Report 7409 SW Tech Center Dr,Ste. 145
Tigard,OR 97223
411=""' '" Ph:503-443-3799 Fax:503-620-2748
OnV
ri1tfsv,,.,*(
503.443.3799 Special Inspection
Final Report
Date: 8-20-13 Job# 13-4255-D35
Permit#BUP2013-00188
Mail To: Project:
NORTHWEST HANDLING SYSTEMS PCC-CENTRAL DISTRIBUTION
18008 NE AIRPORT WAY 671NITA RD STE 200
PORTLAND,OR 97210IT CARD,OR 97224
JOB#03ER130628C
To Whom It May Concern:
ACS Testing, Inc.attests that their inspectors performed special inspection(s)on a continuous and/or
Periodic basis as required by the specific jurisdiction and/or IBC. Special inspection(s)were performed
For the following:
Proprietary Anchors-Expansion
Based on personal observation, inspection and reports reviewed by me for the above project, I attest on behalf
of ACS that work was performed to the best of my knowledge, in accordance with approved plans,
specifications,and the applicable codes and standards for the jurisdiction.
-to‘e)')(314(ANA--
Approved by:
Bob Brown/President
BB/sa
t
Proud to be Nationally Accredited by International Accrediting Service
ACCREDITED
7409 SW Tech Center Dr.Ste. 145
Tigard,OR.97223
spar Ph:503-443-3799 Fax:503-620-2748
TE DAILY FIELD REPORT FOR PROPRIETARY ANCHORS
OHS
TESTING,INC
503.4f3.3799 Date: 8/12/2013 Permit#: BUP2013-00188
NORTHWEST HANDLING PCC-CENTRAL DISTRIBUTION
Continuous 6713 BONITA RD STE 200
SYSTEMS
18008 NE AIRPORT WAY TIGARD, OR 97224
Periodic
PORTLAND, OR 97210 ,/
JOB#03ER130628C
INSPECTOR/CERT Jason Brown 1018 ACS Job # 13-4255-D35
Anchor Embedded in: Concrete IS THIS A REINSPECTION?: f Yes 111 No
Compressive Strength: EXISTING UNKNOWN APPROVED PLANS AVAILABLE ✓ Yes ❑ No
HOLE DETAIL/CONDITION WORK ACCEPTABLE PER
APPROVED PLANS: C Yes ( No
ANCHO HOLE HOLE Installation complies with
RSIZE: 1/2" DIA. 1/2" DEPT 3" + 0Yes I No
H: manufacturers evaluation report?
Holes cleaned properly?: ✓❑ Yes n No
LOCATION OF ANCHORS
Hole depth per plans?: ❑✓ Yes n No
GRIDLINES New racking in PCC warehouse
ESRINSTALLATION
REPORT#
GRIDLINES
ESR-1917 TZ CARBON &STAINLESS IN CONCRETE GRIDLINES
TYPE OF ANCHOR: WEDGE ANCHOR
IS THERE AN RFI? ❑ Yes ✓ No
EPDXY TYPE: N/A RFI ATTACHED? Yes n No
INSPECTION DETAILS:
Exp.Date: N/A
ACS Testing arrived on site for periodic inspection of the 1/2"HILT
KW K bolt TZ wedge anchors per note 5 on drawing 13-0982-A using
two for each base plate placed diagonally with a minimum embedment
of 2-1/2 inches per detail 3 on drawing 13-0982-A. Torque test
performed at 40 ft/lbs per ESR-1917.The work performed appears to be
in conformance with ESR-1917 and the approved plans. Latest revision
#0 issue for permit 06/12/2013.
Foreman notified of 0 Yes 0 No ✓] NA
nonconformance items?
Foremans Name: Tom
Revieweda i 3t Date: CC:
OS-13-2013 Nathan Buhl,Jerry Griffith
BB/JB Bob Brown,President
�..r-