Report (20) • * f-PS2-0 ? ,C) c ,
SYSTEM Ittikmill -
SENSOR®
clay F TIGARD
Indoor Selects 11
- ;N � �N.
ti E
Output Horns,
Strobes, and
Horn Strobes for
Wall Applications
SpectrAlert®Advance audible visible notification products SPE T
are rich with features guaranteed to cut installation times r C� I ert
and maximize profits.
Features The SpectrAlert Advance series offers the most versatile and
• Plug-in design with minimal intrusion into the back box easy-to-use line of horns,strobes,and horn strobes in the industry.
• With white and red plastic housings,wall and ceiling mounting
• Tamper-resistant construction options,and plain and FIRE-printed devices,SpectrAlert Advance
• Automatic selection of 12-or 24-volt operation at can meet virtually any application requirement.
15 and 15/75 candela
Field-selectable candela settings on wall units: 15, 15/75, Like the entire SpectrAlert Advance product line,wall-mount horns,
• 30, 75,95, 110, 115, 135, 150, 177,and 185 strobes,and horn strobes include a variety of features that increase
their application versatility while simplifying installation.All devices
• Horn rated at 88+dBA at 16 volts feature plug-in designs with minimal intrusion into the back box,
• Rotary switch for horn tone and three volume selections making installations fast and foolproof while virtually eliminating
• Universal mounting plate for wall units costly and time-consuming ground faults.
• Mounting plate shorting spring checks wiring continuity before To further simplify installation and protect devices from construction
device installation damage,SpectrAlert Advance utilizes a universal mounting plate
• Electrically Compatible with legacy SpectrAlert devices with an onboard shorting spring,so installers can test wiring
• Compatible with MDL3 sync module continuity before the device is installed.
• Listed for ceiling or wall mounting Installers can also easily adapt devices to a suit a wide range of
application requirements using field-selectable candela settings,
automatic selection of 12-or 24-volt operation,and a rotary switch
for horn tones with three volume selections.
Agency Listings
SIGNALING
rO.
EA
LISTED APPROVED approvedMM 77125-125-16531653 186(horn strobintloor strobeses)
.188(
54011(chimes,horn strobes.horns) 3023572 MEA452-05-E chime strobes)
S5512(strobes) 7135-1653-189(horns,chimes)
•
SpectrAlert Advance Specifications
Architect/Engineer Specifications
General
SpectrAlert Advance horns,strobes,and horn strobes shall mount to a standard 4 x 4 x 11/2-inch back box,4-inch octagon back box,or
double-gang back box.Two-wire products shall also mount to a single-gang 2 x 4 x 17/8-inch back box.A universal mounting plate shall
be used for mounting ceiling and wall products.The notification appliance circuit wiring shall terminate at the universal mounting plate.
Also,SpectrAlert Advance products,when used with the Sync•Circuit'°Module accessory,shall be powered from a non-coded notification
appliance circuit output and shall operate on a nominal 12 or 24 volts.When used with the Sync•Circuit Module, 12-volt-rated notification
appliance circuit outputs shall operate between 8.5 and 17.5 volts;24-volt-rated notification appliance circuit outputs shall operate between
16.5 and 33 volts. Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-
wave rectified unfiltered power supply.Strobes and horn strobes shall have field-selectable candela settings including 15, 15/75,30,75,95,
110, 115, 135, 150, 177,and 185.
Strobe
The strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and shall be approved for fire protective service.
The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for
visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash
tube and associated lens/reflector system.
Horn Strobe Combination
The horn strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and UL 464 and shall be approved for
fire protective service.The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with
Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light
shall consist of a xenon flash tube and associated lens/reflector system.The horn shall have three audibility options and an option to switch
between a temporal three pattern and a non-temporal(continuous)pattern.These options are set by a multiple position switch.On four-wire
products,the strobe shall be powered independently of the sounder.The horn on horn strobe models shall operate on a coded or non-coded
power supply.
