Loading...
Report (3) &' 52a?- 0oU2 CP 77, 5 !/vvi •<<-" PROFsS • 40°MgliMik v„‘G kN,.? tr 799 O 6N R'�. 13.7° 0 SL.DE EXPIRES: (Z"3147 1 Fire Protection by Computer Design • • Fire Systems West Inc. 600 SE Maritime Ave. Suite 300 Vancouver, WA. 360-771-2690 Job Name : BONITA WEARHOUSE Building : 2 of 3 Location : 6777 SW BONITA System : 2 Contract : 1-11-1460 Data File : Bonita CaIc.WXF • Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Water St. Curve C • t • Fire Systems West Inc. Page 1 BONITA WEARHOUSE Date 2/24/17 City Water Supply: Demand: Cl -Static Pressure : 105 D1 - Elevation : 9.138 C2 - Residual Pressure: 98 D2- System Flow : 1053.09 C2- Residual Flow : 1680 D2-System Pressure : 93.047 Hose ( Demand) : 500 D3-System Demand : 1553.09 Safety Margin : 5.900 150 140 130 p120 R110 A Cl C2 E 100 = D2 S 90 _ o S 80 D3 U 70 R60 = E 50 40 30 20 10 D1 200 400 600 800 1000 1200 1400 1600 1800 FLOW ( NA1.85) Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Fittingsl4 Summary 0 r • Fire Systems West Inc. Page 2 BONITA WEARHOUSE Date 2/24/17 Fitting Legend Abbrev. Name 1/2 3 1 1'/ 11/2 2 21/2 3 31/2 4 5 6 8 10 12 14 16 18 20 24 E NFPA 13 90'Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow I 90'Grvd-Vic Elbow#10 0 0 2 3 4 3.5 6 5 8 7 8.5 10 13 17 20 23 25 33 36 40 J 90'Tee-Branch Gry Vic#20 0 0 4.5 6 8 8.5 10.8 13 17 16 21 25 33 41 50 65 78 88 98 120 T NFPA 13 90'Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121 Zce Colt C300 Vert Butt Fitting generates a Fixed Loss Based on Flow Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a*show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a *will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Pressure / Flow Summary - STANDARD Fire Systems West Inc. Page 3 BONITA WEARHOUSE Date 2/24/17 SNode Elevation K-Fact Pt Pn Flow Density Area Press No. Actual Actual Req. R11 22.4 20.37 na 101 22.4 11.2 19.67 na 49.67 0.495 100 7.0 102 22.4 11.2 19.58 na 49.56 0.495 100 7.0 103 22.4 11.2 19.58 na 49.56 0.495 100 7.0 104 22.4 11.2 19.64 na 49.63 0.495 100 7.0 105 22.4 11.2 19.86 na 49.91 0.495 100 7.0 106 22.4 11.2 20.35 na 50.53 0.495 100 7.0 R9 22.6 20.32 na 107 22.6 11.2 19.62 na 49.61 0.495 100 7.0 108 22.6 11,2 19.53 na 49.5 0.495 100 7.0 109 22.6 11.2 19.53 na 49.5 0.495 100 7.0 110 22.6 11.2 19.59 na 49.57 0.495 100 7.0 111 22.6 11.2 19.81 na 49.85 0.495 100 7.0 112 22.6 11.2 20.31 na 50.47 0.495 100 7.0 R7 22.8 20.34 na 113 22.8 11.2 19.65 na 49.65 0.495 100 7.0 114 22.8 11.2 19.57 na 49.55 0.495 100 7.0 115 22.8 11.2 19.57 na 49.54 0.495 100 7.0 116 22.8 11.2 19.63 na 49.62 0.495 100 7.0 117 22.8 11.2 19.86 na 49.91 0.495 100 7.0 118 22.8 11.2 20.36 na 50.53 0.495 100 7.0 R5 23.0 21.57 na 119 23.0 11.2 21.6 na 52.05 0.495 100 7.0 120 23.0 11.2 21.73 na 52.21 0.495 100 7.0 121 23.0 11.2 22.1 na 52.66 0.495 100 7.0 R3 23.2 24.49 na R1 23.4 24.7 na C6 21.68 21.74 na • C5 21.68 21.77 na C4 21.68 21.88 na C3 21.68 22.09 na - C2 21.68 23.13 na R12 22.4 36.27 na R10 22.6 36.25 na R8 22.8 36.44 na - R6 23.0 37.56 na R4 23.2 39.27 na R2 23.4 40.73 na M6 21.68 39.56 na M5 21.68 39.65 na M4 21.68 39.97 na M3 21.68 40.65 na M2 21.68 41.76 na M1 21.68 43.31 na M 21.68 64.1 na TOR 21.68 73.34 na BF1 7.0 82.51 na BF2 1.0 92.05 na BOR -3.0 93.85 na TEST 1.5 93.05 na 500.0 The maximum velocity is 23.16 and it occurs in the pipe between nodes M1 and M III .. Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 1 Final Calculations - Hazen-Williams Fire Systems West Inc. Page 4 BONITA WEARHOUSE Date 2/24/17 IVHyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn R11 -105.08 2.703 0.0 25.250 20.372 to 120.0 0.0 0.0 0.0 101 -105.08 -0.0279 0.0 25.250 -0.704 Vel = 5.88 101 49.67 2.703 0.0 10.000 19.668 K Factor= 11.20 to 120.0 0.0 0.0 0.0 102 -55.41 -0.0086 0.0 10.000 -0.086 Vel = 3.10 102 49.56 2.703 0.0 10.000 19.582 K Factor= 11.20 to 120.0 0.0 0.0 0.0 103 -5.85 -0.0001 0.0 10.000 -0.001 Vel = 0.33 103 49.56 2.703 0.0 10.000 19.581 K Factor= 11.20 to 120.0 0.0 0.0 0.0 104 43.71 0.0055 0.0 10.000 0.055 Vel = 2.44 104 49.63 2.703 0.0 10.000 19.636 K Factor= 11.20 to 120.0 0.0 0.0 0.0 105 93.34 0.0224 0.0 10.000 0.224 Vel = 5.22 105 49.92 2.703 0.0 10.000 19.860 K Factor= 11.20 to 120.0 0.0 0.0 0.0 106 143.26 0.0495 0.0 10.000 0.495 Vel = 8.01 106 50.53 2.703 0.0 184.000 20.355 K Factor= 11.20 to 120.0 0.0 0.0 0.0 R12 193.79 0.0865 0.0 184.000 15.919 Vel = 10.83 0.0 193.79 36.274 K Factor= 32.18 R9 -104.58 2.703 0.0 25.250 20.316 _ to 120.0 0.0 0.0 0.0 107 -104.58 -0.0276 0.0 25.250 -0.698 Vel = 5.85 107 49.61 2.703 0.0 10.000 19.618 K Factor= 11.20 to 120.0 0.0 0.0 0.0 108 -54.97 -0.0084 0.0 10.000 -0.084 Vel = 3.07 108 49.50 2.703 0.0 10.000 19.534 K Factor= 11.20 to 120.0 0.0 0.0 0.0 109 -5.47 -0.0001 0.0 10.000 -0.001 Vel = 0.31 109 49.50 2.703 0.0 10.000 19.533 K Factor= 11.20 to 120.0 0.0 0.0 0.0 110 44.03 0.0056 0.0 10.000 0.056 Vel = 2.46 110 49.57 2.703 0.0 10.000 19.589 K Factor= 11.20 to 120.0 0.0 0.0 0.0 111 93.6 0.0225 0.0 10.000 0.225 Vel = 5.23 111 49.86 2.703 0.0 10.000 19.814 K Factor= 11.20 to 120.0 0.0 0.0 0.0 112 143.46 0.0496 0.0 10.000 0.496 Vel = 8.02 112 50.47 2.703 0.0 184.000 20.310 K Factor= 11.20 to 120.0 0.0 0.0 0.0 R10 193.93 0.0866 0.0 184.000 15.941 Vel = 10.84 0.0 193.93 36.251 K Factor= 32.21 • R7 -103.90 2.703 0.0 25.250 20.341 _ to 120.0 0.0 0.0 0.0 113 -103.9 -0.0273 0.0 25.250 -0.689 Vel = 5.81 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams Fire Systems West Inc. Page 5 BONITA WEARHOUSE Date 2/24/17 • Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn 113 49.64 2.703 0.0 10.000 19.652 K Factor= 11.20 to 120.0 0.0 0.0 0.0 114 -54.26 -0.0082 0.0 10.000 -0.082 Vel = 3.03 114 49.55 2.703 0.0 10.000 19.570 K Factor= 11.20 to 120.0 0.0 0.0 0.0 115 -4.71 -0.0001 0.0 10.000 -0.001 Vel = 0.26 115 49.55 2.703 0.0 10.000 19.569 K Factor= 11.20 to 120.0 0.0 0.0 0.0 116 44.84 0.0057 0.0 10.000 0.057 Vel = 2.51 116 49.61 2.703 0.0 10.000 19.626 K Factor= 11.20 to 120.0 0.0 0.0 0.0 117 94.45 0.0229 0.0 10.000 0.229 Vel = 5.28 117 49.91 2.703 0.0 10.000 19.855 K Factor= 11.20 to 120.0 0.0 0.0 0.0 118 144.36 0.0502 0.0 10.000 0.502 Vel = 8.07 118 50.53 2.703 0.0 184.000 20.357 K Factor= 11.20 to 120.0 0.0 0.0 0.0 R8 194.89 0.0874 0.0 184.000 16.088 Vel = 10.90 0.0 • 194.89 36.445 K Factor= 32.28 R5 18.83 2.703 0.0 25.250 21.567 - to 120.0 0.0 0.0 0.0 119 18.83 0.0011 0.0 25.250 0.029 Vel = 1.05 119 52.05 2.703 0.0 10.000 21.596 K Factor= 11.20 - to 120.0 0.0 0.0 0.0 120 70.88 0.0135 0.0 10.000 0.135 Vel = 3.96 120 52.21 2.703 0.0 10.000 21.731 K Factor= 11.20 to 120.0 0.0 0.0 0.0 121 123.09 0.0373 0.0 10.000 0.373 Vel = 6.88 121 52.66 2.703 0.0 214.000 22.104 K Factor= 11.20 to 120.0 0.0 0.0 0.0 R6 175.75 0.0722 0.0 214.000 15.454 Vel = 9.83 0.0 175.75 37.558 K Factor= 28.68 R3 147.51 2.703 0.0 283.000 24.494 to 120.0 0.0 0.0 0.0 R4 147.51 0.0522 0.0 283.000 14.779 Vel = 8.25 0.0 147.51 39.273 K Factor= 23.54 R1 147.23 2.703 0.0 308.000 24.702 to 120.0 0.0 0.0 0.0 R2 147.23 0.0520 0.0 308.000 16.028 Vel = 8.23 0.0 147.23 40.730 K Factor= 23.0.7 R11 105.08 2.703 2T 37.301 0.750 20.372 0 to 120.0 0.0 37.301 0.312 C6 105.08 0.0279 0.0 38.051 1.061 Vel = 5.88 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams Fire Systems West Inc. Page 6 BONITA WEARHOUSE Date 2/24/17 IFHyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn 0.0 105.08 21.745 K Factor= 22.53 R9 104.58 2.703 2T 37.301 1.000 20.316 to 120.0 0.0 37.301 0.398 C5 104.58 0.0277 0.0 38.301 1.060 Vel = 5.85 0.0 104.58 21.774 K Factor= 22.41 R7 103.90 2.703 2T 37.301 1.160 20.341 to 120.0 0.0 37.301 0.485 C4 103.9 0.0273 0.0 38.461 1.051 Vel = 5.81 0.0 103.90 21.877 K Factor= 22.21 R5 -18.83 2.703 2T 37.301 1.340 21.567 to 120.0 0.0 37.301 0.572 C3 -18.83 -0.0012 0.0 38.641 -0.045 Vel = 1.05 0.0 -18.83 22.094 K Factor= -4.01 R3 -147.51 2.703 2T 37.301 1.500 24.494 to 120.0 0.0 37.301 0.658 iiiC2 -147.51 -0.0522 0.0 38.801 -2.026 Vel = 8.25 0.0 - -147.51 23.126 K Factor=-30.67 R1 -147.23 2.703 2T 37.301 1.680 24.702 to 120.0 0.0 37.301 10.134 - Cl -147.23 -0.0520 0.0 38.981 -2.028 Vet = 8.23 0.0 -147.23 32.808 K Factor=-25.70 C6 105.08 4.31 0.0 10.000 21.745 to 120.0 0.0 0.0 0.0 C5 105.08 0.0029 0.0 10.000 0.029 Vel = 2.31 C5 104.58 4.31 0.0 10.000 21.774 to 120.0 0.0 0.0 0.0 C4 209.66 0.0103 0.0 10.000 0.103 Vel = 4.61 C4 103.90 4.31 0.0 10.000 21.877 to 120.0 0.0 0.0 0.0 C3 313.56 0.0217 0.0 10.000 0.217 Vel = 6.90 C3 -18.82 4.31 21 19.512 33.750 22.094 to 120.0 0.0 19.512 0.0 C2 294.74 0.0194 0.0 53.262 1.032 Vel = 6.48 C2 -147.51 4.31 21 19.512 35.000 23.126 to 120.0 0.0 19.512 9.390 Cl 147.23 0.0054 0.0 54.512 0.292 Vet = 3.24 0.0 147.23 32.808 K Factor= 25.70 R12 193.79 2.703 2J 33.571 0.750 36.274 0 to 120.0 0.0 33.571 0.312 M6 193.79 0.0865 0.0 34.321 2.970 Vel = 10.83 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams Fire Systems West Inc. Page 7 BONITA WEARHOUSE Date 2/24/17 WHyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn 0.0 193.79 39.556 K Factor= 30.81 R10 193.93 2.703 2J 33.571 1.000 36.251 to 120.0 0.0 33.571 0.398 M5 193.93 0.0867 0.0 34.571 2.996 Vel = 10.84 0.0 193.93 39.645 K Factor= 30.80 R8 194.89 2.703 2J 33.571 1.160 36.445 to 120.0 0.0 33.571 0.485 M4 194.89 0.0874 0.0 34.731 3.037 Vel = 10.90 0.0 194.89 39.967 K Factor= 30.83 R6 175.75 2.703 2J 33.571 1.340 37.558 to 120.0 0.0 33.571 0.572 M3 175.75 0.0722 0.0 34.911 2.520 Vel = 9.83 0.0 175.75 40.650 K Factor= 27.57 R4 147.51 2.703 2J 33.571 1.500 39.273 to 120.0 0.0 33.571 0.658 0 M2 147.51 0.0522 0.0 35.071 1.832 Vel = 8.25 0.0 - 147.51 41.763 K Factor= 22.83 R2 147.23 2.703 2J 33.571 1.680 40.730 to 120.0 0.0 33.571 0.745 - M1 147.23 0.0521 0.0 35.251 1.835 Vel = 8.23 0.0 147.23 43.310 K Factor= 22.37 M6 193.79 4.31 0.0 10.000 39.556 to 120.0 0.0 0.0 0.0 M5 193.79 0.0089 0.0 10.000 0.089 Vel = 4.26 M5 193.93 4.31 0.0 10.000 39.645 to 120.0 0.0 0.0 0.0 M4 387.72 0.0322 0.0 10.000 0.322 Vel = 8.53 M4 194.89 4.31 0.0 10.000 39.967 to 120.0 0.0 0.0 0.0 M3 582.61 0.0683 0.0 10.000 0.683 Vel = 12.81 M3 175.75 4.31 0.0 10.000 40.650 to 120.0 0.0 0.0 0.0 M2 758.36 0.1113 0.0 10.000 1.113 Vel = 16.68 M2 147.50 4.31 0.0 10.000 41.763 to 120.0 0.0 0.0 0.0 M1 905.86 0.1547 0.0 10.000 1.547 Vel = 19.92 M1 147.23 4.31 I 9.756 92.000 43.310 to 120.0 0.0 9.756 0.0 M 1053.09 0.2043 0.0 101.756 20.790 Vel = 23.16 411 M 0.0 6.357 21 25.147 212.000 64.100 to 120.0 2J 62.867 88.014 0.0 - TOR 1053.09 0.0308 0.0 300.014 9.237 Vel = 10.65 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams Fire Systems West Inc. Page 8 ighBONITA WEARHOUSE Date 2/24/17 111. Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ****"** Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn TOR 0.0 6.357 I 12.573 15.000 73.337 to 120.0 J 31.433 44.006 7.358 ** Fixed Loss = 1 BF1 1053.09 0.0308 Fsp 0.0 59.006 1.817 Vel = 10.65 BF1 0.0 6.357 Zce 0.0 3.000 82.512 to 120.0 0.0 0.0 9.449 ** Fixed Loss =6.85 BF2 1053.09 0.0307 0.0 3.000 0.092 Vel = 10.65 BF2 0.0 6.357 0.0 2.000 92.053 to 120.0 0.0 0.0 1.732 BOR 1053.09 0.0310 0.0 2.000 0.062 Vel = 10.65 BOR 0.0 8.27 2E 42.809 50.000 93.847 to 120.0 T 41.62 84.429 -1.949 TEST 1053.09 0.0085 0.0 134.429 1.14.9 Vel = 6.29 500.00 Qa = 500.00 1553.09 93.047 K Factor= 161.01 • • Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Tol-Brace Seismic Calculations FIRE SYSTEMS WEST •Project Address: BONITA WAREHOUSE 600 SE MARITIME AVE.#300 B-Line VANCOUVER,WA 98661 - 6777 SW BONITA 360-693-9901 by F,1 T.N TIGARD, OR OR:49732 WA: FIRESWI140F Job#1-11-1460 Calculations based on 2013 NFPA Pamphlet#13 Brace Information Tolco Brace Components Maximum Spacing 30'0"(9.14 m) Tolco Component Fig. Number Adjusted Load Maximum Brace Length 7'0"(2.13 m) Fig. 1001 Clamp 1425 lbs(646 kg) Bracing Material 1"SCh.40 Fig.980 Universal Swivel 1425 lbs(646 kg) *Calculation Based on CONCENTRIC Loading Angle from Vertical 45° Min. *Please Note:These calculations are for Tolco components only. Use of any other components voids these calculations and the listing of the assembly. Least Rad.of Gyration 0.42"(11 mm) Assembly Detail LIR Value 200 Max Horizontal Load 1310 lbs(594 kg) TOLCO FIG. 98 II UNIVERSAL SWAY BRACE Force Factor(Cp) 0.5 ATTACHMENT . O STEEL PIPE ee*/ Fastener InfIIIormation ,, , Fastener Orientation NFPA Type H .,..,;,4':,),,./ de.,/, Maximum Load 405 lbs(184 kg) $, f4 Diameter 5/8in. TOLCO FIG. 1001 FAST CLAMP '4 Length 3-1/2in. �♦4 Type Through-Bolt Brace Identification on Plans 6"-LAT Orientation of Brace Lateral Braced Pipe:6"Sch.10 Steel Pipe Load Information Size and Type of Pipe Total Length Total Calculated Load 6"Sch.10 Steel Pipe(152.4 mm) 30ft(9.1 m) 345 lbs(156 kg) • Percentage added for Fittings and Sprinklers 15% 52 lbs(23.59 kg) - Total Adjusted Load of all pipe within Zone of Influence 397 lbs(180 kg) {Tol-Brace Verizon 8} Tol-Brace Seismic Calculations 1111/ BONITA WAREHOUSE Job#1-11-1460 B Line 6777 SW BONITA t, Brace Identification 6" - LAT by E„"r!N Brace Type(Per NFPA#13) NFPA Type H Braced Pipe 6"Sch.10 Steel Pipe Spacing of Brace 30'0" (9.14 m) Orientation of Brace Lateral Bracing Material 1"Sch.40 Maximum Brace Length 7'0" (2.13 m) Slenderness Ratio used for Load Calculation 200 True Angle of Brace for Calculation 45° Type of Fastener 5/8in.x 3-1/2in.Through-Bolt Length of Fastener 3-1/2in. Summary of Pipe within Zone of Influence 6"Sch.10 Steel Pipe(152.4 mm) 1 30ft(9.1 m) • Allowance for Heads and Fittings 15% Conclusions Total Adjusted Load of Pipe in Zone of Influence 397 lbs(180 kg) Material Capacity 1310 lbs(594 kg) Fastener Capacity 405 lbs(184 kg) Fig. 1001 Clamp 1425 lbs(646 kg) Fig.980 Universal Swivel 1425 lbs(646 kg) Structural Member Wood Joists Calculations prepared by J.CHAPMAN • `The description of the Structural Member is for informational purposes only. Tal-Brace software calculates the brace assembly only,not the structure it is attached to. Calculated with Tol-Brace 8 Visit us at www.tolco.com Tol-Brace Seismic Calculations FIRE SYSTEMS WEST 4Project Address: BONITA WAREHOUSE 600 SE MARITIME AVE.