Loading...
Plans S f-145.2 0 - C10l7� 14 $ . 13L-/3s- Sw �� � �� tqcs SF P 2 9 2016 Worldwide Fire Protection Contacts www.tyco-fire.com Products .41,„ . ' Series TY-FRB — 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General when exposed to corrosive atmo- spheres. Although corrosion-resistant Description coated sprinklers have passed the standard corrosion tests of the appli- The TYCO Series TY-FRB, 2.8, 4.2, cable approval agencies,the testing is 5.6,and 8.0 K-factor Upright,Pendent, not representative of all possible cor- and Recessed Pendent Sprinklers rosive atmospheres. Consequently, described in this data sheet are quick it is recommended that the end user response, standard coverage, deco- be consulted with respect to the suit- ability of these coatings for any given rative 3 mm glass bulb-type spray corrosive environment. The effects of sprinklers designed for use in light or ordinary hazard,commercial occupan- ambient temperature,concentration of cies such as banks, hotels, and shop- chemicals, and gas/chemical velocity, y ping malls. should be considered, as a minimum, along with the corrosive nature of the The recessed version of the Series chemical to which the sprinklers will be TY-FRB Pendent Sprinkler, where exposed. applicable,is intended for use in areas An intermediate level of the Series with a finished ceiling. This recessed TY-FRB Pendent Sprinklers is detailed pfendent ssprinkler uses one of the in Technical Data Sheet TFP356, and g Sprinkler Guards are detailed in Tech- • A two-piece Style 10(1/2 inch NPT) nical Data Sheet TFP780. 4. or Style 40(3/4 inch NPT)Recessed Escutcheon with 1/2 inch (12,7 mm) NOTICE 4 of recessed adjustment or up to 3/4 inch (19,1 mm) of total adjustment The Series TY-FRB, 2.8, 4.2, 5.6, ti. from the flush pendent position,or a and 8.0 K-factor, Upright, Pendent, and Recessed Pendent Sprinklers A,i%= • A two-piece Style 20(1/2 inch NPT) described herein must be installed or Style 30(3/4 inch NPT)Recessed and maintained in compliance with . Escutcheon with 1/4 inch (6,4 mm) this document and with the applica- s' , of recessed adjustment or up to 1/2 ble standards of the National Fire Pro- s- 444" inch (12,7 mm) of total adjustment tection Association, in addition to the from the flush pendent position. standards of any authorities having The adjustment provided by the jurisdiction.Failure to do so may impair Recessed Escutcheon reduces the the performance of these devices. Sprinkler accuracy to which the fixed pipe drops The owner is responsible for maintain- Identification to the sprinklers must be cut. ing their fire protection system and Corrosion-resistant coatings, where devices in proper operating condition. Number (SIN) applicable,are utilized to extend the life The installing contractor or sprinkler of copper alloy sprinklers beyond that manufacturer should be contacted with TY1131 -Upright 2.8K,112-NPT which would otherwise be obtained any questions. TY1231 -Pendent 2.8K,1/2'NPT City -Upright 4.2K,1/2-NPT City of Tigard TY2231 -Pendent 4.2K,1/2-NPT IMPORTANTq TY3131 -Upright 5.6K,1/2"NPT Always refer to Technical Data API a V-d Plans TY3231 -Pendent 5.6K,1/2-NPT Sheet TFP700 for the "INSTALLER r , E . TY4131 -Upright 8.0K,3/4"NPT WARNING"that provides cautions __ Date ( I TY4231 -Pendent 8.0K,3/4"NPT with respect to handling and instal- TY4831 -Upright 8.0K,1/2-NPT lation of sprinkler systems and com- L ff// ,//���` ��� TY4931 -Pendent 8.OK 1/2'NPT ponents. Improper handling and � 1 V`- (�t�1-�'� ' installation can permanently damage a sprinkler system or its compo- OFFICE COPY nents and cause the sprinkler to fail COPY 1 to operate in a fire situation or cause it to operate prematurely. Page 1 of 10 NOVEMBER 2015 TFP171 14 TFP171 Page 2 of 10 *Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Assembly Screw Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector* SURFACE 7 - Bushing _— P 7 Y 4k 1 7/16" _ 6!' 3 (11,1 mm) NOMINAL 2-1/4" ,- r 2 MAKE-IN ��� I r�1 2-3/16 (57,2 mm) 4 (55,6 mm) 1 li 1-9/16" (39,7 mm) II a 5 ���..._‘ 1/2"NPT** f WRENCH STYLE 10 or 20 2-7/8"(73,0 mm)DIA. - FLATS RECESSED UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION FIGURE 1 QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY//31)AND PENDENT(TY1231)SPRINKLERS 2.8 K-FACTOR, 1/2 INCH NPT *Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Assembly Screw Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector* SURFACE 1 1i>'f1T�'f ��. 7/16" ___________ _ _______ ____ our-=---- I N11,1 mmi)_' l 44 0 3 I�� 2 al 2-3/16" MAKE IN i (55,6 mm) 4 1111. 1 2 3/16r"n 1-1/2" l� 1 6m (55, ) iil, (38,1 mm) i"!_---------5 6* 1/2"NPT** WRENCH STYLE 10 or 20 1--.--- 8"(73,0 mm)DIA. -- FLATS RECESSED UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION FIGURE 2 QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY2131)AND PENDENT(TY2231)SPRINKLERS 4.2 K FACTOR, 1/2 INCH NPT *Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression is indicated on ISO 7-1 can be provided on 2 - Button Assembly Screw Deflector. special request. ESCUTCHEON 4 - Bulb 6 - Deflector* PLATE SEATING SURFACE i �6, 1 __ ...___ ___ 7/16" ___ _ I (11,1 mm) 1■ � C NOMINAL 0_l } 2-3/16" w II v—A &. 2 MAKE-IN I (55,6 mm) �l 2-3/16" 1-1/2" �I� 4 (55,6 mm) I (38,11I mm) _ - _ —5 6* 1/2"NPT** WRENCH STYLE 10 or 20 2-7/8"(73,0 mm)DIA. - FLATS RECESSED UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION FIGURE 3 QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY3131)AND PENDENT(TY3231)SPRINKLERS 5.6 K-FACTOR, 1/2 INCH NPT S u TFP171 Page 3 of 10 *Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Assembly Screw Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector* SURFACE "UI kr1/2" I / (12,7 mm)OrNOMINAL2-5/16" ��f — A ;fi_ MAKE-IN L (58,7 mm) r 2 (57,22-1/mm) II 1-9/,6" IiIri I 4 39,7 mm) 4-�,�.` * 3/4"NPT** } WRENCH STYLE 30 or 40 2.7/8" 73,0 mm r 6 FLATS RECESSED ( )DIA. - UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION FIGURE 4 QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY4131)AND PENDENT(TY4231)SPRINKLERS 8.0 K-FACTOR,3/4 INCH NPT CEILING PLATE 1 - Frame 5 - Compression SEATING SURFACE 2 - Button Screw �,t_r__ _I_�,, 1 3 AssemblySealing 6 Deflector 7/16 Y ,�t 3 4 - Bulb (11,1 mm) �' 2-1/4" 1 A 4` 2 0 NOMINALI 1 /I (57,2 mm) ;A - MAKE-IN r * Temperature rating is ` r I 2 " 10 " I 4 indicated on Deflector. (553/166 mm) (391-9/16,7 mm) r!,_----5 ** Pipe thread connections —'sliE"\'— per ISO 7-1 can be 6 * provided on special 1/2 NPT** I WRENCH request. UPRIGHT FLATS PENDENT CROSS SECTION FIGURE 5 QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY4831)AND PENDENT(TY4931)SPRINKLERS 8.0 K-FACTOR, 1/2 INCH NPT 41e1WRENCH RECESS WRENCH RECESS (END"A"USED FOR `�ill .....„.1000/".WRENCH 1/2"NPT MODELS) t WRENCH RECESS • (END"B"USED FOR ��' 3/4"NPT MODELS) PUSH WRENCH IN TO ENSURE • ENGAGEMENT WITH SPRINKLER WRENCHING AREA FIGURE 6 FIGURE 7 W-TYPE 6 SPRINKLER W-TYPE 7 RECESSED WRENCH SPRINKLER WRENCH 4 TFP171 Page 4 of 10 Technical Design Do not attempt to compensate for g insufficient adjustment in the Escutch- Data Criteria eon Plate by under-or over-tightening the sprinkler. Re-adjust the position of Approvals The TYCO Series TY-FRB, 2.8, 4.2, the sprinkler fitting to suit. UL and C-UL Listed 5.6,and 8.0 K-factor,Upright,Pendent, Series TY-FRB Upright and Pendent FM,LPCB,and NYC Approved and Recessed Pendent Sprinklers are Sprinklers Refer to Table A and B for complete intended for fire protection systems The Series TY-FRB Pendent and approval information including corrosion- designed in accordance with the stan- Upright Sprinklers must be installed resistant status. dard installation rules recognized by in accordance with the following Maximum Working Pressure the applicable Listing or Approval instructions. Refer to Table C. agency (such as, UL Listing is based Step 1.Install Pendent sprinklers in the on the requirements of NFPA 13, and Step posin. upright thDischarge Coefficient FM Approval is based on the require- klers in the upright Install position. sprin- K=2.8 gpm/psi (40,3 Ipm/bar ) ments of FM's Loss Prevention Data K=4.2 qpm/osis(60.5lom/bary21 Sheets). Only the Style 10, 20, 30, or Step 2. With pipe-thread sealant K=5.6 gpm/psis(80,6 Ipm/barY2) 40 Recessed Escutcheon, as applica- applied to the pipe threads, hand- K=8.0 gpm/psis(115,2 Ipm/bars) ble,is to be used for recessed pendent tighten the sprinkler into the sprinkler Temperature Rating installations. fitting. Refer to Table A and B. Step 3. Tighten the sprinkler into the Installation sprinkler fitting using only the W-Type Finishes Sprinkler:Refer to Table D. The TYCO Series TY-FRB,2.8,4.2,5.6, 6 Sprinkler Wrench(Figure 6).With ref- and 8.0 K-factor,Upright,Pendent,and erence to Figures 1 through 5, apply Recessed Escutcheon:Signal or Pure the W-Type 6 Sprinkler Wrench to the White,Jet Black,Chrome Plated,or Recessed Pendent Sprinklers must p s rinkler wrench flats. Natural Brass be installed in accordance with this section. Series TY-FRB Recessed Pendent Physical Characteristics General Instructions Sprinklers Frame Bronze The Series TY-FRB Recessed Pendent Button Brass/Copper Do not install any bulb-type sprinkler Sprinklers must be installed in accor- Sealing Assembly..Beryllium Nickel w/TEFLON if the bulb is cracked or there is a loss dance with the followinginstructions. Bulb Glass of liquid from the bulb.With the sprin- Compression Screw Bronze kier held horizontally,a small air bubble Step A.After installing the Style 10,20, DeflectorsCopper/Bronze should bepresent.The diameter of the 30, or 40 MountingPlate, as applica- air (K=2.8) Bronze pP air bubble is approximately 1/16 inch ble,over the sprinkler threads and with Operation (1,6 mm)for the 135°F(57°C)and 3/32 pipe-thread sealant applied to the pipe inch(2,4 mm)for the 286°F(141°C)tem- threads,hand-tighten the sprinkler into The glass bulb contains a fluid that perature ratings. the sprinkler fitting. expands when exposed to heat.When A leak-tight 1/2 inch NPT sprinkler Step B.Tighten the sprinkler into the the rated temperature is reached, the joint should be obtained bya I in a sprinkler fittingusingonlythe W T e fluid expands sufficiently to shatter the pp y g p yp glass bulb, allowing the sprinkler to minimum to maximum torque of 7 to 7 Recessed Sprinkler Wrench (Figure activate and water to flow. 14 ft.