Report (41) Application
Quick response sprinklers are used in fixed fire protection systems: Wet, Dry, Deluge or Preaction. Care must be
exercised that the orifice size, temperature rating, deflector style and sprinkler type are in accordance with the latest
published standards of the National Fire Protection Association or the approving Authority Having Jurisdiction. Quick
response sprinklers are intended for installation as specified in NFPA 13. Quick response sprinklers and standard re-
sponse sprinklers should not be intermixed.
*Pin tle
(XLH Only)
Deflector
4didetill\
rtf
Load Screw
Washer Bulb
Frame / Cup
4C01 .14
aN*
014FGO6A
Model F1FR42, F1FRXLH Upright
Technical data:
Thread Max. Min. Temperature
Models Discharge Coefficient Response Size Working Working Rating Finish
Pressure Pressure
F1FR56 K 5.6
**F1 FR56LL(1
F1FR42 Quick 1/2" NPT See See
**F1 FR42LL(1) K 4.2 Response (R1/2) 175 PSI 7 PSI "Temperature "Finish Table"
F1FRXLH Ratings"Table.
F1FR28 K 2.8
(1)Low Lead Sprinklers available only with Temperature Rating 200°F/93°C
Material Data:
Frame Deflector Load Screw *Pintle Cup Washer Bulb
DZR Brass CDA Alloy 260, CDA Alloy 360 CDA Alloy 360 CDA Alloy 651 Nickel Alloy 440 or Alloy 360
CDA Alloy 220
QM Brass or or or coated with PTFE Adhesive Glass
or
**Low Lead Brass CDA AlIoy510 CDA Alloy 544 CDA Alloy 544 CDA Alloy 693 Tape
2.
r
Model Fl FR56, Upright, Pendent & Conventional Sprinklers
Model Fl FR42, Fl FRXLH & Fl FR28 Upright & Pendent Sprinklers
Installation Wrench: Model D Sprinkler Wrench
Installation Data:
Nominal Thread Nominal K Factor Sprinkler Approval Sprinkler Identification Number
Orifice (SIN)
Size US Metric Height Organization Upright Pendent
Standard-Upright(SSU)and Pendent Deflectors Marked to Indicate Position
1/2" (15mm)(1) 1/2" NPT(R1/2) 5.6 80 2.25"(57mm) 1, 2, 3,4, 6 RA1425(eo(3)'4> RA1414"0>(3)r4)
7/16"(10mm) 1/2" NPT(R1/2) 4.2 60 2.25"(57mm) 1 RA1423")'4) RA1413(4)
3/8" (10mm) 1/2" NPT(R1/2) 2.8 40 2.25" (57mm) 1 RA14210)'4) RA1411,4)
Conventional-Install in Upright or Pendent Position
15mm m> 1/2" NPT(R1/2) 5.6 80 57mm 3, 4, 6 RA1475)
"e cULus listed corrosion resistant(Polyester coated)sprinkler.
(2)Polyester coated FM approved sprinkler.
(3)Polyester coated LPCB&VdS approved sprinkler RA1425, RA1414&RA1475.
'4)Electroless Nickel PTFE(Teflon')"Plated -cULus listed Corrosion Resistant
Q" !°'"'
A
i
s
Upright Pendent Conventional
Model Fl FR56LL & Fl FR42LL Pendent Sprinklers
Installation Wrench: Model D Sprinkler Wrench
Installation Data:
Thread Nominal K Factor Sprinkler Approval
Sprinkler Identification Number
Nominal p ' (SIN)
Orifice
Size US Metric Height Organization Pendent
Standard-Pendent Deflectors Marked to Indicate Position
1/2"(15mm)") 1/2" NPT(R1/2) 5.6 80 2.25" (57mm) 1, 5 RA1415
7/16"(11mm) 1/2" NPT(R1/2) 4.2 60 2.25"(57mm) 1, 5 RA1410
")cULus listed corrosion resistant(Polyester coated)sprinkler.
tit
"DuPont Registered Trademark
3.
Model Fl FR56, Fl FR42, Fl FRXLH & Fl FR28 Quick Response Recessed Pendent Sprinkler 1
Installation Wrench: Model GFR2 Sprinkler Wrench
Installation Data:
Nominal Thread K Factor Sprinkler Sprinkler Identification Number
Orifice Size US Metric Height (SIN) .
