Plans Centurion Fire Protection, LLC 051706-Orthopedics NW Page 1 Date 5-14-17 HYDRAULIC CALCULATIONS for Project name: ORTHOPEDICS NW Location: 15755 SW SEQUOIA PKWAY#200 PORTLAND, OR 97224 Drawing no: SP-100.00 Date: 5-14-17 Design Remote area number: 1 Remote area location: GROUND FLOOR Occupancy classification: LIGHT HAZARD Density: .10-Gpm/SqFt Area of application: 946-SqFt Coverage per sprinkler: 144 -SgFt Type of sprinklers calculated: V2708, 1/2" 5.6 K-FACTOR No. of sprinklers calculated: 12 In-rack demand: N/A-GPM Hose streams: 100-GPM Total water required(including hose streams): 296.30-GPM Type of system: WET @ 50.42- Psi Volume of dry or preaction system: N/A-Gal Water supply information Date: Location: Source: Name of contractor: CENTURION FIRE PROTECTION LLC Address: PO BOX 1705 OREGAN CITY, OR 97045 Phone number: 503-894-0563 Name of designer: Authority having jurisdiction: Notes:(Include peaking information or gridded systems here.) 6 -''''.,:**°.\\,,,, -..„ r rrrr, rr r ; . - 4 ; a iirPM V Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Water Supply Curve C Centurion Fire Protection, LLC 051706-Orthopedics NW Page 2 Date 5-14-17 City Water Supply: Cl -Static Pressure 103 Demand: C2-Residual Pressure: 100 D1 -Elevation 5.305 C2-Residual Flow : 2564 D2-System Flow : 196.307 D2-System Pressure : 49.898 Hose (Demand) : 100 D3-System Demand :296.307 Safety Margin : 53.047 150 140 130 p 120 R 110 C1 E 100 C2 S 90 ° S 80 U 70 R 60 D2 E 50 40 Qa 30 20 10 300 600 900 1200. . , . . . .1500 . . .1800. . . . . I . . . . . . . . 2100 2400 2700 FLOW N^ 1.85) Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Fittings Used Summary Centurion Fire Protection, LLC 051706-Orthopedics NW Page 3 Fitting Legend Date 5-14-17 Abbrev. Name 1/2 'A 1 11/4 1% 2 2'A 3 3% 4 5 6 8 10 12 14 16 18 20 24 E NFPA 13 90'Standard Elbow 1 2 2 G NFPA 13 Gate Valve 0 0 0 3 4 51 61 71 8 10 12 14 8 22 27 35 40 45 50 13 T NFPA 13 90'Flow thru Tee 0 0 1 1 1 1 2 2 3 461 Vcfd 'Nin 13 90 A to -60hr in Tee 0 4 53 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 11 13 Zff Febco 876V 0 0 0 0 0 0 91 101 121 Fitting generates a Fixed Loss Based on Flow 0 0 0 0 0 0 0 Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with*. The fittings marked with a *show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a *will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Pressure / Flow Summary- STANDARD Centurion Fire Protection, LLC 051706-Orthopedics NW Page 4 Date 5-14-17 Node Elevation K-Fact Pt Pn Flow Density Area Press No. Actual Actual Req. DP02 11.25 5.6 7.0 EQ02 12.25 na 14.82 0.1 144 7.0 10.23 na DP01 11.25 5.6 7.0 na 14.82 0.1 EQ01 12.25 10.0 144 7.0 S9 12.25 K=K @ EQ01 10.0 na S10 12.25 K=K @ EQ02 10.79 na 14.82 1 12.25 15.22 2 12.25 13.551na 3 12.25 29.569.2 na 4 12.25 na 35.16 na TOR 12.25 BOR38.15 na -3.0 50.42 na TEST 0.0 49.9 S11 12.25 K=K@EQ01 1281 na 116.0 S12 12.25 K=K @ EQ01na 17.81 5 12.25 14.45 na 17.81 S5 12.25 K=K @ EQ01 10.43 28.99 na S6 12.25 K=K @ EQ02 11.82 na 15.1315.92 S7 12.25 K=K @ EQ02 14.16 na 4 7 12.25 na 17.44 8 12.25 15.1217.17 na S8 12.25 K=K @ EQ01 13.94 na Si 12.25 K=K@EQ01 10.47 na 17.49 9 12.25 na 15.16 11.25 na 10 12.25 11 12.25 14.25 na 1215.28 na 12.25 17.14 na 13 12.25 26.41 S2 12.25 K=K @ EQ01 10.89 na S3 12.25 K=K @ EQ01 13.63 na 15.46 S4 12.25 K=K na 17.3 @ EQ01 14.46 na 17.81 The maximum velocity is 14.15 and it occurs in the pipe between nodes 7 and 8 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams Centurion Fire Protection, LLC Page 5 051706-Orthopedics NW Date 5-14-17 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn DP02 14.82 1.049 T 5.0 1.000 7.000 K Factor=5.60 to 120.0 Vcfd 43.0 48.000 -0.433 EQ02 14.82 0.0747 0.0 49.000 3.660 Vel= 5.50 0.0 14.82 10.227 K Factor= 4.63 DP01 14.82 1.049 E 2.0 1.000 7.000 K Factor= 5.60 to 120.0 Vcfd 43.0 45.000 -0.433 EQ01 14.82 0.0747 0.0 46.000 3.436 Vel = 5.50 0.0 14.82 10.003 K Factor= 4.69 S9 14.82 1.049 E 2.0 8.470 10.003 K Factor @ node EQ01 to 120.0 0.0 2.000 0.0 S10 14.82 0.0747 0.0 10.470 0.782 Vel = 5.50 S10 15.21 1.049 0.0 10.000 10.785 K Factor @ node EQ02 to 120.0 0.0 0.0 0.0 1 30.03 0.2761 0.0 10.000 2.761 Vel = 11.15 1 16.77 1.38 0.0 10.000 13.546 to 120.0 0.0 0.0 0.0 2 46.8 0.1650 0.0 10.000 1.650 Vel= 10.04 2 17.81 1.38 T 6.0 41.960 15.196 to 120.0 0.0 6.000 0.0 3 64.61 0.2996 0.0 47.960 14.367 Vel = 13.86 3 131.70 2.635 T 16.474 39.310 29.563 to 120.0 0.0 16.474 0.0 4 196.31 0.1003 0.0 55.784 5.596 Vel = 11.55 4 0.0 2.635 0.0 29.840 35.159 to 120.0 0.0 0.0 0.0 TOR 196.31 0.1003 0.0 29.840 2.994 Vel= 11.55 TOR 0.0 4.26 2E 26.334 15.250 38.153 to 120.0 Zff 0.0 26.334 11.865 **Fixed Loss = 5.26 BOR 196.31 0.0097 0.0 41.584 0.402 Vel= 4.42 BOR 0.0 6.16 2E 40.168 600.000 50.420 to 140.0 G 4.304 44.472 -1.299 TEST 196.31 0.0012 0.0 644.472 0.777 Vel = 2.11 100.00 Qa = 100.00 296.31 49.898 K Factor= 41.95 S11 16.77 1.049 T 5.0 2.790 12.814 K Factor @ node EQ01 to 120.0 0.0 5.000 0.0 1 16.77 0.0940 0.0 7.790 0.732 Vel= 6.23 0.0 16.77 13.546 K Factor= 4.56 S12 17.81 1.049 T 5.0 2.060 14.454 K Factor @ node EQ01 to 120.0 0.0 5.000 0.0 2 17.81 0.1051 0.0 7.060 0.742 Vel= 6.61 0.0 17.81 15.196 K Factor= 4.57 3 -131.70 2.635 0.0 12.000 29.563 to 120.0 0.0 0.0 0.0 5 -131.7 -0.0479 0.0 12.000 -0.575 Vel= 7.75 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams Centurion Fire Protection, LLC 051706-Orthopedics NW Page 6 Date 5-14-17 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn 5 65.98 2.635 0.0 8.740 28.988 to 120.0 0.0 0.0 5.305 6 -65.72 -0.0132 0.0 8.740 -0.115 Vel = 3.87 0.0 -65.72 34.178 S5 15.13 1.049 K Factor=-11.24 E 2.0 10.900 10.426 K Factor @ node EQ01 to 120.0 T 5.0 7.000 0.0 S6 15.13 0.0776 0.0 17.900 1.389 S6 15.92 1.049 Vel= 5.62 0.0 8.000 11.815 K Factor @ node EQ02 to 120.0 0.0 0.0 S7 31.05 0.2936 0.0 0.0 8.000 2.349 Vel = 11.53 S7 17.44 1.38 0.0 5.420 14.164 to 120.0 K Factor @ node EQ02 7 48.49 0.1762 0.0 0.0 0.0 0.0 5.420 0.955 Vel= 10.40 7 17.48 1.38 0.0 6.580 15.119 to 120.0 0.0 0.0 8 65.97 0.3114 0.0 0.0 6.580 2.049 Vel= 14.15 8 0.0 1.38 T 6.0 31.960 17.168 to 120.0 0.0 6.000 0.0 5 65.97 0.3114 0.0 37.960 11.820 Vel = 14.15 0.0 65.97 28.988 S8 17.49 1.049 E 2.0 K Factor= 12.25 to 4.650 13.936 K Factor @ node EQ01 120.0 T 5.0 7.000 0.0 7 17.49 0.1015 0.0 11.650 1.183 Vel = 6.49 0.0 17.49 15.119 S1 15.16 1.049 T K Factor= 4.50 5.0 6.800 10.468 K Factor @ node EQ01 to 120.0 0.0 5.000 0.0 9 15.16 0.0779 0.0 11.800 0.919 Vel= 5.63 9 15.45 1.049 0.0 10.000 11.387 to 120.0 0.0 0.0 0.0 10 30.61 0.2860 0.0 10.000 2.860 10 17.30 1.38 Vel= 11.36 to 0.0 6.000 14.247 120.0 0.0 0.0 0.0 11 47.91 0.1723 0.0 6.000 1.034 Vel= 10.28 11 17.81 1.38 0.0 6.000 15.281 to 120.0 0.0 0.0 12 65.72 0.3092 0.0 0.0 6.000 1.855 Vel= 14.10 12 0.0 1.38 0.0 30.000 17.136 to 120.0 0.0 0.0 13 65.72 0.3092 0.0 0.0 30.000 9.275 Vel= 14.10 13 0.0 1.38 T 6.0 1.960 26.411 to 120.0 0.0 6.000 5.305 6 65.72 0.3093 0.0 7.960 2.462 Vel = 14.10 0.0 65.72 34.178 K Factor= 11.24 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams Centurion Fire Protection, LLC 051706-Orthopedics NW Page 7 Date 5-14-17 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn S2 15.46 1.049 T 5.0 1.200 10.886 to 120.0 0.0 5.000 0.0 K Factor @node EQ01 9 15.46 0.0808 0.0 6.200 0.501 Vel= 5.74 0.0 15.46 11.387 K Factor= 4.58 S3 17.30 1.049 T 5.0 1.200 13.630 to 120.0 0.0 5.000 0.0 K Factor @ node EQ01 10 17.3 0.0995 0.0 6.200 0.617 Vel= 6.42 0.0 17.30 14.247 S4 17.81 1.049 T 5.0 2.800 14.461 K Factor= 4.58 K Factor @ node EQ01 to 120.0 0.0 5.000 0.0 11 17.81 0.1051 0.0 7.800 0.820 Vel= 6.61 0.0 17.81 15.281 K Factor= 4.56 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 SUBMITTAL PACKAGE CENTURION FIRE PROTECTION Portland Orthopedics NW PO Box 1705 5755 SW Sequoia Parkway#200 Oregon City, OR 97045 Portland, OR 97224 503-593-9791 www.centurionfirepro.com SECTION A: PIPE Pages 1,2 SECTION B: FITTINGS Pages 3-10 SECTION C: VALVES& BACKFLOW DEVICES Pages N/A SECTION D: HANGERS Pages 3-17 SECTION E: ELECTRICAL Pages N/A SECTION F: FIRE SPRINKKERS Pages 18-29 SECTION G: SIESMIC BRACING Pages N/A SECTION H: MISCELLANEOUS Pages 30-48 _;F'—` a � � SPRINKLER PIPE ..... .... ......... ...... ... . ...... ...... .......... .......... Trust ll Moose whencomes to protecting st valuable assets. As the leading manufacturer of steel sprinkler pipe, we understand that there are no second chances in fire suppression. You need products of enduring quality and exceptional strength-plus reliable service. You need Bull Moose. BULL MOOSE ADVANTAGES: TH EN FIT' / RV ICE S • UL listed(US&Canada)and FM approved • We have the most stocking locations in industry,for best delivery and availability • ASTM A135 and A795 Type E, Grade A Certified • Plain end or roll groove • Complies with NFPA-13,13R and 14 • Eddy Guard II°bacterial-resistant internal coating • Industry-leading hydraulic characteristics. • Custom length options • CRR of 1.0 and greater • Hot dipped galvanization • All pipe NDT weld tested • Reddi-Pipe®red pipe to eliminate field painting Exclusive maker of Reddi-Pipe® • Compatible for use in wet,dry,preaction red painted pipe. and deluge sprinkler systems caus LISTED ►APPROVED MO NEPA' Sprh k1z ��� = f BULL 7y[OOSE'"TUBE ullMooseTube.com Bull Moose Fire Sprinkler Pipe Product Information Nominal Pipe Size(Inches) 1" 11/4" 1-1/2" 2" 2-1/2" 3" 4" 6" 8" O.D.(m) 1.660 1.900 2.375 2.875 3.500 4.500 LD.(in) 1.530 1.728 2.203 2.705 3.334 4.310 Empty Weight(lb/ft) 1.222 1.844 2.330 2.809 3.361 4.968 Water Filled Weight(Ib/ft) 2.019 2.860 3.982 5.299 7.144 11.290 C.R.R. 1.98 3.44 2.78 1.66 1.00 1.00 Pieces per Lift 61 61 37 30 19 19 Lift Weight(lbs)21'lengths 1,565 2,362 1,810 1,770 1,341 1,982 Lift Weight(lbs)24 lengths 1,789 2,700 2,069 2,022 1,533 2,265 Lift Weight(lbs)25'lengths 1,864 2,812 2,155 2,107 1,596 2,360 O.D.(in) 1.315 1.660 1.900 2.375 2.875 3.500 4.500 6.625 8.625 l.D.(in) 1.097 1.442 1.682 2.157 2.635 3.260 4.260 6.357 8.249 Empty Weight(lb/ft) 1.410 1.810 2.090 2.640 3.530 4.340 5.620 9.290 16.940 Water Filled Weight(lb/ft) 1.820 2.518 3.053 4.223 5.893 7.957 11.796 23.038 40.086 C.R.R. 15.27 9.91 7.76 627 4.92 3.54 2.50 1.158 1.805 Pieces per Lift 91 61 61 37 30 19 19 10 7 Lift Weight(lbs)21'lengths 2,695 2,319 2,677 2,051 2,224 1,732 2,242 1,951 2,490 Lift Weight(lbs)24'lengths 3,079 2,650 3,060 2,344 2,542 1,979 2,563 2,230 2,848 Lift Weight(lbs)25'lengths 3,208 2,760 3,187 2,442 2,648 2,062 2,670 O.D.(in) 1.295 1.650 1.900 2.375 I D.(in) 1.083 1.418 1.645 2.123 Empty Weight(Ib/ft) 1.461 2.070 2.547 3.308 „ rill Water Filled Weight(Ib/ft) 1.860 2.754 3.468 4.842 C.R.R. 1.00 1.00 1.00 1.00 Pieces per Lift 70 51 44 30 Lift Weight(lbs)21 lengths 2,148 2,217 2,353 2,084 Lift Weight(lbs)24'lengths 2,454 2,534 2,690 2,382 Lift Weight(lbs)25'lengths 2,557 2,639 2,802 2,481 0.0.(in) 1.315 1.660 1.900 2.375 2.875 3.500 4.500 I.D.