Report HIS)-0 0-000(041 5 iRECE](VED1O AY 15 ?0 CITY OF TI ARD' 13UILDING VISION SIEMENS 15201 NW Greenbrier Parkway Suite A-4 Beaverton,Oregon 97006 Phone: (503)207-1900 Fax:(503)207-1901 FIRE ALARM SUBMITTAL VICTORIA'S SECRET WASHINGTON SQUARE MALL VS B10 TENANT IMPROVEMENT Submittal Version Date Siemens Job Number 520054388 Issued for Review 05.11.2017 Siemens Project Manager Moses Frangopoulos Siemens Project Engineer Garrick Youngberg,SET Proprietary document for approval only TABLE OF CONTENTS SIEMENS 1 BILL OF MATERIALS & COMPONENT SPECIFICATIONS 2 FIRE ALARM NOTIFICATION VOLTAGE DROP CALCULATIONS 3 4 5 r I 1_ BILL OF MATERIALS SIEMENS FIRE ALARM SUBMITTAL VICTORIA'S SECRET WASHINGTON SQUARE MALL Fire Alarm System Panel Components Item Model# Siemens Part# Quantity Color Mfg Description 1 DB-11 500-094151 1 White Siemens Smoke Detector Base 2 E90-24MCC-FW 9 White Wheelock Multi-Candela Speaker/Strobe,Ceiling Mount 3 STW 5 White Wheelock Exceder Multi-Candela Strobe-Wall Mount 4 FDBZ492-HR S54319-B23-A1 5 Red Siemens Air Duct Housing w/Relay,Connects to Remote LED/Test Switch F 5 FDBZ492-RTL 354319-S27-A1 5 Red Siemens Remote Test Switch FDBZ492-RTL,Connect to Duct Housing FDI 6 FP-11 500-095112 6 White Siemens MXL Smoke Detector-Photo * Catalog Cut Sheets not available PROPRIETARY DOCUMENT FOR APPROVAL ONLY 5/10/2017 SIEMENS Data Sheet Fire Safety&Security Products Specialized Detection Devices 'DB' Series Detector Bases Models DB2-HR, DB-11 and DB-11E ARCHITECT AND ENGINEER SPECIFICATIONS _ • Each detector base is compatible with Model'H',"11 , and"121"series of conventional detectors ` • All bases compatible with the optional Model LK-11 detector-locking kit " ,ly, Q cp • Each detector base also functions with the addressable .A, Model'H'series,as well as Models FD0421,FDOT421, u' - CO FDOOT441,FDOOTC441 and FDT421 intelligent devicesModel DB2-HR OJ i • Model DB2-HR is also compatible with ASAtechnology°detectors .• �'' • Model DB2-HR has backwards compatibility with Siemens i" Model'H'-series intelligent detectors r► • Models DB-11 and DB-11E mount on a 4-inch square, I" Model DB-11E octagon or single-gang electrical box ��- • Model DB 11 has plugs to cover the outer-mounting screw holes Model DB-11 • Model DB2-HR mounts on a 4"-square,double- •0.1.1L 268 Listed, ....ULC-S529 Listed; gang electrical box FM,CSFM and NYC Fire Department Approved Product Overview Specifications—(continued) The detector bases are low-profile,surface-mounting bases Moreover,Models DB-11 and DB-11E mount on a 4"-square, used on various Siemens—Fire Safety conventional and (10.2 cm)octagon or single-gang box. Model DB-11 has addressable detectors. integral,decorative plugs to cover the outer screw holes. Model DB2-HR,which is a redesign of Model DB-HR,is However,Model DB2-HR mounts on a double-gang,4-inch compatible with the standard,addressable type of (10.2 cm.)square electrical box. intelligent detectors,as well as those detection devices Dimensions that operate with ASAtechnologyrM. Model DB-11 Additionally,Model DB2-HR is backward compatible with ,_ 6"(11.4 cm-)Diameter-----, the Siemens Model'H'-series intelligent detectors and 3%4" m f, detector-assigned FACPs. Model DB2-HR can also operate ---- with Siemens'50-point addressable;252-point lir '131=11111111:11111111111 01,^ addressable;504-point addressable,and FireFindermo XLS 1 vimmommow 1 fire systems. A relay output from the fire detector base for 1 vS'I''1mov .Lr�l !_ 'l� signaling other devices is provided by Model DB2-HR. I L.. 2-3! m)--� L---4-1/8"(10-6.-)Diameter-•J The detector bases use screw-clamp contacts for electrical Note: Model 05-1 1 E basedetector has a diameter dimension of 4-5°X11-4 cm.). connections and self wiping contacts for better reliability. Further,the bases can be used with the optional Model LK- Mounting Diagram G BOX 11 detector locking kit,which contains 50 detector locks Model DB2-HR DOUBLE-GAN 3-IQ-INCHES DEEP and an installation tool,to prevent unauthorized removal a•iNcr+scwAREBox 3-02•INCHES DEEP 2-11S-INCHES � U �n ' / of the detector head. Specifications ;_r 0 1 ,'' 4y'�„/ Models DB-11 and DB-11E are the standard bases for o " 'o � Model'H'-series"11"and Model"121"-series conventional t,./. \V o d . -PTAV V detectors,as well as the Model'H'-series addressable t.-7,-,-;=, —,;f i ' ,, - detectors. Model DB-11 has a 6-inch(15.2 cm)diameter. :� / ;---o. The diameter for Model DB-11E is 4.5 inches(11.4 cm). 4,,,,',.4` SEECTTION W� \\ BREAKETIOFFTHIS ��' USING A4-INCH USING ADO BL -,..'a„ .., ...SQUARE BOX �'USING 'GANG BOXOUBLE- _ Notes:The Module Barrier(shown to the right)must be usedwhen Model DB2-HR relay contacts are --- connectedtonon-power limited circuits.Break apart the barrier to the conect size and shape for either the flinch square or doublegang box Install the barrier diagonally into the back box 6161 to create two(2),separate compartments with back box,in order to separate the wirest Detector Bases [DE�r Series SIEMENS Industry, Inc. Building Technologies Division Wiring Diagrams �„ra,rw2 , Ire. �—r; ,r „�.QAFUYPX, �������� i.CAofICiStr S.RCKts to 1e SES IEbreCEvrY w3rwx:lo+h xON WMCAfLvt§. 1.Y.,,,S 1,11r 5 8_ f COpA�xSuws}� Y— c.11001.Utior psECWpN_q_/ e Aro ix vAYt1 4 1,061,34:061e2. '22 CAMS 1.De pet Imps/Mrs seder bwNaiad e.4atwi4 4aw`uzmw`«u .m T"lEEt«wm am c°e"om"; Nato provide aysrsoim al ameselms. AraN 2.Whims made May O mut smmtrN•critical spore agail N-C-fl RUN-fl Bodo*ENNIaVsad Xs=sodded dotteler mdeprkes1 pxcax.,xrarr-x. �e4taacwm s.t.,,.w.z maddeNTPENIM MOLLYE +t.ns+wn wnrna.0.1 edea rlM ii6sTip ebad4 AIG-n.Awx, tYtnx,RLwn aalcunavxcxra w.-n Note: The illustration above is typical wiring for Models DB-11 and DB-11E(using Models PE-11,PE 11T,DT-11,OP121,01-1121,and H1121 detectors). O8111-T1E1NO RE1.40550L*ACE) OadtXRS(REMOTE BELAYTTASR TO NEXT BASE 110 NOT + / E` OP TO INITIATING w _ •• O iwCE CIEGUITLITE SIEMENS S 1a ,..REM°PuOrE ■�i3« RELAY. 5 1a a,15.. INDUSTRY.INC, fi 1b ALARM I' IE.'.... CONIACr5 1 `.E COMPATIBLE �. O INDICATOR D STB R !:je-UC }a�4.tVOC © �`�S- ;.E CONTROL UNIT NOT ELM/RU-2 1 USE AN — I 1 cuetN — —— LNE 'Toe relay=teas aro shown in the Nan-Alarm/System Reset condemn. TO NEX1 eA a Deme Note: The illustration above is typical wiring for Models DB 11 and DB-11E(using Models FP-11,FPI-11,FS-DP,FS-DPT,and FS DT detectors). OB-11 iNOREMOre osvtOE) read IREMOTE RELAY BASE) TO NEXT BASE OO NOT L.Et•' it / /--►USE AN ENO OE TOINITIATINC ♦ • a. O O&E O TT 5 to MOTE air ta. 5 1a 1 INDUSTRY,1NG. S lb MARY L. I 1 NC;si OON1mCT4 fi lb + ND 1i l OMPATIBLe ♦ O E s TWO— •a: a-4C•�i ISA.t2n!(4C • 0 '1')6-re ilr CONTROL,UNIT .4 itL4W lRW/C TO 3A. =tit USE AN at- 1,., I.. ... .-. ..�.� _� f�cue 'The relay contacts are shorn>n the Non-Alarm/System Resat corention. TO NeXT BABE OEVCE ^NFP-t1AMFPT-11+1#PO•il/SFP-1t+SFPT-t1ISFPO-11 a a sky insensitive detector.Line l and Line 2 can be ether Ma of the leap. NOTE.SFP-11 Sedan debctoa are approved fa use et Canada only. Note: The illustration above is typical wiring for Models DB-11 and DB-11E(using Models HFP-11 Series and SFP-1 1 Series detectors). 1381 TIE tro1EXT aev ?MOTS NELAYEASE OQNOT EN) MOW.DEalN Ce CON CORM *PUS MIMI.NWq 2041.4 TONtlGTaei CACAO OP BEATEN N8J9TM, •••• ili'Y• T/ERELAVCONMLTE NG CONTRCILRAMC •1 . fl...r.