Bulletin 014 Rev. 0
co
Reliable
O Model FR Series
Quick ResponsF1e o
Glass Bulb SprinklersDJ
0
Model Fl FR56 Sprinkler Types
Standard Spray Upright "
Standard Spray Pendent J 4
Conventional Upright/Pendent
Vertical Sidewall ft
Horizontal Sidewall -
Model Fl FR56 Recessed Sprinkler Types Upright Pendent Conventional
Standard Spray Pendent
Horizontal Sidewall
Model Fl FR56 Concealed Sprinkler Types .
Standard Spray Pendent
Model F1 FR42, F1 FRXLH & F1 FR28 Sprinkler cip.
Types Vertical Sidewall Horizontal Sidewall Recessed
Standard Spray Upright Pendent/F1/F2
Standard Spray Pendent ",. ,", P
Model Fl FR40 Sprinkler Types .; ' �,
Standard Spray Pendent ," t
Model Fl FR42, Fl FR40, Fl FRXLH & Fl FR28 `-:, . ,
s� w
Recessed Sprinkler Types • #' .
Standard Spray Pendent !' + -.'
1 Model Fl FR56LL&Fl FR42LL Low Lead Sprinkler Recessed Concealed Recessed
Horizontal Sidewall Pendent Pendent/FP
Types
Standard Spray Pendent with less than 0.25% Lead
Content
Listing & Approvals
The following organizations provide Listings or Approvals ' ,
it
for various Model Fl FR series sprinklers. See the Design r
il
and Installation table in this Bulletin for information on XLH Upright XLH Pendent XLH Recessed
specific listings and approvals applicable to each sprin- Pendent F1/F2
kler. Product Description
1. Underwriters Laboratories Inc. and Certified for
Canada(cULus) in accordance with ANSI/UL199. Reliable Model F1 FR series sprinklers -'
2. FM Approvals (FM) are quick-response automatic sprin-
klers with a glass bulb thermal element.
3. Loss Prevention Certification Board (LPCB) , .
4. VdS Schadenverhutung GmbH (VdS) Model F1 FR series sprinklers are Stan
5. Underwriters Laboratories Inc. and Underwriters dard Spray sprinklers, with the excep
Laboratories of Canada Certified for Health Effects tion of the Model F1 FR56 Conventional XLH Recessed
to NSF/ANSI Standard 61 Annex G (ULH) sprinkler which is an Old-style/Conven- Pendent FP
6. EC Certificate: 0786-CPD-40239 (RA1414), 0786- tional sprinkler.
CPD 40251 (RA1425), 0786-CPD-40252 (RA1475) The Model F1 FR Series automatic sprinklers utilize a 3.0
(EC) mm frangible glass bulb.These sprinklers have demonstrat-
UL Listing Category ed response times in laboratory tests which are five to ten
times faster than standard response sprinklers. This quick
Sprinklers,Automatic&Open (VNIV) response enables the Model Fl FR Series sprinklers to apply
Quick Response Sprinkler water to a fire faster than standard-response sprinklers of the
same temperature rating.
The glass bulb consists of an accurately controlled amount
of special fluid hermetically sealed inside a precisely man-
ufactured glass capsule. This glass bulb is specially con-
structed to provide fast thermal response.
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
At normal temperatures, the glass bulb contains the fluid Model F1FR Series sprinklers must be installed with the
in both the liquid and vapor phases. The vapor phase can Reliable sprinkler installation wrench identified in the Design
be seen as a small bubble. As heat is applied, the liquid and Installation Information table in this Bulletin. Any other
expands, forcing the bubble smaller and smaller as the liq- wrench may damage the sprinkler. A leak tight sprinkler joint
uid pressure increases. Continued heating forces the liquid can be obtained with a torque of 8 to 18 lb-ft(11 to 24 N-m).
to push out against the bulb, causing the glass to shatter, Do not tighten sprinklers over the maximum recommended
opening the waterway and allowing the deflector to distrib- installation torque. Exceeding the maximum recommended
ute the discharging water. installation torque may cause leakage or impairment of the
Model Fl FR Series sprinklers provide a wide range of op- sprinkler.