1/2" (15mm) 1/2" NPT(R1/2) 5.6 80 2.25" (57mm) RA1414
7/16"(10mm) 1/2" NPT(R1/2) 4.2 60 2.25"(57mm) RA1413
3/8"(10mm) 1/2"NPT(R1/2) 2.8 40 2.25" (57mm) RA1411
("Refer to escutcheon data table for approvals&dimensions
Model Fl FR56LL & Fl FR42LL Quick Response Recessed Pendent Sprinklerf'>
Installation Wrench: Model GFR2 Sprinkler Wrench
Installation Data:
Nominal Thread K Factor Sprinkler Sprinkler Identification Number
Orifice Size US Metric Height (SIN)
1/2"(15mm) 1/2" NPT(R1/2) 5.6 80 2.25"(57mm) RA1415
7/16"(10mm) 1/2" NPT(R1/2) 4.2 60 2.25"(57mm) RA1410
w Refer to escutcheon data table for approvals&dimensions
I1°"""'r_ I _II 1•X I/2'REDUCER
r ---- 2 5/8'DIA.[66.1]
rs==_ mail HOLE M CWHO
r•x Vz•REncrER
wm COLLAR It Ti 2 5/16'M 1.58.21..) _. 1
ACA/NSr.VMMYIEN I CUP -
MT.BOSS� \ / FACE OF CEILING
DI ---
TO FACE C OF N DIMENSION L J
I- I Fr ESOLCUMEI CEILING _
i_\
1
AT MOXIMW/RECESS-IPS Amm) ' .ilk FACE OF MING
1 /� 1 1 Ar MgRMUAM RECESS-J/BT95mm) iinCUrCNFIIti _ TODIMENSION
II-7 'Iii Al'At IMXIMIMINIMURECESS RECESS . IT25.Mnm8'm]
AOJUSINEM AT MNNYU4 RECESS J/6T9.SnnnJ AAAaa „il �'�'
12 2)mm11 fl AXIMUM REN _
ADJUSTMENT AT MAXIMUM RECESS-T/B'(2i.2mm) ,,\� I/rl ]
lipid
,.. �' AT MINIMUM RECESS-S/IATII.JTm
1'\1'I„ AIS I-s/6TAI.Jmm] AADJUSTMENmi `��„-�... A!MINIMUM RECESS- 1725.1mm]
*;_n$ Ar...AM RECESS=r-I/8728Rmm) --
AI WARN RECESS-I-5/6TAI.Jmm) J I/4'DIA. f
.• _ (62.6m4
(XR
Model F1FR56, F1FR56LL, F1FR42, F1FR42LL, F1FRXLH& Model F1FR56, F1FR56LL, F1FR42, F1FR42LL, F1FRXLH &
F1FR28 F1 or F2 F1FR28 FP
Model Fl FR56 Quick Response Vertical Sidewall Sprinkler
Installation Wrench: Model D Sprinkler Wrench
Installation Position: Upright or Pendent
Approval Type: Light Hazard Occupancy
Installation Data:
Nominal K Factor Sprinkler
Nominal Thread Size Sprinkler Approval Identification
Orifice US Metric Height Organizations Numbers(SIN)
1/2"(15mm) 1/2" NPT(R1/2) 5.6 80 2.25"(57mm) 1, 2, 3 8A1485(2)(3)
15mm 1/2" NPT(R1/2) 5.6 80 2.25"(57mm) 3(1)
(1)LPC Approval is for pendent position only.
`2)cULus Listed corrosion resistant(Polyester coated)sprinkler.
cai Electroless Nickel PTFE(Teflon®)*Plated -cULus listed Corrosion Resistant
Sprinkler Type Deflector to Ceiling Distance
01111 (Min.-Max.)
Upright 4"(102mm)- 12" (305mm)
tri Pendent 4" (102mm)- 12" (305mm)
4
Vertical Sidewall
*DuPont Registered Trademark
4.
Bulletin 121 Rev, L
co
c
R111 Ell ® Model G4 Concealed a_.
eliable Automatic Sprinkler N
r
I The ConcealerTM
A Concealed Sprinkler
With 1/2" (13mm) or
11/2" (38mm) Adjustment
o.
Features
1. Cover plate assembly attachment (Plain
or Perforated) with 1/2" (13mm) adjustment. •,---- 1 .
Does
--
Does not require clips or springs.
2. 11/2" (38mm) Total adjustment provided by
adjustable inlet versions.
3. Adjustable inlet version available with either
1" NPT male or female threads eliminating
costly reducing coupling.
4. Smooth aesthetic ceiling profile.
5. Available in white or other color painted or The concealerTM is designed for use where aesthetic ap- 1
brass, chrome, or black plated finishes. pearance is important. Offices,hospitals,motels and restau-
6. Ordinary and intermediate temperature rants are but a few of the applications where it can be used.
It is available in different orifice sizes allowing the designer
ratings. to optimize system performance, thereby achieving a most
• 7. Multiple orifices for design flexibility. efficient installation.