#300 B-Li ne VANCOUVER,WA 98661 - 6777 SW BONITA 360-693-9901 by E• r*(41 TIGARD,OR OR:49732 WA: FIRESWI140E Job#1-11-1460 Calculations based on 2013 NFPA Pamphlet#13 Brace Information Tolco Brace Components Maximum Spacing 40'0"(12.19 m) Tolco Component Fig. Number Adjusted Load Maximum Brace Length 7'0"(2.13 m) Fig. 1001 Clamp 1131 lbs(513 kg) Bracing Material 1"Sch.40 Fig.980 Universal Swivel 1425 lbs(646 kg) 450 Min. 'Calculation Based on CONCENTRIC Loading Angle from VerticalPlease Note:These calculations are for Tolco components only.Use of any other components voids these calculations and the listing of the assembly. Least Rad.of Gyration 0.42"(11 mm) Assembly Detail L/R Value 200 1310 lbs(594 kg) TOLCO FIG. 980 Max Horizontal Load __. UNIVERSAL SWAY BRACE ATTACHMENT Force Factor(Cp) 0.5 ' STEEL PIPE .es IIIFastener Information Fastener Orientation NFPA Type E ,xl Maximum Load • o + /•. 350 lbs(159 kg).. .., P® 4. Diameter 1/2in. TOLCO FIG. 1001 •.. Length 3-1/2in. FAST CLAMP 4♦* Type Through-Bolt Brace Identification on Plans 4"-LAT Orientation of Brace Lateral Braced Pipe:4"Sch.7 Steel Pipe Load Information Size and Type of Pipe Total Length Total Calculated Load 4"Sch.7 Steel Pipe(101.6 mm) 40ft(12.2 m) 217 lbs(98 kg) percentage added for Fittings and Sprinklers 15% 33 lbs(14.97 kg) 1 Total Adjusted Load of all pipe within Zone of Influence 250 lbs(113 kg) (Tol-Brace Verizon 8} Tol-Brace Seismic Calculations • BONITA WAREHOUSE Job#1-11-1460 B_Li ne 6777 SW BONITA T Brace Identification 4" - LAT by E t.N Brace Type(Per NFPA#13) NFPA Type E Braced Pipe 4" Sch.7 Steel Pipe Spacing of Brace 40'0" (12.19 m) Orientation of Brace Lateral Bracing Material 1" Sch.40 Maximum Brace Length 7' 0" (2.13 m) Slenderness Ratio used for Load Calculation 200 True Angle of Brace for Calculation 45° Type of Fastener 1/2in.X 3-1/2in.Through-Bolt Length of Fastener 3-1/2in. Summary of Pipe within Zone of Influence 4"Sch.7 Steel Pipe(101.6 mm) (40ft(12.2 m) I Allowance for Heads and Fittings 15% Conclusions Total Adjusted Load of Pipe in Zone of Influence 250 lbs(113 kg) Material Capacity 1310 lbs(594 kg) Fastener Capacity 350 lbs(159 kg) Fig.1001 Clamp 1131 lbs(513 kg) Fig.980 Universal Swivel 1425 lbs(646 kg) Structural Member Wood Joists Calculations prepared by J.CHAPMAN • *The description of the Structural Member is for informational purposes only. Tol-Brace software calculates the brace assembly only,not the structure it is attached to. Calculated with Tol-Brace 8 Visit us at www.tolco.com Tol-Brace Seismic Calculations FIRE SYSTEMS WEST #roject Address: BONITA WAREHOUSE 600 SE MARITIME AVE.#300 B-Li ne VANCOUVER,WA 98661 6777 SW BONITA 360-693-9901 by ,•r IT#N TIGARD, OR OR:49732 WA: FIRESWI140E Job#1-11-1460 Calculations based on 2013 NFPA Pamphlet#13 Brace Information Tolco Brace Components Maximum Spacing 30'0"(9.14 m) Tolco Component Fig. Number Adjusted Load Maximum Brace Length 7'0"(2.13 m) Fig.4L Clamp 1425 lbs(646 kg) Bracing Material 1"SCh.40 Fig.980 Universal Swivel 1425 lbs(646 kg) Angle from Vertical 45°Mill. "Calculation Based on CONCENTRIC Loading "Please Note:These calculations are for Tolco components only. Use of any other components voids these calculations and the listing of the assembly. Least Rad.of Gyration 0.42"(11 mm) Assembly Detail L/R Value 200 TOLCO FIG. 980 Max Horizontal Load 1310 lbs(594 kg) UNIVERSAL SWAY BRACE ATTACHMENT *AO Force Factor(Cp) 0.5 �* STEEL PIPE • Fastener Information Fastener Orientation NFPA Type E / '.ski TOLCO FIG. 4L Maximum Load 400 lbs 181 k PIPE CLAMP FOR GIw „g) .._,.u_._ __. SWAY BRACING;------ Diameter 5/8in. K Length 3-1/2in. JI it Type Through-Bolt Brace Identification on Plans 6"-LON Orientation of Brace Longitudinal Braced Pipe:6"Sch.10 Steel Pipe Load Information Size and Type of Pipe Total Length Total Calculated Load 6"Sch.10 Steel Pipe(152.4 mm) 30ft(9.1 m) 345 lbs(156 kg) OPercentage added for Fittings and Sprinklers 15% 52 lbs(23.59 kg) I Total Adjusted Load of all pipe within Zone of Influence 397 lbs(180 kg) {Tol-Brace Verizon 8} Tol-Brace Seismic Calculations . BONITA WAREHOUSE Job#1-11-1460 B-Line 6777 SW BONITA T Brace Identification 6" - LON by E,1 'l'N Brace Type(Per NFPA#13) NFPA Type E Braced Pipe 6"Sch.10 Steel Pipe Spacing of Brace 30'0" (9.14 m) Orientation of Brace Longitudinal Bracing Material 1"Sch.40 Maximum Brace Length 7'0" (2.13 m) Slenderness Ratio used for Load Calculation 200 True Angle of Brace for Calculation 45° Type of Fastener 5/8in.x 3-1/2in.Through-Bolt Length of Fastener 3-1/2in. Summary of Pipe within Zone of Influence 6"Sch.10 Steel Pipe(152.4 mm) 130ft(9.1 m) • Allowance for Heads and Fittings 15% Conclusions Total Adjusted Load of Pipe in Zone of Influence 397 lbs(180 kg) Material Capacity 1310 lbs(594 kg) Fastener Capacity 400 lbs(181 kg) Fig.4L Clamp 1425 lbs(646 kg) Fig.980 Universal Swivel 1425 lbs(646 kg) Structural Member Wood Joists Calculations prepared by J.CHAPMAN • "The description of the Structural Member is for informational purposes only. Tol-Brace software calculates the brace assembly only,not the structure it is attached to. Calculated with Tol-Brace 8 Visit us at www.tolco.com Tol-Brace Seismic Calculations FIRE SYSTEMS WEST um 1110Project Address: BONITA WAREHOUSE 600 SE MARITIME AVE.#300 B-Li neVANCOUVER,WA 98661 6777 SW BONITA by F T.N __. __. 360-693-9901 TIGARD, OR OR:49732 WA: FIRESWI140E Job#1-11-1460 Calculations based on 2013 NFPA Pamphlet#13 Brace Information Tolco Brace Components Maximum Spacing 60'0"(18.29 m) Tolco Component Fig. Number Adjusted Load Maximum Brace Length 7'0"(2.13 m) Fig.4L Clamp 1425 lbs(646 kg) Bracing Material 1"Sch.40 Fig.980 Universal Swivel 1425 lbs(646 kg) Angle from Vertical 45°Min. °Calculation Based on CONCENTRIC Loading "Please Note:These calculations are for Tolco components only.Use of any other components voids these calculations and the listing of the assembly. Least Rad.of Gyration 0.42"(11 mm) Assembly Detail LIR Value 200 TOLCO FIG. 980 Max Horizontal Load 1310 lbs(594 kg) UNIVERSAL SWAY BRACE ATTACHMENT 041 Force Factor(Cp) 0.5 STEEL PIPE Fastener Information • r Fastener Orientation NFPA Type E ,�, ' TOLCO FIG. 4L PIPE CLAMP FOR iG Maximum Load SWAY BRACING 400 lbs(181 k ) _ Diameter 5/bin. Length 3 1/2i n. _____J' Type Through-Bolt Brace Identification on Plans 4"-LON Orientation of Brace Longitudinal Braced Pipe:4"Sch.7 Steel Pipe Load Information Size and Type of Pipe Total Length Total Calculated Load 4"Sch.7 Steel Pipe(101.6 mm) 60ft(18.3 m) 326 lbs(148 kg) 1 ip Percentage added for Fittings and Sprinklers 15% 49 lbs(22.23 kg) - Total Adjusted Load of all pipe within Zone of Influence 375 lbs(170 kg) {Tol-Brace Verizon 8} Tol-Brace Seismic Calculations • BONITA WAREHOUSE Job#1-11-1460 B-Line 6777 SW BONITABrace Identification 4" - LON by F.lT .N Brace Type(Per NFPA#13) NFPA Type E Braced Pipe 4"Sch.7 Steel Pipe Spacing of Brace 60'0" (18.29 m) Orientation of Brace Longitudinal Bracing Material 1"Sch.40 Maximum Brace Length 7'0" (2.13 m) Slenderness Ratio used for Load Calculation 200 True Angle of Brace for Calculation 45° Type of Fastener 5/8in.x 3-1/2in.Through-Bolt Length of Fastener 3-1/2in. Summary of Pipe within Zone of Influence 4"Sch.7 Steel Pipe(101.6 mm) 160ft(18.3 m) S Allowance for Heads and Fittings 15% Conclusions Total Adjusted Load of Pipe in Zone of Influence 375 lbs(170 kg) Material Capacity 1310 lbs(594 kg) Fastener Capacity 400 lbs(181 kg) Fig.4L Clamp 1425 lbs(646 kg) Fig.980 Universal Swivel 1425 lbs(646 kg) Structural Member Wood Joists Calculations prepared by J.CHAPMAN • *The description of the Structural Member is for informational purposes only. Tol-Brace software calculates the brace assembly only,not the structure it is attached to. Calculated with Tol-Brace 8 Visit us at www.tolco.com Tol-Brace Seismic Calculations FIRE SYSTEMS WEST illroject Address: BONITA WAREHOUSE 600 SE MARITIME AVE.#300 B Li ne VANCOUVER,WA 98661 6777 SW BONITA 360-693-9901 by ,r AT.N TIGARD, OR OR:49732 WA: FIRESWI140E Job#1-11-1460 Calculations based on 2013 NFPA Pamphlet#13 Brace Information Tolco Brace Components Maximum Spacing 80'0"(24;.38 m) Tolco Component Fig. Number Adjusted Load Maximum Brace Length 7'0"(2.13 m) Fig.4L Clamp 1425 lbs(646 kg) Bracing Material 1"SCh.40 Fig.980 Universal Swivel 1425 lbs(646 kg) Angle from Vertical 45° Min. °Calculation Based on CONCENTRIC Loading `Please Note:These calculations are for Tolco components only.Use of any other components voids these calculations and the listing of the assembly. Least Rad.of Gyration 0.42"(11 mm) Assembly Detail L/R Value 200 TOLCO FIG. 980 Max Horizontal Load 1310 lbs(594 kg) UNIVERSAL SWAY BRACE ATTACHMENT �• Force Factor(Cp) 0.5 STEEL PIPE ;; i • Fastener Information • / Fastener Orientation ✓'•' NFPAType E TOLCO FIG. 4L Maximum Load 350 lbs(159 9k ) PIPE CLAMP FOR SWAY BRACING ----- • Diameter 1/2in. ' Length 3-1/2in. J Type Through-Bolt Brace Identification on Plans 2'%"-LON Orientation of Brace Longitudinal Braced Pipe:2.5"Sch.7 Steel Pipe Load Information Size and Type of Pipe Total Length Total Calculated Load 2.5"Sch.7 Steel Pipe(63.5 mm) 80ft(24.4 m) 204 lbs(93 kg) Percentage added for Fittings and Sprinklers 15% 31 lbs(14.06 kg) Total Adjusted Load of all pipe within Zone of Influence 235 lbs(107 kg) {Tol-Brace Verizon 8} Tol-Brace Seismic Calculations • BONITA WAREHOUSE Job#1-11-1460 BLjfle 6777 SW BONITA Brace Identification 21/2" - LON by E-I•N Brace Type(Per NFPA#13) NFPA Type E Braced Pipe 2.5"Sch.7 Steel Pipe Spacing of Brace 80'0" (24.38 m) Orientation of Brace Longitudinal Bracing Material 1" Sch.40 Maximum Brace Length 7' 0" (2.13 m) Slenderness Ratio used for Load Calculation 200 True Angle of Brace for Calculation 45° Type of Fastener 1/2in.X 3-1/2in.Through-Bolt Length of Fastener 3-1/2in. Summary of Pipe within Zone of Influence 2.5"Sch.7 Steel Pipe(63.5 mm) 180ft(24.4 m) • Allowance for Heads and Fittings 15% Conclusions Total Adjusted Load of Pipe in Zone of Influence 235 lbs(107 kg) Material Capacity 1310 lbs(594 kg) Fastener Capacity 350 lbs(159 kg) Fig.4L Clamp 1425 lbs(646 kg) Fig.980 Universal Swivel 1425 lbs(646 kg) Structural Member Wood Joists Calculations prepared by J.CHAPMAN The description of the Structural Member is for informational purposes only. Tol-Brace software calculates the brace assembly only,not the structure it is attached to. Calculated with Tol-Brace 8 Visit us at www.tolco.com • tLICD /Fire & Building Products - Technical Services:Tel: (800)381-9312/Fax: (800) 791-5500 Series ELO-231B — 11.2 K-factor Upright and Pendent Sprinklers Standard Response, Standard Coverage General sentative of all possible corrosive at- mospheres.Consequently,it is recom- mended - Description that the end user be consulted with respect to the suitability of these corrosion resistant coatings for any , The 11.2 K-factor, Series ELO-231 B, given corrosive environment. The ef- Standard Response, Standard Cover- fects of ambient temperature, concen- age, Upright and Pendent Sprinklers tration of chemicals,and gas/chemical (Ref. Figure 1) are automatic sprin- velocity, should be considered, as a klers of the frangible bulb type. They minimum, along with the corrosive na- p are "standard response - spray sprin- ture of the chemical to which the sprin __ klers" that produce a hemispherical klers will be exposed. water distribution pattern below the deflector. An upright intermediate level version ' +' of the Series ELO-231 B Sprinklers for • The 11.2 K-factor, ELO-231 B Sprin- in-rack applications can be obtained klers were subjected to full scale,high- by utilizing the Series ELO-231 B Up- piled storage, fire tests to qualify their right Sprinkler with the WSG-2 Guard - use in lieu of 5.6 or 8.0 K-factor stand- & Shield, and a pendent intermediate and spray sprinklers for the protection level version of the Series ELO-231 B of high-piled storage. Sprinklers can be obtained by utiliz- Higher flow rates can be achieved at ing the Series ELO 231 B Pendent much lower pressures with the 11.2 Sprinkler the WS 2 Shield. If there - , K-factor, ELO-231 B Sprinklers — is a possibility of the pendent interme t making their use highly advantageous diate level version being exposed to in high density applications, such as mechanical damage, a G-2 Guard can the protection of high-piled storage. be added. ,,- Wax or lead coatings can be used to WARNINGS extend the life of the copper alloy com- The 11.2 K-factor, Series ELO-2318 ' z ponents used in Series ELO-231 B Upright and Pendent Sprinklers de- sprinklers beyond that which would scribed herein must be installed and .