tions where quick-response, glass bulb sprinklers are used: Recessed Sprinklers
• Pendent, recessed pendent, upright, horizontal side- Model F1FR Series Recessed sprinklers are to be installed
wall, and vertical sidewall deflectors as shown in Fig. 1, Fig. 2,or Fig. 3,as applicable to the spe-
• K-factors of 2.8 (40 metric), 4.0 (57 metric), 4.2 (60 cific model being installed.The Recessed Escutcheon Data
metric), and 5.6(80 metric) table in the Bulletin identifies the only recessed escutcheons
• Flush, recessed, and concealed installations that are permitted to be used with each Model F1FR Series
See the Design and Installation Information table in this Recessed sprinkler.The use of any other recessed escutch-
Bulletin for information on the approvals and availability of eon will void all approvals and negate all warranties.
specific Model Fl FR series sprinkler configurations. Concealed Sprinklers
Model F1FR Recessed Pendent and Recessed Horizon- Model F1FR Series Concealed Pendent sprinklers are to
tal Sidewall sprinklers are required to be used with Reliable be installed as shown in Fig. 4 or Fig.5,as applicable to the
Model F1, F2, or FP recessed escutcheons. See the Re- selected cover plate. Model F1FR56 Concealed Pendent
cessed Escutcheon Data table in this Bulletin for listing and and Model Fl FR56LL Concealed Pendent sprinklers have
approval information with each specific Model F1FR series a factory-installed Model CCP cup. A protective cap is in-
sprinkler. Model Fl and F2 recessed escutcheons,shown in stalled at the factory that should remain on the sprinkler until
Fig. 1 and 3, are a friction fit assembly allowing for 3/4-inch the sprinkler is installed and should then be reinstalled on
(19mm)and 1/2-inch (12.7mm)of adjustment, respectively. the sprinkler until the cover plate is installed.The concealed
Model FP recessed escutcheons,shown in Fig. 2, provide a sprinkler assemblies are completed by the installation of a
1/2-inch(12.7mm)threaded adjustment. Model CCP push-on/thread-off cover plate assembly. The
Model F1FR56 Concealed Pendent and Model F1FR56LL cover plate and sprinkler cup assemblies are joined using
Concealed Pendent sprinklers are required to be used with a cover plate skirt with flexible tabs for threaded engage-
Model CCP cover plates.A standard profile Model CCP cov- ment. A choice of two Model CCP cover plate assemblies
er plate is available that provides up to 1/2-inch(12.7mm)of provides either 1/2-inch (13mm)or 5/8-inch (8mm)of cover
cover plate adjustment. In addition,a low profile Model CCP adjustment. Do not install Model Fl FR Series Concealed
cover plate is also available that provides up to 5/16-inch Pendent sprinklers in ceilings which have positive pressure
(8.0mm) of cover plate adjustment. See the Design and In- in the space above.
stallation Information and Listed and Approved Temperature Model F1FR Series Concealed Pendent sprinklers require a
Ratings tables in this Bulletin for further information on ap- 2-5/8-inch (67mm) diameter hole to be cut in the ceiling. The
proved cover plate options. Model RC1 wrench is used to engage the sprinkler wrenching
Application surfaces and to install the sprinkler in the fitting. Remove the
Model Fl FR Series sprinklers are intended for use in protective cap to install the sprinkler,then reinstall the protective
accordance with NFPA 13, FM Property Loss Prevention cap until the cover plate is installed. When inserting or remov-
Data Sheets, and the requirements of the Authority Hay- ing the wrench from the sprinkler/cup assembly,care should be
ing Jurisdiction. Care must be exercised that the k-factor, taken to prevent damage to the sprinkler. Do not wrench any
temperature rating, deflector style, and sprinkler type are other part of the sprinkler/cup assembly. Installation is corn-
in accordance with the requirements of the applicable pleted by removing the protective cap from the sprinkler and
design and installation standards. In addition, Model pushing the cover plate onto the cup. Final adjustment is made
Fl FR Series sprinklers must be used in accordance with by hand turning the cover plate until the skirt flange makes full
their listings and approvals, as well as the information contact with the ceiling.Cover plate removal requires turning the
provided in this Bulletin. cover plate in the counter clockwise direction.After installation,
Installation inspect all sprinklers to ensure that there is a gap between the
Glass bulb sprinklers have orange bulb protectors or pro- cover plate and ceiling and that the four cup slots are open and
tective caps to minimize bulb damage during shipping,han- free from any air flow impediment to the space above.
