Report (13)
Fes 0--avoiz /c.--7s-s 5cv 5e,tolc( FireWarden-50(E) DN-7102:E Intelligent Addressable FACP NOTIFIER®OTIFIER® with Built-In Communicator by Honeywell Addressable Fire Alarm Control Panels General The NOTIFIER FireWarden-50(NFW-50)is a Fire Alarm Con- trol Panel(FACP)and Digital Alarm Communicator/Transmitter (DACT)combined into one circuit board. This compact, intelli- gent addressable control panel supports up to 50 addressable devices in any combination of detectors or modules. With an jr:‘,ED extensive list of powerful features, the FireWarden-50 pro- �` y ,'. grams just like FireWarden-100 products, yet fits into applica ° t9 tions previously served only by conventional panels. The FireWarden-50's integral DACT transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via the a� Oil C ITV public switched telephone network. It also allows remote and local programming of the control panel using the PS-Tools ION Upload/Download utility. In addition,the control panel may be /t ,i.Llir programmed or interrogated off-site via the public switched JTiJ telephone network.Any personal computer with WindowsT"'95 or greater, and compatible modem with a speed of 14.4 kbps r. or faster and Upload/Download software, may serve as a Ser- vice Terminal. This allows download of the entire program or upload of the entire program, history file, walk-test data, cur- • Point trouble identification. rent status and system voltages. • Waterfloselection per module int. The power supply and all electronics are contained on a single • Alarm verification selection per detector point. circuit board supported on a new quick install chassis and • Maintenance alert warns when smoke detector dust accu- housed in a metal cabinet.Available accessories include local mulation is excessive. and remote upload/download software, remote annunciators, • One-person audible or silent walk test with walk-test log and reverse polarity/city box transmitter.(4XTM) and printout. The FireWatch Series internet monitoring modules IPDACT-2 • System alarm verification selection per detector point. and IPDACT-2UD permit monitoring of alarm signals over the • PAS (Positive Alarm Sequence) and Pre-signal per point Internet, saving the monthly cost of two telephone lines. Although not required, the secondary telephone line may be • U(NFPA eight7ANN-ant). retained providing backup communication over the public Up to ANN-BUS annunciators switched d telephonerline. • Remote Acknowledge, Alarm Silence, Reset and Drill via NOTE: Unless otherwise specified, the term FireWarden-50 is • addressable modules or remote annunciator. used in this data sheet to refer to both the FireWarden-50 and the Uplgral DACT. d(local or remote)of program and data via FireWarden-50E FACPs. For FireWarden-50C, refer to DN- integral DACT. 60446. SLC COMMUNICATION LOOP Features • Single addressable SLC loop which meets NFPA Style 4,6 and 7 requirements. • Listed to UL Standard 864,9th edition. • Auto-program (learn mode) reduces installation time.two devices set to the same address. • 50 addressable device capacity (any combination of Reports addressable detectors and modules). • Reports DACT. • Compatible with NOTIFIER FireWarden addressable devices(refer to the FireWarden SLC Wiring Manual). • Two independently programmable Style Z(Class A)or Style Y(Class B)NAC circuits. NOTIFICATION APPLIANCE CIRCUITS(NAGS) • Selectable strobe synchronization for System Sensor, • Two independently programmable output circuits. Circuits can be configured for the following outputs: Wheelock,and Gentex devices. • Remote Acknowledge,Silence,Reset and Drill via address- —Style Y(Class B) able monitor modules. —Style Z(Class A) • Two programmable relays and one fixed trouble relay. —Door Holder Service(cannot be used for notification appliances) • Built-in Programmer. • Telephone Line Active LEDs. —Aux Power Source(cannot be used for notification appliances) • Silence Inhibit and Autosilence timer options. • EIA 232 PC interface. • Integral 80-character LCD display with backlighting. ma▪ nic circuit board NACs wi hemporal two-stagor e capability.California code for • Real-time clock/calendar with automatic daylight savings • Selectable strobe synchronization per NAC. control. • 2.5 A total power for NACs. • History file with 500 event capacity. NOTE:Maximum or total 24t/DC system power shared between Automatic detector sensitivity testing(NFPA 72 compliant). all NAC circuits and the ANN-BUS is 2.7 A. • • Automatic device type-code verification. DN-7102:E•02/22/2011—Page 1 of 4 PROGRAMMING AND SOFTWARE 11111- • Autoprogram(learn mode)reduces installation time. • Custom English labels(per point)may be manually entered or selected from an internal library file. • Two programmable Form-C relay outputs. • 20 software zones. • Continuous fire protection during online programming at the front panel. NFW-50 • Pro r Fire Alarm 11111 9 am Check automatically catches common errors not Control Panel linked to any zone or input point. a OFFLINE PROGRAMMING: Create the entire program in N-ANN-80 your office using PS-Tools, Windows®-based software package, and upload/download system programming locally. PS-Tools is available on www.magni-fire.com. _N-ANN-S/PG NP-100 Printer Gateway User interface Photo Detector N-ANN-10 LED INDICATORS Graphic LED • AC Power(green) Module • Fire Alarm(red) NI-100 • Supervisory(yellow) Ionization Detector N-ANN-LED • Trouble(yellow) • Alarm Silenced signals(yellow) KEYPAD N-ANN-RLY • 16 key alpha-numeric pad _ NH-100 Series Relay Module • Acknowled p Heat Detector ge/Ste • Alarm Silenced imi • Drill(Manual Evacuate) • Reset(lamp test) NDM-100 Strobe Product Line Information Dual Monitor Module NFW-50: Combination DACT/Fire Alarm Control Panel with 111 one SLC loop.Includes main circuit board with display,chassis with transformer, backbox with door, plastic bag containing screws,cables, key, etc.,manual. (For NFW-50C, refer to DN- NP-100T,NP-A100 P2R 60446.) Photo/Thermal Strobe NFW-50E:Same as NFW-50,but operates at 240 VAC. Power Supply FCPS-24S6 FCPS-24S8 NFW-50R:Same as NFW-50,with red backbox and door. DP-51050B:Optional dress panel for NFW-50(black). NMM-1 o0 P2R DP-51050:Optional dress panel for the NFW-50R(red). Monitor Module Strobe TR-CE-B: Optional trim ring for semi-flush mounting. (Black. in For red,order TR-CE.) NZM-100 6, BB-XP:Optional cabinet for one or two modules. NMM-100-10 BB-25: Optional cabinet for up to six modules mounted