.6mm] r Fig.2 Model F1FR56,F1FR56LL,F1FR42,F1 FR40,F1FR42LL,F1FRXLH&F1FR28 Recessed Pendent sprinkler with Model FP escutcheon 5. k FACE OF FITTING TO FACE OF CEILING DIMENSION //A// Fl ESCUTCHEON j/////�� AT MAXIMUM RECESS = 1[25.4mm] / Fl ESCUTCHEON AT MINIMUM RECESS = 3/8[9.5mm] AT MAXIMUM RECESS = 1-3/8'[34.9mm] F2 ESCUTCHEON N _ AT MINIMUM RECESS = 2-1/16[52.4mm] AT MAXIMUM RECESS = 3/4'[19mm] 7 F2 ESCUTCHEON AT MINIMUM RECESS = 3/8[9.5mm] AT MAXIMUM RECESS = 1-5/8[41.3mm] 2 1/4" HOLE DIA. -. 1/8.. AT MINIMUM RECESS = 2-1/16[52.4mm] [57.2mm] [3.2mm] 1" X 1/2" REDUCER _I1 t ,,r-�—_--r ( 1 (1) 1,717j " i'j I 1 ` .—r,� I ilii 11 'J����-- 4"-12•• 1 15/16" DIA. J I I ^ __ [101.6 4"-304.8mm] 13-1--- if �" 2 27/32" DIA. CEILING TO 49.2mm 1III 1 �� _ (72.2mm] DEFLECTOR L_r_y. i , 1 TURN COLLAR UNTILTIGHT AGAINST � WRENCH BOSS.SPRINKLER L F1 ESCUTCHEON ---'I 3/4[19mm] ADJUSTMENT F2 ESCUTCHEON 1/2[12.7mm] ADJUSTMENT outeaa,E RECESSED HSW W/F1 OR F2 ESCUTCHEON (1) FM APPROVED FOR 4" - 6" [101.6MM - 152.4MM] CEILING TO DEFLECTOR WITH F2 ONLY. Fig.3 Model Fl FR56 Recessed Horizontal Sidewall sprinkler with Model Fl or F2 escutcheon 1 " x 1/2" REDUCING TEE OR ELBOW Fil IT — - - - }{{ - - - -+- - - - C{F - - - — iii 12 5/8" DIA. L I HOLE IN CEILING 2 5/16" DIA — 1 :=-----,---_,_—_J___=_---7. , LJ CUP _—:>tj �1 I l p 'tl II 1 1/2" MAX. ///'///-5//--/// ///7//-///1 '', =o IIII FACE OF FITTING � ���� _ _ TO FACE OF CEILING / - ,,,1 i�,; .,,,,,�� DIMi NSION CEILING—/ ''�. Q._ ••- ./ 1/2" MAX. — 15/16" - COVER ADJUSTMENT COVER PLATE / ASSEMBLY 3 5/16" DIA. SPRINKLER / CONCEALED, 1/2" ADJUSTMENT 017FGO1A Fig.4 Model F1 FR56/F1 FR56LL Concealed Pendent sprinkler with standard depth 1/2-inch(12.7mm)adjustment-Model CCP cover plate 6. V. 1" x 1/2" REDUCING TEE OR ELBOW - - -1L , I -, PI 2 5/8" DIA. 2 5/16" DIA — L; HOLE IN CEILING L__.- ---..=:=----- J CUP =i--�1• �, 1111!1- tl�_IIIII 1 1/2 MAX. I , i FACE OF FITTING """" it TO FACE OF CEILING k / "' DIMENSION Fi ♦ ���� .. !i/ i ,7/,,,,,/ `� �� CEILING �;; -_,I_ : -_—__. `opt �� 5/76" MAX. 3/4" r,�.i COVER ADJUSTMENT COVER PLATE / ASSEMBLY 3 5/16" DIA. SPRINKLER CONCEALED, 5/16" ADJUSTMENT 017FG02A Fig.5-Model Fl FR56/F1 FR56LL Concealed Pendent sprinkler with low profile 5/16-inch(8.0mm)adjustment-Model CCP cover plate Maintenance Material Data The Model Fl FR Series sprinklers should be inspected and Frame: DZR Brass,QM Brass,or Low Lead Brass the sprinkler system maintained in accordance with NFPA 25. Do not clean sprinklers with soap and water,ammonia or Deflector: CDA Alloy 220,260,or 510 any other cleaning fluids. Remove dust by using a soft brush Load Screw\Pintle: CDA Alloy 360 or 544 • or gentle vacuuming. Replace any sprinkler which has been Cup: CDA Alloy 651 or 693 painted(other than factory applied)or damaged in any way. Washer: Nickel Alloy 440 or 360,coated with PTFE A stock of spare sprinklers should be maintained to allow Adhesive Tape quick replacement of damaged or operated sprinklers. Bulb: Glass Finishes (1) Standard Finishes Sprinkler Escutcheon Cover plate') Ordering Information Bronze Brass Chrome Specify: 0 Chrome Plated Chrome White 1. Sprinkler Model: [F1 FR28][F1 FR40][F1 FR42] Polyester s Plated [F1 FR42LL][F1 FRXLH][F1 