Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Report (32)
ci y-vK sw was%otehv, WYATT FIRE PROTECTION, INC. 9095 S.W. Burnham Tigard, OR 97223 TUMI AT WASH SQ 9585 SW WASHINGTON SQ RD #J02 TIGARD, OR 97223 FIRE PROTECTION EQUIPMENT SUBMITTAL , , ticti Worldwide Contacts www.tyco-fire.com Series RFII — 5.6 K-factor "Royal Flush II" Concealed Pendent Sprinklers Quick & Standard Response, Standard Coverage General stallation or finish. The tip of the Pro- tective Cap can be used to mark the Description center of the ceiling hole into plaster board or ceiling tiles by gently push- The TYCO Series RFII 5.6 K-factor, ing the ceiling product against the Pro- "Royal Flush II" Concealed Pendent tective Cap. When ceiling installation Sprinklers Quick Response (3 mm is complete, the Protective Cap is re- bulb) and Standard Response (5-mm moved and the Cover Plate/Retainer bulb), are decorative sprinklers featur- Assembly is installed. ing a flat cover plate designed to con- As an option, the Series RFII Standard .rt. ceal the sprinkler.These sprinklers are Response(5-mm bulb)"Royal Flush II" optimal for architecturally sensitive ar- Concealed Pendent Sprinklers can be eas such as hotel lobbies,office build- fitted with a silicone Air and Dust Seal. • TY3531 (3-mm Bulb) is UL Listed, ings,churches,and restaurants. (Refer to Figure 5.) The Air and Dust Each sprinkler includes a Cover Plate/ Seal is intended for sensitive areas CUL Listed, Approved (Certif Retainer Assembly and a Sprinkler/ where it is desirable to prevent air and icate No. G409900 007), and NYC Ap Support Cup Assembly. The separa- dust from the area above the ceiling to proved (MEA 353-01-E) as Quick ble, two-piece assembly design pro pass through the cover plate. Response. vides the following benefits: • TY3531 (3-mm Bulb) is FM and • NOTICE LPCB Approved (Ref. No. 094a/10) Allows installation of the sprinklers The Series RFII Concealed Pendent Approved as Standard Response. and pressure testing of the fire pro- FactoryMutual and LPCB do not tection system prior to installation Sprinklers described herein must be of a suspended ceiling or applica- installed and maintained in compli- approve any concealed sprinklers tion of the finish coating to a fixed ance with this document and with the for quick response. ceiling. applicable standards of the National • TY3551 (5-mm Bulb) is UL Listed, Fire Protection Association, in addi- C-UL Listed, FM Approved, LPCB • Permits the removal of suspended tion to the standards of any authori- Approved (Ref. No. 094a/9), and ceiling panels for access to building ties having jurisdiction.Failure to do so NYC Approved (MEA 353-01-E) as service equipment without having may impair the performance of these Standard Response. to first shut down the fire protection devices. system and remove sprinklers. Approvals for Air and Dust Seal The owner is responsible for maintain- • Provides for 1/2 inch (12,7 mm) of ing their fire protection system and de- UL and C-UL Listed for use with the vertical adjustment to allow a mea- vices in proper operating condition. RFII Standard Response Concealed sure of flexibility in determining the The installing contractor or sprinkler Sprinkler(TY3551). length of fixed piping to cut for the manufacturer should be contacted Maximum Working Pressure sprinkler drops. with any questions. The Series RFII Sprinklers are shipped Maximum 250 psi (17,3 bar) by UL, with a Disposable Protective Cap.The Sprinkler C-UL,and NYC Protective Cap is temporarily removed Maximum 175 psi (12,1 bar) by FM, during installation and replaced to help Identification VdS,and LPCB protect the sprinkler during ceiling in- Temperature Rating Number (SIN) 155°F(68°C)Sprinkler with IMPORTANT 139°F 59°C Always refer to Technical Data TY3531 — 3 mm bulb ( )Plate Sheet TFP700 for the "INSTALLER TY3551 — 5 mm bulb 200°F(93°C)Sprinkler with WARNING" that provides cautions 165°F(74°C) Plate with respect to handling and instal- Technical Discharge Coefficient lation of sprinkler systems and com- ponents. Improper handling and in- Data K.5.6 GPM/psi1a(80,6 LPM/bar1/2) stallation can permanently damage Adjustment a sprinkler system or its components Sprinkler Approvals 1/2 inch(12,7 mm) and cause the sprinkler to fail to Approvals apply only to the service operate in a fire situation or cause it conditions indicated in the Design Cri- Finishes to operate prematurely. teria section. See the Ordering Procedure section. Page 1 of 4 MARCH 2013 TFP181 TFP181 Page 2 of 4 Physical Characteristics 1/2"NPT Frame Bronze ` SEALING Support Cup Chrome ASSEMBLY Plated Steel Guide Pins Stainless Steel Deflector Bronze FRAME Compression Screw Brass CAP Bulb Glass Cap Bronze or Copper SUPPORT Sealing Assembly Beryllium CUP WITH Nickel w/TEFLON I I BULB Cover Plate Brass ROLL FORMED Retainer Brass THREADS Ejection Spring Stainless Steel Desi n COMPRESSION Criteria PGUIDE INS(2) A o % 1' SCREW AE AO The TYCO Series RFII 5.6 K-factor, DEFLECTOR "Royal Flush II" Concealed Pendent — — (DROPPED Sprinklers are intended for fire protec- DEFLECTOR i i i i POSITION) tion systems designed in accordance TFP181 Page 3 of 4 FACE OF CLEARANCE HOLE CLEARANCE SPRINKLER - DIAMETER HOLE FITTING DIMENSION C 1 SPRINKLER 1k Anal SPRINKLER CUP ASSEMBLY 1 JIr.1i 1/2"(12,7 mm).. THREADED - D ADJUSTMENT �1 - 41 ����� 1E1__ FACE o OF CEILING, RETAINING RING ,—/ MOUNTING z SURFACE j I - Alt FIGURE 4 r ---� t DISPOSABLE PROTECTIVE CAP N.