-lbs.(9,5 to 19,0 Nm).A leak tight 7). With reference to Figures 1 to 4, 3/4 inch NPT sprinkler joint should be apply the W-Type 7 Recessed Sprinkler obtained with a torque of 10 to 20 ft.- Wrench to the sprinkler wrench flats. lbs. (13,4 to 26,8 Nm). Higher levels of Step C. After ceiling installation and torque can distort the sprinkler Inlet finishing,slide on the Style 10,20,30, with consequent leakage or impairment or 40 Closure over the Series TY-FRB of the sprinkler. Sprinkler and push the Closure over the Mounting Plate until its flange comes in contact with the ceiling. TFP171 Page 5 of 10 K TYPE TEMPERATURE BULB LIQUID NATURAL CHROME FACTOR COLOR BRASS PLATED POLYESTER*** 135°F(57°C) Orange PENDENT 155°F(68°C) Red (TY1231) and 175°F(79°C) Yellow U 1,2,3,4 UPRIGHT (TY1131) 200°F(93°C) Green 286°F(141°C) Blue 2.8 RECESSED 135°F(57°C) Orange 1/2"NPT PENDENT 155°F(68°C) Red (TY1231)* 175°F 79°C Figure 8 ( ) Yellow 200°F(93°C) Green 135°F(57°C) Orange 1,2,4 RECESSED PENDENT 155°F(68°C) Red (TY1231)** 175°F ° 79C Figure 9 ( ) Yellow 200°F(93°C) Green 135°F(57°C) Orange PENDENT 155°F(68°C) Red (TY2231) and 175°F(79°C) Yellow UPRIGHT (TY2131) I 200°F(93°C) Green 286°F(141°C) Blue 4.2 RECESSED 135°F(57°C) Orange 1/2"NPT PENDENT 155°F(68°C) Red (TY2231)* 1,2 Figure 10 175°F(79°C) Yellow 200°F(93°C) Green RECESSED 135°F(57°C) Orange PENDENT 155°F(68°C) Red (TY2231)** 175°F 79° Figure 11 ( C) Yellow 200°F(93°C) Green NOTES: 1. Listed by Underwriters Laboratories,Inc.,(UL)as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories,Inc.,for use in Canada(C-UL)as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers. 4. Approved by the City of New York under MEA 354-01-E. 5. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers. *Installed with Style 10(1/2"NPT)or Style 40(3/4"NPT)3/4"Total Adjustment Recessed Escutcheon,as applicable. **Installed with Style 20(1/2"NPT)or Style 30(3/4"NPT)1/2"Total Adjustment Recessed Escutcheon,as applicable. ***Frame and Deflector only. N/A:Not Available TABLE A LABORATORY LISTINGS AND APPROVALS FOR 2.8 AND 4.2 K-FACTOR SPRINKLERS TFP171 Page 6 of 10 SPRINKLER FINISH(See Note 8) K BULB LIQUID NATURAL I CHROME POLYESTER*** LEAD TYPE TEMPERATURE FACTOR COLOR BRASS PLATED COATED 135°F(57°C) Orange PENDENT 155°F(68°C) Red (TY3231) and 175°F(79°C) Yellow 1,2,3,4,5,6,7 1,2,3,5 UPRIGHT 200°F(93°C) Green (TY3131) 286°F(141°C) Blue 135°F(57°C) Orange RECESSED 155°F(68°C) Red N/A 5.6 PENDENT 175°F(79°C) Yellow 1,2,4,5 1/2"NPT (TY3231)* Green Figure 12 200°F(93°C) 286°F(141°C) Blue 135°F(57°C) Orange RECESSED 155°F(68°C) Red N/A PENDENT 175°F(79°C) Yellow 1,2,3,4,5 (TY3231)** Green Figure 13 200°F(93°C) 286°F(141°C) Blue 135°F(57°C) Orange PENDENT 155°F(68°C) Red (TY4231) and 175°F(79°C) Yellow 1,2,3,4,5,6,7 1,2,5 UPRIGHT 200°F(93°C) Green (TY4131) 286°F(141°C) Blue 135°F(57°C) Orange RECESSED 155°F(68°C) Red N/A 8.0 PENDENT 175°F(79°C) Yellow 1,2,5 3/4"NPT (TY4231)* Green Figure 14 200°F(93°C) 286°F(141°C) Blue 135°F(57°C) Orange RECESSED 155°F(68°C) Red N/A PENDENT 175°F(79°C) Yellow 1,2,3,5 (TY4231)** Green Figure 15 200°F(93°C) 286°F(141°C) Blue • 135°F(57°C) Orange PENDENT(TY4931) 155°F(68°C) Red 1,2,4,5,6 1,2,5 1/28.0"NPT and 175°F(79°C) Yellow UPRIGHT 200°F(93°C) Green (TY4831) 286°F(141°C) Blue NOTES: 1. Listed by Underwriters Laboratories,Inc.,(UL)as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories,Inc.,for use in Canada(C-UL)as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers. 4. Approved by the Loss Prevention Certification Board(LPCB Ref.No.007k/04)as Quick Response Sprinklers.However,LPCB does not rate the thermal sensitivity of recessed sprinklers. 5. Approved by the City of New York under MEA 354-01-E. 6. VdS Approved(For details,contact Tyco Fire Suppression&Building Products,Enschede,Netherlands,Tel.31-53-428-4444/Fax 31-53-428-3377.) 7. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/06)as Quick Response Sprinklers. 8. Where Polyester Coated and Lead-Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers. Where Lead-Coated Sprinklers are noted to be FM Approved,the sprinklers are FM Approved as a Corrosion-Resistant Sprinklers. 'Installed with Style 10(1/2"NPT)or Style 40(3/4"NPT)3/4"Total Adjustment Recessed Escutcheon,as applicable. "`Installed with Style 20(1/2"NPT)or Style 30(3/4"NPT)1/2"Total Adjustment Recessed Escutcheon,as applicable. **'Frame and Deflector only. N/A:Not Available TABLE B LABORATORY LISTINGS AND APPROVALS FOR 5.6 AND 8.0 K-FACTOR SPRINKLERS 4 TFP171 Page 7 of 10 SPRINKLER FINISH KNATURAL CHROME TYPE FACTOR BRASS PLATED I POLYESTER LEAD COATED PENDENT(TY1231) and 2.8 UPRIGHT(TY1131) 1/2"NPT 175 PSI(12,1 BAR) N/A RECESSED PENDENT(TY1231) PENDENT(TY2231) and 4.2 UPRIGHT(TY2131) _______>1/2"NPT 175 PSI(12,1 BAR) N/A RECESSED PENDENT(TY2231) PENDENT(TY3231) and 5.6 UPRIGHT(TY3131) 250 PSI(17,2 BAR) 1/2"NPT OR 175 PSI(12,1 BAR) RECESSED (SEE NOTE 1) PENDENT(TY3231) PENDENT(TY4231) and 175 PSI 8.0 UPRIGHT(TY4131) (12,1 BAR) 3/4"NPT 175 PSI(12,1 BAR) RECESSED PENDENT(TY4231) N/A 8.0 PENDENT(TY4931) 1/2"NPT UPRIGHT(TY4831)and 175 PSI(12,1 BAR) 175 PSI NOTES: (12,1 BAR) 1. The maximum working pressure of 250 psi(17,2 bar)only applies to the Listing by Underwriters Laboratories Inc.(UL);the Listing by Under- writers Laboratories,Inc.for use in Canada(C-UL);and,the Approval by the City of New York. TABLE C MAXIMUM WORKING PRESSURE Care and have not operated,should be replaced Care must be exercised to avoid if they cannot be completely cleaned damage to the sprinklers -before, Maintenance by wiping the sprinkler with a cloth or during, and after installation. Sprin- by brushing it with a soft bristle brush. The TYCO Series TY-FRB must be Care must be exercised to avoid klers damaged by dropping, striking, maintained and serviced in accordance damage to the sprinklers before, bewrreplaced. replace mt sprin- with this section, be re p anyage,or the during, and after installation. Sprin- kier that has a cracked bulb or that has Before closing a fire protection system klers damaged by dropping, striking, lost liquid from its bulb. (Ref. Installa- wrench twist/slippage,or the like,must main control valve for maintenance tion Section). be replaced. Also, replace any sprin- Initial and frequent visual inspections of work on the fire protection system that it controls, obtain permission to kler that has a cracked bulb or that has random samples are recommended for lost liquid from its bulb. (Ref. Installa- systems from the proper authorities tion Section.) corrosion-resistant sprinklers to verify shut down the affected fire protection and notify all personnel who may be The owner is responsible for the the integrity of the corrosion-resistant affected by this action. inspection,testing,and maintenance of annuamateria.inspectionsof cper NFPA Thereafter,2should annual per 25 should Absence of the outer piece of an their fire protection system and devices suffice. in compliance with this document, as Inspections of corrosion-resistant escutcheon, which is used to cover a clearance hole, can delay sprinkler well as with the applicable standards operation in a fire situation. of the National Fire Protection Asso- sprinklers are recommended at close ciation e. NFPA 25), in addition to range, instead of from the floor level Sprinklers which are found to ( g.' per NFPA. Inspection at close range leaking or exhibiting visible signs be the standards of any other authorities 9 having jurisdiction.Contact the install- can betterdidetermine the theoexactm integ- corrosion must be replaced. ing contractor or sprinkler manufac- kler condition andithe sistant m integ- corrosion , Automatic sprinklers must never be turer regarding any questions. whrity of the corrosion-resistant material, painted, plated, coated, or other- Automatic sprinkler systems are rec- condichtions can b r affected by the corrosive wise altered after leaving the factory. ommended to be inspected, tested, conditions present. Modified sprinklers must be replaced. and maintained by a qualified Inspec- Sprinklers that have been exposed to tion Service in accordance with local corrosive products of combustion,but requirements and/or national codes. TFP171 Page 8 of 10 2-7/8"DIA. 2-7/8"DIA. - 5/8±1/4" (73,0 mm1/2±1/8" ) 3/4"(19,1 mm) (73,0 mm) 1/2"(12,7 mm) (15,9±6,4 mm) 1/4"(6,4 mm) (12,7±3,2 mm) 2-1/4"DIA. 1/4"(6,4 mm) 2-1/4"DIA. / FACE OF (57,2 mm) MOUNTING / FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING / I 1/8" 1/8" (3,2 mm) / (3,2 mm)li T —� �� �l/.Ti. at_ MI / t ��`�J MOUNTING lir SURFACE ,�r MOUNTING . SURFACE .