Approvals & Listings The Concealer"'can eliminate the need for precise cutting I
1. Underwriters Laboratories Inc. (UL) of drop nipples. The cover plate assembly can be adjusted
2. Underwriters Laboratories of Canada. (ULC) without tools so it mates accurately with the ceiling. The fire
3. N.Y.C. BS&A No. 587 75-SA. protection system need not be shut down to adjustor remove
the cover plate assembly.
Note: Approvals are for light and ordinary hazard, except for small Product Description
orifice sprinklers which are limited to light hazard occupancies.
The cup and skirt are fabricated from plated steel and are in- The Reliable Model G4 ConcealerTM
standard response I
tended for interior non corrosive applications, uses the proven Model G fusible element in a standard style
sprinkler frame with a drop-down deflector. This assembly is
I recessed into the ceiling and concealed by a flat cover plate.
This threaded engagement provides 1/2"(13mm)of cover ad-
Application MI_ justment. The flat cover plate is attached to the skirt using
The Reliable Model G4 Con- an ordinary temperature classification solder. This results in
I cealerTM is the most versatile a strong cover plate assembly with an ordinary temperature
concealed sprinkler available. It rating,and an intermediate temperature sprinkler which can
provides the best form of fire pro- be installed in 150°F(66°C)environments. When the ceiling
tection while offering an attractive temperature rises, the solder holding the cover plate to the
appearance and 1/2"(13mm) of cover adjustment for ease skirt melts, the flat cover plate released thus exposing the
of installation. The adjustable 1" NPT inlet versions have sprinkler inside to the rising ambient temperature.
11/2" (38mm) of total adjustment and also eliminates the The subsequent fusing of the sprinkler element opens the
need for a reducing coupling. The small diameter cover waterway and causes the deflector to drop into position to
plate assembly is easily attached and blends into the ceil- distribute the discharging water.Any secure engagement of
ing, concealing the most dependable fire protection avail- the threads between the cover plate and cup will assure that
able, an automatic sprinkler system. the drop-down deflector is properly located below the ceiling
when a sprinkler operates.
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Installation
Do not install The ConcealerTM in ceilings which have posi- tion is to be adjusted with the G4 Wrench. Install the cover
tive pressure in the space in the space above, plate assembly by hand turning it clockwise until it is tight
After a 25/8 inch diameter hole is cut in the ceiling,the sprin- against the ceiling.
kler is to be installed with the Model G4 Wrench. The wrench Maintenance
has drive tangs which insert into cup slots. When installing
a sprinkler the wrench is first positioned into the sprinkler/
The Model G4 ConcealerTM should be inspected and the
cup assembly until the wrench tangs engage drive slots in sprinkler system maintained in accordance with NFPA 25,
the top of the cup(there are two sets of mating drive slots in Do not clean sprinklers with soap and water,ammonia or any
the cup). The sprinkler is then tightened into the pipe fitting. other cleaning fluids. Remove any sprinkler that has been
When inserting or removing the wrench from the sprinkler/ painted(other than factory applied)or damaged in any way.
cup assembly care should be taken to prevent damage to A stock of spare sprinklers should be maintained to allow
the sprinkler. DO NOT WRENCH ON ANY OTHER PART OF quick replacement of damaged Cover Plate Finishes())
THE SPRINKLER/CUP ASSEMBLY, or operated sprinklers. Prior to Standard Finishes
installation, sprinklers should
The adjustable inlet versions are similar to the standard Chrome
Model G4 except that an addition 1"(25mm)of adjustment is be maintained in the original White Paint
provided by means of a telescoping inlet section that threads cartons and packaging to mini- Special Application
in or out of a stationary coupling reducer(either 1 male or 1 mize the potential for damage Finishes(2)
female)as shown in Fig.2 or Fig,3. These sprinklers must be to sprinklers that would cause Bright Brass
installed before the ceiling is in place, by wrenching on only improper operation or non-op- Finished Bronze
eration.
the coupling reducer hex flats. After the ceiling has been in- Black Plating
stalled with holes for the sprinkler,each telescoping inlet sec- Ordering Information Black Paint
Temperature Ratings 1. Sprinkler Model Off White
2. Temperature Rating Satin Chrome
Classification Sprinkler Cover Plate Max.Ambient 3. Nominal Orifice (1)
Temp, Other finishes and colors
Ordinary 135°F/57°C 135°F/57°C 100°F/38°C 4. Flat Cover Plate Finish are available on special
Ordinary 165°F/74°C 135°F/57°C 100°F/38°C 5. Inlet Type order. Consult factory for
Ordinary 165°F/74°C 165°FI74°C 150°F/66°C Note: Unless otherwise specified, details.Coverplate custom
the 165°F(74°C) sprinkler will paint is semi-gloss, unless
Intermediate 212°F/100°C 165°F/74°C 150°F/66°C be provided with the 165°F specified otherwise.