\ — I I Arms during ceiling installation and/or -z_r -7-- r=� finish.You can also use the Protective T _~ Cap to locate the center of the clear- 3/16"to 11/16" MANUFACTURER DEFLECTOR COVER PLATE ance hole by gently pushing the ceiling (4,8 to 17,5 mm) PRESET GAP IN DROPPED RETAINER material up against the center point of REFERENCE 3/32"(2,4 mm) POSITION ASSEMBLY the Protective Cap. COVER PLATE COVER PLATE NOTICE -PROFILE DEPTH DIAMETER As long as the Protective Cap remains DIMENSION B DIMENSION A in place, the system is considered A:3-1/4 inches(82,6 mm) C:2-3/8 to 2-5/8 inches(60,3 to 66,7 mm) "Out of Service". B:3/16 inches(4,8 mm) D:1-3/4 to 2-1/4 inches(44,5 to 57,2 mm) Step 6.After the ceiling has been com- pleted with the 2-1/2 inch(63,5 mm)di- ameter clearance hole and in prepa- FIGURE2 ration for installing the Cover Plate/ SERIES CONCEALED SPRINKLER INSTALLATION DIMENSIONS Retainer Assembly, remove and dis- card the Protective Cap.Verify that the Deflector moves up and down freely. If the Sprinkler is damaged and the it 1, FRAME 1-.a-U-1.10.. Deflector does not move up and down ARM -------..........L(..„. /�; Don freely, replace theoentireiyrepairea /- �I not attempt to modify or a �b damaged sprinkler. SUPPORT _I1f , Step 7. When installing an Air and CUP ; Dust Seal, refer to Figure 5;otherwise, Plii :'� i I proceed to Step 8. To attach the Air ,1-" and Dust Seal, verify the angle of the _---- outside edge of the seal is oriented ac I cording toFigure 5. Start the edge of - - the Retainer in the grooved slot of the iiiimii , 7/8"(23 mm) 0 Air and Dust Seal and continue around SQUARE ---N....:_. the retainer until the entire Air and Dust Seal is engaged. -` Step 8. Screw on the Cover Plate/ ALIGN �� Retainer Assembly until the Retainer ARROWS WITH / i 1 \ (shown in Figure 2)or the Air and Dust FRAME ARMSf Seal (shown in Figure 5) contacts the 1 r ceiling. Do not continue to screw on ( 1 1.....:2 the Cover Plate/Retainer Assembly ACCEPTS \ ` ,—r�� so that it lifts a ceiling panel out of its 0 1/2"SOCKET \ normal position. If you cannot engage DRIVE the Cover Plate/Retainer Assembly FIGURE 3 with the Support Cup or you cannot SPRINKLER WRENCH engage the Cover Plate/Retainer As- RFIIsembly sufficiently to contact the ceil- ing, you must reposition the Sprinkler Fitting. TFP181 Page 4 of 4 Care and SUPPORT SPRINKLER FACE OF ORIENT Maintenance CUP CEILING �—SEAL BEVEL AS j�l�--- 'T SHOWN The TYCO Series RFII 5.6 K-fac- 'irii _ 1 COVER �� i tor, "Royal Flush II" Concealed Pen- ; PLATEdent Sprinklers must be maintained RETAINERand serviced in accordance with this � �� ASSEMBLYsection. � /:jr t Before closing a fire protection system main control valve for maintenance �l� AIR work on the fire protection system that /= ����� %• ��/ AND DUST it controls, obtainpermission to shut -=��._I'C'I SEAL - – � LIP OF COVER down the affected fire protection sys- RETAINER PLATE tem from the proper authorities and FIGURE 5 notify all personnel who may be affect- OPTIONAL AIR AND DUST SEAL FOR SERIES RFII(TY3551) ed by this action. Absence of the Cover Plate/Retainer If you must remove a sprinkler, do not Assembly can delay sprinkler opera- reinstall it or a replacement without re- tion Ordering in a fire situation. installing the Cover Plate/Retainer As- sembly. Procedure When properly installed, there is a y. Ifa Cover Plate/Retainer As- �/ nominal 3/32 inch (2,4 mm)air gap be- sembly becomes dislodged during Contact your local distributor for tween the lipof the Cover Plate and the service,replace it immediately. availability. When placing an order, ceiling,as shown in Figure 2. The owner is responsible for the in- indicate the full product name. This air gap is necessary for proper spection, testing, and maintenance of Sprinkler/Support their fire protection system and devic- p pport Cup Assembly operation of the sprinkler. If the ceil- es in compliance with this document, ing requires repainting after sprinkler p Specify:. , "Royal Series RFII (specifyndeSrin- installation, ensure that the new paint as well as with the applicable stan- K=5.6, Flush II" Pendent Sarin- installation, not seal offany the air gap. dards of the National Fire Protection klers (specify) temperature rating and Association(e.g., NFPA 25), in addition (specify)finish, P/N(specify). Do not pull the Cover Plate relative to to the standards of any other authori- the Enclosure.Separation may result. ties having jurisdiction.Contact the in- 155°F(68°C) 200°F(93°C) Sprinklers which are found to be leak stalling contractor or sprinkler manu- TY3531 51-792-1-155 51-792-1-200 ing or exhibiting visible signs of corro facturer regarding any questions. Tv3551 51-790-1-155 51-I90-1-200 sion must be replaced. Automatic sprinkler systems should be Separately Ordered Cover Plate/ Automatic sprinklers must never be inspected,tested,and maintained by a Retainer Assembly: utomaqualified Inspection Service in accor- painted, plated, coated, or other- dance with local requirements and/or Specify: (temperature rating from be- wise altered after leaving the factory. national code. low) Series RFII Concealed Cover Modified sprinklers must be replaced. Plate with(finish), P/N(specify). Sprinklers that have been exposed to 139°F(59°C)(a) 165°F(74°c)(b) corrosive products of combustion, but Grey White have not operated,should be replaced (RAL9002)....56-792-0-135 56-792-0-165 if they cannot be completely cleaned Brass 56-792-1-135 56-792-1-165 by wiping the sprinkler with a cloth or Pure White(c) by brushing it with a soft bristle brush. (RAL9010)....56-792-3-135 56-792-3-165 White Care must be exercised to avoid dam- Signal (RAL9003)003j....56-792-4-135 56-792-4-165 age to the sprinklers - before, during, Jet Black and after installation. Sprinklers dam- (RAL9005).... 