(in) 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Empty Weight(Ib/ft) 1.680 2.270 2.720 3.660 5.800 7.580 10.800 Water Filled Weight(lb/ft) 2.055 2.918 3.602 5.114 7.875 10.783 16.316 C.R.R. 1.00 1.00 1.00 1.00 1.00 1.00 1.00 Pieces per Lift 70 51 44 30 30 19 19 Lift Weight(lbs)21'lengths 2,470 2,431 2,513 2,306 3,654 3,024 4,309 Lift Weight(lbs)24'lengths 2,822 2,778 2,872 2,635 4,176 3,456 4,925 Lift Weight(lbs)25'lengths 2,940 2,894 2,992 2,745 4,350 3,601 5,130 arc., � i i, � � � ' BULL ]/[OOSE'" TUBS u(IMooseTube.com FIG. MT-1 Threaded Mechanical Branch Tee (*ANVIL 411;C:O Mechanical branch connections for reducing branch outlets without welding. The MT-1 is a bolted saddle type fitting o with NPT female threaded outlets. Design assures superior sealing, full pipe support, excellent stability and easy installation. For the latest UL/ULC listed, LPCB, VdS and FM Approved pressure ratings versus pipe schedule, see www.anvilintl.com or contact your local Anvil Representative. cOus ® =`LPCB= [VdS) LISTED APPROVED o For Listings/Approval Details and Limitations,visit our website at www.anvilintl.corn or contact an Anvile Sales Representative. MATERIAL SPECIFICATIONS HOUSING: GASKETS: Materials Ductile Iron conforming to ASTM A-536,Grade 65-45-12 Properties as designated in accordance with ASTM D-2000. ANSI BOLTS & HEAVY HEX NUTS: 0 Grade"E"EPDM(Green color code) Heat treated,oval-neck track head bolts conforming to ASTM A-183 -40°F to 230°F(Service Temperature Range)(40°C to 110°C) Grade 2 with a minimum tensile strength of 110,000 psi and heavy hex nuts Recommended for water service,diluted acids,alkalies solutions, of carbon steel conforming to ASTM A-563 Grade A or Grade B,or SAE oil free air and many chemical services. J995 Grade 2.Bolts and nuts are provided zinc electroplated as standard. NOT FOR USE IN PETROLEUM APPLICATIONS. METRIC BOLTS & HEAVY HEX NUTS: Heat treated,zinc electroplated oval-neck track head bolts made of carbon steel with mechanical properties per ISO 898-1 Class 8.8.Hex nuts and bolts are zinc electroplated followed by a yellow chromate dip. COATINGS: ❑Rust inhibiting paint Color:ORANGE(standard) ❑Hot Dipped Zinc Galvanized(optional) El Other available options: Example:RAL3000 or RAL9000 Series For other coating requirements contact an Anvil Representative. LUBRICATION: ❑Standard Gruvlok ❑Gruvlok XtremeTM required for dry pipe systems and freezer applications. PROJECT INFORMATION APPROVAL STAMP Project: El Approved Address: Contractor: ['Approved as noted ['Not approved Engineer: Remarks: Submittal Date: Notes 1: Notes 2: FP-4.12 FIG. MT-1 Threaded Mechanical Branch Tee *ANVIL; C71:0 Y rZ Y T 4 ' } a P T 1111 1 -)- N1 u . ,rrA W v... v''� MT-I THREADED MECHANICAL BRANCH TEE Nominal Hole Dimensions Max. Dimensions Size O.D. Working Y Bolt Approx. Min.Diameter Max.Diameter pressured T Threaded W Y Z Size Wt.Ea. In./DN(mm) In./mm In./mm In./mm PSI/bar In./mm In./mm In./mm In./mm In./mm In./mm Lbs./Kg 2 x 1 2.375 x 1.315 11/2 1% 300 1'3/46 25/8 1%6 45/8 21/2 3/8 x 2 1.7 50 x 25 60.3 x 33.7 38 41 20.7 50 67 40 117 63 0.8 2 x 11/4 2.375 x 1.660 13/4 1' 300 115A6 2% 19/6 45/8 21/2 3/x 2 1.7 50 x 32 60.3 x 42.4 44 48 20.7 49 67 40 117 63 0.8 2 x 11/2 2.375 x 1.900 13/4 11/8 300 115/6 25/8 19/6 45/8 21/8 3/8 x 2 1.7 50 x 40 60.3 x 48.3 44 48 20.7 49 67 40 117 73 0.8 21/2 x 1 2.875 x 1.315 11/2 15/8 300 2'/6 31/8 113/6 59/6 3% /x 23/4 3.6 65 x 25 73.0 x 33.7 38 41 20.7 62 79 46 141 86 1.6 21/2 x 11/4 2.875 x 1.660 2 21/2 300 2'/6 3'/8 113/6 59/6 3% /x 23/4 3.6 65 x 32 73.0 x 42.4 51 54 20.7 62 79 46 141 86 1.6 27/x 11/2 2.875 x 1.900 2 2'/8 300 2'/6 31/8 113/6 59/6 3% h x 23/4 3.6 65 x 40 73.0 x 48.3 51 54 20.7 62 79 46 141 86 1.6 3 x 1 3.500 x 1.315 11/2 1% 300 23/4 3'/16 21/8 61/4 31%6 h x 23/4 3.8 80 x 25 88.9 x 33.7 38 41 20.7 71 87 55 159 99 1.7 3 x 11/4 3.500 x 1.660 2 27/8 300 23/4 31/16 21/t 61/4 315/6 /2 x 23/4 3.8 80 x 32 88.9 x 42.4 51 54 20.7 70 87 55 159 99 17 3 x 17/2 3.500 x 1.900 2 21/2 300 23/4 3'/6 21/8 6'/4 315/6 1/2 x 23/4 3.8 80 x 40 88.9 x 48.3 51 54 20.7 70 87 55 159 99 1.7 3 x 2 3.500 x 2.375 21/2 2% 300 23/4 31/16 21/8 61/4 375/6 1/x 23/4 4.4 80 x 50 88.9 x 60.3 64 67 20.7 70 87 55 159 99 2.0 4 x 1 4.500 x 1.315 11/2 1% 300 35/6 4 2% 71/4 313/6 1/2 x 23/4 4.6 100425 114.3x33.7 38 41 20.7 85 102 67 184 97 21 4 x 11/4 4.500 x 1.660 2 21/2 300 35/6 4 2% 71/4 313/6 1/2 x 23/4 4.6 100 x 32 114.3 x 42.4 51 54 20.7 84 102 67 184 97 21 4 x 11/2 4.500 x 1.900 2 21/2 300 35/6 4 2% 71/4 313/16 1/2 x 23/4 4.6 100 x 40 114.3 x48.3 51 54 20.7 84 102 67 184 97 2.1 4 x 2 4.500 x 2.375 21/2 25/8 300 35/6 4 2% 71/4 41/2 1/2 x 23/4 4.8 100 x 50 114.3 x 60.3 64 67 20.7 84 102 67 784 115 2.2 4 x 21/2 4.500 x 2.875 23/4 21/8 300 3'/16 4 2% 71/4 41/2 1/2 x 23/4 5.4 100x65 114.3x73.0 70 73 20.7 78 102 67 184 115 24 4 x 3 4.500 x 3.500 31/2 3% 300 3 41/8 2% 71/4 5'/t 1/2 x 23/4 5.4 700 x 80 114.3 x 88.9 89 92 20.7 76 105 67 184 130 2.4 5 x 11/2 5.563 x 1.900 2 27/8 300 41/16 43/4 33/6 85/6 313/6 Vex 4 7.4 125x40 141.3x48.3 51 54 20.7 103 127 81 271 97 3.4 5 x 2 5.563 x 2.375 21/2 2% 300 41/6 43/4 33/16 85/16 313/6 %x 4 7.9 125x50 741.3x60.3 64 67 20.7 103 121 81 211 97 3.6 5 x 21/2 5.563 x 2.875 23/4 21/8 300 313/16 43/4 33/,6 85/6 313A6 5/8 x 4 7.9 125x65 741.3x73.0 70 73 20.7 97 121 81 211 97 3.6 6 x 11/4 6.625 x 1.660 2 21/2 300 313/16 415/16 31%6 93/8 31/8 %x 4 8.0 150 x 32 768.3 x 42.2 51 54 20.7 97 126 94 238 98 3.6 6 x 11/2 6.625 x 1.900 2 21/2 300 41/6 5'/e 3"16 93/t 3% %x 4 7.5 150 x 40 168.3 x 48.3 51 54 20.7 113 130 94 238 98 3A 6 x 2 6.625 x 2.375 21/2 2% 300 41/16 51/2 311/6 93/8 41/16 %x 4 8.0 150 x 50 168.3 x 60.3 64 67 20.7 112 130 94 238 112 3.6 6 x 21/2 6.625 x 2.875 23/4 2'% 300 43/6 51/2 311A6 9% 4'/6 5/8x 4 8.0 150x65 168.3x73.0 70 73 20.7 706 130 94 238 112 3.6 6 x 3 6.625 x 3.500 31/2 3% 300 41/2 51/4 3"/4 93/8 5% 5/8 x 4 9.7 150 x 80 168.3 x 88.9 89 92 20.7 105 133 94 238 143 4.4 8x2 8.625x2.375 21/2 2% 300 51/6 61/4 4% 105/6 41/6 3/4x4'/4 10.2 200 x 50 219.1 x 60.3 64 67 20.7 138 159 123 313 112 4.6 All sizes may be used as mechanical crosses. Threads are NPT per ANSI/ASME B1.20.1 A WARNING A-Working Pressure Ratings are for reference only and based on Sch.40 pipe.For the latest UL/ULC,FM,VdS and LPCB pressure For dry pipe systems and freezer applications ratings versus pipe schedule,please visit anvilintl.com or contact your local Anvil Representative. lubrication of the gasket is required, Gruvlok®XtremeTM Lubricant is required. FP-4.12 Ductile Iron• Thread •. 16. • • • • • ed Fiffings 7,7 y1 iE- q; •A t ;. ' t `'N'Ekzi . F y'�`�4�`' r -� �S, ��r•€ �' r^#'�•�;�.�-�'`��- k�a� � S;�r�.� S.^ ;�.. rratt.04 No; r \ II I IIS- ( ( � ( � I I I � b r. t n .-s'a:fr'if7A-'etwftn0.kgit;trvltIIS.q-*i.gp44M4Vkzv.kgxi:;:.* Z,*wlttfg.;,-.4RL .. Ductile Iron Threaded Fiffings O ,S • CI branded ductile iron threaded fittings are UL Listed and FM Approved at 500 psi • Rated to 300 WSP ® L US • Ductile iron castings conform to ASTM A536 • Fitting dimensions conform to ASME B16.3 LISTED • Bushings and plugs conform to ASME B16.14 • Fittings are 100% air tested APPROVED • NPT threads on all fittings conform to ASME B1.20.1 • Independent lab verification that fittings meet applicable chemical &physical properties • Manufacturing facilities are ISO 9001:2008 and ISO 14001 Temperature Working Pressure, Nonshock psiG Degrees F 300# Class Threaded Fittings 20 to 100 500 150 ..: 500° 200 480 250.,. 460 300 440 350 400 400 x#50 X80 360 500 550. 340 320 600 650 300 1.'1 �tlDuctile Iron Fittings - Class 300 UL/FM 117,1, .i ,_- c43us APPROVED A Fig. 35E 3-90°Elbow LISTED Size Part Number A Packing Weight ••� in in Inner Master lb 4 1/2 „,,,.,, ..:35.E.,,300.4,,,'.._".,.:_, '..',,,_'1'.1.3_ 100 200 __, _,,: 0i..3.24,1, 1 '0 3/4 35E 30001 `11 21 140 : 0 ��.►j� ,l A 1 35E3010 1.50 40 80 0 5 �1_lI,. 11/4, 3 rE 301 ... '75, ...: 22.55' . : 59 0 8 "' 1-1/2 35E 3014 1.94 18 36 1.1 2 ., 5E 3020.. ..2 25 1 6...: 13 ........ 2-1/2 35E 3024 2.70 4 8 3.2 Fig. 35RE3-90°Reducing Elbow B Size Part Number' An B Packing Weight; JbI A.....11114. in In in Inner Mas#er'' Ib 3/4x1/235RE3006004 120 1 22 80 160 0 3 '1 x 1 2 3 flE30110004 12 136 70 146 :::"..--,...0...4,...-.F. 1 x 3/4 35RE3010006 1.38 _I....45 50 100 _0.4 ala VA 11:111/44:131/24 1/44x1/2 35RE3512004 .... "1:44 1.53 357700 0 5 7�} 1 1/4 x 3/4 35RE3012006 1 45 1 63 35 70 0 6 III 1-1/4x 1 .:: 36RfiE;3 S1201o, 1.156 ... :.: '1„ l 30 . ,:..; 6a.. 0 7..1;11 1-1/2 x 1/2 35RE3014004 1.52 1.75 30 60 0.6 11/2:x 314. : 35RE3014005 1.52 '. 1,76 :.; ': 25 . .: 50. 0.7 ':' 1-1/2 x 1 35RE3014010 1.65 1.80 20 40 0.8 1-1/2 x 1-114 35RE3014012 1.82 1..88 18 26. 1.0 2 x 1/2 35RE3020004 1.60 1.97 18 36 1.0" 2"x 3/4 369E6020006 '1.1,60 . 1..97' .... :..18 ""' ;.36"." 1,0 2 x 1 35RE3020010 1.73 2.02 16 32 1.2 2x 1-1,4 35RE3025012 1.90 . - 2.10" :: 12i,..: 2 x 1-1/2 35RE3020014 2.02 2.16 10 20 1.5 ,j1 2-1/2'x 1-1/2 35RE3024014 2.16 2,51, 6 12 2.2 • 11, 2-1/2 x 2 35RE3024020 2.39 2.60 6 12 2.5 ill Fig. 35F 3-45°Elbow Size Part Number A Packing Weight in in Inner Master lb 1/2 35F 3004 0 88 150 300 0.2 3/4 35F.3006 '.1.91,38' ." 80 1610 0.3 /it 135F010408p051 1-1/4" . 35F 3012 . . 1.29.. . 25 : 50 0,7 . 1-1/2 35F 3014 1.44 20 40 1 0 gji�i4 IA .2' 35F.3020 1.69.. ._10: 2-1/2 35F 3024 1.95 4 8 2.7 Fig. 35T 3- Tee Size Part Number A Packing Weight 01 inin Inner Master- lb I=UIILe TA 1/2 351 3004 1.13 80 160 0.3 JI. 3/4 35T 3006 1.31 30 60 ' 0.5 1 351 3010 1.50 25 50 0.7 1-114 . 35T.3012 . 1..75:. 10 '20 1.1 *-A-)1(-7- 1-1/2 35T 3014 1.94 10 20 1.5 101 .2 .. 35T 3020 . 2.25. 6 ' 12 . 2.4 . 2-1/2 35T 3024 2.70 4 8 4.3 111 SMITH-COOPER INTERNATIONAL° • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com -.4S,..„,'} ‘,0'• Ductile Iron Fittings - Class 300 UL/FM c03us 411> APPROVED Fig. 35RT3-Reducing Tee LISTED Imo :Size Part Number A B C Packing Weight in in in Inner Master lb I I C 3/4 x 1/2 35613006004 1.20 1.20 1.22 60 120 0.4 _ i II- 1'x 1 .. 33;RT3Q 1 OQ04 :126 ..:''11-2366 126 . ..136 '''''3030H':'''''''6606' 30 606 '''''''00'.$6'' 0 6 II � i 1 x 1/2 x 1 35613010004010 1 50 1 36 11:5360'''' 50 30 60 0 6 ' ��,� I .1.x3/4. ...'. .35 irVit0® .. ..:1 38. ...138 ?45 25 5Q X�6 4--1 -3 B . E A 1111 1 x 3/4 x 3/4 35RT3010006006 1.38 1.31 1.45 35 70 0.6 I x:314•x I 356.13010006010..... :15'0 1 45"".. 1 ... .: 50 .. 'Ott 1-1/4x1/2 35RT3012004 1.34 1.34 1.53 20 40 0.8 11J4 x 112 x 1 114 35RT3012904012 ..3 75 53 1 75 ..: 251i:',R'ila.$01,15i Mill,a92R 1-1/4x3/4 35RT3012006 1.45 1.45 1.62 15 30 0.9 1 1/4 x 3/4 x 1 134 356 3012006012 ,.:1 75 1 0.:. „162 :175 20 40 ' 1 1/4 x 1 35RT3012010 1.58 1.58 1.67 15 30 1.0 1.114., 1 x 112. 35RT301201/r1004 ` 34--, `f 26 ;#53 25. 50 117 :4 1-1/4 x 1 x 3/4 35RT3012010006 1.45 1.38 1.63 20 40 0.8 1-1/4 x 1 x 1..: 35RT3012010010 ....1 58 .. 150.. :159 . 20 4(1 ,,,,..?,11',A9,:01,, 1-1/4 x 1 x 1-1/4 35RT3012010012 1.75 1.69 1.75 15 30 1.0 RAI1 1X2 x 1/2 35613014004 :4"..-,14.18..... 1 41 •.,. 1 66 ...,:. 16. 32.... 10. 1-1/2 x 1/2 x 1-1/4 35RT3014004012 1.81 1.56 1.88 24 48 1.1 ?::: 1 112 35613014094014 .... 1.94 "."T•66.......';104 122 ,:.:: 24 12 1-1/2x3/4 35RT3014006 1.52 1.52 1.75 16 32 1.1 ! 1 I/2 x"3/4 x 1 1/4 35613014008012 l 94 ,"1:66 188 ., 20 40 1 1 1-1/2 x 3/4 x 1-1/2 35RT3014006014 1.94 1.75 1.94 18 36 1.2 1-1/2 x 1 35FiT3014010" 1.:55 1.05 1.80 " 1-1/2 x 1 x 1/2 35RT3014010004 1.44 1.25 1.69 20 40 0.8 1-1/2 x 1 x 3/4 35613014010006. 1`,50" 4,,44 1.75 16 32 :` 0:9, 1 1/2 x 1 x 1 35RT3014010010 1.65 1.50 1.80 16 32 1.0 l-1/2.xc 1 x 1-1/4. 35613014010012 1182 ;1',67; l88 ;12 '..",:.:!''"'..:2:4:, : 1.2;. ' 1-1/2 x 1 x 1 1/2 35RT3014010014 1.94 1.80 1.94 12 24 1,3 1-1/2x1-1/4 35R713014012 1.82 1".82" 1.88 12 :24 1.4 cI 1-1/2 x 1 1/4 x 1/2 35RT3014012004 1.41 1.34 1.66 16 32 0.9 ik ',',,'1'.:1/2.X"":1...1/4.".)0,/.4],:, 35R13014012006 1.52 1.45 1,75 16 32 ' 1'.0 1-1/2 x 1-1/4 x 1 35RT3014012010 1.65 1.58 1.80 16 32 1.1 l-1/2x1-1/4x11/4 35813014012012 .:,-,,:,,,1,:,.a?.::::.! 1.76 11.88 `14 2851.3 1-1/2 x 1-1/4 x 1-1/2 35RT3014012014 1.94 1,88 1.94 14 28 1.4 2,:x 1/2 .. 35673020004 1.49 1:49 1',88.: 10 . , 20 1:5 2 x 3/4 35RT3020006 1.60 1.60 1.97 10 20 1.6 '. . ° 2 Vie"1 35813020010 1.73 1.73 2!.02, " 8 16 s1.7 ' 2 x 1 x 2 35RT3020010020 2.25 2.02 2.25 8 16 1.9 2"x 1-1/4 3561302001'2 " 1.90 1.90' 2.10 8 !16 1.9. 2 x 1-1/4 x 2 35RT3020012020 2.25 2.10 2.25 8 16 2.0 2 x 1-1/2 35R13020014 2.02 2.02 2.16 ':,:::',.',..::8-,,,,''':',1-: 16 2,1 2 x 1 1/2 x 1/2 35RT3020014004 1.49 1.41 1.88 10 20 1.3 2x'1-112x3/4.".! 356130200140,06 ':::::,'.1:„Q();1':',,,]]]]]]1];,52.]:]:: .1.97 10., 20 1 4i',i4 2 x 1-1/2 x 1 35RT3020014010 1.73 1.65 2.02 8 16 1.5 2x1-1/2x1-1/4"" 35813020014012 1.90 1.82 2,10 8 116. 1.7 . 2 x 1-1/2 x 1-1/2 35RT3020014014 2.02 1.94 2.16 8 16 1.8 Fig. 35BT3-Bull Head Tee 11111 viol.: Size Part Number A B Packing Weight in in in in Inner Master Ib -;j' � C 3/4 x 1 35813006010 1.45 1.45 1.37 30 60 0.6 i , 1 x 1-114 35813010012 ]]]1].'67]]]]' 1,67 1.58. 20 ]40 `0,9 . :�� 1 x 1-1/2 35BT3010014 1.80 1.80 1.65 15 30 1.0 1-1/4 x 1:x 1-1/2 35BT30120100141.88' 1.80 1.82 15. 30 1.2 1-1/4x1-1/2 35B13012014 1.88 1.88 1.82 15 30 1.3 1-1/4'x 2 35B13012020 2.10 2.10 ']...]:,1],90,-]] 10 20 1.6 1-1/2 x 1-1/4 x 2 35BT3014012020 2.16 2.10 2.02 10 20 1.8 I-1/2x 2 35BT3014020 2.16 2.16 2:02 8 16 1.8 SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com 112 4:J-----T--- I"mmmmmI.l..l...l..I.IIl.l..I...11II.IlMMIlIIlI.IIIIIIIllllIlI:tl:t,:,,.'