Loading...
Report Capitol / ozco s-w G k,44 4--- Electric Co., Inc. scw RECEIvEr April 25, 2016 APR 2 6 2016 CITY OF ,( I BUILOI j Plans Examiner City of Tigard Building Services 13125 SW Ha11 Blvd. Tigard, OR 97223 Re: Tenant Fire Alarm System Modifications Experis, Suite 500 @ Lincoln Tower 10260 SW Greenburg Road Tigard, OR 97223 Please find attached building and electrical permit applications, three sets of plans, calculations, and product submittals for the fire alarm tenant improvements at the address shown above. Occupancy Group: B The fire alarm system design includes the following: 1. Install (3) new ceiling strobes and relocate (5) ceiling strobes in tenant space per fire alarm plans. 2. We will pre-test the fire alarm devices prior to requesting a final fire alarm inspection. 3. Fire alarm design by Simplex-Grinnell, installation by Capitol Electric Co. Please contact me if you have questions or comments. Respectfully, air Dan Wilson, SET Project Manager/Estimator Fire/Life Safety Division Capitol Electric Company, Inc. (503) 262-0411 Direct Dan@cepdx.com NICET Level IV, Fire Alarm Systems #104512 11401 NE Marx • Portland, Oregon 97220-1041 • 503-255-9488 • Fax 503-257-7121 CCB# 48748 • www.capitolelectricco.com RECEIVED REGFIVFD r'=i 2 € 2016 APR 2 2016 �m lex TrueAlertcfil ca Notification Appliances � 5 p f UL, ULC, CSFM Listed; FM Approved; Visib dation Appliances with Synchronized Flash; MEA (NYC) Acceptance* Non-Addressable, SmartSyncTM Operation Compatible Visible only(V/O)24 VDC notification appliances with high output xenon strobe, available for wall or ceiling mount: • UL listed to Standard 1971 • Intensity is selectable as 15,30,75,or 110 candela with visible selection jumper secured behind strobe housing p • Operation is compatible with ADA requirements(referR E to important installation information on page 3) • Polarized input allows connection to compatible reverse Wall Mount Strobes polarity,supervised notification appliance circuit(NAC) I • Regulated circuit design ensures consistent flash output F R E and provides controlled inrush current ' � �:_ ° • Rugged,high impact,flame retardant thermoplastic -4i housings are available in red or white with clear lens -Y Strobes provide synchronized flash for use with: • 4006,4008,4010,and 4100U Series fire alarm control Ceiling Mount Strobes panels with NACs selected to provide strobe Description synchronization or SmartSync two-wire control** • 4009 IDNetTM NAC Extenders Multi-Candela TrueAlert synchronized strobes• Separate strobe Synchronization Modules that are provide convenient installation to standard electrical available for Class B or Class A operation boxes.The enclosure designs are both impact and vandal resistant and provide a convenient strobe intensity • Separate SmartSync Control Modules(SCMs)that selec Ninputstion.Since each model can be selected for intensity provideClass B or Class A output from conventional output,on-site model inventory is minimized and changes NAC encountered during construction can be easily Strobe housings provides flexible, easy, and accommodated. convenient semi-flush or surface wall mounting: Wall mount strobe housings are a one-piece assembly • Rear of housing does not extend into box (including lens)that mounts to a single or double gang,or • Wall mount strobes easily mount to single gang,double 4"square standard electrical box.The cover can be quickly removed(a tool is required)and covers are gang,or 4 inch square outlet box available separately for color conversion. • Ceiling mount strobes mount to single gang boxes Ceiling mount strobes install using standard single gang Wall mount strobe features: electrical boxes.Color choice is determined by model • Wiring terminals are accessible from the front of the number. housing providing easy access for installation, Strobe Intensity Selection inspection,and testing • Covers are available separately