56-792-6-135 59-792-6-165 aged by dropping, striking, wrench Brushed twist/slippage, or the like, must be re- Chrome 56-792-8-135 56-792-8-165 placed.Also,replace any sprinkler that Chrome 56-792-9-135 56-792-9-165 has a cracked bulb or that has lost Custom 56-792-X-135 56-792-X-165 liquid from its bulb. (Ref. Installation (a) For use with 155°F(68°C)sprinklers. Section.) (b) For use with 200°F(93°C)sprinklers. Exercise care to avoid damage to (c) Eastern Hemisphere sales only. sprinklers before, during, and after in- Sprinkler Wrench stallation.Replace sprinklers damaged Specify:RFII Sprinkler Wrench, by dropping, striking, wrench twisting, P/N 56-000-1-075. wrench slipping, or the like. Also, re- place any sprinkler that has a cracked Air and Dust Seal bulb or that has lost liquid from its Specify:Air and Dust Seal, bulb.(Refer to the Installation section.) p y' P/N 56-908-1-001. GLOBAL HEADQUARTERS 1 1400 Pennbrook Parkway,Lansdale,PA 19446 Telephone+1-215-362-0700 Copyright©2013 Tyco Fire Products,LP. All rights reserved. two TEFLON is trademark of The DuPont Corporation. tqcciWorldwide Fire Protection Contacts www.tyco-fire.com Products Series TY-FRB, 5.6 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General NOTICE The TYCO Series TY-FRB Sprinklers w" •• %1s Description described herein must be installed and maintained in compliance with this doc- The TYCO Series TY-FRB,5.6 K-factor, ument, as well as with the applicable ; Upright(TY313) and Pendent(TY323) standards of the National Fire Protec- • � ^, Sprinklers described in this data sheet tion Association,in addition to the stars- '11r' ; .64. I are quick response,standard coverage, dards of any other authorities having decorative 3 mm glass bulb-type spray jurisdiction.Failure to do so may impair sprinklers designed for use in light or the performance of these devices. ordinary hazard,commercial occupan- - ; The owner is responsible for maintain- ping cies such as banks, hotels,and shop- ping malls. ing their fire protection system and devices in proper operating condition. The recessed version of the Series TY- The installing contractor or sprinkler FRB Pendent Sprinkler,where applica- manufacturer should be contacted with ble, is intended for use in areas with a any questions. finished ceiling.This recessed pendent sprinkler uses one of the following: Sprinkler • A two-piece Style 15 Recessed p - - _, Escutcheon with recessed adjust- Identification ment up to 5/8 inch (15,9 mm)from ,�. , the flush pendent position. Number (SIN) • A two-piece Style 20 Recessed Escutcheon with recessed adjust- TY313 Upright 5.6K, 1/2"NPT , ment up to 1/2 inch (12,7 mm) from TY323 Pendent 5.6K, 1/2"NPT .. ° < the flush pendent position. ,>y The adjustment provided by the Technical Recessed Escutcheon reduces the Temperature Rating accuracy to which the fixed pipe drops Data 135°F(57°C) to the sprinklers must be cut. 155°F(68°C) Intermediate level versions of Series Approvals 175°F(79°C) TY-FRB Sprinklers are described in UL and C-UL Listed 200°F(93 oC) Technical Data Sheet TFP357. Sprin- FM, LPCB,and VdS Approved 286 F(141 C) kler guards and shields are described CE Certified Finishes in Technical Data Sheet TFP780. Sprinklers with Polyester Finish are UL Sprinkler: Refer to Table A and C-UL Listed as Corrosion-Resis- Recessed Escutcheon:White Coated, tant Sprinklers. Chrome Plated,or Brass Plated Maximum Working Pressure Physical Characteristics 175 psi(12.1 bar) Frame Bronze 250 psi(17.2 bar)* Button Brass/Copper *The maximum working pressure of 250 psi Sealing Assembly Stainless IMPORTANT (17.2 bar)only applies to the listing by Un- Steel w/TEFLON Always refer to Technical Data derwriters Laboratories,Inc.(UL). Bulb Glass Sheet TFP700 for the "INSTALLER Discharge Coefficient Compression Screw Bronze WARNING"that provides cautions K=5.6 GPM/psi112(80,6 LPM/barlI2) Deflector Bronze with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and installation can permanently dam- age a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 4 FEBRUARY 2014 TFP172 TFP172 Page 2 of 4 Components: *Temperature rating is ** Pipe thread connections per ISO 7-1 1 - Frame 4 - Bulb indicated on Deflector. can be provided on special request. 2 - Button 5 - Compression STYLE 15 or 20 3 - Sealing Screw ESCUTCHEON PLATE 1/2" 7/16"(11,1 mm) RECESSED Assembly 6 - Deflector* DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE-IN ESCUTCHEON 6* I 1 5 .