Report Q1, ) 7_ c or (271ce Sw I/rfvcrs OPT E COPY _ _ _ _ _ p.....` lib" r1_..m..M_t,i— ..,4nn u. 1.8 1 DELTA FIRE, INC 14795 SW 72ND AVE PORTLAND, OR, 97224 503-620-4020 Job Name : MADRONA-CALC Building : 2 Location : 7000 SW VARNS ST. TIGARD, OR 97223 System : 1 Contract : 17-5707 Data File : MADRONA-CALC Area 1.WXF Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 DELTA FIRE, INC Page 1 MADRONA-CALC Date HYDRAULIC CALCULATIONS for Project name: MADRONA RECOVERY CTR Location: 7000 SW VARNS ST. TIGARD, OR 97223 Drawing no: 2 Date: 7-5-17 Design Remote area number: 1 Remote area location: LEVEL 2 OFFICE Occupancy classification: LIGHT HAZ. Density: 0.1 -Gpm/SqFt Area of application: 936-SqFt Coverage per sprinkler: 122- SqFt Type of sprinklers calculated: RELIABLE F1FR56 1/2" 155 DEG BRASS SSU No. of sprinklers calculated: 10 In-rack demand: -GPM Hose streams: 100-GPM Total water required(including hose streams): 294.152-GPM @ 66.8851 - Psi Type of system: WET Volume of dry or preaction system: NA-Gal Water supply information Date: 3/27/17 Location: 7000 VARNS ST Source: WYATT FIRE Name of contractor: DELTA FIRE, INC Address: 14795 SW 72ND AVE/ /PORTLAND, OR, 97224 Phone number: 503-620-4020 Name of designer: D.ASCHBACHER Authority having jurisdiction: TIGARD Notes:(Include peaking information or gridded systems here.) USED ROOM DESIGN METHOD TO DETEMIN REMOTE AREA AO PROPe., 54330P: Vr 'S OREGON lttfoor Y13At � c.Sejv Expires: 7/1/18,;. Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Water Supply Curve C DELTA FIRE, INC MADRONA-CALC Page 2 Date City Water Supply: Cl -Static Pressure : 72 Demand: C2- Residual Pressure: 62 D1 - Elevation 6.063 C2-Residual Flow : 1133 D2-System Flow : 194.152 D2-System Pressure : 66.885 Hose( Demand) : 100 D3-System Demand : 294.152 Safety Margin : 4.290 150 140 130 p 120 R 110 E 100 S 90 S 80 Cl U 70 C2 R E 50 40 30 20 10 ,,....4... ......... . 200 400 600 800 1000 1200 1400 1600 1800 FLOW(NA1.85) Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Fittings Used Summary DELTA FIRE, INC MADRONA-CALC Page 3 Date Fitting Legend Abbrev. Name 1/2 ' 1 1'4 1% 2 2% 3 3'/ 4 5 6 8 10 12 14 16 18 20 24 Bvcb B Fly Vic 705W 0 0 0 0 0 0 5 5 0 12 12 8 11 12 14 0 0 0 0 0 E NFPA 13 90'Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow T NFPA 13 90'Flowthru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121 Zaf Ames 3000SS Fitting generates a Fixed Loss Based on Flow Unit Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with*. The fittings marked with a*show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a*will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Pressure / Flow Summary - STANDARD DELTA FIRE, INC Page 4 MADRONA-CALC Date Node Elevation K-Fact Pt Pn Flow Density Area Press No. Actual Actual Req. 1 14.0 5.6 7.0 na 14.82 0.1 122 7.0 2 14.0 5.6 7.75 na 15.59 0.1 122 7.0 3 14.0 8.62 na 4 14.0 8.87 na 5 14.0 10.16 na 6 14.0 23.59 na 7 14.0 32.1 na 8 14.0 38.99 na 9 14.0 39.06 na 13 14.0 47.73 na BOR -3.0 64.17 na HOSE -3.0 67.82 na 100.0 TEST 0.0 66.89 na 14 14.0 5.6 7.2 na 15.03 0.1 122 7.0 15 14.0 5.6 7.97 na 15.81 0.1 122 7.0 16 14.0 8.86 na 17 14.0 5.6 7.21 na 15.03 0.1 122 7.0 18 14.0 5.6 7.98 na 15.82 0.1 122 7.0 19 14.0 5.6 8.27 na 16.1 0.1 122 7.0 20 14.0 5.6 9.15 na 16.94 0.1 122 7.0 22 14.0 38.87 na 21 14.0 5.6 38.87 na 34.92 0.1 140 7.0 23 14.0 5.6 37.08 na 34.1 0.1 100 7.0 The maximum velocity is 26.84 and it occurs in the pipe between nodes 6 and 7 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 • Final Calculations - Hazen-Williams - 2007 DELTA FIRE, INC Page 5 MADRONA-CALC Date Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn 1 14.82 1.049 0.0 10.050 7.000 K Factor= 5.60 to 120.0 0.0 0.0 0.0 2 14.82 0.0747 0.0 10.050 0.751 Vel = 5.50 2 15.59 1.38 T 6.0 5.690 7.751 K Factor= 5.60 to 120.0 0.0 6.000 0.0 3 30.41 0.0743 0.0 11.690 0.868 Vel = 6.52 3 -15.08 1.38 0.0 12.000 8.619 to 120.0 0.0 0.0 0.0 4 15.33 0.0209 0.0 12.000 0.251 Vel = 3.29 4 30.85 1.38 0.0 8.000 8.870 to 120.0 0.0 0.0 0.0 5 46.18 0.1610 0.0 8.000 1.288 Vel = 9.91 5 33.04 1.38 T 6.0 24.750 10.158 to 120.0 0.0 6.000 0.0 6 79.22 0.4368 0.0 30.750 13.432 Vel = 16.99 6 45.92 1.38 E 3.0 5.360 23.590 to 120.0 0.0 3.000 0.0 7 125.14 1.0177 0.0 8.360 8.508 Vel = 26.84 7 0.0 1.61 T 8.0 6.340 32.098 to 120.0 0.0 8.000 0.0 8 125.14 0.4803 0.0 14.340 6.888 Vel = 19.72 8 34.91 2.635 0.0 1.030 38.986 to 120.0 0.0 0.0 0.0 9 160.05 0.0689 0.0 1.030 0.071 Vel = 9.42 9 34.10 2.635 T 16.474 47.080 39.057 to 120.0 3E 24.711 41.185 0.0 13 194.15 0.0983 0.0 88.265 8.675 Vel = 11.42 13 0.0 2.635 3E 24.711 30.280 47.732 to 120.0 Bvcb 6.864 31.575 10.363 * Fixed Loss =3 BOR 194.15 0.0983 Fsp 0.0 61.855 6.080 Vel= 11.42 BOR 0.0 4.1 3E 43.601 119.000 64.175 to 140.0 T 29.067 72.668 2.000 * Fixed Loss =2 HOSE 194.15 0.0086 Zaf 0.0 191.668 1.645 Vel = 4.72 HOSE 100.00 6.16 T 43.037 100.000 67.820 Qa= 100 to 140.0 0.0 43.037 -1.299 TEST 294.15 0.0025 0.0 143.037 0.364 Vel = 3.17 0.0 294.15 66.885 K Factor= 35.97 14 15.03 1.049 0.0 10.050 7.201 K Factor= 5.60 to 120.0 0.0 0.0 0.0 15 15.03 0.0766 0.0 10.050 0.770 Vel= 5.58 15 15.81 1.38 T 6.0 5.690 7.971 K Factor= 5.60 to 120.0 0.0 6.000 0.0 16 30.84 0.0763 0.0 11.690 0.892 Vel = 6.62 16 15.07 1.38 T 6.0 80.490 8.863 to 120.0 2E 6.0 12.000 0.0 6 45.91 0.1592 0.0 92.490 14.727 Vel = 9.85 0.0 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams DELTA FIRE, INC Page 6 MADRONA-CALC Date Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn 45.91 23.590 K Factor= 9.45 17 15.03 1.049 0.0 10.050 7.207 K Factor= 5.60 to 120.0 0.0 0.0 0.0 18 15.03 0.0767 0.0 10.050 0.771 Vel = 5.58 18 15.82 1.38 T 6.0 5.690 7.978 K Factor= 5.60 to 120.0 0.0 6.000 0.0 4 30.85 0.0763 0.0 11.690 0.892 Vel = 6.62 0.0 30.85 8.870 K Factor= 10.36 19 16.10 1.049 0.0 10.050 8.270 K Factor= 5.60 to 120.0 0.0 0.0 0.0 20 16.1 0.0871 0.0 10.050 0.875 Vel = 5.98 20 16.94 1.38 T 6.0 5.690 9.145 K Factor= 5.60 to 120.0 0.0 6.000 0.0 5 33.04 0.0867 0.0 11.690 1.013 Vel= 7.09 0.0 33.04 10.158 K Factor= 10.37 3 15.08 1.38 0.0 12.000 8.619 to 120.0 0.0 0.0 0.0 16 15.08 0.0203 0.0 12.000 0.244 Vel = 3.23 0.0 15.08 8.863 K Factor= 5.07 22 0.0 1.049 E 2.0 10.900 38.873 to 120.0 0.0 2.000 0.0 21 0.0 0.0 0.0 12.900 0.0 Vel = 0 21 34.92 2.635 T 16.474 10.890 38.873 K Factor=5.60 to 120.0 0.0 16.474 0.0 8 34.92 0.0041 0.0 27.364 0.113 Vel = 2.05 0.0 34.92 38.986 K Factor= 5.59 23 34.10 1.049 T 5.0 0.650 37.084 K Factor= 5.60 to 120.0 0.0 5.000 0.0 9 34.1 0.3492 0.0 5.650 1.973 Vel = 12.66 0.0 34.10 39.057 K Factor= 5.46 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 i t U EL 14795 POCBR#T64.N14. 6O21"R00vn0uOFFICE COPYj FIRE, INC. CSAW6D,7a5A72e2e MADRONA RECOVERY CENTER SOUTH TIGARD, OREGON DATA SUBMITTAL FOR FIRE PROTECTION SYSTEM APRIL 4, 2017 DELTA FIRE, INC. PROJECT # 17-5707 FIRE PROTECTION CONTRACTORS Madrona Recovery Center April 4,2017 Page 2 of 2 TABLE OF CONTENTS Pipe & Fittings Steel Pipe Ductile Iron Pipe Class 52 Ductile Iron Screwed Fittings Victaulic Firelock Fittings Fig. 01, 02, 03, & 06 Victaulic Firelock Rigid Coupling Fig. 009N Victaulic Coupling Fig. 75/04 Hangers Anvil Ring Hangers Fig. 69 Anvil Riser Clamp Fig. 261 Anvil Threaded Rod Sammy Vertical Anchor Fig. GST-20 Sammy Horizontal Anchor Fig. SWG-20 Tolco In-Line Sway Brace Fig. 4L Tolco Universal Swivel Sway Brace Fig. 980 Tolco Fast Clamp Sway Brace Attachment Fig. 1000 Tolco Sway Brace Attachment Fig. 1001 Sprinkler Heads Reliable F1 FR-56, W, 155 Degree, Chrome, Horizontal Sidewall Reliable F1 FR-56, 1/", 155 Degree, Chrome, Pendent Reliable F1 FR-56, '/", 155 Degree, Brass, Upright Switches & Bells Potter Electric 6" Bell Valves Victaulic Butterfly Valve Fig. 705 Victaulic Check Valve Fig. 717 Victaulic Riser Module Fig. 747M w/Pressure Relief Kit Watts Ball Valve %2"- 2" FIRE PROTECTION CONTRACTORS DEL S.W. 97224e PORT OR PORTLAND, OR Avenue PHONE 503-620-4020 FAX FIRE, INC. CCB#6416 4-1058 PIPE FITTINGS FIRE PROTECTION CONTRACTORS . Mk It MM. 111111111 MIN& INIIIMMAIL I I 111111116.- MOW 111 St MOM - = "Pipe gLILN I _ _"- � Pipe and Supply Corp. � Pipe Specification A135 Specification A135 NPS 1/4--30", Schedules 10, 40 and XL THD, Lightwall Scope Covers two grades of electric resistance welded steel pipe. Grade A is adapted for flanging and bending and is suitable for welding. Purpose for which pipe is intended should be stated on order. Kinds of Steel Permitted Open-hearth Basic-oxygen For Pipe Material Electric-furnace Permissible Variations The minimum wall thickness at any point shall not be more than 12.5%under the nominal wall thickness specified. in Wall Thickness Threadable,lightwall(XL)must meet manufacturers minimums. Chemical C max% Mn max% P max% S max% Requirements Seamless or ERW Grade A 0.25 0.95 0.05 0.06 Grade B 0.30 1.20 0.05 0.06 Tensile Grade A Grade B Requirements Tensile Strength,min.,psi 48,000 60,000 Yield Strength,min.,psi 30,000 35,000 NDE& Hydrostatic inspection test pressures for plain end and threaded are specified. Hydrostatic pressure shall be maintained Hydrostatic for not less than 5 seconds for all sizes of electric resistance weld pipe. Non-destructive electric test should be in accordance Testing with practices E213,method E227 or practice E213. Permissible Variations Plus or Minus 10%schedule 10 in Weights per Foot Plus 10%minus 3 1/2%schedule 40 Permissible Variations Plus or minus 1% in Outside Diameter Mechanical Tests Tensile Test--Transverse returned on pipe NPS 8 and larger. Specified Flattening test--Three steps required with weld located 0°or 90°from the line of direction of force required. Number of Flattening and tensile on one length of pipe from each lot of 400 lengths or less of a style. Tests Required Lengths Pipe shall be furnished in 38'with a minimum of 20 ft. Pipe furnished to schedule 10 shall be in a specified length between 16 and 22 ft. Required Markings Rolled,Stamped or Stenciled(Mfgrs.Option) on Each Length Name or brand of manufacturer. (On Tags attached to Kind of pipe,that is,electric-resistance welded A,electric welded B,same schedule wall thickness,schedule 10 or 40,NL each Bundle in case ASTM A135 of Bundled Pipe) Length of pipe. General End finish may be plain end beveled or plain end square cut. Information PACIFIC STATES PSCIPCO CAST IRON PIPE COMPANY DIVISION OF McWANE,INC. P.O. BOX 1219, PROVO, UTAH 84603 TELEPHONE(AREA CODE 801)373-6910 Mechanical Joint with Tyton® Joint Thickness, Dimensions and Weights of MJ/TJ Joint Ductile Iron Pipe by size for Each Thickness Wt. of Nominal Nominal Barrel Wt. of Wt. Per Nom.Wt. Laying** Thickness Thickness OD* Per Ft. f Bell Lgth.f Per Ft.$ Length Size Class In. In. Lb. Lb. Lb. Lb. Ft. 6 50 .25 6.90 16.00 29 315 17.71 6 51 .28 6.90 17.80 29 345 19.37 6 52 .31 6.90 19.60 29 380 21.30 6 53 .34 6.90 21.40 29 410 22.95 6 54 .37 6.90 23.20 29 445 24.88 6 55 .40 6.90 25.00 29 475 26.54 6 56 .43 6.90 26.70 29 505 28.19 18.125 8 50 .27 9.05 22.80 51 445 25.431 8 51 .30 9.05 25.20 51 490 27.64 8 52 .33 9.05 27.70 51 535 30.12 8 53 .36 9.05 30.10 51 575 32.61 8 54 .39 9.05 32.50 51 620 35.09 8 55 .42 9.05 34.80 51 660 37.30 8 56 .45 9.05 37.20 51 705 39.78 18.125 10 50 .29 11.10 30.10 66 590 33.60 10 51 .32 11.10 33.20 66 645 36.91 10 52 .35 11.10 36.20 66 695 39.94 10 53 .38 11.10 39.20 66 750 42.70 10 54 .41 11.10 42.10 66 805 45.74 10 55 .44 11.10 45.10 66 860 48.77 10 56 .47 11.10 48.00 66 910 51.53 18.125 12 50 .31 13.20 38.40 79 750 42.21 12 51 .34 13.20 42.00 79 815 45.79 12 52 .37 13.20 45.60 79 880 49.66 12 53 .40 13.20 49.20 79 945 53.24 12 54 .43 13.20 52.80 79 1010 56.55 12 55 .46 13.20 56.30 79 1070 59.86 12 56 .49 13.20 59.90 79 1135 63.45 18.125 14 50 .33 15.30 47.50 148 935 54.90 14 51 .36 15.30 51.70 148 1010 59.31 14 52 .39 15.30 55.90 148 1085 63.45 14 53 .42 15.30 60.10 148 1160 67.59 14 54 .45 15.30 64.20 148 1235 71.72 14 55 .48 15.30 68.40 148 1310 75.59 14 56 .51 15.30 72.50 148 1385 79.72 18.125 -1-Including bell;calculated weight of pipe rounded off to the nearest 51b. *Tolerances of OD of spigot end;3-12 in.±0.06 in., 14-24 in. $Including bell;average weight per foot,based on calculated weight of +0.05 in.,-0.08 in. pipe before rounding. **Average lengths only. Variances may occur as a result of foundry processes or installation. Pacific States Cast Iron Pipe Company Mechanical Joint With Tyton® Joint Thickness, Dimensions and Weights of MJ/TJ Joint Ductile Iron Pipe by size for Each Thickness Wt. of Nominal Nominal Barrel Wt. of Wt. Per Nom.Wt. Thickness Thickness OD* Per Ft. t Bell Lgth.t Per ft.* Laying** Size Class In. In. Lb. Lb. Lb. Lb. Length 16 50 .34 17.40 55.80 74 1100 60.69 18.125 16 51 .37 17.40 60.60 74 1185 65.38 18.125 16 52 .40 17.40 65.40 74 1270 70.07 18.125 16 53 .43 17.40 70.10 74 1355 74.76 18.125 16 54 .46 17.40 74.90 74 1445 79.72 18.125 16 55 .49 17.40 79.70 74 1530 84.41 18.125 16 56 .52 17.40 84.40 74 1615 89.10 18.125 18 50 .35 19.50 64.40 85 1270 70.07 18.125 18 51 .38 19.50 69.80 85 1365 75.31 18.125 18 52 .41 19.50 75.20 85 1465 80.83 18.125 18 53 .44 19.50 80.60 85 1560 86.07 18.125 18 54 .47 19.50 86.00 85 1660 91.59 18.125 18 55 .50 19.50 91.30 85 1755 96.83 18.125 18 56 .53 19.50 96.70 85 1850 102.07 18.125 20 50 .36 21.60 73.50 98 1445 79.72 18.125 20 51 .39 21.60 79.50 98 1555 85.79 18.125 20 52 .42 21.60 85.50 98 1665 91.86 18.125 20 53 .45 21.60 91.50 98 1770 97.66 18.125 20 54 .48 21.60 97.50 98 1880 103.72 18.125 20 55 .51 21.60 103.40 98 1985 109.52 18.125 20 56 .54 21.60 109.30 98 2090 115.31 18.125 24 50 .38 25.80 92.90 123 1830 100.97 18.125 24 51 .41 25.80 100.10 123 1960 108.14 18.125 24 52 .44 25.80 107.30 123 2090 115.31 18.125 24 53 .47 25.80 114.40 123 2215 122.21 18.125 24 54 .50 25.80 121.60 123 2345 129.38 18.125 24 55 .53 25.80 128.80 123 2475 136.55 18.125 24 56 .56 25.80 135.90 123 2605 143.72 18.125 1-Including bell;calculated weight of pipe rounded off to the nearest 51b *Tolerances of OD of spigot end;3-12 in.±0.06 in., 14-24 in. $Including bell;average weight per foot,based on calculated weight of +0.05 in.,-0.08 in.,30-36 in.+0.08 in.,-0.06 in. pipe before rounding. **Average lengths only. Variances may occur as a result of foundry processes or installation. . . -,.. 900 ELBOW FF.011 F.F....Y.FDPF.F.4 <CC:PF/FINV1L Ductile Iron MATERIAL SPECIFICATIONS q n I • Ductile iron threaded fittings ore UL&ULC Listed& . i l FM Approved for 500 psi service. ... - ,..1 Ductile iron per ASTM A536 Class 65-45.12. Dimensions conform to ASME 8163 Threads are NPT per ANSI/ASME B1.20.1. NOTICE Ductile iron fittings he higher tensile strength than that of sired pipe.Therefore,osier tightening con cause dorrioge to pipe Illf....which may cone leakage Ductile iron fittings should be tightened three turns beyond bond tight,but no more than four hens, C.®14 4C> ISM APPROVE Fr,:imth.orkpirovad 0040$mr4 Liftglzkyvx 90 ELBOW aise air WtgeleD if*NV(AtrlIfirt corn FX 414ftUt1 Oh 11/s,'Fain A. nun, Itomi 1 SU Mot Working Dimensions *wax, ne e Pressure. 1111111111111=1111 Wt,Ear lit Wel iPSF Xki I.Avg I.OW les Cte) ,"4--A—1 MI 500 1.50 1.50 0.62 s,'• il":-.!' IMIll 500 MEM! 090 T--- 4 im 500 1.94 1,94 1.20 .,..4i.A.,''' ,. ...., 1 :,..54 F IM SW 'Mil 215 1.05 A-Working Pressure beings are for inference only and based on Sobs.40 kw For*sr loess UtilitC, and FM prawns roting$vorwo live#41-Askilo,ploosovizii-01144.044V on CF7Frdrid riff local Anvil Roottoentatiye --„, 450 ELBOW . ( )...,,,.....„....... (t, EC-PF/FINVIL.-:> Ductile Iron MATERIAL SPECIFICATIONS , , .