Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Plans (156)
• - 'Y OFTIG.ARD ., _ POR CODE CoMPLIANCS I. �FLUCTUR APS � 1 ' •\`QED PROFFss OTC* I I �� 4�GtNFF9 .oma Permit#� Z7 t - ,( 5 66P 9� Address* l 2 9 /�. Suite /,� Y ; t/GOREGON�� P}'t � :! Da r i L f, ��j0 4, 18,2° �p JAMES E' UNIT CASING EXP. 12/31/2017 UNIT BASE AND BASE RAIL SECURE HOLDOWN TO UNIT WITH(2)#14 TEK SCREWSlir'-i „ >.. ., , , - - SECURE ANCHOR TO CURB WITH(4)#10 x 1/2"TEK SCREWS,TYPICAL 10 GAUGE STEEL'CANFAB' HVAC UNIT ADAPTER CURB OR EQUAL SEISMIC HOLDDOWN, (4)TOTAL,(1)EACH CORNER ON LONG SIDES OF UNIT SECURE HVAC UNIT ADAPTER CURB PA OFFICE COPY TO EXISTING CURB WITH MINIMUM (4)#10 x 1/2"TEK SCREWS EACH CORNER AND AT 12"O.C.AT SIDES, I: TYPICAL 1 • Ii 1SG EXISTING UNIT IL MOUNTING CURB (APPROX 14"HEIGHT) EXISTING ROOF SHEATHING ' RI EXISTING ROOFING A'..:. 01 . plc VERIFY THAT EXISTING CURB IS FASTENED TO v EXISTING SUPPORT FRAMING WITH A#14 SCREW EXISTING FRAMING MINIMUM AT EACH CORNER AND AT 24"O.C., PER PLAN EACH SIDE.IF ANCHORAGE DOES NOT EXIST, PROVIDE SIMPSON'LTP4'OR'A35'CLIPS AT EACH CORNER AND AT 48"O.C.EACH SIDE FROM THE INSIDE OF THE CURB TO THE EXISTING ROOF FRAMING NOTE: WHERE SIDE DISCHARGE UNITS ARE SUPPORTED ON WOOD SLEEPERS(I.E.NO CURBS),VERIFY THAT EXISTING UNIT IS FASTENED TO EXISTING SLEEPERS WITH A#14 SCREW AT 24"O.C. C1 HVAC UNIT ATTACHMENT DETAIL S K 1 1 1/2"=1'-0" Ir HVAC REPLACEMENT 20170472 08/14 Pxoa"o. DATE 11675 SW 67TH AVENUE JJE JJE VL MKENGINEERING PORTLAND,OR 97223+ DESIGN HVAC ATTACHMENT DETAIL SKI 3933 SW Kelly Avenue Portland,Oregon 97239 I te1:503.222.4453 I fax I wwW.Nmk.00m am.. 8/10/2017 AERICEms: Temp Control Mechanical Service Corp. 4750 N Channel Avenue#1 Portland,OR 97217 Re: HVAC Replacement Project: 11675 SW 67'1 Avenue HVAC Replacement Dear Aeric Estep: As requested, we have reviewed the (9) HVAC units to be replaced on the above noted building. The purpose of this review was to determine whether the new units and their components weigh more than the existing units and their components. (5) of the new units weighed less than the existing units, so no further analysis was needed. (4) of the new units weighed more than the existing units, so a roof framing analysis was completed and the existing joists and girders proved to be sufficient to support the heavier units. Please note that this review is for HVAC replacement only and does not address the increase in gravity load due to the concurrent reroofing project. Sincerely, SPU CT Ui PRac VLMK Engineering + Design � �GINFF�so ��S JUSTIN ELLIOTT P.E., S.E. � 566P 9r Associate I Senior Structural Engineer i OREGON J)'klti 18,2°\ �'JAMES EXP. 12/31/2017 Attachments: HVAC Unit Weight Summary, Framing Analysis VVLMK ENC I;!FCP NG 4 i-'SIGN 3933 SW r.!!;.�;e fu,dt.id 01 97239 )03.222-1453 ck"'N C01'I C.'od2Q17,20176477v92(t uloiiuj3v iemo.doxx Foae 1 of 1 — Nr VLMK PrO)CCt (((,,--1 9„j 6 71 --4 Job,;,, "p,,,,t--1.- By 0-,...„...... vole ,Z / .07- ,Pet _____ ____ ENG,NEE4ING a DESIGN ,1-1 VAL- 9-1:----pi-i-tc-C--vi,50T , • u/v IT _,______________________ ,,,-- "41-71a 11.---..c,oNomi .:E-k.. --- c,,,,i 4.-1-_ ,,,,_/tr- • -7 5q6, t' -.---- .:. i.to ((..,' ;.,Ai.) S L n:.--a- (",1A-.(- C.,-- . y12 ") , _ -r 0-1-11.L. k)1,--,A..). wl.,,,: (..,-tvl. ..,. C,SG -1/44- (CI?'4:: c ,) Ac ---f 0 kl kr LP, I (.<,AJ o Al 1 Z.ra. z' r-,-p-4 44 vivIr • := 566 4/' (9- --co,jo) --,,to... t.,k•-.-.6-- La v..1(,t.rt 7 C.:7i 'i 'f... a-uo/vorvi 1 7-.... n-- -- -" 6 — A tE 1, II > ( St.-t_L-TPt.f...... R- Cir-IR.V.,. 9 L0 ?S (4-1 Li'' x -11 .') ( uA/I r kl 1 1-R '1:i cn, 41) , A2- --- 1 i ( 1-1 T ) 'I-6-1-AL C..:><7"..y- tr.%g.:((..-14-r -- s.--7,4 4, .(-pk,om ,t_ ir.A... (Airk . . 1.11 >,_. 1,., , .• Li H ft- T(DT AL— eVE- iJ Li arc-H-7- * - 6-'4. 4' .z. 1.01 r ‘ -1--0-f-AL L-)c-r6.- Liet6-14T-- -:* S q- 1-: ---- ( ri TOAj) I I, cyl) •:,,,,, f, c) : I TOTAL j ..-.‘,p i,, -1,G-(-{T-- . „..., g t741_ I cc i _____II(c.ittl-tik) S / _.....4...._. : ,...... .. i , 0 uiv tr-5 ' IAC.--2— , Ac. /.' AL---‘t/ A —•S, AAA" Pzc..ci A(2-6 Alit— ce--Ay . , 0 unit-T-5 Acii 4c--6 \C-7, AA,(") AC-7 l'0?-, k L-s--fi‘v 1 ci-A -11-k'A Ai 11-0---- E---4q s7110(1"- '-'it-rs ; 5 4:1 e3 F 0 fil tr2-0A-1 1?..,.. tkiVA.1—`1C I 5 , , . - - ' . , . , . . . : • . , , . , . 3933 SW Kelly Avenue Portland,OR 97239 tel:503.222.4453 fax: 503.248.9263 wvvw.vimk.com ' Vr V I.. M K Pr ojer 1 / '7 C <,.,..! -1-7'. Joh It''2_0 BY- !--J o 77--. ::),:ite. s if-:,.....,..__,,-7 'Meet — ENGINEERING,DESIGN . . . MVAc._ .t.,.), i 6--tiT C--, cr-k.P:1 ..) . i..-5 a-(7,,3 ,...rr--"..-- Aro.,) A ..r."-•7 c.---1(;.:: R.t.1.‘; A__AC-1:.1•-et,t 1,!-:-.A)°T" : ' _ 5--Pi (q, Tt..( .1 --r-c-1-4 t___ yi-6- t,,, to-f-1-7-- ---, 51'--i .'"(-''''')°-'14/ -2:Z•v2,-. '':" '''-' * - Cc...a' LIT P 6_-R. .% . 7..0r/4.,1..... At C.:/ A 1,....3 CI et-447- i---:-. G -s G ( 1,...P,11-.4 g:c.,0A.,,0.An 1 1-i',"..IR.. if uA./IT ... . (. 5 TO A-) ') c A.ps)A rf..;,:n-Jt),-,e---r/5'/..0 Litrfi. 47,-- i 1.6.7.,-4.- ( kik% A,• •, -...' too 1-°7-AL IVs) (Cr4,47' . .. . , . _ AL. 3 uA-)17 t,•,/Ci-H L;Crofvo Ai i'?.- 19.. ',-- 59 L-/- 4 ' 1.(PVIT cA c.s i...LE.a:7 4 v c.-1-/1.1..lat-felf-? ,:• ('2 ti ' I -1--()T.l -• -)(-r'('-' Wr=I 6-147, 1:=.' 7 ii .4'1- , ecoLA.,,om 1 r',:-.41Z : 7, 2...6 tir C).ef 9 .4' i• (3' . .T.' - —..-_-..--,-2.....-..(..,....,....,...--..—...L..,...,- .—.---, . . . . AL H UNIT Wri-44 'r,COA/0/1`14- 6-k.: 74' .q,,,91t41--' ittiAi IT" . ., r_r§,f)si4LEL-'17.00.7-1 5/ FEPE-P,-- 1-2-5 *1 1 c...-tik...Z. At D A('''rei:g. -'"- 100"g' i • . ( s -tc) . . . 1 , . • .. -r oT AL t-x-r6- W E16-14-r = i I 9 1*'• 1 ,L---c.04./(.)m/ 4..4.•(Z., : --• z-(--4 ' f . royls,L_. 4/41j.i,./g•1.6-147- _ ---;..7.9.:1,tt- ..., , • .... ...,_ . . . . hp -.-itotvp. ( ; 1-0/j) C-IVP'5141f.E,71/1Y4C-T/ L-L:Petlk T .t21idi '.4 Cc/P.E..s iAA '-'1P ' t=. 1. 0 o , • , , ; 0,9 9 4, I.a -•-/(-r6;- 14•-'/(r--1-1.-t- ; -7- --/i 4/ 14. _1'.., EtoN0114/7.1::::R. '''''--' 26 . . . . ...,-r-GT,4L..., me 1.,./, wEl(r,47 :„- ."112- 14 • "' • , . . , . . . . . . , .. - , .. . , • • 1 , . . • 3933 SW Kelly Avenue Portland,OR 97239 tel:503.222.4453 fax: 503.248.9263 www.ylnik.com - NfrVLIVIK Project (C . 5j Jo!) 0,f By , S-heel FI,G IN EE RING DESIGN — FRAMiAJG— ' VJ ,\JA-1(7-5 Zr S k(2_ ',>p A A) .44 op, - k QA.11-y AC- Ai A ;-)05-ri- 16-t,./iF-v...itAJTL.:1, I do(-IA, c 15. (3,1k1 • '1- tST-0 '5AI 1,--) 1-0 6.C..) 9 0, 04.; CC?0 kC_C, PLIA.G02 s e\a • s 111.11111111111111111 1,3 atztp-s Mill.111111.111 ‘...