on NZM-100 Multiple-Circuit 2-Wire Detector Interface Module CHS-6 chassis. Monitor Module BB-26: Battery backbox, holds up to two 25 AH batteries and CHG-75. — NFS-LBB:Battery box,houses two 55 AH batteries CHS-6: Chassis, mounts up to six multi-modules in a BB-25 DNR cabinet. Duct Detector CHG-75: Battery charger for lead-acid batteries with a rating FI of 25 to 75 AH. ;+ NFW-50 CHG-120: Remote battery charging system for lead acid bat I L ADDRESSABLE FIRE ALARM teries with a rating of 55 to 120 AH. Requires additional NFS- LBB for mounting. NOT-BG12LX CONTROL PANEL NOTE: CHG-120 or CHG-75 required for batteries larger than Addressable 18AH. Manual Pull Station BAT Series:Batteries,see data sheet DN-6933. Page 2 of 4—DN-7102:E•02/22/2011 PRT/PK-CABLE: Cable printer/personal computer interface DNR: InnovairFlex low-flow non-relay duct-detector housing. cable. (Order NP-100R separately.) PRN-6: UL listed compatible event printer. Uses tractor-fed DNRW: InnovairFlex low-flow non-relay duct-detector housing, paper. with NEMA-4 R separately.) IPDACT, IPDACT2/2UD Internet Monitoring Module: NMM-00: Addressable Watertight. ttMoniir Module Norlone zone of nor- Mounts in bottom of enclosure with optional mounting kit(PN mally-open dry-contact initiating devices. Mounts in standard IPBRKT). Connects to primary and secondary DACT tele- 4.0" (10.16 cm.) box. Includes plastic cover plate and end-of- phone output ports for internet communications over customer line resistor. Module may be configured for either a Style B provided ethernet internet connection. Requires compatible (Class B)or Style D(Class A)IDC. Teldat Visoralarm Central Station Receiver.Can use DHCP or static IP. (See data sheet do-60408 for more information.) NDM-100: Dual Monitor Module. Same as NMM-100 except it IPBRKT:Mounting kit for IPDACT-2/2UD in common enclosure. provides two Style B(Class B)only IDCs. NMM- 0P: Miniature version of NMM-10. IPSPLT: Y-adaptor option allows connection of both panel and Stye D option. Connects with wire pigtails. MaydmounLED in dialer outputs to one IPDACT-2/2UD cable input. device backbox. AC-TRMBLK:AC Terminal Block mounts to a metal bracket,in NZM-100A: Similar to NMM-100A.Addressable Monitor Mod- turn, mounts to the FACP chassis. Use AC-TRMBLK when ule for one zone of conventional two-wire detectors. Requires wire nuts are not allowed for AC connections to the trans- resettable 24 VDC power. Refer to the Device Compatibility former. Document for listed compatible devices and quantity limita- OPTIONAL MODULES tion. NZM-100-6: Six-zone interface module. Mount one or two 4XTM Reverse Polarity Transmitter Module: Provides a supervised output for local energy municipal box transmitter, idesmodon in a -6 chassis cabinet BB-2(optional).aMount up to six mod alarm and trouble. Includes a disable switch and disable trou ides a CHS 6 in a BB-25 cabinet. ble LED. NMM-100-10: Ten-input monitor module. Mount one or two ANN-SEC: Optional secondary ANN-BUS interface module. modules in a BB-2 cabinet(optional).Mount up to six modules Note:Used only with firmware 3.0 or higher. on a CHS-6 chassis in a BB-25 cabinet. COMPATIBLE ANNUNCIATORS NC-100:Addressable Control Module for one Style Y/Z(Class B/A) zone of supN-ANN-80(-W): Remote LCD annunciator mimics the informa- Mounts directly to a 4.0"(10.16 cm.)electricalrvised polarizedtion box.NotificationAppliances. tion displayed on the FACP LCD display. Recommended wire Appliance Circuit option requires external 24 VDC to power type is un-shielded. (Basic model is black; order-W for white; notification appliances. see DN-7114.) NC-100R: Addressable relay module containing two isolated N-ANN-I/O: LED Driver Module provides connections to a sets of Form-C contacts, which operate as a DPDT switch. user supplied graphic annunciator.(See DN-7105.) Mounts directly to a 4.0"(10.16 cm.)box,surface mount using N-ANN-LED: Annunciator Module provides three LEDs for the SMB500. each zone: Alarm, Trouble, and Supervisory. Ships with red NOT BG12LX:Addressable manual pull station with interface enclosure.(See DN-60242.) module mounted inside. N-ANN-RLED: Provides alarm (red) indicators for up to 30 N100-ISO:Fault Isolator Module. input zones or addressable points. (See DN-60242.) N-ANN-RLY: Relay Module provides 10 programmable Form- SMB500:NOTE: Used to mount all modules except the NMM-100P. C relays. Can be mounted inside the cabinet. (See DN-7107.) for use Fw'th the nfor more/FieWatrden-50, see the following data on Compatible Addressableion shvices eets N-ANN-S/PG: Serial/Parallel Printer Gateway module pro- (document numbers): N100-/SONH-100/NH-100(DN-6994),R NP(-100(DN-6997) D series (DN- NR/ vides a connection for a serial or parallel printer. (See DN- 6995), N/-100 (DN -6996), , 7103.) InnovairFlex(DN-60424, DN-60429), NP-A100(DN-6998), NMM- ADDRESSABLE DEVICES 7000),NC 100R(DN-60383)?NMM-1000(DN-6990),100 and N(DN- OT- All feature a polling LED and rotary switches for addressing. BG 12LX(DN-7001). N1-100:Addressable low-profile ionization smoke detector. ADDRESSABLE DEVICE ACCESSORIES NP-100:Addressable low-profile photoelectric smoke detector. End-of-Line Resistor Assembly (R-47K and R-3.9K): The 47k ohm asthe NM -1 , NDM-100, NP-100T: Addressable low-profile photoelectric smoke detec- NMM 100P,sy a d I NC-1ses 00 suI module c rcuits 0-10 The 3.9k ohm tor with thermal sensor. assembly supervises the NZM-100-6 module circuit. These NP-100R: Remote test capable addressable photoelectric resistors are included with each module. smoke detector for use with DNR(W)duct detector housing. Power Supervision Relay: Supervises the power to 4-wire NH-100:Fast-response,low-profile heat detector. smoke detectors and notification appliances. NH-100R: Fast-response, low-profile heat detector with rate of-rise option. Wiring Requirements NH-100H: Fast-response, low-profile heat detector that acti- While shielded wire is not required, it is recommended that all vates at 190°F/88°C. SLC wiring be twisted-pair to minimize the effects of electrical NP-A100:Addressable low-profile multi-sensor detector. interference.Refer to the panel manual for wiring details. DN-7102:E•02/22/2011—Page 3 of 4 . SYSTEM SPECIFICATIONS System Capacity (noncondensing) at 32°C ± 2°C (90°F t 3°F). However, the • Intelligent Signalling Line Circuits 1 useful life of the system's standby batteries and the electronic • Addressable device capacity components may be adversely affected by extreme