Installation Data (74°C)cover. (2) For the perforated style -
Nominal Sprinkler coverplate,consult factory
Sprinkler Total Nominal for availability on these
K Factor Thread Approvals Identification
Inlet Adjustment Orifice US Metric Number(SIN) and other custom finishes.
Note:Paint or any other coat-
Non-Adjustable '/z"(13mm) 1/2"(15mm) 5.6 80 1/2" NPT(R' ) 1,2,3 R2115 ings applied over the factory
Non-Adjustable 1/2"(13mm) 7/16"(11mm) 4.2 60 1/2"NPT(R1/2) 1,2,3 R2113 finish will void all approvals
Non-Adjustable 'h"(13mm) 3/8"(10mm) 2.8 40 '/"NPT(R'/2) 1,2,3 R2111 and warranties.
Adjustable 11/2"(38mm) 'h"(15mm) 5.6 80 1"NPT Male or Female 1,2,3 R2118
Adjustable 1W'(38mm) 7/8"(11mm) 4.2 60 1"NPT Male or Female 1,2,3 R2113 Installation Wrench
Adjustable 1'/2"(38mm) 3/8"(10mm) 2.8 40 1"NPT Male or Female 1,2,3 - R2112 Model G4 Sprinkler Wrench
War
n OR ELBOW
r �i� II =
( TTI--Ti f+ —iii -C- _al
,_ _H__
Hli-it --,- i,Jlli i lii.� in _
fill r - J i�
^SPRINKLER CUP E-lmil Il CEILING air
MT
i 1
_1 r� 11'. ZS/8'Imm;Ma.,". 'uErs Ei Le'`Y:
CEILING , .I..11. 1...
.fin �� Pu' �.,t• ato l;1'a IPPLE
° �N
O illa
1,,,,,,,,,,,,,lit.A. ff;-::,,,,7, bail4d
(9;;mm,,w. „'-...., gie , ,61 ,::� 'gtk' g , —�—2.:-,-,-/ J
Fig.1-1/2"NPT(R1/2)Non-Adjustable Inlet Hg.2-1"NPT Male-Adjustable Inlet Fig.3-1"NPT Female-Adjustable Inlet
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association,Factory
Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years,and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States,Canada and foreign countries.
Manufactured by
Reliable Automatic Sprinkler Co.,Inc. Recycled
eIiaII ® (800)431-1588 Sales Offices Paper
(800)848 6051 Sales Fax Revision lines indicate updated or new data.
(914)829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address EG.Printed in U.S.A.05/15 P/N 9999970014
Bulletin 110 Rev.S
Model G co
R-1111-111-abld Automatic Sprinklers
Spray Upright,
Spray Pendent o
And Conventionalco
J)
Product Description
The Reliable Model G Automatic Sprinkler utilizes the
center strut solder in compression principle of ton ,,,,..
construction. The fusible alloy is captured in thei
cylinder of the solder capsule by a stainless steel ball. '�
When the fusible alloy melts, the ball moves into the el t
cylinder allowing the cylinder to fall away from the 1...:, t
sprinkler. When this happens, the lever is released to
spring free from the sprinkler so that all of the operating Basco; ik .V ,
parts clear from the waterway allowing the deflector to "t
distribute the discharging water. _¢ -:
Except for the parts in the cylinder as mentioned
above, the sprinkler components are made from Upright Pendent
copper based alloys for maximum corrosion
protection. Lead plated, wax coated or wax over lead
plated sprinklers are available for specially severe .,
environments. Chrome plated sprinklers are available "'P )
for decorative purposes. 7
All sprinklers are individually hydrostatically tested. ? f'
All sprinklers are identified as to their fusing point by -
markings that appear on several of the operating parts ;,;
and by an identifying color that appears on the frame. •
Sprinkler Types
Standard Upright - This deflector configuration is Small Orifice Upright Conventional
normally used with exposed piping installations.Water
is distributed laterally and downward in a wide pattern
approximating a hemisphere which is completely and
uniformly filled with water in the form of small drops or
spray.