. Ductile Iron Fittings - Class 300 UL FM c (;), uS LISTED APPROVED A Fig. 35CP3 -Straight Coupling with Ribs ,v�� Size Part Number Packing Weight1 11 ' in in Inner Master ib_ - 1/2 35CP3004 1:38 , ��� 200 400 p 1 � 3/4 �5�P3006' �„� 1 35CP3010 175 60 120 0.4 111110 1-1/2 35CP3014 2.19 25 50 0.7 2 . 35P030...;` 30 2-1/2 35CP3024 3.00 9 t2 18 2.2 Fig. 35RC3 -Hex Reducing Coupling Size rIMII in Part Number A packing Weight A 1 30169 8lb Ank 1X3/4x1/2 85R 5RC301610004 �69160 3�0 12� £l4, ' ;\ 1-1/4 x 3/4 35RC3012006 2.06 40 80 0.6 2x 1.,(not hex) 36RC3020010 2.81 ::: 20 40'::. •;t 1.0 . :.. Fig. 35HB3 -Hex Bushing Size Part Number A Packing Weight B , 10 in Inner Master Ib 11 , 1 x 1/2 35H83010004 1.06 180 360 0 2 IlIc„A 1 x 3/4 35HB301 0006 1.06. 180' 360 0.1 1-1/4 x 1 35HB3012010 1.19 90 180 0.2 1-1/2 x 1 i 35HB3014010.: 1.25 . i 75 150. 0.4 1-1/2x 1-1/4 35HB3014012 1.25 75 150 E 0.3 2x1 35HB3©20010. 1.38 40 80 0.6 2 x 1-1/4 35H33020012 1.38 40 80 0 6 2 x 1-112 35H83020014. 1 38 40 80 0.6 Fig. 35SP3 -Square Head Plug Size Part Number PA Packing Weight in in Inner Master lb 1/2 35SP3004 0 94 600 1200 0.07 AA IA 3/4 35SP3006 1.12 350' 700 0.1 1 35SP3010 1.25 200 400 0.1 1-1/4 35SP3012 1.37 100 200 0.3 1-1/2 35SP3014 1.44 80 160 0,4 2 353P3020 .; 1.50 45 r 90 0.6. Fig. 35U 3-Union with Brass Seat A Size Part Number A Packing Weight orArdisiMmas in Inner Master lb 1 35U 3010 2 19 20 40 1 0 1-1/4 35U 3012 2.50 15 301111111J I1-1/2 35U 3014 2.621.7 10 20 1 7 PArAr 2 35U 3020 3.12 6. 12. 2.4 113 SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com Ductile Iron Fittings - Class 300 UL/FM Iopal ;4 cOL) us APPROVED Fig. 35X 3—Cross LISTED A (---,R---)A Size in Part Number A Packing Weight in Inner 'Master lb N..- tvie IA 1 35X 3010 1.50 20 40 0.9 1114 35X3012 =i 1.75 24. 'I 4 _= A 1-1/2 35X 3014 1.94 8 16 1.8 §I62 3ar1t3 I ., ;1225 :._: . _ ...: 12.... 28.. f6 B Fig. 35RX3—Reducing Cross Size ■■y A in Part Number A` B Packing Weight in in Inner Master lb - 1111_ i 1 1-1/4 x 1 35RX3012010 1.67 1.58 15 30 1.2 1 '1 f2 1 358 1;4010 ... 1 80 .; 16 " 2 ' 4 ',...11,4-.1.i..."." 1 ; I IA . 2 x 1 358X3020010 2.02 1.73 8 16 2.0 ry Fig. 35C 3— Cap Size Part Number A Packing> Weight PISA in' in Inner Master lb 1111111111 1/2 35C 3004 0.87 300 600 0 1 314,.. . . .:. 35 X006 ......"r °1'.9167 37 200400 1 1 35C 3010 1 16 110 220 0.2 1-1/4 35C3012 1.28 . 70 140 0.4 1-1/2 35C 3014 1.33 50 100 0.5 2 350 3020 1.45 25 50 0.8 2-1/2 35C 3024 1.70 18 36 1.6 • • Fig. 35BC3—Beam Clamp Al Weight Size Part Number A Packing: ■ in Inner Master lb — 43/8 35BC3003 0.75 100 200 0.3 NI Ali/ 112 ; 35803004... ... . :0,75.. .": . 80 ".`: ..--;...."--160..-. Sffii SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com 114 ..te47g§§ P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org 300 RING HANGER • 1 1 thru 4 inch pipe 1/2&3/4 inch pipe LISTED FOR STEEL/CPVC 5 thru 8 inch pipe NFPA 13 UL 1 WT 5 WT.+250 TEST PIPE ROD LOAD 1 3/8 30.75 403.75 750 11/4 3/8 43.95 469.75 750 SIZE-ROD-3/8"or 1/2" 1 1/2 3/8 54.15 520.75 750 SIZE-SYSTEM PIPE- 1/2" thru 8" 2 3/8 183 841 634.755 750 MATERIAL-Carbon Steel,Mil. Galvanized to G-90 spec. 2 72 3/8 162.30 841.75 3 3/8 162.30 1061.50 10505 0 LISTING/APPROVAL- 4 3/8 246.00 1480.00 1500 11 5 1/2 349.45 1996.75 2000 CU TED's 203-EX 2551 1"-8" 6 1/2 476.35 2631.75 2650 .0.Approval guide-1"-8" 8 1/2 711.00 3805.00 4050 OSHPD OPA-0601 See Website. CONFORMS WITH:Federal Specification WW-H-171E,Type 10. Manufacturers Standardization Society ANSI/MSS-SP-58 Type 10. MAXIMUM TEMPERATURE-650°F. FUNCTION-Pipe hanger component of an AFCON hanger. To support steel,CPVC or copper pipe. INSTALLATION-Per NFPA 13, 13R, 13D,these instructions and the CPVC or copper pipe manufacturers instructions. PIPE A 1 1.8793 2.5259 FEATURES- 11/4 2.1382 2.7850 * Sized and listed exclusively for use with#310 Surge Restrainer. 2 2.2673 2.9'4° * Band edge is offset for EASY pipe insertion. A B 2 2.6046 3.25'6 2,.2 3. * Custom fit swivel nut for better retention in ring. 3 3.7845 7845 4115° .. a 4 4311 ORDERING-Part#,pipe size. 4.3562 4.9992 6 6.0668 6.8180 \,/98,88,801 8 7.5768 8.3290 6 P 11/09 -Powers FASTENERS PRODUCT INFORMATION Mini Dropin TM Mini Dropin Internally Threaded Expansion Anchor SECTION CONTENTS Page No. PRODUCT DESCRIPTION Q o General Information 1 V CC The Mini Dropin is a carbon steel machine bolt anchor for use in shallow embedment Material and Installation Z = applications. In addition to solid concrete and precast hollow core plank, it can be used Specificationsonce V in post-tensioned concrete slabs and concrete pours over steel deck. Performance Data 2 U Q Design Criteria 3 W GENERAL APPLICATIONS AND USES Ordering Information 4 •Suspending Conduit • Fire Sprinkler • Cable Trays and Strut • Utilities �) • Pipe Supports • Suspended Lighting FEATURES AND BENEFITS Mini Dropin +Internally threaded anchor for easy bolt removability and service work +Ideal for precast hollow core plank and post-tensioned concrete slabs THREAD VERISON + Lip provides flush installation and consistent embedment UNC Thread +Setting tool scores flange when set to verify proper expansion depth ANCHOR MATERIALS APPROVALS AND LISTINGS Zinc Plated Carbon Steel Tested in accordance with ASTM E 488 and AC01 criteria ROD/ANCHOR SIZE RANGE(TYP.) Factory Mutual Research Corporation (FM Approvals)—File No.J.I. 3002071 1/4"diameter to 1/2"diameter See listing for applicable sizes-www.fmglobal.com SUITABLE BASE MATERIALS GUIDE SPECIFICATIONS Normal weight Concrete Structural Lightweight Concrete CSI Divisions:03151-Concrete Anchoring and 05090-Metal Fastening. Anchors shall be Precast Hollow Core Plank Mini Dropin anchors as supplied by Powers Fasteners, Inc., Brewster, NY. Concrete Over Steel Deck MATERIAL AND INSTALLATION SPECIFICATIONS Material Specification Installation Specification Anchor Component Carbon Steel Anchor Body SAE 1009 Rod/Anchor Diameter,d Dimension 1/4" 3/8" 1/2" Plug SAE 1009 ANSI Drill Bit Size dbt(in.) 3/8 1/2 5/8 Zinc Plating ASTM B633,SC1,Type III(Fe/Zn 5) Maximum Tightening Torque,9 9 9 ,T max.(ft-lbs) 3 5 10 Thread Size(UNC) 1/4-20 3/8-16 1/2-13 Thread Depth(in.) 3/8 13/32 5/8 Overall Anchor Length(in.) 5/8 3/4 1 Installation Guidelines Drill a hole into the base "u Blow the hole clean of dust If using a fixture, position it, insert bolt and material to the depth ��J and other materials. Insert of embedment required. ; the anchor into the hole tighten. Most overhead applications utilize The tolerances of the drill . ' - / ', threaded rod. Minimum thread engagement bit used must meet the v '� and tap flush with surface. o� should be at least one anchor diameter. v Using a Powers setting requirements of ANSI ° • f I" • y tool specifically,set the Standard B212.15. , ° °I.. ° anchor by driving the tool �� ' ' • ' with a sufficient number b /� In post-tensioned concrete '- r of hammer blows until r� 1 slabs,take care to avoid v ...• ...-- slabs, shoulder of the tool is � � ... drilling into the post-tensioned e seated against the anchor. . tc7" ,'"Il 1 ,.1> "�!_►`_� • cables. Anchor will not hold P r`d P;•, " d. , a I a allowable loads required if , ., d. ' - V . o C shoulder of Powers setting o D v tool does not seat against anchor. P ' f Powers USA:(800)524-3244 or(914)235-6300 Canada: (905)673-7295 or(514)631-4216 www.powers.com 1 ?owers Mini Dropin PRODUCT INFORMATION FASTENERS n m PERFORMANCE DATA 0 Z Ultimate Load Capacities for Mini Dropin in Normal-Weight Concrete'•2 6f51.. , lA D Rod/Anchor Minimum Minimum Concrete Compressive Strength(Fr) r- Size Embedment 3,000 psi(20.7 MPa) 4,000 psi(27.6 MPa) 6,000 psi(41.4 MPa) d Depth Tension Shear in. h, lbs. Tension Shear Tension Shear lbs. lbs. lbs. lbs. lbs. (mm) In• (mm) (kN) (kN) (kN) (kN) (kN) (kN) 1/4 5/8 1,100 1,260 1,150 1,650 1,200 1,650 (6.4) (15.9) (6.3) (5.7) (5.1) (7.4) (5.3) (7.4) 3/8 3/4 1,980 2,700 2,120 4,220 2,270 4,220 (9.5) (19.1) (8.9) (12.2) (9.5) (19.0) (10.2 (19.0) 1/2 1 3,360 4,400 3,360 4,875 3,750 4,875 (12.7) (25.4) (15.1) (19.8) (15.1) (21.9) (16.9) (21.9) 1.Tabulated load values are for anchors installed in concrete.Concrete compressive strength must be at the specified minimum at the time of installation. 2.Ultimate load capacities must be reduced by a minimum safety factor of 4.0 or greater to determine allowable working load. Allowable Load Capacities for Mini Dropin in Normal-Weight Concrete"2 Rod/Anchor Minimum Minimum Concrete Compressive Strength(f'‘) Size Embedment 3,000 psi(20.7 MPa) 4,000 psi(27.6 MPa) 6,000 psi(41.4 MPa) d Depth h, Tension Shear Tension Shear Tension lbs. Shear (mm) In• lbs. lbs. lbs. lbs. lbs. (mm) (kN) (kN) (kN) (kN) (kN) (kN) 1/4 5/8 275 315 285 415 300 415 (6.4) (15.9) (1.2) (1.4) (1.3) (1.9) (1.3) (1.9) 3/8 3/4 495 675 530 1,055 570 1,055 (9.5) (19.1) (2.2) (3.0) (2.4) (4.7) (2.6) (4.7) 1/2 1 840 1,100 840 1,220 940 1,220 (12.7) (25.4) (3.8) (5.0) (3.8) (5.5) (4.2) (5.5) 1.Allowable load capacities listed are calculated using and applied safety factor of 4.0. 2.Linear interpolation may be used to determine allowable loads for intermediate compressive strengths. Ultimate and Allowable Load Capacities for Mini Dropin Installed Through Steel Deck into Structural Lightweight Concrete"2'3 Installation Detail for Mini Dropin Installed Through Soffit of Steel Deck into Concrete Lightweight Concrete Over Min.20 Ga.Steel Deck. Rod/Anchor Minimum f a 3,000 psi(20.7 MPa) STRUCTURAL SAND-LIGHTWEIGHT CONCRETE Size Embed. Minimum 1-3/4"Wide Deck OR NORMAL WEIGHT CONCRETE OVER STEEL DECK d Depth (MINIMUM 3,000 PSI) h" Ultimate Load Allowable Load UPPER FLUTE(VALLEY) In. (mm) in. Tension Shear Tension Shear (mm) lbs. lbs. lbs. lbs. VFLUTEEDOE (kN) (kN) (kN) (kN) 01/4 5/8 740 1,880 185 470 ANCHOR (6.4)a. (TYP) a (15.9) (3.3) (8.5) (0.8) (2.1) a d4 3/8 3/4 880 2,040 220 510 (9.5) (19.1) (4.0) (9.2) (1.0) (2.3) as NO MIN.EDGE DISTANCE 1/2 1 1,380 2,120 345 530 (UPPER FLUTE) (12.7) (25.4) (6.2) (9.5) (1.6) (2.4) MIN.7/8"(LOWER FLUTE) - -.-- 1.The metal deck shall be No.22 gage to No.18 gage thick steel[0.030-inch to 0.047-inch base metal thickness LOWER FLUTE(RIDGE) (0.75 mm to 1.20 mm)). NO.22 to NO.18 GAGE STEEL DECK 2.Allowable load capacities listed are calculated using and applied safety factor of 4.0. 3,Tabulated load values are for anchors installed with a minimum edge distance of 7/8"when installed through the lower flute.Anchors installed through the upper flute may be in any location provided the proper installation procedures are maintained. f 2 www.powers.com Canada: (905)673-7295 or(514)631-4216 Powers USA:(800)524-3244 or(914)235-6300 -Powers FASTENERS PRODUCT INFORMATION Mini Dropin PERFORMANCE DATA Vix � Ultimate and Allowable Load Capacities for Mini Dropin Z 0 in Precast Hollow Core Concrete Plankt2 j" = U Rod/ Minimum Min.Concrete Compressive Strength Lu Q Installation Detail for Mini Dropin Anchor Embed. Minimum Minimum f;s 5,000 psi(34.5 MPa) Installed in Precast Hollow Core Size Depth Spacing D stance Ultimate Load Allowable Load Concrete plank d h, in. in. Tension Shear Tension Shear in. in. (mm) (mm) lbs. lbs. lbs. lbs. e • as (mm) (mm) (kN) (kN) (kN) (kN) ° Q \ f1/4 5/8 3 3 1,400 1,840 350 460 (--/i 0 (6.4) (15.9) (76.2) (76.2) 6.2 (8.3) (2.1) 3/8 3/4 4-1/2 4-1/2 2,600 3,400 650 850 MIN.1-1/2" 3 (9.5) (19.1) (114) (114) (11.7) (15.3) (2.9) (3.8) ANCHOR(TYP) 1 1 6 6 2,600 3,540 650 885 (12.7) (25.4) (152.4) (152.4) (11.7) (15.9) (2.9) (4.0) 1.Tabulated load values are for anchors installed in concrete.Concrete compressive strength must be at the specified minimum at the time of installation. 2.Allowable load capacities listed are calculated using and applied safety factor of 4.0. DESIGN CRITERIA (ALLOWABLE STRESS DESIGN) Combined Loading For anchors loaded in both shear and tension, the combination of loads should be proportioned as follows: IN5 5 1Where: Nu=Applied Service Tension Load u 1 IVu 1 1 OR (Nu Nn=Allowable Tension Load t J 1 / / (Vu < 1 Nn Vn Nn Vn Vu=Applied Service Shear Load Vn=Allowable Shear Load Load Adjustment Factors for Spacing and Edge Distance1,2,3 Anchor Installed in Normal-weight Concrete Anchor Dimension Load Type Critical Distance Critical Load Factor Minimum Distance Minimum (Full Anchor Capacity) (Reduced Capacity) Load Factor Spacing(s) Tension and Shear scr=3.0h, FNc=FVc=1.0 smin=1.5h FNS=Fv5=0.50 Edge Distance(c) Tension ccr=12d FN,=FVc=1.0 cmin=6d FNc=0.90 Shear' ccr=12d FNc=FVc=1.0 cmin=6d FVc=0.75 1.Allowable loads for anchors loaded in shear parallel to the edge have no load factor FVC=1.0 when installed at minimum edge distances. 