tempera • Programmable software zones 50 ture ranges and humidity. Therefore, it is recommended that 20 this system and its peripherals be installed in an environment • Annunciators 8 with a normal room temperature of 15—27°C/60—80°F Electrical Specifications NFPA Standards AC Power: FireWarden-50: 120 VAC, 60 Hz, 3.0 A. FireWar- The FireWarden-50 complies with the following NFPA 72 Fire den-50E:240 VAC,50 Hz, 1.5 A.Wire size:minimum 14 AWG Alarm Systems requirements: (2.00 mm2) with 600 V insulation. Nonpower-limited, super- —LOCAL (Automatic, Manual, Waterflow and Sprinkler vised. Supervisory). Battery: Two 12 V 18 AH lead-acid batteries.Battery Charger —AUXILIARY(Automatic, Manual and Waterflow) (requires Capacity: 7-18 AH (FireWarden-50 cabinet holds maximum of 4XTM). two 18 AH batteries.) Communication Loop: Supervised and power-limited. —REMOTE a DACT is"nott accepted,(Automatic, ^the alarm, trouble anual andWaterfland) Notification Appliance Circuits: Terminal Block provides supervisory relays may be connected to UL 864 listed connections for two NACs, Style Y(Class B)or Style Z(Class trouble,4XT ForM is requiequiree polarity signaling of alarm and trouble,4XT A). Special Application power. Power-limited, supervised cir- red.) cir- cuitry. Maximum signaling current per circuit: 2.5 A. End-of —PROPRIETARY(Automatic,Manual and Waterflow). Line Resistor:4.7k ohm,1/2 watt(P/N 71252 UL listed)for Style —CENTRAL STATION (Automatic, Manual and Waterflow, Y(Class B)NAC. Refer to the NOTIFIER Device Compatibility and Sprinkler Supervised). Document for listed compatible devices. —OT, PSDN (Other Technologies, Packet-switched Data Two Programmable Relays and One Fixed Trouble Relay: Network) Contact rating: 2.0 A @ 30 VDC (resistive), 0.5 A @ 30 VAC (resistive). Form-C relays,nonpower-limited,nonsupervised. Agency Listings and Approvals The listings and approvals below apply to the basic FireWar- Cabinet Specifications in modules may no Door: 19.26" (48.92 cm.) high x 16.82" (42.73 cm.) wide x den-50 cbe listed b bytrol certain appro al ag ncies,oranel.In soe cases, t listing may be in pro- 0.72" (1.82 cm.) deep. Backbox: 19.00" (48.26 cm.) high x cess.Consult factory for latest listing status. 16.65" (42.29 cm.) wide x 5.25" (13.34 cm.) deep. Trim Ring • UL:S635 (TR-CE/B):22.00"(55.88 cm.)high x 19.65"(49.91 cm.)wide. • FM approved Shipping Specifications • CSFM:7165-0028:239 Weight:26.9 lbs. (12.20 kg.) Dimensions:20.00"(50.80 cm.) • MEA:442-06-E Vol.2 high x 22.5"(57.15 cm.)wide x 8.5"(21.59 cm.)deep. NOTE:See DN-60446 for ULC-listed model. Temperature and Humidity Ranges This system meets NFPA requirements for operation at 0 — 49°C/32 — 120°F and at a relative humidity 93% ± 2% RH NOTIFIER®, FireWarden®, and System Sensor® are registered trademarks of Honeywell International Inc. Microsoft®and Windows®are registered trademarks of the Microsoft Corporation. 02011 by Honeywell International Inc.All rights reserved.Unauthorized use of this document is strictly prohibited. 1SO 9001 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. C E R T F 1 E O We cannot cover all specific applications or anticipate all requirements. BIRINEMINI A MANIFMTIRIN6 All specifications are subject to change without notice. QUALITY SYSTEMS For more information,contact Notifier.Phone:(203)484-7161,FAX:(203)484-7118. Made in the U.S.A. www.notifier.corn Page 4 of 4—DN-7102:E•02/22/2011 Monitor Modules DN-6999:C NMM-100(A), NMM-100P(A), m NOTIFIER® NZM-100(A), and NDM-100(A) for FireWarden Series Panels by Honeywell Intelligent Addressable Devices General Four different monitor modules are available for Notifier's Fire- Warden Series intelligent control panels for a variety of appli- t ,44 v cations. Monitor modules supervise a circuit of dry-contact input devices, such as conventional heat detectors and pull F stations, or monitor and power a circuit of two-wire smoke detectors(NZM-100(A)). c NMM-100(A)is a standard-sized module(tYP� Y icall mounts to a 4" [10.16 cm] square box) that supervises either a Style D (Class A) or Style B (Class B) circuit of dry-contact input devices. NMM-100P(A) is a miniature monitor module a mere 1.3" (3.302 cm) H x 2.75" (6.985 cm) W x 0.5" (1.270 cm) D that supervises a Style B (Class B) circuit of dry-contact input �x devices. Its compact design allows the NMM-100p(A) to be mounted in a single-gang box behind the device it monitors. NZM-100(A) is a standard-sized module that monitors and • supervises compatible two-wire,24 volt,smoke detectors on a Style D(Class A) or Style B(Class B)circuit. NDM-100(A) is a standard-sized dual monitor module that NMM-100(A)(Type H) monitors and supervises two independent two-wire Style B (Class B) dry-contact initiating device circuits (IDCs) at two separate,consecutive addresses in intelligent,two-wire systems. NMM-100(A) OPERATION Each NMM-100(A) uses one of the available module NMM-100(A) Monitor Module Built-in type identification automatically identifies this device addresses n an SLC its. It typeand theonds to rstatus polls • the control panel and reports ( p as a monitor module to the control panel, mal/short)of its Initiating Device Circuit(IDC). A flashing LED • Powered directly by two-wire SLC loop.No additional power indicates that the module is in communication with the control required. panel. The LED latches steady on alarm (subject to current • High noise(EMF/RFI)immunity. limitations on the loop). • SEMS screws with clamping plates for ease of wiring. NMM-100(A) SPECIFICATIONS • Direct Decade entry of address: 01 — 99 on FireWarden- Nominal operating voltage: 15 to 32 VDC. 100-2,01 —50 on FireWarden-50. Maximum current draw:5.0 mA(LED on). • LED flashes during normal operation and latches on steady Average operating current: 350 pA (LED flashing), 1 com- to indicate alarm. munication every 5 seconds,47k EOL. The NMM-100(A)Monitor Module is intended for use in intelli- gent, two-wire systems, where the individual address of each Maximum IDC wiring resistance:40 ohms. module is selected using the built-in rotary switches. It pro EOL resistance:47K ohms. vides either a two-wire or four-wire fault-tolerant Initiating Temperature range:32°F to 120°F(0°C to 49°C). Device Circuit (IDC) for normally-open-contact fire alarm and supervisory devices. The module has a panel-controlled LED Humidity range: 10%to 93%noncondensing. indicator. Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x NMM-100(A)APPLICATIONS 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x Use to monitor a zone of four-wire smoke detectors, manual 2.125"(5.398 cm)deep box. fire alarm pull stations, waterflow devices, or other normally- open dry-contact alarm activation devices. May also be used to monitor normally-open supervisory devices with special supervisory indication at the control panel. Monitored circuit may be wired as an NFPA Style B(Class B)or Style D(Class A) Initiating Device Circuit. A 47K ohm End-of-Line Resistor (provided) terminates the Style B circuit. No resistor is required for supervision of the Style D circuit. DN-6999:c•10/06/2010—Page 1 of 4 'c F p -,:,,,, ,--A,--. :.,,,,-,.4 * Rk 4F p,� � ' • � Dimensions: 1.3" (3.302 cm) high x 2.75" (6.985 cm) wide x • Built-in type identification automatically identifies this device 0.65"(1.651 cm)deep. as a monitor module to the panel. Wire length:6"(15.24 cm)minimum. • Powered directly by two-wire SLC loop.No additional power required. NZM-100(A) Interface Module • High noise(EMF/RFI)immunity. • • Tinned,stripped leads for ease of wiring. • Supports compatible two-wire smoke detectors. • Direct Decade entry of address: 01 — 99 on FireWarden- source.Supervises IDC wiring and connection of external power 100-2,01 —50 on FireWarden-50. • High noise(EMF/RFI)immunity. '° • SEMS screws with clamping plates for ease of wiring. 1415 0 1 ADDRESS 0 1 • Direct Decade entry of address:, 01 — 99 on FireWarden- 1 12 3 , 2 100-2,01 —50 on FireWarden-50. 113,' 4 LOOP 4 • LED flashes during normal operation. 10 O� 5 O�gm LED latches steadyto 5 indicate alarm on command from 9 8 7 6 9 8 6 control panel. nTENS ONES The NZM-100(A)Interface Module is intended for use in intelli- n n n gent, addressable systems, where the individual address of each module is selected using built-in rotary switches. This module allows intelligent panels to interface and monitor two- 0 LU wire conventional smoke detectors.It transmits the status(nor- O U mal,open,or alarm)of one full zone of conventional detectors O back to the control panel. All two wire detectors being moni CQ Cored must be UL compatible with the module. NZM-100(A) APPLICATIONS Use the NZM 100(A) to monitor ah zone of two-wire smoke I detectors. The monitored circuit may be wired as an NFPA The NMM 100P(A) Mini Monitor Module can be installed in a Style B(Class B)or Style D(Class A) Initiating Device Circuit. single-gang junction directly behind the monitored unit. Its endA 3.9 K ohm Style B End-of-Line Resistors (provided)(maximumithe small size and light weight allow it to be installed without rigid of the B or D mlass B or A) circuit IDC mounting. The NMM-100p(A)is intended for use in intelligent, loopresistancefor gliapplication.ohms). Install ELR across terminals 8 two-wire systems where the individual address of each module and 9 for Style D is selected using rotary switches. It provides a two-wire initiat- NZM-100(A)OPERATION ing device circuit for normally-open-contact fire alarm and Each NZM-100(A) uses one of the available module security devices. NMM-100P(A) addresses on an SLC loop. It responds to regular polls from NMM-100P(A)APPLICATIONS the control panel and reports its type and the status(open/nor- Use to monitor a single device or a zone of four-wire smoke mal/short)of its Initiating Device Circuit(IDC). A flashing LED detectors,manual fire alarm pull stations,waterflow devices,or painnel. Thees that the module t in communicationnalarm (subjectwith the control Trent other normally-open dry-contact devices. May also be used to t LED latches steady on to current monitor normally-open supervisory devices with special super- visory indication at the control panel. Monitored circuit/device NZM-100(A)SPECIFICATIONS is wired as an NFPA Style B(Class B)Initiating Device Circuit. Nominal operating voltage: 15 to 32 VDC. A 47K ohm End-of-Line Resistor(provided)terminates the cir- cuit. Maximum current draw:5.1 mA(LED on). NMM-100P(A)OPERATION Maximum IDC wiring resistance:25 ohms. Each NMM-100P(A) uses one of the available module Average operating current: 300 pA, 1 communication and 1 addresses on an SLC loop. It responds to regular polls from LED flash every 5 seconds,3.9k col. the control panel and reports its type and the status(open/nor- EOL resistance:3.9K ohms. mal/short)of its Initiating Device Circuit(IDC). External supply voltage (between Terminals T3 and T4): NMM-100P(A) SPECIFICATIONS DC voltage: 24 volts power limited. Ripple voltage: 0.1 Vrms Nominal operating voltage: 15 to 32 VDC. maximum.Current:90 mA per module maximum. Average operating current: 350 pA, 1 communication every Temperature range:32°F to 120°F(0°C to 49°C). 5 seconds, 47k EOL; 600 pA Max. (Communicating, IDC Humidity range: 10%to 93%noncondensing. Shorted). Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x Maximum IDC wiring resistance:40 ohms. 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x Maximum IDC Voltage: 11 Volts. 2.125"(5.398 cm)deep box. Maximum IDC Current:400 pA. EOL resistance:47K ohms. Temperature range:32°F to 120°F(0°C to 49°C). Humidity range: 10%to 93%noncondensing. ;::;:77.4.7=:7:70=...........................................,: ge 2 of 4—DN-6999:c•10/06/2010 NDM-100(A) Dual Monitor Module • MEA: 72-01-E Vol. 2 (NMM-100, NMM-100P, NZM-100); The NDM-100(A) Dual Monitor Module is intended for use in 227'03 E Vol.3(NDM-100) i - ' - intelligent, two-wire systems. It provides two independent two- wire initiating device circuits(IDCs)at two separate,consecutive Product Line Information addresses. It is capable of monitoring normally open contact fire NOTE:A"suffix indicates ULC-listed model. alarm and supervisory devices.The module has a single panel- controlled LED. NMM-100(A): Monitor module. NOTE: The NDM-100(A)provides two Style B(Class B)/DC cir- NMM-100P(A):Monitor module,miniature. cults ONLY Style D(Class A)IDC circuits are NOT supported in NZM-100(A): Monitor module,two-wire detectors. any application. NDM-100(A)SPECIFICATIONS NDM-100(A): Monitor module, dual, two independent Class B circuits. SMB500:Optional surface mount backbox. NOTE: See installation instructions and refer to the SLC Wiring Normal operating voltage range: 15 to 32 VDC. Maximum current draw:6.4 mA(LED on). Average operating current:750 pA(LED flashing). Manual,PN 52304. Maximum IDC wiring resistance: 1,500 ohms. Maximum IDC Voltage: 11 Volts. Maximum IDC Current:240 pA EOL resistance:47K ohms. Maximum SLC Wiring resistance:40 Ohms. Temperature range:32°to 120°F(0°to 49°C). Humidity range: 10%to 93%(non-condensing). Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 2.125"(5.398 cm)deep. NDM-100(A) AUTOMATIC ADDRESSING The NDM-100(A) automatically assigns itself to two address- able points, starting with the original address. For example, if the NDM-100(A) is set to address "26", then it will automati- cally assign itself to addresses"26"and"27". NOTE: `Ones"addresses on the NDM-100(A)are 0, 2, 4, 6, or 8 only. Terminals 6 and 7 use the first address,and terminals 8 and 9 use the second address. ZS, CAUTION: Avoid duplicating addresses on the system. Installation NMM-100(A), NZM-100(A), and NDM-100(A) modules mount directly to a standard 4"(10.16 cm)square,2.125"(5.398 cm) deep, electrical box. They may also be mounted to the SMB500 surface-mount box. Mounting hardware and installa- tion instructions are provided with each module. All wiring must conform to applicable local codes,ordinances,and regu- lations. These modules are intended for power-limited wiring only. The NMM-100P(A) module is intended to be wired and mounted without rigid connections inside a standard electrical box. All wiring must conform to applicable local codes, ordi- nances,and regulations. Agency Listings and Approvals In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult fac- tory for latest listing status. • UL:S635 • ULC:S635 • FM Approved • CSFM: 7300-0028:0230 (NMM-100, NMM-100P, NZM- 100);7300-0028:0237(NDM-100) DN-6999:C•10/06/2010—Page 3 of 4 . 0 B DBC From Tyco Security Products HSPA Universal Wireless Commercial Fire Alarm Communicator osc 3G401 OCF 4 4Fea 4 4� ake VD`iferen e• x • Uses HSPA(3G)network°`for r A..high Spoe liable and ow cost ® unctions,to'an)P" Automatic illy swiitches'to 3G technology from DSC! EDGPF )if,30 serviis The 3G4010CF connects the alarm protected premises within 'not a ar abl0 - :. ' control panel to the Cellular network than 24 hours of the failure. more �` Co ble'witt ontrdl:peels ' _ and reports alarm signals directly to A �thatAcommunicate using Contact a monitoring station receiver How it Works ID or SIA( do baud)formats (Sur-Gard System I-IP/II/III/IV/5).The ,: 3G4010CF uses the Cellular network The 3G4010CF can be used as n , g A T to ensure low-cost, high-speed and either a Sole Communicator or as a ' reliable alarm communications and is Backup Communicator.When being • , 4 onrboar&thbota with NC,,p1.0 n used as a Sole Communicator the or SEOL supervision 4 aN x compatible with control panels that t. T 4.- communicate using the Contact ID or 3G4010CF will replace the phone 4 on-board outputs(open / t line connection on the panel and ',46611ttr f . SIA(300 baud)format. as soon as it detects that an alarm �.. 43' The 3G4010CF is compliant needs to be transmitted it will send • A`ct do and initialization re T with the latest requirements for the alarm across the Cellular network ,� t Communications Methods as per immediately.When being used as a -u� UL864 and NFPA72 2010 and backup the communicator assesses ., : 'Wig*, �t a pr d t" y V „ 2013 Editions. It can be used in the connection to the PSTN phone '' „ *Duni Fire Monitoring applications as a line, and onlyin the event of a phone ' A. • `" View i j ta A single communications technology, line failure will it send all alarm traffic A. dire m g ®bili .n6 in which case any failure of the across the Cellular network to the ,v, a � e o of T communications path shall be monitoring station.roufilehoo� ' * * .; -A, T annunciated at the supervising station � ' within 5 minutes(NFPA72 2010)or In instances where the control panel p� � it Sur-C rd`s T does not support�x � � M 1 hour(NFPA72 2013)of the failure, Contact ID or *Sser `I1FJlIVS=monitorxg .' •or it can be used as part of a multiple SIA(300 baud),the 3G4010CF has 'settd Ors. , ' ' :744: p inputs pre-set to transmit fire alarm, communications technologies(for •''` n'clud Used power example in conjunction with a DACT), fire supervisory or system trouble. ' When used as a back-up sopl�ygransfor ngr.and 7 k *a provision Alarm signals are transmitted directly , rechargeable battery #= shall be made to monitor the integrity without the need of a clearinghouse of each communication path and to the IP linecard of the monitoring . L �ste 4 V f x= 2. 4 failure of any communications station receiver(Sur-Gard®System A. A ,x{ �listed ' path shall be annunciated at the IIP/II/III/IV/5). I' t I a supervising station and at the Contact your DSC distributor. communications www.dsc.corn 1 1-888-888-7838 DSC From Tyco Security Products Activating & Initializing the Unit Rate Plan Activating and initializing the 3G4010CF can be done using Cost-effective rate plans have been negotiated and are the automated telephone activation system(VRU), mobile available through authorized master resellers. Contact your interface or web-user interface provided by monitoring station or visit www.connect24.com to find a C24 Communications. No special tools are required. master reseller.When used as a sole communicator,the 3G4010CF requires use of the 4MB(NFPA72 2010)or Mobile Site for Easy Installation and 500kB(NFPA72 2013)rate plans to support the supervision Comprehensive Maintenance requirements. C24 Communications mobile site(m.connect24.com) makes the installation a simple process and offers intuitive Specifications trouble-shooting features, cutting down on time and cost Dimensions 11-1/2"x 10"x 3" allocated to maintenance. (290 mm x 254 mm x 75 mm) Input Voltage 120 VAC Current Draw 200 mA(standby) see 0:.: 400 mA(transmitting) Operating Environment 32°to 120°F(0°to 49°C) Weight 12.8 lbs(5.8 kg) < <r; D 0 Optional Acessories UL Listing Model ' Description GS-15ANt 15 ft extension antenna(internal Use) The 3G4010CF is UL listed under File S4019, Listing guide GS-25ANT U0>0<,as a sole or backup communicator for Commercial Fire 25 ft exxtern antenna monitoring installations.When used as a sole communicator (internall e/external use) under NFPA72 2010 guidelines the 3G4010CF will send GS-50ANT 50 ft extension antennause its heartbeat once every 97 seconds ensuring that three (Internal/external rise) ... ...: ... ... heartbeats will be received at the supervising station within the 300 second window.When used as a sole communicator under NFPA72 2013 guidelines the 3G4010CF will send its heartbeat once every 5 minutes to monitor connectivity with the supervising station within the 1 hour window.When used as a backup