dling and installation. Reliable sprinkler installation wrench- Concealed cover plate/cup assemblies are listed only for
es are designed to install sprinklers with bulb protectors in use with specific sprinklers.The use of any concealed cover
place. Remove the bulb protector at the time when the sprin- plate/cup assembly other than the Reliable Model CCP with
kler system is placed in service for fire protection. Removal Model F1FR56 Concealed Pendent and Model F1FR56LL
of the bulb protector before this time may leave the bulb vul- Concealed Pendent sprinklers or the use of the Model CCP
nerable to damage. Remove bulb protectors by undoing the Concealed cover plate assembly on any sprinkler with which
clasp by hand. Do not use tools to remove bulb protectors. it is not specifically listed my prevent good fire protection and
will void all guarantees,warranties, listings and approvals.
2.
Technical Data:
Sensitivity: Quick-response
Thread Size: 1/2-inch NPT standard; ISO 7-R1/2 optional
Maximum Working Pressure: 175 psi (12 bar)- 100% Factory tested hydrostatically to 500 psi (34.5 bar)
SIN RA1425, RA1414& RA1435 cULus listed for 250 psi (17 bar)
Design and Installation Information
Nominal Nominal Nominal
s
Listin
Model K-factor Orifice Deflector/ Sprinkler Installation SIN andg Approval
Diameter Orientation Height Wrench Notes
US Metric inches mm inches mm Approvals
Pendent 2.25 57 D RA1411 cULus 2
F1FR28 2.8 40 3/8 10 Recessed Pendent 2.25 57 GFR2 RA1411 cULus 2
Upright 2.25 57 D RA1421 cULus 1,2
F1FR40 4.0 57 3/8 10 Pendent 2.25 57 D RA1418 VdS
Recessed Pendent 2.25 57 GFR2 RA1418 VdS
Pendent 2.25 57 D RA1413 cULus 2
F1FR42 4.2 60 7/16 10 Recessed Pendent 2.25 57 GFR2 RA1413 cULus 2
Upright 2.25 57 D RA1423 cULus 1,2
F1FR42LL 4.2 60 7/16 10 Pendent 2.25 57 D RA1410 cULus, ULH
Recessed Pendent 2.25 57 GFR2 RA1410 cULus, ULH
F1FRXLH Pendent 2.25 57 D RA1413 cULus 2
(F1FR42 4.2 60 7/16 10 Recessed Pendent 2,25 57 GFR2 RA1413 cULus 2
with Pintle) Upright 2.25 57 D RA1423 cULus 1,2
Pendent 2.25 57 D RA1414 cULus, FM, 1,2,3,4
LPCB,VdS, EC
Recessed Pendent 2.25 57 GFR2 RA1414 cULus, FM, 1,2,3,4
LPCB,VdS,EC
F1FR56 5.6 80 1/2 15 Concealed Pendent 2.25 57 RC1 RA1414 cULus,VdS,EC 5,6
cULus, FM,
Upright 2.25 57 D RA1425 LPCB,VdS, EC 1,2,3,4
"Conventional
2.25 57 D RA1475 LPCB,VdS, EC 4
(Pendent or Upright)"
Pendent 2.25 57 D RA1415 cULus, ULH 1
F1FR56LL 5.6 80 1/2 15 Recessed Pendent 2.25 57 GFR2 RA1415 cULus, ULH
Concealed Pendent 2.25 57 RC1 RA1414 cULus, ULH 6
Horizontal Sidewall 2.63 67 D RA1435 cULus, FM 1,2,3,7
F1FR56 5.6 80 1/2 15 Recessed Horizontal
Sidewall 2.63 67 GFR2 RA1435 cULus, FM 8
F1FR56 5.6 80 1/2 15 Vertical Sidewall 2 25 57 D RA1485 cULus, FM, 1,2,3,9
(Pendent or Upright) LPCB
('1 cULus Listed Corrosion Resistant sprinkler when ordered with available Polyester coating.
