Plans (47) OFFICE COPY
Interstate Roofing 15065 SW 74th Avunue Portland, OR 97224
CITY OF IGARD
REVIEWED FOR DE COMPLIANCE
T PGE
Approved: [ C7.4G4 fr c e l
OTC: [
Permit 11: £1.-L2v1 7- Com° 7 Li if
(3)#4 PVC Address: /c0,1,5" c., 7 H+` ,
Meter Socket Suite#:
1-1/4" 208/120
Ft:3i
CT B}. Date: f/i/ i
600 AMP
ENCLOSURE 3 PHASE
2-1/2" PVC 2-1/2" PVC 2-1/2" PVC
(3)4/0 (4)3/0 (4)3/0
(1)3/0
208/120 208/120 208/120
225 AMP 200 AMP 200 AMP
OFFICE PANEL 1 3 PHASE OFFICE PANEL 2 3 PHASE HVAC PANEL 3 3 PHASE
TOTAL WATTS 61,458 TOTAL WATTS 22,321 TOTAL WATTS 48,846
I
#4 BARE I #4 BARE
#2 BARE GROUND #6 BARE GAS PIPE
BAR C 0
r-� D
TOTAL WATTS 132,625 Z O
360 3/0 COPPER 0 T rr m
368 AMPS <� c C
N_
UFERGROUND �� ti
o
v
3g'3 ,)-:
INTERSTATE ROOFING
OFFICE
10,635 SQUARE FEET
LIGHTING 10,635 X 3.5 w X 1.25% = 46,528
GENERAL USE RECEPTACLES 81 X 180 va = 14,580 =
DERATE 10,000 = 10,000
4,580 X 0.5 = 2,290
MICROWAVE 14 amps X 120v = 1,680
COFFEE MAKER 8 amps X 120v = 960
TOTAL WATTS 61,458
360
171 amps
WAREHOUSE
7,770 SQUARE FEET
LIGHTING 7,770 X 0.25 w X 1.25% = 2,428
GENERAL USE RECEPTACLES 20 X 180 w = 3,600
SIGN 1,200 X 1.25% = 1,500
HOT WATER HEATER 43amps X 208v 8,944
TOTAL WATTS 16,472
360
46 amps
EXISTING WAREHOUSE
2,400 SQUARE FEET
LIGHTING 2,400 X 0.25 w X 1.25% = 750
GENERAL USE RECEPTACLES 20 X 180 w = 3,600
SIGN 1,200 X 1.25% = 1,500
TOTAL WATTS 5,850
360
16 amps
HVAC EQUIPMENT
7.5 TON ROOF MUNTED GAS PACK 42 amps X 1.25% X 208v X 1.73% = 18,913
10 TON ROOF MOUNTED GAS PACK 50 amps X 1.25% X 208v X 1.73% = 22,516
4TON MULTI-SPLIT 27amps X 1.25% X 208v = 7,020
TOTAL WATTS 48,449
360
135 amps
3 g3
INTERSTATE ROOFING
OFFICE PANEL#1
DESCRIPTION L1 L2 13 Ni N2 N3
LIGHTING 15,509 15,509 15,509 15,509 15,509 15,509
GENERAL USE RECEPTACLES 4,097 4,097 4,097 4,097 4,097 4,097
MICROWAVE 1,680 1,680
COFFEE MAKER 960 960
21,286 20,566 19,606 21,286 20,566 19,606
TOTAL WATTS 61,458 - 360 = 171 amps
NEUTRAL LOAD 171 amps
Wig,
3'?3gs
INTERSTATE ROOFING
PANEL#2
DESCRIPTION L1 L2 L3 Ni N2 N3
LIGHTING 809 809 809 809 809 809
GENERAL USE RECEPTACLES 1,200 1,200 1,200 1,200 1,200 1,200
SIGN 1,500 1,500
EXISTING WAREHOUSE 2,950 1,450 1,450 2,950 1,450 1,450
HOT WATER HEATER 4,472 4,472
6,459 7,931 7,931 6,459 3,459 3,459
TOTAL WATTS 22,321 - 360v = 62 amps
NEUTRAL LOAD 54 amps
333 ..35
INTERSTATE ROOFING
HVAC PANEL#3
DESCRIPTION L1 L2 L3 Ni N2 N3
7.5 TON ROOF TOP 6,304 6,304 6,304
10 TON ROOR TOP 7,505 7,505 7,505
4 TON MULTI SPLIT 3,510 3,510
17,319 17,319 13,809 - - -
TOTAL WATTS 48,447 - 360 volts = 135 amps
NEUTRAL LOAD 0 amps
Portland General Electric Company
/11\
GE02/16/17
CONTACT: RICH METZLER N.
PHONE: 503-860-5249
CUSTOMER NAME: INTERSTATE ROOFING
ADDRESS: 15065 SW 74TH AVE TIGARD
SDPM/ENGR: CHRIS JEWETT WR: M2184287
PHONE: 503-6723-5481
3-PHASE SECONDARY LINE-LINE FAULT CURRENT (RMS)
TRANSFORMER DATA PAD MOUNT? YES
XFMR Impedance(%): 2.98 % 3-PH SUBMERSIYES
TRANSFORMER SIZE: 300 INA XFMR? NO
Secondary VOLTAGE(L to L): 208 v WYE OH BANK? NO
VAULT--> VAULT ( or Pole --> Pole) SECONDARY
Secondary Wire LENGTH: 0 Feet WIRE SIZE
Number of SECONDARY RUNS: 1 Run(s)of:
Secondary WIRE Resistance R: 0.0180 Ohms/1000'
Secondary WIRE Reactance X: 0.0258 Ohms/1000'
VAULT ( or Pole) —> PANEL SECONDARY (or Svc Drop)
Service Wire LENGTH: 135 Feet WIRE SIZE
Number of Service RUNS: 2 Run(s)of: 350 AL XLP
Service WIRE Resistance R: 0.0600 Ohms/1000'
Service WIRE Reactance X: 0.0520 Ohms/1000'
MAXIMUM FAULT CURRENT*: 12,436 Amps
*Maximum fault current based upon transformers/conductors sized for 100% of electrical panel rating.
Based on a panel size of: 600 Amps
To Print This Page: "Ctrl M"and choose"Print 3-Phase Data"