®N otherwise be obtained when exposed maintained in compliance with this to corrosive atmospheres. Although document, as well as with the applica- wax, lead, and polyester coated sprin- ble standards of the National Fire Pro- klers have passed the standard corro- Lection Association, in addition to the sion tests of the applicable approval standards of any other authorities hav- agencies, the testing is not repre- ing jurisdiction. Failure to do so may impair the performance of these de- vices. The owner is responsible for maintain- IMPORTANT ing their fire protection system and de- Always refer to Technical Data vices in proper operating condition. Sheet TFP700 for the "INSTALLER The installing contractor or manufac- WARNING" that provides cautions turer should be contacted with any with respect to handling and instal- questions. lation of sprinkler systems and com- ponents. Improper handling and in- Installation of Series ELO-2318 Pen- stallation can permanently damage dent Sprinklers in recessed escutch- a sprinkler system or its compo- eons will void all sprinkler warranties, nents and cause the sprinkler to fail as well as possibly void the sprinkler's to operate in a fire situation or cause Approvals and/or Listings. it to operate prematurely. Page 1 of 6 MARCH, 2007 TFP342 Page 2 of 6 TFP342 SPRINKLER FINISH • TYPE TEMPERATURE BULB NATURAL CHROME LEAD WAX WAX LIQUID BRASS PLATED COATED COATED OVER LEAD - UPRIGHT 155"F/68°C Red 3 (TY5151 200°F/93°C Green & 1,2,3,4 TY5851) 286°F/141°C Blue 3 3(a) 155°F/68°C Red 3 PENDENT 200°F/93°C Green (TY5251 1,2,3,4 286°F/141°C Blue 3 3(a) NOTES: 1. Listed by Underwriters Laboratories, Inc. (UL Listed). 2. Listed by Underwriters Laboratories, Inc.for use in Canada(C-UL Listed). 3. Approved by Factory Mutual Research Corporation (FM Approved). 4. Approved by the City of New York under MEA 291-04-E. (a). FM Approved for a maximum ceiling temperature of 150°F/66°C. TABLE A LABORATORY LISTINGS AND APPROVALS FOR 11.2 K-FACTOR SERIES ELO-231B UPRIGHT AND PENDENT SPRINKLERS (Refer to the Design Criteria Section) Model/Sprinkler Technical Design Criteria • Identification Data UL and C-UL Listing Requirements A rovals The 11.2 K-factor, Model ELO-231B Numbers UL and C-UL Listed. FM and NYC Ap- (TY5151, TY5251 & TY5851) Sprin- TY5151 -Upright 11.2K, 3/4"NPT proved. (Refer to Table A for complete klers are to be installed in accordance TY5251 -Pendent 11.2K, 3/4"NPT approval information including corro- with NFPA 13 standard sprinkler posi- TY5851 -Upright 11.2K, 1/2"NPT sion resistant status. The approvals tion and area/density flow calculation TY5151 is a redesignation for C5151. apply to the service conditions indi requirements for light, ordinary, or ex- cated in the Design Criteria section.) tra hazard occupancies, as well as TY5251 is a redesignation for C5251, Maximum Working Pressure high piled storage occupancies (solid G1871, and S2531. 175 psi (12,1 bar) piled,palletized, rack storage,bin box, TY5851 is a redesignation for C5851. Discharge Coefficient and shelf storage including but not lim- s 11.2 GPM/psi-I/2 ited to Class I-IV and Group A plastics) K61,4 2 GPM/p� 1 with a minimum residual (flowing) pressure of 7 psi (0,5 bar) for wet or Temperature Ratings dry pipe systems. Refer to Table A Finishes FM Approval Refer to Table A Requirements Physical Characteristics The 11.2 K-factor, Model ELO-231B y (TY5151, TY5251 & TY5851) Sprin- Frame Bronze klers are to be installed in accordance Cap Bronze with the applicable"control mode den- Sealing Assembly sity/area" guidelines provided by Fac- Beryllium Nickel w/Teflont tory Mutual. (FM guidelines may differ Bulb(5 mm dia.) Glass from UL and C-UL Listing criteria.) Compression Screw Bronze Deflector Bronze t Registered trademark of DuPont. • TFP342 Page 3 of 6 • *Temperature rating is indicated on deflector. **Pipe thread connections per ISO 7/1 can be provided on 1/2"(12,7 mm) - special request. r NOMINAL MAKE-IN I 3/4"** 7 e 1 f = NPT Components: f /Wl 1�7-7TITY ltT /I/lTT1-1Y 1T 1--• .-=-- 2 1 -2 - Frame 2-13/16" 3 ln , (71,4 mm) I WRENCH THREAD 3 - Capel mbly TYP. FLATS RELIEF (1110044 4 4 - Bulb /' �, 5 - Compression ti46 5 O." Screw 1/2"** ---- la 3/4"** 6 - Deflector* NPT NPT • 6 L 7/16"(11,1 mm) L 1/2"(12,7 mm) NOMINAL MAKE-IN NOMINAL MAKE-IN UPRIGHT UPRIGHT PENDENT CROSS TY5851 TY5151 TY5251 SECTION FIGURE 1 11.2 K-FACTOR SERIES ELO-231B UPRIGHT-3/4"NPT(TY5151), UPRIGHT- 1/2"NPT(TY5851),AND PENDENT-3/4"NPT(TY5251)SPRINKLERS Operation Installation "FITTING SIDE" TOWARDS SPRINKLER 0 The glass bulb contains a fluid that The Series ELO-231B Sprinklers must FITTING expands when exposed to heat.When be installed in accordance with the fol- the rated temperature is reached, the lowing instructions: - fluid expands sufficiently to shatter the / ' WRENCH glass bulb, allowing the sprinkler to NOTES activate and water to flow. Do not install any bulb type sprinkler ifthe bulb is cracked or there is a loss of liquid from the bulb. With the sprinklerRECESS held horizontally, a small air bubble should be present. The diameter of the . (END"A") air bubble is approximately 1/16 inch (1,6 mm) for the 155°F/68°C to 3/32 FIGURE 2 inch (2,4 mm) for the 286°F/141°C W-TYPE 3 SPRINKLER temperature ratings. WRENCH A leak tight 3/4 inch NPT sprinkler joint should be obtained with a torque of 10 to 20 ft.lbs. (13,4 to 26,8 Nm).A maxi- installed in the pendent position, and mum of 30 ft.lbs. (40,7 Nm) of torque upright sprinklers are to be installed in is to be used to install sprinklers with the upright position. 3/4 NPT connections. A leak tight 1/2 Step 2. With pipe thread sealant ap- inch NPT sprinkler joint should be ob- plied to the pipe threads, hand tighten tained with a torque of 7 to 14 ft.lbs. the sprinkler into the sprinkler fitting. (9,5 to 19,0 Nm). A maximum of 21 ft. Step 3. Tighten the sprinkler into the lbs. (28,5 Nm)of torque may be used to install sprinklers with 1/2 NPT con- sprinkler fitting using only the W-Type nections. Higher levels of torque may 3 Sprinkler Wrench (Ref. Figure 2), distort the sprinkler inlet and cause except that an 8 or 10 inch adjustable leakage or impairment of the sprinkler. Crescent wrench is to be used for wax coated sprinklers. With reference to Do not attempt to make-up for insuffi- Figure 1, the W-Type 3 Sprinkler dent adjustment in the escutcheon Wrench or the adjustable Crescent plate by under- or over-tightening the wrench, as applicable is to be applied sprinkler. Readjust the position of the to the wrench flats. 4111 sprinkler fitting to suit. When installing wax coated sprinklers The Series ELO-231B Upright and with the adjustable Crescent wrench, - Pendent Sprinklers must be installed additional care needs to be exercised in accordance with the following in- to prevent damage to the wax coating structions. on the sprinkler wrench flats or frame - Step 1. Pendent sprinklers are to be arms and, consequently, exposure of Page 4 of 6 TFP342 bare metal to the corrosive environ- It is recommended that automatic • ment. The jaws of the wrench should Care and sprinkler systems be inspected, be opened sufficiently wide to passtested, and maintained by a qualified over the wrench flats without damag- Maintenance Inspection Service in accordance with ing the wax coating. Before wrench local requirements and/or national tightening the sprinkler,the jaws of the Series ELO-231B Sprinklers must be code. wrench are to be adjusted to just con- maintained and serviced in accord- _ tact the sprinkler wrench flats. After ance with the following instructions: Limited wrench tightening the sprinkler,loosen the wrench jaws before removing the NOTES wrench. Before closing a fire protection system Warranty control valve for maintenance work on After installation, the sprinkler wrench the fire protection system that it con- Products manufactured by Tyco Fire& flats and frame arms must be in- trols, permission to shut down the af- Building Products (TFBP) are war- spected and the wax coating re- fected fire protection system must be ranted solely to the original Buyer for touched(repaired)whenever the coat- obtained from the proper authorities ten (10)years against defects in mate- ing has been damaged and bare metal and all personnel who may be affected rial and workmanship when paid for is exposed. The wax coating on the by this action must be notified. and properly installed and maintained wrench flats can be retouched by gen- under normal use and service. This tly applying a heated 1/8 inch diameter Sprinklers that are found to be leaking warranty will expire ten (10) years steel rod to the areas of wax that have or exhibiting visible signs of corrosion from date of shipment by TFBP. No been damaged,to smooth it back over must be replaced. warranty is given for products or com- areas where bare metal is exposed. Automatic sprinklers must never be ponents manufactured by companies NOTES painted, plated, coated or otherwise not affiliated by ownership with TFBP Only of the wax coating ap- altered after leaving the factory. Modi- or for products and components which Only retouchingto the flats and fied sprinklers must be replaced. have been subject to misuse,improper armsplied is permitted,wrenched, and the andretoframeae Sprinklers that have been exposed to installation, corrosion, or which have ise performed ed only at time of corrosive products of combustion, but not been installed, maintained, modi- sto initial sprinklerominstallation.the have not operated,should be replaced fied or repaired in accordance with ap- theif they cannot be completely cleaned plicable Standards of the National Fire The steel rod should be heated only to by wiping the sprinkler with a cloth or Protection Association, and/or the the point at which it can begin to melt by brushing it with a soft bristle brush. standards of any other Authorities • the wax, and appropriate precautionsHaving Jurisdiction. Materials found need to be taken, when handlingthe Care must be exercised to avoid dam- by TFBP to be defective shall be either heated rod, in order to prethe age to the sprinklers—before,during, repaired or replaced, at TFBP's sole and after installation. Sprinklers dam- option. TFBP neither assumes, nor installer from being burned. aged by dropping, striking, wrench authorizes any person to assume for it, If attempts to retouch the wax coating twist/slippage, or the like, must be re- any other obligation in connection with with complete coverage are unsuc- placed.Also,replace any sprinkler that the sale of products or parts of prod- cessful,additional wax can be ordered has a cracked bulb or that has lost ucts.TFBP shall not be responsible for in the form of a wax stick (the end of liquid from its bulb (ref. Installation sprinkler system design errors or inac- which is color coded). Only the correct Section Note). curate or incomplete information sup- color coded wax is to be used, and Frequent visual inspections are rec- plied by Buyer or Buyer's repre- retouching of wrench flats and frame ommended to be initially performed for sentatives. arms is only permitted at the time of corrosion resistant sprinklers,after the In no event shall TFBP be liable, in initial sprinkler installation. With the installation has been completed, to steel rod heated as previously de- contract, tort, strict liability or under scribed, touch the rod to the area re- verify the long term potential integrity any other legal theory, for incidental, of the sprinkler coatings. Thereafter, indirect,special or consequential quiring additional wax with the rod an- p dam- annual inspections per NFPA 25 ages, includingbut not limited to labor gled downward, and then touch the should suffice; however, instead of in- g wax stick to the rod approximately charges, regardless of whether TFBP pp y specting from the floor level,a random was informed about the possibilityof one-half inch away from the area