to convert housing color During determineslthe desired he strobe intensity.An housing Optional adapters and wire guards: attached flag with black letters on a highly visible yellow • Wall mount strobe adapters are boxes and available to adapt ctover bside of tuned alllows oe Tense selected intensity to be seen at the surface mounted electrical Simplex®2975-9145 boxes Strobe Application Reference • UL listed red wire guards are available for wall or ceiling mount strobes Proper selection of visible notification is dependent on occupancy,location,local codes,and proper applications of:the National Fire Alarm Code(NFPA 72),ANSI ' This product has been approved by the California State Fire Marshal(C SEM)pursuant to A117.1;the appropriate model building code:BOCA, Section 13144.1 of the California Health and Safety Code.See CSFM Listing 1125-0026:316 for allowable values and/or conditions concerning material presented in ICBG,or SBCCI;and the application guidelines of theericans with Disabilities Act(ADA). this document. is subject to re-examination,revision,and possible cancellation.Refer to Am page 2 for listing status of wire guards.Additional listings may be applicable;contact your Simplex multi-candela SmartSync two-wire horn/strobe appliance operation is protected under one or more laf the following U.S.Paho[Numbers:pliance is ; e,527; local Recorderrx Co.ate the 1prope the oflTycoyct status.t. ProductsLirdus and Westminstser. under Simplex P Time Co.are the property Safety Westminster. 5,886,620;6,281,789;6,954,137;7,005,911;and 7,006,003. S4906-0001-3 5/2008 P: Synchronized Strobes . SmartSync Control Sources Multiple Strobes.When multiple strobes and their Class B SmartSync two-wire control is available reflections can be seen from one location,synchronized from: flashes reduce the probability of photo-sensitive reactions • 4006,4008,4100U,and 4010 Fire Alarm Control as well as the annoyance and possible distraction of Panels(refer to individual product data sheets for more random flashing.These multi-candela strobes are information) synchronized over a two-wire circuit when connected to compatible NACs,to compatible Synchronized Flash • 4009 IDNet NAC Extender(refer to data sheet Modules,or to SmartSync Control Modules. S4009-0002) • SmartSync Control Module (SCM)4905-9938(refer to SmartSync Two-Wire Control data sheet S4905-0003) Some applications desire the audible notification Class A SmartSync two-wire control is available appliances to be capable of being silenced before the from 4100U NACs and from the 4905-9938 SCM. alarm condition is reset(on-until-silenced)while the Additional SmartSync compatible notification visible notification appliances are kept activated until the appliances include separate horns and combination alarm condition is reset(on-until-reset). SmartSync horn/strobe notification appliances. operation mode provides this function using a single circuit(two-wire operation). Product Selection Multi-Candela Visible Notification Appliances (Strobes) Model Mounting Housing Color "FIRE"Lettering Description 4906-9101 Wall Red White 4906-9103 White Red Multi-candela strobe with intensity selectable as: 15,30,75,or 110 candela;synchronized flash rate; 4906-9102 CeilingRed White SmartSync two-wire control compatible 4906-9104 White Red Wall Mount Strobe Adapters • Model Description Dimensions 4905-9937 Red Surface Mount Adapter Skirt;use to cover 1-1/2"(38 mm) 5-3/8"H x 5-1/4"W x 1-5/8"D deep surface mounted boxes (136 mm x 133 mm x 41 mm) 4905-9940 White Total depth with strobe=4-3/8"(111 mm) 4905-9931 Red Adapter Plate for mounting to Simplex 2975-9145 box(typically for 8-5/16"x 5-3/4"x 0.060"Thick retrofit,may be mounted vertical or horizontal) (211 mm x 146 mm x 1.5 mm) 2975-9145 Red Mounting Box, requires Adapter Plate 4905-9931 7-7/8"x 5-1/8"x 2-3/4"D (200 mm x 130 mm x 70 mm) Ceiling Mount Strobe Adapter Model Description