Loading...
Report (27) sea/&,- ,o/ tlYS- S% tLI1c1Worldwide www.tyco-fire.com Fire Protection Contacts Products Series TY-FRB, 5.6 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General NOTICE The TYCO Series TY-FRB Sprinklers `' Description described herein must be installed and maintained in compliance with this doc- The TYCO Series TY-FRB,5.6 K-factor, ument, as well as with the applicable . U ri ht(TY313)and Pendent(TY323) F 4 P 9 standards of the National Fire Protec- Sprinklers described in this data sheet tion Association,in addition to the stan- are quick response,standard coverage, dards of any other authorities having ., decorative 3 mm glass bulb-type spray jurisdiction.Failure to do so may impair .. sprinklers designed for use in light or the performance of these devices. 4 ordinary hazard,commercial occupan- ,4 cies such as banks, hotels,and shop- The owner is responsible for maintain ,.., 9 ping malls. ing their fire protection system and devices in proper operating condition. The recessed version of the Series TY- The installing contractor or sprinkler FRB Pendent Sprinkler,where applica- manufacturer should be contacted with ble, is intended for use in areas with a any questions. finished ceiling.This recessed pendent sprinkler uses one of the following: Sprinkler i.y • A two-piece Style 15 Recessed 4‹ � ,- Escutcheon with recessed adjust- „�Identification ment up to 5/8 inch (15,9 mm) from �„ the flush pendent position. Number (SIN) r • A two-piece Style 20 Recessed Escutcheon with recessed adjust- TY313 Upright 5.6K, 1/2”NPT ' 4 ment up to 1/2 inch (12,7 mm) from TY323 Pendent 5.6K, 1/2"NPT the flush pendent position. The adjustment provided by the Technical Recessed Escutcheon reduces the Temperature Rating accuracy to which the fixed pipe drops Data 135°F(57°C) to the sprinklers must be cut. 155°F(68°C) 175 Intermediate level versions of Series Approvals 200°F (79°C)(93°C) TY-FRB Sprinklers are described in UL and C-UL Listed 286°F(141°C)) Technical Data Sheet TFP357. Sprin- FM, LPCB,and VdS Approved kler guards and shields are described CE Certified Finishes in Technical Data Sheet TFP780. Sprinklers with Polyester Finish are UL Sprinkler: Refer to Table A and C-UL Listed as Corrosion-Resis- Recessed Escutcheon:White Coated, tant Sprinklers. Chrome Plated,or Brass Plated Maximum Working Pressure Physical Characteristics 175 psi (12.1 bar) Frame Bronze 250 psi(17.2 bar)* Button Brass/Copper *The maximum working pressure of 250 psi Sealing Assembly Stainless IMPORTANT (17.2 bar)only applies to the listing by Un- Steel w/TEFLON Always refer to Technical Data derwriters Laboratories,Inc.(UL). Bulb Glass Sheet TFP700 for the "INSTALLER Discharge Coefficient Compression Screw Bronze WARNING"that provides cautions K=5.6 GPM/psi112(80,6 LPM/bar112) Deflector Bronze with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and installation can permanently dam- s age a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 4 FEBRUARY 2014 TFP172 t 1 TFP172 y Page 2 of 4 f Components: *Temperature rating is ** Pipe thread connections per ISO 7-1 1 - Frame 4 - Bulb indicated on Deflector. can be provided on special request. 2 - Button 5 - Compression STYLE 15 or 20 3 - Sealing Screw ESCUTCHEON PLATE 1/2" 7/16"(11,1 mm) RECESSED ,' Assembly 6 - Deflector* DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE-IN ESCUTCHEON * I5 °:iri�'rc�:. zr���r r�-A�• 7/16" Y1 \ �R_ 7------- / (11,1 mm)NOMINAL 2" t 1•r c 4 MAKE-IN ghil (50,8 mm) �� El mior 2 ra 0 2" \I) 0/ 1 3/8" 3 (50,8 mm) (34,9 mm) lir WRENCH 1 / - j FLATS t 1/2"NPT** DEFLECTOR* 2-7/8"(73,0 mm)DIA. CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT FIGURE 1 SERIES TY-FRB UPRIGHT(TY313)AND PENDENT(TY323)SPRINKLERS 5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE L. Operation Installation The glass bulb contains a fluid which The TYCO Series TY-FRB,5.6 K-factor, .....17".. WRENCH