$COMAL'TS ME II«108 NTIE I Ask,as WC LAIVOYSEm RESET ODLxTON .T01EXT IMAM LNE2 LME2 Down T1¢MEM a LIE DEVICE W2EBOOME1®lC TIMM/WA ENTER Oi EXR ELECIRCALrw Cl OReOEtTE SCE ta,WIFE MMECTEeT0Tete TIM 14112l0asA11 ACEORae OR 10p4*PCMS2 MI=1PPUCAIKN Note: The illustration above is typical wiring for Model DB2-HR for polarity-insensitive detectors). Details for Ordering Mode! ' �) cart 716 Illi ,�," ',' nnOdel*. at 1 ,, 11" Descr .3tion] III i i: ,ipesct°iptiorl,� �II�I�, Number, umbar �l'i -Pumper I�INumoer ,1' (,li� v v AD2-P 500-649706 Air-Duct Housing FP-11 500-095112 FirePrintr.Intelligent Detector AD2-PR 500-649707 Air-Duct Housing with Relay FP-11C 500-095112C FirePrintfls Intelligent Detector[Canada] DB-11 500-094151 Low-Profile Surface-Mount Base _ FPT-11 500-095918 Thermal Detector DB-11C 500-095687 Low-Profile Surface-Mount Base[Canada] FPT-11C 500-095918C Thermal Detector[Canada] DB-11E 500-094151E Smaller-Diameter Detector Base HFPO-11 500-034800 FS-250 Addressable Detector DB-HR 500-033220 Relay Base for'H'-Series Intelligent Detector HFP-11 500-033290 FirePrintfe Detector DB2-HR 554370-F12-A1 Relay base compatible with'S'-Line and'C'-line detectors; HFPT-11 500-033380 Thermal Detector backwards compatible with Model'H'-series detectors Ht121 554372-F3-A1 Heat Detector DT-11 500-095430 135°F{57.2°C}Low-Profile Thermal Detector OH121 S54372-F2-A1 Multi-Sensor Smoke Detector DT-11C 500-095983 Low-Profile Thermal Detector[Canada] OP121 554372-Fl-A1 Photoelectric Smoke Detector FD0421 554320-F4-A1 Photoelectric Smoke Detector PE-11 500-094150 Conventional Photoelectric Smoke Detector FDOT421 554320-F6-A1 Addressable Multi-Criteria Fire Detector Photoelectric Smoke Detector with 135°F FDT421 554320-F5-A1 Thermal(Heat)Detector PE-11T 500-095150 {57.2T)Thermal Sensor FDOOT441 554320-F7-A1 Multi-Criteria Fire Detector with ASAtechnologyTe SFP-11 500-33290C Photo/Thermal Detector[Canada] FDOOTC441 554320-F8-A1 Multi-Criteria Fire I CO Detector with ASAtechnologyi^^ SFPO-11 500-34800C Photo Detector[Canada] LK-11 500-695350 Base Locking Kit for Model'11'-series detectors SFPT-11 500-033380C Detector Package[Canada] Notice: This marketing data sheet is not intended to be used for system design or installation purposes. For the most up-to-date information,refer to each product's installation instructions, Fire Safety Fire Safety 8 Fernwood Road 2 Kenview Boulevard SIEMENS Industry, Inc. Florham Park,NJ 07932 Brampton,Ontario Building Technologies Division Tel:(973)593-2600 (sli-Fs) L6T 5E4/Canada September 2012 FAX:(908)547-6877 Printed in U.S.A. Tel:(905)799-9937 Supersedes sheet dated 4/12 (Rev.1) URL:www.usa.Siemens.com/Fire FAX:(905)799-9858 COOPER Notification Series E70 Speakers and Speaker Strobes t FIRE I • FIRE SERIES E70 STROBE SERIES E90 SERIES E90 SERIES E70 STROBE SPEAKER SPEAKER Description Features The Wheelock Series E Low Profile Speakers and Speaker Strobes • are designed for high efficiency sound output, with dual voltage Approvals include: UL Standard 1971, UL Standard 1480, (25/70 VRMS) capability and field selectable taps from 1/8 to 2 Newyork City l(FM) California State Fire Marshal(Cala by watts. The low profile design incorporates a speaker mounting plate Factory Mutual(FM)and Chicago(BFP) See approvals by for faster and easier installation. Each model has a built-in level model in Specifications and Ordering Information adjustment feature and an aesthetic two(2)screw grille cover. • ADA/NFPA/ANSI compliant The Series E Speaker Strobe models incorporate the Low Current • Complies with OSHA 29 Part 1910.165 draw Series RSS Strobes. • Wall mount models are available with Field Selectable Strobe options for wall mount models include 1575 or Wheelock Candela Settings of 15/30/75/110cd or 135/185cd(Multi- patented MCW multi-candela strobe with field selectable candela Candela models),or 1575cd(Single Candela model) settings of 15/30/75/110cd or the high intensity MCWH strobe with field selectable 135/185a • Ceiling mount models are available with field selectable candela settings of 15/30/75/95cd or 115/177cd (Multi- Ceiling mount models are available in Wheelock patented MCC candela models) multi-candela ceiling strobe with field selectable intensities of • 15/30/75/95cd or the high intensity MCCH strobe with field Strobes produce 1 flash per second over the regulated voltage range selectable 115/177cd. • Series E Speakers and Speaker Strobes provide high audio 24 VDC with wide UL"Regulated Voltage" output with clear audibility and are designed to meet the critical using filtered DC or unfiltered VRMS input voltage needs of the life safety industry for effective emergency voice • Synchronize using the Wheelock Sync Modules or panels communications, tone signaling and visible signaling to alert the with built-in Wheelock Patented Sync Protocol hearing impaired. •The strobe portion of all Series E Speaker Strobes may be Field selectable taps for 25 or 70 VRMS operation from 1/8 watt up to 2 watts synchronized when used in conjunction with the Wheelock DSM Sync Modules,Wheelock Power Supplies or other manufacturers • High efficiency design for maximum output at minimum panels incorporating the Wheelock Patented Sync Protocol. wattage across a frequency range of 400 to 4000 HZ Wheelock synchronized strobes offer an easy way to comply with • Fast installation with IN/OUT screw terminals using#12 to ADA recommendations concerning photosensitive epilepsy. #18 AWG wires Series E Speaker Strobes are UL Listed for indoor use under Standard 1971 (Signaling Devices for the Hearing-Impaired)and Standard 1480(Speaker Appliances),and use a Xenon flashtube with solid state circuitry enclosed in a rugged Lexan® lens to provide maximum reliability for effective visual signaling. All inputs are supervised and employ IN/OUT wiring terminals for fast installation using#12 to#18 AWG wiring. Color options for the Series E Speakers and Speaker Strobes are red,white and nickel plated. YLIip MEA APPROVED S5391 151-92-E 7125-0785:152 7320-0785:134(Speaker) NOTE:All CAUTIONS and WARNINGS are identified by the symbol A.All warnings are printed in bold capital letters. A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING,SPECIFYING OR APPLYING THIS PRODUCT. VISIT WWW.COOPERNOTIFICATION.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS,CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION,INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION,WHICH COULD RESULT IN PROPERTY DAMAGE,AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. General Notes: • Strobes are designed to flash at 1 flash per second minimum over their"Regulated Voltage Range". Note that NFPA-72 specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second. • All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971. • "Regulated Voltage Range"is the newest terminology used by UL to identify the voltage range. Prior to this change UL used the terminology"Listed Voltage Range". Table 1: UL Max Current* E70/E90 E70 Strobe Current-Wall Mount E90 Strobe Current-Ceiling Mount Speaker 241575W 24MCW 24MCWH 24MCC 24MCCH Strobes 1575cd 15cd 30cd 75cd 110cd 135cd 185cd 15cd 30cd 75cd 95cd 115cd 177cd 16-33 VDC 0.090 0.060 0.092 0.165 0.220 0.300 0.420 0.065 0.105 0.189 0.249 0.300 0.420 Table 2: E70/E90 UL Reverberant dBA @ 10 Feet** *UL max current rating is the maximum RMS current watts 1/8 1/4 1/2 1 2 within the listed voltage range (16-33v for 24v units). For strobes the UL max current is usually at E Speaker 77 81 83 86 89 the minimum listed voltage(16v for 24v units). For E Speaker Strobe 76 80 82 85 88 audibles the max current is usually at the maximum **dBA ratings are based on testing under UL Standard 1480. listed voltage(33v for24v units). For unfiltered FWR ratings,see installation instructions. Wiring Diagrams# SERIES E SPEAKER&STROBE OPERATE SERIES E SPEAKER STROBES SYNCHRONIZED INDEPENDENTLY(NON-SYNC OR SYNC) WITH MULTIPLF5AM MODULES FROM Audible AC it PRECEDING + TO NEXT 0+ Note: Figure APPLIANCE APPLIANCE Strobe NAC Cir. Y OR VOICE F OR EOLR f I0 ©, shows intercon- EVACUATION I DSM#2 nection to strobe PANEL A Audible NAC Cir PROM ——_ — TO NEXT PRECEDING r —— STROBE SlrobeNACCir. ,Sync through sync _ FROM,SYNC - - __ (� ■��+ 1 SMODULE, rt 1 r - EOOLR ` , ©�© module. Speaker POWER SUPPLY �! n Audible NAC Cir I DSM" portion requires 2 nc OR —UU$ FACP Strobe NAC Cir. L'=+ BM tors to FACPn,duc- STROBE SPEAKER DSM Interconnecting wiring shown.Maximum of twenty(20) SERIES E SPEAKER STROBE APPLIANCES SERIES E SPEAKER STROBE APPLIANCES&RSS SYNCHRONIZED WITH DSM MODULE SINGLE STROBES SYNCHRONIZED WITH WHEELOCK POW- CLASS "A" DSM ER SUPPLIES6enes PS Power Supplies STROBE + NAC SYNC CIRCUIT - OUT ,/+OUT, E a CM ri OUTPUTS EOLR /+IN1 ©�© ©Z F 1-4 �J mil 1 'MI1aU51 4-CLASS �� I < • • Pril�/+AUDIBLE OR E2-CLASSitt4 A MINUS2 CP STROBE p+oUTz NAC CIRCUIT < RETURN E Series PS Power Supplies 1 For wiring information on the Wheelock power supplies, please refer to Data Sheet#S9100. *For detail using DSM Sync Module refer to Data Sheet S3000 or Installation Instructions P83177 for DSM. For wiring information on the power supplies refer to Installation Instructions P84905. Specifications and Ordering Information Strobe Sync w/ Model Model Model Order Wall Ceiling DSM or Strobe Mounting Op- Agency Approvals Model Code Mount Mount Wheelock Power Candela Color Color Color tions Supplies RED White Nickel UL MEA CSFM FM BFP E70-24MCW-FR 9022 X - X 15/30/75/110 X - - L,O,P,Q,R,U,Y X X