Dimensions 4905-9910 Surface Mount Adapter Plate;zinc plated;required for mounting to 4-7/8"x 3-1/8"x 0.060"D handy box;not needed when using 4905-9926 guard (124 mm x 79 mm x 1.5) Synchronization Modules (refer to data sheet S4905-0003 for additional information) Model Description Dimensions 4905-9914 Class B Synchronized Flash Module;epoxy encapsulated with 1-3/8"x 2-7/16"x 13/16" in/out 18 AWG(0.82 mm )wire leads,rated for 2 A NAC, (35 mm x 62 mm x 20 mm) 4905-9922 Class A requires 10 mA for power 4905 9938 SmartSync Control Module with Class B or Class A output; mounts in 4"x 4-1/8"x 1-1/4"D 4"(102 mm)square box (102 mm x 105 mm x 32 mm) Replacement Covers and Guards Model. Description Dimensions 4905-9992 Red cover with white"FIRE"lettering 5-1/8"H x 5"W x 1-1/2"D For Wall mount strobes 4905-9993 White cover with red"FIRE"lettering (130 mm x 127 mm x 38 mm) 4905-9961* Wall mount 6-1/16"H x 6-1/16"W x 3-1/8"D Red wire guard with mounting plate,compatible with (154 mm x 154 mm x 79 mm) 4905-9926* Ceiling mount semi-flush or surface mounted boxes 6-1/8"x 4-3/8"x 2-7/8"deep (156 mm x 111 mm x 73 mm) *UL listed by Space Age Electronics Inc. 2 S4906-0001-3 5/2008 / Strobe S•ecifications Wall Mount or Ceiling Mount, Common Specifications Rated Voltage Range UL Listed Rating Regulated 24 VDC;see Note 1 below ULC Listed Rating 20 VDC to 30 VDC per ULC S526-M878 Flash Rate 1 Hz Synchronized NAC Loading Up to 35 synchronized strobes maximum per NAC Temperature Range 32°to 122°F(0°to 50°C) Humidity Range 10%to 93%,non-condensing at 100°F(38°C) Connections Terminal blocks for 18 AWG to 12 AWG(0.82 mm2 to 3.31 mm2);two wires per terminal for in/out wiring Housing Dimensions(with lens) 5-1/8"H x 5"W x 2-3/4"D(130 mm x 127 mm x 70 mm) Wall Maximum RMS Current Rating per 15 cd 30 cd 75 cd 110 cd Mount Strobe Setting(see Note 2 below) 60 mA 94 mA 186 mA 252 mA Reference RMS Currents 18 VDC 53 mA 84 mA 165 mA 224 mA at other voltages 24 VDC 40 mA 63 mA 124 mA 168 mA Housing Dimensions(with lens) 4-3/4"L x 2-5/16"W x 2-5/8"D(121 mm x 75 mm x 67 mm) Ceiling Maximum RMS Current Rating per 15 cd 30 cd 75 cd 110 cd Mount Strobe Setting(see Note 2 below) 75 mA 125 mA 233 mA 316 mA Reference RMS Currents 18 VDC 67 mA 111 mA 207 mA 281 mA at other voltages 24 VDC 50 mA 83 mA 155 mA 211 mA NOTES: 1. "Regulated 24 VDC"refers to the voltage range of 16 to 33 VDC per UL Standard 1971, Signaling Devices for the Hearing Impaired,changes effective May 1,2004.This voltage range is the absolute operating range.Operation outside of this range may cause permanent damage to the strobe. Please note that 16 VDC is the lowest operating voltage that is allowed at the last appliance on the NAC under worst case conditions. 2. The maximum RMS current listed is the device nameplate rating.Strobe designs are constant wattage and the maximum RMS current rating occurs at the lowest allowable operating voltage.(RMS is root mean square and refers to the effective value of a varying current waveform.) Installation Reference, Surface or Semi-Flush Wall Mounting LTh �� (= 2 Mounting is compatible with \ o / o single gang,double gang,and �, ° I II 4"(102 mm)square boxes, 1-1/2"(38 mm)deep,by others_�[91 1 ° n` /'� _- L / U � � IMPORTANT!WALL MOUNT INSTALLATION HEIGHT REFERENCE li o� )1/ Bottom of lens �QI'OOUV TMisen d O d is either even Q UP with,or slightlyElectrical Wiring access hole i O ® '-\ e/ / above bottom _ box outline of compatible i Wiring terminals , °, ( o ) boxes Q • ti Mounting Holes: w„m�am°a ti 4"square(4) ( m) ® ;u.t NFPA 72 requires 80" 2.03 vSingle gang(2) that the entire lens minimum Double gang(3) be not less than 80"and not greater than 96"above the Transparent housing finished floor and lens assembly Intensity selection €at, plug,accessible only from rear of housing; 115 Iy y Efactory setting is 15 cd / Removable cover Strobe intensity (tool required) viewing slot 3 S4906-0001-3 5/2008