FR56][F1 FR56LL] Coated White Painted Special Application Finishes 2. Sprinkler Deflector/Orientation: [Pendent][Recessed Sprinkler Escutcheon Cover plate') , Pendent][Upright][Conventional][Horizontal Sidewall] Electroless Nickel Electroless Nickel Bright Brass [Recessed Horizontal Sidewall][Vertical Sidewall] PTFE(7) PTFE Bright Brass(3) Bright Brass Black Plating 3. Sprinkler threads: [1/2-inch NPT][ISO 7-R1/2] Black Plated Black Plated Black Paint 4. Sprinkler Temperature Rating: [135°F (57°C)][155°F Black Paint>2>>61 Black Paint Off White68°C 175°F 79°C 200°F 93°C 286°F (141°C)] Off White«>>6> Off White Satin Chrome ( k[ ( )][ ( )][ ( )] Chrome Dull Chrome Dull 5. Sprinkler Finish c1 Other finishes and colors are available on special order. Consult the 6. Escutcheon Model: [F1][F2][FP] factory for details.Custom color painted sprinklers may not retain their 7. Escutcheon Finish (where applicable) UL Corrosion resistance listing.Coverplate custom paint is semi-gloss, 8. Cover plate Model: [standard profile CCP 1/2-inch unless specified otherwise. (12.7mm) adjustment][low profile CCP 5/16-inch (2) cULus Listed only, '='> 200°F(93°C)maximum. (8.0mm) adjustment] (4) cULus listed "corrosion resistance" applies to SIN Numbers RA1435 9. Cover plate Temperature Rating: [135°F(57°C)for use (HSW), RA1485(VSW), RA1425 (Upright), RA1414 (Pendent) and with Ordinary Temperature sprinklers][165°F (74°C) RA1415 (Pendent) in standard black or white. Corrosion resistance in for use with Intermediate Temperature sprinklers] other polyester colors is available upon request. (5) FM Approvals finish as"Polyester coated"applies to SIN Number 10. Cover plate Finish - RA1414,RA1435 and RA1425 in standard black or white. +6i LPCB and VdS Approved finish applies only to RA1425,RA1414,RA1418 Note: When Model F1 FR Series Recessed sprinklers are ordered, the (VdS)and RA1475. sprinklers and escutcheons are packaged separately. cULus listed Corrosion Resistant • 7. ti. Reliable . . . For Complete Protection . Reliable offers a wide selection of sprinkler components. Following are some of the many precision-made Reliable products that guard life and property from fire around the clock. • Automatic sprinklers • Deluge valves • Flush automatic sprinklers • Detector check valves • Recessed automatic sprinklers • Check valves • Concealed automatic sprinklers • Electrical system • Adjustable automatic sprinklers • Sprinkler emergency cabinets • Dry automatic sprinklers • Sprinkler wrenches • Intermediate level sprinklers • Sprinkler escutcheons and guards • Open sprinklers • Inspectors test connections • Spray nozzles • Sight drains • Alarm valves • Ball drips and drum drips • Retarding chambers • Control valve seals • Dry pipe valves • Air maintenance devices • Accelerators for dry pipe valves • Air compressors • Mechanical sprinkler alarms • Pressure gauges • Electrical sprinkler alarm switches • Identification signs • Water flow detectors • Fire department connection The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association,Factory Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for almost 100 years. Manufactured by Reliable Automatic Sprinkler Co.,Inc. a RePapercycled ® (800)431-1588 Sales Offices