2.Allowable load values found in the performance data tables are multiplied by reduction factors when anchor spacing or edge distances are less than critical distances.Linear interpolation is allowed for intermediate anchor spacing and edge distances between critical and minimum distances.When an anchor is affected by both reduced spacing and edge distance,the spacing and edge reduction factors must be combined(multiplied).Multiple reduction factors for anchor spacing and edge distance may be required depending on the anchor group configuration. Anchor Installed in Through Steel Deck Structural Lightweight Concrete Anchor Dimension Load Type Critical Distance Critical Load Factor Minimum Distance Minimum (Full Anchor Capacity) (Reduced Capacity) Load Factor Spacing(s) Tension and Shear scr=3.0h5 FNS=FVS=1.0 smin=1.5h, Ns=Fvs=0.50 3.Allowable load values found in the performance data tables are multiplied by reduction factors when anchor spacing is less than critical distances.Linear interpolation is allowed for intermediate anchor spacing between critical and minimum distances.Multiple reduction factors for anchor spacing may be required depending on the anchor group configuration. f Powers USA:(800)524-3244 or(914)235-6300 Canada: (905)673-7295 or(514)631-4216 www.powers.com 3 ?owers. Mini Dropin PRODUCT INFORMATION FASTENERS mDESIGN CRITERIA (ALLOWABLE STRESS DESIGN) = Load Adjustment Factors for Normal-weight and Lightweight Concrete Spacing,Tension(FA.,,,)&Shear(Fv�)(Normal-weight and Lightweight Concrete over deck) Notes:For anchors loaded in tension and shear, 0 Z Dia.(in.) 1/4 3/8 1/2 the critical spacing(s„)is equal to 3 embedment D [Iv(in.) 5/8 3/4 1 depths(3k)at which the anchor achieves 100% of load. s (in.) 1-7/8 2-1/4 3 Minimum spacing s p g(m�,)is equal to 1.5 embedment sr,,,(in.) 1 1-1/8 1-1/2 depths(1.5hv)at which the anchor achieves 50% 1 0.50 of load. 1-1/8 0.60 0.50 N /2 0.67 0.50 N 11-1 7/8 0.80 1.00 0.83 0.63 40 2 0.89 0.67 21/4 1.00 0:75 2-1/2 0.83 s 3 1.00 Edge Distance,Tension(FNc)(Normal-weight concrete only) Notes:For anchors loaded in tension,the critical edge distance(cc)is equal to 12 anchor diameters Dia.(in.) 1/4 3/8 1/2 (124 at which the anchor achieves 100%of load. c,,(in.) 3 4-1/2 6 Minimum edge distance(cmin)is equal to 6 anchor diameters(6o}at which the anchor achieves 90% s,.,(in.) 1-7/8 2-1/4 3 1-1/2 0 g0 of load. 2 0.93 2-1/4 0.95 0.90 2-1/2 0.97 0.91 3 1.00 0.93 0.90 - 4 4 1/2 0.00 0.93 1 00 0.95 5 0.97 6 1.00 Edge Distance,Tension(Fuc)(Normal-weight concrete only) Notes:For anchors loaded in shear,the critical edge distance(cc)is equal to 12 anchor diameters Dia.(in.) 1/4 3/8 1/2 (124 at which the anchor achieves 100%of load. 4`(in.) 3 4-1/2 6 Minimum edge distance(cmin)is equal to 6 anchor cm• (in.) 1-1/2 2-1/4 3 diameters(6d)at which the anchor achieves 75% 1-1/2 0.75 of load. 2 0.83 ▪ 2-1/4 0.88 0.75 2-1/2 0.92 0.78 • 3 1.00 0.83 0.75 4111/1.111%/ 0 4 0.94 0.83 4-1/2 1.00 0.88 w 5 c 0.92 1.00 ORDERING INFORMATION Carbon Steel Mini Dropin Cat No. Rod/Anchor Dia. Drill Diameter Overall Length Standard Box Standard Ctn. 6335 1/4" 3/8" 5/8" 100 1,000 6322 3/8" 1/2" 3/4" 100 1,000 6337 1/2" 5/8" 1" 50 250 Setting Tool for Mini Dropin Cat No. Mini Dropin Size Standard Box Standard Cartoon 6336 1/4" 1 50 6323 3/8" 1 50 6338 1/2" 1 50 Accu-BitTM Drill Stop for Mini Dropin Cat No. Rod/Anchor Size Standard Box 00392 3/8"Accu-Bit for 1/4"Mini Dropin 1 00398 1/2"Accu-Bit for 3/8"Mini Dropin 1 00411 5/8"Accu-Bit for 1/2"Mini Dropin 1 ©2012 Powers Fasteners,Inc. All Rights Reserved. Dropin and Accu-Bit are a Trademark of Powers Fasteners,Inc.For the most current information visit www.powers.com 4 www.powers.com Canada:(905)673-7295 or(514)631-4216 Powers USA:(800)524-3244 or(914)235-6300 Page 1 of 2 Fastenal Product Standard Date: December 1,2010 REV 03 TROD.LC.Z Threaded Rod,Low Carbon,Zinc Plated The information below lists the required dimensional,chemical and physical characteristics of the products in this purchase order. If the order received does not meet these requirements,it may result in a supplier corrective action request,which could jeopardize your status as an approved vendor. Unless otherwise specified,all referenced consensus standards must be adhered to in their entirety. 11111111111111111111111 D ----f L------ L -----0-1 Diameter Nominal Size D (Major Diameter) Max. Min. 4-40 * .1120 .1112 .1061 6-32 * .1380 .1372 .1312 8-32 * .1640 .1631 .1571 10-24 * .1900 .1890 .1818 10-32 * .1900 .1891 .1831 12-24 * .2160 .2150 .2078 1/4-20 .2500 .2489 .2367 1/4-28 .2500 .2490 .2392 5/16-18 .3125 .3113 .2982 5/16-24 .3125 .3114 .3006 3/8-16 .3750 .3737 .3595 3/8-24 .3750 .3739 .3631 7/16-14 .4375 .4361 .4206 7/16-20 .4375 .4362 .4240 1/2-13 .5000 .4985 .4822 1/2-20 .5000 .4987 .4865 9/16-12 .5 62 5 .5609 .5 43 7 9/16-18 .5625 .5611 .5480 5/8-11 .6250 .6233 .6051 5/8-18 .6250 .6236 .6105 3/4-10 .7500 .7482 .7288 3/4-16 .7500 .7485 .7343 7/8-9 .8750 .8731 .8523 7/8-14 .8750 .8734 .8579 1-8 1.000 .9980 .9755 1-14 * 1.000 .9984 .9881 1 1/8-7 1.12 5 1.1228 1.0982 1 1/8-12 1.125 1.1232 1.1060 1 1/4-7 1.25 0 1.2478 1.2 232 1 1/4-12 1.250 1.2482 1.2310 1 3/8-6 1.37 5 1.3726 1.3453 1 1/2-6 1.50 0 1.4 976 1.4703 1 1/2-12 1.500 1.4981 1.4809 1 3/4-5 1.75 0 1.7 473 1.7165 2-4.5 2.000 1.9971 1.9641 *Class 2A threads shall be used for sizes where 1A is not applicable Length I Tolerance 3' I +/- 1/4" 6' - 12' +/- 1/2" Length shall be measured form end to end Page 2 of 2 Fastenal Product Standard REV-03 Date: December 1,2010M1A TROD.LC.Z Specification Requirements: • Standard: ASME B18.31.3 • Material& • Mechanical Properties: ASTM A307,Grade A • Thread requirements: Roll threaded to ASME,B1.1 UNC&UNF, and UNS Class 1A. • Coating: Fe/Zn 3AT Per ASTM F1941 FireLock® V38, K5.6 Models V3801, V3802 °t 40.50 40.50 Adjustable Concealed Standard Spray Technical Specifications: Standard and Quick Response Models: V3801,.V3802 Style: Adjustable concealed, ordinary hazard, light Wim: Y hazard Nominal Orifice Size: 1/2"/13 mm K-Factor: 5.6 Imp./8.1 S.I.1 V3801 and V3802 Nominal Thread Size: 1/2715 mm Max. Working Pressure: 175 psi/120 �,�0 kPa Approvals/Listings: Factory Hydrostatic Test: 100% @ 500 psi/3450 kPa 4� c , ® C E LPCB �P LISTED 0832 104-1a/02 Min. Operating Pressure: 7 psi/48 kPa See Victaulic Publication 10.01 for more details. Temperature Rating: See chart on page 3. 1 For K-Factor when pressure is measured in Bar,multiply S.I.units by 10.0. Product Description: This concealed, designer style sprinkler allows up to n 1/2"/13 mm adjustment to accommodate concealment .�; j. needs. The "standard" design provides a consistent �; �(`�-�, hemispherical spray pattern. The separate two-piece �r mounting cup/cover plate allows easy installation and testing prior to ceiling installation. It also permits removal of suspended ceiling panels without system shutdown. J This sprinkler is available in various temperature ratings 1► �-/ (see chart on page 3) and finishes to meet many design requirements. o (A11111W" Coverage: o For coverage area and sprinkler placement, refer to NFPA 13 or applicable standards. Exaggerated for clarity Job/Owner Engineer System No. Spec Section Location I � I Paragraph Contractor Approved Submitted By Date Date victaulic.com I Sprinkler I FireLock® I K5.6, V38 I Publication 40.50 40.50 2558 Rev.0 Updated 07/2014 ©2014 Victaulic Company.All rights reserved. 1 �ctaulic' victaulic.com I Sprinkler I FireLock® I K5.6, V38 I Publication 40.50 Material Specifications: Accessories: Deflector: Bronze per UNS C22000 Installation Wrench: Cover Plate: Fusible solder ❑ Concealed: V38 4 or V38 5 Bulb: Glass with glycerin solution. Sprinkler Finishes: Bulb Nominal Diameter: ❑ Plain Brass (only) ❑ Standard: 5,0 mm Cover Finishes: ❑ Quick Response: 3,0 mm ❑ Chrome Plated Load Screw: Bronze per UNS C65100 ❑ White Painted3 ❑ Flat Black Painted3 Pip Cap: Bronze per UNS C65100 ❑ Custom Painted3 2 Teflon is a registered trademark of Dupont Co. Spring: Stainless steel per UNS S30100 UL Listed for corrosion resistance. Seal: Teflon2 tape Frame: Die cast brass 65-30 Pins: Stainless steel per UNS S30400 Cup: Cold rolled steel, zinc chrome plated Cover/Escutcheon: Brass per UNS C26000 Lodgement Spring: Stainless steel per UNS S30200 Protective Cap: Polyethylene 40.50 2558 Rev.0 Updated 07/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 2 �Ctaulia victaulic.com I Sprinkler I FireLock® I K5.6, V38 I Publication 40.50 Approval/Listings: f Approvals/Listings Model V3801 V3002 Orifice Size(inches) 1/2" 1/2" Orifice Size(mm) 13 13 Nominal K Factor Imperial 5.6 5.6 Nominal K Factor S.I 4 8.1 8.1 Response Standard 5mm bulb Q,itki 3rrt txtii?' Deflector Type Concealed Pendent Concealed Pendent Adjustment I Approved Temperature Ratings Fo/Co V3801 V3802 1350F/57°C 135°F/57°C cULus 155°F/68°C 155°F/68°C 175°F/79°C 175°F/79°C 200°F/93°C 200°F/93°C FMS 155°F/68°C4 NONE 175°F/79°C4 200°F/93°C4 135°F/57°C 135°F/57°C NYC/MEA5#62-99-E 155°F/68°C 1550F/68°C 175°F/79°C I 175°F/79°C 2000F/93°C I 200°F/93°C 1350F/57°C 135°F/57°C CSFM5#7690-0531:112 1550F/68°C 1550F/68°C 175°F/79°C 175°F/79°C 200°F/93°C 200°F/93°C 155°F/68°C Sprinkler/138°F/59°C Cover 155°F/68°C Sprinkler/138°F/59°C Cover LPCB 175°F/79°C Sprinkler/165°F/74°C Cover 175°F/79°C Sprinkler/165°F/74°C Cover 200°F/93°C Sprinkler/165°F/74°C Cover 200°F/93°C Sprinkler/165°F/74°C Cover 135°F/57°C 135°F/57°C VNIIPO 155°F/68°C 1550F/68°C 175°F/79°C 2000F/93°C 2175°F/790C 2860F/1410C //93°C 28866°°F/141°C CCCf ZSTDY 155°F/68°C r NONE 4 For K-Factor when pressure is measured in Bar,multiply S.I.units by 10.0. 5 Recognized by FM as standard response only. Note:Listings and Approvals as of printing.All are approved open. 40.50 2558 Rev.0 Updated 07/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 3 ✓ctaulic° victaulic.com, I Sprinkler I FireLock® I K5.6, V38 I Publication 40.50 Dimensions: Models V3801, V3802 (drawings not to scale) 2/,6/68 mm r Max.Hole 36/80 mm 2%"/60 mm Min.Hole IPRINEL 1 e7774 e Yi 2uAs'lIl mm ,11������� 2%6/59 mm `� '-moi _ --Lo Ill; -2•4, z°/5,mm „� ,;;, '/"/13 mm Adjustment e, ..„.&77_,,, Oak. yp 9 ',:% I'.,' Typical1/2"18 � Typical Ceilin Tile mm yp Ceiling Tile 31/4"/83 mm Cover Plate Finished Surface Finished Surface Minimum Extension Maximum Extension Distribution Patterns: Models V3801, V3802 K5.6 standard concealed pendent distribution patterns —trajectory i.. zi 10' 3.0m • •.•' �8' `••` ♦♦4♦ 2.4 m •• ♦♦ • 6' `•• 4> 1.8 m N• ♦�♦ • ••. :♦ 4' N • 1.2 m �` ♦♦ �♦ 2' `• ♦♦ 0.6m ••` ♦4' 0 ` �♦ 2' 4' 6' 8' 10' 12' 14' 0.6 m 1.2 m 1.8 m 2.4 m 3.0 m 3.7 m 4.3 m 7 psi 15 psi 30 psi 48 kPa 103 kPa 207 kPa NOTES: 1 Data shown is approximate and can vary due to differences in installation. 2 These graphs illustrate approximate trajectories,floor-wetting,and wall-wetting patterns for these specific Victaulic FireLock automatic sprinklers.They are provided as information for guidance in avoiding obstructions to sprinklers and should not be used as minimum sprinkler spacing rules for installation.Refer to the appropriate NFPA National Fire Code or the authority having jurisdiction for specific information regarding obstructions,spacing limitations and area of coverage requirements.Failure to follow these guidelines could adversely affect the performance of the sprinkler and will void all Listings,Approvals and Warranties. 3 All patterns are symmetrical to the centerline of the waterway. 