Standard Pendent - This deflector configuration is Application and Installation
normally used where the space above the piping is Standard sprinklers are used in fixed fire protection
I limited or where a concealed piping installation is systems:Wet, Dry, Deluge or Preaction. Care must be
employed. The discharge characteristics of the exercised that the orifice sizes, temperature ratings,
standard pendent are virtually identical to the deflector styles and sprinkler spacings are in
standard upright as described above. accordance with the latest published standards of the
National Fire Protection Association or the approving
Large and Small Orifice—By varying the orifice size, authority having jurisdiction.
a large or small orifice sprinkler is created that will The sprinklers must be installed with the Reliable
distribute as much as 40% more water or 65% less Model D Sprinkler Wrench. Any other type of wrench
water than the normal '/z" (15mm)orifice sprinkler. may damage the sprinkler.
The approvals or listings of Reliable Automatic
Conventional—This deflector configuration is used Sprinklers by major approving organizations are
primarily in those countries where the LPC installation shown in the tabulated list provided on the back of this
rules have precedence. The sprinkler is designed to bulletin.
distribute a portion of its water discharge upward
against the ceiling with the balance downward. It may
be installed in either the upright or the pendent
position. Sprinklers with conventional deflectors are
available with orifice sizes corresponding to light, *Patent No.4,440,234
ordinary and extra-high hazard installations.
The Reliable Automatic Sprinkler Co.,Inc.,525 North MacQuesten Parkway,Mount Vernon,New York 10552
Technical Data
"K"Factor Sprinkler Identification
Sprinkler Number(SIN)
Sprinkler Type US Metric Height Approvals SSU SSP
Standard-Upright(SSU)and Pendent(SSP)
Deflectors Marked to Indicate Position
}2"(15 mm)Standard Orifice with/2"NPT(R/2)Thread 5.62 81.0 2/8" (73 mm) 1,2,3,4,5,6,7 R1025 R1015
/fi'(11 mm)Small Orifice with/2"NPT(R/)Thread 4.24 61.0 2'/a" (73 mm) 1,3,7 R1023 R1013
X"(10 mm)Small Orifice with/8"NPT(R/)Thread 2.82 40.6 2'/s" (73 mm) 1,2,3,7 R1021 R1011
K''(8mm)Small Orifice with/8"NPT(R/)Thread 1.98 28.5 2'/8" (73 mm) 1,3,7 R1022 R1012
1/2'(20 mm)Large Orifice with y"NPT(R/8)Thread 7.96 114.7 2 Y8" (73 mm) 1,2,3,7 R1026 R1016
1/2'(20 mm)Large Orifice with X"NPT(R%)Thread 8.20 118.2 218/e' (75 mm) 1,2,3,7 R1027 R1017
20 mm XHH with 20 mm Thread 8.20 118.2 75.4 mm 4,5,6 R1027 R1017
10 mm XLH with 10 mm Thread 4.10 59.1 73 mm 4,5,6 R1024 R1014
Conventional—Installed in Upright or Pendent Position
10mm XLH with l omm Thread 4.10 59.1 73 mm 5 81074
15mm Standard Orifice with(R/2) Thread 5.62 81.0 73 mm 4,5,6 R1075
20mm XHH with(R%)Thread 8.20 118.2 75.4 mm 4,5 R1077
Temperature Ratings Maintenance
Maximum Model G Sprinklers should be inspected quarterly and the
Sprinkler Ambient sprinkler system maintained in accordance with NFPA 25. Do
Rating Temperature Frame(1) not clean sprinklers with soap and water,ammonia or any other
Classification °F °C °F °C Color cleaning fluids. Remove any sprinkler that has been painted
Ordinary 135 57 100 38 Black (other than factory applied)or damaged in any way.A stock of
Ordinary 165 74 100 38 Uncolored spare sprinklers should be maintained to allow quick replace-
Intermediate 212 100 150 66 White ment of damaged or operated sprinklers. Prior to installation,
High 286 141 225 107 Blue sprinklers should be maintained in the original cartons and
packaging until used to minimize the potential for damage to
(1)Frame color does not apply to painted or plated sprinklers sprinklers that would cause improper operation or
-Use sprinkler rating as identified on operating parts. non-operation. Use only the Model D Sprinkler Wrench for
sprinkler removal and installation.Any other type of wrench may
damage the sprinkler.
Finishes()
Standard Finishes Approval Organizations
Bronze —All Temperature Ratings 1. Underwriters Laboratories, Inc.