RECESS expands when exposed to heat.When Upright(TY313)and Pendent(TY323) (USE ONLY the rated temperature is reached,the Sprinklers must be installed in accor- fluidEND"A") expands sufficiently to shatter the dance with this section. glass bulb, allowing the sprinkler to activate and water to flow. General Instructions FIGURE 2 Do not install any bulb-type sprinkler if W-TYPE 6 the bulb is cracked or there is a loss SPRINKLER WRENCH _ Design of liquid from the bulb.With the sprin- kler held horizontally, a small air bub- Criteria ble should be present. The diameter WRENCH of the air bubble is approximately 1/16 RECESS The TYCO Series TY-FRB,5.6 K-factor, inch(1,6 mm)for the 135°F(57°C)and Upright(TY313)and Pendent(TY323) 3/32 inch(2,4 mm)for the 286°F(141°C) Sprinklers are intended for fire protec- temperature ratings. /�� tion systems designed in accordance A leak tight 1/2 inch NPT sprinkler joint with the standard installation rules rec- should be obtained byapplying a min- imum by the applicable Listing or Approval agency(such as, UL Listing imum to maximum torque of 7 to 14 is based on the requirements of NFPA ft.-lbs. (9,5 to 19,0 Nm). Higher levels 411. t �..r 13, and FM Approval is based on the of torque can distort the sprinkler Inlet requirements of FM's Loss Prevention with consequent leakage or impairment PUSH WRENCH Data Sheets).Only the Style 15 or Style of the sprinkler. IN TO ENSURE 20 Recessed Escutcheon is to be used Do not attempt to compensate for ENGAGEMENT for recessed pendent installations. insufficient adjustment in the Escutch- WITH SPRINKLER WRENCHING AREAeon Plate by under-or over-tightening FIGURE 3 the sprinkler. Re-adjust the position of W-TYPE 7 RECESSED the sprinkler fitting to suit. SPRINKLER WRENCH Upright and Pendent Sprinklers The Series TY-FRB Upright and Pen- dent Sprinklers must be installed in accordance with the following instructions. Step 1.Install Pendent sprinklers in the pendent position. Install upright sprin- klers in the upright position. Step 2. With pipe-thread sealant applied to the pipe threads, hand- tighten the sprinkler into the sprinkler fitting. + w 1 TFP172 ` Page 3 of 4 Step 3.Tighten the sprinkler into the 2-7/8"DIA. sprinkler fitting using only the W-Type - (73,0 mm) - 6 Sprinkler Wrench(Figure 2).With ref- erence to Figure 1,apply the W-Type 6 2-1/4"DIA. Sprinkler Wrench to the wrench flats. FACE OF — (57,2 mm) - Torque sprinklers 7 to 14 ft.-lbs.(9,5 to SPRINKLER 19,0 Nm). FITTING 5/8"(15,9 mm) Recessed Pendent Sprinklers i \ us FLUSH The Series TY-FRB Recessed Pendent 3/8±5/16" ,�,� —, Sprinklers must be installed in accor- (9,5±7,9 mm) 7,%_ [ - '/ / dance with the following instructions. } / +-1- �, Step A.After installing the Style 15 or MOUNTING -, 1/8" i Style 20 Mounting Plate over the sprin- SURFACE (3,2 mm) kler threads, and with pipe-thread -----•,-----— sealant applied to the pipe threads, CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) hand-tighten the sprinkler into the TY-FRB PLATE 3/4"(19,1 mm) sprinkler fitting. Step B.Tighten the sprinkler into the FIGURE 4 Step B. fitting using onin the into Wthe SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323) 7spriRecessed Sprinkler Wrench (Figure WITH TWO PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15 3).With reference to Figure 1,apply the RECESSED ESCUTCHEON W-Type 7 Recessed Sprinkler Wrench to the sprinkler wrench flats. Torque 2-7/8"DIA. sprinklers 7 to 14 ft.-lbs. (9,5 to 19,0 (73,0 mm) Nm). FACE OF Step C.After ceiling installation and fin- SPRINKLER — 2-1/4"DIA.(57,2 ishing,slide on the Style 15 or Style 20 FITTING (57,2 mm) Closure over the Series TY-FRB Sprin- 5/16±1/4" kler and push the Closure over the (7,9±6,4 mm) 1/2"(12,7 mm) Mounting Plate until its flange comes in + - FLUSH contact with the ceiling. 