‘„, • • • (1,J 4- k")5L 4" k,`) L / I °-)PCF 2_S PST- k"2_. S F) (PST-R )12/ + ( t„IS) 1L1 1- FT> (-2);i Le,-Pr (SE E C_, • . S-1`,..S 0 V--itsci" `7"-• $t.J.? er'r AC_ ' 41( 7 AC8 G-riRD"--5 1-144/0- A LAR-1-'15- Ai (24 . P '-Co 4=1 t/VC...R.C4SI-C IA/ arG-RT c A 8 I 3933 SW Kelly Avenue Portland,OR 97239 tel:503.222.4453 fax:503.248.9263 www.vImk.com ` Nr VLMKi;,.;,,fSW 67 HVAC 20170472 l -: WOD 8/17 C-4 ---- ----------- -------- --------- --------------v4 00-Software Copyright 2015 VLMK Consulting Engineers. All Rights Reserved. i Snow Drift Design - Flat Roofs Based on the 2012 International Building Code Section 1608 and ASCE 7-10 Chapter 7 i, jR. ii,, SURCHARGEt.OAD • I DUE TO DRIFTING / DUE TO D IFTINGD r ' '/ BALANCED SNOW-- f I) .6-1.- t BALANCED SNOW aothumailim:ID __ r LOAD I 11111 LiIIhiii111 .. _k, �,iiiiiiiiiiiiii=iiiin iiiiiiiiiiii,iiiiil ■ii70 ' t // , ,/ / I _ — W �. s W .--- ,- - F -4 3 -�.a Ii Drift Type 'L' - drifts on lower roofs Drift Type 'P' - drifts on projections (e.g. stepped roofs and canopies) (e.g. parapets and mechanical units) i i pg= 10 psf ground snow load [Figure 7-1 &Table 7-1] i Ce— 1.00 exposure factor [Table 7-2] Ct= 1.00 thermal factor [Table 7-3] 1s= 1.00 importance factor [Table 7-4] t I Pf= 7 psf snow load on flat roofs (roof slope 5 5) [Eqn. 7.3-1] Pmin= 10 psf minimum snow roof load [Section 7.3.4] Pf(design)= 25 psf design snow roof load j y = 17.3 pcf density of drifted snow, not to exceed 30 pcf [Eqn. 7.7-1] 4 hb= 1.45 ft height of balanced snow load, oily l„= (input below) length of roof upwind of the drift (leeward drift) li= (input below) length of lower roof(windward drift) hr= (input below) total height of roof projection i hd= (calculated below) height of snow drift i Pmax= (calculated below) max drift load + roof snow load, y(hd+hb) i ( drift l Il hr hd he Pmax W Pd ; Location type (ft) (ft) (ft) (ft) (ft) (psf) (ft) (psf) I Lower Roof(Addition) P 20.0 20.0 15.0 0.7 13.6 37.5 2.9 12.5 , 1 9 I I I I 1 i i i I A 3933 SW Kelly Avenue PoitIond,09 97239 tel: 203.222.4433 fav S03.248.9263 mcw. 14.com 914''1r SECTION 1: 91/2"-16" TJI® JOISTS C5 JOISTS This section contains design information for 9W-16"deep Trus Joist®TJI®joists. These standard-size TJI(6'joists are readily available through your local Weyerhaeuser dealer or distributor. Offered with the flange sizes shown below,they come in lengths up to 60' (in 1'increments). Design Properties (100%Load Duration) + r1w Basic Properties Reaction Properties 1'/a"-13/8-"�- I Maximum Maximum 3W'Intermediate 5%"Intermediate Depth Tll® Joist Resistive Joist Only Vertical 1'/a"End 3'h"End Reaction(lbs) Reaction(lbs) 3/i 6„ 11/Z8" Weight Moment(7) EI i 10 Shear Reaction Reaction 14" (lbs/ft) (ft-lbs) (in.-lbs) (lbs) (lbs) (lbs) No Web With Web No Web With Web 16" Stiffeners Stiffenersr21 Stiffeners Stiffenersr2r I 110 2.3 ' 2,500 i 157 1,220 910 1,220 1,935 ' N.A. 2,350 I N.A. T110 110 joists 9W 210 2.6 3.000 I 186 1.330 1,005 1,330 2,145 N.A. 2,565 N.A. 230 2.7 ' 3,330 206 ! 1,330 1,060 1,330 2,410 I N.A. 2,790 N.A. t-2V6" 110 2.5 3,160 , 267 1,560 910 1,375 1,935 2,295 2,350 2,705 i 210 2.8 3,795 ; 315 1,655 1,005 1.460 2,145 2,505 2,565 2,925 11/4"-11/2" 112/8" 230 3.0 4,215 ; 347 1655 1,060 1485 2,410 2,765 2,790 3,150 91/2" 360 3.0 6,180 ;_ 419 1,705 1,080 1,505 2,460 2,815 3,000 3,360 11'/8" 560 4.0 9,500 I 636 2,050 1,265 1,725 3,000 f 3,475 3,455 3,930 14° 110 2.8 3,740 I 392 1,860 910 1,375 1,935 2,295 2,350 2,705 16 210 3.1 4,490 1 462 1,945 1,005 1,460 2,145 2,505 2,565 2,925 14" 230 3.3 4,990 i 509 1,945 1,060 1,485 2,410 2,765 2,790 3,150 T110 210 Joists 360 3.3 7,335 : 612 i 1,955 1,080 1,505 2,460 2,815 3,000 3,360 560 4.2 11,275 i 926 2,390 1,265 1,725 3,000 1 3,475 3,455 j 3,930 j -25/16 110 3.0 4,280 I 535 2,145 910 1,375 1,935 2,295 2,350 2,705 11/4"-11/2"210 3,3 5,140 629 2,190 1,005 1,460 2,145 j 2,505 2,565 ( 2 _925 -� 16" 230 3.5 5,710 , 691 2,190 1,060 1,485 2,410 J 2,765 2,790 3150 117/8" 360 3.5 ! 8,405 830 2190 1080 1,505 2,460 i 2,815 3,000 i 3,360 3/8" - 14" 560 4.5 12,925 f 1,252 -- 5 i- - 2,110 1,265 1,125 3,000 � 3,475 3,455 � 3,930 16" (1)Caution:Do not increase joist moment design properties by a repetitive member use factor. (2)See detail Won page 27 for web stiffener requirements and nailing information. TJ1®230 joists General Notes For Tll® + -� 1--25/16"110,210,230,and 360 Joists ■ Design reaction includes all loads on the joist.Design shear is computed at the4= 22.5 w12, + 2.67 wL2 13/8" inside face of supports and includes all loads on the span(s).Allowable shear El d x 105 11'e" may sometimes be increased at interior supports in accordance with 3/8"- 14" ICC ES ESR-1153,and these increases are reflected in span tables. For T.11/6 560 Joists 16" ■ The formulas at right approximate the uniform load deflection of 4(inches). 4= 22.5 wL° + 2.29 wL2 { El do 105 T11®360 joists w = uniform load in pounds per linear foot SomeMeoistseriesma not be available L =span in feet �1 I-3�" TIle joists are intended / y d =out-to-out depth of the of I for dry-use applications in your region.Contact your Weyerhaeuser P joist 13/8+ representative for information. EI =value from table above j--- 7/i6" 14" 16" TJ1®560 joists 1WARNING WARNING NOTES: lack of proper bracing during construction can result DO NOT walk on joists in serious accidents.Observe the following guidelines; until braced. Joists are ` IN/UNYMAY RESUU. unstable 1. All blocking,hangers,rim boards,and rim joists at the end supports of the TJI®joists must be completely installed and properly nailed. until braced 2. Lateral strength,like a braced end wall or an existing deck,must be established at the ends DO NOT stack laterally of the bay.This can also be accomplished by a temporary or permanent deck(sheathing) Al II ft building materials on fastened to the first 4 feet of joists at the end of the bay. unsheathed joists. Bracing Includes: 'V Stack only over 3. Safety bracing of 1x4(minimum)must be nailed to a braced end wall or sheathed area(as in NNW beams or walls. •Blocking note 2)and to each joist.Without this bracing,buckling sideways or rollover is highly probable •Hangers under light construction loads-such as a worker or one layer of unnailed sheathing. •Rim Board 4. Sheathing must be completely attached to each TJI®joist before additional loads can be 171 DO NOT walk on joists •Sheathing placed on the system. .