Chro e —All Temperature Ratings 2. Factory Mutual Research Corporation
White —All Temperature Ratings 3. Underwriters' Laboratories of Canada
Only Frame and Deflector are Painted 4. Loss Prevention Council
Special Application Finishes 5. Pleniere Assemblee
6. VdS Schadenverhutung
Bright Brass Plated —Only frame,deflector and cap are plated.135°F(57°C), 165°F 7. N.Y.C. BS&A No. 587-75-SA or
(74°C),212°F(100°C)Temp.Rating. N.Y.C. MEA 258-93-E
Black Plated —Only frame,deflector and cap are plated.All Temp.Ratings.
Polyester Coated(2) —Only frame and deflector are coated.
Lead Plated —165°F(74°C),212°F(100°C)and 286°F(141°C)Temp.Ratings. Ordering Information
Wax-Coated(3) —165°F(74°C)Clear Wax,212°F(100°C) Brown Wax. Specify
Wax-Coated Over 1. Model G
Lead Plated(3) —165°F(74°C)Clear Wax,212°F(100°C) Brown Wax. 2. Deflector
•Upright
(11 Other colors and finishes are available.Consult factory for details. •Pendent
(2) UL listed and NYC MEA Approved only. •Conventional
(3) 212°F(100°C)brown wax may be used on 286°F(141°C) 3. Nominal Orifice
sprinklers when maximum ambient temperatures do not exceed 150°F 4. Inlet Thread
(66°C).UL Listed,FM Approved,NYC MEA 258-93-E. 5. Temperature Rating
6. Finish
The equipment presented in this bulletin is to be instated in accordance with the latest pertinent Standards of the National Fire Protection Association,Factory Mutual
Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 80 years,and are instated and serviced by the most highly qualified and
reputable sprinkler contractors located throughout the United States,Canada and foreign countries.
Manufactured by
The Reliable Automatic Sprinkler Co.,Inc.
Heliable (800)431-1588 Sales Offices :; Reryded
(800)848-6051 Sales Fax Paper
(914)668-3470 Corporate Offices Revision lines indicate updated or new data.
IMOINIMINI www.reliablesprinkler.com Internet Address EG.Printed in U.S.A. 11/04 P/N 9999970005
Bulletin 111M
. 7.
Do
• ReliabId
MIIIIIodel G
Recessed c
Automatic Sprinkler K
:
The Most Compact Attractive ,h ,_ ti
r and Easily Installed Sprinkler r
Ever Designed!
Featurest
,
1. 11/2" (38mm) Total adjustment provided
1 1 ..
by adjustable inlet versions. - :
2. 1/2"(13mm)Total adjustment provided by - 61* ~-. , ,-
economical standard inlet version. I • c, _ , t .
3. Adjustable inlet version available with
either 1" NPT male or female threads
eliminating costly reducing coupling.
4. Small diameter escutcheon.
5. Available in brass, chrome or white finish.• The Model G Recessed Sprinkler's threaded
6. Multiple orifice sizes for design flexibility. two-piece construction makes initial field installation a
7. Listed by Underwriters Laboratories Inc. very easy task. It allows ceilings panels to be removed
without shutting down the fire protection thus facilitating
& Underwriters' Laboratories of Canada. maintenance of above ceiling services. The adjustable
Approved by Factory Mutual Research ofadjustment wh ch eliminates both the ne inch NPT inlet versions have one ormally relquired
Corp. & Loss Prevention Council, NYC reducing coupling and the need to accurately cut drop
BS&A No., 587-75-SA. nipples. This sprinkler can be adjusted after the ceiling is
in place and even while the system is pressurized elimi-
nating the final corrections to pipe hangers or ceilings that
might otherwise be required.
Product Description The Reliable Model G Automatic Sprinkler is the heart
Today's modern buildings demand that a sprinkler not of the Recessed Sprinkler. This sprinkler utilizes the cen-
only provide the best fire protection but also achieve an ter strut solder in compression principle of construction.
attractive appearance. Reliable's Model G Recessed The fusible alloy,captured in the cylinder of a small solder
Sprinkler meets both criteria. It combines the fire fighting capsule by stainless steel ball, acts as the trigger of the
capability of a proven sprinkler with the smallest practica- sprinkler. When the fusible alloy melts,the sprinkler oper-
ble recessing unit. Its small profile does not disrupt the ating parts sprinkler free from the sprinkler clearing the
overhead aesthetics,and yet one vertical glance upward waterway and allowing the deflector to distribute the dis-
gives a visual assurance of the finest in fire protection,an charging water.
automatic sprinkler system.