communicator the 3G4010CF will monitor the other communication method(DACT)and send a daily test transmission to the supervising station. CSFM Listing The 3G4010CF has been approved by the California State Fire Marshal(CSFM)pursuant to Section 13144.1 of the California Health and Safety Code. Ordering Information: 3G4010CF-USA Universal Wireless Commercial Fire Alarm Communicator ca (U.S. Model/SIM Card Included) S 0 Co Z a communications For product information www.dsc.com Product specifications and availability subject to change without notice.Certain product names mentioned herein may he trade names and/or registered trademarks of other companies. ©2015 Tyco Security Products DN-6995:C•Al-320 NP-100(A) Series 8 Addressable Photoelectric Detectors NOTIFIER for the FireWarden Series by Honeywell Addressable General The NP-100(A), NP-100T(A) and NP-100R(A) addressable, low-profile plug-in photoelectric detectors use a state-of-the- art photoelectric sensing chamber with communications to provide open area protection and are used exclusively with x NOTIFIER's FireWarden Series(FireWarden-100-2 and Fire- Warden-50) and Spartan (NSP-25) Addressable Fire Alarm Control Panels (FACPs). The NP-100T(A) adds thermal sen- sors that will alarm at a fixed temperature of 135°F (57°C). Since these detectors are addressable, they will help emer- gency personnel quickly locate a fire during its early stages, potentially saving precious rescue time while also reducing property damage.Two LEDs on each sensor light to provide a local,visible sensor indication. Remote LED annunciator capail - bility is available as an optional accessory, PN RA100Z(A). °° The NP-100R(A)is a remote test capable detector for use with NP-100(A) in B210LP(A) Base DNR(A)/DNRW duct smoke detector housings. Features SLC loop Applications Use photoelectric detectors in life-safety applications to pro- • Two-wire loop connection. vide a broad range of fire-sensing capability, especially where • Unit uses base for wiring. smoldering fires are anticipated. Ionization detectors are often Addressing better than photoelectric detectors at sensing fast, flaming • Addressable by device. fires. • Rotary,decimal addressing:01 –99 with FireWarden-100-2 and NSP-25,and 01–50 with FireWarden-50. Construction Architecture These detectors are constructed of off-white fire resistant plas- tic. NP-100(A) series plug-in, low-profile smoke detectors are • Unique single-source, dual-chamber design to respond designed to commercial standards and offer an attractive quickly and dependably to a broad range of fires. appearance. • Sleek,low-profile design. • Integral communications and built-in type identification. Installation • Built-in tamper-resistant feature. NP-100(A)series plug-in detectors use a detachable mounting • Removable cover and insect-resistant screen for simple base to simplify installation,service and maintenance. field cleaning. Mount baseall base Operation ( types)on an electrical backbox which is at least 1.5"(3.81 cm)deep. For a chart of compatible junction • Withstands air velocities up to 4,000 feet-per-minute(20 m/ boxes,see DN 60054. sec.)without triggering a false alarm. NOTE:Because of the inherent supervision provided by the SLC • Factory preset at 1.5% nominal sensitivity for panel alarm loop, end-of-line resistors are not required. Wiring `T-taps" or threshold level. branches are permitted for Style 4(Class B) wiring. NP-f00R(A) Visible LED"blinks"when the unit is addressed (communi- mounts in a DNR(A)/DNRW duct detector housing. • cating with the fire panel)and latches on in alarm. Mechanicals Operation • Sealed against back pressure. Each NP-100(A) series detector uses one of 99 possible addresses on the FireWarden-100-2 and NSP-25,or one of 50 • Direct surface mounting or electrical box mounting. possible addresses on the FireWarden-50 Signaling Line Cir- • Mounts to: single-gang box, 3.5' (8.89 cm) or 4.0" (10.16 cuit (SLC). It responds to regular polls from the system and cm)octagonal box,or 4.0"(10.16 cm)square electrical box reports its type and status. (using a plaster ring—included). The addressable photoelectric sensor in the NP-100(A)series - Other system features has a unique unipolar chamberthat responds quickly and uni- formly• Fully coated circuit boards and superior RF/transient pro- to a broad range of smoke conditions. It can withstand lection. wind gusts up to 4,000 feet-per-minute (20 m/sec.) without sending an alarm level signal. Because of its unipolar cham- 94-VO plastic flammability rating. ber, the NP-100(A) series is • Low standbycurrent. ( ) approximately two times more responsive than most photoelectric sensors. This makes it a Options more stable detector. • Remote LED output connection, PN RA100Z(A). DN-6995:C•12/07/2011—Page 1 of 2 Detector Sensitivity Test NP-100RA:Same as NP-100R with ULC Listing for use with a Each detector can have its sensitivity tested (required per DNRA duct detector housing;B210LPA base included. NFPA 72,Chapter 14 on Inspection, Testing and Maintenance) INTELLIGENT BASES when installed/connected to a FireWarden-100-2 or FireWar- • den-50 addressable fire alarm control panel.The results of the NOTE:'A"suffix indicates ULC Listed model. sensitivity test can be printed off the FireWarden-100-2 or Fire- NOTE:For details about intelligent bases and their mounting,see Warden-50 for record keeping. DN-60054. B210LP(A): Plug-in detector base (included); standard U.S. Specification flanged low-profile mounting base. B210LPBP:Bulk pack of B210LP;package contains 10. Voltage range: 15-32 VDC(peak). Standby current:300 pA ©24 VDC. B501(A):Standard European flangeless mounting base. LED current:6.5 mA 24 VDC(latched"ON"). B501 BP: Bulk pack of B501;package contains 10. B200SR(A): Intelligent sounder base capable of producing Air velocity:4,000 ft./min.(20 m/sec.)maximum. Size:2.1"(5.33 cm)high;base determines diameter. sound output with ANSI Temporal 3 or continuous tone. Replaces 6501 BH series bases in retrofit applications. -B210LP(A):6.1"(15.5 cm)diameter. B224RB(A): Plug-in System Sensor relay base. Screw termi- -B501(A):4.1"(10.4 cm)diameter. nals:up to 14 AWG2.0 mm2). Relay type:Form-C.Rating:2.0 -B200SR(A):6.875"(17.46 cm)diameter. A CP 30 VDC resistive; 0.3 A © 110 VDC inductive; 1.0 A 02 -B224RB(A):6.2"(15.748 cm)diameter. 30 VDC inductive. Weight:3.6 oz.