X X X E70-24MCW-FW 9023 X - X 15/30/75/110 - X - L,O,P,Q,R,U,Y X X X X X E70-24MCW FN 3099 X - X 15/30/75/110 - - X Q,U X X X X X E70-241575W-FR 7871 X - X 15(75 on Axis) X - - L,O,P,Q,R,U,Y X X - X X E70-241575W-FW 7876 X - X 15(75 on Axis) - X - L,O,P,Q,R,U,Y X X - X X E70-241575W-FN 3100 X - X 15(75 on Axis) - - X L,O,P,Q,R,U,Y X X - X X E70-R 7866 X X - - X - - Q,U XX X XX E70-W 7868 X X - - - X - Q,U XX X XX E70-N 3108 X X - - - - X Q,U XX X XX E70-24MCC-FW 0102 X X 115/177 - X - Q,U,V X X X X X E70-24MCWH-FR 3470 X - X 135/185 X - - L,O,P,Q,R,U,Y X X X X - E70-24MCWH-FW 3474 X - X 135/185 - X - L,O,P,Q,R,U,Y X X X X E70-24MCWH-FN 0059 X - X 135/185 - - X Q,U X X X X - E90-24MCC-FW 3166 - X X 15/30/75/95 - X - Q,U,V X X X X - E90-24MCC-FR 3165 - X X 15/30/75/95 X - - Q,U,V X X X X - E90-24MCC-FN 3185 - X X 15/30/75/95 - - X Q,U,V X X X X - E90-W 7869 X X - - - X - Q,U,V X X X X X E90-R 7867 X X - - X - - Q,U,V XX X XX E90-N 3109 X X - - - - X Q,U,V X X X X X E90-24MCCH-FW 3471 - X X 115/177 - X - Q,U,V X X X X - E90-24MCCH-FR 3481 - X X 115/177 X - - Q,U,V X X X X - E90-24MCCH-FN 0062 - X X 115/177 - - X Q,U,V X X X X - Also comes in NW(no writting).Models available with no writting,may be subject to minimum quantity order. Architects and Engineers Specifications The speaker appliances shall be Wheelock Series E Speakers and the speaker strobe appliances shall be Wheelock Series E Speaker ,--T, - ' mmmMlMMMMMMMMMMMM.M...M.M.I_ Strobes or approved equals.The speakers shall be UL Listed under Standard 1480 for Fire Protective Service and speakers equipped with strobes shall be listed under UL Standard 1971 for Emergency Devices for the Hearing-Impaired. In addition,the strobes shall be certified to meet the requirements of FCC Part 15,Class B. All speakers shall be designed for a field selectable input of either 25 or 70 VRMS,with selectable power taps from 1/8 watt to 2 watts. All models shall have listed sound output of up to 87 dB at 10 feet and a listed frequency response of 400 to 4000 Hz. The speaker shall also incorporate a sealed back construction.All inputs shall employ terminals that accept#12 to#18 AWG wire sizes. The strobe portion of the appliance shall produce a flash rate of one(1)flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan®lens.The strobe shall be of low current design.Where Multi-Candela Speaker Strobes are specified, the strobe intensity shall have field selectable settings and shall be rated per UL Standard 1971 at 15/30/75/110cd or 135/185cd for wall mount and 15/30/75/95cd or 115/177cd for ceiling mount. The selector switch for selecting the candela shall be tamper resistant. The 1575 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75 candela on-axis is required(e.g.ADA compliance). When synchronization is required,the strobe portion of the appliance shall be compatible with Wheelock DSM sync modules,Wheelock Power Supplies or other manufacturers panels incorporating the Wheelock Patented Sync Protocol.The strobes shall not drift out of synchronization at any time during operation. If the sync module or Power Supply fails to operate, (i.e., contacts remain closed),the strobe shall revert to a non-synchronized flash rate. The speaker and speaker strobe appliances shall be designed for indoor surface or flush mounting.The speaker and speaker strobe shall incorporate a speaker mounting plate with a grille cover which is secured with two screws for a level, aesthetic finish and shall mount to standard electrical hardware requiring no additional trimplate or adapter. The finish of the Series E speakers and strobe speakers shall be white, red,or nickel plate. All speaker and speaker strobe appliances shall be backward compatible. Member WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY S1610 E70/E90 06/11 NJ Location 273 Branchport Ave. Long Branch,NJ 07740 P:800-631-2148 F:732-222-8707 www.coopernotification.corn11411 Cooper Notification Is Wheelock® SAFEPATH° WAVES, COOPER Notification HN Series Technical Data TD001017EN Effective October 2014 HS Series Supersedes May 2013 ST Series _ Exceder Strobe, Horn Strobe, and Horn Notification Appliances Description The Wheelock Exceder Series of notification appliances .0410,6„,..„. 0.0_ 1. feature a sleek modern design that will please building owners ` with reduced total cost of ownership. Installers will benefit from its comprehensive feature list, including the most candela options in one appliance, low current draw, no tools needed for setting changes,voltage test points, 12/24 VDC operation, universal mounting base and multiple mounting options for both new and retrofit construction. a tThe Wheelock Exceder Series incorporates high reliability and high __ — — FARE N. efficiency optics to minimize current draw allowing for a greater number of appliances on the notification appliance circuit.All strobe € models feature an industry first of 8 candela settings on a single * r appliance. Models with an audible feature 3 sound settings(90,95, � �1r " , 99 dB).All switches to change settings,can be set without the use �.��t of a tool and are located behind the appliance to prevent tampering. -� Wall models feature voltage test points to take readings with a iii 1voltage meter for troubleshooting and AHJ inspection. The Wheelock Exceder Series of wall and ceiling notification appliances feature a Universal Mounting Base(UMB)designed to simplify the installation and testing of horns, strobes,and combination horn strobes.The separate universal mounting base can bepre-wired to allow full testing of circuit wiring before the appliance is installed and the surface is finished. It comes complete with a Contact Cover for protection against dirt, dust, paint and damage to the contacts.The Contact Cover also acts as a shunting device to allow pre-wire testing for common wiring issues. The Contact Cover is polarized to prevent it from being installed incorrectly and prevents the appliance from being installed while it is on the UMB. When the Contact Cover is removed the circuit will show an open until the appliance is installed.The UMB allows for consistent installation and easy replacement of appliances if required.Wall models provide an optional locking screw for extra secure installation,while the ceiling models provide a captivated screw to prevent the screw from falling during installation. : - ET•N Powering Business Worldwide Technical Data TD001017EN HN Series Effective October 2014 HS Series ST Series Features • Environmentally friendly • Sleek modern aesthetics Low current draw • Finger slide switches • Up to 9 models now in 1 appliance draw,O • Voltage test points • 12/24VDC on a single appliance • Multiple voltages • Easy to remember model numbers • 3 Audible settings O Patented • 90, 95, 99 dB Note:All CAUTIONS and WARNINGS are identified by the symbol A.All warnings are printed in bold capital letters. • Industry leading-8 candela settings on 1 device • Wall: 15/1575/30/75/95/110/135/185 A WARNING • Ceiling: 15/30/60/75/95/115/150/177 PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING,SPECIFYING OR APPLYING THIS PRODUCT VISIT WWW.COOPERNOTIFICATION.COM OR CONTACT COOPER NOTIFICATION FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS,CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION,INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE,AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. General Notes • Strobes are designed to flash at 1 flash per second minimum over their"Regulated Voltage Range" • All candela ratings represent minimum effective strobe intensity based on UL Standard 1971. • Universal mouting base • Series Exceder Strobe products are Listed under UL Standards • Ceiling and wall 1971 and 464 for indoor use with a temperature range of 32°F to 120°F(0°C to 49°C)and maximum humidity of 93% (±2%) UL • Mounts to 5 backbox types: 1 gang, 2 gang,4" square, 464(85% UL 1971). 3.5"octal.&4" octal. (100mm for international customers) • Series Exceder horns are under UL Standard 464 for audible Universal mounting base Contact cover signal appliances(Indoor use only). ,,,, Compatibility and requirements # 1► :l w 0 , _ • Synchronize using the Wheelock®Sync Modules or panels with m � built-in Wheelock®Patented Sync Protocol ti it td - .11.4'1.-'.'.›1":1''',7::-, ' s , ¢, y 3'rF ,, • Compatible with UL"Regulated Voltage" using filtered VDC or ,, .