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Installation
The Reliable Model G Recessed Sprinkler has been \''
designed with ease of installation in mind. A choice serted into the special Reliable Model RC-1 Installation
Wrench. This wrench must be used. The wrenching
three inlets with up to one inch adjustment coupled with
the '/2" (13mm) escutcheon adjustment enables most pads of the sprinkler easily slip into the rectangular •
system to be installed usin cut-outs of the wrench as the outside diameter locates the
g pre-cut drop nipples. The threaded cup. A 1/2"(13mm) drive ratchet can then be
adjustment can be accomplished after the ceiling instal- used for installation and tightening.
lation and while the system is pressurized thereby provid- Figure 5 shows the removal of the wrench. Care
ing sprinkler protection before construction is completed, should be taken during this procedure to avoid hitting the
The Non-Adjustable inlet version(Figure 1)Consists of deflector with the wrench. The wrench should be lowered
the Reliable Model G Sprinkler with an attached cup re- until it clears the sprinkler. The installation completed by
cessed in the ceiling. A ceiling hole of 21/2"(67mm)diam-
eter is recommended. threading the escutcheon on until it contacts the ceiling.
The Adjustable inlet version uses the same sprinkler as To avoid leaving smudge marks on the ceiling, the Reli-
ablethe Non-Adjustable inlet version uses the same shoeld be used. See Bulletin 20sprinkler Model FEA Flush Sn 20le Escutcheon Wrench
as the Non-Adjustable inlet type except the 1 of additional 5
Note:
adjustment is provided by a telescoping sprinkler inlet
Ad-
section that threads in or out of a stationary Coupling Re- 1. Use hex wrench in Coupling Reducer to tighten ducer(either 1 male or 1 female)as shown in figures 2 or Wrench Sprinkler purpose.into fittings. Do not use RC 1
3. The Sprinkler-Cup assembly comes attached to thein Wrench for this
let Coupling Reducer Comes attached to the inlet Cou-
pling Do not install the Model G Recessed Sprinkler in ceil-
pling Reducer and is retained from separation past its ings which have positive pressure in the space above.
maximum adjustment length by a snap ring. This combi-
nation is simply installed after the system drop nipple, el- Maintenance
bow or tee has been "roughed in" to the dimensions The Model G Recessed Pendent Sprinklers should be
inspected quarterly and the sprinkler system maintained
shown in figures 2 or 3. Wrenching means are provided
by hex flats on the coupling reducer as depicted in the in accordance with NFPA 20. Do not clean sprinklers with
soap and water,ammonia or any other cleaning fluid. Re-
figures-do not wrench on any other part of the sprinkler.
After the ceiling tiles have been cut and installed in place move any sprinkler that has been painted(other that fac-
tory(a 2'/a" {57mm}hole is recommended), the sprinkler can applied) or damaged in any way. A stock of spare
sprinklers should be maintained to allow quick replace-
be adjusted using the RC-1 Concealed Wrench,
When using the wrench in this application, however, of damaged or operated sprinklers. Prior to instana
do not over-torque beyond the adjustment stops. tionion,, sprinklers should be maintained in the originall
Figure 4 shows a 1/2" NPT (R1/2) non-adjustable inlet cartons and packaging until used to minimize the poten-
sprinkler,with the attached sprinkler cup combination in-
operation
for damage to sprinklers that would cause improper
operation or non-operation.
•
��la moA��
• ;E aso.
Ya-%I6-t 1>/...ORa1C'(; 1III VIII , MEL r-L. �== cos.PP[E
1
ITI, ; i'rin TI L ql I I I II iL — Mo>E 1
II
i T---� IIMI
��,{ flu1111
r, i Muf ���� rvore r
2 J/I6'Q0.
(JJ 1 lay
CEtt; ''''' 5500
J J QEF
FACE OF N.T.TO J J/A'3J%
r%•%j�•A FACE OF Cell.
ST
L'-----.--..-..
,. tr
• TOROP NIPPLE td iro1 —�1/1•ESLVIEMf'py I „AN Ei NG - ,-Iry i! ASSEUBCv �� r/ri
='ll ASS'''''
(IJ/ Aa0SNCNT '
J
,;, I..i Cr
P.,1 --- i Q i:r :L 1 L
Nom-ASCUICM£OII Q 5/a' AALjly�,MENr --Vir 3/a-
MUSTMErvT �� �I
1/2" NPT Non-Adjustable Inlet 1" NPT Male-Adjustable Inlet 1" NPT Female-Adjustable Inlet
Figure 1 Figure 2 Figure 3
2.