„'s,.... Ductile iron threaded fittings are LK&ULC Listed& FM Approved for 500 psi service, .41I. . Ductile iron per ASTM A536 Class 65-45-12. Dimensions conform to ASME 816.3 Threads are NPT per ANSI/ASME 81,20.1. NOTICE:Ductile iron fittings have higher ems&strength than that of steel pipe,Therefore,ewer lighterrng can cause damage ia pipe threads which may wine leakage.Ductile iron fitiiiNs shakdd be tightened three turns beyond hood 004,but 00 mare thanlour hprns, CeUS <> 11610 04100110VEIO Fo,Int,nri&upvul We.are Lem4etees 45' ELBOW est oar webs.*e verh,larrere cern or WIWI OM MOO"Saks Rnoineriono Alec Working Dimensions Approx. Nominal Size . rrassurea 111111= WI.Eads t's\ hi,*V IV Wei kl.*0 hi OM) iiik 4 Mill 500 11111111111111 0:46 1111= 500 1.29 129 0/3f'0, j,4:1:, ,.. i A '--1','.1 -..:.;;Y 500 143 1 43 0 92 i...... ,'4:Av-. =11 , Mill 500 L68 1.68 1.50 0 4.7:1: 4:e l f.`.i., A-Working Pressure Ratings ore for reference only ond based an 5,41.AO pipe.For Ere knee LIVULC, mid het pressure ratings versus pipe schedule,pious*visit onvEintteorr or coritoti your loco'Anvil RiVttionibliVe A STRAIGHT TEE N7iitti�a.�ag�y Ai, ''r ': Ductile Iron MATERIAL SPECIFICATIONS Ductile iron threaded fittings are Ut&ULC Listed& FM Approved for 500 psi service. Ductile iron per ASTM A536 Class 65-45,12. x ,; Dimensions conform to ASME 816,3 Threads are NPT per ANSI/ASME B1,20,1. NOTICE:Dat le batt fittings kwe higher seRslle strength than that of steel pipe,thereioeu,over tightening eon ame dotnuge to pipe&roots which may cause leakgge,Ducele iron fittings should be tightened three turns beyond Mond light,bur no room than tour rums __. _..... _.. _.. Me APPROV O STRAIGHT TEE rmIn,; . ,t . vitat far asw of Moe Working Dimensions Nominal Sire Approx. Pressure• �;' Wt.Each It OW PSI fkPa3 tn, in,Awn) 4 .,,.4:...„ ,. f 3 15D 1.541 0.85 B c. "� MS 7 � ' r77Al - INII 500 49:, Mill s... 500 2.25 MI 2_45 1—Workig Pra awre Roaigs are for ro *0y and based on WI,4O pipe.For tic loot UIJUIC, and FM pressure ratings versus pese schedule,please visit orrolirtl.ca-,or contact your local Anvil Itneentereative, . , --,„ BUSHINGS ,sirlimmvii: .}........Tt.M., (C-eme-RN Ductile Iron MATERIAL SPECIFICATIONS Ductile iron threaded fittings are UL&ULC Listed & FM Approved for 500 psi service. Ductile iron per ASTM A536 Class 65-45-12. --- Dimensions conform to ASME 816.14 Threads are NPT per ANSI/ASME B1.20.1.- NOTICE:Ductile iron fittings hove higher tens&strength than thcn of steel pipe,Therefore,4,Ver 60e:eying con toes*clornoge to pipe thireods whirls may cause leakage.Ductile Iron fittings should be tightened three turns beyond frond tigkt but no more thews 6r turns, e@eS ADP WEB APPROVER 11111111111111111111111111. F.,toaANT.Appvwg NuoN aocIL,Wobores. owl oo,wotroto a+toroonvOrti oom or oontaia at Most^S. Floproromobot Nornirkio Size Hex.Workin DIMORSICAIS ,.j ApproA, ft raw eA A 6 ( Are WI Fath Li.61,1,4 PSI NW Li.(mm) k f-it ki 04%) w ag) '"--C—1 4 1 x ih 500 I 0.75 0.25 1,42 I 'i i 0.22 Oj AB 1 x....4 500 0,75 0.25 1A2 t i'. ' 0,17 1 th x 1 500 0.60 0.28 1,76 Outside 018 Inside Head 1":1' 1 500 0.83 0.31 2.00 Otitskie 0.45 4' :, j•;',", .2::',c /?'''4 55.82 0 0,3 ti x PA 500 0.83 0.31 2.00 Outside 0.30 14 C I 2 x 1 500 0.88 0.41 1.95 Msidie 0.67 A ---_—_–_- 7 x l'A 500 0.88 0.34 2.48 Outside 0,73 Outside Head 2 x 1 h 500 0.88 0.34 2,48 Out 0,61 A-Working Pressure Winos are for reference only and hosed on WI 40 pipe For P .i. UVLILC, end FM pressure ratings versus p4se schedule.Otiose visit ormitirelcorn or contoct your local Anvil kepesentotive, CAP (C-115FIRNVIL: Ductile Iron MATERIAL SPECIFICATIONS Ductile iron threaded finings ore Ut&ULC Listed& FM Approved for 500 psi service. Ductile iron per ASTM A536 Class 65-45-12. Dimensions conform to ASME 816,14 Threads are NPT per ANSI/ASME 131,20,1. NOTICE:Deceits iron fittings hove higher Smelts strength than*sot of sted pipe.liserelore,over tightening con coos;kenos*ki pipe&roods which moy otiose leakage..Ductile iron httirvs should be tightened three turns beyond hood tight,but no more thonicurternst8T, itPPKYVte FP=4Afroi1/44",..4 Sk4+A lino.k.s CAP aunties an Moir Sian Rovnmentwni, Max..Working Dimensions Approx. Nominal Size Pressures 11111110111.1111 191.Each W OW PSI(kV ki.(en) 445-40 1 500 1.16 0.32 A 500 MIMI 060 500 1,45 0.91 It A-working Pressure Ratings ore for reference only and based on Srr 40 pipe For*is low UlAtik, and FM Pre041n0 ratings VOnitn CMV$ckedtilic,phtsso visit AivAlirtti.coni oscittsd your beat Anvil Represtlikihrit . . 1 COUPLING ( 1........„......: (C-ppieRNiv . Ductile Iron MATERIAL SPECIFICATIONS -tc--- - Ductile iron threaded fittings are UL&ULC Listed& FM Approved for 500 psi service, Ductile iron per ASTM A536 Class 65-45-12, Dimensions conform to ASME 816,14 Threads are NPI per ANSI/ASME B1.20,11_ NOTICE:Ductile iron fittings have higher Scissile strength*on that of steel pipe.Therefore,over tightening can cove stoning*to pipe dumb which may cause leakage Ductile iron fngs should be tightened three turns beyond bond 11914,but no more than four Ivrn$ Until MITIOVE0 its ItOrgr,Apprwit iietail art!Liniabov,s COUPLING wsr Dir%Vb.It weekamitAll axii COriti&I an Alwr saw Nominal Size Max.Working Dimensions Approx. Pressure. MEM Wi.Foch h.IOW PSI teof in OP) U.44) ...--,,C 11111111 500 ,JAI 111,7 .1241' 0.40 .... Mill 500 1,93 0,57 , .7=1 . ---,-- - --* ' EMI 501 ERE" 0,75 i n 501 2.53 1.1M1 A-Working Pressure Resings are for relinenee air and hosed on Sib 40 ptpe,For the latest 1.11/ULC., owl FM prAwme raiimin versus pipe scheduleobese visit anvilintow or Conine your local Anvil Steoresenthiive 1 . . CROSS , w (gil jir,i. (CC—PF/Fli Ductile Iron ,.._ MATERIAL SPECIFICATIONS •° -; t , _ ( 0,,., Ductile iron threaded fittings are UL&ULC Listed& zi FM Approved for 500 psi service. Ductile iron per ASTM A536 Class 65-45-12. Dimensions conform to ASME 816.3 Threads are NPT per ANSI/ASME B1,20,1. NOTICE:Ductile iron fittings have higher tensile strength than that of sleet pipe,Therefore,over tightening can*Poe damage la pipe thread$which may couse leakage.Ductile iron fittings should be tightened three turns beyond hand fight but no mare than hum ntrns, C®61 40* Mrs AN410vEtt Fto tostrwr Avowal OptaWs auld Lottaton, CROSS ..ourwettrowatt,*wwvwvamor 04.0 off,kV"540*ROPVIOTWV4 Nominal Sire last Waking Dimensions Approx, PiessureA i A 0 WI.Each In,OW NAPO In(mm) kikegn./ 165.119,1 1 500 130 1.50 0,98 500 1.75 1,75 1.50 I t 1 II e,...4.. 1 vri 500 1.94 1,94 1,90 A --,...,..t0z. + '.! .; ":,' 1 ',. r* 2 500 ' 2.25 2,25 2.95 'I.- --"' ------!,'.-t . ,' .S43t , ',,r'' .5.1.' i 34 I ., .:,•:, ',',..:. ', ..,„, -,- 1'.x 1 500 158 1.67 1.27 A 1 X 1 500 1.65 1.80 1A8 1 2x 1 500 133 2,02 2.10 A-Mlorldna Pressure Rn are for reference only and based on SA.46 pipe.For the loresr ULIULC, ond FM pressure ratings W0146 pope schedde,please visit novAimi.com or contact yow loco!Anvil Reprewtotive, . . REDUCING 900 ELBOW (C-PF/RNVL. Ductile Iron MATERIAL SPECIFICATIONS Ductile iron threaded fittings are Lk&ULC Listed& 7 i 'f FM Approved for 500 psi service. • Ductile iron per ASTM A536 Class 65-45-12. Dimensions conform to ASME 816.3 Threads are NPT per ANSI/ASME 81.20.1. — ,..._... NOTICE:Ductile iron fittings have higher teinlie strength than thot of stud :ipeTherefore,over tightening con cause damage to pipe threads which say'cleakage,Ductile iron finings should be tightened three tures beyond bond tight but no more than four turns, IT APPROVED r.t.o.04040,-,44 Coh..4 amd REDUCING 90' ELBOW s.w,Fiwout,nat,k Mux.Working Dimensions Approx. Nominal Size Pressure. A 8 Wt.Each b.OW ' PS/Obi Al(met) - ft(tivrit fte.NV 1 t'A 500 1.26 1.36 0.44 1 OA 500 .•':,,2c .?%;.'5?,.I :44 IC. 48 8? '..,;4 1%x!,",' 500 134 1,53 0..64 34'".1 34 i",:' V;% "f----06+4'"-"-•xV..' 1X'ix3/4 500 145 1.67 032 A 32 x.4 :..;44i •."?.f,5 4; ', ., ?.33 a__, TTrafi 1 4x 1 500 138 1.67 0.75 rri A 1 500 1.65 1.80 0.92 . ,,i.,:".; •°"°' 4101 45 2.? ,,, t.J.? 1V4W, 500 1.82 1.88 1.08 Cr 7,, 44:4' 46 0:" 47 ., 2 x Vi 500 1,49 - 1.88 1.08 7 x Vi 509 1,60 1.97 1,24 , „4S0 ..:::,,' 7 x 1 SOO 1.73 2.02 1,40 .704,:' 34'4' 4374 .5 f 4'4 0,44 2 x 1 IA 500 1.90 2.10 132 2 x 114 504,1 2.02 2.16 1.65 CC.4 f j,:Ni. : 47 ,'!,0r SIC A... 'Iv pressure&tine,are for,AcA,Ance 044 and based on Soh.40 pipe.For Co loses!U.li,..a. C., end FM pre' is retinas pipesettedvie„please visit otwilinicom Of contact rut.local Anvil Representative. REDUCING COUPLING 'F/RINIVL: Ductile Iron MATERIAL SPECIFICATIONS Ductile iron threaded fittings are UI&ULC Listed& FM Approved for 500 psi service. Ductile iron per ASTM A536 Class 65-4512. Dimensions conform to ASME 816.3 Threads are NPT per ANSI/ASME B1.20.1. NOTICE:Ductile eon fittings hove higher tensile strength than that of staid pipe.Theretore,over lightening con<ooze&usage to pipe diroarls*hitch may cause leakoge.Ductile iron finings should be tightened three turns beyond hood light,but no more than lour turns, Ce6 utto APPROVED thangs,kprowl 004A.h and Lroato, REDUCING COUPLING nen ow entente at*weeny/elf oren not enArent$414it F1441,40Muit,ww, Racine!Size Max.Working Approx, Fressurea WI,Each 42. (nivt) nt00 ODED tie 0. 1 x 1/2 500 149 39 A /5A 111MI 5a) 10 033 34.541 A-Wodsr Pressure Wings ere for reference only and based on Sch.41)pipe.Far the latest UL/ULC, and fM pressure rating:mintli pipe schedide,please visit aiwilinti core or contact your local Anvil Reptirsentotree 1 REDUCING TEE : . `�wrL 14:C-PmafFirti Ductile Iron MATERIAL SPECIFICATIONS : :1 � �- Ductile iron threaded fittings ore UL&1.11+ listed C r :1.9: FM Approved for 500 psi service. 4 t 0i, ---74"4" '''''-7r`'''''- Ductile iron per ASTM A536 Class 65-45-12. it Dimensions conform to ASME 816.3 A -13-• Threads ore NPT per ANSI/ASME 61.20.1. REDUCING TEE NOI KE:Ductile iron fittings hove higher Ignite strength than that d steel pipe.Therefore,o'er tiOterting con corse dr0009e to pipe erreods which Mex. Dimensions may caerse leakage.Ductile iron fittings should be tightened three turns Nominal Size PWo king tipprox, beyond frond light,but rto more thoo lour terra, B ( Tri.tach At( PS.!(kflxl A. At dmns) Ft(mm) tbs.(kg) c ec "*. DEER APPROVED 1 x i,x 1 500 i 130 1.36 130 . 0.64 r.,um.---.0.4.0,0o,..,Oe sa'S 8,4 1r ' t , ,r 56 2=F i`. •'4„' ?5 i(, d,9 v,>di o.r met+arx id.�rrwran CCM ca 1 x x+x 1 500 130 1,45 1.50 0,7 ` tia`n" $'"' ftt'K "`$"t 224;37,7472 r r 31:., l... =1%� � 5t10 126 1.22 6 1,36 411 REDUCING TEE 1 x 1 x 91 500 137 1.31 L45 0.76 line. Dimensions Approx. .77 5550 b,551 i'(. r j,; 51-. Hommel Sue Working Wt. 1 1 x 1 x 1 Y, 500 1.67 1.67 1:58 . 0.98_ Pressure. A 8 t ,rt lxixiV.I. 500 1.80 1.80 1.65 1.16 In.(nett) PSI W in.01w10 . it fmtr0 At(41101b1 607 ''' wX45"` ",l c 1' 4r..r CJA ,. . ll x1x 500 1.34 1.26 1.53 0.82 1f;x1�,x1 5 1.52 132 1.75 1.24 �,, �., lif;x I,ix 500 1. 5 1.65 1.80 1.30 , 1!,x 1 x 1ri 500 1.45 1,37 1,62 0,90 4 4 ,,55 34515 ,01 G - 1 V4 x 1 x 1 5001 1 38 130 X167 1.0{0 1 x 1 t 1,� 5001. 2' 1 1.48 1.82 ,« 1`° 500 1.75 1,67 1.75 1.08 iv;x h x 2 500 2.16 2.16 707 1.98 v.. >' r .d 6 �, .k k 1a ;. �� 2x1x2 54f 245 2. 725 215 1hxIe1' 500 t188 1,80 1.82 1,i2 ,�, . , ; .1.. 3.','_ '` 61 .2. IV,x Ili% , 500 134 1.89 1:53 0.86 ?x 1 x? 500 2.25 2.10 7 25 2,30 '' ,, ,54.5515 4 S_;'Gu a5 s"�,r fir" , 5 1,�x1'14s4#t 5500 1.45 1.45 1.62 0.92 x1! x',h 51t 1.49 1.41 188 1.50 rat_ ,::i :..7 ,5'..�* 'il 55 � 0.i'^' x 1 tr7 x Yi t�..._.. _.... ..__ "? '�_.._. 1 V.x 1%1.1 500 1.58 1.58 1,67 0.95 1.60 1 5 1 2 r= 55,553,5 4 ;:` 4 1 457 2 x 1',4 x 1 5001 1.73 1464 .65 2.02 1.64 1YrxlVtxlh 500 188 1.88 1.82 1.45 :,J4. .r,' 5� ., 3. ? .ri 500 1.90 1 i s rG_ 2x1'hx1V 82 2.10 1.80 11,1x114x2 SrOO 210 710 1.90 175 , ,, ,; .,, 5 5,5 51,'4 4k ;„ 2x 11 x 11", 500 2.02 1.94 2.16 2.00 1 git x l x I 500 1.41 1,34 ' 1.66 0,95 500 1.51i. ;; F 7 x l ri x 2 500 2 25 2,16 2,25 2,35 1'lsxlx1, ` ,. 1.37 1.15 1 14 0 1:x 1 x 1 500 1.65 1.50 1.80 1.17 y2%?x��` 500 1.b0 1"49 . . . 4 ABB: . 16 ` G t e7 4 19x 1 x 1,r 500 1.82 1.67 1.88 1.34 ,, 1 1.68 S 1/7:t 60 2 2 Ph h x l x 19 500 1.94 1.80 1.94 1.45 . 3 1.13 0 1 5 �4�� .,T„.2,,, . . , ;.� 7 n 4•�� ��< <. �� � . r. 44 6 10 2 x 2 x b t 500 1.90 1.70 2.10 2_04 LAx174Xir 500 1.41 1.34 1.66 1.05 30, .:3 ;0 44.45 41 ,' G44' C. .441` 1416 ver. t 11, xl It x 1a 500 1.52 1.45 1.75 1.15 2 x 2 x 1'4 500 2.0V2t 2.02 2.16 218 4i § 't 0,0 ''00 `a k? ..i i,: ", ;1m%r' G3 60 2.4. ti r,9 r €1 SnP4 1'1rx1l�x1 500 1.65 1,58 1.80 1.25 2x2x2r= 5 2jd} 2.602.39 3.61 1' xiirx2 500 2.16 7.02 1.90 252x216 500 114 1.60 7.37 228 ti ,;' i 7.16 2.10ter i : 60, ./�' ,34t?..... 22 ==f ,.r 1 x 1;s x',' S4iO 141 1 41 1.16 A-�Pre re Rot ngs k"'nAn " and bawd an 40 ,�the s 115 ''. ; .5474 '5:05; ;, ulaksi U ,and FM l Representative. rta ng.eerst a chrxlulr, visit n at linti can or .1.' ''-',,' contact your local I R eeenlati.e. • ...."45„FAREIP11,5,IWOPT ^' FireLock'-' Fiti i 6 C)<> 0) LPCB (VdS) v ! See Victaulic publication 10.01 for details FireLock®products comprise a unique system specifically designed for fire protection aitr services. FireLock full-flow elbows and tees are a CAD-developed, hydrodynamic design that has a shorter center-to-end dimension than standard fittings.A noticeable bulge allows the water to make a smoother turn to maintain similar flow characteristics as standard full flow fittings. FireLock fittings are designed for use exclusively with Style 005 and Style 009 FireLock couplings.Use of other couplings or flange adapters may result in bolt pad interference. Victaulic FireLock fittings pressure ratings conform to the ratings of Victaulic FireLock Style 005 couplings. a MATERIAL SPECIFICATIONS Fitting: Ductile iron conforming to ASTM A-536,grade 65-45-12. Fitting Coating:Orange enamel. • Optional: Hot dipped galvanized. JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date Approved Date www.victaulic.com VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. -Irt.`c�I:Iic REV_H 1(.7,03_1 I IPS CARBON STEEL PIPE-FIRE PROTECTION PRODUCTS 10.03 rc c ® Fittings DIMENSIONS R-CtoE+1 ,t C j _v j to o CtoE o 0 C tr- ,, ,, o0 0 �. o c la- to E o ��,�� jo to ___, NO.001 NO.003 NO.002 NO.006 No.001 No.003 No.002 No.006 Size 90 Elbow 45°Elbow Straight Tee Cap site ..outside Diameter '.-,Dto E ' '. ',Weight Each 'C to£ Weight Each ' C to E Weight Each Thickness.1' . ....Witight E1.,, :.,ii S. nib m! i? nth my . 11/4 1.660 0.8 0.3 _..... 32 42.4. _... _.. - 21 0.1 11/2 1.900 - _ 77 _.... 0.82 0.4_. ._.... 40 48.3. - 21 0.2 2 2.375 2.75 1.7 2.00 1.8 2.75 2.4 0.88 0.6 .__.. 50 ...60.3 _.._. 70 _.... 0.8 51 _.. 0.8 70 1.1 22 0.3 2Y2 2.875 3.00 3.1 2.25 2.2 3.00 3.6 0.88 1.0...... 65 .73.0 76 1.4 57._. 1.0 76 1.6 22 0.5 ,._ 3.000 3.00 3.30 2.25 2.4 76.1 mm _..... ........ __. ... 76.1 76 1.5 57 1.1 3 3.500 3.38 4.0 2.50 3.1 3.38 5.3 0.88 1.2 80 88.9 ..........86 1.8 64 1.4 86 2.4 22 0.5 108 mm 4.250 4.00 5.7 3.00 5.1 4.00 7.5 ...108.0 ......102 2.6 76 2.3 102 3.4 4 4.500 4.00 6.7 3.00 5.6 4.00 8.7 1.00 2.4 100 .114.3 102 3.0 76 2.5 102 3.9 25 1.1 5 5.563 4.88 ', 12.6 3.25 8.3 4.88 15.7 1.00 4.1 125 141.3 124... 5.7 83 3.8 124 7.1 25 1.9 159 mm 6.250 5.50 12.6 3.50 9.2 5.50 17.9 -.. 158.8 140 5.7 89 4.2 140 8.0 i 6 6.625 5.50 183 3.50 11.7 5.50 22.7 1.00 5.9 150 168.3 140 8.3.... 89 5.3 140 10.3 25 2.7 8 8.625 6.81 25.5 4.25 20.4 6.94 38.7 113 12.7 200 219.1 173 11.6 108 9.3 176 17.6 29 5.8 www.victaulic.com VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. \J'C{'aUlIC` 10.03_2 REILH IPS CARSON STEEL PIPE--EIRE PROTECTION PRODUCTS 10.03 FreL •ck..® Fittirigs FLOW DATA Frictional Resistance Size Equivalent Feet/meters of Straight Pipe t 0 2 , .Y t� � m is , j ,�°, ii/OW,.. nit -., n, 1 Va 1.660 1.5 • 0.8 3.7 1.5 32 42.4 0.5 0.2 1.1 0.5 11/2 1.900 2.2 1.1 5.5 _.. 2.2 _. 40 48.3 0.7 0.3 1.7 0.7 2 2.375 3.5 1.8 8.5 3.5 50 60.3 1.1 0.5 2.6 1.1 21/2 ...2.875 4.3 2.2 ...... 10.8 _.... 4.3 _. 65. 73.0 1.3 0.7 3.3 1.3 76.1 mm 3.000 4.5 2.3 11.0 4.5 76.1 _... 