\ that are lying flat •Rim Joist 5. Ends of cantilevers require safety bracing on both the top and bottom flanges. •Strut Lines 6. The flanges must remain straight within a tolerance of y"from true alignment. Trus Joist®TJI®Joist Specifier's Guide TJ-4000 I February 2017 6 a Trane Foundation Gas/Electric Rooftop Unit Overview-GBC048A3EMA**000000000000000000000000000 Application Unit Size pP Supply Fan External Dimen5iofiSOfi:j i�` ` '� lJ {get�� � ' EER IEERISEER External Gas/Electric 4 Ton Airflow Static Height Width Length Minimum Maximum Pressure 12.0 EER 14.00 1600 cfm 0.500 in H2O 3.55 ft 3.99 ft 6.40 ft 566.0 lb 765.0 lb Unit Features Fresh Air Selection Without fresh air selection Supplyfan/Drive!Standard drive motor MotorType Unit Electrical Voltage/phase/hertz 208-230/60/3 MCA 23.60 A -y MOP 35.00 A SCCR Rating None Controls Unit Controls Electro-mechanical System Monitoring Controls 1 Without system montioring controls System Monitoring Controls 2 None Cooling Section Entering Dry Bulb 80.00 F Entering Wet Bulb 67.00 F Gross Total 49.59 MBh Ambient Temp 95.00 F Gross Sensible 38.53 MBh Leaving Unit Dry Bulb 58.12 F Net Total 48.09 MBh Leaving Unit Wet Bulb 57.02 F Net Sensible 37.03 MBh Refrig Charge-circuit 1 4.6 lb Heating Section Heat Type Gas heat Heating Stages 2 Output Heating Capacity 92.00 MBh Output Heating Capacity with Fan 92.00 MBh Heating EAT 70.00 F Heating LAT 123.00 F Heating Temp Rise 53.00 F Fan Section Indoor Fats Data` °t e t`Fan Mata• Type FC Centrifugal Type Propeller Drive Type Belt Fan Quantity 1 Indoor Fan Performance Drive Type Direct Airflow 1600 cfm ittotilitirSlitPerformance Design ESP 0.500 in H2O Condenser Fan FLA 1.40 A Component SP 0.000 in H2O > n Data Total SP 0.500 in H2O Type FC Centrifugal Indoor Motor Operating Power 0.54 bhp Drive Type Direct Indoor Motor Power 0.40 kW - alarf Performance Indoor RPM 856 rpm Exhaust Fan Power 0.25 kW Exhaust Fan FLA 5.00 A Compressor Section Accessories Circuit 1 RLA 13.70 A Roof curb Roof curb(3-5 Tons) Circuit 2 RLA 0.00 A Fresh air selection 0-100%Economizer,Dry Bulb - Downflow 2017-07-19719:44:42 Barometric Relief yes Pagel of 10 I. Warranty Parts Less Compressor None Afik NOTES: 1.THRID THE-BASE ELECTRICAL IS N0 STANDARD ON ALL UNITS, 2.VERIFY WEIGHT,CONNECTION,AND ALI.DINE.NSION WITH INSTALLER DOCUMENTS BEFORE INSTALLATION / 3. DISCONNECT SWITCH IS NOT STANDARD ON ALL.IINRS. DISCONNECT 'A SWITCH �= A ` SEE NOTE(3) V THRU THE BASE �. J"! GAS CONNECTION/ �` ` HORIZONTAL RETURN KNOCK OUT W/DUCT OPENING COVER ft CONDENSATE DRAIN CONNE.CT ION GAS CONNECTION H ORIZONTAL SUPPLY GAS EXHAUST WIDU CT OPENING COVE R FILTER ACCESS [:''...,:,....... ... 40 . CUSTOMER POWER _ CONDU IT CONNECTION ` 001. ` e RE FRIGE RANT GAUGE ACCESS CONDENSATE DRAIN .255/CS"—.. 511!76" CONNECTION(1")NPT CONNENSA!ECTION DRAM CONNECTION (1`)NPT I--RETURN IIP FLOW 1� 1 10 7/8" I 17 4" 30" 73/6° 5 1/6"-_— ---,yid( ? F f 3116" x-27 3116" r_i / ' 511/16^ CONDENSATE DRAIN DOWNF LOW SUPPLY ) 2LI 314'•••,•- 1.,,,--____74 "- DIMENSION DRAWING r d512" �7d3/6' HORIZONTAL RETURN 9/16" - 3/16" S PPLYNTAL. 16314"- 10 1/2" IIII SII PP LY Il NIII _ �,,,IIi 42" 125116„ I1LI--�-- ©I i1 f.-'i 16" Y =�IIC r �." 88116" 0�l�tss�n .� L111—MII_ 7 3/6" 42 9116" 28 3/4" - 7 ., 7 1/4" - II 77P6" 4311/16" 7716" - 37 1/2" 44 11/16" - 15 7/6" 24" - 76 13/16" 4715116" •- 203/4" 4715/16" 3-5 PACKAGED CLING DIMENSION DRAWING 2017-07-19719:44:42 Page 2 of 10 r l$. G . • ELECTRICAL/GENERAL DATA GENERAL cm+xa nx+m HEATING PERFORMANCE Model: GEIC048 Oat.reined Motor HEATING-GENERAL DATA Unit Operating Voltage: MCA: Unit Primary Voltage: 208 MFS: Heating Model: Medium Unit Secondary Votage 230 MOP: H eating Input(BTU): 115000/92000 Unit H ertz: 60 H eating Output(BTU): 920011/7 360 0 Unit Phase.: 3 No.Burners: 3 N o.Stages 2 EER: 12/14 IEEROne Speed Fan; - Gas mlelPressure IEE R Muth Speed Fan: .. Natural Gas(Min/14 ax): 4.5/14.0 er,me LP(Min/Max) 11.0114.0 in.mc Standard Motor Field Insisted Oversaed Motor Gas Pipe Connection Size: 1/2` MCA: 23.E MCA: MFS: 35,0 MFS: MCO: 35.0 MCB: 'INDOOR MOTOR Standard M oto r Oversized Motor Field Installed Oversized Motor Number. 1 Number: Number Horsepower: 1.0 Horsepower: Horsepower: Motor Speed(RPM): - Motor Speed(RPM): Motor Speed(RPM): Phase 3 Phase Phase Fut Load Amps: 50 Fut Load Amps: Fut Load Mips: Locked R oto r Amps: 24.5 Locked Rotor Amps: Locked Rotor Amps COMPRESSOR Circuit 1/2 OUTDOOR MOTOR Number. 1 Number. 1 Horsepower 5.39 Horsepower. 0.33 Phase: 3 Motor Speed(RPM): Rated Load Amps: 13.7/15.3 Phase: 3 Locked Rotor Amps: 83.1 Fut Load Amps: 1.4 Locked R otorAm pa: 4.6 POWER EXHAUST ACCESSORY (3) FILTERS REFRIGERANT (2) (Field Installed Power Exhaust) Type: R-410A Phase: Type: Throwaway Horsepower. Furnished: Yes Factory Charge: Motor Speed(RPM); Number 4 Crcult 141 4.6 lb Fut Load Amps: Recommended 16'316",2" Circuital Locked RolorAmps: NOTES: 1. Maximum(HACR)Circuit Breaker sizing Is tor instatktions in the United States only. 2, Refrigerant charge is an approximate value.Fora more precise value.see unit nameplate and service instructions 3.Value does not include Power Exhaust Accessory. 4. %lug does not include Heater. 5.Value include Standard Motor. 6.Value it dude Oversized MI otor 7.PER is rated at MRI conditions and in accordance eth DOE test procedures 6.For Com pressor Motors and Condenser Fan Motors:Amp draw for each motor,multiply valve by number of motors to determine total amps. 9. HP breach compressor. 10. Integrated Energy E tkciency Ratio(IE ER)is rated in accordance with AH RI standard 210/240 or 360. 