Loading...
Report Mc?' 4,0 s k 6975 SW SANDBURG ST#160 11-'4* • TIGARD, OR 97223 . °a. .c: (971)371-1958 SPECIAL INSPECTION—FINAL SUMMARY LETTER April 3,2017 Mr. Mark Van Domelen City of Tigard, Building Department 13125 SW Hall Blvd. Tigard, OR 97223 RE: Laird Residence Underpinning 14392 SW 88t Ave. Tigard,OR 97223 Permit#MST2017-00088 Dear Mark: This letter certifies that we have performed special inspection of the referenced project, in accordance with Chapter 17 of the International Building Code. Special inspection has been performed on (4)push piers, as shown on the permit documents. On March 27,2017,a representative of i.e.Structural observed the installation of(1)Foundation Supportwork Incorporated model PP288T push piers,as shown on structural drawings.All push piers reached or exceeded the specified installation pressure and the minimum penetration depth specified on structural drawings.Load testing was performed on piers (1) and (2) in accordance with ASTM method D1143 (Quick Method), and passed the creep acceptance criteria.i.e.Structural has reviewed the installation logs of the remaining piers and confirmed them to be acceptable. Special inspections have been provided to meet the requirements of the building code and do not constitute a guarantee of the installed work. It is the responsibility of the contractor to execute the work in accordance with the structural drawings. If you have any questions or need further information,please call me. „UCT Sincere! �Ep PRoFS fr�G1NE���O 73626 Dima Shemetov Inspector 4.; 21,26\ , W, No