1.4 0.7 3.4 1.4 3 3.500 5.0 2.6 13.0 50 80. 88.9 1.5 0.8 4.0 1..5 1"mm 4.250 6.4 3.2 15.3 6.4 _... . 108.0 2.0 0.9 4.7 2.0 4 4.500 6.8 3.4 16.0 6.8 100 .......114.3. 2.1 10 4.9 2.1 55.563 8.5 _... 4.2_... 21.0 8.5 125... ... _.... 141.3 2.6 1.3 6.4 2.6 159mm 6.250 9.4 4.9.... 25.0. 9.6 _. _._. 158.8 2.9 1.5 7.6 2.9 6 6.625 10.0 5.0 25.0 10.0 150 168.3 3.0 1.5 7.6 3.0 8 8.625 .......13.0 5.0 __. 33.0 ...13.0 200 219.1 4.0 LS 10.1 4.0 L The flow data listed is based upon the pressure drop of Schedule 40 pipe. www.victautic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. �Ct'aulIC° REV_H 1.0.03 3 , QN 'JP F FireLock® Fittings GENERAL NOTES NOTE:When assembling FireLock EZ couplings onto end caps,take additional care to make certain the end cap is fully seated against the gasket end stop. For FireLock EZ Style 009 and Style 009V couplings, use FireLock No.006 end caps containing the"EZ"marking on the inside face or No.60 end caps containing the"QV EZ" marking on the inside face. Non-Victaulic end cap products shall not be used with Style 009/009V couplings. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. III I I III III 1111111111111 111111111 III WCAS-7MX2JY For complete contact information,visit www.victaulic.com 10.03 1539 REV H UPDATED 1/2009 1CtaaUI.0 VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. e 10.03 Victaulic® FirelockTM Rigid Coupling ✓ctaulic° Style 009N 10.64 ^J , P. Patented 1.0 CERTIFICATION/LISTINGS °a• FM (LPCBJ Vds C104-1a/36 2.0 PRODUCT DESCRIPTION • The FireLock EZTM Style 009N Installation-ReadyTM Rigid Coupling is for use in the fire protection market. • The coupling's unique design eliminates loose parts, promotes consistent installation and provides substantial gains in productivity. • IMPORTANT: FireLock EZTM Style 009N couplings are recommended for use ONLY on fire protection systems. 3.0 MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A 536, Grade 65-45-12. Ductile iron conforming to ASTM A 395, Grade 65-45-15, is available upon special request. Housing Coating: (specify choice) ® Orange enamel (North America, Asia Pacific) ❑ Red enamel (Europe) ❑ Hot dipped galvanized Gasket: (specify choicer) [� Grade "E" EPDM (Type A) FireLock EZ products have been Listed by Underwriters Laboratories Inc., Underwriters Laboratories of Canada Limited, and Approved by Factory Mutual Research for wet and dry (oil free air) sprinkler services within the rated working pressure. 1 Services listed are General Service Guidelines only.It should be noted that there are services for which these gaskets are not compatible.Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service guidelines and for a listing of services which are not compatible. Bolts/Nuts: Zinc electroplated carbon steel, trackhead meeting the physical and chemical requirements of ASTM A 449 and physical requirements of ASTM A 183. System No. Location Spec Section Paragraph Submitted By Date Approved 1 Date I _ • victaulic.com I Couplings I FireLock I Rigid I Style 009N I Publication 10.64 10.64 7072 Rev G Updated 10/2014 ©2014 Victaulic Company.All rights reserved. 1 •ctaulic° victaulic.com I Couplings I FireLock I Rigid I Style 009N I Publication 10.64 • • 4.0 LISTINGS/APPROVAL 2 The information provided below is based on the latest listing and approval data at the time of publication. Listings/Approvals are subject to change and/or additions by the approvals agencies. Contact Victaulic for performance on other pipe and the latest listings and approvals. Nominal Size cULus FM i Vds LPCB Ji — Sch.5 1 Sch. 10 1 Sch.40 Sch.5 Sch. 10 Sch.40 1 inches psi 1 psi psi psi psi psi psi psi mm kPa kPa 1 kPa kPa kPa I kPa kPa kPa 1Y 232 365 365 j 175 363 363 363 363 32 1600 2517 1 2517 1205 2502 _2502 2500 2500 r- 1Y 232 365 365 175 363 363 363 363 40 1600 2517 2517 1205 2502 2502 2500 2500 2 363 365 365 175 363 363 363 363 50 2502 2517 2517 I 1205 2502 2502 2500 2500 2'/z 365 365 175 363 363 363 363 65 N/A 2517 2517 1205 2502 { 2502 2500 2500 365 3 76.1 mm N/A N/A N/A 3634 363 363 25173 25024 N/A 2500 2500 3 1 365 365 175 363 363 363 363 80 N/A 2517 2517 1205 1 2502 2502 2500 2500 175 - — 108.0 mm N/A N/A N/A T 365 365 175 363 363 363 363 100 N/A 2502 2500 2517 2517 1205 2502 i i � 2500 363 363 1205 2502 2502 N/A N/A 5 1, N/A 1 290 365 N/A 363 363 232 125 2000 2517 2502 2502 1600 N/A 133.0 mm N/A N/A 4 N/A t N/A + 25024 N/A N/A N/A 290 139.7 mm 1 N/A 00055 N/A N/A 363 2502 a N/A 232 1600 N/A { 159.0 mm N/A N/A N/A N/A 4 363 N/A N/A N/A 2502 4 290 6 N/A I 363 4 165.1 mm N/A 20006 N/A 25024 N/A N/A N/A 16 150 N/A I 290 365 N/A 363 363 232 – 2000 2517 2502 2502 I 1600 N/A 216.0mm N/A N/A N/A N/A 4 363 N/A N/A N/A i ___ 2502 8 290 365 T363 1 363 232 200 1 N/A 2000 2517 1 N/A 2502 1 ....? P? . 1600 N/A 2 Listed/Approved for wet and dry pipe systems(>–40°F/-40°C)for continuous use in freezing conditions,use of Style 005H Coupling with Silicone Gasket is recommended. Please see the Victaulic Installation Manual I-009N/009H for details concerning when supplemental lubrication is required. 3 cULus listed for DIN 2458 2.6 mm pipe wall. 4 FM approved for BS 1387 Medium 3.6 mm pipe wall. 5 cULus listed for EN 10220 4.0 mm pipe wall. 6 cULus listed for EN 10255 4.5 mm pipe wall. • 10.64 7072 Rev G Updated 10/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 2 ✓Ctaulic° 1 victaulic.com I Couplings I FireLock I Rigid I Style 009N I Publication 10.64 • • 4.1 LISTINGS/APPROVAL Speciality Pipe Pipe I Size Pressure Rating i Pipe I Size _ Pressure Rating i Pipe Size Pressure_Rating cULus FM ( cULus FM cULus 7 FM inches psi psi inches psi psi inches psi psi ( kPa kPa j kPa kPa 1 kPa kPa 300 BLT 1 1/a—2 2068 56 5 7 EZT ' 1 1/4—2 2068 2517 MT 1 Ya—2 300 365 I300 365 ----+ 2068 2517 - 2517 DF 11/4—4 300 365 FF 1/a-4 300 365 MLT 1/a-2 N/A 365 2068 2517 2068 2517 i I DT 11/a-2 206802517FLF 1Ya-4 5 i I N/A 365 t ST 11/7a-2 N/A 2517 EF I 1 1/a-4 175 175 FLT 11/4—2 N/A 365 STF 1 Ya-4 N/A 365 1206 1206 2517 , 2517 300 365 EL 11/4 2 2068 2517 FLTL 11/4-2 1 N/A 365 1 TF 21/4-4 N/A 365 _.... 2517 2517 300 365 , 300 365 300 365 ET40 1 1/a 2 1 2068 2517 GL 11/4—2 II 2068 2517 i WLS 11/4—2 2068 2517 EZF , 3—4 300 365 MF 1 1/4—4 300 365 WST 1 1/4—2 N/A 365 2068 L 2517 2068 2517 2517 XL 11/4—2 300 365 2068 2517 NOTES • BLT-BLT steel pipe manufactured by Allied Tube&Conduit Corp. • DF=DYNA-FLOW steel pipe manufactured by Allied Tube&Conduit Corp. • DT=DYNA-FLOW steel pipe manufactured by Allied Tube&Conduit Corp. • EF=EDDY FLOW steel pipe manufactured by Bull Moose Tube Co. • EL=EDDYLITE steel pipe manufactured by Bull Moose Tube Co. • ET40=Eddythread 40 steel pipe manufactured by Bull Moose Tube Co. • EZF=EZ-Flow steel pipe manufactured by Northwest Pipe Co. • EZT=EZ-Thread steel pipe manufactured by Youngstown Tube Co. • FF=Fire-Flo steel pipe manufactured by Youngstown Tube Co. • FLF=Fire-Line Flow steel pipe manufactured by Western International Forest Products Inc. • FLT=Fire-Line Threadable steel pipe manufactured by Western International Forest Products Inc. • FLTL=Fire-Line Threadable Light steel pipe manufactured by Western International Forest Products Inc. • GL=GL steel pipe manufactured by Wheatland Tube Co. • MF=Mega-Flow steel pipe manufactured by Wheatland Tube Co. • MT=Mega-Thread steel pipe manufactured by Wheatland Tube Co. • MLT=MLT steel pipe manufactured by Wheatland Tube Co • ST=STD wall pipe in accordance with ASTM A53. • STF=Steady Flow steel pipe manufactured by AMS Tube Corp. • TF=Tex-Flow steel pipe manufactured by Tex-Tube Co. • WLS=WLS steel pipe manufactured by Wheatland Tube Co. • WST=WST steel pipe manufactured by Wheatland Tube Company. • XL=XL steel pipe manufactured by Allied Tube&Conduit Corp. 10.64 7072 Rev G Updated 10/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 3 ✓ctaulic` victaulic.com I Couplings I FireLock I Rigid I Style 009N I Publication 10.64 5.0 DIMENSIONS Style 009N Y Z Y :1�\ pi ILII1. N.t ZZ oil ,� IMI ‘�" VII Style 009N Pre-Assembled Style 009N Joint Assembled (Push On Condition) Dimensions Actual w Maximum Maximum ! Allow. Pre-assembled Nominal Outside Working End Pipe End Bolt/Nut e I (Push On Condition) Joint Assembled APPght 1 Weight 1 Size Diameter ','Pressure 7 Load 7 1Separation81' Size 1 X ! Y X Y Z ! Each inches inchespsi 1 j lbs. inches ! � inches I inches inches i inches j inches 1 inches lbs. mm mm kPa N mm No. mm I__ mm mm 1 _mm mm mm kg 1 1/4 1.660 365 790 0.10 3/e x 2 3.13 5.00 l 2.75 5.00 2.00 ! 1.4 32 42.4 2517 3514 2.54 2 M10 x 2 79 127 70 127 11h ! 1.900 365 -+---- I------ - , ---- 1 51 0.6 j 1035 0.10 • 3/b x 2 3.38 5.13 3.00 5.13 r 2.00 1.5 1 402 i 48 .3 2517 4604 254 2 M10 x2 86 130 76 130 51 0.7 2.375 365 1616 0.121 3/s x211 j 4.00 5.63 3.50 5.63 ! 2.00 1.9 1-1j 50 I 60.3 2517 7193 3.05 2 M10 x21/2 1 102 143 89 143 51 0.9 21/2 2.875 � 365 2370 I 0.12 ' 3/8 x 21/2 i 4.50 6.13 4.00 C 6.13 2.00 2.1 65 73.0 2517 I 10542 3.05 2 M 10 x 21/2( 114 _ 156 102 156 � 51 1.0 76.1 mm 3.000 365 2580 0.12 3/9 x 21/2 4.63 6.00 4.13 6.13 2.00 2.1 t 76.1 2517 11476 3.05 2 M10 x21/21 118 152 +- 105 j 156 ! 51 1.0 3 3.500 365 3512 0.12 3/e x 21/2 5.13 6.75 4.63 6.75 2.00 2.3 80 88.9 2517 15622 3.05 2 M10 x21/2, 130 171 I 117 171 j 51 1.0 4 4.500 365 5805 I 0.171 x 21/2 6.00 7.88 5.63 750 2.13 2.9 100 114.3 2517 25822 i 4.32 2_M_3/8 10 x 21/2 152 200 143 191 54 I 1.3 108.0 mm 4.250 1 365 5175 0.17 ' 3/a x 21/2 1 5.63 738 538 738 2.13 3.1 _108.0 2517 23020 I 4.32 2 M 10 x21/2,I 152 _1.87 137 1 187 j 54 1.4 I® 5.563 365 1 8870 0.172 1/2 x 3 1 7.25 9.25 6.75 I 9.13 1 2.25 5.0 141.3 2000 39456 4.32 M12 x 3 184 1 235 i 171 j 232 57 2.3 133.0 mm 5.250 1 365 7897 017 ' 2 1 1/z x 3 1 6.63 9.00 6.38 0 2.25 T 4.8 133.0 2517 1 35106 ! 4.32 1 M12 x 3L-168 229 162 229 j 57 2.2 139 7 mm 5.500 1 365 8667 0.17 J 2 1/2x 3 6.88 9.25 6.75 9.13 ! 2.25 4.9 139.7 j 2517 38529 4.32 1 M12 x 3 1 175 235 171 232 57 j 2.2 159.0 mm 6.250 365 11192 1 0.17 1 1/z x 3 1/4 1 7.88 10.00 , 7.38 9.88 1 2.25 5.6 159.0 2517 49753 4.32 2 1 M12 x31/41 200 254 187 I 251 ! 57 2.5 165.1 mm 6.500 j 365 12105 1 0.17 1 2 1 1h x 3 1/4 I 8.00 10.25 j 7.75 ! 10.13 2.25 6.0 I I 165.1 2517 I 53813 4.32 'M12 x 3,1/41 203 260 A. 197 _ 257 57 2.7 1 6 , 6.625 365 12582 0.17 i1h x 31/4 ,1 8.38 10.38 • 7.88 F 10.13 ! 2.25 6.0 150 168.3_ 2000 44469 4.32 l. M12 x 31/4 213 264 200 257 i 57 2.7 2 ! 1 216.0 mm 8.500 365 20712 0.17 2 5/s x 4 ( 10.63 13.25 10.25 10.13 2.63 11.4 216.0 1 2517 55968 4.32 1 1 M16 x4 1 270 337 260 257 67 � 5.2 1___...-._' I -- 8 8.625 365 21326 0.17 2 j 5/e x 4 10.88 13.38 10.25 13.13 2.50 11.4 L 7 2WorkingnPee sssureVa td Ecd6 specifications.8from all internal Aand external loads,based publicationn tadard weight(oNSI)stlstandard r 64 5.2 0 I .9486 M16x4 nd are h pipe, roll or cut grooved in accordaP Listings/Approvals section of t ratingspipe. 8 The allowable pipe separation dimension shown is for system layout purposes only.FireLock EZTM couplings are considered rigid connections and will not accommodate expansion or contraction of the piping system. 9 Number of bolts required equals number of housing segments. NOTES • When assembling FireLock EZTM couplings onto end caps,take additional care to make certain the end cap is fully seated against the gasket end stop.For FireLock EZTM Style 009N couplings,use FireLock No.006 end caps containing the"EZ"marking on the inside face or No.60 end caps containing the"QV EZ"marking on the inside face.Non-Victaulic end cap products shall not be used with Style 009N couplings.IMPORTANT:Gaskets intended for the Style 009 or Style 009V couplings cannot be used with the Style 009N coupling.There is no interchanging of gaskets or housings between coupling styles. • Use Of Flushseal Gaskets For Dry Pipe Systems FireLock EZTM couplings are supplied with FireLock EZTM Grade"E"Type A gaskets.These gaskets include an integral pipe stop,that once installed provides the similar benefits as a FlushSeal gasket for dry pipe systems.It should be noted that standard Victaulic Flush-SealTM gaskets are not compatible and cannot be used with the FireLock EZTM couplings. 10.64 7072 Rev G Updated 10/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 4 ✓ctaulic° victaulic.com I Couplings I FireLock I Rigid I Style 009N I Publication 10.64 • • 6.0 REFERENCE MATERIALS Publication 05.01:Seal Selection Guide 1-009N/009H.Installation Instructions FireLock EZ° Rigid Coupling • • User Responsibility for Product Selection and Suitability Note Each user bears final responsibility for making a determination as to the suitability of This product shall be manufactured by Victaulic or to Victaulic specifications.All products Victaulic products for a particular end-use application,in accordance with industry to be installed in accordance with current Victaulic installation/assembly instructions. standards and project specifications,as well as Victaulic performance,maintenance, Victaulic reserves the right to change product specifications,designs and standard safety,and warning instructions.Nothing in this or any other document,nor any verbal equipment without notice and without incurring obligations. recommendation,advice,or opinion from any Victaulic employee,shall be deemed to Installation alter,vary,supersede,or waive any provision of Victaulic Company's standard conditions Reference should always be made to the -009N/I-0091-I Rrelock[7 Rig d Coupling of sale,installation guide,or this disclaimer. Installation Instructions for the product you are installing.Handbooks are included with Intellectual Property Rights each shipment of Victaulic products,providing complete installation and assembly data, No statement contained herein concerning a possible or suggested use of any material, and are available in PDF format on our website at www.victaulic.com. product,service,or design is intended,or should be constructed,to grant any license Warranty under any patent or other intellectual property right of Victaulic or any of its subsidiaries Refer to the Warranty section of the current Price List or contact Victaulic for details. or affiliates covering such use or design,or as a recommendation for the use of such material,product,service,or design in the infringement of any patent or other intellectual Trademarks property right.The terms"Patented"or"Patent Pending"refer to design or utility patents Victaulic,FireLock EZTC,Flush-Seal.",and Installation-Ready00 are trademarks or or patent applications for articles and/or methods of use in the United States and/or other registered trademarks of Victaulic Company,and/or its affiliated entities,in the U.S.and/ countries. or other countries. • 10.64 7072 Rev G Updated 10/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 5 ✓ctaulic° !nmwFr .,. .4M�.., r ,.:: wsus ' "'��,.�,S�d " nE �..u.0. .. ,4 .. ....-. :. Coupling SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS STYLE 75 Style 75 is available where moderate pressures are expected or weight • considerations are a factor. Up to 50% lighter in weight than the Style 77, the Style 75 coupling is recommended for service up to 500 psi/3450kPa depending on size. Housings are cast in two identical pieces in all sizes. Hot-dip galvanized and special coatings are available for all sizes. Kof 111 Exaggerated tar clarity MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A-536,grade 65-45-12. Ductile iron conforming to ASTM A-395,grade 65-45-15, is available upon special request. Housing Coating: Orange enamel. • Optional: Hot dipped galvanized and others. Gasket: (specify choice*) • Grade"E" EPDM EPDM (Green color code).Temperature range—30°F to+230°F/-34°C to+110°C. Recommended for hot water service within the specified temperature range plus a variety of dilute acids,oil-free air and many chemical services. UL classified in accordance with ANSI/NSF 61 for cold+86°F/+30°C and hot+180°F/+82°C potable water service. NOT RECOMMENDED FOR PETROLEUM SERVICES. • Grade "T"nitrile Nitrile(Orange color code).Temperature range—20°F to+180°F/-29°C to+82°C. Recommended for petroleum products,air with oil vapors,vegetable and mineral oils within the specified temperature range;except hot,dry air over+140°F/+60°C and water over +150°F/+66°C. NOT RECOMMENDED FOR HOT WATER SERVICES. * Services listed are General Service Recommendations only. It should be noted that there are services for which these gaskets are not recommended. Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service recommendations and for a listing of services which are not recommended. Bolts/Nuts: Heat-treated plated carbon steel,trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date Approved Date www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. �Ctau�lC® REV H 06.06 1 CARBON STEEL PIPE-GROOVED COUPLINGS 06.05 Coupiirig STYLE 75 • DIMENSIONS Max.Work Allow.Pipe Bolt/Nut@ Approx. Size Pressure Max.End Load* End Sep.f Deflect.Fr.CO' r No-Size Dimensions Inches/mm Wgt.Each eknninal Otitsr g ..; Site Diametet •-• Heli inches psi: s ..° t . a : • -egCPla �+1 1 1.315 500 680 0-0.062" 0.57 2.38 4.27 1.77 1.3.6 25 33.4 3450 3025 0 1.6 -43' 48 2-%x 2 0 61 108 45 13/4 1.660 500 1080 0-0.06 0.45 26.688 4 61 1.77 1.4 32 42.2 3450 4805 0 1.6 2 - 0 38 2-3/s x 2 117 45 0.6 1'/ 1.900 5001.420 0-0.061 -56' 0.40 2-/s x 2 27491 122 45 0.6 4.82 1.5 40 48.3 3450 6320 0-1.6 33 2 2 375 500 2.215 0 0.061 0.32 3.43 5.22 1.88 1.7 50 60.3 3450 9860 0-1.6 -31' 26 2-8/8 x 2 87 133 48 0.3 2 Yz 2.875 500 3 245 0-0.06 0.26 3.88 3.68 88 1.9 65 73.0 3450 14440 0-1.6 1°-15' 22 2-3/a 98 144 48 x 2 0 9 76.1 mm# 3.000 500 3.535 0-0.061 0.26 4.00 5.90 1.88 1.99 76.1 3450 15730 0-1.6 - 2' 22 2-3/a x 2 102 150 48 0 3 3.500 500 4.800 0-0.06 -2 0.22 4.50 00 88 2.9 80 88.9 3450 21360 0-1.6 18 2- x 2'/a 114 178 48 3 31/2 4.000 500 6 300 0-0.06 01.19 5. '/z 12700 191 50 48 88 2.9.3 90 101.6 3450 28035 0 1.6 0°-54' 6 2 y x 2 3/a 4 4.500 500 7.950 0-0.131._30 02.384 5 80 8 03 2 13 4.119 100 1143 3450 35380 0 32 2-/zx2s/, --- 147 204 54 4.250 450 6.380 0-0.131° 0.359 14 5 515 198 9 25143 31..77 108.0 mm '108.0 3100 28395 0-3.2 41 2 I. 2-12 x 70.0 --- 41/2 5.000 450 8.820 0-0.13 0.25 "6.13 9 43 2 13 5.5 120 127.0 3100 39250 0-3.2 -26 21 2-s/sx3Ya 156 240 54 2.5 5 5.563 450 10.935 0-0.13 0.27 6.88 007 2.13 5.8 125 141.3 3100 48660 0-3.2 - 8 2-s/ax3Yn 23 175 256 54 2.6 133.0mm 5.250 450 9.735 0-0.13 0.28 655 9.37 2.13 6.0 133.0 3100 43325 0 3.2 21 2-16 x 82.5 24166 238 54 2.7 139.7mm# 5.500 450 10.665 0-0.13 0.28 6.80 9.59 2.13 6.3 139.7 3100 47460 0 3.2 - 8' 24 2-s/x''''' 173 244 54 2.9 152.4 mm 6.000 450 12.735 0-0.131 0.21 7.38 10.48 1.88 6.2 152.4 3100 56670 0 3.2 12' 18 2 5/s x 3%n 187 266 48 2.8 6 6.625 450 15.525 0-0.13 0.23 8.00 07 2.13 0 150 168.3 3100 69085 0-3.2 -5 18 2-s/x3/ 203 281 54 3.2 Continued on page 3. *t @#Refer to notes on page 3. < Y ��1 111�1�1i www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. Ictc`1VlIc REV H CARSON STEEL PIPE.. GROOVED COUPLINGS 06.05 CCLIPFini,› STYLE 75 DIMENSIONS AMax.Work Allow.Pipe Size Pressure* Max End Load* End Sep.t Deflect.Fr CLt Not/Suzee Dimensions Inches/mm Wgt.Each r OutsN9�;,. s Size r t i s Inches � �Et 'fit PSL ' LbS" dips to fit. y. 1 . " grt iPa ,. .� 159.0 m m 6.250 450 13.800 0-0.13 0.24 7.63 10.49 2.13 6.8 9' 2-16x82.5 159.0 3100 61405 0-3.2 20 194 266 54 3.1 165:1 mm# 6.500 450 14.940 0-0.1316 0.23 7.84 0.66 2 06 7.2 165.1 3100 66483 0-3.2 19 2-5Ax3Ya 199 271 52 3.3 203.2 mm# 8.000 450 22.635 0 0.13 0` 54' 0.16 9.72 3 33 2 31 2.6 203.2 3100 100725 0-3.2 2-3/ax4'/a 13 247 339 58 5.7 8 8.625 450 26.280 0-0.13 0° 50 0.18 2-3/a x 4'/n 0 34 13.97 2.32 12.4 200 219.1 3100 116945 0-3.2 14 263 355 59 5.6 254.Omm# 10.000 350 27.500 0-0.13 0° 43' 0.15 1216 15.81 2-5,3„ 20.8 254.0 2400 122375 0 3.2 2-'/e x 5 V2 309 402 69.4 304.8 mm# 12.000 350 39.500 0-0.13 0` 36' 0.13 4.16 17.69 2 53 23.6 304.8 2400 5775 0 3.2 9 2-'/s x 5'/z 360 449 64 10.7 Working Pressure and End Load are total,from all internal and external loads,based on standard weight(ANSI)steel pipe,standard roll or cut grooved in accordance with Victaulic specifications.Contact Victaulic for performance on other pipe. WARNING:FOR ONE TIME FIELD TEST ONLY,the Maximum Joint Working Pressure may be increased to 1 1/2 times the figures shown. t Allowable Pipe End Separation and Deflection figures show the maximum nominal range of movement available at each joint for standard roll grooved pipe.Figures for standard cut grooved pipe may be doubled.These figures are maximums;for design and installation purposes these figures should be reduced by:50%for 3/4-3 1/2"/20 90 mm;250/0 for 4"/100 mm and larger. @ Number of bolts required equals number of housing segments. Metric thread size bolts are available(color coded gold)for all coupling sizes upon request.Contact Victaulic for details. y > 1.6Z1 p: /��:' 11111 imi iii . - Iii www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. �Ct�UI1C° REV H 06.05_3 15 P 05 444, nielkx...:11074.773W31.;,449 Coupitng STYLE 75 WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. • NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. INSTALLATION Reference should always be made to the 1-100 Victaulic Field Installation Handbook for the product you are installing. Handbooks are included with each shipment of Victaulic products for complete installation and assembly data,and are available in PDF format on our website at www.victaulic.com. III 111 111 1 111111111111 1 11 PIM 111 WCAS-6QAQQT For complete contact information,visit www.victaulic.com 06.05 1470 REV H UPDATED 9/2006 VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. .�Ctau�l�..'® 06.05 DEL S.W. 72nd97224e PORTLAND, ORR Avenue PHONE 503-620-4020 FAX 503-620-1058 FIRE, IRE, INC. CCB#64174 HANGERS FIRE PROTECTION CONTRACTORS PIPE RINGS (0Anivi Fig. 69 Adjustable Swivel Ring, Tapped Per NFPA Standards Size Range:1/2"through 8" Material:Carbon steel Finish:❑Galvanized Service:Recommended for suspension of non-insulated stationary pipe line. Maximum Temperature:650°F e\V Approvals:Complies with Federal Specification A-A-1192A(Type 10) WW-H-171-E(Type 10),ANSI/MSS SP-69 and MSS SP-58(Type 10). UL Listed and FM Approved(Sizes 3/4"-8"). Features: • Threads are countersunk so that they cannot become burred or damaged. • Knurled swivel nut provides vertical adjustment after piping is in place. • Captured swivel nut in the'/2"through 6"sizes.The capture is permanent in the bottom portion of the band,allowing the hanger to be opened during installation if desired,but not allowing the nut to fall completely out. Ordering:Specify size,figure number and name. Note:The acceptability of galvanized coatings at temperatures above 450°F is at the discretion of the end user. Metric nut available upon request.Non-captured nut also available upon request. , fA1 _illiiII . \ F C B /---, cl tB1F \ li , i 1'/<"through 8"pipe '/2"through 1"pipe FIG. 69: LOADS (LBS) • WEIGHT (LBS) • DIMENSIONS (IN) Pipe Size Max Load Weight Rod Size A B C F 1/2 0.10 2' 2 19/6 3/4 0.10 2% VA 15A6 1 300 0.10 29/,6 11//16 1 1'/ 0.10 2% 1% i 1'/2 0.10 3/6 2% 1% /6 2 0.11 3' 2% 1% 21/2 525 0.20 4 2% 15/16 3 0.20 313/,6 215/,6 13/16 4 650 0.30 4"A6 313A6 5 0.54 55/9 4a/ 19/6 6 1,000 0.65 /2 6"A6 59/6 21/ 8 1.00 8 7 211/6 Note:Reflects changes in rod diameter from previously published data per recent revisions in MSS-SP-58&69 PROJECT INFORMATION APPROVAL STAMP Project: ❑Approved Address: ❑Approved as noted Contractor: ❑Not approved Engineer: Remarks: Submittal Date: Notes 1: Notes 2: Catalog PH-2008 STEEL PIPE CLAMPS &P)..4,NY14 Fig. 261 Extension Pipe or Riser Clamp Size Range:3/4"through 24" Material:Carbon steel Finish:❑Plain,❑Hot-Dip Galvanized with Zinc Plated Bolts&Nuts or❑Epoxy Coated IMP . Service:For support of stationary steel pipe risers,cast iron pipe or conduit.This product is not intended for use with hanger rods. For this application, refer to Fig.40 Riser Clamp. " LISTED Maximum Temperature:Plain 650°F,Galvanized and Epoxy 450°F Note:Refer to Technical Data Section for cast iron soil pipe data. Approvals:Complies with Federal Specification A-A-1192A(Type 8) WW-H-171-E(Type 8),ANSI/MSS SP-69 and MSS SP-58(Type 8). 7.7------\---\ _____ri UL, ULC Listed(Sizes 11/2"-8"). ( l 1 I Installation:Clamp is fitted and bolted preferably below a coupling, i hub or welded lugs on steel pipe.Bolt torques should be per industry I standards.Clamp is designed for standard steel pipe O.D.and this l_1J must be considered in sizing the riser for other types of piping. Ordering:Specify pipe size,figure number,name and finish. ) IG I. B .I 14 L FIG.261: LOADS(LBS) •WEIGHT(LBS) • DIMENSIONS(IN)• TORQUE (FT-LBS) Pipe Max G Bolt Torque Size Load Weight L Width Diameter C Diameter Values 314 220 1 1 87/8 1 2'/e — 31/8 3 3 11/4 1.6 10 3i/3 /e /8 21 11/2 250 1.6 10'/n 3'/8 2 300 1.7 1 41A 212 400 1.9 111/4 43/4 1/2 7/6 32 3 500 1.9 113/8 512 31/2 600 2.3 127/e 612 4 750 2.4 7 5 1,500 3.6 13% 8 1/2 /z 46 6 1,600 4.0 143/4 11/2 9 8 7.6 1812 12 10 2,500 11.1 201/4 13% 5 5 12 16.5 22% 2 153/4 /8 /e 100 14 2,700 17.7 24 171/4 16 30.4 26 193/4 18 2,900 33.8 28 212 21% 3/a 34 150 20 35.0 30 23% 24 3,200 82.0 36% 3 30 1 7/8 190 PROJECT INFORMATION APPROVAL STAMP Project: ❑Approved Address: ❑Approved as noted Contractor: ❑Not approved Engineer: Remarks: Submittal Date: Notes 1: Notes 2: PH-1.15 HANGER RODS (*.A.VVK: Fig. 146 Continuous Threaded Rod Size Range:'/4"through l'/2"Stocked in six,ten,and twelve foot lengths.Other even foot lengths can be furnished to order. Material:Carbon steel;rod threaded complete length. Finish:❑Plain or❑galvanized. Maximum Temperature:650°F. Ordering:Specify rod diameter and length,figure number, name and finish. Note:The acceptability of galvanized coatings at temperatures above 450°F is at the discretion of the end user. Length A FIG. 146: LOADS(LBS)•WEIGHTS(LBS)DIMENSIONS(IN) Rod Size Threads Max Load Weight A per Inch 650° F per Ft. '/4 20 240 0.12 3/e 16 730 0.30 '/2 13 1,350 0.53 5/e 11 2,160 0.84 3/4 10 3,230 1.20 9 4,480 1.70 1 8 5,900 2.30 11/4 7 9,500 3.60 1 Y2 6 13,800 5.10 Note:Other rod sizes available upon request.Class 2 fit is available upon request. PROJECT INFORMATION APPROVAL STAMP Project: ❑Approved Address: ❑Approved as noted Contractor: ❑Not approved Engineer: Remarks: Submittal Date: Notes 1: Notes 2: Catalog PH-2008 ir. = Nis GST Wood , SAMMYS W it.D 4(4,41 lik,divve , ;:.,I gtoviiii.,, ,, BOA quantity 100 except as noted with this marking (o) , t ...Wp",' ,1' Ott#14 N--,,,?, fleilti,, . .,:f,'9 •. '- 376—, • Box quantity 50 Item # Model Rod Size Shk Dia Shk Lgth 20 ,GST.750 1/4-20 1/4 3/4 matem#100) 21 GST 100 1/4-20 1/4 1 22 GST 200 1/4-20 1/4 2 23 GST 300 1/4-20 1/4 3 24• GST 600 1/4-20 1/4 6 See page 13 for Stainless Steel 0.,• 0'40i'Unitoir?-:„1 .. ;0,1 ,•':,',.",7„7 1',111t 1,1..•,.'''''''''',.!5?; ,;11,- ittg,..., Note:Screwy less than 2,,in ,12.71, ,i'l'''T..;:,. 't';',4.—*,,,,,, ,141;41.,"te.:,r:,,oc: ::"Z*4':.11'.'.4.:.'• ''''''.4.,,',,,,t :-.:iir;t,,..„,,..... . length will be plated yellow. ,. ..., 14,, :' ',...e't:A bi, ""4'I' '''',71'`,,,.,.....;0''.; "%4::''''' Greater than 2"are clear , RVI Test IL Test ULJFM zinc per ASTMB633111 Item# Model Rod Size Shk Dia 'Shk Lgth Load,lb. Load,lb. Pipe Size Actual Pullout 4 10 GST.75 318-16 1/4 3/4 ' 564#-6 Ry 210#-7/18 068 11 GST 10 3/8.16 1/4 1 670#-3/4"Fly 12 GST 20 3/8-16 1/4 2 940# 850# 3/4-21/2 1760#-Rr_ #I4 them mow 27 •GST 25-380 3/8-16 3/8 2 1/2 , 1500# 4 2113#-Rr 13 GST 30 3/8-16 1/4 3 1475# 1500# 3/4-4 20604*-Ar 403•GST 40 3/8-16 1/4 4 , 2180#-Rr 14 * GST 60 3/8-16 1/4 6 2230#-Rr , 14(1;',2,,it ir'"i, :(,•-,', -, .. ..,,,e;) i - ,..`4,,,,r,"‘" f.k.- -_-• 1,,• , ,,,i..4...,,,,.. rr; ir= '' 4..„4,.4.-,•,,,'•...*-1111-' ...$41Aor, f...,kt.' ,,,','4:v. 7 ; Item4* Model Rod Size 1 Shk Dia Shk Lgth Actual Pullout 8 • GST 2 1/2-13 1/4 2 176011-RI- Note:the#14SW moot be used 06• GST 2.5-381 1/2-13 3/8 21/2 21134t-Ar m.,(4, 4 15• GST 3 1/2-13 1/4 , 3 22754*-At' , 16* GST 4 1/2-13 1/4 4 1 2180#-Rr i 1 17 GST 6 1/2-13 1/4 I, 6 223041-Rr Installations Not8ess than 2'nominal width See Page 5 for installation instructions. < (1 trr) > ,..1 7 Installation , a. per 14FPA 13 P I 6 Is I 1...a , i."`, I I 1 I , - TGI Joist/Truss ,.. 1. , .. Consult truss manufacturer for recommended Installation point. (See"Special Notes" er•Wood Flooring on"peer i") r r'.m a Wood Joist Lower face of/ beam or Joist • al Minimum r itraminvent Into bete aMIMMIIMMIggdwwwwwwwwwwwesegge Ormaer •1M••••••■mg mailaimImaterial for NFPA 13 compliance For vertical use. 1rilli Install in center liglit' , .-• Sammy of lower Isom Double Sheetrock Ceiling (..; If F you diozooneltocooln us at I. I' 4 Wood-Sammys I 5 Note:Must be installed with appropriate nut driver to comply with warranty. i , SWG awe Wood k do ".. ' Olk See page 13 for Stainless Steel SIDEWINDERS g b - r r • ;: r r rr: ray '' Box quart:dr 100 except as noted with this marking(4) r i � ,. r Box quantity SO ., r, . i_ *.^es W • m,..,r`o-.k,�, Item# Model Rad Size Shk Ola Shk Lgth Actual Shear/Pullout t14sw(hem#un I 300 SWG 200 1/4-20 1/4 2 1725#-Fir Note:Screws less than 2"in length , r sl r * 'e : rr�a'-,',4--`4' fir`✓ ,,,i well be plated yellow:Greater than jj . ,',..'7,/,', J,:'..-'4,',0.., . A.„=a,n,k�..x" ... ,t .a,,,,,,,,„440,- 2,"are clear enc per Item # Model Rod Size Shk Dia UL Test UL Pipe Actual AS1MBd33111 Shk Lgth'Load,lb. Size Shear/Pullout 18 SWG 10 3/8-16 1/4 1 -_-_ tl4s1%ore,0101) I19 r SWG 20 3/8-16 1/4 2 1250# 3 1725#-Fir 26, SWG 25-388 3/8-16 3/8 2 1/2 ° 1500# 4 2249#-Fir 25• SWG 30 3/8-16 1/4 3 i if fastening through gusset plates,use She SWD 20(see page 5) Installations TG1 Joist/Truss Consult truss manufacturer for recommended krstallation point. floor Joist e+ § Sidewinder ~` (See"Special Notes" Mi., ..s Sidewinderan"page.r 1 I; i 111 I i r/ WOOD INSTALLATION INSTRUCTIONS GST&SWG—See diagram figures 1-4,11-14 on page 1 18 and 19, (Self drilling&sell-tapping into wood) Not less than 2"nominal width(1 1/2") up to 3 tn"pipe;not less than 3" nominal width 4"&5"pipe Step 1: Insert the appropriate nut driver into a 3/8"or 1/2" portable drill:(a)Use#14 for GST for 3/8"and 1/4"rod;(b) Installation - ,,. use#14SW for SWG,and for GST for 1/2"rod. per NFPA 13 Step 2: Insert the screw into the nut driver.Now you are ready to install the screw. Step 3: Position drill and begin installation: (a)for installing GST drill should be in a vertical position;(b)for installing SWG drill should be in a horizontal position at a right angle r4 to the structural member. Minimum 2 fn"from bottom for ^ ri branch lines.Minlmtnn 3"from Step 4:When the nut driver spins freely on the cap of the bottom for main lines.Exr ption: This requirement shall not apply to 2" screw installation is complete. or thicker nailing strips reeling on top of steel beams. „.4 iligk Step 5:Screw is now ready to receive 1/4",3/8", 1/2"or metric all thread rod or bolt stock. Eye protection should be worn at all times when Install- ={ ing this product. Note:Must be installed with appropriate nut driver to comply with warranty. Wood-Sidewinders 5 Seismic Bracing Fig.4L - Longitudinal "In-Line"Sway Brace Attachment 1•,•Y C !S Size Range: 2"(50mm)through 8"(200mm)ips. LISTED ,,,, Material: Steel Function: For bracing pipe against sway and seismic disturbance. Set Screw&Hardware • � � Included SSS.