(2)cULus Listed Corrosion Resistant sprinkler when ordered with available Electroless Nickel PTFE plating.
(3)Available with FM approved Polyester coating in black or white,
(4)Available with LPCB and VdS approved Polyester coating.
(5)VdS and EC approvals of the F1FR56 Concealed Pendent sprinkler are for 155°F(68°C)temperature rated sprinklers only.VdS approved sprin-
klers must use Norbulb brand glass bulbs with the 1/2-inch(12.7mm)adjustment Model CCP cover plate only.
(6)Model F1FR56 Concealed Pendent and Model F1FR56LL Concealed Pendent sprinklers must be used with Reliable Model CCP cover plates,
available as either standard depth with 1/2-inch(12.7mm)of adjustment or low profile with 5/16-inch(8.0 mm)of adjustment.
°1 cULus Listing of the F1FR56 Horizontal Sidewall sprinkler is for Light and Ordinary Hazard occupancies only. FM Approval of the F1FR56 Hori-
zontal Sidewall sprinkler is for Light Hazard occupancies only.
(8)cULus Listing and FM Approval of the F1FR56 Recessed Horizontal Sidewall sprinkler is for Light Hazard occupancies only.
(9)The F1FR56 Vertical Sidewall sprinkler is listed and approved for use only in Light Hazard occupancies. Minimum to maximum deflector to ceil-
ing distance shall be 4 inches to 12 inches(102mm to 305mm). LPCB approval of the F1FR56 Vertical Sidewall sprinkler is for installation in the
Pendent position only.
3.
Listed and Approved Temperature Ratings
Ordinary Temp. Intermediate Temp. High Temp.
Classification Classification Classification
Deflector/ 100°F(38°C)Max.Ambient 150°F(65°C)Max.Ambient 225°F(107°C)Max.
Model Temp. Temp. Ambient Temp.
Orientation 135°F(57°C) 155°F(68°C) 175°F(79°C) 200°F(93°C) 286°F(141°C)Temp.
Temp.Rating _Temp. Rating Temp. Rating Temp. Rating Rating
Orange Bulb Red Bulb Yellow Bulb Green Bulb Blue Bulb
Pendent cULus
F1FR28 Recessed Pendent cULus --
Upright cULus
F1FR40 Pendent VdS
Recessed Pendent VdS --
Pendent cULus
F1FR42 Recessed Pendent cULus --
Upright cULus
F1FR42LL Pendent -- cULus, ULH --
Recessed Pendent -- cULus, ULH --
Pendent cULus
F1 FRXLH Recessed Pendent cULus --
Upright cULus
Pendent cULus, FM, LPCB,VdS, EC
Recessed Pendent cULus, FM, LPCB,VdS, EC --
F1FR56 Concealed Pendent* cULus cULus,VdS,EC cULus --
Upright cULus, FM, LPCB,VdS, EC
"Conventional LPCB,VdS,EC
(Pendent or Upright)"
Pendent -- cULus, ULH --
F1FR56LL Recessed Pendent -- cULus, ULH --
Concealed Pendent* -- cULus, ULH --
Horizontal Sidewall cULus, FM
F1FR56 Recessed Horizontal
Sidewall cULus, FM --
F1 FR56 Vertical Sidewall (Pen cULus, FM, LPCB
dent or Upright)
* Model F1FR56 Concealed Pendent and F1FR56LL Concealed Pendent sprinklers must be used with Reliable Model
CCP cover plates. For Ordinary Temperature Classification sprinklers use a 135°F (57°C) temperature rated cover
plate. For Intermediate Temperature Classification sprinklers use a 165°F(74°C)temperature rated cover plate.