°` ` '' ' ' , ' unfiltered VRMS input voltage C '' 1" • Strobes produce 1 flash per second over the"Regulated . Voltage" range Common base for wall and ceiling with 5 mounting options Compliance • Voltage test points for quick troubleshooting and easy spot UL 1971, UL 464, ULC, CSFM, FM checking(wall models only) • ADA/NFPA/ANSI/OSHA • RoHS , . . --***\ 0 0 2 EATON www.eaton.com HN Series Technical Data TD001017EN HS Series ST Series Effective October 2014 Table 1. Strobe Ratings per UL Standard 1971 UL Max Current® 24 VDC/24 FWR 12 VDC Regulated Voltage Model Range VDC 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 ST 8.0-33.0 0.057 0.070 0.085 - 0.135 0.163 0.182 - 0.205 - - 0253 0.110 0.140 STC 8.0-33.0 0.061 - 0.085 0.103 0.135 0.163 - 0.182 - 0.205 0253 - 0.110 - Table 2. Horn Strobe Ratings per UL 1971 &Anechoic at 24 VDC UL Max Current®at Anechoic 99 dBA 24 VDC 12 VDC Regulated Voltage Model Range VDC 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 HS 8.0-33.0 0.082 0.095 0.102 - 0.148 0.176 0.197 - 0.242 - - 0.282 0.125 0.159 HSC 8.0-33.0 0.082 - 0.102 0.141 0.148 0.176 - 0.197 - 0.242 0.282 - 0.125 - UL Max Current®at Anechoic 95 dBA 24 VDC 12 VDC Regulated Voltage Model Range VDC 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 HS 8.0-33.0 0.073 0.083 0.087 - 0.139 0.163 0.186 - 0.230 - - 0.282 0.122 0.153 HSC 8.0-33.0 0.073 - 0.087 0.128 0.139 0.163 - 0.186 - 0.230 0272 - 0.122 - UL Max Current®at Anechoic 90 dBA 24 VDC 12 VDC Regulated Voltage Model Range VDC 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 HS 8.0-33.0 0.065 0.075 0.084 - 0.136 0.157 0.184 - 0.226 - - 0.267 0.120 0.148 HSC 8.0-33.0 0.065 - 0.084 0.120 0.136 0.157 - 0.184 - 0.226 0.267 0.120 ,O UL max current rating is the maximum RMS current within the listed voltage range(16-33 VDC for 24 VDC units).For strobes the UL max current is usually at the minimum listed voltage(16 VDC for 24 VDC units).For audibles the max current is usually at the maximum listed voltage(33 VDC for 24 VDC units).For unfiltered ratings,see installation instructions. Table 3. Horn Ratings per UL Anechoic Model Legend RegulModel Range Voltageted geVDC 99 dB 95 dB 90 dB HN = Horn R = Red HN 16-33.0 0.064 0.044 0.022 ST = Strobe A = Agent Lettering(strobes only) HNC 16-33.0 0.084 0.044 0.022 HS = Horn Strobe AL = Alert Lettering(strobes only) HN 8.0-17.5 0.047 0.026 0.017 C = Ceiling Mount N = No Lettering(strobes only) HNC 8.0-17.5 0.047 0.026 0.017 W = White Example 1:STRC=Strobe,Fled,Ceiling Mount Table 4. Specification&Ordering Information Example 2:HSR=Horn Strobe,Red,Wall Mount Sync w/DSM or Example 3:HSW=Horn Strobe,White,Wall Mount Model Strobe Candela Wheelock Power 12/24VDC® OtonMounting Example 4:STW-AL=Strobe,White,Wall Mount,Alert Lettering Horn Strobes HSR 15/1575/30/75/95/110/135/185 X X UMB© HSW 15/1575/30/75/95/110/135/185 X X UMB© i' r ` ' h � HSRC 15/30/60/75/95/115/150/177 X X UMBO HSWC 15/30/60/75/95/115/150/177 X X UMB© Strobes �, STR 15/1575/30/75/95/110/135/185 X X UMB© ,,,,�� ,. STW 15/1575/30/75/95/110/135/185 X X UMBO v >' STRC 15/30/60/75/95/115/150/177 X X UMBO ' STWC 15/30/60/75/95/115/150/177 X X UMB© « N. '" Horn .. do... HNR X X UMBO HNW X X UMB© ` HNRC X X UMBO L HNWC X X UMB© Example:HSR Example:HSWC ,O 12 VDC models feature 15&15/75 settings OO UMB=Universal Mounting Base EATON www.eaton.com 3 Technical Data TD001017EN HN Series Effective October 2014 HS Series ST Series Architects and Engineers Specifications The notification appliances shall be Wheelock Exceder Series HS Audible Strobe appliances, Series ST Visual Strobe appliances and Series HN Audible appliances or approved equals.The Series HS and ST Strobes shall be listed for UL Standard 1971 (Emergency Devices for the Hearing-Impaired)for Indoor Fire Protection Service.The Series HS and HN Audibles shall be UL Listed under Standard 464(Fire Protective Signaling).All Series shall meet the requirements of FCC Part 15 Class B.All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP)with the ability to operate from 8 to 33 VDC. Indoor wall models shall incorporate voltage test points for easy voltage inspection. The Series HS Audible Strobe and ST Strobe appliances shall produce a flash rate of one(1)flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan®lens.The Series shall be of low current design.Where multi- candela appliances are specified,the strobe intensity shall have 8 field selectable settings at 15, 15/75, 30, 75, 95, 110, 135, 185 candela for wall mount and 15,30,60, 75,95, 115, 150, 177 candela for ceiling mount.The selector switch for selecting the candela shall be tamper resistant.The 15/75 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75 candela on-axis is required (e.g.,ADA compliance).Appliances with candela settings shall show the candela selection in a visible location at all times when installed. The audible shall have a minimum of three(3)field selectable settings for dBA levels and shall have a choice of continuous or temporal (Code 3)audible outputs. The Series HS Audible Strobe, ST Strobe and Series HN Audible shall incorporate a patented Universal Mounting Base that shall allow mounting to a single-gang, double-gang,4-inch square,3.5-inch octal,4-inch octal or 100mm European type back boxes.Two wire appliance wiring shall be capable of directly connecting to the mounting base.Continuity checking of the entire NAC circuit prior to attaching any notification appliances shall be allowed. Product shall come with Contact Cover to protect contact springs. Removal of an appliance shall result in a supervision fault condition by the Fire Alarm Control Panel(FACP).The mounting base shall be the same base among all horn, strobe, horn strobe,wall and ceiling models.All notification appliances shall be backwards compatible. The Series HS and ST wall models shall have a low profile measuring 5.24" H x 4.58"W x 2.19" D. Series HN wall shall measure 5.24" H x 4.58"W x 1.6" D. The Series HSC and STC shall been round and have a low profile with a diameter of 6.68"x 2.63" D. Series HNC ceiling shall have a diameter of 6.68" x 1.50" D. When synchronization is required,the appliance shall be compatible with Wheelock's DSM Sync Modules,Wheelock Power Supplies or other manufacturer's panels with built-in Wheelock Patented Sync Protocol.The strobes shall not drift out of synchronization at any time during operation. If the sync protocol fails to operate,the strobe shall revert to a non-synchronized flash-rate and still maintain(1)flash per second over its Regulated Voltage Range.The appliance shall also be designed so that the audible signal may be silenced while maintaining strobe ` activation when used with Wheelock synchronization protocol. Wall Appliances:UL Standard 1971, UL Standard 464, California State Fire Marshal(CSFM), ULC, FM, RoHS Ceiling Appliances:UL Standard 1971, UL Standard 464, California State Fire Marshal(CSFM), ULC, FM, RoHS Note:Due to continuous development of our products,specifications and offerings are subject to change without notice in accordance with Cooper Wheelock Inc.,dba Cooper Notification standard terms and conditions. IrEillitil Member WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Eaton 1000 Eaton Boulevard Cleveland,OH 44122 United States Eat on.com Eaton Cooper Notification 273 Branchport Ave. Long Branch,NJ 07740 CooperNotif ication.com E.T N ©2018 Eaton • All Rights Reserved Eaton is a registered trademark. Printed in USA Powering Business Worldwide Publication No.TD001017EN All other trademarks are ro e rty October 2014 of their respective owners. p s � Data Sheet Specialized Devices Air-Duct Housings (FDBZ Series) Models FDBZ492, FDBZ492-HR, FDBZ492-R and FDBZ492-RP{with FDBZ-WT and FDBZ492-RTL} ARCHITECT AND ENGINEER SPECIFICATIONS • Four(4) models available • Addressable and conventional with and without relays • Compatible with Siemens—Fire Safety conventional i i, is and addressable fire-alarm control panels(FACPs) • p • Magnet test feature with the Model OP121 1 FDBZ series of air-duct housings conventional detector hi [FDBZ492,FDBZ492-HR,FDBZ492-R&FDBZ492-RP] • Design for air-velocity range of 100 Remote alarm indicator ' to 4,000 feet-per-minute(fpm) IFDBz492-RTL] ' " • Robust,compatible conventional remote indicator test switch that incorporates tri-color light-emitting diode(LED) • Clear housing cover with smoke test port