40.50 2558 Rev.0 Updated 07/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 4 jctaulia victaulic.com I Sprinkler I FireLock® I K5.6, V38 I Publication 40.50 Ratings: All glass bulbs are rated for temperatures from -67°F/-55°C to those shown in table below. Sprinkler Sprinkler-V3801,V3802 Cover-V38 Temperature-°F/°C Temperature-°F/°C Nominal Maximum Ambient Nominal Maximum Ambient Temperature Victaulic Part Temperature Temperature Victaulic Part Temperature Temperature Classification Identification Rating Allowed Glass Bulb Color Identification Rating Allowed Ordinary A 135°F/57°C 100°F/38°C Orange A6 1358 100 57 57 41 riaty v ,55° °C 00:940t, +... D 7 165 150 74 65 Intermediate E 175°F/79°C 150°F/65°C Yellow Intermediate F 200°F/93°C 150°F/65°C Green High J 286°F/141°C 225°F/107°C Blue Extra High 8 K, 360°F/182°C 300°F/149°C Purple M Open - No Bulb 6 A For use with Standard or Quick Response Concealed Sprinkler 135°F/57°C or 155°F/68°C. 7 D For use with Standard or Quick Response Concealed Sprinkler 175°F/79°C or 200°F/93°C. 8 138°F/59°C per LPCB Note:Custom Finish-Customer to provide paint specification,allow 4-6 weeks for samples. Available Wrenches: Sprinkler Type Recessed Concealed Pendent-V3801,V3802 V38-4 or V38-5 40.50 2558 Rev.0 Updated 07/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 5 ✓Ctaulic victaulic.com I Sprinkler I FireLock®I K5.6, V38 I Publication 40.50 . . ,,.,-W.._. L�...:,s.. ..._«�,,:.s,.,.,s.,=s.:,.:a..s,..:-.;*...�::.,,:,.a::.r.4.;a.•�:„;:�t:�aat:i:__::s:[<^.t • Always read and understand installation, care, and maintenance instructions, supplied with each box of sprin- e klers, before proceeding with installation of any sprinklers. • Always wear safety glasses and foot protection. S • Depressurize and drain the piping system before attempting to install, remove,or adjust any Victaulic piping products. • Installation rules,especially those governing obstruction, must be strictly followed. 0 • Painting, plating, or any re-coating of sprinklers(other than that supplied by Victaulic)is not allowed. Faure to foe iiesinjury and/or property damage. The owner isllow responsible for maintainingcould qtr fire protectionpersonal system and devices in proper operating minimumilmaintenancethesandnstructinspectionons requirementsultin , referserious to the current National Fire Protection Associationcondition.pamFor- phlet that describes care and maintenance of sprinkler systems. In addition,the authority having jurisdiction may have additional maintenance, testing, and inspection requirements that must be followed. If you need additional copies of this publication, or if you have any questions about the safe installation of this product, contact Victaulic World Headquarters: P.O. Box 31, Easton, Pennsylvania 18044-0031 USA, Telephone: 001-610-559-3300. I I r01 1 I 1 .Installation Reference should always be made to the -100 Victaulic Field Installation Handbook for Note the product you are installing.Handbooks are included with each shipment of Victaulic toThis installedduct shall accordance withithed currentby VictaulicVictaulic to Victaulic assembly in tr All onproducts products for complete installation and assembly data,and are available in PDF format Victaulicbe inthe ight eeinstallation/a i ns an instructions. ns. on our website at www.victaulic.com. euip t without the right andtwithout productncurrig obligationss,designs and standard equipment without notice without incurring obligations. Warranty Refer to the Warranty section of the current Price List or contact Victaulic for details. Trademarks Victaulic and Zero-Flex are registered trademarks of Victaulic Company. 40.50 2558 Rev.0 Updated 07/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 6 ictaaulic FireLock® V27, K5.6 Models V2703, V2707 V2704, V27 jctaul 0i0 O8 . ' 40.10 Standard Spray Technical Specifications: Upright, Pendent and Recessed Pendent Standard and Quick Response Models: V2703, V2704, V2707, V270B Style: Pendent, Upright or Recessed Pendent .` Nominal Orifice Size: 1/2"/13 mm 0K Factor: 5.6 Imp./8.1 S.I.1 - Nominal Thread Size: 1/2 NPT/15 mm ,fir Max. Working Pressure: V2703/V2704 v2707/v2708 v2707iv27o8 • 175 psi/1200 kPa (FM) • 250 psi/1725 kPa (UL) Upright Pendent Recessed Pendent Factory Hydrostatic Test: 100% @ 500 psi/3450 kPa Approvals/Listings: Min. Operating Pressure: cOus ® LPCB 0. ® (yds) (E • 7 psi/48 kPa 0786 • 0.35 bar/5 psi (VdS for upright only) See Victaulic Publication 10.01 for more details. Temperature Rating: See chart 1 For K-Factor when pressure is measured in Bar,multiply S.I.units by 10.0. Product Description: These Model V27 standard spray sprinklers are designed to produce a hemispherical spray pattern for standard commercial applications. They are available with either standard or quick response bulbs. It is cast with a hex-shaped wrench boss to allow easy tightening0 from many angles, reducing assembly effort. This sprinkler is available in various temperature ratings (see t chart on page 3) and finishes to meet many design requirements. The recessed pendent should be utilized with a Model V27 recessed escutcheon which provides �, up to 3/4719 mm of adjustments. ►j Coverage �I� NIP For coverage area and sprinkler placement, refer to NFPA 13 or applicable standard. Exaggerated for clarity Job/Owner Engineer System No. j --- � Spec Section Location Paragraph Contractor Approved Submitted By I Date Date victaulic.com I Sprinklers I FireLock® I K5.6, V27 I Publication 40.10 40.10 2544 Rev.J Updated 07/2014 ©2014 Victaulic Company.All rights reserved. 1 ✓ctaulic' victaulic.com I Sprinklers I FireLock®I K5.6, V27 I Publication 40.10 Material Specifications: Accessories Upright Deflector: Bronze per UNS C11000 Pendent Deflector: Bronze per UNS C51000 Installation Wrench: Bulb: Glass with glycerin solution El Open End: V27 Bulb Nominal Diameter: ❑ Recessed: V27-2 ❑ Standard: 5.0 mm Sprinkler Finishes: ❑ Quick Response: 3.0 mm ❑ Plain Brass Load Screw: Bronze per UNS C65100 ❑ Chrome plated Pip Cap: Bronze per UNS C65100 ❑ White painted3 Spring: Beryllium nickel ❑ Black painted3 Seal: Teflon2 tape ❑ Custom painted3 Frame: Die cast brass 65-30 ❑ Proprietary Nickel Teflon2 coating3 Lodgement Spring: Stainless steel per UNS S30200 ❑ VC-2504 155, 200, 286 SR Only: ❑ Wax3 For cabinets and other accessories refer to separate sheet. 2 Teflon is a registered trademark of Dupont Co. 3 UL Listed for corrosion resistance. 4 UL Listed and FM Approved for corrosion resistance. 40.10 2544 Rev.J Updated 07/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 2 ✓ctaulic victaulic.com I Sprinklers I FireLock® K5.6, V27 I Publication 40.10 Approvals/Listings: APPROVALS/LISTINGS Model V2703 V2707 V2707 V2704 V2708 .1/2708,? Orifice Size(inches) 1/2" 1/2° 1/2„ 1/2„ 1/2° � # Orifice Size(mm) 13 13 13 13 13 13 Nominal K Factor Imperial 5.6 5.6 5.6 5.6 5.6 Nominal K Factor S.I.s 8.1 8.6 8.1 8.1 8.1 8.1 8.1 Response Standard Standard Standard Quick Quick Q�lrck Deflector Type Upright Pendent Recessed f3ec*5$ed Upright Pd Pendent enent Approved Temperature Ratings ' r/C° 135°F/57°C 135°F/57°C 135°F/57°C 135°F/57°C 135°F/57°C 155°F/68°C 155°F/68°C 155°F/68°C 155°F/68°C 155°F/68°C 135°F/57°C cULus 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C 155°F/68°C 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C 175°F/79°C 286°F/141°C 286°F/141°C 286°F/141°C 286°F/141°C 286°F/141°C 200°F/93°C 360°F/182°C 360°F/182°C 135°F/57°C 135°F/57°C 155°F/68°C 155°F/68°C 135°F/57°C 135°F/57°C 135°F/57°C 175°F/79°C 175°F/79°C 155°F/68°C 155°F/68°C 155°F/68°C 135°F/57°C FM 175°F/79°C 175°F/79°C 155°F/68°C 200°F/93°C 200°F/93°C 175°F/79°C 175°F/79°C 286°F/141°C 286°F/141°C 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C 360°F/182°C 360°F/182°C 286°F/141°C 286°F/141°C 135°F/57°C 135°F/57°C 135°F/57°C 135°F/57°C 135°F/57°C 155°F/68°C 155°F/68°C 155°F/68°C 155°F/68°C 155°F/68°C 135°F/57°C NYC/MEA 62-99-E 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C 155°/68°C- 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C 175°F/79°C 286°F/141°C 286°F/141°C 286°F/141°C 286°F/141°C 286°F/141°C 200°F/93°C 360°F/182°C 360°F/182°C 135°F/57°C 135°F/57°C 155°F/68°C 155°F/68°C 135°F/57°C 135°F/57°C I 135°F/57°C 175°F/79°C 155°F/68°C 155°F/68°C � 155°F/68°C 135°F/57°C CSFM 7690-0531:112 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C 155°F/68°C 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C 175°F/79°C 286°F/141°C 286°F/141°C 200°F/93°C 360°F/182°C 360°F/182°C 286°F/141°C 286°F/141°C 286°F/141°C 135°F/57°C 155°F/68°C 135°F/57°C LPCB None 175°F/79°C 155°F/68°C 200°F/93°C i None 175°F/79°C None None 286°F/141°C 200°F/93°C 360°F/182°C 135°F/57°C 135°F/57°C 155°F/68°C 155°F/68°C 135°F/57°C 135°F/57°C 135°F/57°C 175°F/79°C 175°F/79°C 155°F/68°C 155°F/68°C 155°F/68°C 135°F/57°C VNIIPO 175°F/79°C 175°F/79°C 155°F/68°C 200°F/93°C 200°F/93°C 175°F/79°C 175°F/79°C 286°F/141°C 286°F/141°C 200°F/93°C 200°F/93°C 200°F/93°C 360°F/182°C 360°F/182°C 286°F/141°C 286°F/141°C 200°F/93°C ZSTZ ZSTX K-ZSTZ K-ZSTZ CCC 155°F/68°C 155°F/68°C None 155°F/68°C 155°F/68°C None 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C 135°F/57°C 155°F/68°C 135°F/57°C VdS 175°F/79°C 155°F/68°C 200°F/93°C None None 175°F/79°C None None 286°F/141°C 200°F/93°C 360°F/182°C 286°F/141°C 135°F/57°C 135°F/57°C 155°F/68°C CE 175°F/79°C 155°F/68°C 200°F/93°C None None 175°F/79°C None None 286°F/141°C 200°F/93°C 360°F/182°C ( 286°F/141°C For K Factor when pressure is measured in Bar, multiply S.I.units by 10.0 FM Approved with 1/2"adjustment escutcheon only-quick response Note: Listings and Approvals as of printing.All are approved open. 40.10 2544 Rev.J Updated 07/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 3 ✓ctaulic victaulic.com I Sprinklers I FireLock® K5.6, V27 I Publication 40.10 Dimensions: -- 116/ EA 37 mm ,,..). 1,,,,,,I, ., 23/8"/ pl.11111 Z15/a"/ 60 mm 3/8„/ 41 mm 15/a"/ llii 60 mm ifi 41 mm .. EEO ! III, Standard Pendent Standard Upright— V2707,V2708 V2703,V2704 2%760 mm Max.Hole 2751 mm f Min.Hole Typical hilt X76/ I 0 / 17mm W�I j�l�� C;ilingTile ��I�� �I��30 mm 43 mm rE7Finished Surface 13/,6"/ 30�nm I MAXIMUM RECESS 2's/e"/ 75mm MAXIMUM EXTENSION 'h"Adjustment Recessed—V2707,V2708(drawing not to scale) 23/8°/60 mm Max.Hole -- 2751 mm Min.Hole b"/ + IcLl 17A67 6 �� �� ■ 24 mm 18 mm Typical CeilingTile �.��r�i�1�%.� 37 mm f } �iuf®l�L)� � Yp I 1 Finished24 mm ��'�� Surface a 1. MAXIMUM RECESS 25/6'/ 75mm MAXIMUM EXTENSION 3/4"Adjustment Recessed—V2707,V2708(drawing not to scale) 40.10 2544 Rev.J Updated 07/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 4 ✓Ctaulic' victaulic.com I Sprinklers I FireLock® I K5.6, V27 I Publication 40.10 Distribution Patterns: Models V2707,V2708 K5.6 Standard Pendent and Recessed Pendent Agn�r, Distribution Patterns—Trajectory 10'YY �.s • * . ♦♦♦ • ♦♦ .. 4 8' `. ♦• 6' • ••♦• � 48 kPa `. • • 44 15 psi �� 4' �, '•• 103 kPa 1.2m •`..... ...♦♦.. ._. • • •. ♦ 30 psi ` `• 207 kPa •4 2' '• 0.6m _. -. •. o '♦ 4. 2 4' 6' 8' 10' 12' 14' 0.6m 1.2m 1.8m 2.4m 3.0m 3.7m 4.3m Models V2703,V2704 K5.6 Standard Upright Distribution Patterns—Trajectory 10' 3.0m CCC333�. • •... � N 444. 8. . 2.4m •`• `♦• •`• ..4. 6' ♦N .♦ 7 psi .... 1... ' ' 48 kPa 1.8m �. `♦♦ ♦ 15 psi •�• ♦♦♦ 4 ♦• 103 kPa 7.2m \ 44 `• 30 psi \ '• 207 kPa • 44 2' 444 •` •• •• 2 4' 6' 8' 10' 12' 14' 16' 0.6m 1.2m 1.8m 2.4m 3.0m 3.7m 4.3m 4.9m NOTES: A. Data shown is approximate and can vary due to differences in installation. B.These graphs illustrate approximate trajectories,floor-wetting,and wall-wetting patterns for these specific Victaulic FireLock Automatic Sprinklers.They are provided as information for guidance in avoiding obstructions to sprinklers and should not be used as minimum sprinkler spacing rules for installation.Refer to the appropriate NFPA National Fire Code or the Authority Having Jurisdiction for specific information regarding obstructions,spacing limitations and area of coverage requirements.Failure to follow these guidelines could adversely affect the performance of the sprinkler and will void all Listings,Approvals and Warranties. C. All patterns are symmetrical to the centerline of the waterway. 