Recessed Escutcheon Data
Listed and Approved Recessed Escutcheons
Deflector/ Model F1 Model F2 Model FP
Model Orientation (Fig. 1 &3) (Fig. 1 &3) (Fig.2) SIN
3/4-inch(19mm) 1/2-inch(12.7mm) 1/2-inch(12.7mm)
adjustment adjustment adjustment
F1FR28 Recessed Pendent cULus cULus cULus RA1411
F1FR40 Recessed Pendent VdS VdS VdS RA1418
F1FR42 Recessed Pendent cULus cULus cULus RA1413
F1FR42LL Recessed Pendent cULus, ULH cULus, ULH cULus, ULH RA1410
F1FR42XLH Recessed Pendent cULus cULus cULus RA1413
F1FR56 Recessed Pendent cULus, LPCB,VdS, cULus, FM, LPCB, cULus,VdS, EC RA1414
EC VdS, EC
F1FR56LL Recessed Pendent cULus, ULH cULus, ULH cULus, ULH RA1415
F1FR56 Recessed Horizontal Sidewall cULus cULus, FM cULus RA1435
4,
2 1/4"HOLE DIA.
[57.2mm]
I 15/16"DIA
[49.2mm] ll
_
L-_ _ _
L- -_-_-I
IT Ti 1" X 1/2" REDUCER
TURN COLLAR
UNTIL TIGHT
AGAINST SPRINKLER
WRENCH BOSS \ \ FACE OF FITTING
TO FACE OF CEILING DIMENSION
II 1
��
Fl ESCUTCHEON
II r - -----i II AT MAXIMUM RECESS = 1[25.4mm]
_ AT MINIMUM RECESS = 3/8[9.5mm]
F1 ESCUTCHEON ' J
10 F2 ESCUTCHEON
3/4[19mm] ,1 . /AT MAXIMUM RECESS = 3/4[19mm]
ADJUSTMENT 5' AT MINIMUM RECESS = 3/8[9.5mm]
F2 ESCUTCHEON I 03 II
1 2' 12.7mm ������ ���� ������
] t I!'!i IPA
ADJUSTMENT (I Fl ESCUTCHEON
I`I pli
1/a" AT MAXIMUM RECESS = 7/8[22.2mm]
��n [3.2mm] AT MINIMUM RECESS = 1-5/8[41.3mm]
Iii
,'1 l,� F2 ESCUTCHEON
`,' �1 ; ' AT MAXIMUM RECESS = 1-1/8'[28.6mm]
'.,.. AT MINIMUM RECESS = 1-5/8[41.3mm]
2 27/32"DIA.
[72.2mm]
Fig. 1
Model F1 FR56,F1FR56LL,F1FR42,F1 FR40,F1FR42LL,F1FRXLH&F1FR28
Recessed Pendent sprinkler with Model F1 or F2 escutcheon
L_
I I 1" X 1/2" REDUCER
2 5/8" DIA. [66.7mm]
HOLE IN CEILING
2 5/16" DIA. [58.7mm]
CUP
L J
CEILING >s .� FACE OF FITTING
(11� TO FACE OF CEILING
Ill ®���� III I DIMENSION
_ _ _ : '
I!!!� -� �!!'I j: AT MAXIMUM RECESS = 1—1/2[38mm]
1�I" ,���
AT MINIMUM RECESS = 1 [25.4mm]
1 0`,,-..._,..i�I AT MAX/MUM RECESS = 9/16[14.3mm]
/2[12.7m m] �,, �� AT MINIMUM RECESS = 1"[25.4mm]
ADJUSTMENTm
•
1••••••••••••••••••1
31/4' DIA. t
VI.-
[82.6mm]
Fig.2
Model F1FR56,F1FR56LL,F1FR42,F1 FR40,F1FR42LL,F1FRXLH&F1FR28
Recessed Pendent sprinkler with Model FP escutcheon
5,
FACE OF FITTING
TO FACE OF CEILING DIMENSION
Fl ESCUTCHEON /A
AT MAXIMUM RECESS = 1-25.4mm]
AT MINIMUM RECESS = 3/879.5mm] / Fl ESCUTCHEON
F2 ESCUTCHEON AT MAXIMUM RECESS = 1-3/8[34.9mm]
AT MAXIMUM RECESS = 3/4[19mm] AT MINIMUM RECESS = 2 1/16'[52.4mm]
AT MINIMUM RECESS = 3/879.5mm] F2 ESCUTCHEON
AT MAXIMUM RECESS = 1-5/8741.3mm]
2 1/4" HOLE DIA. --.1-1/8" AT MINIMUM RECESS = 2-1/16[52.4mm]
[57.2mm] ` [3.2mm]
1" X 1/2" REDUCER 7
_PILI
niIAllil -f1
IIIA 1.