//s Approvals: Underwriters Laboratories Listed in the USA(UL)and _I/�1 Canada(cUL)21/2"(65mm)through 8"(200mm)pipe.Approved by Factory I Mutual Engineering(FM),2"(50mm)through 8"(200mm)pipe. Installation Instructions: Fig.4L is the"braced pipe"attachment component of a longitudinal sway brace assembly. It is intended to be D A combined with the"bracing pipe" and Cooper B-Line/TOLCO structural attachment component to form a complete bracing assembly.NFPA 13 and/or OSHPD guidelines should be followed. iki To Install: Place the Fig.4L over the pipe to be braced and tighten m bolts.Then engage "bracing pipe" into jaw opening and tighten set screw C 2 until head snaps off.Jaw attachment can pivot for adjustment to properj brace angle. i ;m in Finish: Plain.Contact Cooper B-Line for alternative finishes and materials. Order By: Figure number, pipe size and finish. y® Mia 4-Way Riser Brace Eft , Longitudinal (plan view) ,a Brace Pipe Max.Rec.Load *Max.Design Load Approx. Part Size A C D Bolt Size (cULuc) (FM) Wt./100 No. in. (mm) in. (mm) in. (mm) in. (mm) lbs. (kN) lbs. (kN) lbs. (kg) 4L-2 mg (50) 53/8 (136.5) 21/16 (52.4) 21/16' (52.4) 1/2"-13 2015 (8.96) -- (--) 247 (112.0) 414112t 21/2" (65) 67/16" (163.5) 21/2" (63.5) 23/4" (69.8) 1/2"-13 2015 (8.96) 3000 (13.34) 253 (114,7) L ;® (80) 7" (177.8) 23/4" (69.8) 31/16" (77.8) 1/2"-13 2015 (8.96) 1550 (6.89) 268 (121.5) 4L-4 (100) 8112" (215.9) s 33/8' (85.7) 311/16" (93.7); 1/2"=13 2015 (8.96) 1550 (6.89) 348 (157.8) 41-5 ® (125) 93/4" (247.6) 37/8' (98.4) 43/8" (111.1) 1/2"-13 2015 (8.96) 1450 (6.45) 380 (172.3) 4(.6y 6" (150) 111/2 (292.1) 5" (127.0) 51/8" (130.2) 1/2"-13 2015 (8.96) 1450 (6.45) 640 (290.3) 41 , 8" (200) 131/4" (336.5) 55/8" (142.8) 55/8" (142.9) 1/2"-13 2015 (8.96) 1450 (6.45) 728 (330.2) Pipe Max.Rec.Load *Max.Design Load(FM) Part Size (cULuc) 30°-44° 45°-59° 600-74° 750-90° No. in. (mm) lbs./(kN) lbs. (kN) lbs. (kg) *The loads listed are axial loads on the brace. 2 The horizontal load capacity,H,of the 4 .® (50) 2015(8.96) -- -- brace is: H=F x sin?,where?the installation 41 2112; 21/2" (65) 2015(8.96) 1030(4.58) 1180(5.24) 1420(6.31) 1590(7.07) ; angle measured from the vertical. 4L-3`I® (80) 2015(8.96) 1030(4.58) 1180(5.24) 1420(6.31) 1590(7.07) FM approved when used with 1", 11/4", 11/2"or 4L-4 : 4 (100) 2015(8.96) 530(2.36) 730(3.25) 890(3.96) 990(4.40) 2 Sch.40 brace pipe. ® (125) 2015(8.96) 530(2.36) 730(3.25) 890(3.96) 990(4.40) ,,,4L-6,-. 6' ' (150) 2015(8.96) 530(2.36) 730(3.25) 890(3.96) 990(4.40) -8 ; 8' (200) 2015(8.96) 490(2.18) 680(3.02) 830(3.69) 930(4.13) Cooper B-Line,Inc.'s("Cooper B-Line")seismic bracing components are designed to be compatible only with other Cooper B-Line bracing components,resulting in a listed seismic bracing assembly.Cooper-B-Line's warranty for seismic bracing components will be the warranty provided in Cooper B-Line's standard terms and conditions of sale made available by Cooper B-Line,except that,in addition to the other exclusions from Cooper B-Line's warranty,Cooper B-line makes no warranty relating to Cooper B-Line's seismic bracing components that are combined with products not provided by Cooper B-Line. All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. IIMIIIIIIIIIIIIIIIIIIEIMIIIIIIIIIIIIPPrmlim COOPER B-Line , . ®TOLCO' Fig. 980 - Universal Swivel Sway Brace Attachment c 0 us 11> WEB APPROVED Size Range — One size fits bracing pipe 1"thru 2",TOLCO 12 gauge channel, and all structural steel up to 1/4"thick. Component of State of California OSHPD Approved Material — Carbon Steel Seismic Restraints System Function — Multi-functional attachment to structure or braced pipe fit- ting. Features — This product's design incorporates a concentric attachment ,w► opening which is critical to the performance of structural seismic con- rie nections. NFPA 13(2010)9.3.5.8.4 indicates clearly that fastener table load values are based only on concentric loading. Mounts to any sur iii _ face angle. Break off bolt head assures verification of proper installation. Installation — The Fig.980 is the structural or transitional attach- H ment component of a longitudinal or lateral sway brace assembly. It is intended to be combined with the"bracing pipe"and TOLCO "braced '�'+ pipe" attachment, Fig. 1000, 1001, 2002,4L, 4A or 4B to form a com- I \11 plete bracing assembly. NFPA 13 and/or OSHPD guidelines should be I 4 followed. To Install — Place the Fig. 980 onto the "bracing pipe".Tighten the set INIIIIII bolt until set bolt head breaks off.Attachment can pivot for adjustment to proper brace angle. A I Approvals — Underwriters Laboratories Listed in the USA(UL)and Canada(cUL).Approved by Factory Mutual Engineering(FM). Included B in our Seismic Restraints Catalog approved by the State of California Officeof Statewide Health Planning and Development(OSHPD). For additional load, spacing and placement information relating to OSHPD projects, please refer to the TOLCO Seismic Restraint Systems Guidelines. Note — The Fig. 980 Swivel Attachment and the Fig. 1001, Fig. 1000, Fig. 2002, Fig. 4A, Fig. 4B or Fig. 4L Pipe Clamp make up a sway brace system of UL Listed attachments and bracing materials which satisfies • 'i " F the requirements of Underwriters' Laboratories and the National Fire _.---_.. '..''1"-:::::.::':/-- Protection Association (NFPA) / -..-;,, , ,, . ,, , ,,,,it4(1(Finish — Plain 1 s`--; , 1 ,, I. Note — Available in Electro-Galvanized finish. 4. ( ,q,:4' , ' Order By — Figure number and finish. Pat.#6,273,372, Pat.#6,517,030, Pat.#6,953,174, -, Pat.#6,708,930, Pat.#7,191,987, Pat.#7,441,730, - ' Pat. #7,669,806 Dimensions•Weights *Available with hole sizes to accommodate up to 3/4"fastener. Max.Design Max.Design Consult factory. A B H* Load Lbs. Load Lbs.** APprox. **The loads listed are axial loads on the brace.The horizontal load (CULus) (FM) Wt./100 capacity, H,of the brace is:H=F x sin 0,where 0 is the installation „ angle measured from the vertical. 5/a 17/8 A2 2765 2800 132 Cooper B-Line, Inc.'s("Cooper B-Line")seismic bracing components are designed to be compatible only with other Cooper B-Line bracing components, resulting in a listed seismic bracing assembly. Cooper B-Line's warranty for seismic bracing components will be the warranty provided in Cooper B-Line's standard terms and conditions of sale made available by Cooper B-Line,except that,in addition to the other exclusions from Cooper B-Line's warranty,Cooper B-Line makes no warranty relating to Cooper B-Line's seismic bracing components that are combined with products not provided by Cooper B-Line. COOPER B-LINE 1375 Sampson Ave•Corona,CA 92879•800.786.5266•FAX:951.737.0330 WWw.tOICO.COm O. COOPER B-Line 0 TOLCO www.tolco.com NIBCO Revision 7/15/2011 Fig. 1000 - "Fast Clamp" Sway Brace Attachment Component Oof State SHPD California OSHPD Approved Seismic Restraints System Size Range — Pipe size to be braced: 1" thru 6" Schedule 10 thru 40 IPS.* Pipe size used for bracing: 1" and 11/4" Schedule 40 IPS. ..— ' cua LISTED / '\ \ "Additionally(UL)approved for use with Allied Dyna Flow sprinkler 1 r , pipe up to 2" as a restraint device. Maximum horizontal design load / 7 r \. , '\ .,.. is 655 lbs. Torque requirement is 6-8 ft. lbs. `�,; Material — Carbon Steel I Function — For bracing pipe against sway and seismic disturbance. Ii '� 'x, Features — Field adjustable, making critical pre-engineering of 1 1 \ bracing pipe unnecessary. Unique design requires no threading of bracing pipe. Can be used as a component of a 4-way riser brace. I Can be used as longitudinal brace with Fig. 907. Steel leaf spring I insert provided to assure installer and inspector necessary minimum ,././ k r torque has been achieved. ' +, 1 t Installation — The Fig. 1000 is the "braced pipe" attachment ; i j' component of a lateral sway brace assembly. It is intended to be combined with the "bracing pipe" and TOLCO structural attachment I'�- f ,,-- " -./ component, Fig. 980, 910 or 909 to form a complete bracing assem- r bly. Follow NFPA 13 and/or OSHPD guidelines. , To Install — Place the Fig. 1000 over the pipe to be braced, insert bracing pipe through opening leaving a minimum of 1" extension. Brace pipe can be installed on top or bottom of pipe to be braced. Tighten hex nuts until leaf spring is flat. It is recommended that the brace angle be adjusted before hex nuts are fully tightened. UL Listed Design Load Approvals — Underwriters Laboratories Listed in the USA(UL) 1" thru 4" pipe size — 2015 lbs. and Canada(cUL). Approved by Factory Mutual Engineering (FM). Included in our Seismic Restraints Catalog approved by the State of California Office of Statewide Health Planning and Development FM Approved Design Loads (OSHPD). For additional load, spacing and placement information 1" - 21/2" - 600 lbs. relating to OSHPD projects, please refer to the TOLCO Seismic 3" - 4" - 700 lbs. Restraint Systems Guidelines. Application Note — Position Fast Clamp and tighten two hex nuts until leaf spring flattens. A minimum of 1" pipe extension beyond the Fig. 1000 is recommended. Finish — Plain .3 Note — Available in Electro-Galvanized and HDG finish or Stainless `' Steel materials. Order By — Order first by pipe size to be braced, followed by pipe size used for bracing, figure number and finish. 7./ / ,��._ . TOLCO®brand bracing components are desgined to be compatible ONLY with \ t ,;; other TOLCO®brand bracing components,resulting in a Listed seismic brac- `{,'''' ing assembly. DISCLAIMER — NIBCO does NOT warrant against the failure of \, / TOLCO®brand bracing components, in the instance that such TOLCO®brand bracing components are used in combination with products,parts or systems \\ Lateral Brace which are not manufactured or sold under the TOLCO®brand. NIBCO shall NOT be liable under any circumstance for any direct or indirect, incidental or conse- quential damages of any kind,including but not limited to loss of business or profit,where non-TOLCO brand bracing components have been,or are used. OFFICE/MANUFACTURING FACILITY•1375 SAMPSON AVE.•CORONA,CA 92879•PH: 951 737.5599•FAX: 951.737 0330 CUSTOMER SERVICE•800.786.5266III www.tolco.com Seismic Bracing Fig. 1001 - Sway Brace Attachment MTOLCO Size Range: Pipe size to be braced:21/2" (65mm)thru 8" (200mm)IPS. c US "Pipe size used for bracing: 1" (25mm)and 11/4" (32mm)Schedule 40 IPS. LISTED Material: Steel a Function: For bracing pipe against sway and seismic disturbance. n The pipe attachment component of a sway brace system: C Fig. 1001 is used in conjunction with a Fig.900 Series fitting and c, joined together with bracing pipe per NFPA 13,forming a complete 2 sway brace assembly. Features: Can be used to brace schedules 7 through 40 IPS. Field adjustable, making critical pre-engineering of bracing pipe length unnecessary. Unique design requires no threading of bracing pipe. Comes assembled and ready for installation. Fig. 1001 has built-in visual verification of correct installation. See installation note below. Installation Note: Position Fig. 1001 over the pipe to be braced Set Bolts and tighten two hex head cone point set bolts until heads bottom cl.Included out.A minimum of 1"(25mm)pipe extension is recommended. Brace pipe can be installed on top or bottom of pipe to be braced. Approvals: Underwriters Laboratories Listed in the USA(UL) and Canada(cUL). UL Listed Design Load For FM Approval information refer to page 65. Sch.7 - 1600 lbs.(7.11kN) Finish: Plain. Contact Cooper B-Line for alternative finishes and materials. Sch.10&40 w/1"(25mm)Brace Pipe Order By: Order by figure number, pipe size to be braced,followed by pipe 2015 lbs.(8.96kN) size used for bracing(1" (25mm)or 11/4" (32mm)) ,and finish. Sch.10&40 w/11/4"(32mm)Brace Pipe Important Note: Fig. 1001 is precision manufactured to perform its 2765 lbs.(12.30kN) function as a critical component of a complete bracing assembly.To ensure performance,the UL Listing requires that Fig. 1001 must be used only with other Cooper B-Line/TOLCO bracing products. r .k,, Pipe Part Number&Approx.Wt./100 Design OP Size 1"(24mm)Brace Pipe 11/4"(32mm)Brace Pipe Load in. (mm) Lbs. (kg) Lbs. (kg) " ® (65) 0.211g,21:/2 1 138.6 (62.8) 001 21/2 X 1114 160.4 (72.7) UL El (80) y 001-31)01-3V6r 147.2 (66.7) 1000.01/4 1 168.7 (76,5) UL 4" (100) ,i1.. 4 X 1 160.9 (73.0) ,1001-41 11/4.'a 182.4 (82.7) UL 6" (150) 1001-6 X344 ; 190.0 (86.2) 1001-6; 1/4 211.4 (95.9) UL 8" (200) 101-8 X 1 217.4 (98.6) 1001 8'a X1/4 a. 238.8 (108.3) UL ""See load ratings in UL Listed Design Load chart. * The loads listed are axial loads on the brace.The horizontal load capacity, H,of the brace is: H=F x sin?,where?is the installation angle measured from the vertical. II \(11140 1 Lel -4r0 01 ill o NI All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. COOPER B-Line Seismic Bracing Fig. 1001 - Sway Brace Attachment IVTQLCO Size Range: Pipe size to be braced:21/2" (65mm)thru 8" (200mm)IPS. 441> *Pipe size used for bracing: 1"(25mm)and 11/4" (32mm)Schedule 40 IPS. APPROVEb Material: Steel c Function: For bracing pipe against sway and seismic disturbance. 0 The pipe attachment component of a sway brace system: L° Fig. 1001 is used in conjunction with a Fig.900 Series fitting and m joined together with bracing pipe per NFPA 13,forming a complete �, sway brace assembly. tin Features: Can be used to brace schedules 7 through 40 IPS. Field adjustable, making critical pre-engineering of bracing pipe length unnecessary. Unique design requires no threading of bracing \1 pipe.Can be used as a component of a four-way riser brace. Comes assembled and ready for installation. Fig. 1001 has built-in visual verification of correct installation.See installation note below. set Bolts Installation Note: Position Fig. 1001 over the pipe to be braced 1 Included and tighten two hex head cone point set bolts until heads bottom • out.A minimum of 1" (25mm)pipe extension is recommended. Brace pipe can be installed on top or bottom of pipe to be braced. Approvals: Approved by Factory Mutual Engineering(FM). For UL Listed information refer to page 64. FM Approved Design Loads* Finish: Plain. Contact Cooper B-Line for alternative finishes and materials. 21/2"(65mm)pipe size-1600 lbs.(7.11kN) Order By: Order by figure number, pipe size to be braced,followed by pipe 3"(75mm)to 4"(100mm)pipe size-1700 lbs.(7.56kN) size used for bracing(1" (25mm)or 11/4" (32mm)) ,and finish. 5"(125mm)to 8"(200mm)pipe size-1033 lbs.(4.59kN) Important Note: Fig. 1001 is precision manufactured to perform its function as a critical component of a complete bracing assembly.To ensure performance,the FM Approval requires that Fig. 1001 must be used only with other Cooper B-Line/TOLCO bracing products. Designed to meet or exceed requirements of FM DS 2-8. A,�x r v Pipe Part Number&Approx.Wt./100 Design Size 1"(24mm)Brace Pipe 11/4"(32mm)Brace Pipe Load in. (mm) Lbs. (kg) Lbs. (kg) ** ® (65) 100121/2 X 1 138.6 (62.8) 1001 2112 X 11/4 , 160.4 (72 7) FM Till } (80) 1001 3 x 1 147.2 (66.7) 401 3"X 1114 168.7 (76,5) FM 4" (100) 1;0 X 4 160.9 (73.0) 01001-4 X i14;.. 182.4 (82.7) FM 6 (150) . 1001-6 X 1 190.0 (86.2) 1001 6,X1114 211.4 (95.9) FM 8" (200) 100/-8 if- x'' 217.4 (98.6) i001 8 X 11/4 238.8 (108.3) FM **See load ratings in FM Approved Design Load chart. * The loads listed are axial loads on the brace.The horizontal load capacity, H,of the brace is: H=F x sin?,where?is the installation angle measured from the vertical. FM Approved design loads are based on ASD design method. 