Reliable (800)884289-62005421 Sales Fax Revision lines indicate updated or new data. (914) Corporate Offices www.reliablesprinkler.com Internet Address EG.Printed in U.S.A.03/17 P/N 9999970300 I :SED AS NECRESSARY TO MATCH EXISTING RESPONSE TYPE IN COMPARTMENT Bulletin 117Rev.R II. ® Model Fl co Model F1 Recessed liable _. Standard Response 33 Sprinklers IIMMI.The Designer® Model F1 Sp .A �r Standard Upright f Standard Pendent j U I.r 3 1 :1' i '° Extended Coverage Pendent Conventional CITY r I Vertical Sidewall BUILDING DIVISION Horizontal Sidewall Upright Pendent -HSW 1 Deflectora Horizontal Sidewall Extended Coverage " -EC-6 Deflectorilti Model Fl Recessed Sprinkler The DesignerR�ll p Recessed Pendent Recessed Extended Coverage Pendent _ Recessed Extended Coverage Horizontal Sidewal Vertical Sidewall on e'tio al Approval Organizations 1. Underwriters Laboratories Inc. . 2. Underwriters' Laboratories of Canada . ' 3. Factory Mutual Research Corp. 4. Loss Prevention Council 5. NYC BS&A No. 587-75-SA Horizontal Sidewall Recessed Pendent 6. Pleniere Assemblee 7. Verband der Schadenversicherer 8. NYC MEA 258-93-E UL Listing Categoryi� A ` Sprinklers, Automatic &Open (VNIV) Patents: US Patent No. 6,374,920 Applies to Extended Coverage Recessed Extended Model Fl Vertical Sidewall Sprinklers Horizontal Sidewall Coverage Horizontal Product Description Sidewall The Fl Glass Bulb Sprinkler combines the durability of a standard sprinkler with the attractive low profile of a decora tive sprinkler. Whether installed on exposed piping or in an 1` — i t office ceiling, it is functional and attractive. The Horizontal and Vertical Sidewall Sprinklers provide an equally attractive 11) - s,..-:. :-#' appearance when ceiling piping cannot be used. Beautifully versatile is the description for the Reliable Model Extended Coverage Recessed Extended Fl Recessed Designer glass bulb sprinkler. Recessing The Pendent Coverage Pendent Designer®enhances its already low profile decorative appear- ance, and facilitates a rapid and perfect installation. At normal temperatures,the glass bulb contains the fluid Model Fl Recessed Designer's escutcheon is highly ad- in both the liquid phase and in the vapor phase.The vapor justable.The two piece construction makes field installation a phase can be seen as a small bubble.As heat is applied,the very easy and rapid task.This also allows ceiling panels to later liquid expands forcing the bubble smaller and smaller as the be removed without shutting down the fire protection system, liquid pressure increases. Continued heating forces the liq- thus facilitating maintenance of above ceiling services. uid to push out against the bulb,causing the glass to shatter, The Designer Automatic Sprinkler utilizes a frangible opening the waterway and allowing the deflector to distribute glass bulb. The glass bulb consists of an accurately con- the discharging water. trolled amount of special fluid hermetically sealed inside of a The F1 Sprinkler temperature rating is identified by the precisely manufactured glass capsule. This glass bulb is color of the glass bulb capsule as well as frame color where specially constructed to provide fast thermal response. applicable. The Reliable