�•��� i/teI 1-5/16"(33,3 mm) SERIES 1-5/16"(33,3 mm) CLOSURE SERIES CLOSURE TY FRB 1 1/16"(27,0 mm) TY-FRB 13/16"(20,6 mm) FIGURE 8 FIGURE 9 SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE E2RECESSED/2 INCH TOTAL SED ESCUTCHEONMENT STYLE 10 RECESSED ESCUTCHEON2.8 STYLE 0FACTOR, 1/ ES1CH NPT 2.8 K-FACTOR, 1/2 INCH NPT 2-7/8"DIA. 2 7/8"DIA. (73,0 mm) (73,0 mm) 3/4"(19,1 mm) 1/2±1/8" 1/2"(12,7 mm) 5/8±1/4" 1/4"(6,4 mm) (15,9±6,4 mm) 1/4"(6,4 mm) (12,7±3,2 mm) 2-1/4"DIA. 2 1/4"DIA. (57,2 mm) 1 / FACE OF (57,2 mm) MOUNTING / FACE OF I MOUNTING SPRINKLER PLATE SPRINKLER PLATEFITTING FITTING I 1/8" 1/8" / (3,2 mm) 1/8" (3,2 pliii fir, =1 I,I I igi_t_ 111 �� MOUNTING RI SURFACE ,Ir MOUNTING • SURFACE 1-1/4"(31,8 mm) SERIES 1-1/4"(31,8 mm) CLOSURE SERIES CLOSURE TY-FRB 1"(25,4 mm) TY-FRB 3/4"(19,1 mm) FIGURE 10 FIGURE 11 SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH WOO-PEE 1/2 INCH TOTAL SED SCUTCHEONMENT STYLE 10 RECESSED ESCUTCHEON STY4,2 K0-FACTOR, 1/2 INCH NPT 4.2 K-FACTOR, 1/2 INCH NPT TFP171 Page 9 of 10 2-7/8"DIA. 2-7/8"DIA. 5/8±1/4" (73,0 mm) 3/4"(19,1 mm) (73,0 mm (15,9±6,4 mm) 2-1/4"DIA. 1/4"(6,4 mm) 1/211/8" ) 1/2"(12,7 mm) / FACE OF (57,2 mm) (12,7±3,2 mm) 2.1/4"DIA. 1/4"(6,4 mm) SPRINKLER MOUNTING / FACE OF (57,2 mm) i FITTING PLATE SPRINKLER I MOUNTING / FITTING PLATE 1/8" (3,2 mm) ► 1/8" 3,2( mm) 4-7/ ,1v MOUNTING 110SURFACE ��;_. SURFACE PI - CLOSURE SERIES 1-1/4"(31,8 mm) CLOSURE SERIES 1-1/4"(31,8 mm) TY-FRB 3/4"(19,1 mm) TY-FRB FIGURE 12 1"(25,4 mm) SERIES TY-FRB RECESSED PENDENT SERIES FIGURE 13 TY-FRB RECESSED PENENT WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 5.6 K-FACTOR, 1/2 INCH NPT 5.6 K-FACTOR, 1/2 INCH NPT 2-7/8"DIA. 5/8±1/4" (73,0 mm) 3/4"(19,1 mm) 2-7/8"DIA. (15,9±6,4 mm) 2-1/4"DIA. 1/4"(6,4 mm) 1/2±1/8" (73,0 mm) 1/2"(12,7 mm) / (57,2 mm) (12,7±3,2 mm) 2-1/4"DIA. 1/4"(6,4 mm) FACE OF MOUNTING / (57,2 mm) i SPRINKLER PLATE FACE OF MOUNTING FITTING SPRINKLER PLATE / 1/8" FITTING (3,2 mm) (3,2 3,2 mm) 141 ' 1777 1air. . , 'ill• MUNTING SO gill. URFACE �I r SURFACE \ CLOSURE SERIES 1-5/16"(33,3 mm) CLOSURE SERIES 1-5/16"(33,3 mm) TY-FRB 13/16"(20,6 mm) TY-FRB FIGURE 14 1-1/16"(27,0 mm) SERIES TY-FRB RECESSED PENDENTFIGURE 15 TY-FRB RECESSED PENDENT WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH SERIES TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON 8.0 K-FACTOR,3/4 INCH NPT 8.0 K-FACTOR,3/4 INCH NPT TFP171 Page 10 of 10 P/N 57 - XXX- X- XXX SIN SPRINKLERFINISH TEMRAT PERATUNGSRE 330 2.8K UPRIGHT(1/2"NPT) TY1131 1 NATURAL BRASS 135 135°F(57°C) 331 2.8K PENDENT(1/2"NPT) TY1231 3 PURE WHITE 155 155°F(68°C) (RAL9010)1 340 4.2K UPRIGHT(1/2"NPT) TY2131 4 SIGNAL WHITE 175 175°F(79°C) (RAL9003) 341 4.2K PENDENT(1/2"NPT) TY2231 5 JET BLACK 200 200°F(93°C) POLYESTER(RAL9005)2 370 5.6K UPRIGHT(1/2"NPT) TY3131 7 LEAD COATED 286 286°F(141°C) 371 5.6K PENDENT(1/2"NPT) TY3231 9 CHROME PLATED 390 8.0K UPRIGHT(3/4"NPT) TY4131 NOTES: 1. Eastern Hemisphere sales only. 391 8.0K PENDENT(3/4"NPT) TY4231 2. Available 200°F(93IC);requires lead time and to mafacture. 155°F nuand . 360 8.0K UPRIGHT(1/2"NPT) TY4831° 361 8.0K PENDENT(1/2"NPT) TY4931° TABLE D SERIES TY-F PAPENDENT RT NUMBER DELECTION UPRIGHT SPRINKLERS Limited Ordering Warranty Procedure For warranty terms and conditions,visit Contact your local distributor for www.tyco-fire.com. availability. When placing an order, indicate the full product name and Part Number(P/N). Sprinkler Assemblies with NPT Thread Connections Specify: Series TY-FRB (Specify SIN), (specify K-factor), (specify Pendent or Upright)Sprinkler(specify)temperature rating, (specify)finish or coating, P/N (specify from Table D) Recessed Escutcheon Specify: Style (10, 20, 30, or 40) Recessed Escutcheon with (specify") finish,P/N(specify*) Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387 Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001 ' Refer to Technical Data Sheet TFP770 GLOBAL HEADQUARTERS 11400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright©2015 Tyco Fire Products,LP. All rights reserved. tyCO TEFLON is trademark of The DuPont Corporation. Fire Protection Products , FireLock® V27, K5.6 Models V2709, 40.11V2710 4taUIicr0. Standard Spray Technical Specifications: Horizontal and Recessed Horizontal Sidewall Standard and Quick Response Models:V2709, V2710 , .„., Style: Horizontal Sidewall or Recessed Horizontal Sidewall . ,° A Nominal Orifice Size 1"/13 mm a � f� �, " K Factor:5.6 Imp./8.1 S.L1 Nominal Thread Size: W/15 mm V2709/V2710 V2709/V2710 Standard Horizontal Recessed Horizontal Max.Working Pressure: Sidewall Sidewall • 175 psi/1200 kPa (FM) • 250 psi/1725 kPa (UL) Approvals/Listings: Factory Hydrostatic Test: 100% @ 500 psi/3450 kPa O <1> LPCBJ Min. Operating Pressure: LIMO See Victaulic Publication 10.01 for more details. • 7 psi/48 kPa Temperature Rating:See chart on page 3 1 For K-Factor when pressure is measured in Bar,multiply S.I.units by 10.0. Product Description: These Model V27, standard spray horizontal sidewall / sprinklers are designed for up to ordinary Hazard per 1:1 NFPA 13, and can be used for standard or recessed installations. The design provides a crescent-shaped water discharge pattern for installation along a wall or under a beam or ceiling. It is cast with a hex-shaped wrench boss to allow easy tightening from many angles, reducing assembly effort. This sprinkler is available in various temperature ratings(see chart on page 3) U and finishes to meet many design requirements. The V� recessed pendent should be utilized with a Model V27 al ! e recessed escutcheon which provides up to 3/4"/19 mm of �'--��` adjustments. � � '� 0 Coverage I 1110 For coverage area and sprinkler placement, refer to NFPA 13 or applicable standard. Exaggerated for clarity Job/Owner Engineer System No. Spec Section Location Paragraph Contractor Approved Submitted By Date Date victaulic.com I Sprinklers I FireLock®I K5.6, V27 I Publication 40.11 40.11 2545 Rev..1 Updated 07/2014 ©2014 Victaulic Company.All rights reserved. 1 ✓ctauliie i victaulic.com I Sprinklers I FireLock°I K5.6,V27 I Publication 40.11 Material Specifications: Accessories Horizontal Deflector:Commercial bronze per Installation Wrench: UNS C220OO ❑ Open End:V27 Bulb:Glass with glycerin solution ❑ Recessed:V27-2 Bulb Nominal Diameter: ❑ Standard: 5.0 mm Sprinkler Finishes: ❑✓ Quick Response:3.0 mm El Plain Brass Load Screw: Low Silicon bronze per UNS C651O0 ❑ Chrome plated Pip Cap: Low Silicon bronze per UNS C651O0 ✓❑ White painted3 Spring: Beryllium nickel ❑ Flat black painted3 Seal:Teflon2 tape ❑ Custom painted3 Frame: Die cast brass 65-30 ❑ Proprietary Nickel/Teflon2 coating3 Lodgement Spring: Stainless steel per UNS S30200 ❑ VC-2504 155, 200, 286 SR Only: ❑ Wax3 For cabinets and other accessories refer to separate sheet. NOTE:Weather resistant recessed escutcheon available upon request. 2 Teflon is a registered trademark of Dupont Co. 3 UL Listed for corrosion resistance. UL Listed and FM Approved for corrosion resistance. 40.11 2545 Rev.J Updated 07/2014 ©2014 Victaulic Company.All rights reserved. �Ct:9UliC victaulic.com 2 r victaulic.com I Sprinklers I FireLock®I K5.6,V27 I Publication 40.11 Approvals/Listings: APPROVALS/LISTINGS Model V2709 V2709 Recessed V2710 V2710 Recessed V2710 Recessed Orifice Size(inches) 1/2" 1/2" ,/z" '/z° h° Orifice Size(mm) 13 13 13 13 13 Nominal K Factor Imperial 5.6 5.6 5.6 5.6 5.6 Nominal K Factor SI, 8.1 8.1 8.1 8.1 8.1 Response Standard Standard Quick Quick Quick Recessed Recessed Recessed Deflector Type Horizontal Horizontal Horizontal Horizontal Horizontal SidewalI Sidewall" Sidewall Sidewall(up to Sidewall(up to 16"adjustment) 3/a"adjustment) Approved Temperature Ratings F,/C, 135°F/57°C 155°F/68°C 135°F/57°C 135°F/57°C 135°F/57°C 135°F/57°C cULus 175°F/79°C 155°F/68°C 155°F/68°C 155°F/68°C 155°F/68°C 200.F/93°C 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C 286°F/141°C 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C 360°F/182°C 286°F/141°C 135°F/57°C 155°F/68°C 135°F/57°C 135°F/57°C 135°F/57°C FM 6 175°F/79°C 155°F/68°C 155°F/68°C 155°F/68°C 200°F/93°C 175°F/79°C 175°F/79°C 175°F/79°C None 286°F/141°C 200°F/93°C 200°F/93°C 200°F/93°C 360°F/182°C 286°F/141°C 135°F/57°C 155°F/68°C 135°F/57°C 135°F/57°C 135°F/57°C 135°F/57°C NYC/MEA 6#62-99-E 175°F/79°C 155°F/68°C 155°F/68°C 155°F/68°C 155°F/68°C 200°F/93°C 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C 286°F/141°C 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C 360°F/182°C 286°F/141°C 135°F/57°C 155°F/68°C 135°F/57°C 135°F/57°C 135°F/57°C 135°F/57°C CSFM 6#7690-0531:112 175°F/79°G 155°F/68°C 155°F/68°C 155°F/68°C 155°F/68°C 200°F/93°C 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C 286°F/141°C 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C 360°F/182°C 286°F/141°C 135°F/57°C 155°F/68°C 135°F/57°C LPCB6104b/01 175°F/79°C 155°F/68°C None 175°F/79°C None None 6104b/02 200°F/93°C 286°F/141°C 200°F/93°C 360°F/182°C 286°F/141°C 135°F/57°C 155°F/68°C 135°F/57°C 135°F/57°C 135°F/57°C VNIIPO 175°F/79°C 155°F/68°C 155°F/68°C 155°F/68°C 200°F/93°C 175°F/79°C 175°F/79°C 175°F/79°C None 286°F/141°C 200°F/93°C 200°F/93°C 200°F/93°C 360°F/182°C 286°F/141°C CCCf ZSTBS None None None None 155°F/68°C 5 For K Factor when pressure is measured in Bar,multiply S.I.units by 10.0 6 Light Hazard ONLY Note:Listings and Approvals as of printing.All are approved open. 40.11 2545 Rev.J Updated 07/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 3 jctaulic° victaulic.com I Sprinklers I FireLock®I K5.6,V27 I Publication 40.11 Dimensions: r 3"/89 mm 274"/57 mm I I■ {b"/ 5 " 1Y.. i'-' IRI I �1 I T in Standard HSW—V2709,V2710 11/16"/ '17 mm (.23/16"/ 11/16" 11/16"/ 56 mm 43 mm 30 mm i , Finished Ceiling i7 Finished Ceiling o4-12"/102-305 mm 4-127102-305 mm Per NFPA In Per NFPA IN - J7--- -6�1w 2751 mm 23/8"/60 mm 215/16"/ C Il 2751 mm 23/8"/60 mm 7 �,l • Min Hole Max.Hole 75 mm �• Min Hole Max.Hole I ,__1 ! P Finished Surface Finished Surfac- Typical Wall +1 Typical Wall MAXIMUM EXTENSION MAXIMUM RECESS /"Adjustment Recessed—V2709,V2710(drawing not to scale) 15/16"/L 24 mm x_23/16"/ iii9/16"/18 mm 7/16" 5/16" 56 mm 37 mm 37mm CO AWE it ar AffiNtrdirdrat finished Ceiling Finished Ceiling 4-12/1 2-305 mm 77 4-12'/102-305 mm401 Per iNFPA Per NFPA 11 J——__ • �I _1,�w 2751 mm 23/8"/60 mm 215/16•/ C 2/51mle 23/8/60 mm '1II ► ■I Min.Hole Max Hole 75 mm �_ Min.Hole Max Hole 1 MI Ii Finished Surface I�II Finished Surface I�I -.1 l.