2017-07-19T19:44:42 Page 3 of 10 4 , Base Unit and Corner Weights only Elase unit weights Comer Weights Center otGrevity SNIPPING NET O O ® O E E 616.0 lb 1166.9 tr 110.0 lb 119.01b 176.0 lb 16211 lb 40" 29" 1.AN rreigtrls are atrproximate 2.The actual weight are listed on the un d nameplate. - j 3.Refer to unit nameplate and installation guide tor weights before scheduling transportation and installation otund•• . • 4.T he weight shown represents the typical unit operating Height tor the conigurattn n illselected.E:stdnated at 4/.10 %ofthe nameplate varight., t t� 6.Verify weight,connection,and all dimension with in documents before installation. S.Corner weights are given for information only, 7.14 ell&hipp dip weight at optional accessories should be added Io unit weight when ordering lfdory or Meld installed accessories. �I11 Installed Options Net Weight Data nk .Acce rY Weight E onnmi=Manual and Motorized Outside Air Damper 260 lb Barometric Refs f 7,0 lb Power Exhaust Root Curti 61.0 lb °waited Motor PACKAGED COOLING PLAN VIEW Disconnect RIGGING DRAWING Had Guard Through the Elena • 1.Weights for options are approximate. 2.Weights for notions.that are not list ruler to Installation guide. A w, © O ii •'j >,, El 'd; + ` 11i SII ki t r.'i ii'+''SIJ i' jI � •H . FIL 0 I:ACKAGED COOLING PLAN VIEW CENTER OF GRAVITY DRAWING 2017-07-19719:44:42 Page 4 of 10 �'..� f ApA ,,v; NOTES: BRCN OE UPJIT. 1.TH RU-THE-BASE ELECTRICAL IS NOT STANDARD ON ALL UNITS. CLEARANCE 6U" • --,6 • iI HORIZONTAL RETURN II f(Ill�;�f,��t\�l l�ll i ' /� rcth w,lIkd/i/CLFARANGE 6II" ( -±------` � 11> CLEARANCE<6" 1 \ �— HORIZONTAL SU PP LY ,c:U7, CLEARANCE 36" FRONT OF UNIT PACKAGED GAS/ELECTRIC PLAN VIEW CLEARANCE DRAWING ji ' • • • • • • ` • \ ` 4' / 3515/16" i • • PACKAGED GAS/ELECTRIC PLAN VIEW DOI/VNFLOIN CLEARANCE DRAWING 2017-07-191-19:44.42 Page 5 of 10 NOTES: 1.VERIFY WEIGHT,CONNECTION,AND All DIMENSION WITH INSTALLER DOCUMENTS BEFORE INSTALLATION LI PFLOW RETURN THROUGH THE BASE CONDENSATE I DOWNFLOW SUPPLY 0111111111' PACKAGED GAS ROOF CURB DIMENSION DRAWING 323/18" .4-1 V44 .4— 1 H' —4. i 1 134"—I 187 14 7,18" 0 I24 1010" 21 1'180 l 70 7,8" — 13y"1 141110'—.. .4—1 34" RAN VIEW OF UNIT DIMENSION DRAWING i I I 14" 70 7/8" 1 70 1!8" 47 _ I FRONT VIEW OF UNIT RIGHT VIEW OF UNIT DIMENSION DRAWING DIMENSION DRAWING 2017-07-19719:44:42 Page 6 of 10 NOTES; 1.VE RIFY WEIGHT,CONNECTION,AND ALL DIMENSION WITH INSTALLER DOCUMENTS BEFORE INSTALLATION FAN GRILLE ) i HORIZONTAL RETURN WI DUCT OPE NING COVER - HORIZONTAL.SUPPLY W/DUCT OPENING COVER -- ,1:% It ".*-5 : `e. COIL BAROMETRIC RELIEF HOOD 140 BAROMETRIC RELIEFHOOD DIMENSION DRAWING HORIZONTAL.RETURN FAN GRILLE W/DU CT OPENING COVER FILTER ACCESS BARONET RIC RELIEF HOOD HOOD1BAROMETRIC 1111111 RELIEF 11/ I COIL i_____ I ,r il ". 1711 411111111 . I I IMI O MINIM".=IC - 1...--4 119" 7 13116" HORIZONTAL.SUPPLY WIOUCTOPENING COVER - 137/16" - BACK NEW OF UNIT RIGHT VIEW OF UNIT DIMENSION DRAWING DIMENSION DRAWING 2017-07-19T19:44:42 Page 7 of 10 • NOTES; t\ff:RIFE WEIGHT,CONNECTION,AND ALL DIMENSION WITH INSTALLER DOCUMENTS BEFORE INSTALLATION FAN GRILLE COIL. HORIZONTAL SUPPLY _- W/DU CT OPENING COVER ~ CONDEN SATE DRAIN CONNECTION ���._ / E.CONOMIZER HOOD H ORIZONTAL RETU RN W/DUCT OPENING COVER ECONOMIZER HOOLI DIMENSION DRAWING ECONOMIZER HOOD HORIZONTAL.RETURN FAN GRILLE W/DUCT OPENING COYER FILTER ACCESS -- - - HORlZbNTAL.SUPPLY -_- W/DUCT OPE NINE COVER MOTORIZED HOOD 1.110111 11111 BACK VIEW OF UNIT RIGHT VIEW OF UNIT DIMENSION DRAWING DIMENSION DRAWING 2017-07-19719:44:42 Page 8of 10 Agt 7 11,4','1 3 thru 5 Ton General The units shall be dedicated downflow or horizontal airflow. The operating range shall be between 125.0 F and 40.0 F in cooling as standard from the factory for all units. Cooling performance shall be rated in accordance with ARI testing procedures. All units shall be factory assembled, internally wired, fully charged with R-410A, and 100 percent run tested to check cooling operation, fan and blower rotation and control sequence, before leaving the factory. Wiring internal to the unit shall be colored and numbered for simplified identification. Units shall be UL listed and labeled, classified in accordance to UL 1995/C 22.2, 236-05 5rd Edition. 3 thru 5 Ton Casing Unit casing shall be constructed of zinc coated, heavy gauge, galvanized steel. Exterior surfaces shall be cleaned, phosphatized, and finished with a weather-resistant baked enamel finish. Unit's surface shall be tested 672 hours in a salt spray test in compliance with ASTM B117. Cabinet construction shall allow for all maintenance on one side of the unit. In order to ensure a water and air tight seal, service panels shall have lifting handles and no more than four screws to remove. All exposed vertical panels and top covers in the indoor air section shall be insulated with a 1/2", 1.0 lb density foil-faced, fire-resistant, permanent,dorless, glass fiber material. The base of the downflow unit shall be insulated with 1/2", 1.0 lb density foil-faced, closed-cell material. The downflow units base pan shall have no penetrations within the perimeter of the curb other than the raised 1 1/8" high supply/return openings to provide an added water integrity precaution, if the condensate drain backs up. The base of the unit shall have provisions for forklift and crane lifting. 3 thru 5 Ton Compressors All units shall have direct-drive, hermetic, scroll type compressors with centrifugal type oil pumps. Motor shall be suction gas-cooled and shall have a voltage utilization range of plus or minus 10 percent of nameplate voltage. Internal overloads shall be provided with the scroll compressors. All models shall have phase monitors and low and high pressure control as standard. 3 thru 5 Ton Controls Unit shall be completely factory wired with necessary controls and contactor pressure lugs or terminal block for power wiring. Unit shall provide an external location for mounting a fused disconnect device. 3 thru 5 Ton Discharge Line Thermostat A bi-metal element discharge line thermostat is installed as a standard option on the discharge line of each system. This standard option provides extra protection to the compressors against high discharge temperatures in case of loss of charge, extremely high ambient and other conditions which could drive the discharge temperature higher. Discharge line thermostat is wired in series with high pressure control. When the discharge temperature rises above the protection limit, the bi-metal disc in the thermostat switches to the off position, opening the 24 Vac circuit. When the temperature on the discharge line cools down, the bi-metal disc closes the contactor circuit, providing power to the compressor. 