on cover for quick identification of detector type • Removable via four(4)captive-thumb screws(no tools required) — • Includes a smoke I aerosol detector test port Watertight housing • Optional NEMA 4X-reinforced,stainless-steel and [FDBZ-WT] • Self-contained model available with'on-board' watertight enclosure available, Model FDBZ WT No tools required for cover removal,sampling and power supply for conventional detectors exhaust-tube installations • Expanded temperature range • Relay models available • Trouble-event activation upon front-cover removal • ®UL268A Listed,®ULC-5529 Listed; • Alarm LED visible from front FM (#3010), CSFM (#3240-0067:0265)Approved Product Overview The Siemens—Fire Safety Model'FDBZ'-series of air- Notes-(cont.'d): With either the Cerberus PRO series or duct-detector housings are designed for use with Firefinder'XLS series of FACPs, up to 252-addressable detectors with relays per circuit maybe used.The connection of an Siemens Model'H'series,Cerberus PRO series and intelligent remote lamp(ICED)and a remote relay is allowed for Model OP121 detectors. (see: Details for Ordering for a complete list of compatible devices). each detector simultaneously. Designed for installation directly to heating,ventilating Specifications and air-conditioning (HVAC)duct systems,the Model The Model'FDBZ'-series of air-duct housings are uniquely , a 'FDBZ'-series of duct housings complies with National designed to use with the photoelectric detector. Sensitivity Fire Protection Association Standard (NFPA) No.'s 72 of Models PE-11,PE-11C,OP121,and 8854 conventional and 90A,and is Underwriters'Laboratories Listed. detectors can be verified for calibration via LED visual status or a Model RSAW-11, Model RSAC-11 or FDBZ492-RTL multi- When equipped,the air duct detector housing will signal the presence of smoke being carried through color remote lamp. A green flash indicates the detector has passed its self test. Amber indicates a Trouble condition,and the duct system. Air duct detectors are not intended to be substituted for open-area detection. red indicates an Alarm event. Notes: Most conventional time-control equipment guarantee Sensitivity for Models FP-11,HFP-11,SFP-11,HFPO-11, only one(1)detector per zone when the detector's SFPO-11,OP921,00H941,OOHC941,8710,and 8713 operated relay function is critical. The connection of a intelligent detectors is verified from the multi-color LED of remote lamp and a remote relay-per detector- is the respective detector,or its sensitivity reading may be allowed. Refer to the installation manual of the respective conventional FACP. printed by command from the corresponding FACP to an optional printer. Cerberus® PRO 9906 Fire Safety Products Model 'FDBZ' Series of Air-Duct Housings and Detectors al Answers for infrastructure SIEMENS v _ _ Specifications — (continued) Sampling Tube Selection Table The remote alarm indicator(Model FDBZ492-RTL)allows for @ 1, `1,' t o� °� = Same lin Tube Duct-Width iii ���� i, manual testing via a key-switch for conventional and ro , Ill_ �� (Model !), addressable detectors,as well as the conventional and For duct widths 6"to 1' 5T-10 addressable air-duct housing with relay. Model FDBZ492- For duct widths 1'to 3' 5T-25 RTL,which mounts remotely from the conventional and For duct widths 3'to 5' addressable air-duct housing,allows for manual relay- (requires support) ST-50 output control. The duct-detector remote indicator key- For duct widths 5'to 10' switch also indicates the current state of the detector. (requires support) ST 100 The watertight housing (Model FDBZ-WT),which allows the Maintenance of the detector is easily accomplished via the air-duct detector housing to be installed inside the separate removal of the duct-housing sampling chamber cover. The NEMA 4X enclosure,is for installations for either an outdoor detector,which plugs into the housing,is easily removed area or in environments where excessive moisture is for cleaning or replacing by a trained technician. prevalent. All that is necessary for installation of the air-duct detector Each detector unit employs a cross-sectional sampling is the cutting of three(3)small holes for the Sampling Tube principle of operation. Inlet sampling tubes are installation(template included),and the drilling of two(2) available in four(4) lengths(see: Sampling Tube holes for mounting the air-duct housing. The unit is then Selection Table). Outlet sampling tubes are one(1) easily mounted in place,and connection made to the common length and draw. A continuous,cross-sectional existing wires or terminals—if optional accessories are sample of air moves through the duct. Stratification or skin utilized. No mechanical tools are required for removing the affect phenomenon that occurs in the duct can prevent cover or connecting the sampling and exhaust tubes to an smoke(especially in large ducts)from reaching a spot-type air-duct housing. detector. Models ST-50 and ST-100 require support. However,Model In addition,the unique design of the sampling chamber ST-100 is shipped in two(2)5-ft.(152 cm.)pieces with a insures uniform sensitivity in air velocities, ranging from a coupling for field assembly. low of 100 fpm to as high as 4,000 fpm. Each air-duct housing comes with three(3)wiring entry ports: Technical Data • Two(2)3/4"conduit knockouts ■ One(1)1/2"conduit opening Operating The inlet sampling tube length is determined by the width Temperature +32°F(0°C)to 120°F(49°C) of the air duct being protected. The inlettube—greater Ranges: than and nearest to the duct width—should be used(see: Sampling Tube Pressure >0.01 inches; Sampling Tube Selection Table).The inlet tube can then be Range of Differences: < 1.2 inches of water trimmed at the job site to the exact width of the duct.The column outlet sampling tube for all ducts—irrespective of width— has a fixed length of approximately 5.5 inches(14cm.),and Relative Humidity: 0—95%; non-condensing is supplied with the air-duct housing. Air Pressure/ No effect 1 Note: When the use of a remote relay is required,order Altitude Range: No limitations Model FDBZ492-R for conventional systems;Model FDBZ492-HR for addressable systems.When required, Air-Duct Velocity: 100—4,000 ft.I min a separate watertight enclosure(Model FDBZ-WT), which is designed to contain the air-duct housings is (0.51—20m/sec) available. Dimensions: {H-x-W-x-D} (For full details,refer to installation instructions for the •Rectangular: 14.38"-x-5"-x-2.5" respective air-duct housing.) 9_ (37 cm.-x-12.7 cm.-x-6.36 cm.) Note: When a self-contained duct detector with power ■Square: 7.75"x 9" x 2.5" supply is required,order Model FDBZ492-RP. (19.7 cm. x 22.9cm. x 6.36cm.) (For full details,refer to installation instructions part Detector Weight: 1.8 Lbs.(0.82 Kg.) number A6V10330327.) SIEMENSIndustry, Inc. Building Technologies Division Cerberus® PRO Operation Details for Ordering Based on the monitoring results,the LED indicator flashes ill , `, ��� �Modei I _. P7Ct ��°i)esCriptic�Vt i`, the following colors based on the following conditions: ,— 11 Number - _ rb F�aS�I A two-wire addressable or conventional ' _Condition _�. ' duct detector(without relays)designed for�aort1#2rval direct use on heating,ventilating and air- , I\ = _' din sero Ids) conditioning(HVAC)air-duct systems. (t �� Normal supervisory operation. When equipped,the air-duct detector S54319-622- housing will signal the presence of smoke ��t Smoke sensitivityis within FDBZ492 beingcarried through the duct system. 10 9 �, rated limits. Al For use with the following Models: Detector is in Trouble — 8710 —8713 —00H941 —0P121 Yellow: condition,and needs either 4 — 8854 —HFPO-11 —OOHC941 —PE-11 — FP-11 —HFP-11 —PE-11C —SFP-11 repair or replacement. — SFPO-11 A two-wire addressable duct detector(with Alarm condition. 