1I 01 C I*(*°-j i \4(11141) SK (1,. . i ea .4 I 0 All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. COOPER B-Line DEL. 14795 S.W. 72"d Avenue PORTLAND, OR 97224 PHONE 503-620-4020 INC CCB#6416 4 FIRE, -1 058 SPRINKLER HEADS FIRE PROTECTION CONTRACTORS Bulletin 014 Rev. F CO t Model F1FR56 Series ReliableQuick Responseo Standard Spray33 IIIMIIIMIIIIMIIMMIIIIIIIIIIIIIIMIIIMI (D Model F1FR56 Sprinkler Types Standard Upright .. _ Standard Pendent `, 1 Conventional t NU Vertical Sidewall , Horizontal Sidewall rvt1 Model F1FR56 Recessed Sprinkler Types Standard Pendent/F1/F2/FP Upright Pendent Horizontal Sidewall Model F1FR56 Concealed Sprinkler Types Standard Pendent . 0 Listing & Approvals 1. Underwriters Laboratories Inc. and Certified for Canada(cULus). 2. Factory Mutual Approvals(FM) 3. Loss Prevention Council (LPCB, UK) Vertical Sidewall Conventional 4. VdS Schadenverhutung GmbH UL Listing Category Sprinklers,Automatic&Open(VNIV) Quick Response Sprinkler • Product Description `. Reliable Models F1 FR56 Series Sprinklers are quick re- sponse sprinklers which combine the durability of a stan- Horizontal Sidewall Recessed dard sprinkler with the attractive low profile of a decorative Pendent/F1/F2 sprinkler. The Models F1FR56 Series Recessed automatic sprin- klers utilize a 3.0 mm frangible glass bulb. These sprin- x. . -. klers have demonstrated response times in laboratory tests ` _-_ which are five to ten times faster than standard response sprinklers. This quick response enables the Model F1FR56 Series sprinklers to apply water to a fire much faster than • standard sprinklers of the same temperature rating. The glass bulb consists of an accurately controlled amount Recessed Recessed of special fluid hermetically sealed inside a precisely manu Horizontal Sidewall Pendent/FP factured glass capsule. This glass bulb is specially con- structed to provide fast thermal response. At normal temperatures, the glass bulb contains the fluid Application in both the liquid and vapor phases. The vapor phase can Quick response sprinklers are used in fixed fire protec- be seen as a small bubble. As heat is applied, the liquid tion systems: Wet, Dry, Deluge or Preaction. Care must be expands,forcing the bubble smaller and smaller as the liq exercised that the orifice size, temperature rating, deflec uid pressure increases. Continued heating forces the liquid tor style and sprinkler type are in accordance with the lat to push out against the bulb, causing the glass to shatter, est published standards of the National Fire Protection As opening the waterway and allowing the deflector to distrib sociation or the approving Authority Having Jurisdiction. ute the discharging water. Quick response sprinklers are intended for installation as specified in NFPA 13. Quick response sprinklers and stan- dard response sprinklers should not be intermixed. The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Model F1FR56 Quick Response Upright, Pendent & Conventional Sprinklers Installation Wrench: Model D Sprinkler Wrench Installation Data: Sprinkler Identification Number Nominal Thread Nominal K Factor Sprinkler Approval (SIN) Orifice Size Height Organization US Metric Upright Pendent Standard-Upright(SSU)and pendent Deflectors Marked to Indicate Position 1/2"(15mm) 1/2"NPT(R'h) 5.6 80 2.25"(57mm) 1,2,3,4 RA1425(1) RA1414(1)(2) Conventional-Install in Upright or Pendent Position 15mm(1) 1/2"NPT(R'/2) 5.6 80 57mm 3,4 RA1475 (1)cULus listed corrosion resistant(Polyester coated)sprinkler. (2)Polyester coated FM approved sprinkler. — s a.,,. -�..: ,tr 41.1.1'4:7; " N± ' / Upright Pendent Conventional Model F1 FR56 Quick Response Recessed Pendent Sprinkler Installation Wrench: Model GFR2 Sprinkler Wrench Installation Data: Nominal Thread K Factor Sprinkler Sprinkler Identification Number Orifice Size US Metric Height (SIN) 1/2"(15mm) 1/2"NPT(R' ) 5.6 80 2.25"(57mm) RA1414 (1) Refer to escutcheon data table for approvals and dimensions. - --2 5/8"D/A. [66.7mm] 2 1/57.2mm4"HOLE)DIA. HOLE IN CEILING [ 1 15/7G"Dlq -A•2 5/16"D/A. [58.7mm] �-- [49.2mm] CUP L 1 Model Fl FR56 Quick Response Vertical Sidewall Sprinkler Installation Wrench: Model D Sprinkler Wrench Installation Position: Upright or Pendent Approval Type: Light Hazard Occupancy Installation Data: Nominal K Factor Sprinkler Approval Nominal Thread Size p ' Sprinkler Orifice US Metric Height Organizations Identification Numbers(SIN) '/z"(15mm) 1"NPT(R1/2) 5.6 8.0 2.25"(57mm) 1,2,3,4 15mm 1"NPT(R1/2) 5.6 8.0 2.25"(57mm) 40) RA1485 (1)LPC Approval is for pendent position only. Sprinkler Type Deflector to Ceiling Distance . " (Min.-Max) Upright 4"(102mm)- 12"(305mm) 0 Pendent 4"(102mm)- 12"(305mm) Vertical Sidewall Model Fl FR56 Quick Response Horizontal Sidewall Sprinkler Deflector: HSW Installation Wrench: Model D Sprinkler Wrench Installation Data: Horizontal Sidewall Nominal K Factor Sprinkler Approval Organizations Height and Type of Approval Sprinkler Nominal Orifice Thread Size Identification US Metric Light Hazard OrdinaryHazard Numbers(SIN) 1"(15mm) 1/2"NPT(R1/2) 5.6 80 2.63"(67mm) 1,2 1 RA1435 4 FACE OF FITTING(1) TO FACE OF CEILING DIMENSION 1 1/4"MIN. 2 1/4"HOLE DIA. [31.8mm] 1/B" 4"-12" L [57.2mmJ [101.6mm-304.8mm] [3.2mm] CEILING TO ,.. 1"X 1/2"REDUCER DEFLECTOR 1_ r- ' 1 15/16"DIAD%iiii I 1 1 ip.i [49.2mm] ' iiin — i t 1 1 l 2 27/32"DIA. 1 111 1 .—y��� [72.2mm] r r Horizontal Sidewall J1 I TURN COLLAR UNTIL TIGHT AGAINST SPRINKLER WRENCH BOSS. It 3 ADJUSTMENT(1) 01JFC03A (1) REFER TO ESCUTCHEON DATA TABLE FOR APPROVALS AND DIMENSIONS. (2) FM APPROVED FOR 4" — 6"[101.6MM — 152.4MM] CEILING TO DEFLECTOR. Note: For Recessed HSW Sprinklers use installation wrench GFR2. 3. Model F1FR56 Quick Response Concealed Pendent Sprinklers Installation Wrench: Model RC1 Sprinkler Wrench Technical Data: "K"Factor Temp.Rating Max. Bulb Sprinkler Nominal Thread Model Ambient Approvals Identification Orifice US Metric Size Sprinkler Cover Temp Color Number(SIN) 1/2"(15mm) 5.6 80 1/2"NPT F1FR 135°F/57°C 135°F/57°C 100°F/38°C Orange 1,2 RA1414 1/"(15mm) 5.6 80 1/2" NPT F1FR 155°F/68°C 135°F/57°C 100°F/38°C Red 1,2,411 RA1414 1/2"(15mm) 5.6 80 1/2" NPT F1FR 175°F/79°C 165°F/74°C 100°F/38°C Yellow 1,2 RA1414 1/2"(15mm) 5.6 80 1/2" NPT F1FR 200°F/93°C 165°F/74°C 100°F/38°C Green 1,2 RA1414 (1)For VdS only= 155°F/68°C Norbulb and 1/2"[12,7mm]adjustment. 1"x 1/2"REDUCING TEE OR ELBOW 1"x 1/2"REDUCING Ti TEE OR ELBOW ll — m 2 5/8"DIA. i _ / 2 5/16" DIA L, HOLE IN CEILING 2 5 8" DIA. CUP J 2 5/76"DIA HOLE IN CEILING ___ 1 1/2"MAX. CUP � 7-77-- 7,4,IIGr�17�11 7�. i i i DIMENSION : 11111111!III1 1/2}'MAX. III III FACE OF F1TnNG iplc �ili i i � � ''i i'.�_ CEILINGTO FACE OF CEILING _ FACE OF FITTING ITO FACE OF CEILING CEILING , , I j �._ 1 7T. �� DIMENSION ��!p � A : - j I 1/2" MAX. COVER ADJUSTMENT 15 16' 5/16"MAX. ..- -a .. 3/4" COVER ADJUSTMENT COVER PLATE COVER PLATE— } ASSEMBLY3 5/16" DIA. ASSEMBLY / 3 5/16"DIA. — SPRINKLER / SPRINKLER 1/2" ADJUSTMENT on.. 5/16" ADJUSTMENT 017FGo: Figure 1 Figure 2 Installation Aid A protective cap is included for use during installation. Sprinkler with a threaded Model CCP cup which is fac- Important: The F1 FR56 Sprinkler with Model CCP cover tory attached to the sprinkler. The assembly is complet- plate is not an FM Approved combination. ed by the installation of the attractive, low profile, 135°F Installation (57°C) or 165°F (74°C) rated Model CCP push on cover Quick response sprinklers are intended for installation plate assembly. The cover plate and sprinkler cup as- as specified in NFPA 13. Quick response sprinklers and semblies are joined using a cover plate skirt with flexible standard response sprinklers should not be intermixed. tabs for threaded engagement. A choice of two cover The Model F1 FR56 Recessed Quick Response Sprin- plate assemblies provide either 1/2" (13mm)or 5/16" (8mm) klers are to be installed as shown.The Model Fl or F2 Es- of cover adjustment. cutcheons illustrated are the only recessed escutcheons Do not install these sprinklers in ceiling which have to be used with the Model F1FR56 Sprinklers. The use positive pressure in the space above. of any other recessed escutcheon will void all approvals After a 25/8" (67mm) diameter hole is cut in the ceil- and negate all warranties. ing, the sprinkler is easily installed with the Model RC1 When installing Model F1FR56 Sprinklers, use the Mod- Wrench. A Teflon* based thread sealant should be el D Sprinkler Wrench. Use the Model GFR2 Wrench for applied to the sprinkler threads only. The Model RC1 installing F1FR56 Recessed Pendent Sprinklers. Any Wrench is then used to engage the sprinkler wrenching other type of wrench may damage these sprinklers. surfaces and to install the sprinkler in the fitting. When NOTE: A leak tight 1/2" NPT (R1/2) sprinkler joint can inserting or removing the wrench from the sprinkler/cup be obtained with a torque of 8-18 ft-lbs(10,8-24,4 N-m). assembly, care should be taken to prevent damage to Do not tighten sprinklers over maximum recommended the sprinkler. DO NOT WRENCH ON ANY OTHER PART torque. It may cause leakage or impairment of the sprin- OF THE SPRINKLER. The cover plate is then pushed klers. onto the cup. Final adjustment is made by hand turning The Model Fl FR56/CCP Concealed Sprinkler uses the the cover plate until the skirt flange makes full contact 1/2" orifice, 1/2" NPT (R1/2), 135°F (57°C), 155°F (68°C), with the ceiling. Cover plate removal requires turning in 175°F (79°C) or 200°F (93°C) Model F1FR56 Pendent the counter clockwise direction. *DuPont Registered Trade Mark 4. After installation, inspect all sprinklers to ensure that Sprinkler Types there is a gap between the cover plate and ceiling and Standard Upright that the four cup slots are open and free from any air flow Standard Pendent impediment to the space above. Conventional Concealed cover plate/cup assemblies are listed only Recessed Pendent for use with specific sprinklers. The use of any other con- Vertical Sidewall cealed cover plate/cup assembly with the Model Fl FR56 Horizontal Sidewall Pendent Sprinkler or the use of the Model CCP Concealed Recessed Horizontal sidewall cover plate assembly on any sprinkler with which it is not Concealed pendent specifically listed my prevent good fire protection and will void all guarantees, warranties, listings and approvals. Maximum Working Pressure Glass bulb sprinklers have orange bulb protectors to 175 psi (12 bar) minimize bulb damage during shipping, handling and 100% Factory tested hydrostatically to 500 psi (34.5 bar) installation. REMOVE THIS PROTECTION AT THE TIME Finishes 0) THE SPRINKLER SYSTEM IS PLACED IN SERVICE FOR FIRE PROTECTION. Removal of the protectors before this Standard Finishes Sprinkler Escutcheon Cover plate time may leave the bulb vulnerable to damage. RASCO Bronze Brass wrenches are designed to install sprinklers when covers Chrome Plated Chrome Chrome are in place. REMOVE PROTECTORS BY UNDOING THE White Polyester Plated White CLASP BY HAND. DO NOT USE TOOLS TO REMOVE Coated(4)(5) White Painted THE PROTECTORS. Special Application Finishes Sprinkler Escutcheon Cover plate Temperature Ratings Bright Brass(3) Bright Brass Bright Brass Sprinkler Black Plated Black Plated Satin Max.Ambient Black Paint(2) Black Paint Off White Classification Temperature Temp. Bulb Color Off White(2) Off White Black Paint °C °F Satin Chrome Satin Chrome Black Plated Ordinary 57 135 100°F(38°C) Orange (1) Other finishes and colors are available on special order. Ordinary 68 155 100°F(38°C) Red Consult the factory for details. Intermediate 79 175 150°F(66°C) Yellow (2) cULus Listed only. Intermediate 93 200 150°F(66°C) Green (3) 200°F(93°C)maximum. High(1) 141 286 225°F(107°C) Blue (4) cULus listed"corrosion resistance"applies to SIN Numbers (1)Not available for recessed sprinklers. RA1425(Upright)and RA1414(Pendent)in standard black or white. (5) FM Approvals finish as"Polyester coated"applies to SIN Number Escutcheon Data 0) RA1414(Pendent)in standard black or white. Escutcheon Face of Fitting to OrderingInformation Model Approvals Adjustment Dimension Ceiling or Wall Dimension Specify: Fl 1,3,4 Max Recess 11/2"(38.1mm) 1/46'-15h6" 1. Sprinkler Model Min Recess 3/4"(19.1mm) (5mm-24mm) 2. Sprinkler Type F2 1,2,3,4 Max Recess 11/2"(38.1mm) 3/16"-'y1s' 3. Orifice Size Min Recess 1"(25mm) (5mm-17mm) FPPushon/ Max Recessed 116"(11mm) 172"(38.1mm) 4. Deflector Type Thread-off 1'4 Min Recessed 15/16(24mm) 1"(25.4mm) 5. Temperature Rating (1)SIN:RA1435-cULus and FM permits use with Fl or F2 escutcheons for light 6. Sprinkler Finish hazard only. 7. Escutcheon Type 8. Escutcheon Finish (where applicable) Maintenance 9. Cover plate Model The Models F1FR56 and F1FR56 Recessed Sprinklers 10. Cover plate Thread size should be inspected quarterly and the sprinkler system 11. Cover plate Temperature maintained in accordance with NFPA 25. Do not clean 12. Cover plate Adjustment sprinklers with soap and water, ammonia or any other 13. Cover plate Finish cleaning fluids. Remove dust by using a soft brush or gentle vacuuming. Remove any sprinkler which has Note:When Model F1FR56 Recessed sprinklers are ordered,the sprin- been painted (other than factory applied) or damaged klers and escutcheons are packaged separately. in any way. A stock of spare sprinklers should be main- tained to allow quick replacement of damaged or oper- ated sprinklers. Prior to installation, sprinklers should be maintained in the original cartons and packaging to mini- mize the potential for damage to sprinklers that would cause improper operation or non-operation. 5. DEL 14795PORTLANDS.W. 72OR Avenue , PHONE 503-620-4020 FAX 503- FIRE, INC. CCB#641 74 1058 SWITCHES BELLS FIRE PROTECTION CONTRACTORS BELLS PJ; POTTER PBA-AC & PBD-DC The Symbol of Protection UL Listed, FM Approved Sizes Available:6"(150mm),8"(200mm)and 10"(250mm) Voltages Available: 24VAC 120VAC 12VDC(10.2 to 15.6)Polarized fi14 _`: *"g24VDC(20.4 to 31.2)Polarized Service Use: Fire Alarm a General Signaling - % , BurglarAlarm Environment: Indoor or outdoor use(See Note 1) -40°to 150°F(-40°to 66°C) (Outdoor use requires weatherproof backbox.) Termination: 4 No. 18 AWG stranded wires 6" BELL SHOWN Finish: Red powder coating Optional: Model BBK-1 weatherproof backbox These vibrating type bells are designed for use as fire, burglar or general signaling devices. They have low power con- sumption and high decibel ratings. The unit mounts on a standard 4" (101mm) square electrical box for indoor use or on a model BBK-1 weatherproof backbox for outdoor applications. Weatherproof backbox model BBK-1, Stock No. 1500001. ALL DC BELLS ARE POLARIZED AND HAVE BUILT-IN TRANSIENT PROTECTION: SIZE TYPICAL dB MINIMUM dB INCHES VOLTAGE MODEL NO. STOCK NO. CURRENT AT 10 FT. AT 10 FT. (mm) (MAX.) (3m)(2) (3m)(1) 6(150) 12VDC PBD126 1706012 .12A 85 76 8(200) 12VDC PBD128 1708012 .12A 90 76 10(250) 12VDC PBD1210 1710012 .12A 92 76 6(150) 24VDC PBD246 1706024 .06A 87 76 8(200) 24VDC PBD248 1708024 .06A 91 79 10(250) 24VDC PBD2410 1710024 .06A 94 79 6(150) 24VAC PBA246 1806024 .17A 91 76 8(200) 24VAC PBA248 1808024 .17A 94 76 10(250) 24VAC PBA2410 1810024 .17A 94 76 6(150) 120VAC PBA1206 1806120 .05A 92 82 8(200) 120VAC PBA1208 1808120 .05A 99 82 10(250) 120VAC PBA12010 1810120 05A 99 85 Notes: 1. Minimum dB ratings are calculated from integrated sound pressure measurements made at Underwriters Laboratories as specified in UL Standard 464. UL temperature range is-30°to 150°F(-34°to 66°C). 2. Typical dB ratings are calculated from measurements made with a conventional sound level meter and are indicative of output levels in an actual installation. Potter Electric Signal Company•2081 Craig Road,St.Louis,MO,63146-4161•Phone:800-325-3936/Canada 888-882-1833•www.pottersignal.com PRINTED IN USA MKT.#8850001-REV Q PAGE 1 OF 2 MEG.