40.10 2544 Rev.J Updated 07/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 5 ✓ctaulic' victaulic.com I Sprinklers I FireLock® I K5.6, V27 I Publication 40.10 Ratings: Available Wrenches: All glass bulbs are rated for temperatures from -67°F ( 55°C) to those shown in the table below. V27-2 V27 Recessed Open End Temperature—°F/°C V2707,V2708 Pendent V V Maximum V2707,V2708 Recessed Pendent ,/ Sprinkler Victaulic Nominal Ambient Glass - Temperature Part Temperature Temperature Bulb V2703,V2704 Upright ✓ Classification Identification Rating Allowed Color Ordinary A 135°F/57°C 100°F/38°C Orange Ord nary C,, 155°F# °Ci1 f/ 8°CRed' Intermediate E 175°F/79°C 150°F/65°C Yellow Intermediate F 200°F/93°C 150°F/65°C Green High J 286°F/141°C 225°F8/107°C Blue Extra High 7 K 360°F/182°C 300°F/149°C Purple M Open — No Bulb 7 Standard response only. 8 150/65 if wax coated. .:�. tn:-•:.....,; ,,'_.,u.:ec'::-�=r;u�..n'. t:;a;,.;::,::. ::..�,cv..�.:,r�rr.,s;;:�ca:®=:-�v.....;.;:..w �. ,z .... ..,.. ... .5... ..rs ..5 ..., <s.z•xeix..�;v€n„�,:r'"':°uSi==:ate„^�.;..�•:,.;;?:;.3p'at,�;.�:::::::;�;:s.•°..-xe.. :. .,_ „_..- ,... e., ....�;„ „ n.., ;, ,„ .,..�.....:. .......:... ......_..,. ,... :•u•:f.:s..::z3:•ra.-s���'r`�:;fi=.a:::'#..:.;,_::........::::.:. ;�•:::::.„ a,:•.-sts:..-sj... 3„ ,... :: : .. ,a:eE• :•.^s.. ...a s•a..:, .... u ,>._„ ..ab .a "f'' ais �:;a,: ;��:�.:„;':0's:zurce2rii...iE'�v ,....:•.•n:••'.,i:.:••..:mr'?:sz••c,„. a ER >± - _.. ..:.+ s::•:e..:s:„ru:3:: 3 � _:,.,.i?s. " .: ::.. a`:i j.:ro..,z, • _ • Always read and understand installation,care,and maintenance instructions, supplied with each box of sprin- c klers, before proceeding with installation of any sprinklers. • Always wear safety glasses and foot protection. • Depressurize and drain the piping system before attempting to install, remove, or adjust any Victaulic piping 11?� products. • Installation rules, especially those governing obstruction, must be strictly followed. • Painting, plating,or any re-coating of sprinklers(other than that supplied by Victaulic) is not allowed. 0 Failure to follow these instructions could result in serious personal injury and/or property damage. The owner is responsible for maintaining the fire protection system and devices in proper operating condition. For minimum maintenance and inspection requirements, refer to the current National Fire Protection Association pam- phlet that describes care and maintenance of sprinkler systems. In addition, the authority having jurisdiction may have additional maintenance,testing,and inspection requirements that must be followed. If you need additional copies of this publication, or if you have any questions about the safe installation of this ^ product, contact Victaulic World Headquarters: P.O. Box 31, Easton, Pennsylvania 18044-0031 USA,Telephone: ` 001-610-559-3300. nI1 - - Installation Reference should always be made to the 1-40 Victaulic FireLock Automatic Sprinklers Note p This product shall bec manufactured by Victaulic c or to Victaulic assembly tr All noducts Installation and Maintenance Sheet for the product you are installing.This installation sheet to be installed in accordance with current Victaulic installation/assembly instructions. is included with each shipment of Victaulic products for complete installation and assembly Victaulic reserves the right to change product specifications,designs and standard data,and is available in PDF format on our website at victaulic.com. equipment without notice and without incurring obligations. Warranty Trademarks Refer to the Warranty section of the current Price List or contact Victaulic for details. Victaulic is a registered trademark of Victaulic Company. 40.10 2544 Rev.J Updated 07/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 6 ✓Ctaulic' Victaulic° Vic-FIexTM Sprinkler Fittings ✓ctaulic' Series AH2 and AH2-CC Braided Flexible Hoses 10.85 . Flex TM SertesAH2 Series AH2-CC 1.0 PRODUCT DESCRIPTION Available Sizes by Component • Series AH2 Braided Hose: 31, 36, 48, 60, 72"/790, 914, 1219, 1525, 1830 mm. Note: length includes adapter nipple and 5.75"/140 mm straight reducer. • Series AH2-CC Braided Hose: 31, 36, 48, 60, 727790, 914, 1219, 1525, 1830 mm. Note: length includes captured coupling and 5.75"/140 mm straight reducer. • Sprinkler Reducers: 1/" and 3/4715 and 20 mm sprinkler connections and 5.75, 9, 13"/140, 230, 330 mm straight lengths and short, long 90°elbows. Note: The short 90° elbow is typically used with concealed sprinklers while the long 90°elbow is typically used in the installation of recessed pendent sprinklers. • Inlet Connections: • 1"/25 mm Grooved IGS • 1"/25 mm NPT or BSPT adapter nipples for attaching to pipe and fittings outlined in NFPA standards. • 3/4720 mm NPT or BSPT adapter nipples available for VdS. • 1 1/47 32mm BSPT adapter nipples available for LPCB. • Brackets: • Style AB1 for suspended and hard-lid ceilings, allows installation before most ceiling tiles in place • Style AB2 for suspended and hard-lid ceilings, allows for vertical sprinkler adjustment, and installation before most ceiling tiles in place • Style AB3 for surface mount applications, wood, metal and block walls • Style AB4 for hard-lid ceilings with hat furring channel grid systems, allows for vertical sprinkler adjustment • Style AB5 for hard-lid ceilings, allows for vertical sprinkler adjustment • Style AB7 for suspended and hard-lid ceilings • Style AB7 Adjustable for suspended and hard-lid ceilings • Style AB8 for hard-lid ceilings with CD 60/27 profile metal studs (regionally available) • Style AB9 for hard-lid ceilings with hat furring channel grid systems • Style AB10 for Armstrong®TechZoneTM ceilings Maximum Working Temperature • 225°F/107°C ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION,MAINTENANCE OR SUPPORT. System No. Location Spec Section Paragraph Submitted By Date Approved Date victaulic.com .........._.......... 10.85 5839 Rev Z Updated 10/2016 ©2016 Victaulic Company.All rights reserved. 1 ✓ctaulIc victaulic.com 1.0 PRODUCT DESCRIPTION (Continued) Maximum Working Pressure • 200 psi/1375 kPa (FM Approval) • 175 psi/1206 kPa (cULus Listed) • 1600 kPa/232 psi (VdS/LPCB Approved) Connections • To adapter nipple (inlet) via • 1"/25.4 mm Grooved IGS • 1"/25.4 mm NPT or BSPT male thread • 3/4720 mm BSPT male thread (VdS only) • 11/4732 mm BSPT male thread (LPCB only) • To sprinkler head (outlet) via 1/2" or 3/4715 mm or 20 mm Minimum Bend Radius • 77178 mm (FM Approval) • 2"/51 mm (cULus Listed) • 3776.2 mm (VdS/LPCB Approved) Maximum Allowable Sprinkler K-Factors • FM (1/2"/15mm reducer) K5.6/8,1 (S.I.), (3/4"/20mm reducer) K14.0/20,2 (S.I.) • cULus (1/2"/15mm reducer) K8.0/11,5 (S.I.), (3/4"/20mm reducer) K14.0/20,2 (S.I.) • VdS/LPCB (1/2"/l5mm reducer) K5.6/8,1 (S.I.), (3/4"/20mm reducer) K8.0/11,5 (S.I.) 2.0 CERTIFICATION/LISTINGS ® 4� US VdS LPCB LISTED 10.85 5839 Rev Z Updated 10/2016 ©2016 Victaulic Company.All rights reserved. victaulic.com 2 jctau is victaulic.com • 3.0 SPECIFICATIONS - MATERIAL Series AH2 • Flexible Hose: 300-series Stainless Steel • Collar/Weld Fitting: 300-series Stainless Steel • Gasket Seal: Victaulic EPDM • Isolation Ring: Nylon • Nut and Nipple: Carbon Steel, Zinc Plated • Reducer (1/2'/15 mm or 3/4'"/20 mm): Carbon Steel, Zinc-Plated Brackets: Carbon Steel, Zinc-Plated Series AH2-CC • Flexible Hose: 300-series Stainless Steel • Collar/Weld Fitting: 300-series Stainless Steel • Gasket Seal: Victaulic EPDM • Isolation Ring: Nylon • Nut and Nipple: Carbon Steel, Zinc Plated • Reducer (1/2715 mm or 34'"/20 mm): Carbon Steel, Zinc-Plated • Housing: Ductile iron conforming to ASTM A 536, Grade 65-45-12. Ductile iron conforming to ASTM A 395, Grade 65-45-15, is available upon special request. Coupling Housing Coating: • Orange enamel (North America, Asia Pacific). • Red enamel (Europe). • Hot dipped galvanized. Gasket:' • Grade "E" EPDM (Type A) FireLock EZ products have been Listed by Underwriters Laboratories Inc., Underwriters Laboratories of Canada Limited, and Approved by Factory Mutual Research for wet and dry (oil free air) sprinkler services within the rated working pressure. 1 Services listed are General Service Guidelines only.It should be noted that there are services for which these gaskets are not compatible.Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service guidelines and for a listing of services which are not compatible. • Bolts/Nut: Zinc electroplated carbon steel, trackhead meeting the physical and chemical requirements of ASTM A 449 and physical requirements of ASTM A 183. • Linkage: CrMo Alloy Steel zinc electroplated per ASTM B633 Zn/Fe 5, Type III Finish 10.85 5839 Rev Z Updated 10/2016 ©2016 Victaulic Company.All rights reserved. v ctaulic.com 3 jctaullic" victaulic.com • 4.0 DIMENSIONS • Product Details- Series AH2 Braided Hose Item Description 1 Flexible Hose O O ® Q © © O 2 Isolation Rin. 3Gasket 4 Nut ]�► 5 Adapter Nipple i - '!r� du u 6 Braid A7 Collar/Weld'Fitting B 8 Sleeve Hose Length Dimensions Hose Length A B inches inches inches mm mm mm 31/790 25.3/641 31/790 36/915 31.3/794 36/915 48/1219 42.3/1073 48/1220 60/1525 54.3/1378 60/1525 72/1830 66.3/1683 72/1830 Series AH2-CC Braided Hose Item Description 10 0 0 p ° 0 p © p 1 1 Flexible Hose �� �� -� `] 2 Isolation Rin. I I IIIILIIIIIIIIIIIIIIIIIIIIIIIIIII ` v 3 ® �11��1I�� munuunitunlunuunul 11 4 ` A 5 Ca.tured Cou.lin• B 6 Braid 7 Collar/Weld Fittin. Hose Length A B 8 Sleeve inches inches inches _ mm I mm mm 31/790 24.5/622 29.8/757 36/915 29.5/749 34.8/884 48/1219 41.5/1054 46.8/1189 60/1525 53.5/1359 58.8/1494 72/1830 65.5/1664 70.8/1798 Standard Reducer 2.627 --H 66.5 mm F— IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII��� 262^/ iI n F IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII 66.5 mm 5.75 7140 mm straight reducer ,,,„. I Optional Reducers 6sry 166.9 mm 4.83"/ _ _122.7 mm — _ IN . N 9.0"/229 mm straight reducer B MIN I 1 ( A-1.4 Short 90°elbow reducer Long 90°elbow reducer 13.0"/330 mm straight reducer NOTE • The Short 90°elbow reducer is typically used with concealed sprinklers while the longer 90 elbow is typically used in the installation of recessed pendent sprinklers. • FM/VdS Approved only. • 10.85 5839 Rev Z Updated 10/2016 ©2016 Victaulic Company.All rights reserved. • victaulic.com 4 ✓ctauhc victaulic.com • 4.1 DIMENSIONS • VicFlex Brackets Style AB1 • Suspended Ceilings Ifr • Hard-Lid Ceilings (FM Only) �I t Item Description �% 1 249610 mm or 48'/1220 mm Square Bar* 2 Patented Center Bracket --s .,.°' 3 End Bracket �y `Both sizes FM/VdS/LPCB approved,cULus listed O 0 i 0 Style ABS 9 • Suspended Ceilings • Hard-Lid Ceilings Item Description SI°10 1 24'7610 mmor 48'71220 mmSquare;Bar*. 2 Patented Vertically Adjustable Center Bracket 3 End Bracket Both sizes FM/VdS/LPCB approved,cULus listed O 3 oF Style AB3 • Surface Mount Applications I' • FM Approved Imo ` �I_� ,eito ' ` I/ II • • 10.85 5839 Rev Z Updated 10/2016 ©2016 Victaulic Company.All rights reserved. victaulic.com 5 ✓ctaulic' victaulic.com_ • • 4.2 DIMENSIONS VicFlex Brackets Style AB4 <0 • Hard-Lid Ceilings with Hat furring channel grid system (10 00 Item Description 1 24'%610 mm or 48"/1220mm'Square Bar* 40 2 Patented Vertically Adjustable Center Bracket 3 End Bracket for Hat Furring Channel Both sizes FM/VdS approved,cULus listed Style AB5 • Hard-Lid Ceilings 14 Item Description 1 24'/610mm or 48"/1220mm Square Bar* 2 Patented Vertically Adjustable Center Bracket .3 __ End Brackety j; 'Both sizes FM/VdS approved,cULus listed 1�'�� Style AB7 • Suspended Ceilings • Hard-Lid Ceilings 1" Item Description 1 24"/610 mm or 48"/1220 mm Square Bar* 2 Patented 1-Bee2®Center Bracket e 0 3 End Brackett' 'Both sizes FM/VdS approved. I/ Style AB7 Adjustable • Suspended Ceilings • Hard-Lid Ceilings Item Description p 1 700mm or 1400 mm Square Bar* 2 Patented 1-Beet®Center Bracket iP 0 3 End Bracket(adjustable) 'Both sizes FM/VdS approved. • • 10.85 5839 Rev Z Updated 10/2016 ©2016 Victaulic Company.All rights reserved. victaulic.com 6 ✓ctaulic victaulic.com • 4.3 DIMENSIONS • VicFlex Brackets Style AB8 • Hard Lid Ceilings % + Item Description 1 700mm or 1400mm Square Bar*, 2 Patented Vertically Adjustable Center Bracket 3 *Both sizes FMNdS 'Both sizes FM/VdS approved. Style AB9 • Hard-Lid ceilings with Hat furring channel grid system Item Description 1 24"/610mmor48"/1220 mm Square Bar* " � O 2 Patented 1-Beet®Center Bracket •�� 3 End Bracket for Hat Furring Channel 3 `Both sizes FM/VdS approved. Style AB10 • Suspended ceilings �� to v • Armstrong®TechZoneTM Item Description 1 6"/152 mm Square Bar* 2 Patented 1-Beet®Center Bracket 3 End Bracket 'FM/VdS approved,cULus listed. • • 10.85 5839 Rev Z Updated 10/2016 ©2016 Victaulic Company.All rights reserved. victaulic.com 7 ictaulac' victaulic.com_ 4.4 DIMENSIONS CLEARANCES ABOVE CEILING Series AH2 Braided Hose and Style AB1 Bracket Suspended Ceiling Grid with Recessed Sprinkler Suspended Ceiling Grid with Concealed Sprinkler / R / See chart \ / See h IMIMI MI See mart MS Bracket assemblyA . ii A Style AB1 _ See Chart r�7 11 1I e —_— 1,3amm �2.156n ie �.