3 thru 5 Ton Evaporator and Condenser Coils Microchannel coils will be burst tested by the manufacturer. Microchannel condenser coils shall be standard on all units. Coils shall be leak tested to ensure the pressure integrity. The evaporator coil and condenser coil shall be leak tested to 225 psig and pressure tested to 450 psig. Sloped condensate drain pans are standard. 3 thru 5 Ton Filters Two inch standard filters shall be factory supplied on all units. 3 thru 5 Ton Gas Heating Section The heating section shall have a tubular heat exchanger design. An induced draft combustion blower shall be used to pull the combustion products through the firing tubes.The heater shall use a direct spark ignition (DSI) system. On initial call for heat, the combustion blower shall purge the heat exchanger for 20 seconds before ignition. After three unsuccessful ignition attempts, the entire heating system shall be locked out until manually reset at the thermostat. Units shall be suitable for use with natural gas or propane (field-installed kit) and also comply with the California requirement for low NOx 2017-07-19719:44:42 Page 9 of 10 ' . ' i emissions (Gas Heat Only). 3 thru 5 Ton High Pressure Control All units include High Pressure Cutout as standard. 3 thru 5 Ton Indoor Fan Units above shall have belt driven, FC centrifugal fans with adjustable motor sheaves. All motors shall be thermally protected. Oversized motors shall be available for high static application. All indoor fan motors meet the U.S. Energy Policy Act of 1992 (EPACT). 3 thru 5 Ton Low Pressure Control All units include low pressure cutout as standard. 3 thru 5 Ton Outdoor Fans The outdoor fan shall be direct-drive, statically and dynamically balanced, draw-through in the vertical discharge position. The fan motor(s) shall be permanently lubricated and shall have built in thermal overload protection. 3 thru 5 Ton Phase Monitor The Phase Monitor is a three-phase line monitor module that protects against phase loss, phase reversal and phase unbalance. It is intended to protect compressors from reverse rotation. It has an operating input voltage range of 190-600 Vac, and LED indicators for ON and FAULT. There are no field adjustments and the module will automatically reset from a fault condition. 3 thru 5 Ton Refrigerant Circuits Each refrigerant circuit shall have independent thermal expansion valve, service pressure ports, and refrigerant line filter driers factory installed as standard. An area shall be provided for replacement suction line driers. 3 thru 5 Ton Unit Top The top cover shall be double hemmed and gasket sealed to prevent water leakage. Field Installed 3 thru 5 Ton Barometric Relief Designed to be used on downflow units, barometric relief is an unpowered means of relieving excess building pressure. 2017-07-19T19.44:42 Page 10 of 10 Trane Foundation Gas/Electric Rooftop Unit Overview-GBC060A3EMA**000000000000000000000000000 Application Unit Size $uipply Pan External bmensions.n1j,, 1WeIgtt`. EER IEER/SEER External Gas/Electric 5 Ton Airflow Static Height Width Length Minimum Maximum Pressure 12.0 EER 14.00 2000 cfm 0.500 in H2O 3.55 ft 3.99 ft 6.40 ft 586.0 lb 785.0 lb Unit Features Fresh Air Selection Without fresh air selection SupplyFan/Drive/ > MotorType Standard drive motor Unit Electrical Voltage/phase/hertz 208-230/60/3 MCA 26.40 A _ MOP 40.00 A , SCCR Rating None > Controls Unit Controls Electro-mechanical System Monitoring Controls 1 Without system montioring controls System Monitoring Controls 2 None Cooling Section Entering Dry Bulb 80.00 FaiiTY Entering Wet Bulb 67.00 F Gross Total 59.01 MBh Ambient Temp 95.00 F Gross Sensible 43.34 MBh Leaving Unit Dry Bulb 56.16 F Net Total 57.57 MBh Leaving Unit Wet Bulb 55.32 F Net Sensible 41.89 MBh Refrig Charge-circuit 1 5.0 lb Heating Section Heat Type Gas heat Heating Stages 2 Output Heating Capacity 92.00 MBh Output Heating Capacity with Fan 92.00 MBh Heating EAT 70.00 F Heating LAT 112.40 F Heating Temp Rise 42.40 F Fan Section Indoor an Pita «,,g - ` Type FC Centrifugal Type Propeller Drive Type Belt Fan Quantity 1 indoor Fag Performance Drive Type Direct Airflow 2000 cfm F ;01414446 00formince Design ESP 0.500 in H2O Condenser Fan FLA 1.40 A Component SP 0.000 in H2O Total SP 0.500 in H2O Type FC Centrifugal Indoor Motor Operating Power 0.85 bhp Drive Type Direct Indoor Motor Power 0.63 kW ecliaWfan PetiOn00004 Indoor RPM 967 rpm Exhaust Fan Power 0.25 kW Exhaust Fan FLA 5.00 A Compressor Section Accessories Circuit 1 RLA 16.00 A Roof curb Roof curb(3-5 Tons) Circuit 2 RLA 0.00 A Fresh air selection D0-100% y Economizer,Dr Bulb - ownflow 2017-07-1971938.16 Barometric Relief yes Page 1 of 10 Warranty Parts Less Compressor None 40 N C)TES: 1.THRII-THE:-EIASE.E.LE CTRICAL IS NOT STANDARD ON AL.L UNITS. 2.VERIFY WEIGHT,CONNECTION,AND ALL DIMENSION WITH INSTAL.LER DOCUMENTS BEFORE INSTALLATION 3. DISCONNECTSWITCH IS NOT STANDARD ON ALL UNTTS. DISCONNECT SWITCH s. SEE NOTE(3) C`Q .4,1 44411%444......t THRU THE BASE GAS CONNECTION ` HORIZONTAL.RETURN KNOCK OUT 0. WI DUCT OPENING COVER CONDENSATE.DRAIN CONNECTION GAS CONNECTION H OR I2ONTAL.SUPPLY GAS EXHAU ST W/DU CT OPENING COVER FILTER ACCE SS m0 CUSTOMER POWER �` I. CONDUIT CONNECTION RE FRIGE RANT GAUGE ACCESS CONDENSATE DRAIN -0-25,5/R"--o- 5 79/16" CONNECTION(1")NPT CONNCONNECTIONECTION NSATE DRAIN _ (1")NPT J RETURN UPFLOW ^`- 107/8" 'n 17 4" 30• 7 3/EI" 51/8"�.ti-Q—� .".� _______i P 813HE" b--273!16" I -.5 11/16" CONDENSATE DRAIN DOWNFLOW SUPPLY 121/13"- DIME NSI 219 3/4,... ON DRAWING 1.._____74 YB" HORIZONTAL RETURN^ 4512" - 8116° - 3/16" HORIZONTAL SUPPLY 16 3/4"- initD 1/2" MI II R: 1 19 112 ij" 0 p 1 i 11111 , MIIIMILAIMI 11.111111111.0 Ei" Al' '��--_1 7 3/8" 42 3116" - 29 3/4" - 73/6" 71/4" - . 7718" 43 11/16" 7 7/6" 3712" 44 11/16" - 15 7/8" 24' - 76 13/16" 47 15/16" 20 3/4" 47 95116" 3..5 PACKAGED COOLING DIMENSION DRAWING 2017-07-19719:38:16 Page 2 of 10 ELECTRICAL/GENERAL DATA GENERAL (2x4xtwx10) HEATING PERFORMANCE. Model: G6C060 Oversized IAotnr fHEATING•.GENERAL.DATA Unit Operating Voltage: .. MCA: Unit primary\tillage: 208 MFS: Heating Model.: Medium Unit Secondary Voltage 230 MCB: H eating Input(BTU): 115000/92000 Unit H ertz: 60 H eating Output(13T11): 92000/7 3000 Unit Phase: 3 N a.Burners: 3 No.Stages 2 EER: 12/14 IEE.R One Speed Fan: _ Gas holed Pressure IEER Multi Speed Fan: _ Natural Gas(Mined ex): 4.5/14.0 in.we LP(M in/Max) 11.0/14.0 in.we Standard M afar Field Installed Oversized Motor Gas P;ee Cannecdion Size: 1(2" MCA: 26.4 MCA: MES: 40.0 MFS: MCB: 40.0 MCB: 'INDOOR MOTOR Standard M cr/ar Oversized Motor Field Installed Oversized Motor Number. 