re- sampling of close-up visual inspec- quiring retouching. The wax will melttions shouldsuch damages, and in no event shall and run down onto the sprinkler. be made, so as to better TFBP's liability exceed an amount determine the exact sprinkler condi- equal to the sales price. tion and the long term integrity of the corrosion resistant coating, as it may The foregoing warranty is made in lieu be affected by the corrosive conditions of any and all other warranties. ex- present. press or implied. including warranties The owner is responsible for the in- of merchantability and fitness for a par- spection, testing, and maintenance of ticular purpose. their fire protection system and de- This limited warranty sets forth the ex- vices in compliance with this docu- clusive remedy for claims based on ment, as well as with the applicable failure of or defect in products, materi- standards of the National Fire Protec- als or components, whether the claim • tion Association (e.g., NFPA 25), in is made in contract, tort, strict liability addition to the standards of any other or any other legal theory. authorities having jurisdiction. The in- - stalling contractor or sprinkler manu- facturer should be contacted relative to any questions. TFP342 Page 5 of 6 Ordering P/N 50 - XXX - X - XXX Procedure I A Part Number (P/N) is not specified when ordering sprinklers with thread connections per ISO 7/1. Contact your local distributor for avail- SPRINKLER ability. TEMPERATURE TYPE 1 NATURAL BRASS RATING Sprinkler Assemblies with NPT Thread Connection: 510 UPRIGHT 9 CHROME PLATED 155 155°F/68°C Specify: (specify SIN), 11.2 K-factor, 3/4"NPT (specify temperature rating), Series (TY5151) 6 WAX COATED 200 200°F/93°C ELO-231B Standard Response (spec- ify Pendent or Upright) Sprinkler with 512 PENDENT 7 LEAD COATED 286 286°F/141°C (specify finish), P/N (specify from Ta- 3/4"NPT ble B). (TY5251) 8 WAX OVER LEAD Sprinkler Wrench: 501 UPRIGHT Specify: W-Type 3 Sprinkler Wrench, 1/2"NPT P/N 56-895-1-001. (TY5851) Wax Sticks: TABLE B (for retouching wrench damaged PRODUCT SYMBOL NUMBER SELECTION wax coating) 11.2 K-FACTOR SERIES ELO-231B Specify: (Specify color) color coded STANDARD RESPONSE UPRIGHT AND PENDENT SPRINKLERS Wax Stick for retouching (specify tem- perature rating)temperature rated Se- ries ELO-231B Sprinklers, P/N (spec- S if y). Red for 155°F P/N 56-065-1-155 Blue for 200°F and 286°F P/N 56-065-1-286 NOTES Each wax stick is suitable for retouch- ing up to twenty-five sprinklers. The wax used for 286°F sprinklers is the same as for 200°F sprinklers, and, therefore, the 286°F sprinkler is limited to the same maximum ceiling tempera- ture as the 200°F sprinkler (i.e., 150°F). Page 6 of 6 TFP342 • _ • • TYCO FIRE&BUILDING PRODUCTS,451 North Cannon Avenue,Lansdale,Pennsylvania 19446 1111 tqcc, /Fire & Building Products Technical Services: Tel: (800) 381-9312/ Fax: (800)791-5500 Tyco Fire Products Model CV-IF Check Valve General NOTICE The Model CV-1F Check Valve de- Description scribed herein must be installed and i it III I maintained in compliance with this The Tyco®Model CV-1F Check Valve is document and with the applicable a compact and rugged swing-type unit standards of the National Fire Pro- that allows water flow in one direction tection Association, in addition to the l and prevents flow in the opposite di- standards of any authorities having ju • rection. A resilient elastomer seal fac- risdiction. Failure to do so may impair ing on the spring loaded clapper en- the performance of this device. 1 r as sures a leak tight seal and non-sticking ,. operation. The Model CV-1F Check The owner is responsible for maintain- " Valves are designed to minimize water ing their fire protection system and de . , hammer caused by flow reversal. vices in proper operating condition. %` •, The installing contractor or manufac- 0 The CV-1 F is furnished with grooved turer should be contacted with any ends and can be installed using questions. Grinnell®Grooved Couplings or Grin- - nell Figure 71 Flange Adapters. The Technical Model CV-1F Check Valves have been Care and designed with a removable cover for Data ease of field maintenance. Valves in- Maintenance stalled horizontally or inclined (flow up Sizes-Inches/DN or down) are to be positioned with the 2 to 12/DN50 to DN300 The owner is responsible for the in- cover facing up. Valves installed verti- spection, testing, and maintenance of cally may be positioned with flow up or Maximum Working Pressure their fire protection system and devic- down. 300 psi (20,7 bar) es in compliance with this document, A Maintenance Check Valve Kit Approvals as well as with the applicable stan- (TFP1555) is available to allow the UL, FM,and C-UL. dards of the National Fire Protection maintenance procedure of backflush- Protective Coating Association(e.g., NFPA 25),in addition to the standards of any authority hav- ing through the fire department con- Valve assembly ing jurisdiction. The installing contrac- nection without removing the Model • Non-lead paint tor or product manufacturer should be CV-1 F Check Valve from the pipe line. contacted relative to any questions. The Model CV-1F Check Valves are a Installation Any impairments must be immediately redesignation for the Central Figure corrected. 590F and Grinnell Figure 590F. The Model CV-1F Check Valves are to be installed in accordance with the fol- Automatic sprinkler systems should be lowing instructions: inspected,tested, and maintained by a qualified Inspection Service in accor- Step 1. The arrow cast on the Body dance with local requirements and/or must point in the direction of the flow. national codes. Step 2. Valves installed vertically After placing a fire protection system may be positioned with the flow up or in service, notify the proper authorities down. and advise those responsible for mon- Step 3. Valves installed horizontally itoring proprietary and/or central sta- or inclined (flow up or down)are to be tion alarms. 1110 positioned with the Cover facing up. Step 4. Grooved end pipe couplings used with the CV-1F must be installed in accordance with manufacturer's instructions. Page 1 of 4 JULY, 2008 TFP1550 Page 2 of 4 TFP1550 • B - A - ■■ ■■ .1.1 11•111 riima f . , I ► ISMI IIO ... O.D. D liii1 �_ 1/2" — — NPT 1/2" NPTj -...— E E - F Nominal Pipe Size Nominal Dimensions-Inches(mm) Cover Approx. ANSI O.D. Bolt Torq. Weight Lbs.-ft. Lbs. Inches Inches A B C D E F J (Nm) (kg) DN (mm) 2 2.375 6.75 4.38 2.55 2.57 3.25 4.75 1.62 18 9.0 DN50 (60,3) (171,5) (111,3) (64,8) (65,3) (82,3) (120,7) (41,5) (25) (4,5) • 21/2 2.875 8.00 5.80 3.41 3.40 3.88 6.00 1.70 39 10.0 DN65 (73,0) (203,2) (147,3) (86,6) (86,4) (98,6) (152,4) (43,2) (54) (4,5) - - 8.00 5.80 3.41 3.40 3.88 6.00 1.70 39 10.00 DN65 (76,1) (203,2) (147,3) (86,6) (86,4) (98,6) (152,4) (43,2) (54) (4,5) 3 3.500 8.37 5.76 3.60 3.40 3.88 6.00 1.70 39 11.0 DN80 (88,9) (212,6) (146,3) (91,4) (86,4) (98,6) (152,4) (43,2) (54) (5,0) 4 4.500 9.63 6.74 4.61 3.63 4.56 7.13 1.84 50 25.0 DN100 (114,3) (244,6) (171,2) (117,1) (92,2) (115,1) (181,1) (46,7) (69) (11.3) - - 10.50 7.50 5.29 4.20 4.90 7.60 1.90 39 29.0 DN125 (139,7) (266,7) (190,5) (134,4) (106,7) (124,5) (193,0) (48,3) (54) (13.2) 5 5.563 10.50 7.50 5.29 4.20 4.90 7.60 1.90 39 29.0 DN125 (141,3) (266,7) (190,5) (134,4) (106,7) (124,5) (193,0) (48,3) (54) (13,2) - - 11.50 8.05 5.75 4.50 5.00 7.60 1.48 60 47.0 DN150 (165,1) (292,1) (204,5) (146,1) (114,3) (127,0) (193,0) (37,6) (82) (21,3) 6 6.625 11.50 8.05 5.75 4.50 5.00 7.60 1.48 60 47.0 DN150 (168,3) (292,1) (204,5) (146,1) (114,3) (127,0) (193,0) (37,6) (82) (21,3) 8 8.625 14.00 10.25 7.75 5.62 5.45 8.40 2.20 120 66.0 DN200 (219,1) (355,6) (260,4) (196,9) (142,7) (138,4) (213,4) (58,9) (164) (29,9) 10 10.750 18.00 13.00 10.21 6.38 7.50 10.50 3.00 130 109.7 DN250 (273,1) (457,2) (330,2) (259,3) (162.1) (190.5) (266,7) (76,2) (178) (49,4) 12 12.750 21.00 14.28 11.31 7.26 7.62 10.62 2.75 130 151.0 DN300 (323,9) (533,4) (362,7) (287,2) (184,4) (193,5) (269,7) (69.9) (178) (68,0) FIGURE 2 NOMINAL DIMENSIONS MODEL CV-1F CHECK VALVES • TFP1550 Page 3 of 4 • 8 8 - 4,16 18 17 9 IIIru'uulllllllll l '��!I� 5 111ll1I""")16I II11 ■■ ■■ 2 SEE -.. .�- -_ VIEW A ��%�//�� 2 7 9 2 7 5 rim-il 3 v>f R I, ■ 2"-8" 10" 12" �`` r\ mil (DN50 DN200) (DN250-DN300) pk %MIgi\�� r 1la�`\\�`��� VIEW A 13 I ' I D CI SEE 5 13 A111,16 DETAILB 11 1E141 14,16 mks ' „N c► 12 r_ / 6 1 4 . m \\\\\����` 15 2"-8" 5 10"-12" 6 (DN50-DN200) (DN250-DN300) DETAIL B Detail Part Material Qty. Detail Part Material Qty. Detail Part Material Qty. Clapper EPDM Retaining Stainless 1 Body Ductile Iron 1 6 Facing Grade"E" 1 13 Disc Steel 1 2 Cover Ductile Iron 1 7 Spring Stainless 1 14 Locknut Stainless 1 Steel Steel Cover Hinge Stainless Plug-Y2"- 3 Gasket Nitrile Rubber 1 8 Shaft Steel 1 15 14 NPT Cast Iron 2 Hex Cap Steel,Zinc Retaining Stainless Thread 4 Screw Plated AR 9 Ring Steel AR 16 Adhesive Sealer AR Clapper Stainless Retention Stainless 2"-8" Steel 11 Bolt Steel 1 17 Nameplate Aluminum 1 5 1 IIIClapper 10"- 12" Ductile Iron 12 Seal Ring Neoprene 1 18 Rivet Steel 2 - FIGURE 2 MODEL CV-1F CHECK VALVES FLOW RATE IN LITRES PER MINUTE(LPM) (1 GPM=3,785 LPM) 500 700 1000 2000 3000 5000 7000 10000 20000 30000 50000 5.0 Il I I I1lI II I I �� I I I I I LII l 1 LII I I'I') rill I I Ii) I I [ I 1 I l i t I III II t_ _��.. -�� 0,30 4.0 O, coh ����� w O cc = 3.0 =G� =V; O`er ,s, AM, 0,20 m Z h Z N �ry� �C� �O ,.<l o� _ Z W N� U� `O ^� _ a: cc— _ Ill cc cc2.0A-- MOW/ . . O m Q � U•V U� 'c. CV 0)0 LO co CO o ��iiiii h UZ O� �� t co CC Cr) -�01WA ry oo• `0,10 c) o a ¢ -�11■I ,UZ 2 c+� to II � w -�IIL 2 `O = 0,09 cn u a a -�1IIM__ v V� - `0,08 ¢ u, g Cr) 1.0 �A■=� '' AMIIIIIIM UT _ -0,07 Q a O 0 0.9 AIIUI �- ..`ti _-0 06 Z z 0 0.8 �nMMM 2 ? 0.7 - - -0,05 z 0.6 IIV - 0,04 - 0.5 100 200 300 400 600 1000 2000 3000 4000 6000 10000 15000 • FLOW RATE IN GALLONS PER MINUTE(GPM) FIGURE 3 MODEL CV-1F PRESSURE LOSS DATA Page 4 of 4 TFP1550 Limited Ordering • Warranty Procedure - Products manufactured by Tyco Fire The Model CV-1F Check Valves: & Building Products (TFBP) are war- Specify: (specify size) Model CV-1F _ ranted solely to the original Buyer for Check Valve, P/N (specify) ten (10)years against defects in mate- rial and workmanship when paid for 2"(DN50)Valves 59-590-0-020 and properly installed and maintained 2-1/2"(DN65)Valves 59-590-0-025 under normal use and service. This DN65(76,1mm)Valves 59-590-0-076 4"(DN0)Valves 59-590-0-030 warranty will expire ten(10)years from 4"(DN100) Valves 59-590-0-040 date of shipment by TFBP. No warran- DN125(139,7)Valves 59-590-0-139 ty is given for products or components s'°(DN125)Valves 59-590-0-050 manufactured by companies not af- DN150(165,1)Valves 59-590-0-165 filiated by ownership with TFBP or for 6"(DN150)Valves 59-590-0-060 products and components which have 8"(DN200)Valves 59-590-0-080 been subject to misuse, improper in- 10"(DN250)Valves 59-590-0-100 stallation, corrosion, or which have not 12"(DN300)Valves 59-590-0-120 been installed,maintained,modified or Replacement Valve Parts repaired in accordance with applicable Specify: (specify description) for use Standards of the National Fire Protec- with (specify size) Model CV-1 F Check tion Association, and/or the standards Valve, P/N (specify) of any other Authorities Having Juris- 2"(DN50)Valves diction. Materials found by TFBP to be Cover Gasket 976-705-01 defective shall be either repaired or re- Clapper Facing 976-709-01 placed, at TFBP's sole option. TFBP 2-1/2"(DN65)Valves neither assumes, nor authorizes any Cover Gasket 975-618-01 person to assume for it, any other ob- Clapper Facing 975-621-01 ligation in connection with the sale of products or parts of products. TFBP 3"(DN80)Valves shall not be responsible for sprinkler Cov4111 er Gasket 975-618 01 system design errors or inaccurate or Clapper Facing 975-491-01 incomplete information supplied by 4"(DN100)Valves Buyer or Buyer's representatives. Cover Gasket 975-120-01 Clapper Facing 975-003-01 In no event shall TFBP be liable, in 5"(DN125)Valves contract, tort, strict liability or under Cover Gasket 975-120-01 any other legal theory, for incidental, Clapper Facing 975-219-01 indirect,special or consequential dam s°'(DN150)Valves ages, including but not limited to labor Cover Gasket 975-218-01 charges, regardless of whether TFBP Clapper Facing 975-006-01 was informed about the possibility of 8"(DN200)Valves such damages, and in no event shall Cover Gasket 975-479-01 TFBP's liability exceed an amount Clapper Facing 975-463-01 equal to the sales price. 