- Typical Wall +F LTypical Wall MAXIMUM EXTENSION MAXIMUM RECESS 3/a"Adjustment Recessed—V2709,V2710(drawing not to scale) 40.11 2545 Rev..1 Updated 07/2014 ©2014 Victaulic Company.All rights reserved. �CtaUliGP victaulic.com 4 vDistributionictaulic.comPatterns:I Sprinklers I FireLock®ISidewall K5.6,V27 I Publication Sidewall 40.11 Models ,V2710 K5.6 Standard Horizontal V2709and Recessed Horizontal Distribution Patterns-Trajectory r 3.Om I ••� � .,■• •.•*L __ f, g • 1 2.4m f ._ ....._ 7 psi �..�... 6' 3 •• 4'' 48 kPa 1.8m �f ,,....._....�� . ._.. ..,. . 15 psi ., ..... $, • 1' �4 103 kPa 4� 1.2 m • -.. „. E E 30 psi y ' .... ..,.- X„ 4 207 kPa M . 0,6 m i. • 0 2' 4' 6' 8' 10' 12' 14' 16' 18' 20' 22' 24' 26' 0,6m 1,2m 1,8m 2Am 3.Om 3.7m 4.3m 4.9m 5.5m 6.1 m 6.7m 7.3m 7.9m Models V2709,V2710 K5.6 Standard and Recessed Horizontal Sidewall Distribution Patterns-Plan View 2' 4' 6' 8' 10' ' ' ' ' ' ' ' ' ' 0.6m 1.2m 1.8m 2.4m 3.Om 3172r.' 712m 4.314m' 4.9m165.518m' 6.120m 6.227m 7.324m 7.9m268.528m 0' ] '____ ---_ +-._.... + 2, i ■ 0.6m _..._ ---t ■1.2m ■ .. ;i_.. Ips I k 48 kPa 1.8 m i 15 psi --_. -+ •• ----._ r. .__. _. --■ 103kPa 2.4m ••' F ■ 30m ..i •..r..�..�. r..•�•'�•• ,... -. ...._ - psi 2070kPa 3.7 m 14' !. • ••♦ imam,■■■■■■■■ ■■r--------------------S . 4.9 m NOTES: A.Data shown is approximate and can vary due to differences in installation. B.These graphs illustrate approximate trajectories,floor-wetting,and wall-wetting patterns for these specific Victaulic FireLock Automatic Sprinklers.They are provided as information for guidance in avoiding obstructions to sprinklers and should not be used as minimum sprinkler spacing rules for installation.Refer to the appropriate NFPA National Fire Code or the Authority Having Jurisdiction for specific information regarding obstructions,spacing limitations and area of coverage requirements.Failure to follow these guidelines could adversely affect the performance of the sprinkler and will void all Listings,Approvals and Warranties. 40.11 2545 Rev.J Updated 07/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 5 ✓otauliC 4 victaulic.com I Sprinklers I FireLocke I K5.6,V27 I Publication 40.11 Ratings: Available Wrenches: All glass bulbs are rated for temperatures from -67°F (-55°C)to those shown in the table below. V27-2 V27 Recessed Open End Temperature-*PT No escutcheon ✓ ✓ Maximum With escutcheon / - Sprinkler Victaulic Nominal Ambient Glass Temperature Part Temperature Temperature Bulb Classification Identification Rating Allowed Color Ordinary A 135°F/57°C 100°F/38°C Orange -> Ordinary C 155°F/68°C 100°F/38°C Red Intermediate E 175°F/79°C 150°F/65°C Yellow Intermediate F 200°F/93°C 150°F/65°C Green High J 286°F/141°C 225°F/107°C Blue Extra High 7 K 360°F/182°C 300°F/149°C Purple - M Open - No Bulb 7 Standard response only. Oc •., • Always read and understand installation,care,and maintenance instructions,supplied with each box of sprin- klers,before proceeding with installation of any sprinklers. • Always wear safety glasses and foot protection. • Depressurize and drain the piping system before attempting to install,remove,or adjust any Victaulic piping products. • Installation rules,especially those governing obstruction,must be strictly followed. • Painting,plating,or any re-coating of sprinklers(other than that supplied by Victaulic)is not allowed. 43 Failure to follow these instructions could result in serious personal injury and/or property damage. The owner is responsible for maintaining the fire protection system and devices in proper operating condition.For minimum maintenance and inspection requirements,refer to the current National Fire Protection Association pam- phlet that describes care and maintenance of sprinkler systems. In addition,the authority having jurisdiction may have additional maintenance,testing,and inspection requirements that must be followed. If you need additional copies of this publication,or if you have any questions about the safe installation of this product,contact Victaulic World Headquarters:P.O.Box 31,Easton,Pennsylvania 18044-0031 USA,Telephone: 9 001-610-559-3300. Installation Note Reference should always be made to the 1-40 Victaulic FireLock Automatic Sprinklers This product shall be manufactured by Victaulic or to Victaulic specifications.All products Installation and Maintenance Sheet for the product you are installing.This installation sheet to be installed in accordance with current Victaulic installation/assembly instructions. is included with each shipment of Victaulic products for complete installation and assembly Victaulic reserves the right to change product specifications,designs and standard data,and is available in PDF format on our website at victaulic.com. equipment without notice and without incurring obligations. Warranty Trademarks Refer to the Warranty section of the current Price List or contact Victaulic for details. Victaulic is a registered trademark of Victaulic Company. 40.11 2545 Rev.J Updated 07/2014 ©2014 Victaulic Company.All rights reserved. jctauliCP victaulic.com 6 FIRE PROTECTION PRODUCTS-AUTOMATIC SPRINKLERS 40.47 V27, K4.9 cOUS SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS Residential Pendent and Recessed Pendent V274O QUICK RESPONSEOA This Model V27 residential sprinkler is designed to meet the requirements of NFPA 13, 13D and 13R for residential use in a variety of room sizes,depending upon available operating pressure and room configuration.The design incorporates state-of-the-art,heat responsive, frangible glass bulb design(quick response)for prompt,precise operation. T.' The die cast frame is more streamlined and attractive than traditional sand cast frames. It is cast with a hex-shaped wrench boss to allow easy tightening from many angles, g. reducing assembly effort.This sprinkler is available in various finishes to meet many design —. requirements. PENDENT (V2740) SPRINKLER OPERATION: The operating mechanism is a frangible glass bulb which contains a heat responsive liquid.During a fire,the ambient temperature rises causing the liquid in the bulb to expand.When the ambient temperature reaches the rated temperature of the sprinkler,the bulb shatters.As a result,the waterway is cleared of all sealing parts and water is discharged towards the deflector.The deflector is designed to distribute the water in a pattern that is most effective in controlling the fire. COVERAGE: Residential spray coverage up to 20 feet x 20 feet/6.1 m x 6.1 m room sizes per NFPA. TECHNICAL SPECIFICATIONS: Model:V2740 ACCESSORIES Style:Pendent and Recessed Pendent Installation Wrench: Nominal Orifice Size:7/16"/12 mm • Open End:V27 , K-Factor:4.9 Imp./7.1 S.I.^for room sizes up to • Recessed:V27-1 20'/6.1 m Sprinkler Finishes: � Nominal Thread Size:h"NPT/15mm • Plain brass Max.Working Pressure: 175psi/1200kPa • Chrome plated Factory Hydrostatic Test:100%@ 500 psi/ • White painted** � 1 I 3450kPa • Custom painted** �)11) Min.Operating Pressure:7 psi/48 kPa For escutcheons,cabinets and other accessories iJTemperature Rating:See chart on page 3 refer to separate sheet. 4fj7A For K-Factor when pressure is measured in U� MATERIAL SPECIFICATIONS Bar,multiply S.I.units by 10.0. Pendent Deflector:Bronze per UNS C51000 *Teflon is a registered trademark of Bulb:Glass with glycerin solution Dupont Co. Bulb Nominal Diameter: I i • Quick Response:3.0mm **UL Listed for corrosion resistance in all configurations. lt Load Screw:Bronze per UNS C65100 NOTE:Weather resistant recessed escutcheon Pip Cap:Bronze per UNS C65100 available upon request. '1. .AP. Seal:Teflon*tape 'cot Frame:Die cast brass 65-30 Exaggerated for clarity JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date Approved Date www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2013 VICTAULIC COMPANY.ALL RIGHTS RESERVED. jcf.aL.1I1 d REV_E 40.47_1 A FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS 40.47 V27, K4.9 Residential Pendent and Recessed Pendent V2740 QUICK RESPONSE APPROVALS/LISTINGS Orifice Nominal Approved Temperature Ratings Model Size K-Factor Response Deflector Type "F/`C Inches Imperial mm 5.1.^ cUlus r7A6 4.9 155175 V2740 12 I 71 Quick Pendent 68,79 rAs 4.9 / Recessed Pendent 155,175 V2740Quick 12 71 Up to'h Adjustment i 68,79 > V2740 r4s 4'9 l Quick ? Recessed Pendent 155,175 12 7.1 I Up to 14"Adjustment# 68,79 #Listings and approval as of printing. A For K Factor when pressure is measured in Bar,multiply S.I.units by 10.0. *For 12'x 12'to 20'x 20'rooms #For 12'x 12'to 18'x 18'rooms RATINGS All glass bulbs are rated for temperatures from—67°F/-55°C to those shown in table below. Temperature-°F/°C Victaulic Sprinkler Temperature Part Nominal Temperature Maximum Ambient Classification Identification Rating Temperature Allowed Glass Bulb Color Ordinary 3 C 58 108 Red Intermediate ' E t 175 150 Yellow 79 65 ORDERING INFORMATION Please specify the following when ordering: Sprinkler Model Number Style Temperature Rating K-Factor Thread Size Quantity Sprinkler Finish Escutcheon Finish Wrench Model Number www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2013 VICTAULIC COMPANY.ALL RIGHTS RESERVED. jotaulace 40.47 2 REV_E i FIRE PROTECTION PRODUCTS-AUTOMATIC SPRINKLERS 40.47 V27, K4.9 Residential Pendent and Recessed Pendent V2740 QUICK RESPONSE WARNING • Always read and understand installation,care,and maintenance instructions,supplied with each box of sprinklers,before proceeding 0 with installation of any sprinklers. • Always wear safety glasses and foot protection. • Depressurize and drain the piping system before attempting to install,remove,or adjust any Victaulic piping products. • Installation rules,especially those governing obstruction,must be strictly followed. • Painting,plating,or