1 Number: Number Horsepower. 1.0 Horanpower: Horsepower: Motor Speed(RPM): -- Motor Speed(RPM): Motor Speed(RPM): P3 Phase Phase Fun Load Naps: 5,0 Fut Load Amps: Full Loyd Amps: Locked Rotor Amps: 24.5 Locked Rotor Amps: Locked Rotor Amps: COMPRESSOR Circuit 12 OUTDOOR MOTOR Number: 1 Number. 1 Horsepower: 6.45 Horsepower 0.33 Phase: 3 Motor Speed(RPM): - Rated Load Amps: 16.0/17.8 Phase: 3 Locked Rotor Amps: 110.0 Fut Load Amps: 1.4 Locked Rotor Am Ps: 4.6 POWER EXHAUST ACCESSORY (3) FILTERS REFRIGERANT (2) (Field Installed Power Exhaust) Type: R-410A Phase: Type: Thmwawey Horsepower.. Motor Speed(RPM): Famished: 'Yes Factory Charge: Fut Load Amps; Number 4 Circuit Sl 5.0b R acorn mended 16"x16"x2" Circuit B2 Locked RotorAmps: NOTES: 1. Maximum(HACR'Circuit Breaker sizing is for inetellatlons in the Voted States on y. 2. Reiterant charge as an approximate value.Fora more precise value,see unit nameplate and service instructions 3.Value does not Include Power Exhaust Accessory. 4, %tue does not include Heater. 0. Value include Standard Motor. 6.Value in dude Oversized Motor 7.0 ER is rated ste/I Pt conditions and in accordance vh DOE test prciCeduree. 6,For Com pressor Motors and Condenser Fan Motors:Amp draw for each motor,multiply value by number of motors to determine total amps. B. H P for each compressor. 10. Integrated Energy E ficlency Ratio(IEER)is rated in accordance with AH RI standard 210/240 or 360. 2017-07-19719:38:16 Page 3 o 10 Base Unit and Corner Weights only Buwr and weights: Comer Weights Center o t Gravity SN IPP INC NET O O O (I) E P 636.0 b 665.6 b 120.0 b 125.0 Ib 174.0 lb 168.0 lb 40" 29" 1.At weights are approximate. 2.The actual weight are bided on the and nameplate. �., 3.Refer to unit nameplate and installation guide br weightsbebre scheduling transportation and installation Diane. • 4.The weight shown represents the typical unit operating weight for the cont gumbo selected,Estimated at+1-16 %°Ptbe nameplate weight.. t"'�,��� 5.Verify weight,connection,and all dimension wth installer documents beforeinstallation. 6.Comer weights are given tor ntmmation only, 7.N et/Shipping weight of optional accessories should be added to unit weight when ordering bsdory or held installed accessories. d i_6Installed Options Net Weight Datary Weight Acce E conoamier,M anuat end Al otort,ed Outside Air Damper 260lb Barometric Petal 7.0 lb Power Exhaust R bot Curb 61.0 lb Oversized Motor PACKAGED COOLING PLAN VIEW Disconnect RIGGING DRAWING flail Guard Through the Base 1.Weights fpr options are approximate. 2.Weights Ra-options that are not list refer to Installation guide. A 0 D • • • Its o O PACKAGED COOLING PLAN VIEW CENTER OF GRAVITY DRAWING 2017-07-19719:38:16 Page 4 of 10 • NOTES: RACK OF UNIT 1.THRU-THE-RASE ELECTRICAL IS NOT STANDARD ON ALL UNITS. CLEARANCE.6D" ir\r ♦ l' / . HORIZONTAL RETURN \\:.kv,..,L_:=, ,,v,,,i [11> CLEARANCE,gff' \-\E _ J CLEARANCE 46" HORIZONTAL SUPPLY CLEARANCE 216' FRONT OF UNIT PACKAGED GAS/ELECTRIC PLAN VIEW CLEARANCE DRAWING i r \ „40 3315/16" di. \ 'r r PACKAGED GAS/ELECTRIC PLAN VIEW DOWNFLOW CLEARANCE.DRAWING 2017-07-19T19:38:16 Page 5 of 10 N OTE'5: 1.VERIFY WEIGHT,CONNECTION,AND ALL.DIMENSION WITH INSTAL.LER DOCUMENTS DE FORE:INSTALLATION IIPFLOW RETURN 7HROLIGHTHE:BASE'.CONDE NSATE Oilloo.#00/°. DOME LOW SUPPLY PACKAGED GAS ROOF CURB DIMENSION DRAWING 32 d�1C' -134" 1 34" 10' 14 7/18" a 24 U18" 21 1'10' 70 L'8" -7374:3-34"J --141i19"-4. .rte 1 24•' RAN VIEW OF UNIT DIMENSION DRAWING ! t 1 14" • L 10 718" J 70718' 42' FRONT VIEW OF UNIT RIGHT VIEW OF UNIT DIMENSION DRAWING DIMENSION DRAWING 2017-07-19T19:38:16 Page 6 of 10 NOTES, 1.VERIFY WEIGHT,CON NE.CTION,AND ALL DIMENSION WITH INSTALLER DOCUMENTS BEFORE INSTALLATION FAN GRILLE HORIZONTAL.RE.TURN W/DUCT OPE WING COVER I II HORIZONTAL.SUPPLY W/DUCT OPENING COVER - ika • .. - 00 pi- COIL BAROMETRIC RELIEF HOOD `Co BAROMETRIC RELIEF HOOD DIMENSION DRAWING HORIZONTAL.RETURN FAN GRILLE W/DLI CT OPENING COVER F ILTE R ACCESS BAROMETRIC RELIEF HOOD • BAROMETRIC LPI111 RELIEF I HOOD I COIL. t Off 0 IC -I - �-4 913" 713118- - HORIZONTAL SUPPLY - t3 7116" - W/DUCT OPENING COVER BACK VIEW OF UNIT RIGHT VIEW OF UNIT DIMENSION DRAWING DIMENSION DRAWING 2017-07-19T19;38:18 Page 7 of 10 • NOTES: 1.VERIFY WEIGHT.CONNECTION,AND ALL DIMENSION WITH INSTAL.LER DOCUMENTS BEFORE INSTALLATION FAN GRILLE COIL H OR!METAL.SUPPLY 4111111‘"�_. � W/DU CT OPENING COVER CONDE NSATE DRAIN CONNECTION - ' CONOMITER HGDD HORIZONTAL RETII RN W/DUCT OPENING COVER ECONOMIZER HOOD DIMENSION DRAWING ECONOMIZER HOOD HORIZONTAL.RETURN W/DUCT OPENING COVER FAN GRILLE FILTER ACCESS . �---- ---_--- HORIZONTAL SUPPLY W/DUCT OPENING COVER MOTORIZED HOOD I 11 1i1 • BACK VIEW OF UNIT RIGHT VIEW OF UNIT DIMENSION DRAWING DIME 11S10N DRAWING 2017-07-19719:38:16 Page 8 of 10 7 f 3 thru 5 Ton General The units shall be dedicated downflow or horizontal airflow. The operating range shall be between 125.0 F and 40.0 F in cooling as standard from the factory for all units. Cooling performance shall be rated in accordance with ARI testing procedures. All units shall be factory assembled, internally wired, fully charged with R-410A, and 100 percent run tested to check cooling operation, fan and blower rotation and control sequence, before leaving the factory. Wiring internal to the unit shall be colored and numbered for simplified identification. Units shall be UL listed and labeled, classified in accordance to UL 1995/C 22.2, 236-05 5rd Edition. 3 thru 5 Ton Casing Unit casing shall be constructed of zinc coated, heavy gauge, galvanized steel. Exterior surfaces shall be cleaned, phosphatized, and finished with a weather-resistant baked enamel finish. Unit's surface shall be tested 672 hours in a salt spray test in compliance with ASTM B117. Cabinet construction shall allow for all maintenance on one side of the unit. In order to ensure a water and air tight seal, service panels shall have lifting handles and no more than four screws to remove. All exposed vertical panels and top covers in the indoor air section shall be insulated with a 1/2", 1.0 lb density foil-faced, fire-resistant, permanent,dorless, glass fiber material. The base of the downflow unit shall be insulated with 1/2", 1.0 lb density foil-faced, closed-cell material. The downflow unk,s base pan shall have no penetrations within the perimeter of the curb other than the raised 1 1/8" high supply/return openings to provide an added water integrity precaution, if the condensate drain backs up. The base of the unit shall have provisions for forklift and crane lifting. 