10"(DN250)Valves The foregoing warranty is made in lieu Cover Gasket 976-000-01 of any and all other warranties. ex- Clapper Facing 975-977-01 press or implied, including warranties 12"(DN300)Valves of merchantability and fitness for a Cover Gasket 976-472-01 particular purpose. Clapper Facing 976-474-01 This limited warranty sets forth the ex- clusive remedy for claims based on failure of or defect in products, materi- als or components, whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full ex- tent permitted by law. The invalidity, in whole or part, of any portion of this warranty will not affect the remainder. s ©2008 TYCO FIRE&BUILDING PRODUCTS,451 North Cannon Avenue,Lansdale,Pennsylvania 19446 tyro Worldwide • Contacts www.tyco-fire.com Fire Protection Products Model BFV-N Butterfly Valve Grooved End 2-1/2 to 10 Inch (DN65 to DN250) General Technical Description Data The Model BFV-N Grooved End But- Approvals • terfly Valves(Ref. Figure 1)are indicat- UL and C-UL Listed ing type valves designed for use in fire FM Approved protection systems where a visual in- dication is required as to whether the Listed by California State Fire Marshall valve is open or closed.They are used, under Listing No. 7770-1670:100 for example, as system, sectional, and All laboratory listings and approvals are ~` pump water control valves. They have for indoor and outdoor use. V cut groove inlet and outlet connections that are suitable for use with grooved Maximum Working Pressure end pipe couplings that are listed and 2-1/2 to 8 Inch(DN65 to DN200) approved for fire protection systems. 300 psi(20,7)bar For applications requiring supervision 10 Inch(DN250) of the open position of the valve, the 175 psi(12,0 bar) SGear Operators for the Model BFV-N Materials of Construction Butterfly Valves are provided with two sets of factory installed inter- Body nal switches each having SPDT con- Ductile iron conforming to ASTM A395 tacts (Ref. Figure 3). The supervisory Body Coating switches transfer their electrical con- tacts when there is movement from y the valve's normal open position dur- Disc ing the first two revolutions of the Ductile iron conforming to ASTM A395 handwheel. Disc Seal NOTICE Grade EPDM "E" encapsulated rubber conforming to ASTM D2000 The Model BFV-N Grooved End But Upper&Lower Stem terfly Valves described herein must Type 416 Stainless Steel conformingto be installed and maintained in corn- ASTM 582 pliance with this document, as well as with the applicable standards of the Lower Plug National Fire Protection Association,in PVC addition to the standards of any other Operator authorities having jurisdiction. Failure Gear operator with iron housing to do so may impair the performance p of these devices. The owner is responsible for main- taining their fire protection system and devices in proper operating con- dition. Contact the installing contrac- tor or product manufacturer with any questions. • Page 1 of 4 JANUARY 2015 TFP151O TFP1510 Page 2 of 4 Nominal Nominal Installation Dimensions • Valve PipeOD Inches(mm) Weight Sizes Lbs. - Inches Inch (mm) A B C D E F G H (kg) 2-1/2 2.88 3.85 11.94 3.25 5.67 5.90 5.82 2.13 0 22 - (65) (73,0) (98,0) (303,3) (83,0) (144,0) (149,9) (147,8) (54,1) (10,0) 3 3.50 3.85 12.48 3.54 5.94 5.90 5.82 2.130 23 (80) (88,9) (98,0) (317,0) (90,0) (150,9) (149,9) (147,8) (54,1) (10,4) 4 4.50 4.56 14.18 4.35 6.31 5.90 7.64 2.13 28 (100) (114,3) (116,0) (360,2) (110,0) (160,3) (149,9) (194,1) (54,1) 0 (12,7) 5 5.56 5.86 15.17 4.84 7.32 5.90 7.64 2.13 31 (125) (141,3) (149,0) (385,3) (123,0) (185,9) (149,9) (194,1) (54,1) 0 (14,1) 6 6.63 5.86 17.54 5.93 8.62 5.90 7.64 2.13 0.67 41 (150) (168,3) (149,0) (445,5) (151,0) (218,9) (149,9) (194,1) (54,1) (17,0) (18,6) 8 8.63 5.26 19.42 6.87 9.80 9.80 7.91 2.13 5.86 53 (200) (219,1) (134,0) (493,3) (174,0) (248,9) (248,9) (200,9) (54,1) (148,8) (24,1) 10 10.75 6.29 24.03 9.17 11.61 18.00 9.49 3.03 7.41 88 (250) (273,1) (160,0) (610,4) (233,0) (294,9) (457,2) (241,0) (77,0) (188,2) (40,0) INDICATOR -- G - F - HANDWHEEL FLAG 1/2"NPT CONDUIT 01 I >._:_._ ji ..zCNDUIT GEAR ��= E @OD OPERATOR , BODY u B — -,_I • D + `4j H hr_DISC �_ i C ` _.... A__ ..._■ A--- FIGURE 1 MODEL BFV-N GROOVED END BUTTERFLY VALVE NOMINAL DIMENSIONS Installation switch is intended for connection to the supervisory circuit of a fire alarm The Model BFV-N Grooved End But- control panel in accordance with NFPA terfly Valves may be installed with flow 72.The auxiliary switch is intended for in either direction and can be posi- the unsupervised connection to aux- .01-4111,0L.., tioned either horizontallyor vertically. iliary equipment in accordance withkil.:, y NFPA 70, National Electric Code. A C ! The grooved end pipe couplings used �.�� /V with the Model BFV-N must be listed NOTE: For outdoor applications with ;� P/ or approved for fire protection service internal supervisory switches, it is rec- OPEN B /';.. and installed in accordance with the ommended that wiring connections11 manufacturers instructions. be made at a temperature above 15°F (-9°C), in order to insure sufficient flex- A SHUT The Model BFV-N Butterfly Valve may ibility of the wire lead insulation. be installed with any schedule of pres- FIGURE 2 sure class of pipe or tubing that is list- Stop Adjustment MODEL BFV-N GROOVED END ed or approved for fire protection. Procedure BUTTERFLY VALVE As applicable, refer to Figure 3 for the The gear operator's OPEN and SHUT OPERATOR ADJUSTMENT internal switch wiring diagram. position have been factory set. The Step 2. Remove two lockscrews (A) • following procedure should be used if from the gear operator body. Conduit and electrical connections slight adjustments are needed. Refer are to be made in accordance with to Figure 2. Step 3. Turn the Shut Stop Screw (B) - the authority having jurisdiction and/ clockwise until snug. or the National Electrical Code. With Step 1. Turn the Handwheel until the reference to Figure 3, the supervisory valve is fully closed. Step 4. Turn the Handwheel until the valve is fully open. - TFP151O Page 3 of 4 • FLOW RATE IN LITRES PER MINUTE(LPM) (1 GPM=3,785 LPM) 300 400 600 1000 2000 4000 6000 10000 20000 40000 5.0 II II IIIII)IJF liIIIIJ I III 1 III HIM UM 7111 111 LI I III)I11_ I I I IIIDIUI_ 4.0 :. 0,30 .. 3.0 ,.-0,20 , / ' _ 2.0 - ¢a. mil 11 i �till -0,08 a < � � 1.0 QS0, o o' o��o h� _ ccm O2 o N h -do 0,06 Lo Ci) Q 0.8 = per' QZ, Q2/ :2 Q2 ,�� -0,05 D co .z, , ,z.s/ ,z, o CC A aw 0.6 ry.: 2 �V ' ZV =V $ _V :0,04 w II ¢ a 0.5 ^ ,-. � " v• ::22 h co w ao o - a m zo c1; :11.... A::: :.: _ 003 _ a O � 0.4 Zv Z 0- 0.3 =0,02 z 0.2 - - c 0,01 40 0.1 60 100 200 400 600 1000 20004000 6000 10000 15000 FLOW RATE IN GALLONS PER MINUTE(GPM) GRAPH A DN65 THROUGH DN250 MODEL BFV-N BUTTERFLY VALVE NOMINAL PRESSURE DROP VERSUS FLOW r 1 r I– SUPERVISORY • I— AUXILIARY CONTACT RATING: SWITCH GND SWITCH 1/2A @ 125 VDC • 1/4A @ 250 VDC SWITCH SHOWN SWITCH SHOWN 15.1A/12HP @ 125,250 VAC WITH VALVE WITH VALVE 5A @ 125 VAC"L" `- --- -- --- --I FULL OPEN L ' FULL OPEN w w 0 0 c7 CD z L w O O z z w -, o >- WY O O C0 5 °� m • + n • BELL END OF LINE PANEL RESISTOR POWER • + FIGURE 3 MODEL BFV-N BUTTERFLY VALVE INTERNAL SWITCH WIRING DIAGRAM WITH VALVE IN OPEN POSITION Step 5.Turn the Open Stop Screw(C) Step 7. Replace two lockscrews (A) clockwise until snug. into the gear Operator body locking Step 6. Close the valve by turning the the stops into position. . Handwheel until the valve is fully in the closed position. Ensure the disc has returned to the fully closed position and the disc is centered in the seat area. Readjust the Shut Stop Screw if necessary. TFP1510 Page 4 of 4 Care and Limited Maintenance Warranty Before closing a fire protection sys- For warranty terms and conditions, tem control valve for maintenance or visit www.tyco-fire.com. inspection work on either the valve or fire protection system which it con- Ordering permission to shut down the af- g fected fire protection systems must be Procedure obtained from the proper authorities and all personnel who may be affected Grooved End Butterfly Valves by this decision must be notified. Specify:(specify inch size)Model BFV- The owner is responsible for the in- N Grooved End Butterfly Valve with spection, testing, and maintenance internal supervisory switches, P/N of their fire protection system and de- (specify) vices in accordance with the appli- Valve Size Valve Part Number cable standards of the National Fire Protection Association (e.g., NFPA 2-1/2 59-300-F-025N 25), in addition to the standards of 3 59-300-F-030N ) 4 59-300-F-040N any authority having jurisdiction. 5 59-300-F-050N Contact the installing contractor or 6 59-300-F-060N product manufacturer with any ques- $ 59-300-F-080N tions.Any impairment must be imme- diately corrected. It is recommended that automatic sprinkler systems be inspected, test- ed, and maintained by a qualified in- spection service. • • GLOBAL HEADQUARTERS 1 1400 Pennbrook Parkway, Lansdale,PA 194461 Telephone+1-215-362-0700 Copyright©2015 Tyco Fire Products,LP. All rights reserved. NCO Fire Protection Products ES-A-C300_C300N ColtTM Series C300, C300N AMES FIRE&WATERWORKS Double Check Detector Assemblies Sizes: 21" - 10" (65-250mm) C300BFG ` C3000SY '�� Features • Extremely Compact Design The Colt C300, C300N Double Check Detector Assemblies are designed • 70% Lighter than Traditional to protect drinking water supplies from dangerous cross-connections Designs in accordance with national plumbing codes and water authority IP/ • 304 (Schedule 40) Stainless Steel requirements for non-potable service applications such as irrigation, Housing &Sleeve fire line, or industrial processing. The Colt C300, C300N may be • Groove Fittings Allow Integral installed under continuous pressure service and may be subjected to Pipeline Adjustment backpressure for non-toxic applications. The Colt C300, C300N is used • Patented Tri-Link Check Provides primarily on fire line sprinkler systems when it is necessary to monitor Lowest Pressure Loss unauthorized use of water. For use in non-health hazard applications. • Unmatched Ease of Serviceability Specifications • Available with Grooved Butterfly The Colt C300, C300N Double Check Detector Assemblies shall consist Valve Shutoffs of two independent Tri-Link Check modules within a single housing, • May be Used for Horizontal, sleeve access port, four test cocks and two drip tight shutoff valves. Vertical or N Pattern Installations Tri-Link Check shall be removable and serviceable, without the use of • Replaceable Check Disc Rubber special tools. The housing shall be constructed of 304 (Schedule 40) A WARNING stainless steel pipe with groove end connections. Tri-Link Checks shall It is illegal to use this product in any plumbing have reversible elastomer discs and in operation shall produce drip tight system providing water for human consumption, closure against the reverse flow of liquid caused by backpressure or such as drinking or dishwashing,in the United backsiphonage. The bypass assembly shall consist of a meter, which States. Before installing standard material prod- registers in either gallon or cubic measurement, a double check valve uct,consult your local water authority,building assembly and required test cocks. Assembly shall be a Colt C300, C300N and plumbing codes. as manufactured by the Ames Company. Job Name Contractor Job Location Approval Engineer Contractor's P.O.No. Approval Representative Ames product specifications in U.S.customary units and metric are approximate and are provided for reference only.For precise measurements,please contact Ames Technical Service.Ames reserves the right to change or modify product design,construction,specifications,or materials without prior notice and without incurring any obligation to make such changes and modifications on Ames products previously or subsequently sold. amesfirewater.com Configurations Available Models • Horizontal Suffix: • Vertical up OSY - UL/FM outside stem and yoke resilient 411 • "N" pattern horizontal seated gate valves BFG - UL/FM grooved gear operated butterfly valves Materials with tamper switch • Housing&Sleeve: 304 (Schedule 40)Stainless Steel "OSY FxG - Flanged inlet gate connection and grooved • Elastomers: EPDM, Silicone and Buna'N' outlet gate connection • Tri-Link Checks: Norylm, Stainless Steel "OSY GxF-Grooved inlet gate connection and flanged • Check Discs: Reversible Silicone or EPDM outlet gate connection • Test Cocks: Bronze Body Nickel Plated *OSY GxG - Grooved inlet gate connection and grooved outlet gate connection • Pins& Fasteners: 300 Series Stainless Steel Available with grooved NRS gate valves - consult factory" • Springs: Stainless Steel Post indicator plate and operating nut available-consult factory" "Consult factory for dimensions Dimensions — Weights Pressure — Temperature Temperature Range: 33°F- 140°F (0.5°C-60°C) Maximum Working Pressure: 175psi (12.1 bar) i .a t I Al 117111 ._ difillItikA ij VII Inil C(open) 1I riff° I•iIiD • � '�j•tta i'� 11- i- I,11$ t? est IL .