�:i�rif=lr-V:\ zirr!T rTt ,-. - / 7/16" Y �R=_ (11,1 mm) '■Fc 4 A NOMINAL 2" 0 �� • MAKE-IN (50,8 mm) I 2 �. a 2c 1-3/8" -� 3 �. (50,8 mm) (34,9 mm) / WRENCH 1 / - FLATS 1/2"NPT** DEFLECTOR* 2-7/8"(73,0 mm)DIA. CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT FIGURE 1 SERIES TY-FRB UPRIGHT(TY313)AND PENDENT(TY323)SPRINKLERS 5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE L, Operation Installation The glass bulb contains a fluid which The TYCO Series TY-FRB,5.6 K-factor, WRENCH RECESS expands when exposed to heat.When Upright(TY313)and Pendent(TY323) (USE ONLY the rated temperature is reached, the Sprinklers must be installed in accor- ^ END"A") fluid expands sufficiently to shatter the dance with this section. glass bulb, allowing the sprinkler to General Instructions FIGURE 2 activate and water to flow. Do not install any bulb-type sprinkler if W-TYPE 6 the bulb is cracked or there is a loss SPRINKLER WRENCH Design of liquid from the bulb.With the sprin- kler held horizontally, a small air WRENCH bub- Criteria ble should be present. The diameter of the air bubble is approximately 1/16 RECESS The TYCO Series TY-FRB,5.6 K-factor, inch (1,6 mm)for the 135°F(57°C)and Upright(TY313)and Pendent(TY323) 3/32 inch(2,4 mm)for the 286°F(141°C) t �,� Sprinklers are intended for fire protec- temperature ratings. Fr tion systems designed in accordance with the standard installation rules rec- ognized by the applicable Listing or by Approval agency(such as, UL Listing min- imum to maximum torque of 7 to 14 Q4Iis based on the requirements of NFPAft.-lbs. (9,5 to 19,0 Nm). Higher levels 11b 13, and FM Approval is based on the of torque can distort the sprinkler Inlet requirements of FM's Loss Prevention with consequent leakage or impairment PUSH WRENCH Data Sheets).Only the Style 15 or Style of the sprinkler. IN TO ENSURE 20 Recessed Escutcheon is to be used Do not attempt to compensate for ENGAGEMENT for recessed pendent installations. insufficient adjustment in the Escutch- WITH SPRINKLER 1 WRENCHING AREA eon Plate by under-or over-tightening the sprinkler. Re-adjust the position of FIGURE 3 the sprinkler fitting to suit. W-TYPE 7 RECESSED SPRINKLER WRENCH Upright and Pendent Sprinklers The Series TY-FRB Upright and Pen- dent Sprinklers must be installed in accordance with the following instructions. Step 1.Install Pendent sprinklers in the pendent position. Install upright sprin- klers in the upright position. Step 2. With pipe-thread sealant applied to the pipe threads, hand- tighten the sprinkler into the sprinkler fitting. TFP172 Page 3 of 4 Step 3. Tighten the sprinkler into the 2-7/8' DIA. sprinkler fitting using only the W-Type - (73,0 mm) 6 Sprinkler Wrench(Figure 2).With ref- erence to Figure 1,apply the W-Type 6 2-1/4" DIA. Sprinkler Wrench to the wrench flats. FACE OF ~ (57,2 mm) — Torque sprinklers 7 to 14 ft.-lbs.(9,5 to SPRINKLER 19,0 Nm). FITTING 5/8"(15,9 mm) Recessed Pendent Sprinklers ir \ - FLUSH The Series TY-FRB Recessed Pendent 3/8±5/16" =1 I I Sprinklers must be installed in accor- (9,5±7,9 mm) Z/Ul i i% % + } dance with the following instructions. } / Step A.After installing the Style 15 or MOUNTING ! , 1/8 Style 20 Mounting Plate over the sprin- SURFACE (3,2 mm) kler threads, and with pipe-thread sealant applied to the pipe threads, I CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) hand-tighten the sprinkler into the TY-FRB PLATE 3/4" sprinkler fitting. (19,1 mm) Step B.Tighten the sprinkler into the FIGURE 4 Step B. fitting using onln the W-Type SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323) 7 Recessed Sprinkler Wrench (Figure WITH TWO PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15 3).With reference to Figure 1,apply the RECESSED ESCUTCHEON W-Type 7 Recessed Sprinkler Wrench to the sprinkler wrench flats. Torque 2-7/8" DIA. sprinklers 7 to 14 ft.-lbs. (9,5 to 19,0 (73,0 mm) Nm). FACE OF Step C.After ceiling installation and fin- SPRINKLER 2-1/4" DIA. fishing,slide on the Style 15 or Style 20 FITTING (57,2 mm) Closure over the Series TY-FRB Sprin- 5/16±1/4" kler and push the Closure over the (7,9±6,4 mm) 1/2"(12,7 mm) Mounting Plate until its flange comes in + - FLUSH contact with the ceiling. 1 g M ' t Care and fI MOUNTING �l� 1/8" Maintenance SURFACE (3,2 mm) The TYCO Series TY-FRB,5.6 K-factor, I Upright(TY313)and Pendent(TY323) CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) Sprinklers must be maintained and ser- TY-FRB PLATE 7/8"(22,2 mm) viced in accordance with this section. FIGURE 5 Before closing a fire protection system SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323) main control valve for maintenance WITH TWO PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 work on the fire protection system RECESSED ESCUTCHEON that it controls, obtain permission to shut down the affected fire protection Modified sprinklers must be replaced. standards of any other authorities hav- systems from the proper authorities Sprinklers that have been exposed to ing jurisdiction. Contact the installing and notify all personnel who may be corrosive products of combustion,but contractor or sprinkler manufacturer affected by this action. have not operated,should be replaced regarding any questions. Absence of the outer piece of an if they cannot be completely cleaned Automatic sprinkler systems are rec- escutcheon, which is used to cover by wiping the sprinkler with a cloth or ommended to be inspected, tested, a clearance hole, can delay sprinkler by brushing it with a soft bristle brush. and maintained by a qualified Inspec- operation in a fire situation. Care must be exercised to avoid dam- tion Service in accordance with local The owner must assure that the sprin- age to the sprinklers before,during,and requirements and/or national codes. klers are not used for hanging any after installation. Sprinklers damaged objects and that the sprinklers are only by dropping, striking, wrench twist/ cleaned by means of gently dusting slippage,or the like,must be replaced. with a feather duster;otherwise, non- Also, replace any sprinkler that has a operation in the event of a fire or inad cracked bulb or that has lost liquid from vertent operation may result. its bulb.