M
I
I-
Technical Data
"K"Factor Sprinkler
Total Approval Identification
• Sprinkler Inlet Adjustment Nominal Orifice U.S. Metric Thread Organizations Number(SIN)
Non-Adjustable 1/2"(13mm) 1/2"(15mm) 5.62 81.0 1/2"NPT(R'/z) 1,2,3,4,5, R1015
Non-Adjustable 1/2"(13mm) Y 16'(11 mm) 424 61.0 1/2"NPT(R1/2) 1,3,4 R1013
Non-Adjustable 1/2"(13mm) X"(10mm) 2.82 40.6 Y"NPT(R1/2) 1,3,4 R1011
Non-Adjustable 1/2"(13mm) 17/32"(20mm) 7.96 114.7 1/2"NPT(RY) 1,3 R1016
Adjustable 11/2"(38mm) 1"(15mm) 5.53 79.7 1"NPT Male or Female 1,2,3,4 R1118
Adjustable 11/2"(38mm) '1,"(11 mm) 4.24 61.0 1"NPT Male or Female 1,3,4 R1113
Adjustable 11/2"(38mm) %"(10mm) 2.75 39.2 1"NPT Male or Female 1,3,4 81117
Adjustable 11/2"(38mm) 15mm 5.53 79.7 R1 Male or Female 5 R1118
*Sprinkler escutcheon provides'/(13mm)of the total adjustment. Adjustable inlets,when used,provide 1 (25mm)of the total adjustment.
t"Identified by pintle extending above the deflector.
Temperature Ratings Ordering Information
Maximum Ambient Specify:
Sprinkler Rating Temperature 1. Temperature Rating
Classification °F co °F °C 2. Nominal Orifice
Ordinary 135 57 100 38 3. Sprinkler Finish
Ordinary 165 74 100 38 4. Escutcheon Finish
Intermediate 212 100 150 ss 5. Sprinkler Type:Either Non-Adjustable Inlet(Fig. 1);1"
Male Adjustable Inlet(Fig. 2); 1" Female Adjustable
Approval Organizations Inlet(Fig.3)
1. Underwriters Laboratories Inc.
2. Factory Mutual Research Corp. Finishes f1'
• Light Hazard Occupancies-No limitations Standard Finishes
• Ordinary Hazard Occuncies-Groups 1 &2,Wet Sprinkler Escutcheon
Systems Only Bronze Brass
3. Underwriters Laboratories of Canada Chrome Chrome
4. NYC BS&A No. 587-75-SA white Painted'4 white Painted
• 5. Loss Prevention Council Special Application
• XLH, OHI and OHII Occupancies Only Sprinkler Escutcheon
6. NYC MEA 258-93-E Bright Brass( Bright Brass
• Black Plated`a Black Plated
Note: Unless otherwise indicated, Ordinary hazard ap- Satin Satin
provals are without limitations.X62(11 mm)and%2(10mm) Polyester Coated"' Polyester Coated
orifice sprinklers are limited to light hazard occupancies. '>Other color Finishes available upon request.Consult Factory for
details.
(')Only frame,deflector and cap are plated
'3'Only frame and deflector are painted or coated.Operating parts
are chrome plated.UL Listed and MEA Approved only.
t :)
1
•
,, *I --: 3,
r#
, ; r li*/ '
• Figure 4 Figure 5
3.
Reliablea.. For Complete Protection 'N.. •
Reliable offers a wide selection of sprinkler components. Following are some of the
many precision-made Reliable products that guard life and property from fire around
the clock.
• Automatic sprinklers • Deluge valves
• Flush automatic sprinklers • Detector check valves
• Recessed automatic sprinklers • Check valves
• Concealed automatic sprinklers • Electrical system
• Adjustable automatic sprinklers • Sprinkler emergency cabinets
• Dry automatic sprinklers • Sprinkler Wrenches
• Intermediate level sprinklers • Sprinkler escutcheons and
guards
• Open sprinklers • Inspectors test connections
• Spray nozzles • Sight drains
• Alarm valves • Ball drips and drum drips
• Retarding chambers • Control valve seals
• Dry pipe valves • Air maintenance devices
• Accelerators for dry pipe valves • Air compressors
• Mechanical sprinkler alarms • Pressure gauges
• Electrical sprinkler alarm switches • Identification signs
• Water flow detectors • Fire department connection
The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association,Factory Mutual Re-
search Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years,and are installed and serviced by the most highly qualified and
reputable sprinkler contractors located throughout the United States,Canada and foreign countries.
Manufactured by
® The Reliable Automatic Spunkier Co.,Inc. Recycled
iaRelble (800) 431-1588 Sales Offices •' Paper
(800) 848-6051 Sales Fax
(914) 829-2042 Corporate Offices Revision lines indicate updated or new data
www.reliablesprinkler.com Internet Address EG.Printed in U.S.A.12100 P/N9999970006