� H . C300, C300N SIZE(DN) DIMENSIONS WEIGHT A C(OSY) D G H I J P C300 C300N in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm lbs. kgs. lbs. kgs. 21/2 65 303/4 781 163/8 416 31/2 89 291A6 738 211/2 546 151/2 393 813/16 223 133/16 335 139 63 147 67 3 80 313/4 806 181/2 479 311/16 94 301/4 768 221/4 565 17% 435 93/6 233 141/2 368 159 72 172 78 4 100 333/4 857 223/4 578 4 102 33 838 231/2 597 1812 470 915/6 252 153/16 386 175 79 198 90 6 150 431/2 1105 301/8 765 51/2 140 443/4 1137 33'/4 845 233/6 589 131/46 332 19 483 309 140 350 159 8 200 493/4 1264 373/4 959 611/46 170 541/8 1375 401/2 1019 277/16 697 1511/6 399 213/16 538 494 224 569 258 10 250 573/4 1467 453/4 1162 83/6 208 66 1676 491/2 1257 321/2 826 175/16 440 24 610 795 361 965 438 ■ Mill Ik , i ,.-... ` I.- ' ,. CII)• KI17 " �� i:—_ ; •11411;,; � I� ■w A -- I. I H I J P C300BFG, C300NBFG - G SIZE(DN) DIMENSIONS WEIGHT A C D G H I J P C300BFG C300NBFG in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm lbs. kgs. lbs. kgs. 21/2 65 273/4 705 8 203 31/2 89 297/8 759 211/2 546 1415/16 379 813/16 223 13 330 70 32 78 35 3 80 281/4 718 85/6 211 311/16 94 3011/16 779 221 565 157/6 392 93/6 233 131/2 343 68 31 81 37 4 100 29 737 815/6 227 311/46 94 3115/is 811 231/2 597 161/4 412 915/16 252 14 356 75 34 98 44 _ 6 150 361/2 927 10 254 5 127 433/16 1097 331 845 1911/16 500 131/16 332 141/2 368 131 59 171 78 8 200 423/4 1086 121/4 311 61/2 165 511/46 1297 401/2 1019 235/6 592 1511/46 399 183/46 462 275 125 351 159 Noryle is a registered trademark of SABIC Innovative PlasticsTv. Approvals ;bus�ssto *„.44). • ® c)® approved C uS 1048 B64.5 (**BFG&OSY Only) Flow capacity chart identifies valve performance based upon rated water velocity up to 25fps For additional approval information please contact the factory or • Service Flow is typically determined by a rated visit our website at www.amesfirewater.com velocity of 7.5fps based upon schedule 40 pipe. • Rated Flow identifies maximum continuous duty Capacity performance determined by AWWA. p y • UL Flow Rate is 150% of Rated Flow and is not recommended for continuous duty. UUFM Certified Flow Characteristics • AWWA Manual M22 [Appendix C] recommends Flow characteristics collected using butterfly shutoff valves. that the maximum water velocity in services be See literatue S-Colt-200/300 for gate valve flow characteristics not more than 10fps. Horizontal Vertical N - Pattern 21" (65mm) 6" (150mm) psi Service Flow Rated Flow *UL Rated Flow psi Service Flow Rated Flow *UL Rated Flow 14 12 N 12 //. ' N 10 �'r y y 10 _// V 8 / ° 4 �,, a 4 d °' V 2 F- 2 0 0 0 50 100 150 200 250 300 350 gpm 0 300 600 900 1200 1500 gpm 0 190 380 570 760 950 1140 1330 Ipm 0 1140 2280 3420 4560 5700 Ipm el 7.5 15 fps 7.5 15 fps 3" (80mm) 8" (200mm) pSlService Flow Rated Flow *UL Rated Flow p 2 Service Flow Rated Flow *UL Rated Flow 12 / 10 H 10 '-. H / V 0 z 6 ,»+ .. ...-..�� ,,./ - s =' 6 i //� 4 2 a LL 2 0 _ 0 0 100 200 300 400 500 gpm 0 500 1000 1500 2000 2500 gpm 0 380 760 1140 1520 1900 Ipm 0 1900 3800 5700 7600 9500 Ipm 7.5 15 fps 7.5 15 fps 4" (100mm) 10" (250mm) psi Service Flow Rated Flow *UL Rated Flow psi Service Flow Rated Flow *UL Rated Flow 24 12 20 N 10 * N i 8 H a 12 ME Mill /I�_ H n. 1- 8 / v -,,. E 8 IIIERVIIII qLL 4 _, _0L. 0 0 100 200 300 400 500 600 700 800 gpm • 0 380 760 1140 1520 1900 2280 2660 3040 Ipm 0 500 1000 1500 2000 2500 3000 3500 gpm 7.5 15 fps 0 1900 3800 5700 7600 9500 11400 13300 Ipm 7.5 fps NOTICE _ Inquire with governing authorities for local installation requirements • . - AMES • FIRE&WATERWORKS A Watts Water Technologies Company USA:Backflow Tel:(978)689-6066•Fax:(978)975-8350•AmesFireWater.com USA:Control Valves Tel:(713)943-0688•Fax:(713)944-9445•AmesFireWater.com Canada: Tel:(905)332-4090•Fax:(905)332-7068•AmesFireWater.ca Latin America: Tel:(52)81-1001-8600•Fax:(52)81-8000-7091 •AmesFireWater.com ES-A-C300_C300N 1417 ©2014 Ames Fire&Waterworks tqcci IF/re & Building Products Technical Services: Tel: (800)381-9312/Fax: (800)791-5500 Model 513 (13) Riser Manifold 1-1/2 thru 6 Inch (DN40 thru DN15O) For NFPA 13 Sprinkler Systems General Technical 6 Description Data The Figure 513 (13) Riser Manifolds Approvals "— G.` described in this technical data sheet The Figure 513 (13) Riser Manifolds provide the necessary waterflow with a cover tamper switch for the wa- alarm, pressure gauge, alarm test ori- terflow alarm switch are UL Listed, fice, drain, and sight glass equipment ULC Listed, and FM Approved. IVu.. in a single assembly for use in NFPA ' 13 sprinkler systems as follows: The Figure 513 (13) Riser Manifolds .. i without a cover tamper switch for the NFPA 13* waterflow alarm switch are UL Listed i • 1-1/2 Inch (DN40) and FM Approved. lei 0 Male Thread x Female Thread Maximum Working Pressure r '•,. • 1-1/2 thru 6 Inch(DN40 thru DN150) 175 psi (12,1 bar) Groove x Groove Test Orifice 5.6K(80K) *Although the Riser Manifold described in Assembly this data sheet is intended for NFPA 13 nections and/or listed mechanical sprinkler systems,it may be used for NFPA The manifold body of the Figure 513 is grooved connections, as applicable systems, ductile iron, whereas the manifold 13D or 13R residential sprinkler y where a test orifice of 5.6K(80K)is accept- body of the Figure 13 is cast iron.The Step 2. Connect the drain line, and able. two assemblies are completely inter- then close the drain valve. changeable in function, application, Step 3. Refer to Figure 3 for wiring The variety of sizes and grooved end and end-to-end laying length. guidance. All wiring must be per- connections allow cost effective and Finish formed in accordance with the Author- easy transition to check valves,control Red painted. ity Having Jurisdiction and/or the Na- valves, and system piping. The Riser tional Electrical Code. Manifolds may be installed in either the Step 4. Refer to Figure 4 for optional horizontal (flow switch on top) or verti Installation relief valve. cal (flow going up) for both single sprinkler rises and floor control in high The Riser Manifolds may be installed Step 5. Place the system in service by rises. in either the horizontal (flow switch on filling the system with water.When fill- top) or vertical (flow going up). The ing the system, partially open the con- WARNING inlet of the Riser Manifold may be di- trol valve to slowly fill the system. Fill- The Riser Manifolds described herein rectly connected to a shut-off control ing the system slowly will help avoid must be installed and maintained in valve. damaging the waterflow alarm switch. compliance with this document, as After the system is fully pressurized, well as with the applicable standards NOTES completely open the control valve. of the National Fire Protection Asso- Where applicable pipe thread sealant ciation, in addition to the standards of is to be applied sparingly. Use of a Step 6. Secure all supply valves any other authorities having jurisdic- non-hardening pipe thread sealant is open. tion. Failure to do so may impair the recommended. performance of these devices. Never remove any piping component . The owner is responsible for maintain- nor correct or modify any piping defi- ing their fire protection system and de- ciencies without first depressurizing vices in proper operating condition. and draining the system. The installing contractor or sprinkler Step 1. Install the manifold body with manufacturer should be contacted the flow arrow pointing in the down- with any questions. stream position using threaded con- Page 1 of 6 APRIL, 2006 TFP962 Page 2 of 6 TFP962 NO. DESCRIPTION QTY. P/N • 1 1-1/2"Manifold Body, Male x Female NPT 1 N/A NOTES: Groove x Groove 1 N/A 1. Approximate weight,11.2 lbs.(5,1 kg). 2 Waterflow Alarm Switch: 2. ULC Listed Manifolds are equipped with VSR-SF with Paddle, Cover Tamper Switches installed internal UL/FM 1 971-096-00 to the Waterflow Alarm Switches. VSR-SF with Paddle and 3. CH:Common Hardware Cover Tamper Switch, ULC/FM 1 976-519-02 3 300 psi/2000 kPa Water Pressure Gauge .. 1 2341 37 • n l ii 1 1_74 d t> 11111 10"(254,0 mm) ,a, L D Q IN I' O 14-1/4" Male x Female NPT, _ 'q P' (362,0 mm) Groove x Groove --` Manifolds Q c rrcf ..D 11-1/8"(282,6 mm) Inspector's Test 5 Male x Male NPT &Drain Valve Drain Valve Manifolds (Normally set -r-re (Normally CII to"Drain") y 1 r Closed) __._ E] = I • 3/4" 1"/ 5-3/16" 2 3-1/2" (19,1 mm) NPT (131,8 mm) (88,9 mm) 6-1/8" - - (155,6 mm) 12-5/8" (320,7 mm) FIGURE 1 1-1/2 INCH(DN40)RISER MANIFOLD ASSEMBLY AND DIMENSIONS • TFP962 Page 3 of 6 • 2 INCH(DN50)MANIFOLD 4 INCH(DN100)MANIFOLD 6 INCH(DN150)MANIFOLD NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N 1 2"Manifold Body, 1 4"Manifold Body, 1 6"Manifold Body, Groove x Groove 1 N/A Groove x Groove 1 N/A Groove x Groove 1 N/A 2 Waterflow Alarm Switch: 2 Waterflow Alarm Switch: 2 Waterflow Alarm Switch: VSC with Paddle, VSC with Paddle, VSC with Paddle, UL/FM 1 976-357-01 UL/FM 1 976-357-04 UL/FM 1 976-357-05 VSC with Paddle and VSC with Paddle and VSC with Paddle and Cover Tamper Switch, Cover Tamper Switch, Cover Tamper Switch, ULC/FM 1 976-520-01 ULC/FM 1 976-520-04 ULC/FM 1 976-520-05 3 300 psi/2000 kPa 3 300 psi/2000 kPa 3 300 psi/2000 kPa Water Pressure Gauge .. 1 2341 Water Pressure Gauge .. 1 2341 Water Pressure Gauge .. 1 2341 2-1/2 INCH(DN65)MANIFOLD Manifold Nominal Installation Dimensions in Inches and(mm) Drain Size Weight NO. DESCRIPTION QTY. P/N Size A B C D E F G H lbs.(kg) 2 Inch 16-3/4 13 9/16 5-3/8 6-3/8 13-1/16 3-1/21"NPT 13.5 1 2-1/2"Manifold Body, (DN50) (425,5) (330,2) (14,3) (136,5) (161,9) (331,8) (88,9) (6,1) Groove x Groove 1 N/A 2-1/2 Inch 17-3/16 13 1 5-3/4 6-7/8 13-3/4 3-1/216,8 2 Waterflow Alarm Switch: (DN65) (436,6) (330,2) (25,4) (146,1) (174,6) (349,3) (88,9) 1-1/4"NPT (7,6) VSC with Paddle, UL/FM 1 976-357-02 3 Inch 17-3/16 13 1 6 7-1/8 14-1/4 3-1/2 1-1/4"NPT 15.7 VSC with Paddle and (DN80) (436,6) (330,2) (25,4) (152,4) (181,0) (362,0) (88,9) (8,5) Cover Tamper Switch, 4 Inch 20-1/2 13 4-5/16 7-9/16 9-1/16 16-5/8 4-1/2 2"NPT 32.7 ULC/FM 1 976-520-02 (DN100) (520,7) (330,2) (109,5) (192,1) (230,2) (422,3) (114,3) (14,8) 3 300 psi/2000 kPa 6 Inch 20-1/2 13 4-5/16 8-1/2 10 18-1/2 6-5/841,6 Water Pressure Gauge .. 1 2341 (DN150) (520,7) (330,2) (109,5) (215,9) (254,0) (469,9) (168,3) 2"NPT (18,9) 3 INCH(DN80)MANIFOLD el NO. DESCRIPTION QTY. P/N 1 3 / 1 3"Manifold Body, Groove x Groove 1 N/A 2 Waterflow Alarm Switch: VSC with Paddle, - . =m= UL/FM 1 976-357-03 VSC with Paddle and d b Cover Tamper Switch, Drain Valve if '- I. I�.��® ULC/FM 1 976-520-03 (Cormal)y 3 300 psi/2000 kPa Closed) Water Pressure Gauge .. 1 2341 um NOTES: A m 2 1. ULC ListedManifoldsare equipped with 11.;�O it oCover Tamer Switches installed internal B �I to the Waterflow Alarm Switches. 2. CH:Common Hardware 1 ■.7 * 1 1 1°i iiiiO0 ME/ MOM Test C D &Drain Valve G (Normally set E - to"Drain") H - F . FIGURE 2 2 thru 6 INCH(DN50 thru DN150)RISER MANIFOLD ASSEMBLY AND DIMENSIONS Page 4 of 6 TFP962 SWITCH TERMINAL CONNECTIONS 4111 UNINSULATED CLAMPING SEVERED LOOPED SECTION CAUTION: PLATE STRIPPED SINGLE An uninsulated section of a TERMINAL ENDS CONDUCTOR single conductor is not SEPARATE 11111111kpermitted to be looped around CONDUCTORS CLAMPING the terminal and serve as two PLATE separate connections.The TERMINAL ` Nolot. wire must be severed to serve\ ' INCOMING�� atwb separatevillin connections,supervision ›N%.0* ofththereby proninthen of the connection in the event that the wire becomes dislodged from the terminal. OUTGOING IMPROPER CONNECTION METHOD PROPER CONNECTION METHOD WATERFLOW SWITCH TYPICAL ELECTRICA CONNECTIONS CONTACTS SPDT(Form C) END OF LINE LOCAL RESISTOR CONTACT RATING .... 5A @ 125 VAC SIGNAL 2.5A @ 30 VDC DEVICE NC NO NC 1T1 NO• / NC COM COM COM CONTROL POWER PANEL NO FLOW NON-SUPERVISED STYLE B/CLASS B CONDITION CIRCUIT SUPERVISED CIRCUIT • (SEE NOTE) NOTE: For supervised circuits,see"Switch Terminal Connections"above.The Waterflow Alarm Switch has two switches,one can be used to operate a central station,proprietary or remove signaling unit,while the other contact is used to operate a local audible or visual annunciator. COVER TAMPER SWITCH(ULC ASSEMBLIES ONLY) CONTACTS SPDT(Form C) CONTACT RATING .... 3A©250 VAC 5A @ 125 VAC 1 mA @ 5 VDC min. NO 1\ • NC COM CONTACTS SHOWN WITH COVER IN PLACE FIGURE 3 WIRING GUIDANCE TFP962 Page 5 of 6 i1-1/2"(DN40)Manifold Only: NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N -To install optional Pressure Relief Trim on 1 3/8"Copper Tubing, 2 Pressure Relief Valve, a 1-1/2"(DN40)Manifold,a 1/2"NPT outlet 2"(DN50)Manifolds .... 1 971-124-01 175 psi,Nonadjustable .. 1 198-066-00 must be provided by the installer on the 2-1/2"(DN65)and 3 90°Compression Fitting system outlet piping,and a connection back 3"(DN80)Manifolds .... 1 971-124-02 Fitting 2 CH to the manifold drain trim must be fabricated 4"(DN100)and 4 1"x 1/2"Reducing Hex with installer supplied 3/8"copper tubing. 