3 thru 5 Ton Compressors All units shall have direct-drive, hermetic, scroll type compressors with centrifugal type oil pumps. Motor shall be suction gas-cooled and shall have a voltage utilization range of plus or minus 10 percent of nameplate voltage. Internal overloads shall be provided with the scroll compressors. All models shall have hase monitors and low and high pressure control as standard. p 9 3 thru 5 Ton Controls Unit shall be completely factory wired with necessary controls and contactor pressure lugs or terminal block for power wiring. Unit shall provide an external location for mounting a fused disconnect device. 3 thru 5 Ton Discharge Line Thermostat A bi-metal element discharge line thermostat is installed as a standard option on the discharge line of each system. This standard option provides extra protection to the compressors against high discharge temperatures in case of loss of charge, extremely high ambient and other conditions which could drive the discharge temperature higher. Discharge line thermostat is wired in series with high pressure control. When the discharge temperature rises above the protection limit, the bi-metal disc in the thermostat switches to the off position, opening the 24 Vac circuit. When the temperature on the discharge line cools down, the bi-metal disc closes the contactor circuit, providing power to the compressor. 3 thru 5 Ton Evaporator and Condenser Coils Microchannel coils will be burst tested by the manufacturer. Microchannel condenser coils shall be standard on all units. Coils shall be leak tested to ensure the pressure integrity. The evaporator coil and condenser coil shall be leak tested to 225 psig and pressure tested to 450 psig. Sloped condensate drain pans are standard. 3 thru 5 Ton Gas Heating Section The heating section shall have a tubular heat exchanger design. An induced draft combustion blower shall be used to pull the combustion products through the firing tubes.The heater shall use a direct spark ignition (DSI) system. On initial call for heat, the combustion blower shall purge the heat exchanger for 20 seconds before ignition. After three unsuccessful ignition attempts, the entire heating system shall be locked out until manually reset at the thermostat. Units shall be suitable for use with natural gas or propane (field-installed kit) and also comply with the California requirement for low NOx emissions (Gas Heat Only). 3 thru 5 Ton High Pressure Control 2017-07-19719:38:16 Page 9 of 10 All units include High Pressure Cutout as standard. 3 thru 5 Ton Indoor Fan Units above shall have belt driven, FC centrifugal fans with adjustable motor sheaves. All motors shall be thermally protected. Oversized motors shall be available for high static application. All indoor fan motors meet the U.S. Energy Policy Act of 1992 (EPACT). 3 thru 5 Ton Low Pressure Control All units include low pressure cutout as standard. 3 thru 5 Ton Outdoor Fans The outdoor fan shall be direct-drive, statically and dynamically balanced, draw-through in the vertical discharge position. The fan motor(s) shall be permanently lubricated and shall have built in thermal overload protection. 3 thru 5 Ton Phase Monitor The Phase Monitor is a three-phase line monitor module that protects against phase loss, phase reversal and phase unbalance. It is intended to protect compressors from reverse rotation. It has an operating input voltage range of 190-600 Vac, and LED indicators for ON and FAULT. There are no field adjustments and the module will automatically reset from a fault condition. 3 thru 5 Ton Refrigerant Circuits Each refrigerant circuit shall have independent thermal expansion valve, service pressure ports, and refrigerant line filter driers factory installed as standard. An area shall be provided for replacement suction line driers. 3 thru 5 Ton Unit Top The top cover shall be double hemmed and gasket sealed to prevent water leakage. Field Installed 3 thru 5 Ton Barometric Relief Designed to be used on downflow units, barometric relief is an unpowered means of relieving excess building pressure. 2017-07-19T19 38-16 Page 10 of 10 ARI* capacities WM + UNIT NOMINAL STANDARD COOLING TOTAL SOUND RATING 48HJ TONS CFM (Btuh) kW SEERt EER (Bels) IPLV E/F004 3 1200 36,000 3.21 13.0 11.20 7.6 ** D/E/F005 4 1450 47,000 4.25 13.0 11.05 7.6 ** D/E/F006 5 1750 61,000 5.55 13.0 11.00 8.0 ** D/E/F007 6 2100 74,000 6.70 - 11.00 8.0 ** D/E/F008 7.5 3000 90,000 8.18 - 11.00 8.2 11.6 D/E/F009 8.5 3000 102,000 9.44 - 10.80 8.2 10.9 D/E/F012 10 3200 120,000 10.91 - 11.00 8.4 9.7 D014 12.5 4300 139,000 14.04 - 9.5 8.6 9.8 E014 12.5 4300 139,000 14.04 - 9.5 8.6 9.4 LEGEND Bels - Sound Levels(1 bel=10 decibels) EER - Energy Efficiency Ratio IPLV - Integrated Part-Load Value SEER - Seasonal Energy Efficiency Ratio *Air-Conditioning&Refrigeration Institute. tApplies only to units with capacity of 65,000 Btuh or less. **The IPLV is not applicable to single-compressor units. NOTES: 1. Rated in accordance with ARI Standard 210/240(004-012 units)or 360(014 units)and 270(004-014 units). 2. Ratings are net values,reflecting the effects of circulating fan heat.Ratings are based on: Cooling Standard:80 F db,67 wb indoor entering-air temperature and 95 F db outdoor entering-air temperature. IPLV Standard:80 F db,67 F wb indoor entering-air temperature and 80 F db outdoor entering-air temperature. 1A ,,,, igali , . .' . 