#5400776-12/01 . . BELLS P POTTER PBA-AC & PBD-DC ® The Symbol of Protection DIMENSIONS INCHES(mm) FIG. 1 BELLS FIG. 2 WEATHERPROOF BACKBOX BOX HAS ONE THREADED 1/2"CONDUIT ENTRANCE I [ E1 I 10" (200) 6" I let (250) �"-1--� 5 3/4" — 3 3/8" 5" 8" I I (146) O (86) (127) r --f - I LI- (150) i C� I i -0.--11 5/8"1-■-- (86) (41) f 4 1 4 2 11/16" / " (68) DWG, #776-1 (108) DWG. #776-2 FIG. 3 WIRING (REAR VIEW) D.C. BELLS (OBSERVE POLARITY) A.C. BELLS RED (IN) Aiiiiiiihs. RED(OUT) WHITE (IN) WHITE (OUT) FROM CONTROL PANEL i4414 TO NEXT BELL FROM CONTROL PANEL re/ OR OR END-OF-LINE DR PRECEDINGRBELL 010 RESISTOR PRECEDINGRBELL f BLACK (IN) _� BLACK (OUT) BLACK (IN) ' BLACK (OUT) 1111111 \COW cm MON. CAUTION, WHEN ELECTRICAL SUPERVISION IS REQUIRED USE IN AND OUT LEADS AS SHOWN, WHEN ELECTRICAL SUPERVISION IS REQUIRED USE IN AND OUT LEADS AS SHOWN_ NOTES: NOTES: 1, OBSERVE POLARITY TO RING D,C, BELLS, 1, WHEN USING A_C. BELLS, TERMINATE EACH EXTRA WIRE SEPARATELY 2, RED WIRES POSITIVE (+) AFTER LAST BELL. 3, BLACK WIRES NEGATIVE (-) 2, END-OF-UNE RESISTOR IS NOT REQUIRED ON A,C, BELLS, DWG. #776-3 INSTALLATION 1. The bell should be mounted a minimum of 8 ft. (2,4m)from the floor or as close to the ceiling as possible. 2. Removethegong. 3. Connect wiring(see Fig.3). 4. Mount bell mechanism to backbox(bell mechanism must be mounted with the striker pointing down). 5. Reinstall the gong(be sure that the gong positioning pin, in the mechanism housing, is in the hole in the gong). 6. Test all bells for proper operation and observe that they can be heard where required(bells must be heard in all areas as designated by the authority having jurisdiction). PRINTED IN USA MKT.#8850001-REV Q PAGE 2 OF 2 MFG.#5400776-12/01 14795 Avenu S.W. 72R 97224e PORTLAND, OR PHONE 503-620-4020 FAX 503-620-1058 F I R E, I N Cs CCB#64174 SPRINKLER VALVES FIRE PROTECTION CONTRACTORS FButterflyaloe c us LPCB of vds See Victaulic publication 10.01 for details SERIES 7O5W WITH WEATHERPROOF ACTUATOR FOR 300 PSI SERVICE The Series 7O5W butterfly valve features an approved weatherproof actuator housing approved for indoor or outdoor use. It has a ductile iron body and disc with EPDM disc coating.The body is coated with a heat fused polyphenylene sulfide blend to meet FM requirements. Designed for fire protection services only,Series 7O5W valve is UL Listed and FM Approved for 3OOpsi/2O65kPa service.Contact Victaulic for details of agency approvals. WEATHERPROOF ACTUATOR Supervisory switches that monitor the valve in the fully open or fully closed position for valves are available 21/2—12765—300mm pre-wired (PW). OPTIONAL SUPPLY-SIDE TAP Series 7O5W valves are available with a '/z"(for 21/2", 76.1 mm and 3'sizes)or /4"(4— 12"/100—3OOmm sizes) NPT supply side tap designed to allow direct water supply connection to Victaulic FireLock actuated fire protection valves.See separate drawings below.This is an optional feature and must be clearly noted on all orders. 1/4"tap avail- able by special order.Contact Victaulic for additional information on tapped valves. MATERIAL SPECIFICATIONS Body: Ductile iron conforming to ASTM A-536,coated with polyphenylene sulfide blend. Disc: Ductile iron conforming to ASTM A-536,various grades, EPDM coated. Disc Coating: • Grade"E"EPDM EPDM (Green color code).Temperature range—30°F to+230°F/-34°C to+110°C. Recommended for cold and hot water service within the specified temperature range plus a variety of dilute acids,oil-free air and many chemical services. UL classified in accordance with ANSI/NSF 61 for cold+86°F/+30°C and hot+180°F/+82°C potable water service. NOT RECOMMENDED FOR PETROLEUM SERVICES. Stem Bearings:Teflon impregnated fiberglass with stainless steel backing. Stem Bearing Nuts:Type 416 Stainless Steel. Tap Plug:Carbon steel, plated. 0-Ring: EPDM Bracket: Carbon steel, painted. Actuator: • 21/2—8765—2OOmm: Bronze traveling nut on a steel lead screw, in a ductile iron housing. • 10—12"/250—3OOmm:Steel worm and cast iron quadrant gear, in a cast iron housing. JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date Approved Date www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. REV F 10.18 1 IPS CARBON STEEL PIPE -FIRE PROTECTION VALVES 10. 18 nk ve SERIES 705W WITH WEATHERPROOF ACTUATOR FOR 300 PSI SERVICE MATERIAL SPECIFICATIONS Handwheel: Size Version Black Red nun 21/2-4 3.0 65-100 76.2 25 5-6 4.5 125 150 114.3 200 8 ® .. 200 160 mm 250 10 12 9 250-300 225 *Vd5 version not UL Listed,FM Approved or LPCB Approved. • www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA.. �Cta V�1C0 10.1$_2 _._.., .� „,li REV_F IPS CARBON STEEL PIPE-" FIRE PROTECTION VALVES 10. 18 FireLock°') Butterfly :. SERIES 705W WITH WEATHERPROOF ACTUATOR FOR 300 PSI SERVICE DIMENSIONS- O ® LPCB c us Aprx.Wgt. Size Dimensions inches/millimeters Each Nominal Actual Outsi .s, Size iamete., inches., es"" .> 272 2875 3.77 8.76 4.21 6.08 3 00 0.00* 0.75 8.3 65 73.0 95.6 222.5 106.9 154.4 76.2 0.0* 19.1 3.8 76.1 mm 3.000 3.77 8.76 4.21 6.08 3.00 0.00* 0.75 8.3 76.1 95.6 222.5 06.9 154.4 76.2 0.0* 19.1 3.8 3 3.500 3.77 9.40 0.08 4.21 6 08 3.00 0.00* 0.75 8.9 80 88.9 95.6 238.8 2.0 106.9 154.4 76.2 0.0* 19.1 4.0 4 4.500 4.63 10.84 0.07 6.01 6.98 3.00 0.73 1.13 14.9 100 114.3 117.6 275.3 1.8 152.7 177.3 76.2 18.5 28.7 6.8 39.7 mm 5.500 5.88 12.38 0.43 6.01 8.57 4.50 21.0 _ 1 139.7 149.4 314.5 10.9 152.7 217.7 114.3 9.5 5 5.563 5.88 12.38 0.43 6.01 8.57 4.50 21.0 125 ; 141.3 149.4 314.5 10.9 152.7 217.7 114.3 9.5 165.1 mm ` 6.500 5.88 13.41 1.00 7.51 9.32 4.50 1.60 1.88 26.5 165.1 1494 340.6 25.4 190.8 236.7 114.3 40.6 47.8 12.0 6 6.625 5.88 13.41 1.00 7.51 9.32 4.50 1.60 1.88 26.5 150 168.3 149.4 340.6 25.4 190.8 2367 114.3 40.6 47.8 12.0 8 8.625 5.33 16.50 1.27 9.65 10.98 6.30 0.00* 0.68 43.0 200 219.1 135.4 419.1 32.3 2451 278.9 160.0 0.0* 17.3 19.5 5 10 10.750 6.40 19.14 172 12.20 16.19 9.00 80.0 250 273.0 162.6 486.2 43.7 309.9 411.2 228.6 36.3 12 !: 12.750 6.50 21.54 2.66 14.25 17.22 9.00 _ 102.0 300 323.9 165.1 547.1 67.6 362.0 437.4 228.6 46.3 *On Centerline #These dimensions apply only to a Series 705W Butterfly Valve with a 1/2-inch NPT,supply-side tap 1.To prevent rotation of valves.it is recommended that Series 705W be installed with Victaulic Style 07 Zero-Flex',Style 005 FireLock,Style 009/009V FireLock EZ,or Style HP-70 Rigid Couplings.If Victaulic flexible couplings are used.additional support may be required. 2.Valve must not be installed with disc in full open position.Disc must be partly closed so that no part is protruding beyond end of valve body. 3.Victaulic grooved end butterfly valves are permitted for use with grooved end pipe(IPS)only.Not permitted for use with plain end(IPS)pipe. 4.Series 705W valves are designed for ambient weather conditions as opposed to submersible service. ,fl i H R7.7- 0 ° �� s71-011 f`:'. Ki .-= �. II - _II ,,NPT B � %"NPT g PPyTaPPPyTP111111 N it 1 C��►I:� iili IlkrIJ I II J E P J A E P_.. 2' -4-INCH/65-100-MM SIZES 5-12-INCH/125-300-MM SIZES www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. Ictaulic--,.,* REV_F 10.18 3 IPS CARBON STEEL PIPE. FIRE PROTECTION VALVES 10. 18 • FireLock® y krialve SERIES 705W WITH WEATHERPROOF ACTUATOR FOR 300 PSI SERVICE DIMENSIONS- (VdS) Aprx.Wgt. Size Dimensions inches/millimeters Each NominalActual ode Diameter s 2 V I 2.875 3.77 8.76 4.21 6.08 492 0.00* 0.75 8.3 65 73.0 95.6 222.5 106.9 154.4 125 0.0* 19.1 3.8 6.l mm 3.000 3.77 8.76 4.21 6.08 4.92 0.00* 0.75 8.3 761 95.6 222.5 106.9 154.4 125 0.0* 19.1 3.8 3 3.500 3.77 9.40 0.08 4.21 6.08 4.92 0.00* 0.75 89 80 889 95.6 238.8 2.0 106.9 154.4 125 0.0* 19.1 4.0 4 4.500 4.63 10.84 0.07 6.01 6.98 4.92 0.73 1.13 149 100 114.3 1176 275.3 1.8 152.7 177.3 125 18.5 28.7 6.8 139.7 mm 5.500 5.88 12.38 0.43 6.01 8.57 7.87 21.0 139.7 149.4 314.5 10.9 152.7 217.7 200 9.5 5 5.563 5.88 12.38 0.43 6.01 8.57 787 21.0 125 141.3 149.4 314.5 109 152.7 217.7 200 9.5 165.1 mm 6.500 5.88 13.41 1.00 7.51 9.32 7.87 1.60 1.88 26.5 �._ 165.1 149.4 340.6 25.4 190.8 236.7 200 40.6 47.8 12.0 6 6.625 5.88 13.41 1.00 7.51 9 32 7.87 1.60 1.88 26.5 150 168.3 149.4 340.6 25.4 190.8 236.7 200 40.6 47.8 12.0 8 8.625 5.33 16.50 1.27 9.65 10.98 9.84 0.00* 0.68 43.0 200 I 219.1 135.4 419.1 32.3 245.1 2789 250 0.0* 17.3 19.5 10 ,, 10.750 6.40 19.14 1.72 12.20 16.19 9.84 80.0 250 273.0 162.6 486.2 43.7 3099 411.2 250 36.3 12 12750 6.50 21.54 2.66 14.25 17.22 9.84 102.0 300 323.9 165.1 547.1 67.6 I 362.0 437.4 250 46.3 *On Centerline 4 These dimensions apply only to a Series 705W Butterfly Valve with a''/2-inch NPT,supply-side tap 1.To prevent rotation of valves.it is recommended that Series 705W be installed with Victaulic Style 07 Zero-Flex°.Style 005 FireLock,Style 009/009V FireLock EZ,or Style HP-70 Rigid Couplings.If Victaulic flexible couplings are used,additional support may be required. 2.Valve must not be installed with disc in full open position.Disc must be partly closed so that no part is protruding beyond end of valve body. 3.Victaulic grooved end butterfly valves are permitted for use with grooved end pipe(IPS)only.Not permitted for use with plain end(IPS)pipe. 4.Series 705W valves are designed for ambient weather conditions as opposed to submersible service. g.. II I�,�rfl _ I�,ra I_.,1 I-....N� � an11 a J o E��� II �i 0.�� ° �v�Rh � �`N� II _n. pNPT it- s,„..„ TaP111r'';n)I Imo,,, _. ��a� N -1- I Ilk I Ilki� 11 I II I II J A E P 1 - A E P--. 21-4-INCH/65-100-MM SIZES 5-12-INCH/125-300-MM SIZES www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA.. iCtaUlICO 10.1.5_4 REV F . . IPS CARBON sTscLp|pE- FIRE PROTECTION VALVES � ��. ���� ��� .-- ------------- --------------- ------------ ----�------------�------ ------� ��^ � �0� �� �� �N ���� F'����~���,� n��������w� ��xve SERIES 705W WITH WEATHERPROOF ACTUATOR FOR 300 PSI SERVICE .----------------- - ----------------�-- --- --------'------- ---- - ' -- --------. PERFORMANCE The chart expressethe frictional resistance of Victaulic Series 705W in equivalent feet/meters of straight pipe. tie Actual Size Oiametez tquiv. Size :Diameter 6.500 8 21/2 2.875 5 165.1 mm 76.1 mm 4 4.500 12 10 10.750 12 100 114.3 3.7 250 273.0 3.7 5.500 12 12 12.750 14 5 5.563 12 125 141.3 3.7 www.victaulic.com VICTALJLIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.@ 2006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. \/ictaulic° nsvLp 1o.za_s IPS CARBON STEEL PIPE- FIRE PROTECTION VALVES 10. 18 ' oc k® Butterfly SERIES 705W WITH WEATHERPROOF ACTUATOR FOR 300 PSI SERVICE PERFORMANCE Cv values for flow of water at+60°F/+16°C with a fully open valve are shown in the table below. For additional details,contact Victaulic. Formulas for C Values: L\P = Qz Where: C 2 Q=Flow+(G11,61\4°C) tiP=Pressure Drop(psi) Q = C x 4P C =Flow Coefficient Size Cv Size Cv Size Gv a . al td d jai 1,5 tsi 410: tFuil opal 65 8 0 715 325 39.7 mm 39.0 1150 200 8 6q 1 3400 3.000 76.1 mm 76.1 325 5 5.563 1150 0 0.750 5750 125 141.3 250 273.0 80 88.9 482 165.1 mm 6.500 1850 21128207...6737255:00 2.750 8300 165.1 300 323.9 3 4 , 4.500 6- 6625 100 143 600 150 68.3 1850 Formulas for Kv Values: �P = Qz Where: K� Q=Flow(n,�, Q = K x DP AP=Pressure(bar) K =Flow Factor Size K� Size Kv Size K v. 'in bI1 Safi .., I to i inch izea fi+4i.,, ,.vll en llleches 1 2Yz E 2.875 280 39.7 mm 5.500 995 8 8.625 65 73 0 139.7 00 219.1 2940 76.1een mm 3.000 5 5.563 10 10.750 76.1 280 25 141.3 995 250 2730 4975 1. 3 3.500 6.50012 80 88.9 415 651 mm 651 1600 300 323.9 12 750 7180 4 4.500 6 6.625 100 4 3 520 150 68.3 1600 www.victaulic.com iC$a VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY.C 2006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA.. 6 REV_F IPS CARBON STEEL PIPE .. FIRE PROTECTION VALVES 10. 18 Firelock Butterfly Valve SERIES 705W WITH WEATHERPROOF ACTUATOR FOR 300 PSI SERVICE SWITCH AND WIRING 1.The supervisory switch contains two,single pole,double throw, pre-wired switches. 2.Switches are rated: 10 amps @ 125 or 250 VAC/60 Hz 0.50 amps @ 125 VDC 0.25 amps @ 250 VDC 3.Switches supervise the valve in the'open" position. 4.One switch has two#18 MTW wires per terminal,which permit complete supervision of leads (refer to diagrams and notes below).The second switch has one#18 MTW wire per terminal. This double circuit provides flexibility to operate two electrical devices at separate locations, such as an indicating light and an audible alarm, in the area that the valve is installed. 5.A#14 MTW ground lead (green) is provided. Switch#1 =S1 For connection to the supervisory circuit of a UL Listed alarm control panel Switch#2=S2 Auxiliary switch that may be connected to auxiliary devices, per the authority having jurisdiction Normally Closed:(2) Blue Si Common:(2)Yellow Normally Closed: Blue with Orange Stripe S2 Normally Open: Brown with Orange Stripe Common:Yellow with Orange Stripe • N(I�CV 3OY. JV ,, OATYO,. ,.VCO V TOC;N, SJNFaVSOP NEXTu T0+ gritV ..Cl1T 661 'h N WTC T - CONTACT AAT,NG. ®I CON,: CONN,-,NRS 1 0A AT 1,AND 25CJAC, 05A AT 125VDC 02 AT 250 ACC I= MI ME W RF NJT_S WORE VOLTAGE 50,F( TOR, Switch 1:l leads per terminal Switch 2,1 lead per terminal NOTE:The above diagram shows a connection between the common terminal(yellow—S1 and yellow-with-orange stripe—S2)and the normally closed terminal (blue—S1 and blue-with-orange stripe—S2). In this example,the indicator light and alarm will stay on until the valve is fully open. When the valve is fully open,the indicator light and alarm will go out.Cap off any unused wires (e.g.brown with orange stripe). Only 51 (two leads per terminal)may be connected to the fire alarm control panel. The connection of the alarm switch wiring shall be in accordance with NFPA 72 and the auxiliary switch per NFPA 70(NEC). www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. jctaulic°. REV F 10.18_7 r ck° Butterfly valve SERIES 705W WITH WEATHERPROOF ACTUATOR FOR 300 PSI SERVICE WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. • NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications.designs and standard equipment without notice and without incurring obligations. INSTALLATION Reference should always be made to the installation sheet included with the valve.Verify you have the latest revision by visiting our website at www.victaulic.com. Further reference can be found in the 1-100 Victaulic Field Installation Handbook. IlI 11111011111111111111111111111111111III WCAS-6LUPQL For complete contact information,visit www.victaulic.com 10.18 2466 REV F UPDATED 12/2006 .ctauIiic° VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. 10.18 IPS CARBON STEEL PIPE-FIRE PROTECTION VALVES 10.08 VICTAULIC" IS AN 150 9001 CERTIFIED COMPANY Series 717 FireLock® Check Valves PRODUCT DESCRIPTION Series 717 FireLock check valve is a CAD-developed design that is hydrodynamically efficient.A totally .,.-- rubber encapsulated disc on 4 - 12"(100-300 mm)sizes provides superior corrosion resistance, This single disc design incorporates a spring assisted feature for non-slamming operation. For systems requiring a Riser Check option refer to section 1009. OW -:.."10, The 4"(100 mm)and larger sizes are provided with upstream and downstream drains and a welded-in x ® ® nickel seat design.All sizes of Series 717 can be installed in the vertical or horizontal position to provide ''kit; 1111,m‘ leak-free sealing under conditions as low as five feet of head. Each valve is factory tested to 500 psi See Victaulic (3440 kPa).The 21/2 and 3"(65 and 80 mm)sizes are UL/ULC Listed and 4"(100 mm)sizes and larger are publication 10.01 UL/ULC Listed and FM Approved for services up to 250 psi(1725 kPa).Sizes 4-8"/100-200 mm(except Sizes 21/2-3' for details. 