1 15/16" D/A.A I HIM !'4III cB [101.6mm-304.8mm]
[49.2mm] ! 11����Milli l 2 27/32" DIA. CEILING TO
i iiiii - [72.2mm] DEFLECTOR
L-- /i
ii,1 P
TURN COLLAR UNTIL
TIGHT AGAINST
WRENCH BOSS.SPRINKLER
F1 ESCUTCHEON
.3/4"[19 mrn] ADJUSTMENT
--.....--
F2
- F2 ESCUTCHEON
1/2[12.7mm] ADJUSTMENT
0,]FCOJE
RECESSED HSW W/F1 OR F2 ESCUTCHEON
(1) FM APPROVED FOR 4" - 6" [101.6MM - 152.4MM] CEILING TO DEFLECTOR WITH F2 ONLY.
Fig.3
Model Fl FR56 Recessed Horizontal Sidewall sprinkler with Model Fl or F2 escutcheon
7" x 1/2" REDUCING
TEE OR ELBOW
P
_
_ 2 5/8" DIA.
2 516" DIA �j Li HOLE IN CEILING
CUP -' - !1=`-
11 ®�';��_�lll 7 1/2" MAX.
iiiii,i;f ;'l II�'i� i�'� FACE OF FITTING
�,,,,�i,,,I If I!4 ��,
„,„,„ �� �� TO FACE OF CEILING
-,_�_ ��� �i� r/������ DIMENSION
;�������
CEILING �� ., , ,,iiiii
1/2” MAX. Illiter
COVER ADJUSTMENT 1516'"
COVER PLATE
ASSEMBLY �3 5/16" DIA. t
SPRINKLER /
CONCEALED, 1/2" ADJUSTMENT 017FG01A
Fig.4
Model F1 FR56/F1 FR56LL Concealed Pendent sprinkler with standard depth
1/2-inch(12.7mm)adjustment-Model CCP cover plate
6.
1" x 1/2" REDUCING
TEE OR ELBOW
IIf
r P2 5/8" DIA.
2 5/76" 0/A ,J '-- --= r; HOLE IN CEILING
CUP =* --- _;
0I_W__IIIIII 1 1/2 ' MAX.
FACE OF FITTING
""", z ' TO FACE OF CEILING
,,, ,� ..� li„ (,,,,,,,, DIMENSION
CEILING --• � _" ( \---" x---x—
= 4110.m
�•�
5/16" MAX. _= 3/4
COVER ADJUSTMENT
COVER PLATE
ASSEMBLY 5/7 6" DIA.