9 , Sizes 004-012 Size 014 Only Only HEATING CAPACITIES AND EFFICIENCIES HEATING INPUT OUTPUT CAPACITY(Btuh) CALIFORNIA TEMPERATURE AFUE STEADY STATE UNIT (Btuh) Single-Phase Units* 3-Phase Unitst RISE(°F) (%) EFFICIENCY(%) SEASONAL First Stage/Second Stage First Stage/Second Stage First Stage/Second Stage EFFICIENCY(*h.) 48HJE004 50,000/ 72,000 40,000/ 57,100 41,000/ 59,040 _ 15-45 82 82 78.7 48HJF004 82,000/115,000 63,500/ 89,000 65,600/ 92,000 55-85 80 80 77.3 48HJ0005 50,000/ 72,000 40,000/ 57,100 41,000/ 59,040 15-45 82 82 78.7 48HJE005 82,000/115,000 65,600/ 92,000 66,420/ 93,150 35-65 81 81 77.7 48HJF005 120,000/150,000 94,400/118,000 96,000/120,000 50-80 80 80 76.9 48HJD006 50,000/ 72,000 40,000/ 57,100 41,000/ 59,040 15-45 82 82 78.7 48HJE006 82,000/115,000 65,600/ 92,000 66,420/ 93,150 35-65 81 81 77.8 48HJF006 120,000/150,000 94,400/118,000 96,000/120,000 50-80 80 80 76.9 48HJD007 50,000/ 72,000 - 41,000/ 59,040 15-45 82 82 78.7 48HJE007 82,000/115,000 - 66,420/ 93,150 35-65 81 81 77.8 48HJF007 120.000/150,000 - 96,000/120,000 50-80 80 80 76.9 HEATING INPUT OUTPUT CAPACITY TEMPERATURE AFUE STEADY STATE CALIFORNIA UNIT (Btuh) (Btuh) RISE(°F) (%) EFFICIENCY(%) SEASONAL First Stage/Second Stage First Stage/Second Stage EFFICIENCY(%) 48HJD008 90,000/125,000 72,900/102,500 20-50 82 82 77.5 48HJE008 120,000/180,000 98,400/147,600 35-65 82 82 77.5 48HJF008 180,000/224,000 147,600/183,700 45-75 82 82 79.4 48HJD009 90,000/125,000 72,900/102,500 20-50 82 82 78.4 • 48HJE009 120,000/180,000 98,400/147,600 35-65 82 82 78.4 48HJF009 180,000/224,000 147,600/183,700 45-75 82 82 79.4 48HJD012 120,000/180,000 98,400/147,600 35-65 82 82 78.4 48HJD014,HJE012 180,000/224,000 147,600/183,700 35-65 82 82 79.3 48HJE014,HJF012 200,000/250,000 160,000/200,000 40-70 80 80 76.4 LEGEND NOTE:NOx levels are 40 nanograms/ AFUE - Annual Fuel Utilization Efficiency joule with accessory kit. *Single-phase units are rated for output capacity in accordance with U.S.Government Standard Tests. C (2) US 1-Three-phase units are rated for output capacity in accordance with ANSI Z21.47 Standard for gas-fired,central furnaces. Physical data 4 Jr COI. BASE UNIT 48HJ EIF004 D/EIF005 D/E/F006 DIE/F007 NOMINAL CAPACITY 3 4 5 6 OPERATING WEIGHT(Ib) • Unit 530 540 560 615 Durablade Economizer 34 34 34 34 EconoMi$er 47 47 47 47 MoistureMiser Dehumidification Package 18 18 18 18 Roof Curb 115 115 115 115 COMPRESSOR Scroll Quantity 1 1 1 1 Oil(oz) 42 53 50 I 60 REFRIGERANT TYPE R-22 Operating Charge(lb-oz) Standard Unit 5- 8 8-6 10- 0 9-10 Unit With MoistureMiser Dehumidification Package 8-13 11-2 12-13 13- 6 CONDENSER FAN Propeller Quantity...Diameter(in.) 1...22 1...22 1..22 1...22 Nominal Cfm 3500 3500 4100 4100 Motor Hp...Rpm 1/4...825 1/4...825 1/4...1100 1/4...1100 Watts Input(Total) 180 180 320 320 CONDENSER COIL Enhanced Copper Tubes,Aluminum Lanced Fins Standard Unit Rows...Fins/in. 1..17 2...17 2...17 2...17 Total Face Area(sq ft) 14.6 16.5 16.5 16.5 Unit With MoistureMiser Dehumidification Package Rows...Fins/in. 1...17 1...17 1...17 1...17 Total Face Area(sq ft) 3.9 3.9 3.9 3.9 EVAPORATOR FAN Centrifugal Type,Belt Drive Quantity...Size(in.) 1...10 x 10 1...10 x 10 1...10 x 10 1...10 x 10 Nominal Cfm 1200 1600 2000 2400 Maximum Continuous Bhp Std 1.20 1.20 1.30/2.40" 2.40 Hi-Static 2.40 2.40 2.90 2.90 Motor Frame Size Std 48 48 48/56' 56 Hi-Static 56 56 56 56 Fan Rpm Range Std 760-1090 840-1185 1020-1460/1120-1585* 1120-1585 Hi-Static 1075-1455 1075-1455 1300-1685 1300-1685 Motor Bearing Type Ball Ball Ball Ball Maximum Fan Rpm 2100 2100 2100 2100 Motor Pulley Pitch Diameter A/B(in.) Std 1.9/2.9 1.9/2.9 2.4/3.4 2.4/3.4 Hi-Static 2.8/3.8 2.8/3.8 3.4/4.4 3.4/3.4 Nominal Motor Shaft Diameter(in.) Std 1/2 1/2 5/8 5/8 Hi-Static 5/8 5/8 5/8 5/8 Fan Pulley Pitch Diameter(in.) Std 4.5 4.0 4.0 4.0 Hi-Static 4.5 4.0 4.5 4.5 Belt-Quantity...Type...Length(in.) Std 1...A...33 1...A...33 1...A...40 1...A...38 Hi-Static 1...A...39 I...A...39 1...A...40 1...A...40 Pulley Center Line Distance(in.) 10.0-12.4 10.0-12.4 14.7-15.5 14.7-15.5 Speed Change Per Full Turn of Movable Pulley Flange(rpm) Std 65 70 75 95 Hi-Static 65 65 60 60 Movable Pulley Maximum Full Turns From Closed Position Std 5 5 6 5 Hi-Static 6 6 5 5 Factory Setting-Full Turns Open Std 3 3 3 3 Hi-Static 31/2 31/2 31/2 31/2 Factory Speed Setting(rpm) Std 890 980 1240 1304 Hi-Static 1233 1233 1396 1396 Fan Shaft Diameter at Pulley(in.) 5/8 5/8 5/8 5/8 LEGEND Bhp - Brake Horsepower "Single-Phase/3-Phase. f Indicates automatic reset. **48HJD005-007 and 48HJE004(72,000 Btuh heat input)units have 2 burners. 48HJE005-007 and 48HJF004(115,000 Btuh heat input)units and 48HJF005-007(150,000 Btuh heat input)units have 3 burners. ttAn LP Conversion Kit is available as an accessory. a II 1. 8 Carrier r BASE UNIT 48HJ EIF004 I D/E/F005 I D/E/F006 I D/E/F007 EVAPORATOR COIL Enhanced Copper Tubes,Aluminum Double Wavy Fins,AcutrolT'n Feed Device • Rows...Fins/in. 2...15 2...15 4...15 4...15 Total Face Area(sq ft) 5.5 5.5 5.5 5.5 FURNACE SECTION Rollout Switch Cutout Temp(F)t 195 195 195 195 Burner Orifice Diameter(in....drill size)** Natural Gas—Std .113...33 .113...33/.113...33/.129...30 .113...33/.113...33/.129...30 .113...33/.113...33/.129...30 Liquid Propane—Alttt .089...43 .089...43/.089...43/.102...38 .089...43/.089...43/.102...38 .089...43/.089...43/.102...38 Thermostat Heat Anticipator Setting(amps) 208/230/460 v First Stage .14 .14 .14 14 Second Stage .14 .14 .14 .14 Gas Input(Btuh) First Stage 50,000/ 82,000 50,000/ 82,000/120,000 50,000/ 82,000/120,000 50,000/ 82,000/120,000 Second Stage 72,000/115,000 72,000/115,000/150,000 72,000/115,000/150,000 72,000/115,000/150,000 Efficiency(Steady State)(%) 82/80 82/81/80 82/81/80 82/81/80 Temperature Rise Range 15-45/55-85 15-45/35-65/50-80 15-45/35-65/50-80 15-45/35-65/50-80 Manifold Pressure(in.wg) Natural Gas—Std 3.5 3.5 3.5 3.5 Liquid Propane—Alttt 3.5 3.5 3.5 3.5 Maximum Static Pressure(in.wg) 1.0 1.0 1.0 1.0 Field Gas Connection Size(in.) 1/2 1/2 1/2 1/2 HIGH-PRESSURE SWITCH(psig) Standard Compressor Internal Relief 450±50 Cutout 428 Reset(Auto.) 320 LOSS-OF-CHARGE/LOW-PRESSURE SWITCH (Liquid Line)(psig) Cutout 7±3 Reset(Auto.) 22±5 FREEZE-PROTECTION THERMOSTAT Opens(F) 30±5 Closes(F) 45±5 OUTDOOR-AIR INLET SCREENS Cleanable Quantity...Size(in.) 1...20 x 24 x 1 RETURN-AIR FILTERS Throwaway Quantity...Size(in.) 2...16 x 25 x 2 LEGEND Bhp — Brake Horsepower "Single-Phase/3-Phase. 1-Indicates automatic reset. **48HJD005-007 and 48HJE004(72,000 Btuh heat input)units have 2 burners. 48HJE005-007 and 48HJF004(115,000 Btuh heat input)units and 48HJF005-007 (150,000 Btuh heat input)units have 3 burners. ttAn LP Conversion Kit is available as an accessory. w 3 II I, 9