(Ref. Installation Section.) Sprinklers which are found to be leak- The owner is responsible for the ing or exhibiting visible signs of corro- inspection,testing,and maintenance of sion must be replaced. their fire protection system and devices in compliance with this document, as Automatic sprinklers must never be well as with the applicable standards painted, plated, coated, or other- of the National Fire Protection Associa- wise altered after leaving the factory. tion (e.g., NFPA 25), in addition to the TFP172 Page 4 of 4 P/N* 77 - XXX - X - XXX � I SPRINKLER TEMPERATURE FINISH RATINGS SIN 1 NATURAL BRASS 135 135°F(57°C) 370 5.6K UPRIGHT(1/2"NPT) TY313 3 PURE WHITE(RAL9010)** 155 155°F(68°C) • ( ) 371 5.6K PENDENT(1/2"NPT) TY323 4 SIGNAL WHITE(RAL9003) 175 175°F(79°C) POLYESTER Use suffix"I"for ISO 7-1 connection; 9 CHROME PLATED 200200°F 93° • for example,77-370-4-175-I ( C) **Eastern Hemisphere sales only 286 286°F(141°C) TABLE A SERIES TY-FRB UPRIGHT AND PENDENT SPRINKLERS PART NUMBER SELECTION Limited Ordering Warranty Procedure For warranty terms and conditions,visit Contact your local distributor for avail- www.tyco-fire.com. ability.When placing an order,indicate the full product name and Part Num- ber(P/N). Sprinkler Assemblies with NPT Thread Connections Specify:Series TY-FRB Upright or Pen- dent(specify)Sprinkler, SIN (specify), K=5.6,Quick Response,(specify)tem- perature rating, (specify) finish, P/N (specify,refer to Table A). Recessed Escutcheon Specify:Style 15 Recessed Escutcheon with(specify*)finish, P/N (specify') Specify: Style 20 Recessed Escutch- eon with(specify*)finish,P/N(specify*) *Refer to Technical Data Sheet TFP770 Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387 Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001 GLOBAL HEADQUARTERS 1 1400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright©2014 Tyco Fire Products,LP. All rights reserved. NCO TEFLON is trademark of The DuPont Corporation. 'f Fire Protection Products Eddythread 40 A Lightweight Schedule 40 Replacement Pipe That Has a Corrosion Resistance Ratio of 1.0 Bull Moose Tube Company has been making pipe for a long time and is recognized as a producer of quality pipe products. Eddythread 40 is designed with the same thoroughness as our other fine pipe products and now our customers have an option to buy a carefully designed replacement for Schedule 40 that: • Has a Corrosion Resistance Ratio of 1.0 • Has a Pressure Rating of 300 psi • Is Lighter Weight Than Schedule 40 • Is Approved by Factory Mutual and Listed by Underwriters Laboratories • Is Produced in Accordance to ASTM A-135 and A-795 • Can be Used With Standard Schedule 40 Threaded Fittings, Couplings and Valves • Is Produced From Steel With Excellent Properties of Strength and Threadability • Can be Used in Wet, Dry, Preaction, and Deluge Type Sprinkler Systems* • Offers Lower Freight Costs EDDYTHREAD 40 SPECIFICATIONS NOMINAL PIPE G SIZE(in) � ! �I I.D. (in) BUNDLE SIZE, 1 1.461 1.083 70 1 1/4 2.070 1.418 51 1 1/2 2.547 1.654 44 2 3.308 2.123 30 CORROSION RESISTANCE RATIOS NOMINAL PIPE SIZE r SCHEDULE 40 ,. a EDDYTHREAD 40 1 1.00 1.00 1 1/4 1.00 1.00 1 1/2 ` 1.00 1.00 2 1.00 1.00 *Eddythread 40 can be hot dipped galvanized to meet FM's requirement for dry systems (N8.6 1819 Clarkson Road For additional information, C uL us A Chesterfield,MO 63017 contact your salesperson today at BULL MOOSE TUBE COMPANY (800)325-4467 (800)325-4467 or(636)537-2600 L TED FAX:(636)537-2645 in the USA,or from Canada www.bullmoosetube.com call(800)882-4666 A(CAPf1I O)company e-mail:sales abullmoosetube.com APPROVED All information contained herein is accurate as known at the time of publication. But Moose Tube reserves the right to change product specifications without notice and without incurring obligation. 8/08 Ductile Iron Fittings- Class 300 UL/FM c01us APPROVED A Fig. 35E 3-90°Elbow LISTED '-� Size ". - a>ti=A -' ';,, Packings ` Weight _ Part Number ,: M I� .41 in ire, Inner - aster biki.. . ___+� 1/2 35E 3004 1.13 100 200 0.2 I__ 3/43P.,%.1 6 1.31 , 8 1 fi<143 0.3.4 IA 1 35E 3010 1.50 40 80 0.5 na1-14 1 3 ":1 1.75 25 1 '" #8 1-1/2 35E 3014 1.94 18 36 1.1 2 ....-L121--35E300 �.25 ;fir t t. ;- 4715;r4!4:441.8 .,4......2-1/2 35E 3024 2.70 4 8 3.2 Fig. 35RE3-90°Reducing Elbow B Size Part Number , ; . <--� fi X71 B "Cking Weight _ in „ �' Ki n "Inner Master ; Il 3/4 x 1/2 35RE3006004 1.20 1.22 80 160 0.3 I� l; *+ ,,., 35 010i"i ' t:1, ,ma A. 1'1.86 -1 :'70 _' '140 ' Q 4 1111 1 x 3/4 35RE3010006 1.38 1.45 50 100 0.4 �i 1-1/4x€1/ "'35, .s12.a+ 8 1.34 ''''''7 35 0 1116 1-1/4 x 3/4 35RE3012006 1.45 1.63 35 70 0.6 x 1 .W "` 35RE301 f110 b- "'1684,V . 1 i. v i' 6q4.4-- ,i!}7 .. 1-1/2 x 1/2 35RE3014004 1.52 1.75 30 60 0.6 ,3/4 ''''''',''t+.'''..i.,10.,11.11' _' 2 f.„.1-71„,&,,,, T.. 'Al' 1i ,,,P.7 1-1/2 x 1 35RE3014010 1.65 1.80 20 40 0.8 T1/2x 1-1/4 -301 .# 2 '1,...§?.., ,,i. =i,--71.8e,„,,, ,, 36 'w'1.0 2 x 1/2 35RE3020004 1.60 1.97 18 36 1.0 2 x' k -; 15RE 2Q006 _ MI6!'6e `s ' 8t7i -",7:'1;''''''10,:- .. , .,„ 2 x 1 35RE3020010 1.73 2.02 16 32 1.2 2 x 1-114 : '33 ,.8"8.1,;48„q1 'I.•m 2 1 D 2 x 1-1/2 35RE3020014 2.02 2.16 10 20 1.5 LI '4,1/2 x`1 r, 0,,,..;e 14 ' 2.16 .s 261 4.11' .Is,... 