Automatic Sprinkler Co.,Inc., 525 North MacQuesten Parkway,Mount Vernon, New York 10552 Model Fl Upright, Pendent & Conventional Sprinklers Installation Wrench: Model D Sprinkler Wrench . - f, -..,-.. ., fill_ , 4,-. . Upright Pendent Conventional Installation Data: Nominal Sprinkler Nominal Thread K Factor Sprinkler Approval Identification Orifice Size Height Organization Numbers (SIN) US Metric Upright Pendent Standard-Upright(SSU)and Pendent(SSP)Deflectors Marked to Indicate Position t. 1/2"(15mm) 1/2"NPT(R1/2) 5.6 80 2.2"(56mm) 1,2,3,4,5,6,7 R1725 R1715 1X2'(20mm) 3/4"NPT(R3/)t1} 8.0 115 2.3"(58mm) 1,2.3,4,7,8 R1722 R1712 _ 1/2"(15mm)(3) 1/2"NPT(R1/2) 5.6 80 2.2"(56mm) 7 1%2('(20mm)(3) 3/a"NPT(R3/n) 8.0 115 2.3"(58mm) 7 /,s'(11mm) 1"NPT(R1/2) 4.2 60 2.2"(56mm) 1,2,8 R1723 R1713 %"(10mm) 1/2"NPT(R1/2)(2) 2.8 40 2.54"(65mm) 1,2,8 R1721 R1711 10mm XLH R/ 4.2 60 56.1mm 4,6,7 R1724 R1714 Conventional-Install in Upright or Pendent Position 10mm XLH R/ 4.2 60 56.1mm R1774 15mm 1/2" NPT(R'/z) 5.6 80 56.1mm 4,6,7 R1775 20mm 3/4"NPT(R3/4) 8.0 115 58.1mm 4,7 R1772 (j)LPC Approval up 286°F(141°C) (2)FM Approval for SSU up to and including 200°F(93°C)only. (3}VdS Approval for Intermediate Response 155°F(68°C)only. 2. Model Fl Recessed Pendent Sprinkler Installation Wrench: Model RC1 Sprinkler Wrench 2 1/4'HOLE DLA. [57.2mm] 1 13/16'DIA. (49.2''m/ "P q I I 7"5 1/2"REDUCER ", TURN COLLAR �(25,4mm X 17.7mm] ^, UNTIL TICHT .4" t AGAINST SPRINKLER � , WRENCH BOSS W-) I 1-1 E1 ��J =� _ .�I.7W�j. r 13/76" vaJ/4"ADJUSTMENT (0riii:: [2/16"F1 Recessed [19.1Vim] — I `I I. tI W1/B" t t [3.2mm] 7"[25.4mm] A + 117FC0IA 2 27/32"074. (72.2mm] (I)When installed directly into a tee,the escutcheon dimension's adjustment will be reduced. Installation Data: Nominal Sprinkler Nominal Thread Sprinkler Approval Orifice Size K Factor Height Organizations Identification US Metric Numbers (SIN) )2"(15mm) /"NPT(R)2) 5.6 80 2.2"(56mm) 1.2,3(2)4,5,7 R1715 7%2'(20mm) /"NPT(R%) 8.0 115 2.3"(58mm) 1,2,3(2),4,8 R1712 ;"(15mm)(4) );"NPT(R/) 5.6 80 2.2"(56mm) 7 17/,"(20mm)(4) ;"NPT(R,;) 8.0 115 2.3"(58mm) 7 7/,fi"(11mm) ),"NPT(R1/2) 4.2 60 2.2"(56mm) 1,2,8 R1713 /"(10mm) y,"NPT(R1/2) 2.8 40 2.2"(56mm) 1,2,8 R1711 10mm R/ 4.2 60 56.1mm 4(3),7 R1714 (2)FM Approval • Light Hazard—No Limitations. • Ordinary Hazard—Groups 1 &2,Wet Systems only. (3)LPC Approval is for 57°C through 93°C ratings. (4)VdS Approval for Intermediate Response 155°F(68°C)only. 3. .w Model Fl & Fl Recessed Sprinklers Maintenance Application The Models Fl and Fl Recessed Sprinklers should . Model F1 and F1 Recessed sprinklers are used in fixed be inspected quarterly and the sprinkler system main- fire protection systems: Wet, Dry, Deluge or Preaction. main- tained in accordance with NFPA 25. Do not clean sprin- fire must exercised that the orifice size, temperature rat- klers with soap and water, ammonia or any other . cleaning fluid. Remove any sprinkler which has been ing, deflector style and sprinkler type are in accordance with the latest published standards of the National Fire Pro- Painted (other than factory applied)or damaged in any tection Association or the approving Authority Having `^gay. A stock of spare sprinklers should be maintained Jurisdiction. to