1 relays)designed for direct use to HVAC air- ductNo Flash:' Detector is not powered. -- systems and works with the Remote Test Switch(FDBZ492-RTL). This part has a *LED can be turned OFF. programmable relay base,and when Please follow the corresponding description of the panel used. equipped,the addressable air-duct detector FDBZ492- 554319-623- housing will signal the presence of smoke being carried through the duct system. HR Al For use with the following Models: — 8710 — FP-11 Products included with the air-duct housing: — 8713 — HFP-11 — 00H941 — HFPO-11 - (1)short-return(outlet)tube — OOHC941 — 0P921 - (1)stopper — SFP-11 — SFPO-11 - (2)#12+3/4"sheet-metal screws A two wire conventional duct detector with (1)mounting template relays designed for direct use on HVAC air- - duct systems. This detector has a relay Note: Detector and sampling tube to be purchased separately. base,and when equipped with conventional FDBZ492 R S54319-624- air-duct housing,will signal the presence of Minimum hardware required is: one(1)air-duct housing Al smoke being carried through the duct assembly;one(1)sampling tube and one(1)detector. system. For use with the following Models: - PE 11 —PE-11 C — OP121 —8854 A four-wire conventional duct detector with relays and a built-in power supply. Housing is designed for direct use to HVAC air-duct systems. It has a relay base with a built-in FDBZ492 554319 825 power source. When equipped with conventional air-duct housing,this duct RP Al detector will signal the presence of smoke being carried through the duct system. For use with the following Models: — PE 11 —PE-11C — OP121 Device is used for manual testing via a key- switch for duct-housing Models FDBZ492-R, FDBZ492-RP and FDBZ492-HR. Device mounts remotely from the conventional and FDBZ492- S54319-527- addressable air-duct housing,allowing for RTL Al manual relay-output control. The duct- detector remote key-switch also indicates the current state of the detector. For use with the following Models: •FDBZ492-HR •FDBZ492-R •FDBZ492-RP An optional,separate watertight NEMA 4X enclosure(Model FDBZ-WT)that provides added watertight protection for any of the Model FDBZ492-series duct housings.The duct housing fits into the separate 4X enclosure. This part allows the air-duct FDBZ-WT 554319-B26- detector housing to be installed in the Al separate enclosure,and can be used in either an outdoor area or in environments where excessive moisture is prevalent. For use with the following Models: — FDBZ492 — FDBZ492-R — FDBZ492-HR — FDBZ492-RP ST-10 500-649710 Sampling tube for Ducts 6"to 1' ST-25 500-649711 Sampling tube for Ducts over 1'to 3' ST-50 500-649712 Sampling tube for Ducts 3"to 5' ST-100 500-649713 Sampling tube for Ducts 5'to 10' SIEMENSIndustry, Inc. Building Technologies Division Cerberus® PRO SIEMENSCe rbe rus® PRO NOTICE—The information contained in this data-sheet document is intended only as a summary,and is subject to change without notice. The devices described here have specific instruction sheets that les Div. cover various technical,limitation and liability information. Siemens Industry, Inc.—Building Technologies Copies of these instruction sheets and the General Product Warning and Limitations document, 8 Fernwood Road • Florham Park, NJ 07932 which also contains important information,are provided with the product and,are available from Tel:(973) 593-2600 • Fax:(908)547-6877 the Manufacturer. Information contained in these documents should be consulted before specifying or using the Web:www.USA.Siemens.com/Cerberus-PRO product. For further information or assistance concerning particular problems contact the Manufacturer. Building Technologies Division September 2014—Supersedes sheet dated 8/2013 SII–Fire Safety [Printed in U.S.A 1 (Rev.4) SIEMENS Data Sheet Fire Safety&Security Products Intelligent Detection Devices Intelligent FirePrint"' Detector [For use with FireFjnder® XLS and MXL Panels] Model FP-11 ARCHITECT AND ENGINEER SPECIFICATIONS • Most sophisticated'detector intelligence'available in the Fire/Life Safety market • Multi-criteria fire detection for the price of a photoelectric detector • Remote-sensitivity-measurement capability • Easily programmed to match specific hazard profiles from the fire-alarm control panel(FACP) • Fire PrIntTM technology to distinguish between deceptive phenomena and an actual fire • Pre Alarm reporting based upon fire profile selected • • Field-cleanable chamber with replaceable chamber parts ° • System-logic activation based upon any of three(3) inputs from the detector(smoke,heat or neural network) • Supports software-based,automatic environmental compensation • EnviroLINK • Compatible with field programmer/tester • Model DPU I FPI-32 Upgrade Kit • Multi color,detector status • Backward compatible with older MXL systems light emitting diode(LED) • Rev.2 and above • Two wire operation • Optional fully programmable relay base,audible base • t9UL and�l1LC Listed; FM,CSFM&NYCFD Approved and duct housing Product Overview The Intelligent Fire Detector(Model FP-11) is a The upgrade kit(Models DPU or FPI 32)eliminates the highly evolved detection system that provides the need for cumbersome,unreliable mechanical most sophisticated level of fire protection,along programming methods,as well as reduces installation with superior nuisance-alarm immunity currently and service costs by electronically programming and available in the Fire/Life Safety industry. testing the detector prior to installation. Model FP-11 utilizes highly developed detection technology that allows the detector to distinguish Specifications non-threatening deceptive phenomena (i.e.— Model FP 11 is a plug-in,two wire and multi sensor cigarette smoke)from actual fire hazards,while detector with photoelectric and thermal inputs that is optimizing detection for the area of its intended compatible with the FireFinder XLS and MXL family of zone. Model FP 11 uses state-of-the-art FACPs. Each detector consists of a dust-resistant,field- microprocessor circuitry with error check,detector cleanable photo chamber;a solid-state, non thermal sensor,and microprocessor-based self diagnostics and supervision programs. mechanical Model FP 11 is compatible with the Siemens—Fire electronics with a low-profile plastic cover and base. Safety Model FPI-32 upgrade kit or Siemens'field- Model FP-11 utilizes state-of-the-art ASIC and surface- programmer/tester, Model DPU/FPI-32,which is a mount technology for maximum reliability. Every compact,portable and menu-driven accessory for Model FP-11 fire detector is shipped with a protective efficiently programming and testing detectors dust cover. Model FP 11 fire detector utilizes an electronically. infrared light-emitting diode(IRLED),and light sensing photodiode. Intelligent FirePrintTM Detector 61 75 SIEMENS Industry, Inc. Building Technologies Division Specifications — (continued) Under normal conditions, light transmitted by the LED The FirePrint technology for Model FP-11 monitors is directed away from the photodiode and scattered input from the photo chamber and the thermal sensor, through the smoke chamber in a controlled pattern. evaluating this information with sophisticated The smoke chamber is designed to manage light mathematical formulas or algorithms,and compares dissipation and extraneous reflections from dust data transfer to this input to the characteristics of both particles or other non-smoke airborne contaminants in threatening fires and deceptive phenomena that would such a way as to maintain stable,consistent detector deceive any ordinary detector. operation. When smoke enters the detector chamber, This technology was developed over years of research light emitted from the IRLED is scattered by the smoke and reviewing the results of over 20 years of fire-test particles,and is received by the photodiode. data in one of the world's most advanced fire research Model FP-11 also utilizes a modern,accurate and centers. The results of this research are the shock-resistant thermistor to sense temperature mathematical models that form the algorithms used in changes. The'on-board'FirePrint technology FirePrint. No other fire detector has this level of allows the detector to gather smoke and thermal data, intelligence or this amount of research and analyzing this data in the detector's'neural network.' development supporting its design. By comparing data received with the common The software of the microprocessor can identify and characteristics of fires,or fire fingerprints, Model FP-11 disregard false input caused by radio frequency(RFI) can compare these'fire prints'to those of deceptive and electromagnetic(EMI) interference,and validates phenomena that cause other detectors to go into Alarm all Trouble conditions before annunciating or reporting mode. to the control panel. The microprocessor for Model FP- This advanced FirePrint technology allows Model FP-11 11 uses an integral electronically