2.2 8* 2-1/2 x 2 35RE3024020 2.39 2.60 6 12 2.5 ` Fig. 35F 3-45°Elbow .ize -Pa Number �A Iackmg Weight inner Ma ter lb, 1/2 35F 3004 0.88 150 300 0.2 1 35F 3006'`". .; �4' ,"' rts tit 1 35F 3010 1.13 40 80 0.5 11 1-1/4 304 1 -9 5 "' ,.. ,Mid IA � � 50 1. 1 1/2 35F 3014 1.44 20 40 1.0 i M ;a20 1.69 �, 21x ;'" '" ..N � '.�.. 2 Fs<T...«3 3, ,psi . ,� 20 1.6 ,��r. 2-1/2 35F 3024 1.95 4 8 2.7 Fig. 35T 3- Tee Size !'A 'Packing,t!.Y. Weight in 'dart Number .bl ...In' -- in inner.. aster a ��� � 35T 3004 1 13 80 160 0.3 =�ill "3/4.., 3513006 ,}1.3i , , :, 60 0.5 ,;, l �y 1 3513010 1.50 25 50 0.7 ,�. 1-1/4012 '' 1., 4,f1,,,, d ; 20 a `` 4'`' 'i.1 `' 4 ll A 'I A 1-1/2 35T 3014 1.94 10 20 1.5 4,18;2' 4-435T390 2.25 6 ,wS4i'' 12 •,,,,:„.g.„-.41V 2-1/2 35T 3024 2.70 4 8 4.3 111 SMITH-COOPER INTERNATIONAL' • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • wwwsmithcooper.com Ductile Iron Fittings- Class 300 UL/FM c � us APPROVED A Fig. 35CP3 -Straight Coupling with Ribs LISTED Size 4 -A , Paeking - Weight 'Partwtcumber --, g , in ti. ,in , Inner: }"Master`£ lb °" __ 1/2 35CP3004 1.38 200 400 0.1 ,. 3/4 =gym. ,n• ip -f-e3 ;- ,)': 100 z t''' ,,9':i. 1 35CP3010 1.75 60 120 0.4 1-1/2 35CP3014 2.19 25 50 0.7 :1.7'.4.,..4 ii7s "35G"''vO m 2:6._, 1 iiiU it: .mak. Kisfir.. 2-1/2 350P3024 3.00 9 18 2.2 Fig. 35RC3 -Hex Reducing Coupling Bi Sine " Par Number � . innerPaekhl! ,. ,Weight ® Master�" 0. A 1 x 1/2 35RC3010004 1.69 80 160 0.3 1 x3/435 0100E ,_. �' 60 ,.. .. ' : .4 ,, =i�� 1-1/4 x 3/4 35RC3012006 2.06 4080 0.6 4 1 (nbtex) 35EAC3020(1 ..81, ' 0¢ _ 40 =, ri Fig. 35HB3 -Hex Bushing Illi , 7Size art Number 4 V Pai kh A� 7: We B „ n . , ,�rt.. - . .F i , ` ` c nn:r s,„aster ;�� I- , , ; 1 x 1/2 35H133010004 1.06 180 360 0.2 it,.1 x' . 0i 1,, x i' 6 :0 0 Al 1:1 11 x x '� ; A 1-1/4x1 35HB3012010 1.19 90 180 0.2 i • 1-1/ • 34-08'5614.0/47' .''f..044.' w a 5 It - : 0 .' . 4:.4 1-1/2x1 1/4 35HB3014012 1.25 75 150 0.3 an.:7 2 xA' M_,m 200:1., .. , � 8 �; , A tib -...i.' .�.; 2 x 1 1/4 35HB3020012 1.38 40 80 0.6 . '; ,ix 1-1/2 A, 5HB30'i'94 A 1.3>3 '„ :,.. . -_; ,IA'`" 0..07, '. Fig. 35SP3 -Square Head Plug maize A' Pac Weigh , . x h �r Pa Nunn er ,. in �- ; , i m ,,:,,Inner' Master ,�4.'.lb' 1/2 35SP3004 0.94 . .�: 600 1200 0.07 A '' F=: q">..., 5SP300 , ..1.•12 «` -14,-'50.,,1: ,4 :70 ` 0.1 � i 1 35SP3010 1.25 200 400 0.1 <,. 44 35SP3012 1.37 .`,,• i09. ,.TyP.r k 0.3 1-1/2 35SP3014 1.44 80 160 0.4 2 15:' '35SP3020.; ` 150 ' 45 . xs 90 ATO 9.6 4 Fig. 35U 3-Union with Brass Seat A Size - Part Number A Packing Weight u �, in ,.- , �: in -,...e._ Inr ;r ;44,. Master .. ib • 1 35U 3010 2.19 20 40 1.0 _ I "1-1/4,z u 351 -012 . ,°. g50 ,, ` , �. '441.2 1 1-1/2 35U 3014 2.62 10 20 1.7 'Im11W2: .:. ,.t,'35U 3020 '3.12` r.. 12 2.4 113 S\IITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcoopcccom �IP L,P1 g� CVT OD ©�. FM VdS LPCB y 4- , Cunto SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS STYLE 922 The Style 922 Outlet-T provides a convenient method of incorporating'h,3/4,and 1715,20 and 25mm outlets for directly connecting sprinklers,drop nipples,sprigs,gauges,drains and other outlet products.Available for 11/4 through 76.1 mm/32 to 76.1 mm piping systems,Style 922 outlets are UL/ULC Listed,LPCB and FM Approved for branch connections and VdS Approved for direct sprinkler connection only on wet and dry systems. The locating collar engages into the hole prepared in the pipe.When tightened,the assembly compresses the gasket onto the OD of the pipe.The Style 922 Outlet-T is UL/FM rated up to 300 psi/2068kPa and VdS rated up to 16 bar at the ambient temperatures typical for fire protection systems. Style 922 is suitable for use on standard,lightwall,Schedule 5 and other specialty pipes.* Contact Victaulic for other optional coatings. *Consult Section 10.01 for specific listings/approvals. MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A-536,grade 65-45-12.Ductile iron conforming to ASTM A-395,grade 65-45-15,is available upon special request. Gasket: • Grade"E"EPDM-Type A (Violet color code). FireLock products have been Listed by Underwriters Laboratories Inc.and Approved by Factory Mutual Research for wet and dry(oil free air)sprinkler services up to the rated working pressure using the Grade"E"Type A Gasket System. Bolts/Nuts:Heat-treated plated carbon steel,trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. Housing Coating: • Orange enamel(North America, Latin America,Asia Pacific) • Red enamel(Europe) JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date Approved Date www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. �IotaUI1C` REV G 10.52_1 IPS CARBON STEEL PIPE - HOLE CUT PRODUCTS 10.52 oc r STYLE 922 DIMENSIONS Nominal Size Hole Approx. inches/mm Diameter Dimension orches/mill meters Weight Each m h: � -{fix lbsikg 111111 ��� FRIfes„ v 1. 1 Ya %z 1 3/16 1.30 1.83 1.10 3.87 2.56 1.0 ,, to r W' 32 X 15 30.2 33.0 46.5 27.9 98.3. 65.0 0.45 I 4 13/16 1.28 1.83 1.10 3.87 2.56 1.1 u 20 30.2 32.5 46.5 27.9 98.3 65.0 0.50 1 1 3/16 1.52 2.18 ; 1.10 3.87 2.56 ! 1.2 , W 1 (VI 25 30.2 38.6 55.4 27.9 98.3 65.0 0.54 11/21 1 3/16 1.42 1.95 1.22 4.08 2.56 1.2 40 X 15 i 30.2 36.1 49.5 31.0 103.6 65.0 ' 0.54 Ya 1 3/16 1.40 1.95 1.22 4.08 2.56 1.2 20 30.2 35.6 49.5 31.0 103.6 65.0 ? 0.54 1 13/16 1.64 2.30 - 1.22 4.08 2.56 1.3 25 30.2 41.7 58.4 31.0 103.6 65.0 ' 0.59 2 X Y2 13/16 1.66 2.19 1.46 4.60 2.56 1.3 50 15 30.2 42.2 55.6 37.1 116.8 65.0 0.59 3/a 13/16 1.64 2.19 1.46 4.60 2.56 ' 1.4 20._. ! 30.2 41.7 55.6 37.1 116.8 65.0 0.64 1 13/16 1.88 2.54 1.46 4.60 2.56 1.5 25 30.2 47.8 64.5 37.1 116.8 65.0 0.68 2Y '1 13/16 1.91 2.44 ! 