any re-coating of sprinklers(other than that 0 supplied by Victaulic)is not allowed. Failure to follow these instructions could result in serious personal injury and/or property damage. The owner is responsible for maintaining the fire protection system and devices in proper operating condition. For minimum maintenance and inspection requirements,refer to the current National Fire Protection Association pamphlet that describes care and maintenance of sprinkler systems. In addition,the authority having jurisdiction may have addi- tional maintenance,testing,and inspection requirements that must be -7followed. If you need additional copies of this publication,or if you have any questions about the safe installation of this product,contact Victaulic World Headquarters:P.O.Box 31,Easton,Pennsylvania 18044-0031 USA,Telephone:001-610-559-3300. AVAILABLE WRENCHES Sprinkler Type Open End Recessed V2740 Pendent V27 V27-2 V2740 Recessed Pendent° — i V27-2 www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2013 VICTAULIC COMPANY.ALL RIGHTS RESERVED. ICtauI1�. REV_E 40.47_3 A A 4 FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS 40.47 V27, K4.9 Residential Pendent and Recessed Pendent V2740 QUICK RESPONSE DIMENSIONS Standard Pendent—V2740 1 m_.. >•s 2/s"/ Erl 60 mm 41 mm II L1Y,d/J 30 mm Maximum Recess—'h"Adjustment Recessed—V2740(drawing not to scale) 23V/60 mm ` Max.Hole 2"/51 mm Min.Hole 17 mm /IMPM Typical Ceiling Tile ZirtIONTypical Ceiling Tile `,'r 43�m" 3Sn"/ m Finished Surface 30 mm � Finished Surface II MAXIMUM RECESS 2151r"/ 75 mm MAXIMUM EXTENSION Maximum Recess—3/4"Adjustment Recessed—V2740(drawing not to scale) 234"/60 mm Max.Hole 2"/51 mm Min.Hole i vAei " l it ' `"/ 'Hc"/ y � 37 mm ■M 24 mm 18 mm Mg ui I Moll,Typical Ceiling Tile ! � Irtil,lP�Typical �9 1 ..J_ II Ceilin Tile � � 44b"/ N..� 24 mm MM 43 mm/ ��� Finished Surface n Finished Surface MAXIMUM RECESS 2'35x% 75 mm MAXIMUM EXTENSION www.victaulic.com VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2013 VICTAULIC COMPANY.ALL RIGHTS RESERVED. ICtauI1c• 40.47_4 REV_E i FIRE PROTECTION PRODUCTS-AUTOMATIC SPRINKLERS 40.47 V27, K4.9 Residential Pendent and Recessed Pendent V2740 QUICK RESPONSE ROOM SIZE Victaulic V2740,4.9 K-Factor Pendent Sprinkler For Ceiling types refer to NFPA 13, 13R or 13D 2013 Editions Max. Ordinary Temp Intermediate Temp Coverage Rating Rating Deflector to Installation Minimum Area'', 155-F/68-C 175"F/79"C Ceiling Type Spacing Flow,' Pressure" Flow" Pressure" Ft.x Ft. GPM PSI GPM PSI Ft. m x m L/min bar L/min bar m 12X12 I 13 ! 7.0 E 13 1 7.0 37X3.7 49.2 0.48, . 492 d a48 14 X 14 13 7.0 13 1 7.0 t 43X4.3 49.2 0.48 1 492 , 0.48 3/4 .2 - -> 16 X 16 1 13 7.0 13 70 Escutcheon)d 8.0 49X49 49.2 048 i 492 1 13A6to4inch or non-recessed 2.4._ ,. _ _ L. 048 per NFPA 13,13R 18X18 1 17 I 12 17 ..x.._.12 1 or13D 5.5 X 5.5 64.3 0.83 I 64.3 i 0.83 I 20 X 20 I 20 16.7 20 I 16.7 6.1 X6.1 , 75.7 1.15 j 75.7 1.15 I (a)For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b)For NFPA 13 residential applications,the greater of 0.1gpm/ft2 over the design area of the flow in accordance with the criteria in the table must be used. (c) For 20 x 20 Coverage Area-Y2"Maximum Recess www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2013 VICTAULIC COMPANY.ALL RIGHTS RESERVED. jetaulid REV E 40.47_5 d l FIRE PROTECTION PRODUCTS-AUTOMATIC SPRINKLERS 40.47 V27, K4,9 Residential Pendent and Recessed Pendent V2740 QUICK RESPONSE NOMINAL WETTING PATTERNS Model V2740 K4.9 residential pendent and recessed pendent(3/a") 13 GPM/49.2 LPM-16'x 16'/4.9 x 4.9 m coverage area „ .. B' 7 21 ,Y 123, « r.-w-�. 0.9m ,3 ..:. .„. .. _ f _, ...,�.«. 2 g 6 4 3 0 06m � w"�sm ial, 13ma ohm � 0.3m ,.""�06m 12ro �OFSOOM Model V2740 K4.9 residential pendent and recessed pendent(3/a') 17 GPM/64.3 LPM-18'x 18'/5.5 x 5.5m coverage area s 7'r. 5' 'i--- 154 I. i 125 _.. _.. ." .... ffi 094'i..,-»- j "..,.a ...;,, 09M' --^` «6 2.4m tam 18m 13m Obm I '*«'*• "•- .,.,..w.N"I 1' ...-«' 1.8m ' ....,,i; 12'6'0 CL OFROOM See notes on next page. www.victaulic.com xiCtaUlid VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2013 VICTAULIC COMPANY.ALL RIGHTS RESERVED. 40.47_6 REV_E • FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS 40.47 127, K4.9 Residential Pendent and Recessed Pendent V2740 QUICK RESPONSE NOMINAL WETTING PATTERNS Model V2740 K4.9 residential pendent and recessed pendent('h") 20 GPM/75.7 LPM—20'x 20'/6.1 x 6.1 m coverage area 8 0.9m t wr=n � � 0.6m .3�" 6 24m 3.Om 1.4m lam t1m Oam .,.a 3 1 4 am '` CL OPROOM NOTES: 1 Data shown is approximate and can vary due to differences in installation. 2 These graphs illustrate approximate trajectories,floor-wetting,and wall-wetting patterns for these specific Victaulic FireLock automatic sprinklers.They are provided as information for guidance in avoiding obstructions to sprinklers and should not be used as minimum sprinkler spacing rules for installation.Refer to the appropriate NFPA National Fire Code or the authority having jurisdiction for specific information regarding obstructions,spacing limitations and area of coverage requirements.Failure to follow these guidelines could adversely affect the perfor- mance of the sprinkler and will void all Listings,Approvals and Warranties. 3 All patterns are symmetrical to the centerline of the waterway. www.victaulic.com VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY.02013 VICTAULIC COMPANY.ALL RIGHTS RESERVED. jctauliC' REV_E 40.47 7 FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS 40.47 V27, K4.9 Residential Pendent and Recessed Pendent V2740 QUICK RESPONSE WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. For complete contact information,visit www.victaulic.com 40.47 4525 REV E UPDATED 04/2013 ✓ataluklc° VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2013 VICTAULIC COMPANY.ALL RIGHTS RESERVED. 40.47 FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS 40. 10 V27, K5.6 0 <> ® LPCB • . SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS Standard Spray; Upright, Pendent and Recessed Pendent MODELS/S.I.N.V2703 AND V2707 STANDARD RESPONSE MODELS/S.I.N.V2704 AND V2708 QUICK RESPONSE 11 ll These Model V27 standard spray sprinklers are designed to produce a hemispherical spray pattern for standard commercial applications.They are available with either standard or quick response bulbs.The design incorporates = ' state-of-the-art,heat responsive,frangible glass bulb design(standard or quick response)for prompt,precise operation. UPRIGHT PENDENT RECESSED (V2703 AND (V2707 AND PENDENT The die cast frame is more streamlined and attractive than traditional sand cast V2704), V2708) (V2707 AND frames. It is cast with a hex-shaped wrench boss to allow easy tightening from many v27o8) angles,reducing assembly effort.This sprinkler is available in various temperature ratings(see chart on page 2)and finishes to meet many design requirements. The recessed pendent should be utilized with a Model V27 recessed escutcheon which provides up to 44719mm of adjustments. SPRINKLER OPERATION The operating mechanism is a frangible glass bulb which contains a heat responsive liquid.During a fire,the ambient temperature rises causing the liquid in the bulb to expand.When the ambient tem- perature reaches the rated temperature of the sprinkler,the bulb shatters.As a result,the waterway is cleared of all sealing parts and water is discharged towards the deflector.The deflector is designed to distribute the water in a pattern that is most effective in controlling the fire. COVERAGE For coverage area and sprinkler placement,refer to NFPA 13 standards. TECHNICAL SPECIFICATIONS Models/S.I.N.:V2703,V2704,V2707,V2708 Style:Pendent,Upright or Recessed Pendent ACCESSORIES ® Nominal Orifice Size:1/2"/13 mm K-Factor:5.6lmp./8.1 S.I.^ Installation Wrench: Nominal Thread Size:W NPT/15mm • Open End:V27 Max.Working Pressure: • Recessed:V27-2 175 psi/1200 kPa FM Global Finishes: 0250 psi/1725kPa UL • Plain brass Factory Hydrostatic Test: • Chrome plated 100% 500psi/345OkPa • • White painted** U Min.Operating Pressure:7 psi/48 kPa • Black painted** �'''',.(,1} Temperature Rating:See charts on page 2&3. • Custom painted** �,� I • Proprietary nickel Teflon*coating** MATERIAL SPECIFICATIONS • • For 155,200,and 286°F Standard Response Only,wax coated** \. Upright Deflector:Bronze per UNS C22000 `PPendent Deflector:Bronze per UNS C51000 For cabinets and other accessories refer to Bulb:Glass with glycerin solution. separate sheet. � Bulb Nominal Diameter: Standard:5.0mm NOTE:Weather resistant recessed escutcheons • Quick Response:3.0mm available upon request. Load Screw:Bronze per UNS C65100 A For K-Factor when pressure is measured in Pip Cap:Bronze per UNS C65100 Bar,multiply S.I.units by 10.0. Spring:Beryllium nickel * Teflon is a registered trademark of Dupont Co. Exaggerated for clarity Seal:Teflon*tape **UL Listed for corrosion resistance in all Frame:Die cast brass 65-30 configurations. Lodgement Spring:Stainless steel per UNS S30200 JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date Approved Date www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2012 VICTAULIC COMPANY.ALL RIGHTS RESERVED. ✓ctaUltd' REV_I 40.10 1 J FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS 40.10 V27, K5.6 Standard Spray; Upright, Pendent and Recessed Pendent MODELS/S.I.N.V2703 AND V2707 STANDARD RESPONSE MODELS/S.I.N.V2704 AND V2708 QUICK RESPONSE APPROVALS/LISTINGSModel V270352707 52707 52704 1 52708 n—._ 52708_ Orifice Size(inches) M.- --- -... _ _w,... ....—. .,.,_.. _._... .._._. Orifice Size{mm) 13 13 l 13 13 13 13 S 5. Nominal K Factor Impenal ,. � Standard �.,.__ TM 81 Nomtnal K Factor S I a 81 b-_..