� ,I.�, _ I■�tT��MI_ Bracket Assembly NISI __ I� Style ABl 2"hs'/68.3 mm __ I' a..hale iffa —o—_ I 7i7i7irT� 0——._ 2n/,/603 mm I hole 1 `�� enecalm 1 �I U '. 44/113mm I I 1 c YP9 vie 1 1 7/4e3 mm / 11 = ltd) TYP aIc I'ng grd` a �1 �j l M. //15.9 mm I/ ltd �,�� ® II,I`�.II,1�,��.�/"� ■.�■ ( ii7II Nr Tl Pictile 1 M. 11 ( I See note ceing face `�J� T 1II 7743mmI Ill;, I g ., �� -�, 24/610 mm I. yplca gg'd �,�� iIl�l�i /®./ a 'i,r 0 48° 'tit _ / llA..�I /1219 mm Finished on Center See note 24"/610 mm or 48"/1219 mm c ling face on Center V2707 3/4"/19mm Max. Recess V38021/2"/12.7mm Max. Recess Hose Clearance Chart Hose Clearance Chart Dimension Dimension inches inches inches inches inches inches inches inches inches inches inches inches mm1mm mm mm mm mm _ mm mm mm mm mm mm R Minimum 2 3 4 5 6 7 Minimum 2 3 4 5 6 7 Bend Radius 50 80 100 125 150 175 R Bend Radius 50 80 100 125 150 175 A Min. 10.8 11.8 12.8 , 13.8 14.8 15.8 A Min. 10.1 11.1 12.1 13.1 14.1 15.1 273 299 324 349 375 400 269 281 307 333 1358 383 Suspended Ceiling Grid with Recessed Sprinkler with Suspended Ceiling Grid with Concealed Sprinkler with 90° Elbow (Long) 90° Elbow (Short) Bracket assembly,'I.'�I-I t 'I I''�I B1 1 �- Bracket Assembly See Chart _ Style A61 hart Ir = : i El- 11 � ��� m:enoiem II rris oolemSee Chart ol/ i a4/ i■ lP 1 ii IME2//60 mm' 44/ II rTl aim = �� a C` 11 e', .I 17"/43 ngtle 1. _ I //b m II N .' Tvo ice mgged�� If n, .. &_,-, �/43m / .11 tir11� Tv le g l 0- �.r�;�i� ,111•10, g�mleel g9rd, xmotioilliewojawweg Milire See note- — �In9 face riglieff /610 mm 1 ring farce or4/6109mm _ ;_ar 2'/60mm or on Center See note— as/t 3,9 mm on Center ^ V2707 3/a"/19mm Max. Recess V38021/2"/12.7mm Max. Recess Hose Clearance Chart Hose Clearance Chart Dimension Dimension I inches inches mm mm A Min. 8.0 i 5.8 200 A Min. 147 . . 10.85 5839 Rev Z Updated 10/2016 ©2016 Victaulic Company.All rights reserved. victaulic.com 8 jctaulac victaulic.com • 4.4 DIMENSIONS (Continued) • CLEARANCES ABOVE CEILING Series AH2 Braided Hose and Style AB2 Bracket Hard-lid Ceiling with Concealed Sprinkler Hard-lid Ceiling with Recessed Sprinkler 7 1 �nan� iart Tri -I— See chart O n mi lCS '_r8 cke emnly ' 2'x4"sNd� SYIe ABZ — B/ rim wog W ahs45im1 nos `eaaea.,semniy �rnllll �./ zwiea mm �— ► z /w mm a� 4• axunne ���' /, 9 n ie �'xa'RudOgg ,`E.@ III�-Ste �� ! .nsholem Z/ 0' / 2/5 n-e� J' 1•- 4}: Y 89 mm :'t�''\ dr••lelII iiiiiiigiiiii // 1%/ /// /JIri3L // !' ��._a= 9 04.. ! ! L l,1=1--. g30i:?ii}d r igiaia; Al l ldr I r/,, 'r r 4 'IP; yceding face 16/4195 rem stud UC 'FnuM1ed 1.-- - 16'/406mmstudVC— g race V3802 1/2712.7mm Max. Recess V2707 3/4'Y19mm Max. Recess Hose Clearance Chart Hose Clearance Chart Dimension Dimension inches inches inches inches inches inches inches inches inches inches inches inches mm mm mm mm mm mm mm mm mm mm mm mm R Minimum 2 3 4 5 6 7 R Minimum 2 3 4 5 6 7 Bend Radius 50 80 100 125 150 175 Bend Radius 50 80 100125 150 175 } A Min. 7.6 8.6 9.6 10.6 11.6 12.6 1 6.1 7.1 8.1 9.1 10.1 11.1 193 218 ; 244 269 , 295 320 ( A Min. i 155 180 206 231 256 282 NOTE • Variations of ceiling grids,sprinkler heads, brackets,and hoses are permitted but may result in clearance differences from the figures above. Hard-lid Ceiling Grid with Concealed Sprinkler with Hard-lid Ceiling with Recessed Sprinkler with 90° Elbow (Short) 90° Elbow (Long) ,iII:I #01 T see hart 19/ sse,nv qv, s nan 2x4S1utl, �j / 7E-11-0 - SYI nN ■ _rfi k tun I�� : f� 1 — ` OS rS YIekAB2S4embIY _ B2Yaa/66 hole mm _ oie mm e9s m z /s9 mm /so n 1 tat e _" /ill 1' a an HI alp LAG %//. /11 41 14 Y 011 / . /.IIt I ll._, •.- �I i i , I I-� I -<r4ocnmslndoc - —I �'- r// /; III 1.41 II tifte lig /.///i" ./'/1.' ' /A11,al i -4— —1e'/4195 rumsmd oC ceilmo race V3802 1/2'Y12.7mm Max. Recess V2707 3/"/19mm Max. Recess Hose Clearance Chart Hose Clearance Chart Dimension Dimension inches I, inches - mm mm 5.0 I A Min. . A Min. 9.6 I 127 • • 10.85 5839 Rev Z Updated 10/2016 ©2016 Victaulic Company.All rights reserved. victaulic.com 9 ✓ctaulic' victaulic.com • 4.5 DIMENSIONS ' CLEARANCES WITHIN SIDEWALL Series AH2 Braided Hose and Style AB2 Bracket Horizontal Sidewall Sprinkler Horizontal Sidewall Sprinkler with 90° Elbow (Long) art M ._ See chart ,II:I 11 : =p105 B k • A el assembly x4Slutl� = Sryle AB2 Al/ lg°/ See chart �� — I'� 187 45 mmo PIOS w Bracket assembly , 23/."/60 mm — � we A. Smm tl ., , ........ ....... _ a hole —ry _ / I�� /F.5 m r — - 4 t� /fi m B9 mm ,._2.„,„ \� I� n h e = 8 hole g9 / ling facet. L_ �Flmsned Ell)16"/406 mm Stud(/C _i NE ening lace ME V2707 mm Stud GC V2707 3/"/19mm Max. Recess V2707 3/4"719mm Max. Recess Hose Clearance Chart Hose Clearance Chart Dimension Dimension inches inches inches inches inches inches inches mm mm mm mm mm mm mm R Minimum 2 3 4 5 6 7 Bend Radius 50 80 100 125 150 175 A Min. 3.6 91 A Min. 6.1 7.1 1 8.1 9.1 10.1 111.1 i 155 180 ; 206 231 1 256 282 J • • 10.85 5839 Rev Z Updated 10/2016 ©2016 Victaulic Company.All rights reserved. victaulic.com 10 �Ctaulic victaulic.com • 4.6 DIMENSIONS • CLEARANCES ABOVE CEILING Series AH2 Braided Hose and Style AB4 Bracket Hat Furring Channel Grid with Recessed Sprinkler fi see mai/ EN �7 Imo _ _ see cnan Il .II_� maaxbo mm _ 'WI' nnie F__ 1.z-/n1 mml 11'''l t -.nage tf �r . seenote_ T,,,,,r6"/40bmm— Seillnytlle ceiling ,-: .,+� 6i0mm on Center �/e"23 mmJ i.�� Typical ceiliny gritl V2707 3/4"/19mm Max. Recess Hose Clearance Chart Dimension inches inches inches inches inches inches mm mm mm mm mm mm R Minimum 2 3 4 5 6 7 Bend Radius 50 80` 100 125 150 175 A Min. 10.3 11.3 12.3 13.3 14.3 15.3 262 287 313 338 363.5 389 Hat Furring Channel Grid with Recessed Sprinkler with Hat Furring Channel Grid with Concealed Sprinkler with 90° Elbow (Long) 90° Elbow (Short) 01101:. � �� 1_, dna [■ y. �I� m''boopm b P,-- I ;'nale' — b 6i,m nnle \tt 6mm 1 ® /� mm eYpca i V 'D g41r71� ��i.. 1 - z Typi y iggi see noieJ �. — -� m- c rngra�e rz3 �`■� f .. „/i; // snea /dF- D/' �'.<�rLi p a 16'/0'n R Typi�l ceiling gritl `- ce-!ng hce 24"/6,Omm Cen2r `= S. om fi/406m i, '/e'/L1 m,_ /4'/610 mmon Cenrer - ypicalcelringgAtl 3 " V2707 /a/19 mm Max. Recess 3 V2707 /a/19 mm Max. Recess' Hose Clearance Chart y Hose Clearance Chart ti Dimension W Dimension inches mm inches A Min. 8 mm 200 A Min. 5.9 149 NOTE • Variations of ceiling grids,sprinkler heads,brackets,and hoses are permitted but may result in clearance differences from the figures above. • • 10.85 5839 Rev Z Updated 10/2016 ©2016 Victaulic Company.All rights reserved. victaulic.com 11 ✓ctauhc" victaulic.com 4.6 DIMENSIONS (Continued) CLEARANCES ABOVE CEILING Series AH2 Braided Hose and Style AB5 Bracket Hard-lid Ceiling with Recessed Sprinkler t r ' See pM1an See'chart rt MN ME v gee art iSra �(�%. r-Bracket assembly , See.. '.,r/ _co,—re /Sryle AOs V9,11 ,,��, rBracket assembly �� S)mm _p ,,s _ / Sryle Ads I, P w '1�1� 77'1 �'f I�- 2/e/EO mm �'I 2.re I 2 /mole .,fel AZIO l ma,:_, rf ���1 r �sT�,m snp� : : ' : �- rr iiiiiigigii _ as m i+ NM it 2� tr 'i rt r. – E 7//l ✓/ ::r r�lGil��ih����/�/' , /% % 1� i�'x4-- 1 2 mirth_,!! liggmm Typ.Drywall nisM1ed 16"'/40fim Sud C/0----, fng(a<e kik // m Finished 19 MMIIMPP yp D,ywall 16"/90B mm Stud C/C—�. , Ming face V2707 3/4"/19mm Max. Recess V3802 1/2"/13mm Max. Recess Hose Clearance Chart Hose Clearance Chart Dimension 1 Dimension inches inches inches inches inches inches inches inches inches inches inches inches mm mm mm mm mm mm mm mm mm mm mm mm R Minimum 2 3 4_. 5 _ . 6._. ._7 , R .- Minimum 2 3 4 5 6 7 Bend Radius 50 80 100 125 150 175 Bend Radius 50 80 100 125 150 175 A Min. 6.1 7.1 8.1 9.1 10.1 11.1 7.6 8.6 9.6 10.6 11.6 12.6 155 180 206 231 1 256 282 A Min. 193 218 244 269 295 320 , Recessed Pendent with 90° Elbow (Long) Hard-lid Ceiling with Concealed Pendent with 90° Elbow (Short) 0111111 ties , jr-i_i ip 1 A ' I...... kr. hna� � liafivrs – &AN mr . t r = �sm re rr ,St ■■ TDfi1 {i.. . if � 11 A< iL � ywa � i s ...-t.__roEm/ %ilg ' l e/ S 1� ' ►,i ��i 'O / f . li vIzmir 8 V2707 3/4"/19mm Max. Recess V3802 1/2"/13mm Max. Recess Hose Clearance Chart Hose Clearance Chart Dimension 1 Dimension inches inches mm A Min. 3.6 mm 91 A Min. 3.3 84 NOTE • Variations of ceiling grids,sprinkler heads,brackets,and hoses are permitted but may result in clearance differences from the figures above. • • 10.85 5839 Rev Z Updated 10/2016 ©2016 Victaulic Company.All rights reserved. victaulic.com 12 ✓ctaulhc' victaulic.com • 4.6 DIMENSIONS (Continued) • CLEARANCES ABOVE CEILING Series AH2 Braided Hose and Style AB3 Bracket Surface Mount Application with Recessed Sprinkler A 33/4"/ - - 95.3mm I:0= - See Note A LJ 23/8"/60 mm max.hole 2"/51 mm min.hole Hose Clearances Wall Thickness "A" 2 4 6 8 10 2 4 6 8 10 50 100 150 200 250 50 100 150 200 250 Outlet Length 5.75 9 13 5.75 9 13 9 13 13 13 5.75 9 13 5.75 9 13 9 13 13 13 °B° 146.1 228.6 330.2 146.1 228.6 330.2 228.6 330.2 3302 3302 146. 228.6'330.2 146.1 228.6 330.2 228.6'3302 330.2 330.2 Hose 11.6 14.8 18.8 9.6 12.8 16.8 10.8 14.8 12.8 10.8 12.6 15.8 19.8 10.6 13.8 17.8 11.8 15.8 13.8 11.8 Clearance°C" 294 376 478 243 325 427 275 376 325 275 319 402 503 268 351 452 300 402 351 300 Bend Radius 7 8 R" 175 200 NOTE • Variations of ceiling grids,sprinkler heads,brackets,and hoses are permitted but may result in clearance differences from the figures above. • See installation instructions for mounting screw type and size. • • 10.85 5839 Rev Z Updated 10/2016 ©2016 Victaulic Company.All rights reserved. victaul c.corre 13 ✓ctaulic' victaulic.com 4.7 DIMENSIONS BRANCHLINE CLEARANCES Series AH2 Braided Hose with female threaded outlet Series AH2-CC Braided Hose with grooved outlet R See chart R :: See chart '-' IIIIEI - .. See chart See chart Il iir 4.07-8 -Nvi,Nto\ IIFemale Threaded Weld Outlet C U No.142 /...-.0.--Wa.....---. Grooved Weld Outlet � v mi 2750mm Sch.40 Branch Pipe 2mm Sch.40/50 Branch Pipe Hose Clearance Chart Hose Clearance Chart Dimension i Dimension inches inches inches inches inches inches inches inches inches inches inches inches mm mm mm 1 mm mm mm ! mm mm mm mm mm mm , R Minimum 2 3 4 5 6 7 Minimum 2 3 4 5 6 7 E Bend Radius 50 80 100 125 150 175 R Bend Radius 50 80 100 125 150 175 ' A Min. 8.4 9.4 10.4 11.4 12.4 13.41 7.1 8.1 9.1 10.1 11.1 12.1 214 1 239 264 1 290 315 341 A Min. 180 205 231 256 281 307 • 10.85 5839 Rev Z Updated 10/2016 ©2016 Victaulic Company.All rights reserved. victaulic.com 14 iictaulic victaulic.com 4.7 DIMENSIONS (Continued) • BRANCHLINE CLEARANCES Series AH2 Braided Hose with Style 922 threaded outlet Series AH2-CC Braided Hose with Style 922 grooved outlet 1111, I See chart ME if!ffil oi�i�i� ASee c .. See chart III .1. A See chart �- 0.0 III i • jj M Style 922 Threaded �jyp~ O Mechanical Tee i� --)N. Outlet �����-- Style 922 / � Grooved � 11- .� � �\\ Mec Outlet)Tee ,,,, � mu /psi ! �► i � �� 2"/Br mm �� Sch.40 Branch Pipe 2"/50 mm \��/ Sch.40 Branch Pipe Hose Clearance Chart Hose Clearance Chart Dimension Dimension inches inchesiinches inches inches inches inches inches inches inches inches inches mm mm_ mm mm mm mm mm mm mm mm mm mm R Minimum 2 3 4 5 6 7 R Minimum 2 3 4 5 6 7 Bend Radius 50 . 