165,1 mm size)are VdS approved. Grooved ends allow fast, easy installation with just two Victaulic couplings or the valve may be mounted a v. to flanged (ANSI CL.150)equipment using either to Victaulic Style 741 Vic-Flange°or Style 744 FireLock flange adapters on either end. Iv t1 ®® See Victaulic publication 10.01 for details. Sizes 4-12" DIMENSIONS (-- A *B Valve Size Dimensions-Inches/millimeters Actual Approx. IlI,I C Nominal Outside Wgt.s a Diameter Diameter E to E InJmm In./mm A B C D E J K P R kg Typical 21/2-3" 2'/2 2.875 3.88 4.26 3.57 - - - - - - 3.6 65 73,0 99 108 91 - - - - - - 1,6 76,1 mm 3.000 3,88 4.26 3.57 - - - - - - 3.6 76,1 99 108 91 - - - - - - 1,6 A 3 3.500 4.25 5.06 4.17 4.5 -0-[(R F' 80 88,9 108 129 106 - - 2,0 .^ 4 V' 4 4 t 4.500 9.63 6.00 3.88 2.75 3.50 2.00 4.50 3.50 3.35 20.0 �La' '°„1,...11_ __, .11_ C 100 114,3 245 152 99 70 89 51 114 89 85 9,1 III III DE 525 5.563143 10.502 7 6.80173 4.50114 _ 4.17 2555 5.88 104 10181 27,0 1�-KI ,3 a 1 139,7 mm t 5.500 10.50 6.80 4.50 - 4.17 2.15 5.88 4.08 3.98 27.0 f--B-> ->n'J k- o 139,7 267 173 114 - 106 55 149 104 101 12,3 0 1/2"NPT Upstream Drain 6 f 6.625 11.50 8.00 5.00 4.50 2.38 6.67 4.73 3.89 38.0 OO %z"NPT Downstream Drain 150 168,3 292 203 127 - 114 61 169 120 99 17,2 OO 2"NPT(Drain Optional) 6.500 11.50 8.00 5.00 - 4.50 2.38 6.67 4.73 3.89 38.0 165,1 mm 165,1 292 203 127 - 114 61 169 120 99 17,2 Typical 4-8" 8 t 8.625 14.00 9.88 6.06 5.05 5.65 2.15 8.85 5.65 5.75 64.0 200 219,1 356 251 154 128 144 55 225 144 146 29,0 4 A 1 10 10,750 17.00 12.00 7.09 5.96 6.69 2.15 10.92 6.73 100.0 T 250 273,0 432 305 180 151 170 55 277 171 - 45,4 O P I� C 12 12.750 19.50 14.00 8.06 6.91 7.64 2.51 12.81 7.73 140.0 III �I I�� 300 323,9 495 356 205 176 194 64 925 196 - 63,5 D E 1 VdS Approved I4-K--> ©i 0 '-Btu -..1;-,- C,1/2" Iw-101/2"NPT Upstream Drain ©1/2"NPT Downstream Drain Typical 10-12" B REGISTERED TRADEMARK OF VICTAULIC-©COPYRIGHT 2004 VICTAULIC-PRINTED IN U.S.A.-SKU#WCAS.66VPXF 1479 REV F Victaulic Company of America•Phone:1-800-PICK-VIC(1-800-742-5842)•Fax:610-250-8817•e-mail:pickvic@victaulic.com Victaulic Company of Canada•Phone:905-884-7444•Fax:905-884-9774•e-mail:viccanada@victaulic.com Victaulic Europe•Phone:32-9-381-1500•Fax:32-9-380-4438•e-mail:viceuro@victaulic.be Victaulic America Latina•Phone:610-559-3300•Fax:610-559-3608•e-mail:vical@victaulic.com jc t u',C Victaulic Asia Pacific•Phone:86-21-58855151 •Fax:86-21-58851298•e-mail:vicap@victaulic.com �I 10.08 FLOW CHARACTERISTICS NOTE Placement of check valves too close to sources of unstable flow will SERIES 717 shorten the life of the valve and 6.0 i I potentially may damage the system. 5.0 —FLOW OF WATER To extend valve life,valves should be 4.0 _AT 60°F(16°C) installed a reasonable distance THROUGH VALVE downstream from pumps,elbows, expanders,reducers or other similar 3.0 VAre Fdevices.Sound piping practices l� „ dictate a minimum of five(5)times Q,. y, co the pipe diameter for general use. 2.0 r� 'c Distances between three(3)and five • \ry 4t pot 0 5)diameters are allowable provided VJ H ^� b h 4 the flow velocity is less than eight(8) 0- feet per second(2.4 mps).Distances 1 less than three(3)diameters are not d 1.0 recommended and will violate the 0.9 Victaulic product warranty. 06 p 0.7 ui 0.6 n 0.5 cn 0.4 tx 0.3 a 0.2 0,1 10 20 30 40 60 80 100 200 300 400 600 1,000 2,000 4,000 6,000 10,000 20,000 800 3,000 8,000 FLOW RATE-G.P.M. MATERIAL SPECIFICATIONS Body: Ductile iron conforming to ASTM A-536, grade 65-45-12, Ductile iron conforming to ASTM A-395, grade 65-45-15, is available upon special request. 21/2-3”(65-80 mm)sizes PPS coated. 4-12"(100- 300 mm)sizes painted black enamel. Body Seat: 21/2-3" (65-80 mm)sizes PPS coated. 4- 12"(100-300 mm)integrally welded on nickel alloy. Disc Seal or Coating: • Grade"E"EPDM EPDM(Green color code),Temperature range-30°F to+230°F(-34°C to+110°C). Recommended for cold and hot water service within the specified temperature range plus a variety of dilute acids,oil-free air and many chemical services.UL classified in accordance with ANSI/NSF 61 for cold+86°F(+30°C) and hot+180°F (+82°C) potable water service. NOT RECOMMENDED FOR PETROLEUM SERVICES. *Services listed are General Service Recommendations only.It should be noted that there are services for which these gaskets are not recommended, Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service recommendations and for a listing of services which are not recommended. Discs: 21/2-3" (65-80 mm)Aluminum bronze conforming to ASTM B-148 with Grade"E"Seal. 4-12" (100-300 mm) ductile iron conforming to ASTM A-536, grade 65-45-12,fully encapsulated in Grade"E"elastomer. Shaft: 21/2-3" (65-80 mm)Type 416 stainless steel, 4-12" (100-300 mm)Type 316 stainless steel. Spring:All sizes Type 302/304 stainless steel. Shaft Plug:21/2-3"(65-80 mm)only;SAE Hex Socket Type conforming to ASTM A-576,cadmium plated to military specifications QQ-P-416A,class 3 type 2.4-12"(100-300 mm)only;carbon steel zinc plated to ASTM B-633. Pipe Plug: 4- 12"(100-300 mm)only; carbon steel zinc plated to ASTM B-633, This product shall be manufactured by Victaulic Company.All products shall be installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. 2 Series 717 FireLock® Check Valves ON„ R P .: � 5'i z,m,- � ''� .�� Y':�:,. sy � a6s ,.,�t;..... ^s ^d�! . Mt:+' tXs FireLock° Zone Control i 1 ® 0 <> ' SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS SERIES 747M L..---------- ---- ___ , Lf9; Designed for NFPA 13 commercial requirements,the Victaulic Series 747M Zone Control Riser Module features a cast body,and is compact and easy to install in zoned wet sprinkler systems. itte The integrated module body consists of a shut off valve,test and drain valve combination and different orifice sizes(K factors),a UL Listed and FM Approved Flow Switch,and a Pressure r Gauge.The Series 747M FireLock Zone Control Riser Module is available in sizes from 11/4 through 6"/32 mm-150mm with grooved ends on the main pipe for installation in the horizontal or vertical up-flow positions with UL Listed, FM Approved Victaulic grooved couplings.11/4-2"modules have an NPT drain port.2 1/z-6"modules have a grooved drain port. e. The Series 747M FireLock Zone Control Riser Module is FM Approved and UL and ULC Listed for working pressures up to 365psi/2517kPa.An optional pressure relief valve kit is available STYLE 747M for all sizes.The Pressure Relief Valve is FM Approved and UL and ULC Listed for working PATENT PENDING pressures up to 175psi/1200kPa. DIMENSIONS f' Module Body Size Dimensions Inches/mm Aprx Weight ?h[ Each i:AM mr.mil n �' R'x ' H T- (§) 'x x- ,:V ," '!,,,!1:: #1 EN tet: 44 1'14 1.660 1 11.45 7.20 5.77 3.50 10.05 7.48 2 54 15.2 D r 1/':"". 1 32 42 2 33.4 290 8 182 9 146.5 88.9 255 3 190.0 64.5 6.9 `.. � ...r .a 1, -.. s `' C F 1 /2 1.900 1 11.45 7.32 5.77 3.50 10.05 7.48 2.54 15.5 .- 40 48.3 33.4 290.8 185.9 146.5 88.9 255.3 190.0 64.5 7.0 2 2.375 1 1145 7.55 5.77 3.50 10.05 7.48 2.54 19.9 50 60.3 33.4 290.8 191.8 146.5 88.9 255.3 190.0 64.5 9.0 E 21/2 2.875 1 Y4 12.00 ', 8.41 6.18 4.25 9.76 11.87 4.25 22.7 G 65 73.0 42 305 214 157 108 248 302 108 10.3 A 3 3.500 1 Ya 12.00 9.42 6.18 4.25 9.76 11.87 4.25 23.2 13/4-2732-50mm Nominal Sizes -... 80.-. 88.9 : 42 305 239 157 108 248 302 108 10.6 4 4.500 2 12.00 9.90 7.25 5.00 10.15 12.62 4.21 30.3 -VI100 114.3 60 305 252 , 184 127 258 321 107 13.8 4 1 6 6.625 2 12.00 10 85 8.31 6.00 10.15 13.62 4.24 36.7 B 150 168.3 60 305 276 .; 211 154 258 346 107.7 16.7 ". ■i Orif ces � - sro:; Nominal Size " ill Dlip - �1 � f G O 1 25 K5.6 ,t r 1 r~ F . 1.5 K5.6 2 65.6 ( r 25 K5.6K6.9K8.0K11.2 3 K5.6K6.9K8.OK11.2 f- E '-1 I 4 K5.6 K6.9 K8.0 K11.2 K14.0 K16.8 6 K5.6 K6.9 K8.0 K11.2 K14.0 K16.8 A - 2½-6"/65.O-150 mm Nominal Sizes (Valves shown above in the"test"position. Nominal Size Drain Type Drain Size Shown with optional Pressure Relief Valve Kit inches installed) 1.25 NPT Hose Clamp _.... _.. 15 _.._. NPT._ _..... .. _.-, .-..._ 2 _. NPT 1 _.. 2.5 1 Ya Pressure Relief Valve 3 Grooved 1 y, Barbed Fitting 4 Grooved 2 Hose Clamp - - ._..... -... _._.. -... --_.. Close Nipple -Drain Tubing 6 Grooved 2' 4l®1 Elbow Barbed Fitting Optional Pressure Relief Valve Kit Detail JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date Approved Date www.victaulic.com VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2010 VICTAULIC COMPANY.ALL RIGHTS RESERVED. tCtaUlIC REV_I 10.96_-1 FireLock® Zone Control Riser Module SERIES 747M MATERIAL SPECIFICATIONS Module Body:Cast from ductile iron conforming to ASTM A-536,grade 65-45-12 with integral Victaulic grooved ends.Finish:orange enamel. Shut-off and Test/Drain Valve:Chrome plated brass ball,S 37700 brass clapper,416SS or 410SS shafts,Delrin orifice,virgin Teflon*,enhanced Teflon and EPDM rubber seals. `Teflon is a registered trademark of Dupont Coupling:Any UL Listed,FM Approved Victaulic IPS-sized coupling may also be used.Note: Couplings not included with product. Waterflow Detector:System Sensor Model WFD/WFDTH vane type waterflow detector with sealed retard,visual switch activation,and mechanical delay adjustment.Cover includes tamper resistant security screws and tool. Note:ULC models WFDA/WFDTHA include cover tamper switch. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. WARNING A ,:::vo,„,:,„,,,„,„„,:".,::.„:.g,.,,,r,:v,,.i.o,,,,„„,,,:,„„„,,„,;,„,.,,,it,,:,,.„, „:..„,, • This product must be installed by an experienced,trained installer, in accordance with the instructions provided with each valve.These instructions contain important information. Failure to follow these instructions may result in serious personal injury, C , property damage,or valve leakage. If you need additional copies of this product literature or the valve installation instructions,or if you have any questions about the safe installation and use of this device,contact Victaulic Company,P.O. Box 31,Easton,PA 18044-0031 USA,Telephone:001-610-559-3300. For complete contact information,visit www.victaulic.com 10.96 3089 REV I UPDATED 7/2010 �Ctaulic VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2010 VICTAULIC COMPANY.ALL RIGHTS RESERVED. 10.96 Series FBV-3C, FBVS-3C 2-Piece, Full Port, Brass Ball Valves , Sizes: 1/4"—4" (8—100mm) , Series FBV-3C 2-piece, full port,brass ball valves are used in corn- FBV-3C FBVS-3C* mercial and industrial applications for a full range of liquids and gases.They feature a bottom-loaded blowout proof stem,virgin PTFE seats, thrust washer, and adjustable stem packing gland,stem packing nut,chrome plated brass ball,brass adapter, and steel handle. Approvals Features 1/2"—2"(15—50mm)FBV-3C UL/FM approved U) 411. • CSA approved threaded valves only 1/4" —3" (15—80mm) 1/2"—2"(15—50mm)FBVS-3C UL Listed Yv approved •UL/FM approved threaded valves 1/2"—2" (15—50mm) • UL Listed solder valves 1/2" —2"(15—50mm) •Fluorocarbon elastomer stem 0-ring prevents stem leaks Gas Approvals (Threaded Valves Only) • Adjustable stem packing gland 1/4" —3/s" (8—10mm) •PTFE stem packing seal, thrust washer, and seats e® •Bottom loaded blowout proof stem ASME B16.33 CSA c SPus ASME B16.44 • Machined chrome plated brass ball 1/2 psig,5psig, (14,34 kPa) @-40°F to 125°F(-40°C to 52°C) • Valves comply to MSS-SP-110 standard 1/2" —2" (15—50mm)ASME B16.33, CSA ® •Recommended for open/close applications ASME B16.44 c crus Models 1/2 psig,5psig,and 125psig (14,34 and 862 kPa) @-40°F to 125°F(-40°C to 52°C) FBV-3C:V4"—4"(8—100mm)with threaded connections 21/2"—3"(65—80mm) FBVS-3C: 1/2"—3"(15—80mm)with solder connections ASME B16.38, CSA e® Pressure —Temperature ASMEEB16.44 c��us 1/2 psig,5psig,and 125psig(14,34 and 862 kPa) Water Temperature Range:-40°F to 400°F(-40°C to 204°C) @-40°F to 125°F(-40°C to 52°C) Pressure Ratings Specifications FBV-3C:'/a"—2"(8—50mm) Approved valves shall be 2-piece full port design constructed of 600psi (41 bar)WOG,non-shock a forged brass body and end adapter. Seats and stem packing shall be 150psi (10.3 bar)WSP virgin PTFE.Stem shall be bottom loaded,blowout proof design with 21/2"—4"(65—100mm) fluorocarbon elastomer O-ring to prevent stem leaks.Valve shall have 400psi (27.5 bar)WOG,non-shock chrome plated brass ball and adjustable packing gland.Threaded valves 125psi (8.6 bar)WSP '/2"—3"(shall be CSA approved to 1/2,5,and 125psig(14,34 and 862 FBVS 3C:'/2"—2"(15—50mm) kPa),UL/FM approved. Solder valves to be UL listed.Valve sizes 1/4"—2" 600psi (41 bar)WOG,non-shock (8—80mm)shall be rated to 600psi(41 bar)WOG non-shock and 150psi 150psi (10.3 bar)WSP (10.3 bar)WSP.Valve sizes 21/2'—4"(65—100mm)threaded, shall be rated to 400psi(27.5 bar)WOG non-shock and 125psi(8.6 bar)WSP. 2'/2"—3"(65—80mm) Valve sizes 21/2"—3"(65—88mm)solder shall be rated to 400psi(27.5 400psi (27.5 bar)WOG,non-shock bar)WOG non-shock and 125psi(8.6 bar)WSP.Valve shall be a Watts 125psi (8.6 bar)WSP Series FBV-3C(threaded)or FBVS-3C(solder). *This valve is designed to be soft soldered into lines without disassembly, using a low temperature solder to 420°F(216°C). NOTICE Higher temperature solders may damage the seat material. The information contained herein is not intended to replace the full NOTICE product installation and safety information available or the experience of a trained product installer.You are required to thoroughly read all Apply heat with the flame directed AWAY from the center of the installation instructions and product safety information before beginning valve body. Excessive heat can harm the seats.After soldering, the installation of this product. the packing nut may have to be tightened. Watts product specifications in U.S.customary units and metric are approximate and are provided for reference only.For precise measurements, please contact Watts Technical Service.Watts reserves the right to change or modify product design,construction,specifications,or materials with- out prior notice and wthout incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold. Materials -,, -A Temperature -Pressure `� ---A_ Cf r B TC r '4 _ - C ©-C bar psi FBV-3C t-',--D FBV-3C-TH %- 0 41.3 600 E 0- E - F F ` 34.5 500 C' FFrr �r' C' ui H it ', Q ---H 0 :t_ „,.. m 27.6 400 rg > 1 a 'I ✓ ���'l�/7' r K Y 20.7 300 ' e ., J ✓J �( 0 13.8 200 6,/ �►/ 6.9 100 A. Handle Nut Zinc plated carbon steel 3.4 50 B. Handle Assembly Zinc plated carbon steel with vinyl insulator 0 0 C. Packing Nut Brass 50 100 200 300 400 500°F D. Stem Packing Virgin PTFE 10 38 93 149 204 260°C E. 0-ring Fluorocarbon elastomer(FKM) Working Temperature F. Thrust Washer Virgin PTFE G. Stem Machined Brass *See applicable note on reverse side for H. Tag Cardboard,Mylar coated both sides solder end valves with regards to pressure/ I. Body Forged Brass temperature rating. J. Seats Virgin PTFE K. Ball Chrome plated brass L. Adapter Forged Brass Dimensions -Weights - H - -.._ _ Hi .... _ .1 i t, I 1_ { I I L . i L ._.. .- _ ._. LI FBV-3C FBVS-3C Size(DN) DimeNSioNS WeigHt C H Hi I L 1.1 in. mm in. mm inmm in. mm inmm inmm inmm lbs. kg. %a 8 173/46 46 37/16 87 - 1/2 12.9 13/4 45 0.4 0.2 %s 10 113/6 46 3%s 87 - - % 12.9 1% 45 - - 0.4 0.2 1/2 15 113/6 46 33/46 87 37/6 87 1/4 12.9 115/16 50 23/46 52 0.4 0.2 %a 20 2%a 57 4 101 4 101 3/4 19.2 2%6 59 21%6 68 0.8 0.3 1 25 23/4 67 41/4 108 41/4 108 1 25.5 213/6 72 31/ 83 1.2 0.5 11/4 32 213/6 71 4%a 108 4%a 108 11/a 31.9 33/6 81 311/16 94 1.8 0.8 11 40 33/16 80 5%a 134 55/6 135 1%a 38.0 3%2 88 41/a 108 2.6 1.2 2 50 3%2 89 6 153 6 153 2 50.9 41/4 105 55/6 135 3.7 1.7 21/2 65 43/46 104 73/4 187 73/4 188 21/2 63.6 55/16 134 61/a 158 7.1 3.2 3 80 41/2 114 7% 197 73/4 197 3 76.3 61/16 154 7% 185 11.3 4.7 4 100 5%s 136 9% 245 - - 4 101.6 77/16 189 - - 17.7 8.0 L. M�`✓o % VIAF1"S ISO 9001-2008` CERTIFIED A Watts Water Technologies Company USA:Tel (978)688-1811• Fax:(978)794-1848•www.watts.com Canada:Tel (905)332-4090• Fax (905)332-7068•www.watts.ca ES-FBV 1405 ©2014 Watts