1.71 5.40 2.56 1.6 65 X 15 30.2 48.5 62.0 43.4 137.2 65.01. 0.73 3/a 13/16 1.89 2.44 1.71 5.40 2.56 ' 1.6 20 30.2 48.0 62.0 43.4 137.2 65.0 0.73 _.._ 1 1 3/16 2.13 2.79 1.71 5.40 2.56 I 1 6 25 30.2 54.1 70.9 43.4 137.2 65.0 ` 0.73 76.1 mm X Y2 1 3/16 1.91 2.44 1.71 5.50 2.56 I 1.6 15 30.2 48.5 62.0 43.4 139.7 65.0 0.73 3/ 1 3/16 1.89 2.44 1.71 5.50 2.56 1.6 20 30.2 48.0 62.0 43.4 139.7 65.0 0.73 ---- 1 13/16 2.13 2.79 1.71 5.50 ,.. 2.56 1.7 25 30.2 54.1 70.9 43.4 139.7 65.0 0.80 t Victaulic female threaded products are designed to accommodate standard NPT or BSPT(optional) male pipe threads only.Use of male threaded products with special features,such as probes,dry pen- dent sprinklers,etc.,should be verified as suitable for use with this Victaulic product.Failure to verify suitability in advance may result in assembly problems or leakage. *Center of run to engaged pipe end for NPT threads(dimensions are approximate). www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. jctaiull Ca 10.52 2 REV G IPS CARBON STEEL PIPE- HOLE CUT PRODUCTS 10.52 Firelock'') Outiet-T STYLE 922 PERFORMANCE Equivalent Length of 1 inch Schedule 40 Steel Plpe(per UL Run Size x Outlet Size 213,Section 16)(C120),= FT Inches/met Feet/meters 1 Va 1 8.5 • X 32 25 2.6 1½ x 1 8.5 40 25 2.6 2 X 1 8.5 50 25 2.6 21/2 X 1 8.5 65 25 2.6 1 8.5 76.1 mm X 25 2.6 *Hazen-Williams coefficient of friction is 120 www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.(0)20 /Ctaliie 09 VICTAULIC COMPANY.ALL RIGHTS RESERVED. ----- REVS 10523 STEEL, d.R 4S4... 0.5 • it L ` - Outlet-T STYLE 922 INSTALLATION Reference should always be made to the 1-100 Victaulic Field Installation Handbook for the product you are installing.Handbooks are included with each shipment of Victaulic products for complete installation and assembly data,and are available in PDF format on our website at www.victaulic.com. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. --— --------- _ ___ --- ---_-- -----------_._- NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. • For complete contact information,visit www.victaulic.com 10.52 3355 REV G UPDATED 12/2009 Ictaul.c. VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. ._.__.,..,_.._....... 10,52 Pipe Hangers Fig.200- "Trimline"Adjustable Band Hanger (B-Line Fig.B317ONF) eToItco- Fig.200F- "Trimline"Adjustable Band Hanger with Felt Lining (B-Line Fig.B317ONFF) VL gs Fig.200C- "Trimline"Adjustable Band Hanger with Plastic Coated (B-Line Fig.B317ONFC) lin Fig.200S - "Trimline"Adjustable Band Hanger with Non-Captured Nut 41> Size Range: Fig.200 - 1/2" (15mm)thru 8" (200mm)pipe Material: Steel, Pre-Galvanized to G90 specifications s Function: For fire sprinkler and other general piping purposes. Knurled u, swivel nut design permits hanger adjustment after installation. Features: ;_\ • (1/2" (15mm)thru 2" (5omm)) Flared edges ease installation for all pipe �_.v` types and protect CPVC plastic pipe from abrasion. Captured design +_ // keeps adjusting nut from separating with hanger. Hanger is easily a B , I� installed around pipe. ' �I / V For hanger with non-captured nut order Fig. 200S. A 'I , , • (21/2" (65mm)thru 8" (2oomm)) Spring tension on nut holds it securely in V�,_ hanger before installation.Adjusting nut is easily removed. Approvals: Underwriters Laboratories listed (1/2" (15mm)thru 8" (200mm)) in the USA(UL)and Canada(cUL)for steel and CPVC plastic pipe and Fig.2oo 1/s.200s/° Factory Mutual Engineering Approved (FM) (3/4" (20mm)thru 8" (200mm)). Fig.2001to200-2 Fig.200-21/2 to 200-8 Conforms to Federal Specifications\MN-H-171 E&A-A-1192A,Type 10 and Manufacturers Standardization Society ANSI/MSS SP-69&SP-58, Type 10. Maximum Temperature: 650°F(343°C) _ '' i , Finish: Pre-Galvanized. Stainless Steel , materials will be supplied with (2) hex nuts in place of a knurl nut. t Order By: Figure number and pipe size Designed to meet or exceed requirements of , n°'� FM DS 2-0. Fig.200 Fig.200C Fig.200F Pipe Size Rod Size A B Approx.Wt/100 Part No. in. (mm) in. (mm) in. (mm) lbs. (kg) 200-1/2 1/2" (151 3/8"-16 31/8" (79.4) 25/8" (66.7) 11 15.01 , ,, 200-3/4 3/4" (20) 3/6"-16 31/8" (79.4) 21/2" (63.51 11 (5.0) : \. 200-1 1" 125) 3/8"-16 33/a" (85.71 25/8" (66.7) 12 (5.51 200-11/4 11/4" (32) 3/a"-16 33/4" (94.0) 27/8" (73.0) 13 (5.9) 200-11/2 11/2" (40) 3/8"-16 37/8" (98.4) 27/8° (73.0) 14 (6.4) f .. .,4- 200-2 2" (50) 3/a"-16 41/2" (114.3) 3" (76.3) 15 (6.9) 200-21/2 21/2" (65) 3/8"-16 55/8" (142.9) 41/8° 1104.7) 27 (123) 200-3 3" (75) 3/a"-16 57/a" (149.1) 4" 1101.61 29 (13.3) Fig.200S 200-31/2 31/2" 190) 3/8"-16 73/8" (187.3) 51/4 (133.3) 34 (15.6) 200-4 4" (100) 3/8"-16 73/a" (187.3) 5" 1127.0) 35 (16.01 200-5 5" (125) 1/2"-13 91/8" (231.8) 61/4" (158.7) 66 (30.2) 200-6 6" (150) 1/2°-13 101/8" (257.2) 63/4" (171.4) 73 (33.4) 200-8 8" (200) 1/2"-13 131/8" (333.4) 83/4" (222.2) 136 (62.3) All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. Fire Protection Solutions B-Line 21 by E`:T•M Threaded Accessories B3205 -Threaded Rod (right-hand threads - both ends) (mica Fig.103) ,----'r'',. B3205L-Threaded Rod (right& left hand threads) / TL Size Range: 3/3"-16 thru 3"-4 rod Specify Lengthll��l�1 Material: Steel ,,,\ Function: Recommended for use as a hanger support in hanger assemblies. T� _ 1 Rod is threaded on both ends with right hand threads of the length shown.Also available with left and right hand threads-specify