6"(DN150)Manifolds ... 1 971-124-03 Bushing 1 CH Discard unused trim components. CH:Common Hardware 3 1/2"NPT Installer Outlet Provided 1 3 4 / MI System Outlet Piping CIIMMMInstaller II FabricatedCO:la �'Idb3/s°Copper / IIIIIIIIIIM iriri_11. I. ,—�P'0 Tubing IIP • i�� 2"(DN50),2-112"(DN65), _ d b iIiti, 3"(DN80),4"Manifo),or w I� 6"(DN150)ManifoldManifold Drain Trim "pee _� 1101151)- r.m. learn Om III NI 1. 411111 4 a 1-1/2"(DN40)7 Manifold r 411.-1 L,._).) \ , • r r FIGURE 4 OPTIONAL PRESSURE RELIEF VALVE Riser Manifold component in the field. Alarm/Flow Test Procedure Care and Only the pressure gauge, waterflow Maintenance alarm switch, or relief valve can be Step 1. Place the test&drain Valve in replaced. If any other problems are the"test" position. encountered the entire riser manifold Step2. Fullyopen the drain valve. The following inspection procedure must be replaced. Makcertaithat drainage water will must be performed as indicated,in ad The alarm/flow testprocedure will re- not cause anydamage orgin injury. dition to any specific requirements of 9 1 Y the NFPA, and an Im airment must suit in operation of the associated y p alarms. Consequently, notification Step 3.Verify operation of associated be immediately corrected. q y° alarms. must be given to the owner and the fire The owner is responsible for the in- department, central station, or other Step 4. Close the drain valve. spection, testing, and maintenance of signal station to which the alarms are their fire protection system and de- connected, and notification must be Step 5. Place the test&drain Valve in vices in compliance with this docu- the "drain" position. pgiven to the building occupants. ment, as well as with the applicable Step 6. Verify that the residual (flow- standards of the National Fire Protec- Before closing a fire protection system ing) pressure indicated by the pres tion Association (e.g., NFPA 25), in control valve for inspection or mainte-a ) nance work on the fireprotection s s sure gauge is no less that originally addition to the standards of any y - recorded for the system when it was authorityhavingjurisdiction. The in- tem that it controls,permission to shut first installed. stalling contractor or product manufac down the effected fire protection sys turer should be contacted relative to tem must first be obtained from the Step 7. Close the drain valve. any questions. proper authorities and all personnel Step 8.Verify that the static(not flow- who may be affected by this action in pressure indicated bytheores- It nr e It is recommended that automatic must be notified. suregauge is no less that originally systems be inspected, tested, and maintained by a qualified After placing a fire protection system recorded for the system when it was Inspection Service in accordance with in service, notify the proper authorities first installed. local requirements and/or national and advise those responsible for moni- codes. toring proprietary and/or central sta- tion alarms. NOTES No attempt is to be made to repair any Page 6 of 6 TFP962 Limited Ordering • Warranty Information - Products manufactured by Tyco Fire& Riser Manifold: Building Products (TFBP) are war- Specify; Size (specify), Figure 513, - ranted solely to the original Buyer for (specify connection type inlet x outlet) ten(10)years against defects in mate- Riser Manifold (specify - without or rial and workmanship when paid for with) a cover tamper switch for the and properly installed and maintained waterflow alarm switch, P/N (specify). under normal use and service. This warranty will expire ten (10) years NOTES from date of shipment by TFBP. No Orders for Figure 513 may be filled warranty is given for products or corn- with a Figure 13. The two assemblies ponents manufactured by companies are completely interchangeable in not affiliated by ownership with TFBP function, application, and end-to-end or for products and components which laying length. have been subject to misuse,improper If a ULC Listing is required, the Riser installation, corrosion, or which have Manifold must be ordered with a cover not been installed, maintained, modi- tamper switch for the waterflow alarm fied or repaired in accordance with ap- switch. plicable Standards of the National Fire Protection Association, and/or the standards of any other Authorities UL/ULC/FM Assemblies Having Jurisdiction. Materials found With Cover Tamper Switch by TFBP to be defective shall be either 1-1/2 Inch(DN40) repaired or replaced, at TFBP's sole MT x FT P/N 4086 1-1/2 Inch(DN40) option. TFBP neither assumes, nor MT x MT P/N 4087 authorizes any person to assume for it, 2 Inch(DN50) any other obligation in connection with G x G P/N 4090 the sale of products or parts of prod- 2-1/2 Inch(DN65) ucts.TFBP shall not be responsible for G x G P/N 4091 411S sprinkler system design errors or inac- 3 Inch(GN80) p Y 9 G x G P/N 4092 curate or incomplete information sup- 4 Inch(DN100) plied by Buyer or Buyer's repre- G x G P/N 4095 sentatives. 6 Inch(DN150) G x G P/N 4096 In no event shall TFBP be liable, in - contract, tort, strict liability or under any other legal theory, for incidental, UL/FM Assemblies indirect,special or consequential dam- Without cover Tamper Switch P q 1-1/2 Inch(DN40) ages, including but not limited to labor MT x FT P/N 4055 charges, regardless of whether TFBP 1-1/2 Inch (DN40) was informed about the possibility of MT x MT P/N 4056 such damages, and in no event shall 2 Inch G x(GN50) P/N 4060 TFBP's liability exceed an amount 2-1/2 Inch(DN65) equal to the sales price. G x G P/N 4061 3 Inch(DN80) The foregoing warranty is made in lieu G x G P/N 4062 of any and all other warranties. ex- 4 Inch(DN100) press or implied. including warranties G x G P/N 4065 of merchantability and fitness for a par- 6 I G x(GN150) P/N 4066 ticular purpose. This limited warranty sets forth the ex- clusive remedy for claims based on Optional Pressure Relief Valve: failure of or defect in products, materi- Specify: Operational Pressure Relief als or components, whether the claim Valve and Trim for use with (specify is made in contract, tort, strict liability size) Figure 513 or 13 Series Riser or any other legal theory. Manifold, P/N (specify). This warranty will apply to the full ex- tent permitted by law.The invalidity, in 1-1/2"or 23' P/N 4063 P/N 4072 whole or part, of any portion of this 4„1 or 6'? r P/N 4073 warranty will not affect the remainder. Replacement Parts: • Specify: (description)for use with Fig- ure 513 or 13 Riser Manifold,P/N(Ref. _ Figure 1 or 2, as applicable). TYCO FIRE&BUILDING PRODUCTS,451 North Cannon Avenue,Lansdale, Pennsylvania 19446 O C.AR.RQN STEEL.PIPE 7 GRQOVED + x. Rndli c ina 9jOUrli - 0 ® Vds LPCB VNIIPO SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS • STYLE 750 4 The Style 750 Reducing Coupling permits direct reduction on the piping run. Designed iyx to replace two couplings and a reducing fitting,the Style 750 features a special reducing gasket for pressure responsive sealing. A steel washer which prevents telescoping of the smaller pipe inside the larger pipe during vertical systems assembly is available upon request. iff' ii�iiooi C\ Exaggerated for clarity MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A-536,grade 65-45-12. Ductile iron conforming to ASTM A-395,grade 65-45-15, is available upon special request. Housing Coating: Orange enamel • Optional: Hot dipped galvanized and others Gasket: (Specify choice*): • Grade"E" EPDM (All other sizes) EPDM (Green color code).Temperature range—30°F to+230°F/-34°C to+110°C. Recommended for cold and hot water service within the specified temperature range plus a variety of dilute acids,oil-free air and many chemical services. UL classified in accordance with ANSI/NSF 61 for cold +86°F/+30°C and hot+180°F/+82°C potable water service. NOT RECOMMENDED FOR PETROLEUM SERVICES. • Grade"T"nitrile Nitrile(Orange color code).Temperature range—20°F to+180°F/-29°C to+82°C. Recommended for petroleum products,air with oil vapors,vegetable and mineral oils within the specified temperature range. Not recommended for hot water services over+150°F/+66°C or for hot dry air over+140°F/+60°C. * Services listed are General Service Recommendations only. It should be noted that there are services for which these gaskets are not recommended. Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service recommendations and for a listing of services which are not recommended. • Optional: Assembly Washer: Galvanized,carbon steel Bolts/Nuts: Heat-treated plated carbon steel,trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date Approved Date www.victaulic.com /1ictauliC' VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2007 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. v REV I 06.08_ CARBON STEEL PIPE-GROOVED COUPLINGS 06.08 Reducing o� Ri1 STYLE 750 • DIMENSIONS Max.Work Allow.Pipe Bolt/Nut@ Approx. Size Pressure' Max.End Load* End Sep.8 Deflect.Fr.CO- No-Size Dimensions-Inches/mm Wgt.Each Nominal ,, '" Per Pipe Size psi ' Lbs. . C Ig In./Ft. � bo Inches/mm kPa N Inches/mn Deg mm/m Inches X Y 2 * kg 2 1 350 500 0-0.07 0.20 3.38 5.28 1.88 2.7 0°-5T 2 3/8 x 2 85 134 48 1.2 50 x 25 2410 2225 0-1.8 , 17 11/2 2 350 1000 0-0.07 0° 57' 0.20 2 3/8 x 2 3.38 5.28 1.88 2.0 40 2410 4450 0-1.8 17 85 134 48 1.0 21/2 2 500 2215 ; 0-0.07 0.16 4.00 5.93 1.88 3.1 0°-47' 2-3/8x2 65 x 50 3450 9850 0-1.8 14 102 151 48 1.4 76.1 mm x 2 350 1550 0-0.070.16 438 6 63 1.88 4.6 0°-4T 2-%z x 2 3/ 50 2410 6900 0-1.8 14 111 168 48 2.1 3 2 350 1550 0-0.07 0.13 4 75 7.13 1.88 4.9 80 x 50 2410 6900 0-1.8 0°-39 11 2-Yzx23/a 121 181 48 2.2 21/2 500 3250 0-0.07 0°-39` 0.13 2-'/2x23/a 475 713 1.88 4.3 65 3450 14460 0-1.8 121 181 48 2.0 350 2275 i 0-0.07 0.13 4.75 7.13 1.88 4.2 88.9mm x 76.1 mm 0°-39 %z 2- x23/a 2410 10125 0-1.8 11 121 181 48 1.9 4 2 350 1550 0-0.13 0.28 6.25 8.90 2.25 8.1 100 x 50 2410 6900 0-3.2 9 s 2 5/8 x 3 1 25 159 226 57 3.7 21/2 350 2275 0-0.131°-19' 0.28 2-5/8 x 3 Y4 625 8.90 2.25 8.6 65 2410 10125 0-3.2 25 159 226 57 3.9 3 500 4810 0-0.130.28 6 00 8.90 2.25 6.7 180 3450 21400 0-3.2 9' 25 2 5/8 x 3'/4 52 226 57 3.0 114.3mm x 76.1 mm 350 2475 0-0.13 028 6.25 8.90 2.25 6.9 2410 11014 0 3.2 1'-19' 25 2-5/8x3Ya 159 226 57 3.1 5 4 350 5565 0 0.13 0.22 7.18 10 70 2.13 11.2 125 x 100 2410 24765 0-3.2 1°-3 2-3/4x4'/ 19 182 272 54 5.1 4110 6 4 350 5565 0-0.13 0°-52' 0'18 8.63 11.90 2.25 16.7 150 x 2-3/a x 4'/a 100 2410 24765 ! 0-3.2 15 181 302 57 7.6 5 350 8500 0-0.130.18 8.31 11.90 2.25 12.9 0° 52' 2 3/4 x 4'/4 211 302 57 5.9 125 2410 37825 0-3.2 15 165.1 mm x 4 350 5565 0-0.130.19 8 63 11.90 2.25 15.2 100 2410 24765 0-3.2 0`-55' 16 2 3/a x 4Y4 219 302 57 6.9 8 6 350 12000 0-0.13 0° 38' 0.13 2-7B x 5 10.81 14.88 2.50 22.4 200 x 150 2410 53400 0-3.2 1 275 378 64 0.2 350 1625 0-0.13 0.13 10.75 14.88 2.50 23.2 219.1 mm x 1651 mm 2410 0 3.2 0°-38' 11 2-7/8x5 273 378 64 10.5 10 8 350 20450 0-0.13 0.9 13.12 17.26 2.62 31 4 273 x 219.1 2410 0-3.2 0°-25' 8 2-1 x 5'/z 333 438 67 14.2 Style 750 Reducing couplings should not be used with end caps(#60)in systems where a vacuum may be developed.Contact Victaulic for details. *Working Pressure and End Load are total,from all internal and external loads,based on standard weight(ANSI)steel pipe,standard roll or cut grooved in accordance with Victaulic specifications.Contact Victaulic for performance on other pipe.Maximum working pressure rating based on larger pipe size. Maximum End Load rating based on smaller pipe size.WARNING:FOR ONE TIME FIELD TEST ONLY,the Maximum Joint Working Pressure may be increased to 11/2 times the figures shown. t Allowable Pipe End Separation and Deflection figures show the maximum nominal range of movement available at each joint for standard roll grooved pipe.Figures for standard cut grooved pipe may be doubled.These figures are maximums;for design and installation purposes these figures should be reduced by:50%for 3/4-31/2'/20-90 mm;25%for 47100 mm and larger. @ Number of bolts required equals number of housing segments. Metric thread size bolts are available(color coded gold)for all coupling sizes upon request.Contact Victaulic for details. WARNING:Depressurize and drain the piping system before attempting to install,remove,or adjust any Victaulic piping products. .-. --Y-.. 1 4-Z--). 4 Y- --* �Z- ,:4/ftti (Plli eAil 0 rr Irl-:-:I \11111440021.4.,W t,_,j ) AI ......jug al • www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2007 VICTAULIC COMPANY ALL RIGHTS RESERVED.PRINTED IN THE USA. v 'Cct'a�"�'�C'. 06.09_2 ?-{1 I CARBON STEEL PIPE-GROOVED COUPLINGS 06.08 �c du' C.,o .fin 5 • STYLE 750 FLOW DATA HEAD LOSS The head loss across Style 750 Reducing coupling is very small and is essentially the same as for standard short body reducing pipe fittings. Equivalent lengths of standard weight steel pipe are shown in the tables. All data is based on water flowing at ambient temperature. FLOW REDUCING FLOW EXPANDING Equiv.Pipe Equiv.Pipe Size Length Size Length Nominal Nominal Size :F Size Sm.Dia. Size Sm.Dia 4mm Feet/m aT Inches/mon FeeUUm 21 5.9 1 2 j 2.7 SO x 25 1.8 25 x 50 0.8 11/2 2.0 11/2 2 1 9 40 ? 