- 81 81 81 81 81. Response Standard Standard QuickQwck Quick € Recessed Recessed Deflector Type Upright Pendent Pendent Upright Pendent pendent Adjustment ; up to A up to 14" Approved Temperature Ratings RIC-by Agency$ " MOM r 135°F/57°C 135°F/57°C j 135°F/57°C 135°F/57°C €g PIi 135°F/57°C155°F/68°CUL 175°F/79°C200°F/93°C 200°F/93°C ° ° ° °C °C 200°F/93°C286°F/141 C 286°F/141°C 286F/141°C 360°F/182°C 360°F/182°C 6 „t.�„ ,„„„,... .. 13S F/57°C 135°F/57°C 135°F/57 C 135°F/57°CiiII 135°F/57°C 155°F/68°C 155°F/68°C 155°F/68°C 155°F/68°C € 155°F/68°C 135°F/57°C 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C 155°F/68°C ULC 175°F/79°C 200°F/93°C 200°F/93 C 200°F/93°C 200 F/93°C 200 F/93 C 200°F/93°C 286°F/141°C I 286 F/141 C 286°F/141°C 286 F/141°C k 286 F/141 C 360°F/182°C 360'F/182°C I ” 135°F/S7°C 135°F/57°C s 135°F/57°C 135 F/57°C u ' 155°F/68°C 155°F/68°C 135°F/57°C )55°F/68°C 155 F/68°C 135°F/57°C 175°F/79°C 175°F/79°C 155°F/68°C 175°F/79°C 175°F/79°C 155°F/68°C FM# 200°F/93°C 200°F/93°C 175°F/79°C 200°F/93°C 200°F/93°C 175°F/79°C 286°F/141°C 286°F/141°C 200°F/93°C 286°F/141°C286°F/141°C 200°F/93°C 360°F/182°C 1 360°F/182°C ' 135 F/57°C { 135 F/57°C t 135°F/57°C 135°F/57°C 135°F/57°C 135°F/57°C 155°F/68°C 155°F/68°C 15S°F/68°C 155°F/68°C 155°F/68°C 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C 17S°F/79°C 155°F/68°C NYC/MEA 7f`62-99-E. 200°F/93°C 200°F/93°C I z 175°F/79°C 286°F/141°C 286°F/141°C 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C F 360°F/182°C 360°F/182°C 286 F/141°C • 286°F/141°C 286°F/141°C 135 F/57°C 135°F/57°C 135°F/57°C 135°F/57°C i 135°F/57°C 155°F/68°C 155°F/68°C135°F/57°C 155°F/68°C i 155°F/68°C 155°F/68°C 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C 155°F/68°C CSFM#7690-0531:112 200°F/93°C 200°F/93°C 175°F/79°C 286°F/141°C 286°F/141°C 6 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C 360°F/182°C 360°F/182°C 286°F/141 C 286°F/141°C 286 F/141 C 135 135°F/57°C 135°F/57°C s 155°F/68°C 135°F/57°C 155°F/68°C € 135°F/57°C >LPCB 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C None None I 200°F/93°C 200°F/93°C 200°F/93°C ' 200°F/93°C 286°F/141°C I 286°F/141 C i 360°F/182°C 135 F/57°C 135°F/57°C 135 F/57°C 135°F/57°C 155 F/68°C 155°F/68°C 135°F/57°C 135°F/57°C 155 F/68°C 155°F/68°C 175°F/79°C j 175°F/79°C 155°F/68°C 175°F/79°C 175°F/79°C 155°F/68°C VNIIPO 200°F/93°C 200°F/93°C 175°F/79°C j175°F/79°C 286°F/141°C 286°F/141°C 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C 286°F/141°C 286°F/141°C , 360°F/182°C 360°F/182°C ZSTZ ZSTX i K-ZSTZ K-ZSTX '.. CCC 155°F/68°C 155°F/68°C° ° ° ° None 155°F/68°C - 155°F/68°C k None 200F/93C 200F/93C i 200°F/93°C 200°F/93°C t Listings and Approvals as of printing.All are approved open,except for areas designated"No'. "For K Factor when pressure is measured in Bar,multiply S.I.units by 10.0 #FM Approved with 1/2'adjustment escutcheon only-quick response www.victaulic.com jctaulid VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2012 VICTAULIC COMPANY.ALL RIGHTS RESERVED. 40.10_2 REV_I FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS 40.10 V27, K5.6 Standard Spray; Upright, Pendent and Recessed Pendent MODELS/S.I.N.V2703 AND V2707 STANDARD RESPONSE MODELS/S.I.N.V2704 AND V2708 QUICK RESPONSE RATINGS All glass bulbs are rated for temperatures from-67°F/-55°C to those shown in table below. Temperature—"FPC Victaulic Sprinkler Temperature Part Nominal Temperature Maximum Ambient Classification Identification Rating Temperature Allowed Glass Bulb Color Ordinary A • 135 100 • Orange 57 • 38 > Ordinary C fib 1380 Red Intermediate E 175• 5 0 Yellow Intermediate F 93 59 Green High 286 225– Blue 141 107 Extra High# K 360 300 Purple 182 149 –# M Open — No Bulb $Standard response only. All are approved open,except for areas designated"No'. —150/65 if wax coated. ORDERING INFORMATION Please specify the following when ordering: Sprinkler Model Number Style Temperature Rating K-Factor Thread Size Quantity Sprinkler Finish Escutcheon Finish Wrench Model Number I• • www.victaulic.com jctaulid VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2012 VICTAULIC COMPANY.ALL RIGHTS RESERVED. REV_I 40.10_3 ' FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS 40.10 V27, K5.6 Standard Spray; Upright, Pendent and Recessed Pendent MODELS/S.I.N.V2703 AND V2707 STANDARD RESPONSE MODELS/S.I.N.V2704 AND V2708 QUICK RESPONSE WARNING A <� • Always read and understand installation,care,and maintenance 4instructions,supplied with each box of sprinklers,before proceeding with installation of any sprinklers. • Always wear safety glasses and foot protection. • Depressurize and drain the piping system before attempting to install,remove,or adjust any Victaulic piping products. • Installation rules,especially those governing obstruction,must be strictly followed. 0 • Painting,plating,or any re-coating of sprinklers(other than that sup- plied by Victaulic)is not allowed. Failure to follow these instructions could result in serious personal injury and/or property damage. The owner is responsible for maintaining the fire protection system and devices in proper operating condition.For minimum maintenance and inspection requirements,refer to the current National Fire Protection Association document NFPA 25 that describes care and maintenance of sprinkler systems.In addition,the authority having jurisdiction may have additional maintenance,testing,and inspection requirements that O must be followed. If you need additional copies of this publication,or if you have any questions about the safe installation of this product,contact Victaulic World Headquarters:P.O.Box 31,Easton,Pennsylvania 18044-0031 USA,Telephone:001-610-559-3300. DIMENSIONS Standard Pendent—V2707,V2708 Standard Upright—V2703,V2704 r37mm 1 245"/ ��_�60 mm13'a"/ ' 1%y lap 41mm �_� 2%"/ 41mm '�.� 60 mmIm� / 25 mm - 'h"Adjustment Recessed—V2707,V2708(drawing not to scale) 21"Ma/60x.Hole mm 2"/51 mm ���� Min.Hole 17mm17 MEN 1.171.ram YP g IZ.Vs/.,``.IriL/1/1 1m I � � TT ical ■ 3 I 1,�./ 010 1 Ne"/ 43 mm �,�J Finished Surface 30•m �:I MAXIMUM RECESS 2"/w"/ 75 mm MAXIMUM EXTENSION www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2012 VICTAULIC COMPANY.ALL RIGHTS RESERVED. uCtauli CA. 40.10_4 REV J FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS 40.10 V27, K5.6 Standard Spray; Upright, Pendent and Recessed Pendent MODELS/S.I.N.V2703 AND V2707 STANDARD RESPONSE MODELS/S.I.N.V2704 AND V2708 QUICK RESPONSE DIMENSIONS 34"Adjustment Recessed—V2707,V2708(drawing not to scale) 234"/60 mm Max.Hole 2"/51 mm Min.Hole '5167 'y/� ring& + F i I1 1 "724m ��A Typical i Asigir4 $9,� 3 mirii � Ceiling ' :� 5i4c"/ I) Finished Surface �` 24 mm _ _ MAXIMUM RECESS 25Yid/ 75 mm MAXIMUM EXTENSION AVAILABLE WRENCHES Sprinkler Type V27-2 Recessed V27 Open End V2707,V2708 Pendent yes i yes V2707,V2708 Recessed Pendent yes — V2703,V2704 Upright i yes yes DISTRIBUTION PATTERNS Models/S.I.N.V2707,V2708 K5.6 standard pendent and recessed pendent distribution patterns—trajectory 1 O,i F •*• I r �y I r♦♦ • • ♦ ( I , z t I \ I I ♦♦ `s x i_ I • ',--- m _I-_ • I ; 4 I 1 i , ♦♦i I 1.2m Ir I 1\ _ _ 44 1 I ♦ E Sr} ♦ 1 N: • *♦., _ y 2 4' 6' 8' 10' 12' 74' 0.6m 1.2m 1.8m 2.4m 3.0m 3.7m 4.3m 7 psi �•••••• 15 psi 30 psi 48 kPa 103 kPa 207 kPa See notes on next page. www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2012 VICTAULIC COMPANY.ALL RIGHTS RESERVED. jctaulid REV_I 40.10_5 FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS 40.10 V27, K5.6 Standard Spray; Upright, Pendent and Recessed Pendent MODELS/S.I.N.V2703 AND V2707 STANDARD RESPONSE MODELS/S.I.N.V2704 AND V2708 QUICK RESPONSE DISTRIBUTION PATTERNS Models/S.I.N.V2703,V2704 K5.6 standard upright distribution patterns—trajectory 10' 3.0m WJ+� 't.;.. ., .._.,, ._.,. ..., ..._, ... ... ........ ..w 4• C 2.4m .. ♦♦ • i i 1.8m .. .. `♦..... , ,t : .64 1 E i i I 4 i♦ • 4 1.2m ` I { s i I ` I I 0.6m , t I4 I I $ i i 2' 4' 6' 8' 10' 12' 14' 16' 0.6m 1.2m 1.8m 2.4m 3.0m 3.7m 4.3m 4.9m 7 psi •• ••• 15 psi 111, 30 psi 48 kPa 103 kPa 207 kPa NOTES: 1 Data shown is approximate and can vary due to differences in installation. 2 These graphs illustrate approximate trajectories,floor-wetting,and wall-wetting patterns for these specific Victaulic FireLock automatic sprinklers.They are provided as information for guidance in avoiding obstructions to sprinklers and should not be used as minimum sprinkler spacing rules for installation.Refer to the appropriate NFPA National Fire Code or the authority having jurisdiction for specific information regarding obstructions,spacing limitations and area of coverage requirements.Failure to follow these guidelines could adversely affect the perfor- mance of the sprinkler and will void all Listings,Approvals and Warranties. 3 All patterns are symmetrical to the centerline of the waterway. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. For complete contact information,visit www.victaulic.com 40.10 2544 REV I UPDATED 04/2012 ictaulid VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2012 VICTAULIC COMPANY.ALL RIGHTS RESERVED. 