Synchronization Module
The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service.The module
shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three.Also,while operating the strobes,the module shall silence the horns
on horn strobe models over a single pair of wires.The module shall mount to a 411/16 x 411/16 x 21/8-inch back box.The module shall also
control two Style Y(class B)circuits or one Style Z(class A)circuit.The module shall synchronize multiple zones.Daisy chaining two or more
synchronization modules together will synchronize all the zones they control.The module shall not operate on a coded power supply.
Physical/Electrical Specifications
Standard Operating Temperature 32°F to 120°F(0°C to 49°C)
Humidity Range 10 to 93%non-condensing
Strobe Flash Rate 1 flash per second
Nominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR'
Operating Voltage Rangel 8 to 17.5 V(12 V nominal)or 16 to 33 V(24 V nominal)
Operating Voltage Range MDL3 Sync Module 8.5 to 17.5 V(12 V nominal)or 16.5 to 33 V(24 V nominal)
Input Terminal Wire Gauge 12 to 18 AWG
Wall-Mount Dimensions(including lens) 5.6"L x 4.7"W x 2.5"D(142 mm L x 119 mm W x 64 mm D)
Horn Dimensions 5.6"L x 4.7"W x 1.3"D(142 mm L x 119 mm W x 33 mm D)
Wall-Mount Trim Ring Dimensions(sold as a 5 pack)(TR-HS) 5.7"L x 4.8"W x 0.35"D(145 mm L x 122 mm W x 9 mm D)
Notes:
1.Full Wave Rectified(FWR)voltage is a non-regulated,time-varying power source that is used on some power supply and panel outputs.
2.P,S,PC,and SC products will operate at 12 V nominal only for 15 and 15/75 cd.
r
a
UL Current Draw Data
UL Max.Strobe Current Draw(mA RMS) UL Max.Horn Current Draw(mA RMS)
8-1Z5 Volts 16-33 Volts 8-17.5 Volts 16-33 Volts
Candela DC FWR DC FWR Sound Pattern dB DC FWR DC FWR
Standard 15 123 128 66 71 Temporal High 57 55 69 75
Candela 15/75 142 148 77 81 Temporal Medium 44 49 58 69
Range 30 NA NA 94 96 Temporal Low 38 44 44 48
75 NA NA 158 153 Non-temporal High 57 56 69 75
95 NA NA 181 176 Non-temporal Medium 42 50 60 69
110 NA NA 202 195 Non-temporal Low 41 44 50 50
115 NA NA 210 205 Coded High 57 55 69 75
High 135 NA NA 228 207 Coded Medium 44 51 56 69
Candela 150 NA NA 246 220 Coded Low 40 46 52 50
Range 177 NA NA 281 251
185 NA NA 286 258
UL Max.Current Draw(mA RMS),2-Wire Horn Strobe,Standard Candela Range(15-115 cd)
8-17.5 Volts 16-33 Volts
DC Input 15 15/75 15 15/75 30 75 95 110 115
Temporal High 137 147 79 90 107 176 194 212 218
Temporal Medium 132 144 69 80 97 157 182 201 210
Temporal Low 132 143 66 77 93 154 179 198 207
Non-Temporal High 141 152 91 100 116 176 201 221 229
Non-Temporal Medium 133 145 75 85 102 163 187 207 216
Non-Temporal Low 131 144 68 79 96 156 182 201 210
FWR Input
Temporal High 136 155 88 97 112 168 190 210 218
Temporal Medium 129 152 78 88 103 160 184 202 206
Temporal Low 129 151 76 86 101 160 184 194 201
Non-Temporal High 142 161 103 112 126 181 203 221 229
Non-Temporal Medium 134 155 85 95 110 166 189 208 216
Non-Temporal Low 132 154 80 90 105 161 184 202 211