erasable to accurately determine a true fire hazard from non- programmable read-only memory(EEPROM)to store threatening,deceptive phenomena—without the need the detector's address and other critical operating to use alarm-delaying verification and confirmation parameters,which include the assigned program techniques;thus decreasing the probability of losses in values for Alarm and Trouble—command thresholds. infrastructure from an actual fire. Communications within the detector;between Model Model FP-11 provides the highest level of detector FP 11 and the FACP,or with the field programmer 1 intelligence available today with a detector I control- tester(Model DPU I FPI 32),are supervised and panel link that allows the user to program the detector safeguarded against disruption by reliable, for the specific hazard profile. microprocessor-based error checking routines. Detectors are optimized by selecting one(1)of Additionally,the microprocessor supervises all EEPROM the following applications: memory locations and provides a high degree of • Office/Retail EEPROM failure fault tolerance. • Lobby Model FP-11 determines its operating status(Normal, • Computer room Alarm,or Trouble modes) based upon the difference • Dormitory between the alarm-threshold values stored in the • Healthcare facility detector's memory and the detector's latest analog • Parking garage measurement. The detector then communicates • Utility I transformer room changes in its status to the FACP. • Hostile environment In addition,the FACP will sample the value of the • Precious storage •Air duct analog signal for Model FP-11 over a period of time, in •Warehouse I light manufacturing order to determine if those values indicate excessive buildup in the photo chamber. In the event of Once programmed,the software does the rest— excessive buildup,the FACP will accurately indicate no guessing on detector sensitivities or alarm which detector shall require maintenance. verification—the FACP programs Model FP-11 for the protected area without any confirmation delays. Model FP 11 is listed as a self testing device. The LED for Model FP-11 flashes green every four(4)seconds, Once optimized for the hazards in the protected area, indicating communication with the FACP,and that it Model FP-11 provides the utmost means in detection. has passed its self-test. Should the detector sense a Should the operator or installer forget fault or failure within its systems,the LED will flash to program the detector, Model FP-11 will revert amber,and the detector will transmit that data to the to a default setting that, in turn,allows operation FACP. A quick visual inspection is sufficient to indicate as a standard photoelectric or photothermal detector. the condition of the detector at any time. SIEMENS Industry, Inc. Building Technologies Division Specifications — (continued) If more detailed information is required,a printed Model FP-11 uses the low-profile,surface-mounting report can be provided from the FACP, indicating the base, Model DB-11. This base mounts on a 4-inch status and settings assigned to each individual octagon,square,or a single-gang electrical box. The detector. base utilizes screw-clamp contacts for electrical When Model FP-1 lactivates into Alarm mode,the connections and self-wiping contacts for increased detector will flash amber,and will transmit that data to reliability. the FACP. When the FACP confirms the condition of The base can be used with the optional Model LK-11 the detector,the FACP will instruct Model FP-11 to detector locking kit,which contains 50 detector locks, flash red—and continue to flash red—until the system as well as an installation tool,thus preventing is reset manually at the FACP. At that same time,any unauthorized removal of the detector head. Model DB- user-defined system alarm functions programmed into 11 has integral,decorative plugs to cover the outer the system are activated. Each Model FP-11 detector mounting screw holes. can operate one(1) remote alarm indicator;one(1) Model FP-11 is electrically compatible with existing auxiliary relay,or one(1)audible base. MXL-detector accessories,including relays, remote Detector sensitivity,calibration and identification are lamps,duct housings and audible bases. With duct dynamically supervised by the FACP. Detector housings,a base adapter and new detector housing sensitivity and pre-Alarm levels are a function of the cover are required(order AD-11 UK upgrade kit). To use application chosen at the FACP,and are controlled by existing Model DB-3S base or audible base, Model FP- the panel. If an alternate, non-FirePrint mode is 11 requires a base adapter(Model DB-ADPT). selected,then the sensitivity can be changed from the FACP. Temperature and Humidity Range The Program/Test unit(Model DPU or FPI-32) upgrade All Model FP 11 detectors are%UL 864 9th Edition kit is used to program and verify the detector's address. Listed for indoor dry locations within a temperature range of 120+/3°F(49+1 2°C)to 32+/3°F(0+1 2°C)and The technician selects the accessory's program mode to a relative humidity range of 93+/2%at a temperature enter the desired address. In turn,the programmer unit(Model DPU or FPI-32)automatically sets/verifies of 90+/-3°F(32+/-2°C). the address,and tests the detector. Model DPU/FPI-32 Application Data also allows the user to change the device ID from that of a Model FP-11 detector to an older detector ID(such Installation of the Model FP 11 series of fire detectors as: ILP 1,ILPT 1,ILP 2, ID 60P or ID 60PT)to allow for requires a (2)two-wire circuit of 18 American Wire Gauge(AWG), minimum,thermoplastic fixture wire easy replacement of older detectors without the need of reprogramming the FACP. enclosed in conduit,or 18 AWG (American Wire Gauge) limited-energy,shielded-cable without conduit, if The FPI-32 upgrade kit operates on AC power or permitted by local codes. Field wiring should conform rechargeable batteries, providing flexibility and to local and national electric codes and the control convenience in programming and testing equipment panel wiring specifications. from almost any location. When in'test'mode, Model 'T-tapping'is permittedonly for Style 4(Class B)wirin DPU or FPI-32 upgrade kit will perform a series of y g' diagnostic tests without altering the address or other Model FP 11 fire detectors can be applied within the stored data,allowing technicians to determine if the maximum 30 foot center spacing (900 sq.ft.areas),as referenced in NFPA 72. This applications guideline is detector is operating properly. Model FP 11 may be installed on the same initiating based upon ideal conditions—specifically—smooth ceiling surfaces, minimal air movement,and no circuit with Models IL or ID series detectors physical obstructions between potential fire sources (Photoelectric,thermal,or ionization);Model MSI- and the detector. Do not mount detectors in close series manual stations; Model TRI-series interfaces; proximity to ventilation or heating and air-conditioning Model ICP output-control devices,or Model CZM series outlets. of addressable,conventional-zone modules. All Model FP 11 detectors can be cleaned in the field— Exposed joints or beamed ceilings may also affect safe spacing limitations for detectors.Should questions when required— by simply removing the detector cover arise regarding detector placement,observe National and unsnapping the photo chamber. There is also the Fire Protection Association(NFPA)72 guidelines. option of cleaning the interior of the detector with a clean,soft cloth or brush,or replacing the labyrinth and bug screen included in the detector maintenance kit, Model DMK-11. SIEMENS Industry,Inc. Building Technologies Division Technical Data Details for Ordering Environmental !x g - Temperature: 32°F(0°C)to 100°F(38°C) 414,0149 ,k -� E � ' __ ' z ,`; Humidity: Up to 93%RH,non-condensing FP-11 500-095112 Addressable FirePrintTe Detector Air Pressure: No effect Detector Mounting Base Alarm Temperature: 135°F(57°C) DB-11 500-094151 For Series 11 Intelligent Detectors DB-11E 500-094151E Detector Base(Small) _ Electrical Air-Duct Housing Voltage: 16–27 VDC AD2-P 500-649706 (for use with Models FP-11,HFP-11,1 HFPO-11 and PE-11 Detectors) Ripple: 3V,peak-to-peak Supervisory Current: 11 o[,A max _____ Air-Duct Hous�nq _____ AD2-XHR 500-649708 (for use with Models FP-11,HFP-11, Alarm Current: 33-50mA