(102 g). B224BI(A): Plug-in System Sensor isolator detector base. Maximum 25 devices between isolator bases(see DN-6994). Operating temperature range: for NP-100(A):0°C to 49°C (32°F to 120°F);for NP-100T(A):0°C to 38°C(32°F to 100°F). ACCESSORIES NP-100R(A):installed in a DNR(A)/DNRW-20°C to 70°C(-4°F F110: Retrofit flange to convert B210LP(A) to match the to 158°F). B710LP(A Temperature:0°C-49°C(32°F-120°F). profile) rof le) profile, or to convert older high-profile bases to low F110BP:Bulk pack of F110;package contains 15. Relative humidity: 10%-93%,non-condensing. Listings F210: Replacement flange for B210LP(A)base. RA100Z(A): Remote LED annunciator.3-32 VDC.Mounts to Listings and approvals below apply to the NP-100(A), NP- a U.S. single-gang electrical box. For use with B501(A) and 100T(A), and NP-100R(A) detectors. In some cases, certain B210LP(A)bases only. modules may not be listed by certain approval agencies, or SMB600:Surface mounting kit listing may be in process. Consult factory for latest listing sta- tus. M02-04-00:Test magnet. • UL Listed:S1115. M02-09-00:Test magnet with telescoping handle. • ULC Listed:S911. XR2B: Detector removal tool. Allows installation and/or • CSFM:7272-0028:0231. removal of detector heads from bases in high ceiling applica- • MEA:243-02-E Vol.2. tions. • Maryland State Fire Marshal:permit 2173. XP-4: Extension pole for XR2B. Comes in three 5-foot(1.524 • FM approved. m)sections. T55-127-010: Detector removal tool without pole. Product Line Information BCK-200B:Black detector covers for use with NP-100(A)only; NOTE:"A"suffix indicates ULC Listed model. box of 10. = °- , 7.: ;; @ WCK-200B: White detector covers for use with NP-100(A) r, s only,box of 10. NP-100A:Sames as NP-100 with ULC Listing; B210LPA base included. NP-100T: Same as NP-100 but with thermal element; B21 OLP base included. NP-100TA: Same as NP-100T with ULC Listing; B210LPA base included. NP-100R: Remote test capable addressable photoelectric NOTIFIER® and FireWarden® are registered trademarks of Honeywell detector for use with a DNRA/DNRW duct detector housing; International Inc. 621 OLP base included. 02011. All rights reserved. Unauthorized use of this document is strictly prohibited. ISO 9001 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. c E Fs r F E o We cannot cover all specific applications or anticipate all requirements. UICIIIEBIMQ I MMIMCTIRIMU All specifications are subject to change without notice. QUALITY SYSTEMS For more information,contact Notifier.Phone:(203)484-7161,FAX:(203)484-7118. Made in the U.S.A. www.notifier.com Page 2 of 2-DN-6995:C•12/07/2011 • DN-7001:D•Al-380 NOT-BG 12L (i4)4Addressable Manual Pull Station NOTIFIER by Honeywell Intelligent/Addressable Devices It General The Notifier NOT-BG12LX is a state-of-the-art, dual-action (i.e., requires two motions to activate the station) pull station that includes an addressable interface for FireWarden series �' intelligent control panels,and the NSP-25 panel. Because the NOT-BG12LX is addressable,the control panel can display the exact location of the activated manual station. This leads fire personnel quickly to the location of the alarm. Features • Maintenance personnel can open station for inspection and address setting without causing an alarm condition. • Built-in bicolor LED, which is visible through the handle of the station, flashes in normal operation and latches steady red when in alarm. % • Handle latches in down position and the word"ACTIVATED" appears to clearly indicate the station has been operated. • Captive screw terminals wire ready for easy connection to a.L J, SLC loop(accepts up to 12 AWG/3.25 mm2 wire). • Can be surface mounted (with SB-10 or SB-I/O) or semi flush mounted. Semi-flush mount to a standard single- gang,double-gang,or 4'(10.16 cm)square electrical box. • Smooth dual-action design. The NOT-BG12LX • Meets ADAAG controls and operating mechanisms guide- Addressable Manual Pull Station lines (Section 4.1.3[13]); meets ADA requirement for 5 lb. maximum activation force. • Highly visible. The BG12TR is usually needed for semi-flush mounting with 4" • Attractive shape and textured finish. (10.16 cm)or double-gang boxes(not with single-gang boxes). • Key reset. • Includes Braille text on station handle. Operation • Optional trim ring(BG12TR). Pushing in,then pulling down on the handle causes it to latch • Meets UL 38, Standard for Manually Actuated Signaling in the down/activated position. Once latched, the word"ACTI- Boxes. mar (in bright yellow) appears at the top of the handle, while a portion of the handle protrudes from the bottom of the station. To reset the station, simply unlock the station with the Construction key and pull the door open.This action resets the handle;clos- Shell, door, and handle are molded of durable polycarbonate ing the door automatically resets the switch. material with a textured finish. Each manual station, on command from the control panel, sends data to the panel representing the state of the manual Specifications switch.Two rotary decimal switches allow address settings • Shipping Weight:9.6 oz. (272.15 g) (1 —99 on NFW2-100/NFW2-100C, 1 —50 for NFW-50/NFW- 50C). • Normal operating voltage:24 VDC. • Maximum SLC loop voltage:28.0 VDC. Architectural/Engineering • Maximum SLC standby current:375 NA. Specifications • Maximum SLC alarm current:5 mA. Manual Fire Alarm Stations shall be non-coded, with a key- • Temperature Range:32°F to 120°F(0°C to 49°C) operated reset lock in order that they may be tested, and so • Relative Humidity: 10%to 93%(noncondensing) designed that after actual Emergency Operation, they cannot - • For use indoors in a dry location be restored to normal except by use of a key.An operated sta tion shall automatically condition itself so as to be visually Installation detected as activated. Manual stations shall be constructed of red-colored polycarbonate material with clearly visible operat- The NOT-BG12LX will mount semi-flush into a single-gang, ing instructions provided on the cover. The word FIRE shall appear on the front of the stations in white letters, 1.00 inches double-gang,or standard 4"(10.16 cm)square electrical outlet box, or will surface mount to the model SB 10 or SB I/O sur- (2.54 cm) or larger. Stations shall be suitable for surface face backbox. If the NOT-BG12LX is being semi-flush mounting on matching backbox SB-10 or SB I/O;or semi flush mounted, then the optional trim ring (BG12TR) may be used. mounting on a standard single gang, double-gang, or 4"(10.16 cm) square electrical box, and shall