40.10 FIRE PROTECTION PRODUCTS AUTOMATIC SPRINKLERS 40.64 V36, K5.6 0 <> c LISTED Dry Type Standard Spray, Light Hazard Horizontal Sidewall and Recessed Horizontal Sidewall 11,71 V3609 STANDARD RESPONSE I ' V3610 QUICK RESPONSE FLUSH DRY RECESSED DRY SLEEVE&SKIRT HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL 011E4 EXTENDED PLAIN HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL The V36 dry Sprinkler is used in special applications such as freezing environments and conditions where sediment or foreign materials might accumulate in ordinary horizontal pipe nipples. The Model V36 Dry Type Horizontal Sidewall Sprinkler utilizes a frangible glass bulb.At the bulb's rated temperature,the sprinkler opens releasing the bulb seat assembly,causing the inner tube assembly to move,allowing the spring assembly to pivot alongside the inner tube.At this time,water flows through the sprinkler and is distributed by the deflector,in an approved discharge pattern. The heart of the Model V36 sprinkler's proven actuating assembly is a hermetically sealed frangible glass bulb that contains a precisely measured amount of fluid.When heat is absorbed,the liquid within the bulb expands increasing the internal pressure.At the prescribed temperature the internal pressure within the bulb exceeds the strength of the glass causing the glass to shatter.This results in water discharge which is distributed in an approved pattern. COVERAGE: For coverage area and sprinkler placement,refer to NFPA 13 standards. JOB OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date Approved Date www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. jctaulid REV I 40.64_1 * FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS 40.64 V36, K5.6 USTED Dry Type Standard Spray, Light Hazard Horizontal Sidewall and Recessed Horizontal Sidewall -ill ostaiii --k '•:',. 'f'' V3609 STANDARD RESPONSE V3610 QUICK RESPONSE : FLUSH DRY RECESSED DRY SLEEVE&SKIRT HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL EXTENDED PLAIN HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL TECHNICAL SPECIFICATIONS: I nazi III, --.......AwAwArAwAwAwAr—t..T.TQ Imai ',twig toil 11111viia-iisC x-ri' mr•srArAIWV---'- -11 66-7 ...:04SrAlrArAfifrifrArArA/TArl''M' Val iiii I Exaggerated for clarity Models:V3610 and V3609 ACCESSORIES Style:Horizontal Sidewall and Recessed Installation Wrench:Model V36 Open End and Horizontal Sidewall Recessed Wrenches fit all V36 Series frames. Nominal Orifice Size:W/13 mm Finishes: Orifice Insert:Stainless steel per UNS S30300 • Plain brass K-Factor:5.6 Imp./8,1 S.1.^ • Chrome plated° Nominal Thread Size:r NPT/33.7 mm • White Painted's Max.Working Pressure:175 psi/1200 kPa • Flat black painted° Factory Hydrostatic Test:100%@ 500 psi/ • Custom painted° 3450 kPa • Wax° Min.Operating Pressure:7 psi/48kPa • Proprietary Nickel Teflon*Coated° Temperature Rating:See chart on page 3. For cabinets and other accessories refer to separate sheet. MATERIAL SPECIFICATIONS A For K-Factor when pressure is measured in Deflector:Brass per UNS C22000 or Stainless Bar,multiply S.I.units by 10.0. Steel per UNS S30400 * Teflon is a registered trademark of Dupont Co. Bulb:Glass with glycerin solution ° UL Listed for corrosion resistance in all con- • Standard:5.0 mm figurations. • Quick Response:3.0 mm NOTES: Split Spacer:Stainless steel per UNS S30300 1.Weather resistant escutcheon available upon Load Screw:Brass per UNS C36000 request. Pip Cap:Stainless steel per UNS S30300 2.Only the Plain Brass and Nickel Teflon Spring Seal Assembly:Teflon*coated Beryllium finishes are FM approved. nickel alloy and Stainless steel per UNS S30300 Frame:Die cast brass Outer Tube:Galvanized steel pipe Inner Tube:Stainless steel per UNS S30400 Escutcheon:1010-1018 mild steel and Stainless Steel Torsion Spring:Stainless Steel Wire www.victaulic.com ‘iictaulia VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED 40.64_2 REV_I 40,64 • FIRE PROTECTION PRODUCTS-AUTOMATIC SPRINKLERS V36, K5.6 FM c 0 USTED Dry Type Standard Spray, Light Hazard Horizontal Sidewall and Recessed Horizontal Sidewall l-111 ; � V3609 STANDARD RESPONSE "" V3610 QUICK RESPONSE FLUSH DRY RECESSED DRY SLEEVE&SKIRT HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL EXTENDED PLAIN HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL APPROVALS/LISTINGS Orifice Nominal Approved Temperature Ratings Model Size K-Factor Response Deflector Type °F/°C# Inches Imperial Standard mm S.1.° or Quick UL* C.-UL* FM V3610 r/` 5.6 Quick ;I Horizontal Sidewall 135,155,200,286 135,155,200,286 135,155,200,286 13 8.1 57 68,93 141 57 68 93 141 57,68,93,141 '/z 5.6 i Recessed Horizontal 135,155,200,286'135,155,200,286 135,155,200 V3610 13 1 81 ; • FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS 40.64 V36, K5.6 FM c LISTED Dry Type Standard Spray, Light Hazard Horizontal Sidewall and Recessed Horizontal Sidewall I;" V3609 STANDARD RESPONSE '' I V3610 QUICK RESPONSE FLUSH DRY RECESSED DRY SLEEVE&SKIRT HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL 4:11:1E __ EXTENDED PLAIN HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL ORDERING INFORMATION Please specify the following when ordering: Sprinkler Model Number Style Temperature Rating K-Factor Quantity Sprinkler Finish Escutcheon Style "A"Dimension—Distance from face of fitting to the finished ceiling line regardless of escutcheon used. AVAILABLE WRENCHES Model V36 Open End and Recessed Wrenches fit all V36 Series frames. www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. V 'Ctaul1d 40.644 — REV_I it FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS 40.64 V36, K5.6 0 <> c O LISTED Dry Type Standard Spray, Light Hazard Horizontal Sidewall and Recessed Horizontal Sidewall V3609 STANDARD RESPONSE .1 ,1-, , X M 1+� "n V3610 QUICK RESPONSE FLUSH DRY RECESSED DRY SLEEVE&SKIRT HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL OE EXTENDED PLAIN HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL WARNING • Always read and understand installation,care,and maintenance instructions,supplied with each box of sprinklers,before proceeding 4cwith installation of any sprinklers. • Always wear safety glasses and foot protection. • Depressurize and drain the piping system before attempting to install,remove,or adjust any Victaulic piping products. • Installation rules,especially those governing obstruction,must be strictly followed. • Painting,plating,or any re-coating of sprinklers(other than that sup- 0plied by Victaulic)is not allowed. Failure to follow these instructions could result in serious personal injury and/or property damage. The owner is responsible for maintaining the fire protection system and devices in proper operating condition.For minimum maintenance and inspection requirements,refer to the current National Fire Protection Association pamphlet that describes care and maintenance of sprinkler systems.In addition,the authority having jurisdiction may have addi- tional maintenance,testing,and inspection requirements that must be followed. If you need additional copies of this publication,or if you have any questions about the safe installation of this product,contact Victaulic World Headquarters:P.O.Box 31, Easton,Pennsylvania 18044-0031 USA,Telephone:001-610-559-3300. www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. jctaulid REVI 40.64 5 1 . FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS 40.64 V36, K5.6 uL FM co LISTED Dry Type Standard Spray, Light Hazard Horizontal Sidewall and Recessed Horizontal Sidewall . flits t ,.-_ I . . ...* 7. .„.._ _ _. ;,tk G. r V3609 STANDARD RESPONSE V3610 QUICK RESPONSE FLUSH DRY RECESSED DRY SLEEVE&SKIRT HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL 4:11E E EXTENDED PLAIN HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL DIMENSIONS NOTE:The"A"dimension of a dry sprinkler,which extends into a freezer from a wet piping system, must take into account the wall or ceiling thickness of the freezer.See IMPORTANT INSTALLATION INFORMATION later in this document. A" (Mtn.111 u" (Mn.lu, am Two Piece cM1eon 1'NPT I. jINP i II!, __—__� 1K"Min.Diaa /I �..-..� I.'Min �r Hole In Wall 3"Da sl Hole in Wall Tee wttnta kler read sae T spookierouness as sIMPORTAN INSTALLATION e lM O T NTead sire 3 MIn. INSFORMATION ltern this docu 2'h" INFORMATION IRMTIONT Wm INSTALLATION INFORMATION later In this document, INFORMATION later in this document. / a'h•Max. Flush %/ Shwa&Mort •A" Mln.1W) NP I KsI. I LW Tee with sa to outlet size L 2Ms" as sprinkler thread size See IMPORTANT INSTALLATION INFORMATION later in this document Plain Barin (Mlnt)4') 1 1'NPT 1M' m.Dla. \ Wall Cup He LAW_ `iii.... Collar )—r I 1'NPT Tee with sam)outlet sine E---T-_-y T' 1 as sprinkler thread see Two Piece 2'Min.Dia. See IMPORTANT Escutcheon 1 Hole InWall Tee with same outlet Pm INSTALLATION as sprinkler thread sue \ 2W Min INFORMATION later in \ See IMPORTANT INSTALLATION Max Ma document. A' a'Mei \ 2W INFORMATION later in this document. s. (Min.135 WM.- Extended Recessed DEFLECTOR TO CEILING DISTANCE 4—121102—305 MM FOR ALL CONFIGURATIONS SHOWN ABOVE. www.victaulic.com xiCtauliIC VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. 40.64_6 REV_I FIREPROTECTIONPRODUCTS-AUTOMATIC SPRINKLERS 40.64 V36, K5.6 0 <> ce LISTED Dry Type Standard Spray, Light Hazard Horizontal Sidewall and Recessed Horizontal Sidewall ; ,, 0004 V3609 STANDARD RESPONSE +ir 4 .4A ,ikk '4- ____44 oimwot, V3610 QUICK RESPONSE FLUSH DRY RECESSED DRY SLEEVE&SKIRT HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL EXTENDED PLAIN HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL DISTRIBUTION PATTERNS MODELS V3610,V3609 HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL DISTRIBUTION PATTERNS-TRAJECTORY . .. 10 3.0m • 8'01344- .S•s ♦♦' 2.4 m , .,...._._ 6' •. ♦♦ „ I I .... 1.8 m .. v_.. .. . . 4 1.2m 2' L . x ♦♦L i.. 0 1 ,_ ,,_ .6m ._ _ 0 . _ ', .a_ 2' 4' 6' 8' 10' 12' 14' 16' 18' 20' 22' 24' 26 0.6m 1.2m 1.8m 2.4m 3.0m 3.7m 4.3m 4.9m 5.5m 6.1 m 6.7m 7.3m 7.9m 7 psi -•.-.. 15 psi . 30psi 48 kPa 103 kPa 207 kP MODELS V3610,V3609 HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL DISTRIBUTION PATTERNS-PLAN VIEW 2' 4' 6' 8' 10' 12' 14' 16' 18' 20' 22' 24' 26' 28' 06m 1.2m 18m 2Am 3.0m 3.7m 4.3m 4.9m 55m 6.1 m 6.7m 7.3m 7.9m 8.5m 2 ! •i 0.6m _.__ , u.. 4 1.2m1 • i f • 8' # 2.4 m40 : r i �. ... 10' I ... ,►;'�•i •• 3.0 m * , � �•s X #• 12 .• • ' 3.7 m4... � 4.3m .___ �• • 16' ♦ , I 4.9m .. •...!