HFPO-11 Detectors with Relay) ADBX-11 500-096181 Audible Base Dimensions DB-X11 RS 500-096125 Relay Base for Model 11-series Intelligent Detectors Diameter Base Remote Alarm Indicator i 6" RLI-1 500-390673 [15.3 cm] a 4"Octagon Box Mount,Red RLI-2 500-390674 Remote Alarm Indicator --r— i Single-Gang Mount,Red ( DMK 11 500-695338 Model 11-series Maintenance Kit (replacement labyrinth and bug screen) Height yj• DB-ADPT 500-094187 Base Adapter to Model DB-3S Base [.3m� t ii--`'''; LK-11 500-695350 Base Locking Kit for Series 11 Detectors .8• In Canada,please order: 1110.',ityl_IP 135°F Fixed Temperature,Plug-In FP-11C 500-095112C Detector Addressable FirePrintTv Detector[OULC Listed] Detector Mounting Base DB-11C 500-095687 (for Model 11-series Intelligent Detectors) [€IILC Listed] AD-11 PC 500-095984 Air-Duct Housing[€ULC Listed] DB-X11 RSC 500-093125C Relay Base for Model 11-series Intelligent Detectors[OULC Listed] ADBX-11 C 500-096181 C Audible Base for Model 11-series Intelligent Detectors[ ULC Listed] Notice: This marketing data sheet is not intended to be used for system design or installation purposes. For the most up-to-date information,refer to each product's installation instructions. Fire Safety Fire Safety 8 Fernwood Road 2 Kenview Boulevard SIEMENS Industry, Inc. Florham Park,NJ 07932 Brampton,Ontario Building Technologies Division Tel:(973)593-2600 SII FS L6T 5E4/Canada June 2012 FAX:(908)547-6877 Tel:(905)7 Supersedes sheet dated 8/10 Printed in U.S.A. 99-9937 (Rev.2) URL:www.usa.Siemens.com/Fire FAX:(905)799-9858 N I m Q I- FAPS-B1 BATTERY&VOLTAGE DROP CALCULATIONS SIEMENS FIRE ALARM SUBMITTAL VICTORIA'S SECRET WASHINGTON SQUARE MALL FAPS-B1 SPECIFICATIONS FAPS-B1 BATTERY CALCULATIONS FADS-al PANEL 24 Hours(A)Requirement for Standby Charge: PS-8 MODEL i 5 Minutes(B)Requirement for Alarm Charge: 20%Design Voltage Drop(20%Max Voltage Drop) 20%(C)Spare Battery Capacity: 3.00 Amp Max Current Draw Per Output 0.13Amp(F)Standby Total Current Draw 2.50 Amp Max Current Draw Per AUX Output 3.62 Amp(G)Alarm Total Current Draw 8.00 Amp Max Current Draw Per Panel 3.1 Amp Hr(H)Design Standby Charge=(A x F) 14 AWG Wire Gauge 0.3 Amp Hr(J)Design Alarm Charge=(B x G)/60 20:4 Volt Voltage at First Device' 0.7 Amp Hr(K)Additional Capacity Charge=(C x((A x F)+(B x G)160)) 0.13 Amp Standby Current Draw 4.1 Amp Hr(AH)Battery Amp Hour requirement=(H+J+K) 0.13 Amp Alarm Current Draw 7.0 Amp Hr Battery Size 32.0 Amp Hr Max Battery Charging Capacity FAPS-B1 VOLTAGE DROP CALCULATION RESULTS PERCENT STANDBY ALARM PERCENT OUTPUT VOLTAGE CURRENT CURRENT CURRENT LABEL VOLTAGE DROP DROP DRAW DRAW DRAW OUTPUT-1 81-1- 1,56 Volt 7.67% 0.00 Amp 1.19 Amp 39.60%... OUTPUT-2 81-2- 1.22 Volt 6,00% 0.00 Amp 0.89 Amp 29.70% OUTPUT-3 81-3- 0.00 Volt 0,00% 0.00 Amp 0.00 Amp 0.00% OUTPUT-4 81-4- 1.52 Volt 747( 0.00 Amp 1.42 Amp 47.20% AUX OUTPUT N1-AX- 0,00 Volt 0.00% 0.00 Amp 0.00 Amp 0.00%.:. Total Current Draw 0.00 Amp 3.50 Amp 43.69% FAPS-B7 VOLTAGE DROP CALCULATIONS OUTPUT-1 LABEL CD MODEL STANDBY VOLTAGE' Alarm Voltage Drop=VD=R x la FAPS-B1 PS-8 - 'a p 20.450 209.75 Ft (L)Total Circuit Length(One Leg) B1-1-01 15cd STW 0000 0.057 30.92 ft 20.397 3.14 Ohm Wire Resistance Per 1000 Feet B1-1-02 15cd STW 0.000 0.057 18.17 ft 20.370 1.32 Ohm (R)Total Circuit Resistance(Both Legs) B1-1-03 75cd E70-24MCW-FW ,t 000 0.060 13.08 ft 20.356 0.00 Amp (Is)Total Current Draw(Standby) B1-1-04 75cd E70-24MCW-FW 0.000 0.165 21.75 ft 20.324 1.19 Amp (la)Total Current Draw(Alarm) B1-1-05 15cd E70-24MCW-FW 0 000 0.060 12.25 ft 20.293 18.84 Volt (20.4-(la x R))Applied Voltage at Last Device' 81-1-06 75cd E70-24MCW-FW )000 0.165 13.83 ft 20.273 1.56 Volt (VD)Voltage Drop 61-1-07 75cd E70-24MCW-FW 0.00,^, 0.165 3925 ft 20,188 7.67% i+Percent Voltage Drop B1-1-08 75cd E70-24MCW-FW 0.000 0.165 46,00 ft 20.036 39.60% Percent Current Draw Output-1 B1-1-09 75cd E90-24MCC-FW 0.003 0.189 14.33 ft 19.915 61-1-10 30cd E90-24MCC-FW 0.000 0.105 0.17 ft 19.888 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 3 030 0.000 0.000 x.000 0.000 ;'.000 0.000 0.000 0.000 0 000 0.000 0000 OUTPUT-2 LABEL CD MODEL STANDBY VOLTAGE' Voltage Drop=VD=L'R'la FAPS-61 .x, n I� PS-8 '1 ' 20.400 218.75 Ft (L)Total Circuit Length(One Leg) B1-2-01 15cd STW 0.000 0.057 65.83 ft 20.394 3.14 Ohm Wire Resistance Per 1000 Feet 61-2-02 75cd E90-24MCC-FW 0,000 0.189 23.25 R 20.266 1.37 Ohm (R)Total Circuit Resistance(Both Legs) B1-2-03 75cd E90-24MCC-FW U.000 0.189 31.42 ft 20.136 0.00 Amp (Is)Total Current Draw(Standby) B1-2-04 75cd E90-24MCC-FW ')900 0.189 29.67 ft 19.991 0.89 Amp (la)Total Current Draw(Alarm) B1-2-05 15cd STW 0,000 0.057 45.92 ft 19.883 19.18 Volt (20.4-(la x R))Applied Voltage at Last Device' 61-2-06 30cd E90-24MCC-FW 9.000 0.105 0.58 ft 19.842 1.22 Volt (VD)Voltage Drop B1-2-07 30cd E90-24MCC-FW 000 0.105 22.08 ft 19.812 6.00% Percent Voltage Drop 0.000 U 000 2910% Percent Current Draw Output-2 0.000 0.000 0.000 0.000 "0 000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 ..000 0.000 10000 0.000 0.000 6.000 0.000 0.000 0.000 0.000 0.000 PROPRIETARY DOCUMENT FOR APPROVAL ONLY 5/11/2017 FAPS-B1 VOLTAGE DROP CALCULATIONS CONTINUED OUTPUT-3 LABEL CD MODEL STANDBY VOLTAGE' Voltage Drop=VD=L'R'la FAPS-B1 PS-8 rs t@R.Zeta' 20.400 0.00 Ft (L)Total Circuit Length(One Leg) 0.000 0.000 3.14 Ohm Wire Resistance Per 1000 Feet 0.000 3O 0.00 Ohm (R)Total Circuit Resistance(Both Legs) )'900 J0.00 Amp (Is)Total Current Draw(Standby) 0.000 0.000 0.00 Amp (la)Total Current Draw(Alarm) ".000 O 000 20.40 Volt (20.4-(la x R))Applied Voltage at Last Device' ., OuD 1.O00, 0.00 Volt (VD)Voltage Drop 1000 0.000 0.00% Percent Voltage Drop 000 0-000 0.00 Percent Current Draw Output-3 0.000 0.000 0.000 3 OL(0 000 00:0 0.0(00 0.000 0.000 2.000 :?.000 0.000 0.000 0.000 0.000 ':7.000 ).000 0.000 0.000 0.000 7:300 J 1:0 HROP OUTPUT-4 LABEL CD MODEL STANDBY VOLTAGE' Voltage Drop=VD=L'R'la FAPS-B1 =SI PS-8 ; - 20.400 171.42 Ft (L)Total Circuit Length(One Leg) B1-4-01 95cd E90-24MCC-FW 0,000 0.249 7.08 ft 20.395 3.14 Ohm Wire Resistance Per 1000 Feet B1-4-02 15cd E90-24MCC-FW ).000 0.065 14.17 ft 20.353 1.08 Ohm (R)Total Circuit Resistance(Both Legs) B1-4-03 15cd STW i).00,. 0.057 6.08 ft 20.342 0.00 Amp (Is)Total Current Draw(Standby) 131.4-04 15cd STW J;)00 0.057 16.67 ft 20.334 1.42 Amp (la)Total Current Draw(Alarm) 01-4-05 15cd 090-24MCC-FW {10.000 0.065 4.00 ft 20.323 18.88 Volt (20.4-(lax R))Applied Voltage at Last Device' B1-4-06 15cd E90-24MCC FW 3.000 0.065 22.83 ft 20.301 1.52 Volt (VD)Voltage Drop 01-4-07 75cd E90-24MCC-FW ::;.000 0.189 1.17 ft 20.263 7.47% Percent Voltage Drop B1-4-08 95cd E90-24MCC-FW 0.000 0.249 28.83 ft 20181 47,20% Percent Current Draw Output-4 B1-4-09 95cd E90-24MCC-FW '.7.000 0.249 33.92 ft 19.984 B1-4-10 15cd STW 0.000 0.057 9.42 ft 19.913 B1-4-11 15cd STW 0.000 0.057 10.42ft 19.907 B1-4-12 15cd STW 0,000 0.057 16.83 ft 19.896 009 0.000 9 000 O.GO, J-000 0.000 0.000 0.000 ).000 i)b0(3 0.000 0.000 0.000 0.000 0.000 0.000 PROPRIETARY DOCUMENT FOR APPROVAL ONLY 5/11/2017 FAC P-1 db LOSS CALCULATIONS SIEMENS FIRE ALARM SUBMITTAL VICTORIA'S SECRET WASHINGTON SQUARE MALL FACA.T AMP Panel ZAC-30 AMP Model AMP-A7 AMP Label 30 Watt Max Wattage Per Output 0.0048 Max dB Loss 30 Watt Max Wattage Per AMP 16 AWG Wire Gauge 70 VRMS(V)Audio Voltage db LOSS CALCULATION RESULTS OUTPU PERCENT T TOTAL OUTPUT LABEL db LOSS WATTS LOAD OUTPUT 1 I SP1-2-I -0.03 dB 4.75 Watts 15.83% Total Watts 4.75 Watts 15.83% db LOSS CALCULATIONS LABEL WATT MODEL db LOSS db Loss=201og10(RU(RL+RW)) FACP-1 AMP-A1 SP1.2-01 1/4W E70-24MCW-FW .000 dB 70 VRMS (V)Audio Voltage SP1-2-02 1/2W E70-24MCW-FW .001 dB 4.99 Ohm (R)Wire Resistance Per 1000 Feet SP1-2-03 1/4W E70-24MCW-FW .001 dB 370.58 Ft (L)Total Circuit Length(One Leg) SP1-2-04 1/2W E70-24MCW-FW 002 dB 1031.58 (RL)Load Resistance=V^2/W SPI-2-05 1/2W E70-24MCW-FW .004 dB 3.70 Ohm (RW)Circuit Resistance=R*22(Both Legs) SP1-2-06 1/2W E70-24MCW-FW .007 dB 4.75 Watt (W)Total Circuit Wattage SP1-2-07 1/4W E90-24MCC-FW 009 dB -0 03 d6 Total Circuit Signal Loss SP1-2-08 1/4W E90-24MCC-FW 009. dB dB Loss=201og10(RU(RL+RW)) SP1-2-09 1/4W E90-24MCC-FW .012 dB 15.83% Percent Output Load SP1-2-10 1/4W E90-24MCC-FW .015 dB SP1-2-11 1/4W E90-24MCC-FW .018 dB SPI-2-12 1/4W E90-24MCC-FW .020 dB SP1-2.13 1/4W E90-24MCC-FW .023 dB SP1-2.14 1/4W E90-24MCC-FW .025 dB SP1-2.15 1/4W E90-24MCC-FW .028 dB .PROVAL ONLY 5/10/2017