Fig.B3205L when ordering. Thread Size Maximum Temperature: 750°F(399°C) . Finish: Plain.Contact B-Line for alternative finishes and materials. Order By: Part number, rod size, length and finish Standard Design Load Thread Size Thread Length TL 650°F(343°C) 750°F(399°C) Part No. A in. (mm) Lbs. (kN) Lbs. (kN) B3205-3/ix'L' 3/8"-16 21/2" (63.5) 730 (3.25) 572 (2.54) B3205-1:X"L' 1/2"-13 21/2" (63.5) 1350 (6.00) 1057 (4.70) B3205 „8 x1L' 5/8"-11 21/2" (63.5) 2160 (9.61) 1692 (7.52) 03205-3/4 x'L' 314"-10 3" (76.2) 3230 (14.37) 2530 (11.25) i--7 8X'L' Y 7/8"-9 31/2" (88.9) 4480 (19.93) 3508 (15.60) 205-1;x'L' 1 1"-8 4" (101.6) 5900 (26.24) ` 4620 (20.55) i,- '' ' `' 11/8"-7 41/2" (114.3) 7450 (33.14) 5830 (25.93) ' 3205-11/4 x1L' 11/4"-7 5"' (127.0) 9500 (42.25) 7440 (33.09) B3205-1/2 X'L' 11/2"-6 6" (152.4) 13800 (61.38) 10807 (48.07) B3205-3/41x'4' r" 13/4"-5'' MI (177.8) 18600 (82.73) 14566 (64.79) ' x'L ' 2"-41/2 8" (203.2) 24600 (109.42) 19625 (87.29) 83205- 1/4: ,-,,,,. , ' 21/4%41/2 9" (228.6) 32300 (143.67) 25295 (112.51) B320521/2 x'4' 21/2"-4 10 (254.0) 39800 (177.03) 31169 (138.64) ,B3205-23/4* 23/4"-4 ®=111 49400 (219.73) 30687 (172.08) B3205-3 x'L -r 3"-4 12' (304.8) 60100 (267.32) 47066 (209.35) ATR - All Threaded Rod 120" (3.05m) Lengths (TOLCO Fig.100) Fig. 99 -All Threaded Rod Cut To Length x� Size Range: 3/8"-16 thru 11/2"-6 rod in 120"(3.05m)lengths or cut to length �\�'111���1111111�1111111�����1 Material: Steel7�1-lo v a Maximum Temperature: 750°F(399°C) v o 31 0 Finish: Plain.Contact B-Line for alternative finishes and materials. .. i v Order By: Part number, rod diameter and finish a Part No.-Size x Length Threads Recommended Load Approx.Wt./100 Ft. AIR Fig.99 Per Inch Lbs. (kN) Lbs. (kg) ATR. " 1(20'"' ' 99-1/4"-x length 20 240 (1.07) 12 (5.44) ATR 3/e"x 120 9973/e"x length 16 730 (3.24) 29 (13.15) ATR 1/2"x 120 99-1/2"x length 13 1350 (6.00) 53 (24.04) Al' 6/e"x 120 ' /8"X length; 11 2160 (9.60) 89 (40.37) ATR 5/4",, X20 99-3/4"x length, 10 3230 (14.37) 123 (55.79) ATR ye.x 120 99-7/8"x length 9 4480 (19.93) 170 (77.11) ATR,1"x141„4 : 99-1"x length 8 5900 (26.24) 225 (102.06) All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. ■ Pipe Hangers&Supports 236 Revised 4/28/2014 B Line by E:T•N SAMMY X-PRESS® SAMMYS` Sammy X Press° •,.k.J,,. - j Product Features 4 ..? , ( •The Sammy X-Press expands to provide •Installs in seconds,saving time& i (XP) direct vertical attachment in: installation costs. i.x'.:;;,=`Patent No. s -Metal Deck(22-16 gauge) 6,935,821 ;_y• } -Z-Purlin(18-16 gauge) •Use in applications where access j to the back of the installed fastener is •The SammyX-Press Swivel allows you prohibited.ie.metal roof deck,tubular to hang plumb in extreme roof pitches: steel,or vapor barrier fabric. (SWXP) 89°in Z-Purlin C 45°in metal deck for 12/12 pitch •Less jobsite material needed. Patent Pending • for •The SammyX Press Sidewinder expands •No retaining nut required. to provide horizontal attachment in: (SXP) gXtr� Q -16 ga-3/16"steel-purlin,tubular •Provides design flexibility. °r j steel. Patent Pending variant roof pitches Rod Part Ultimate UL Test West Min Max Box Case Approvals Size Number Description Pullout(lbs) Load abs) Load Abs) Thick Thick Qty Qty ' ° 4n VERTICAL MOUNT 11 1/4" 8181922 XP 200 X-Press 200 1146(22 ga) 185(Luminaire) 250(Luminaire) 02T .056" 125° 25 125 Metal Deck • • x. • .;,,...;, : .t if. • •'.f.,185.. pe 94ti Per.. ,�• 3t8°•' ^81ea�{t[�(�� • Xt?20 itt tt46(22 ga) ft_ • : +1 ( per} .027" 025' 25 •125 Metal Deck tiq� ;:;' urnttr: 1475` r" eatijNjN��.%$,,. TM" '« 83(conOtbCebie) '''' 1500(4"Pipe) .060° I. 3/8" 8153922 XP 35 X-Press 35 1783(16 ga) 85(Luminaire) 940 (2'Pipe) 105" 125" 25 125 Pullin 250(Luminaire) 1475(4"Pipe) .027" 416(Conduit&Cable) .056' .,. i_.,..„017Prye} .4 x t'..:.: : +ry k`;"": .' .. f06t(22gaVerBcary 14eNcat(Lgmiriak? :' • • • • t" �%ni 218"•' 8294922 SXP 20 SwivetX-Preis 20 829(45"Off Vertical) 800 e tLleninaire)'.r 635(2"Pipe 02 125 ,x 125 :f etal Dedt ' 283w1C(ConduR6C�le) s r. s . • •... .:rn 233�(� (Conduit&Cable) 1500 14"Pipe) 1675(16 ga Vertical) 250 vertical(Luminaire) • Q.Q 3/8" 8295922 SXP 35 Swivel X-Press 35 1558(89°08 Vertical) 80 @ 90°(Luminaire) 635(2'Pipe) .060" .125" 25 125 Purlin 500 vertical(Conduit&Cable) 333 @ 89°(Conduit&Cable) *:114..:,;`• .F .f x. ._ ;• : • :_ -.t- '"•r:f• Metal Deck :'z } '477-* s .>%.4'. Pre-Pojir Structural Concrete@ 3000 psi ; '. 25 125 '.(P, 6`r — •N8• t `-' �kQ 'Sam "Pru '20` 1146(22 ga) -:. :• 85.0(21471:`: •""`' x .::,; r ' : PosEPour Range II L CF(bsMt1 Metal Deck:<j • 4 W (Post-Pour) i • HORIZONTAL MOUNT 1250(3'/:'Pipe) • 3/8" 8293957 SWXP35 Sidewinder X-Press 35 1798(16ga) 80(Luminaire) .060° .125° 25 125 Purlin 416(Conduit&Cable) Pre-Pour Structural Concrete @ 3000 psi Post-Pour Range II LWC•S 35 PCF(lbs!ft) :: .r.'• : ...r1.--r1.— —Fir— 0 1[ • Sammy X Press It° INSTALLATION TOOL f- IP UXPIT y .; • ;�,.... #c +��, rY ; . 4 •rt:% gc. - hY • ••. 0. b '' . t�: -b • • �� `..`fir: �' x .N Patent Pending a•r r. ° • ,, Part Number Model Description Each Qty • s• 8194910 UXPrT' Universal X-Press it Tool 1 xk. .'' ". 8195910 RXPIT Retro Socket for 8151910 1 815291(} • PDB 25/64"Drill Bit f To watch a video demonstration of the SammyX-Press,visit http://www.sammysuperscrew.com/sammyxpress.htm 'Tool Includes:Sleeve,Bit Receiver,Hex Wrench,and 25/64"Drill Bit. For the most up to date information visit www.sammysuperscrew corn 8 ( k?f 40"-- ,"/ /a