be installed DN-7001:D•4/13/2012—Page 1 of 2 within the limits defined by the Americans with Disabilities Act (ADA) or per national/local requirements. Manual Stations shall be Underwriters Laboratories listed. Manual stations shall connect with two wires to one of the con- trol panel SLC loops. The manual station shall, on command from the control panel,send data to the panel representing the state of the manual switch. Manual stations shall provide address setting by use of rotary decimal switches. • Product Line Information NOT BG12LX: Dual-action addressable pull station. Includes key locking feature. (Listed for Canadian and non-Canadian applications.) SB-10:Surface backbox;metal. SB-I/O:Surface backbox;plastic. BG12TR:Optional trim ring. 17021:Keys,set of two. Agency Listings and Approvals In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in pro- cess.Consult factory for latest listing status. • UL/ULC Listed: S692(listed for Canadian and non-Cana- dian applications). • MEA:67-02-E Vol. IV. • CSFM:7150-0028:0199. • FM Approved. Patented: U.S. Patent No. D428,351; 6,380,846; 6,314,772; 6,632,108. NOTIFIER®is a registered trademark of Honeywell International Inc. ©2012 by Honeywell International Inc.All rights reserved.Unauthorized use of this document is strictly prohibited. ASO 9001 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. C E R T F I E We cannot cover all specific applications or anticipate all requirements. (BIN INI$MMMFACTIINNI All specifications are subject to change without notice. QUALITY SYSTEMS Made in the U.S.A. For more information,contact Notifier.Phone:(203)484-7161,FAX:(203)484-7118. www.notifier.com Page 2 of 2—DN-7001:D•4/13/2012 S‘• UL S� 0., SIGNALING ` LISTED ACE-11 FAD FIRE ALARM DOCUMENTS The FAD is the perfect fit to meet the demanding code requirements today. SAE's number one goal is tt . to manufacture code compliant solutions and this product allows you to do just that. NFPA 72 2007 section 6.2.2.1 states, "A record of installed software and firmware version numbers shall be maintained at the location of the fire alarm control unit." This durable 16 gauge steel enclosure with a solid piano hinge and key lock will keep all of your code required documents in one safe place. With a 4GB USB flash drive it stores your fire alarm software safe and secure eliminating the occurrences of the soft- ware not being on site when technicians arrive to service the system.Along with your fire alarm soft- Standard Features: • Installed with a 4 gig digital flash drive with USB B connector • 2 Key ring hooks to hold system keys • Business card holder for key contacts • Overall Dimensions are 12" x 13"tall and ware you can store your test & inspection docu- ments, service records, manuals &AS built drawings for the system. Using a standard USB B connector it allows you to plug in with any standard SB printer cable to upload or download information. 2 %deep The FDB is designed to hold critical manuals and • 16 gauge steel box and cover for security documents with a durable steel retainer. It has • Durable powercoat baked on finish designated hooks to organize key rings and hold other colors available important business cards for easy access and • Standard3/"cat 30 key lock other lock as- reference. Inside the cover it has a organized note semblies available table that allows for documentation for passwords • Solid stainless steel piano hinge and other critical system information. • Permanently screened white ink 1" high "Fire Alarm Documents" • Legend sheet for passwords and system information [7] r __ SOX 'CALE' riM�l: ISS 9 Space Age Electronics, Inc. R I RED www.lsae.com NFPA .. n,EMBEx FIRE 800.486.1723 Toll Free Made In U.S.A. 508.485.0966 Local 508 485 4740 Fax Space Age Electronics, Inc. 2009 ED0549 LT10559 Rev.D 1/2 No Excuses, Just Solutions! jSPACE AGE ELECTRONICS, INC. Specifications: The fire alarm documents box (FAD) shall be UL Listed, constructed of 18 gauge cold rolled steel. It shall have a red powder coat epoxy finish. The cover shall be permanently screened with 1" high lettering "FIRE ALARM DOCUMENTS " with white indelible ink. The access door shall be locked with a 3/4" barrel lock and the hinge shall be a solid width 12"stainless steel piano hinge. The enclosure will supply 4 mounting holes. Inside the enclosure will accommodate standard 8 1/2 x 11 manuals and loose document records that will be protected within the enclosure.A legend sheet will be permanently attached to the door for system required documentation, key contacts and system information. The FAD will have securely mounted inside a minimum of 4 Gigabyte digital flash memory drive with a standard USB B connector for uploading and downloading information. The drive shall not be accessible without tools to any person whom gains access to the records. The enclosure shall also provide 2 key ring holders with a location to mount standard business type cards for key contact personnel. USB Storage Interface Requires Standard USB-B Connector Key Ring property Mo melton Mlnlmum Requlretl Doeument tion(SIG FUNS Melerence NEPA 72p3 �.„, Hooks .��aM aWAoEca...a>., • Hc' Cern/10800MandApprov,t: 7r: WrK.eon a6., ..r..and� W mm�.l,m.,. ,6.,System 1nslsuatlon coMraclo, e .r.mm,..wo.R...m.....aM....:� teenn1a..,n .....�.,e.,b..R Fes,01...,01 dm..,... .3.,�rc.a.�,e..•.�.,..Mm.«m..m....,,.m,,.b,m 34046. m. Business . Card Holder 6S AunoMyHa ng Jur ad lion Rn E xioneda ,. b �� , �.• �a �� n� 6,x.6 E®...,mb,6..66.6o•.,4mm<.�.b =cladheroin m �01..01. own o Emla.a a n61 amof Mon m. m �.8 rc.wxn 5ee I2 . . of c<a an44va Equipment infonnatlon .�,.c.>.Wq.n'a n rovm• In .in o rc PoR .uw, u � and tranterti documentation in accordance winSecnon No z: Once M.�m.2...n "... ��. Rene, N/A o eaa a.6�.m. nu,...... ,ia..a 4 l sr.any. . ..n o.4 o.mn01564 *488 723 000..,6.5 mm —r—,— .w 58 CMM R LT1o844 Rev.1 Legend sheet for storing system information including contacts,sign-off,maintenance & test information,and alternate locations of additional records. • Ordering Information: Part# Description SSU00685 Fire Alarm Storage Cabinet RED BOX Space Age Electronics, Inc. SSU00686 Custom screening with your Logo www.isae.com 800.486.1723 Toll Free Check out our Infinity line eFAD single gang 2 Gig digital storage 508.485.0966 Local solutions(IAMEFAD) 508 485 4740 Fax This document is subject to change without notice,see doc#ED0479 for legal disclaimer No Excuses, Just Solutions! ED0549 LT10559 Rev.D 2/2