UL Max.Current Draw(mA RMS),2-Wire Horn Strobe,High Candela Range(135-185 cd)
16-33 Volts 16-33 Volts
DC Input 135 150 177 185 FWR Input 135 150 177 185
Temporal High 245 259 290 297 Temporal High 215 231 258 265
Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258
Temporal Low 232 251 282 292 Temporal Low 207 221 248 256
Non-Temporal High 255 270 303 309 Non-Temporal High 233 248 275 281
Non-Temporal Medium 242 259 293 299 Non-Temporal Medium 219 232 262 267
Non-Temporal Low 238 254 291 295 Non-Temporal Low 214 229 256 262
Horn Tones and Sound Output Data
Horn and Horn Strobe Output(dBA)
8-17.5 16-33 24-Volt Nominal
Switch Volts Volts Reverberant Anechoic
Position Sound Pattern dB DC FWR DC FWR DC FWR DC FWR
1 Temporal High 78 78 84 84 88 88 99 98
2 Temporal Medium 75 75 80 80 86 86 96 96
3 Temporal Low 71 71 76 76 83 80 94 89
4 Non-Temporal High 82 82 88 88 93 92 100 100
5 Non-Temporal Medium 78 78 85 85 90 90 98 98
6 Non-Temporal Low 73 74 81 81 88 84 96 92
- 7t Coded High 82 82 88 88 93 92 101 101
8t Coded Medium 78 78 85 85 90 90 97 98
9t Coded Low 74 75 81 81 88 85 96 92
tSettings 7,8,and 9 are not available on 2-wire horn strobes.
, • 4
SpectrAlert Advance Dimensions
14-4.7" 2.5'=-o
tow Pair
11111
Cammizi
I.
1111
IIma.—
5.6" 11111)
J
Wall-mount horn strobes
SpectrAlert Advance Ordering Information
Model Description Model Description
Wall Horn Strobes Wall Strobes(cont.)
P2R 2-Wire Horn Strobe,Standard cd,Red SRH Strobe,High cd,Red
P2R-P 2-Wire Horn Strobe,Standard cd,Red,Plain SRH-P Strobe,High cd,Red,Plain
P2R-SP 2-Wire Horn Strobe,Standard cd,Red,"FUEGO" SRH-SP Strobe,High ed,Red,"FUEGO"
P2RH 2-Wire Horn Strobe,High cd,Red SW Strobe,Standard cd,White
P2RH-P 2-Wire Horn Strobe,High cd,Red,Plain SW-P Strobe,Standard cd,White,Plain
P2W 2-Wire Horn Strobe,Standard cd,White SWH Strobe,High cd,White
P2W-P 2-Wire Horn Strobe,Standard cd,White,Plain SWH-P Strobe,High cd,White,Plain
P2WH 2-Wire Horn Strobe,High cd,White Horns
P2WH-P 2-Wire Horn Strobe,High cd,White,Plain HR Horn,Red
P4R 4-Wire Horn Strobe,Standard cd,Red HW Horn,White
P4R-P 4-Wire Horn Strobe,Standard cd,Red,Plain Accessories
P4RH 4-Wire Horn Strobe,High cd,Red TR-HS Trim Ring,Wall,Red
P4W 4-Wire Horn Strobe,Standard cd,White SBBR Indoor Surface Mount Back Box,Red
Wall Strobes SBBW Indoor Surface Mount Back Box,White
SR Strobe,Standard cd,Red
SR-P Strobe,Standard cd,Red,Plain
SR-SP Strobe,Standard cd,Red,"FUEGO"
Notes:
All-P models have a plain housing(no"FIRE"marking on cover)
All-SP models have"FUEGO"marking on cover
"Standard cd"refers to strobes that include 15,15/75,30,75,95,110,and 115 candela settings.
"High cd"refers to strobes that include 135,150,177,and 185 candela settings.
*T SYSTEM 3825 Ohio Avenue•St.Charles, IL 60174
02014 System sensor.
SEAPhone:800-SENSOR2•Fax 630-377-6495 Productspeaficatons subject tc.change without notice.V sit systemsensor.com
,Y,SOR for current product information,including the latest version of this data sheet.
www.systemsensor.com AVDS10201•1/14