SPRINKLER
CONCEALED, 5/1 6" ADJUSTMENT 017FG02A
Fig.5-Model Fl FR56/F1 FR56LL Concealed Pendent sprinkler with low profile
5/16-inch(8.0mm)adjustment-Model CCP cover plate
Maintenance Material Data
The Model Fl FR Series sprinklers should be inspected and
the sprinkler system maintained in accordance with NFPA Frame: DZR Brass, OM Brass, or Low Lead Brass
25. Do not clean sprinklers with soap and water,ammonia or Deflector: CDA Alloy 220,260,or 510
any other cleaning fluids. Remove dust by using a soft brush Load Screw\Pintle: CDA Alloy 360 or 544
or gentle vacuuming. Replace any sprinkler which has been
painted(other than factory applied)or damaged in any way. Cup: CDA Alloy 651 or 693
A stock of spare sprinklers should be maintained to allow Washer: Nickel Alloy 440 or 360,coated with PTFE
quick replacement of damaged or operated sprinklers. Adhesive Tape
Finishes (1) Bulb: Glass
Standard Finishes
Sprinkler Escutcheon Cover plate"
Bronze Brass Chrome Ordering Information
Chrome Plated Chrome White Specify:
Polyester Plated 1. Sprinkler Model: [F1FR28][F1FR40][F1FR42]
Coated(4)>5)>6> White Painted [F1 FR42LL][F1 FRXLH][F1 FR56][F1 FR56LL]
Special Application Finishes 2. Sprinkler Deflector/Orientation: [Pendent][Recessed
Sprinkler Escutcheon Cover platee') Pendent][Upright][Conventional][Horizontal Sidewall]
Electroless Nickel Electroless Nickel Brass Bright [Recessed Horizontal Sidewall Vertical Sidewall]
PTFE(7) 3 PTFE 9 3. Sprinkler threads: [1/2-inch NPT][ISO 7-R112]
Bright Brass Bright Brass Black Plating 4. Sprinkler Temperature Rating: [135°F (57°C)][155°F
Black Plated Black Plated Black Paint
Black Paint>2>>6> Black Paint Off White (68°C)][175°F(79°C)][200°F(93°C)][286°F(141°C)]
Off White>2>>6> Off White Satin Chrome 5. Sprinkler Finish
Chrome Dull Chrome Dull 6. Escutcheon Model: [F1][F2][FP]
>1>Other finishes and colors are available on special order. Consult the 7. Escutcheon Finish (where applicable)
factory for details.Custom color painted sprinklers may not retain their 8. Cover plate Model: [standard profile CCP 1/2-inch
UL Corrosion resistance listing.Coverplate custom paint is semi-gloss, (12.7mm) adjustment][low profile CCP 5/16-inch
unless specified otherwise.
>2> cULus Listed only. (8.0mm)adjustment]
(3) 200°F(93°C)maximum. 9. Cover plate Temperature Rating: [135°F(57°C)for use
(4) cULus listed "corrosion resistance" applies to SIN Numbers RA1435 with Ordinary Temperature sprinklers][165°F (74°C)
(HSW), RA1485(VSW), RA1425 (Upright), RA1414 (Pendent) and for use with Intermediate Temperature sprinklers]
RA1415 (Pendent) in standard black or white. Corrosion resistance in
other polyester colors is available upon request. 10. Cover plate Finish
(5) FM Approvals finish as"Polyester coated"applies to SIN Number
RA1414,RA1435 and RA1425 in standard black or white. Note: When Model F1 FR Series Recessed sprinklers are ordered, the
>6>LPCB and VdS Approved finish applies only to RA1425,RA1414, RA1418 sprinklers and escutcheons are packaged separately.
(VdS)and RA1475.
>7>cULus listed Corrosion Resistant 7.
Reliable. . . For Complete Protection
Reliable offers a wide selection of sprinkler components. Following are some of the many
precision-made Reliable products that guard life and property from fire around the clock.
• Automatic sprinklers • Deluge valves
• Flush automatic sprinklers • Detector check valves
• Recessed automatic sprinklers • Check valves
• Concealed automatic sprinklers • Electrical system
• Adjustable automatic sprinklers • Sprinkler emergency cabinets
• Dry automatic sprinklers • Sprinkler wrenches
• Intermediate level sprinklers • Sprinkler escutcheons and guards
• Open sprinklers • Inspectors test connections
• Spray nozzles • Sight drains
• Alarm valves • Ball drips and drum drips
• Retarding chambers • Control valve seals
• Dry pipe valves • Air maintenance devices
• Accelerators for dry pipe valves • Air compressors
• Mechanical sprinkler alarms • Pressure gauges
• Electrical sprinkler alarm switches • Identification signs
• Water flow detectors • Fire department connection
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association,Factory
Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for almost 100 years.
Manufactured by
Reliable Automatic Sprinkler Co.,Inc. ® Recycled
( ) 88 Sales Offices Paper
RelbldIIIdUI
(800800)848431 605115Sales Fax Revision lines indicate updated or new data.
(914)829 2042 Corporate Offices
www.reliablesprinkler.com Internet Address EG.Printed in U.S.A.10/16 P/N 9999970300