80 100 125 150 175 Bend Radius 50 80 100 125 150 175 A Min. 8.4 9.4 10.4 11.4 r 12.4 13.4 6.7 7.7 8.7 9.7 10.7 11.7 212 238 j 263 289 314 339 A Min.I 171 197 222 247 273 298 • • 10.85 5839 Rev Z Updated 10/2016 ©2016 Victaulic Company.All rights reserved. victaulic.com 15 ✓ctaulic' victaulic.com • 5.0 PERFORMANCE — FRICTION LOSS DATA • cMos Series AH2 and AH2-CC Braided Hoses with Straight 5.757140 mm Reducers usrm Style AB1, AB2, AB4, AB5 and AB10 Brackets Series AH2 Hose Length of Maximum Equivalent Length Number of Stainless Steel of 1'/33.7 mm 90°Bends at 2"/51 mm Flexible Hose Outlet Size Sch.40 Pipe(C=120) Bend Radius inches/mm inches/mm/type feet/meters 31/775 'Lz"/15/Strai.ht 16/4.9 4 ; /20/Strai.ht 17/5.2- 4 36/900 1/2"/15/Strai•ht 21/6.4 5 3/4"/20/Strai•ht 23/7.0 5 48/1200 '/z'/15/Strai.ht 32/9.8 8 3/4"/20/Strai.ht 37/113 8 60/1500 '/z"/15/Strai•ht 46/14.0 10 3/4"/20/Strai•ht 46/14.0 10 72/1800 '"/15/Strai.ht 55/16.8 12 3/4"/20/Strai•ht 53/16.2 12 Series AH2 and AH2-CC Braided Hoses Equivalent Length Design Guide Equivalent length values at various numbers of 90 degree bends at 2751 mm center line bend radius Length of Stainless Steel Flexible Outlet 1 2 3 4 5 6 7 8 9 10 11 12 Hose Size Bend Bends Bends Bends Bends Bends Bends j Bends Bends Bends Bends Bends inches/ inches/ feet/ feet/ , feet/ feet/ I feet/ feet/ feet/ feet/ feet/ feet/ feet/ feet/ mm mm meters meters meters meters meters meters meters meters ' meters meters meters meters 31/775 1/2"/15 8.5/2.6 11.0/3.4 13.0/4.0 16.0/4.9 N.A N.A N.A N.A N.A 3/4"/20 10.0/3.0 12.5/3.8 14.0/4.3 17.0/5.2 NA IIMINIENI NA NA NA NA NA 36/900 1/2'715 13.5/4.1 16.0/4.9 18.0/5.5 19.0/5.8 21.0/6.4 IIIMMinalliElMICEMINEIMIN.A N.A 3/4"/20 14.0/4.3 17.0/5.2 19.5/5.9 20.0/6.1 23.0/7.0 1113311111321111MEMIMUM N.A N.A 48/1200 1/2x'/15 15.5/4.7 17.0/5.2 19.5/5.9 20.0/6.1 21.0/6.4 22.0/6.7 28.0/8.5 32.0/9.8 N.A N.A N.A 3/4"/20 17.0/5.2 19.0/5.8 21.5/6.6 24.5/7.5 26.0/7.9 27.0/8.2 30.0/9.1 37.0/11.3 NA NA NA NA 60/1500 1/2"/15 21.5/6.6 24.0/7.3 27.0/8.2 28.5/8.7 30.0/9.1 31.0/9.4 37.0/11.3 42.0/12.8 44.0/13.4 46.0/14.0 N.A N.A • 3/4720 23.0/7.0 24.0/7.3 28.0/8.5 ' 29.5/9.0 30.5/9.3 31.0/9.4 38.0/11.6 42.0/12.8 44.0/13.4 46.0/14.0 N.A N.A 72/1800 1/2'715 30.0/9.1 32.0/9.8 36:5/11.1 EOM 40.5/12.5 41.0/12.8 42.0/12.8 46.0/14.0 49.0/14.9 52.0/15.8 54.0/16.5 55.0/16.8 3/4"/20 32.0/9.8 32.5/9.9 35.0/10.7 35.5/10.8!40.0/12.3 40.5/12.3 41.0/12.5 46.0/14.0 50.0/15.2 51.0/15.5 52.0/15.8 53.0/16.2 NOTES: • Values for use with 5.757140 mm straight reducers. How to use this Design Guide: • For some systems,it may be advantageous for the designer to calculate the system hydraulics using shorter equivalent lengths associated with fewer than the maximum allowable number of bends. In this case,the designer may select a design number of bends for the job and use the associated equivalent length from the design guide to determine the system hydraulics. • It is possible that the actual installed condition of some of the flexible drops may have more bends than the designer selected.When this happens,the design guide may be used to find equivalent lengths based on the actual installed number of bends for particular sprinkler installations.The system hydraulics can be recalculated using actual equivalent lengths to verify the performance of the system. • • 10.85 5839 Rev Z Updated 10/2016 ©2016 Victaulic Company.All rights reserved. victaulic.com 16ictauiac victaulic.com • • 5.1 PERFORMANCE— FRICTION LOSS DATA ® Series AH2 and AH2-CC Braided Hoses Style AB1, AB2, AB3, AB4, AB5, AB7, AB7 Adj., AB8, AB9 and AB10 VicFlex Brackets Series AH2 Hose Maximum Length of Equivalent Number Stainless Steel Length of of 90°Bends Flexible Hose ee Outlet 1"/33.7mm at 7'7178mm K-Factor Size Sch.40 Pipe Bend Radius inches/mm Imperial/S.I. inches/mm/type feet/meters 31/775 5.6/8.1 1/2"/15/Straight 23.5/7.1 1/2715/90°Elbow 235/7_1 2 36/900 5.6/8.1 1h"/15/Straight 27.8/8.5 1/2715/90°Elbow 25.6/7.8 2 48/1200 5.6/8.1 1/2715/Straight 38.2/11.6 1/2715/90°Elbow 30.7/9.3 3 60/1500 5.6/8.1 1/2715/Straight 42.4/12.9 1/2"/15/90°Elbow 35.9/10.9 4 72/1800 5.6/8.1 1/2715/Straight 46.6/14.2 /15/90°Elbow 41.1/12.5 4 1 31/775 8.0/11.5 3/4"/20/Straight 16.8/5.1 3/4720/90°Elbow 16.8/5.1 2 36/900 8.0/11.5 3/4720/Straight 20/6.0 3/4720/90°Elbow - 19.7/6:0 2 48/1200 8.0/11.5 3/4"/20/Straight 27.8/8.4 3/4"/20/90°Elbow 26.6/8.1 3 60/1500 8.0/11.5 3/4720/Straight 35.7/10.9 3/4720/90°Elbow 33.6/10.2 4 72/1800 8.0/11.5 I 3/4720/Straight 43.5/13.2 3/4"/20/90°Elbow 40.6/12.2 4 31/775 11.2/16.1 3/4720/Straight 16.5/5.0 3/4720/90°Elbow 17.8/5.4 2 36/900 11.2/16.1 3/4"/20/Straight 19.5/5.9 3/4"/20/90°Elbow 20.7/6.3 2 48/1200 11.2/16.1 3/4"/20/Straight 26.7/8.1 3/4"/20/90°Elbow 27.9/8.5 3 60/1500 11.2/16.1 3/4720/Straight 33.9/10.3 3/4"/20/90°Elbow 35/10.7 4 72/1800 11.2/16.1 3/a"/20/Straight 41.3/12.5 3/4"/20/90°Elbow 42.2/12.8 4 31/775 14.0/20.2 3/4"/20/Straight 14.9/4.5 3/4"/20/90°Elbow 15.5/4.72 2 36/900 14.0/20.2 3/4"/20/Straight 19.4/5.9 3/4"/20/90°Elbow 19.6/5.9 2 48/1200 14.0/20.2 34"/20/Straight 30.3/9.2 3/4"/20/90°Elbow 29.5/8.9 3 60/1500 14.0/20.2 3/4720/Straight 33.9/10.3 3/4"/20/90°Elbow 34.1/10.4 4 72/1800 14.0/20.2 3/4720/Straight 37.5/11.4 3/4720/90°Elbow 38.6/11.7 4 FM NOTES: • Series AH2 has been tested and Approved by FM Global for use in wet,dry and preaction systems per NFPA 13, 13R,and 13D and FM data sheets 2-0,2-5, and 2-8. FM 1637 and Vds standards for safety include,but are not limited to,pressure cycling,corrosion resistance,flow characterisitics,vibration resistance, leakage,mechanical and hydrostatic strength. • Differences in equivalent lengths are due to varying test methods,per FM 1637 and VdS standards.Refer to these standards for additional information regarding friction loss test methods. • EXAMPLE:A 48-inch hose installed with two 30°bends and two 90°bends at a 7-inch bend radius is permitted and considered equivalent to the data in the table shown above.In this example,the total number of degrees is 240°,which is less than the allowable 270°. • • 10.85 5839 Rev Z Updated 10/2016 ©2016 Victaulic Company.All rights reserved. victaulic.com 17 ictaulIc victaulic.com 5.2 PERFORMANCE — FRICTION LOSS DATA • (VdS Series AH2 Braided Hose Style AB1, AB2, AB4, AB5, AB7, AB7 Adj., AB8, AB9, and AB10 Brackets Series AH2 Hose Equivalent Length of Maximum Number Length of steel pipe according to of 90°Bends at Stainless Steel Outlet EN 10255 DN 25 3'776.2mm Bend Flexible Hose Size (33,7 x 3,25) Radius mm/inches mm/inches type meters/feet meters/feet 775/31 15mm/1/2"/Straight 20 mm/3/a"/Straight 5.5/18.0 3 900/36 15mm/1/2"/Straight 20 mm/3/4"/Straight 6.4/21.0 3 1200/48 15mm/1/z"/Straight 20 mm/ala"/Straight 8.5/279 3 1500/60 15mm/1/2"/Straight 20 mm/3/4"/Straight 10.7/35.1 4 1800/72 15mm/'h"/Straight 20 mm/3/a"/Straight 12.8/42.0 4 VDS CEILING MANUFACTURERS LIST AB1,AB2,AB7,AB10 AB4/9 AB8 1.AMF No specific approval 1.Hilti 2.Armstrong 2.Knauf 3.Chicago Metallic 3.Lafarge 4.Dipling 4.Lindner 5.Durlum 5.Rigips 6.Geipel 7.Gema-Armstrong 8.Hilti 9. Knauf 10.Lafarge 11.Linder 12.Odenwald 13.Richter 14.Rigips 15.Rockfon Pagos 16,Suckow&Fischer 17.USG Donn LPCB Series AH2 Braided Hose Style AB1 Bracket Series AH2 Hose Series AH2 Hose Length of Equivalent Length Maximum Length of Equivalent Length Maximum Stainless of steel pipe Number of Stainless of steel pipe Number of Steel according to 90°Bends at Steel according to 90°Bends at Flexible Outlet EN 10255 DN 25 3'776.2mm Flexible Outlet EN 10255 DN 25 3'/76.2mm Hose Size (33,7 x 3,25) Bend Radius Hose Size (33,7 x 3,25) Bend Radius mm/inches mm/inches/type _ meters/feet mm/inches mm/inches/type meters/feet 775/31 15mm/1/2"/Straight 15mm/'/2"/90°Elbow 20 mm/3/a"/Straight 1.8/6.0 2 775/31 1.3/4.3 2 20 mm/3/4'/90°Elbow 900/36 15mm/'/2"/Straight 15mm/Y2"/90°Elbow 20 mm/3/a"/Straight 3.6/11.9 3 900/36 2.8/9.1 3 20 mm/3/4"/90°Elbow 1200/48 — 15mm/'/z"/Straight 15mm/'h"/90°Elbow 20 mm/3/a"/Strai ht 4.3/14.0 3 1200/48 4.1/13.4 3 g 20 mm/3/4"/90°Elbow 1500/60 15mm/1/2"/Straight 15mm/1/z"/90°Elbow 20 mm/3/a"/Straight 4.1/13.6 3 1500/60 20 mm/3/4"/90°Elbow 4.6/15.2 3 1800/72 15mm/1/2"/Straight 15mm/'h"/90°Elbow 20 mm/3/4"/Straight ht 5.5/18.1 3 1800/72 5.3/17.4 3 20 mm/3/4790°Elbow • • 10.85 5839 Rev Z Updated 10/2016 ©2016 Victaulic Company.All rights reserved. victaulic.com 18 ✓ctaulia victaulic.com • 6.0 NOTIFICATIONS • 3 3 s" 'Hx'i:•wc4ia.,...'^.cwr.C.::s:z::,•nss:::^::,. E6.............._,s......,a,_.....•v...., r..,....,C=%.s:•u;::riycs: ...._. ... ... ..., _.....;,;rx:u::-:::;@nrz;{is33s iEzi?iics:::::»isii:(i{=^°E:iEE`sr;;EFo's:'.^.%4Ei�e56nSivEi:•:::•::::.^:ii's, ...o-...ns.• ,.,x„.... .......... ........s. b... .uz...... .,........ ....._,......_,. .,..... ..............,. ,....._....nci^:i;�:i°i£^xvsipun5:i • It is the responsibility of the system designer to verify suitability of 300-series stainless steel flexible hose for use with the intended fluid media within the piping system and external environments. • The effect of chemical composition, pH level, operating temperature, chloride level, oxygen level, and flow rate on 300-series stainless steel flexible hose must be evaluated by the material specifier to confirm system life will be acceptable for the intended service. Failure to follow these instructions could cause product failure, resulting in serious personal injury and/or property damage. 7.0 REFERENCE MATERIALS —CHARACTERISTICS Flexible Hose In-Plane Bend Characteristics One Bend Two Bends Three Bends w 2X 2X Minimum Minimum Minimum bend radius bend radius 1 bend radius --�, I I Minimum OR OR bend radius `Y __ i Minimum I Minimum I bend radius Minimum bend radius bend radius Minimum _— bend radius \ \ Minimum I Ibend radius NOTE • For out-of-plane(three-dimensional)bends,care must be taken to avoid imparting torque on the hose. • • User Responsibility for Product Selection and Suitability Note Each user bears final responsibility for making a determination as to the suitability of This product shall be manufactured by Victaulic or to Victaulic specifications.All products Victaulic products for a particular end-use application,in accordance with industry to be installed in accordance with current Victaulic installation/assembly instructions. standards and project specifications,and the applicable building codes and related Victaulic reserves the right to change product specifications,designs and standard regulations as well as Victaulic performance,maintenance,safety,and warning equipment without notice and without incurring obligations. instructions.Nothing in this or any other document,nor any verbal recommendation, advice,or opinion from any Victaulic employee,shall be deemed to alter,vary,supersede, Installation or waive any provision of Victaulic Company's standard conditions of sale,installation Reference should always be made to I-VICFLEX-ABI-AB2-AB10,I-VICFLEX-AB4-AB9, guide,or this disclaimer. I-VICFLEX-AB7,or I-VICFLEX-AB8 for the product you are installing.Handbooks are included with each shipment of Victaulic products for complete installation and assembly Intellectual Property Rights data,and are available in PDF format on our website at www.victaulic.com. No statement contained herein concerning a possible or suggested use of any material, product,service,or design is intended,or should be constructed,to grant any license warranty under any patentor other intellectual property right of Victaulic or any of its subsidaries Refer to the Warranty section of the current Price List or contact Victaulic for details. or affiliates covering such use or design,or as a recommendation for the use of such Trademarks material,product,service,or design in the infringement of any patent or other intellectual Victaulic and all other Victaulic marks are the trademarks or registered trademarks of property right.The terms"Patented”or"Patent Pending"refer to design or utility patents Victaulic Company,and/or its affiliated entities,in the U.S.and/or other countries. or patent applications for articles and/or methods of use in the United States and/or other countries. • • 10.85 5839 Rev Z Updated 10/2016 ©2016 Victaulic Company.All rights reserved. victaulic.com 19 ✓IatauliC