1� , • , Care and f / -�� }+ MOUNTING VP 1/8" J Maintenance SURFACE (3,2 mm) The TYCO Series TY-FRB,5.6 K-factor, I Upright(TY313)and Pendent(TY323) CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) Sprinklers must be maintained and ser- TY-FRB PLATE 7/8"(22,2 mm) viced in accordance with this section. FIGURE 5 Before closing a fire protection system SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323) main control valve for maintenance WITH TWO PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 work on the fire protection system RECESSED ESCUTCHEON that it controls, obtain permission to shut down the affected fire protection Modified sprinklers must be replaced. standards of any other authorities hav- systems from the proper authorities Sprinklers that have been exposed to ing jurisdiction. Contact the installing and notify all personnel who may be corrosive products of combustion, but contractor or sprinkler manufacturer affected by this action. have not operated,should be replaced regarding any questions. Absence of the outer piece of an if they cannot be completely cleaned Automatic sprinkler systems are rec- escutcheon, which is used to cover by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. to be inspected, tested, a clearance hole, can delay sprinkler and and maintained ined by a qualified Inspec- operation in a fire situation. Care must be exercised to avoid dam- tion Service in accordance with local age to the sprinklers before,during,and requirements and/or national codes. The owner must assure that the sprin after installation. Sprinklers damaged klers are not used for hanging any objects and that the sprinklers are only by dropping, striking, wrench twist/ slippage,or the like, must be replaced. cleaned by means of gently dusting with a feather duster; otherwise, non- Also, replace any sprinkler that has a operation in the event of a fire or inad cracked bulb or that has lost liquid from vertent operation may result. its bulb. (Ref. Installation Section.) Sprinklers which are found to be leak- The owner is responsible for the ing or exhibiting visible signs of corro inspection,testing,and maintenance of sion must be replaced. their fire protection system and devices a in compliance with this document, as Automatic sprinklers must never be well as with the applicable standards painted, plated, coated, or other- of the National Fire Protection Associa- y wise altered after leaving the factory. tion (e.g., NFPA 25), in addition to the I TFP172 Page 4 of 4 P/N* 77 - XXX - X - XXX I I SPRINKLER TEMPERATURE FINISH RATINGS SIN 1 NATURAL BRASS 135 135°F(57°C) 370 5.6K UPRIGHT(1/2"NPT) TY313 3 PURE WHITE(RAL9010)** 155 155°F(68°C) POLYESTER 371 5.6K PENDENT(1/2"NPT) TY323 q SIGNAL WHITE(RAL9003) 175 175°F(79°C) POLYESTER Use suffix"I"for ISO 7-1 connection; 9 CHROME PLATED 200 200°F(93°C) for example,77-370-4-175-I ••Eastern Hemisphere sales only 286 286°F(141°C) TABLE A SERIES TY-FRB UPRIGHT AND PENDENT SPRINKLERS PART NUMBER SELECTION Limited Ordering Warranty Procedure For warranty terms and conditions,visit Contact your local distributor for avail- www.tyco-fire.com. ability.When placing an order, indicate the full product name and Part Num- ber(P/N). Sprinkler Assemblies with NPT Thread Connections Specify:Series TY-FRB Upright or Pen- dent(specify)Sprinkler, SIN (specify), K=5.6,Quick Response, (specify)tem- perature rating, (specify) finish, P/N (specify, refer to Table A). Recessed Escutcheon Specify:Style 15 Recessed Escutcheon with(specify*)finish, P/N(specify*) Specify: Style 20 Recessed Escutch- eon with(specify*)finish, P/N(specify*) *Refer to Technical Data Sheet TFP770 Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387 Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001 I GLOBAL HEADQUARTERS 11400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright©2014 Tyco Fire Products,LP. All rights reserved. Vico TEFLON is trademark of The DuPont Corporation. Fire Protection Products