allow quick replacement of damaged or operated sprinklers. Prior to installation, sprinklers should be Installation maintained in the original cartons and packaging until Model Fl sprinklers are standard response sprinklers in- used to minimize the potential for damage to sprinklers tended for installation as specified in NFPA 13. They must that would cause improper operation or non-operation. also be installed with the Model D Sprinkler Wrench specifi- cally designed by Reliable for use with these sprinklers. The Model Fl Recessed Sprinklers are to be installed Temperature Ratings with a maximum recess of 3/4 inch (19mm). The Model Fl Sprinkler Maximum Ambient Escutcheon illustrated is the only recessed escutcheon to Classification Temperature Temperature Bulb be used with the Model Fl Pendent and EC Sprinklers.The °F °C °F °c Color use of any other recessed escutcheon will void all approv- Ordinary 135 57 100 38 Orange als and negate all warranties.When installing Model Fl Re- Ordinary 155 68 100 38 Red .f— cessed Pendent, EC Pendent,and EC HSW Sprinklers, use Intermediate 175 79 150 66 Yellow the Model GFR1 Sprinkler Wrench. Any other type of Intermediate 200 93 150 66 Green wrench maydamage these sprinklers. High (1) 286 1412 225 107 Blue g p Extra High360 182 300 149 Mauve Glass bulb sprinklers have orange covers to protect the bulb during the installation process. REMOVE THIS PRO- "Not Available For Fl Recessed TECTION ONLY AFTER THE SYSTEM HAS BEEN HYDRO- Patents: U.S. Patent No. 6,374,920 STATICALLY TESTED AND, WHEN APPLICABLE, THE Applies to Model Fl Vertical Sidewall Sprinklers. ESCUTCHEONS HAVE BEEN INSTALLED. RASCO wrenches are designed to install sprinklers when covers are Finishes (1) in place. Standard Finishes Sprinkler Escutcheon Bronze Brass Chrome Chrome Ordering Information White Polyester Coated') White Painted Specify: Special Application Finishes 1. Sprinkler Model Sprinkler Escutcheon 2. Sprinkler Type Bright Brass`"fi' Bright Brass 3. Orifice Size Black Plated' Black Plated Black Paint°°) Black Paint 4. Deflector Type Off White(3'(E) Off White Satin Chrome Satin Chrome 5. Temperature Rating: Lead Plated""°' Wax Coated'")''' Specify Bulb Size when ordering Wax Over Lead,3""") Model El EC HSW Sprinkler. 6. Sprinkler Finish Other colors and finishes are available on special order. Consult factory for details. 7. Escutcheon Finish (where applicable) (2)200°F(93°C)maximum. `3'UL and ULC Listed,and NYC Approved Only. `4'155°F to 200°F(68°C to 93°C)ratings only. `5f 286°F(141°C)Sprinklers may be coated for ambient conditions not exceeding 150°F(66°C). `6'LPC approved for 10mm and 15mm sprinklers only. The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association.Fac- tory Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 80 years,and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States,Canada and foreign countries Manufactured by -- The Reliable Automatic Sprinkler Co.,Inc. Re r flelli�bl (800) 431 1588 Sales Offices aae� data. 848 6051 Sales Fax Revision lines indicate updated or new data. 11.111.11.111111111111111111.11 (914} 668-3470 Corporate Offices •,ro•.wr.reliablesprink1er.corn Internet Address EG printed in USA. 5/05 P/N 9999970011