0.6 40 x 50 0.6 2/z 2 1.9 2 2/z 1.0 65 x 50 0.6 50 x 65 0.3 2 1.9 76.1 mm x 50 0.6 76.1 mm 1.0 3 2 5.5 3 3.5 80 x 501.7 80 1.1 21/2 3.8 4 3.0 65 1.2 100 0.9 3.8 2/z 3 25 88.9mm x 76.1 mm 1.2 65 x 80 0.8 • 4 2 1.0 100 50 4 3.0 x 8 100 0.9 65 �.g 76.1 mm x 88.9mm 0.8 80 6.8 .0 114.3 mm 0.9 114.3 mm x 76.1 mm i 6.0 3 x 4 2.5 18 80 100 0.8 5 4 3.0 4 5 3.3 125 x 100 0.9 100 x 125 1.0 6 4 ' 6.0 6 4.6 150 x 100 1.8 150 1.4 25 4.5. 165 mm 4,4 4 6.0 56 2.3 165.1 mm x 100 1.8 125 x 150 0.7 _ 8 6 7.3 6__ 8 6.0 200 x 150 2.2 150 x 200 1.8 219.1 mm x 1651mm 7.3 165.1mm x 219.1 mm ', 1565 f-- 108 8.7 8 x 10 6.3 x 273 219.1 2.65 219.1 273 19.2 • www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2007 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. jctaulic* REV_i 06.08_3 CARBON STEEL PIPE—q3Q,pligo , • Reducing C -)uplino STYLE 750 • INSTALLATION Reference should always be made to the 1-100 Victaulic Field Installation Handbook for the product you are installing. Handbooks are included with each shipment of Victaulic products for complete installation and assembly data,and are available in PDF format on our website at www.victaulic.com. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. • 11111111111111111111111111111111111111111 • WCAS-6UPKD7 For complete contact information, visit www.victaulic.com 06.08 1536 REV I UPDATED 6/2008 1ctauluc VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2007 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. - •..m..,.,-06.08 ..Z477..gg§0 P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org 078 ATTACHMENT FITTING LOCKING STRAIGHT 9/16 Dia. Part#077- . V NO 1011110.4.17..\*1 Part#078 r• Part#410 — SIZE- 1 and 1 1/4 inch bracing pipe. Use in combination with 1 thru 8 inch AFCON sway brace assemblies. MATERIAL-Carbon Steel or S.S.(Type 304). FINISH-Plain or E.G. LISTING/APPROVAL- ca,s 203A-EX 2625 Listed only for use with other AFCON bracing products. OSHPD OPA-0601 See Website. FUNCTION-Attachment fitting of a sway brace assembly,consisting additionally of AFCON 001 thru 040 sway brace fitting and brace element forming a complete sway brace assembly. Commonly used as the brace pipe attachment component of a #410 longitudinal sway brace assembly-see drawing INSTALLATION- Per NFPA 13. Listed for use with NFPA 13 fastener tables.Installation restricted to NFPA 13, G-H-I orientation ONLY. DO NOT BEND-IF ANGLE REQUIRED USE PART#070,#076 or#077 For installation on H-beam or steel web joist see AFCON 085 thru 088 sway brace adapters. ASSEMBLY-Insert brace pipe into fitting against the pivot bolt.Tighten set bolt until head contacts bracket. FEATURES * UL Horizontal Load Rating: 2015#,All Sizes. *Visual inspection,proper installation when set bolt head contacts bracket. *Bolt hole fits#410 sway brace fitting. ORDERING-Part#,pipe size and finish. • Specific AFCON products arc exclusively designed to be compatible ONLY with other AFCON products including parts and fasteners,resulting in a listed sway brace,restrainer or hanger assembly. Be advised the following warranty restriction will apply. DISCLAIMER-AFCON will NOT warrant against the failure of its products when used in combination with other products,parts or systems not manufactured or sold by AFCON.AFCON shall NOT be liable under any circumstances whatsoever for any director indirect,incidental or consequential damages of any kind,including but not limited to loss of business or profit,when non-AFCON products have been,or are used. 1/09 .. ® . . . SIDE • , „.. - . -hOnzontal mount - i,i-,.,:„.i.f,, ..._:k ,:-„,,,,,,, 1/4" 8019957 SWG 200 1/4 X 2 25 10.78 125 Mii'••,,.,.? ",i-4. :1'; 4,4,,- , ,, . K" ' ''ui. 3/8 8021957 SWG 20 1/4 X 2 25 9.45 125 • `,---1111gtFi;::Y4::'•'.0!At .,) i,:•. ',• -,40a4 VitiK•0; 1`,i.4411110k.,',, ... , '•:,• • ,i!,,i -•-4-‘1, , 3/8 8023925 SWG 30 1/4 X 3 25 10.70 125 ,lipxr-. 4 4:;t4i•4,4.--,n;s •ttf;li.. ...rrpry:' 7.::- ..!, i'4'',..ii,, ': i,::::c -,.• vi..1.n. ;:m , ,:...,.. „„ ‘, 1/4” 8049957 SWDR 100 1/4-20 X 1 25 10.37 125 — aMilltakt . , •,— '4,014111514WOZO*14-4111W:00. Llt...W.: -:.4: ,.•` ells ovr=b4. I 3/8 8051957 SWD 15 1/4-14 X 1-1/2 25 8.47 125 . • . . •a* ,i't -,•' ' i'''''y' ,•= ,. - -,,--TglifkAallial—'--1-0:14:' '.':,;..akiiiiikOM; AlfAlltilt NW' Part#8114910 3/8 8053957 SWD 516 5/16-18 X 1-1/4 25 8.94 125 , „.. ,,,,..000000, 41 aliWW iifaiWirkillaillIENI ,VAIrli .A..41k. UL FM 3/8 8055957 SWDR 1 1/4-20 X 1 25 9.07 125 !IiIMOOMIIIIIIIMONIIIM*5* /**.:41EW*Mill1111461 ,1111111111 3/8" 8057957 SWT 15 12-24 X 1-1/2 25 8.28 125 1110 ---,,,-17,'*::. lir'vo.:;/m: :,,,.. i.::I -- VI:1: :.',!:';I,T-,•'', ri,IV; ;.* .4.2s,Qi i,,,,t -46,,, ,,, ,,' — 3/8" 8061957 SWC 20 5/16 X 1-3/4 25 9.81 125 . 144441 414,14. 44/4414 4. c/44144 Slut 44 441 44 41444Z4 4414. Swivel Head® Use with 3/8" Rod Part Screw Box Weight Case • Use#14 Nut Driver(black) Approvals No. Model Descriptions Qty. (per 125) Qty Part No.8113910. ftilcr.:07M. '''-**MOOPRIW, '.*' ';' MillrailIWIPPW: •17°deflection from vertical. uL•Fm 8141957 SH-GST 30 1/4 x 3 25 10.15 125 • Accommodates up to „ 4 U S.Patent No H jr1MaitAlst-Pt.'llitirekil.', — —10.*611111%..: .k..,--Alli 3-1/2 x 12 pitch roof. 6,443,680 SAMMY X-PRESS® Use with 1/4" or 3/8" Rod Hang Threaded Rod Approvals Steel Ga. Part No. Model Screw Descriptions Rod Size Max Pipe Size Application Directly fromgref#4111-440W. '", ••• .. . .111116e, '-'.-16111111111116' ketta. Thin Gauge Metal Deck FM 12 ga. 8153922 XP 35 Sammy X-Press 35 3/8-16 4" Purim &Purlin g Alligiiir.'.2irrkillikAiiiiligiNPRO-1 .-nft,Va'file4,1010.4W . - t-.4144 . UL 18 ga. 8153922 XP 35 Sammy X-Press 35 3/8-16 31/2" Pullin . , 6_*___- - f4 i-Agnitabefittilt.W. d 4., z .a• 4- UL 22-20 ga. 8294922 SXP' 20 Swivel X-Press 20 3/8-16 : 2" Metal Deck • C;-,i.,,: ,'': '6AitilliallSlii*WMANINSWiftWAS111.1111* .'. 0 , . '';:1;7% •<73 Approvals Concrete Part No. Model Screw Descriptions Rod Size Max Pipe Size Thickness ' 1 Millart-;W:7:T,!OrdWiti: 1,:'82 .:-,-.104111011W10444 .arnaltWOOSIMMIZIPT77-'301114111 UL LWC Concrete 8150922 XP 20 Sammy X-Press 20 3/8-16 2-1/2" 35 PCF Approvals Steel Ga. Part No. Model Screw Descriptions Rod Size Load Rating N. V3'K*1111111fiWNIMPROSPO... Sammy .... *A5NR*044-,",167000, g UL 22 ga 8153922 XP 35 SX-Press 35 3/8-16 185 lbs. S t. 'i 4416irlIrtriww/'1411111Ero3/404*, . -:Iffillierom416,, .:vi.ziNtv, -- . twt4"2"11- ''':,•ii,,- , UL 16 ga. 8150922 XP 20 Sammy X-Press 20 3/8-16 ‘,.,.250116bs - -:•..i 3 111111616.- .' ,Ireti. - €06WirtiAnt..401MINessiallik.- -4;,.7MINIEL. ?p ;4 UL 16 ga. 8181922 XP 200 Sammy X-Press 200 1/4-20 250 lbs. Universal X-Press le TIP .114gf Ataliti . -819491W-44-4tii4ggierOat'AllatiTORMINStAiii:A:ii."7:Z"Wilk- Alki Installation Tool `,i' 8151910 RXPIT Retro Socket for 8151910 ' ,2 i ,':a Alii4,4:: '''ININftilkiliNINW,47.Pdit. ..41,P akikv:..“t''11141ffilbaitif:-.'11.Mk *I ... S *MMYS®. BuiIdeX • n'i vertical' mount • s :;Zrte.., , r. sas,: - $j ^.i '-:^'#F L'i+ . r.'ic ,, y■ 1/4" 8003957 GST 200 1/4 x 2 25 8.64 125 - 3/8' 8006957 GST.75 1/4 x 3/4 25 6.24 125 7 UL-FM 3/8" 8008957 GST 20 1/4 x 2 25 8.17 125 UL•FM 3/8" 8010957 GST 30 1/4 x3 25 9.41 125 Part#8113910 Wil43 *' g: ,, ^ 3/8" 8012925 GST 60 1/4 x 6 25 12.72 125 t v R ,+• 1/2" 8014925 GST 2.5-380 3/8X2-1/2 25 11.99 125 1/2" 8016925GST 4 1/4 X 4 25 13.25 125 PRCO ;,..., q ,;. ,,° '.' 1 � — Part#8114910 -:•r :„,: 1/4” 8025957DST 100 1/4 14 X 1 25 7 23 125 < .:, . ;S*; tII 1/4" 8027957 DST . ;". . a " '' 200 1/4-14 X 2 25 8.31 125 1/4" 8029957 DST 300 1/4-14 X3 25 9.41 125 44 .Fes• *7 k T,-4-.-., " UL.FM 3/8" 8037957 DS yTR1-1/2 12--24 X 1-1/2 25 8.18 125, t•- ,,. '' ,• _ ill UL•FM 3/8" 8039957 DSTR 516 5/16-18 X 1-1/4 25 9.35 125 3/8" 8041957 DST 15 1/4-14 X 1-1/2 25 7.20 125 *:' 47-4,1411114.601.,ktiA4,47 41111ENO - -OA 3/8" 8043957 DST 25 ;yry 1/4-14 X 2-1/2 25 8.42 125 UL•FM 3/8" 8045957 DST 516 5/16-18 X 1-1/4 25 7.79 125 v4of ° r‘ R .'..# win • _ 1/2" 8031925 DST 2.0 1/4-14 X 2 25 8.61 125 1/2" 8033925 DSTR 1.0 1/4-20 X 1 25 8.61 125 :: ,011'11 Y::. — 1/2" 8035925 DST 5.16 5/16-18 X 1-1/4 25 8.51 125 _'. .4: 4 r-- <'12• ,.,r • -3; t• "^s�st�' -. • . :: , :_ . a .,,;;,3_,:`,:i.. , t .-.g, black nut 0 FM 3/8" 8059957 CST 20 5/16 X 1-3/4 25 7.81 125 driver 11,1111111111111100 ' . s, **,` ., a • 5/1.6 +'% alir '2 —`ddiveUt - efiacleas TaPCOnSammys°,Sammy Super Screw®, Sammy Swivel Head',Sammy X-Press°,Sammy X-Press IT.,Sidewinders., 800-BUILDEX Swivel X-Press"",and Sidewinder X-Press"are trademarks of ITW Buildex and Illinois Tool Works,Inc. www.itwbuildex.com ©2007 Illinois Tool Works,Inc SSS30 1 • .,adeggglOIZ P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www.Afcon.org 001/020 SWAY BRACE FITTING MODEL E Part#077it.-, 4 41114%, '.-No; 1.°° 1"min. A.401111111:. " ,..''k,,,NI* : M1 • SIZE-SYSTEM PIPE: Nominal Steel 1"thru 4" Sch. 10 and Sch,40 Max.ASD Horizontal Load SIZE-BRACE PIPE: 1" or 1 1/4" Sch.40 System NPS Sch. 30°-44.° 45%59° so°aa°75%90° MATERIAL-Carbon Steel or S.S.(Type 304). 1" 40 430 610 750 840 FINISH-Plain or E.G. 1 1/4"-1 1/2" LW-40 90 130 160 180 LISTING/APPROVAL- 2" LW 190 280 34Q 380 2" 10 550 790 960 1080 2"-3" 40 500 710 870 970 41>FM Approved-1950 2 1/2"-4" LW 160 230 280 320 OSHPD See Website. 21/2"-4" 10 260 370 460 510 4" 40 1030 1460 1790 1990 FUNCTION- Lateral fitting of an AFCON sway brace assembly. INSTALLATION-Per these instructions including NEPA 13 and FM 2-8. Load rating-see chart. ASSEMBLY-See drawing. Combine with proper AFCON components-see disclaimer below. Insert brace pipe through rod bend and under channel bracket to achieve minimum 1" extension. Tighten hex nuts until gage spring lays flat or torque to 165 lb-in. FEATURES *Visual inspection,verifies proper installation. ORDERING-Part#,size-system pipe,size-brace pipe and finish. 0 . ISpecific AFCON products are exclusively designed to be compatible ONLY with other AFCON products including parts and fasteners,resulting in a listed sway brace,restrainer or hanger assembly. Etc advised the following warranty restriction will apply. DISCLAIMER-AFCON will NOT warrant against the failure of its products when used in combination with other products,parts or systems not manufactured or sold by AFCOtV.AFCONahal!NOT be liable under any circumstances whatsoever for any direct or indirect,incidental or consequential damages ninny kind.including but not limited to loss of business or pro lit,when non-AFCON products have been,or are used. 8/14 .: • 4,Z. ;?7/ 1gC).2 P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org 555 BRACKET SIZE-ROD: 1/2" i SIZE-SYSTEM PIPE: 8"max. MATERIAL-Carbon Steel. I`" FINISH-Plain or E.G. ® LISTING/APPROVAL- O / `®U 203- EX 2551 FUNCTION- Attachment component of an AFCONhanger. /is°500 INSTALLATION- Per NFPA 13 and these instructions. • Install on vertical mounting surface. ASSEMBLY/ATTACHMENT Mounting hole accepts 1/2"or 5/8"fasteners. FEATURES-Tapped rod bore. ORDERING-Part#and finish. 556 BRACKET SIZE-ROD: 1/2" DSIZE-SYSTEM PIPE:8"max. ® MATERIAL-Carbon Steel. FINISH-Plain or E.G. LISTING/APPROVAL- 0Q, u:203- EX 25- NOTE-Criteria same as 555 except smooth 17/32"rod bore. Install hanger rod with'/"nut. 4/13 • o0 P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org 300 RING HANGER ':':. • -,:3.:2,1 h / , • NFPA 13 MAX REC. METRIC 3/4 thru 4 inch pipe % inch pipe PIPE ROD LOAD LBS. REFERENCE LISTED FOR STEEL/CPVC 5 thru 8 inch pipe 3/4 3/8 400 20 1 3/8 400 25 1 1/4 3/8 400 32 11/2 3/8 400 40 2 3/8 400 50 21/2 3/8 600 65 SIZE- 1/2 thru 8 inch pipe. 3 3/8 600 80 MATERIAL-Carbon Steel,Mil. Galvanized to G-90 spec. 31/2 3/8 600 LISTING/APPROVAL- 4 3/8 1000 100 c®us 203-EX 2551 1250 5 1/2 125 FM Approval guide-Pipe Hangers 6 1/2 1250 150 OSHPD OPA-0601 See Website. CONFORMS WITH:Federal Specification WW-H-171 Type 10, 8 1/2 1250 200 Manufacturers Standardization Society ANSI/MSS-SP-58 Type 10. MAXIMUM TEMPERATURE-650°F. FUNCTION-Pipe hanger component for use on steel,CPVC or copper piping. INSTALLATION-Per NFPA 13, 13R, 13D and CPVC manufacturers instructions. SPECIAL NOTE: When installing on CPVC sprinkler system pipe: Verify that all assembly components are cleaned of any surface oil. PIPE A B FEATURES T 6793 2.5259 :k T I 11/4 2.1382 2.]850 Sized and listed exclusively for use with#310 Surge Restrainer. T * Band edge is offset for EASY pipe insertion. ' „/2 2.6048 2.9'40 B 2 2.6048 3.2518 * Custom fit swivel nut for better retention in ring body. / n 2,2 3.4920 4-„s9 Ai * rs-m--' +, 3 3.]845 4.4311 Full length knurl on swivel nut for better grip. ORDERING-Part#,pipe size. ( 43562 4.9992 6 6.5668 6.3296 8 7.5]86 8.3290 ,,oii,,t 9/08