_. .. .x 7 psi 15 psi 30si 48 kPa 103 kPa 207 kPa See notes on last page. www.victaulic.com VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. jetatilie REV I 40.64_7 FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS 40.64 V36, K5.6 O FM B O LISTED Dry Type Standard Spray, Light Hazard Horizontal Sidewall and Recessed Horizontal Sidewall —40/00N ) r. V3609 STANDARD RESPONSE V3610 QUICK RESPONSE ' FLUSH DRY RECESSED DRY SLEEVE&SKIRT HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL 1141Th EXTENDED PLAIN HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL IMPORTANT INSTALLATION INFORMATION For detailed installation instructions,see publication 1-40. No. 1 Victaulic Model V36 Series Dry sprinklers should be installed in accordance with NFPA 13.These sprinklers are to be installed using a pipe wrench applied to the outer tube. When this is not possible,the proper sprinkler wrench may be used with extreme care for lengths up to approximately 18".Excessive force may distort the frame thus destroying the unit. No.2 Dry sprinklers MUST be installed only into the outlet of a cast or malleable iron tee. No.3 DO NOT install dry sprinklers into any couplings or threaded elbows.In addition,DO NOT install dry sprinklers into any fitting that interferes with thread penetration.NOTE:The end seal of the dry sprinkler MUST NOT bottom out in the fitting. -m NOTE:The"A"dimension of a dry sprinkler,which extends into a End Seal IM freezer from a wet piping system,must take into account the wall or HEATED SPACE ceiling thickness of the freezer.The minimum length of the dry sprinkler S___ A should not be less than the lengths specified in the following table,plus I the thickness of the freezer's wall or ceiling("A"="C"+"D"). 'C'Exposed Minimum Barrel Refer to the drawing for a representation of the"A"dimension.DO NOT Length(Refer to Table) Diameter of hole is dependent upon the type of escutcheon selected Space must attempt to modify dry sprinklers,since they are manufactured to this be sealed to prevent condensation from specific"A"dimension. forming,per NFPA requirements. The following table is used when the ambient temperature is maintained .A. between 40°F/4°C and 60°F/16°C around the wet piping system. See Note EXPOSED BARREL AMBIENT TEMPERATURE(°F/°C) Insulation ,D, Exposed Minimum Barrel Length Ambient Temperature inches/mm Exposed to Discharge End of Sprinkler 40`P14`C 50'FRO`C 60'F/16°C F/'C Wall or Ceiling of Freezer 40 0 0 i 0 4 0 0 0 Nil30 0_ 0 . 0 -1 0 0 0 20 4 i 0 0 1101 7 102 t 0 0 1-1/ COLD SPACE 10 8 t.,. 1 0 -12 203 25 0 Exaggerated for Canty 0 12 _. 3 0 -18 `-- 305 _._.76 0__. .._..,.. TYPICAL SLEEVE AND SKIRT CONFIGURATION FOR EXAMPLE ONLY ,14 ? 4 1 23356 102 25 N max. �.. �,m .. �. �.... .,. .w. ,, �.... ., -20 14 6 3 -29 356 r 152 76 -30 16 8 4 -34 406 203 102 -40 18 8 4 -40 457 203 102 1 -50 20 I 10 6 -46508 254 152 -60 20 10 6 -51 508 I 254 i 152 NOTE:Exposed minimum barrel lengths are inclusive up to 30-mph/48-kph wind velocities www.victaulic.com �CtauliC VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. 40.64_8 REV_I FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS 40.64 V36, K5.6 ® FM c LISTED Dry Type Standard Spray, Light Hazard Horizontal Sidewall and Recessed Horizontal Sidewall 1fr Owl, V3609 STANDARD RESPONSE V3610 QUICK RESPONSE ' FLUSH DRY RECESSED DRY SLEEVE&SKIRT HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL . EXTENDED PLAIN HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL NOTES 1 Data shown is approximate and can vary due to differences in installation. 2 These graphs illustrate approximate trajectories,floor-wetting,and wall-wetting patterns for these specific Victaulic FireLock automatic sprinklers.They are provided as information for guidance in avoiding obstructions to sprinklers and should not be used as minimum sprin- kler spacing rules for installation.Refer to the appropriate NFPA National Fire Code and the Authority Having Jurisdiction for specific information regarding obstructions,spacing limitations and area of coverage requirements.Failure to follow these guidelines could adversely affect the performance of the sprinkler and will void all Listings,Approvals and Warranties. 3 All patterns are symmetrical to the centerline of the waterway. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. US&WORLD HEADQUARTERS CANADA CENTRAL AND SOUTH AMERICA P.O.Box 31 905-884-7444 1-610-559-3300 Easton, PA 18044-0031 USA 905-884-9774(fax) 1-610-559-3608(fax) 4901 Kesslersville Road viccanada@victaulic.com vical@victaulic.com Easton, PA 18040 USA EUROPE ASIA PACIFIC 1-800-PICK-VIC(1-800-742-5842) 32-9-381-15-00 86-21-54253300 1-610-559-3300 32-9-380-44-38(fax) 86-21-54253671 (fax) 1-610-250-8817(fax) viceuro@victaulic.be vicap@victaulic.com pickvic@victaulic.com UNITED KINGDOM MIDDLE EAST www.victaulic.com 44(0)1438310690 971-4-883-88-70 44(0)1438310699(fax) 971-4-883-88-60(fax) viceuro@victaulic.be UPDATED 12/2009 40.64 3127 REV I ictauIic VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. 40.64 Bulletin 016 Rev.E ModelDH56 HSW Reliabl ° Model DH56 HSW RecessedcT Model DH56 HSW Concealed o Quick Response, Extended Coverage Dry Sprinklers m For coverages up to 28 feet wide and 10 feet Ione. 250 psi (17,2 bar) rated. Features: ► "i► .h 1. Coverage for long and narrow spaces such as hall- ways, corridors, decks and rooms up to 28 feet wide and 10 feet long.(') 2. Deflector to ceiling dimensions are: 4"(102mm)min.to 12"(305mm)max. DH56 HSW 3. Minimum spacing between sprinklers 13 feet(4m).(1) 4. Polyester Coated Corrosion Resistant Sprinklers(cULus) 5. UL Listed for extended coverage, light hazard appli- 44,1, cations. u.a. 6. 5.6 K Factor. 7. Sprinkler is approved fort. 250 psi(17,2 bar)applications. 8. Quick response performance. 9. 1" (13mm)adjustment of escutcheon and cover. . ' 10.Concealed cover plate can prevent the sprinkler from being used for unintended purposes. No exposed thermal element with the concealed version. DH56 HSW FP Recessed 11.Push-on/thread-off sturdy convenient escutcheon for recessed and cover for concealed. «.-..; 12.Factory assembled sprinkler&cup, shipped complete with bulb protector for concealed and FP recessed ver- sions. 13.Sprinkler&cup assembly and escutcheon or cover are separately packaged. 14.Cover finishes available in standard white paint, spe- cial bronze, black paint or flat white paint. DH56 HSW Concealed (1)See Fig. 7. with SWC coverplate Approval Organizations a fire the rising ambient temperature melts the solder and 1. Listed by Underwriters Laboratories Inc. and the cover plate is ejected away by springs exposing the UL certified for Canada(cULus) 3mm frangible glass bulb. The use of a 3mm bulb allows 2. NYC MEA 258-93-E quick response which enables the sprinkler to apply water to a fire sooner than standard response sprinklers of the Products Description same temperature rating. The Model DH56 are quick response extended coverage Model DH56 dry sprinklers are intended for use in dry sidewall dry sprinklers for use in light hazard applications. and preaction systems to protect areas subjected to freez- The Model DH56 dry sprinkler with SWC cover plate is a ing temperatures and unheated portions inside buildings. concealed sprinkler that uses Reliable's push on/thread off See Fig. 1 for guidelines on using dry sprinklers in wet sidewall cover.This sprinkler has the cup factory mounted systems. and is shipped with a bulb protector that protects the 3mm Environments wherein dry sprinklers are employed can frangible glass bulb during shipping and post installation be corrosive. For this reason, Model DH56 dry sprinklers finishing operations. The DH56 can be combined in the have a special wax fillet placed in the gap between the field with the FP or F2 Escutcheon to make a recessed cup that supports the bulb and the wrenching boss. This dry sprinkler. The SWC cover plate, FP and F2 recessed wax will not interfere with the operation of the sprinkler,and escutcheons have 1/2" adjustment. The SWC cover plate it prevents contaminants from entering the internal portion is attached with 135 & 165 degree solder. In the event of of the drop nipple. The wax must not be removed. The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Application DH56 HSW Concealed with SWC Cover Plate The Model DH56 is a horizontal sidewall dry sprinkler To install the DH56 HSW dry sprinkler with the SWC intended for installation in light hazard occupancies in ac- coverplate as a concealed sprinkler, cut a 21/8" diam- cordance with NFPA 13. These sprinklers are designed to eter hole into the wall as shown in Fig. 6. Temporari- provide fire protection in long and narrow spaces such as ly remove the plastic protective cap, and then use the hallways, corridors, decks and rooms upto 28 feet (8,5m) Model XLO2 wrench (see Fig. 2) to tighten the sprinkler Y , wide and 10 feet(3m)long. They are rated for 250 psi(17,2 until it is secured in the sprinkler fitting. Note:The Model bar) and can be mounted between 4 and 12 inches (102 XLO2 wrench has a notch in it to accommodate the de- and 305mm)down from the ceiling. flector top. This wrench can only be inserted one way. Care must be taken not to damage the deflector during General Installation Instructions tightening.Apply a Teflon**based sealant to the sprinkler Model DH56 dry sprinklers must be installed only in stan- threads before installing in the sprinkler. Wrench only on dard (ANSI B 16.3 class 150 and ANSI B 16.4 class 125) the square boss. DO NOT WRENCH ON ANY OTHER pipe tees in the horizontal position,even at branch line ends. PART OF THE SPRINKLER. It is recommended that the They should not be installed into elbows or pipe couplings sprinkler be protected during plastering and painting op- located on drop nipples to the sprinklers. For these and erations by reinstalling the plastic protective cap. Instal- other fittings including CPVC, the dry sprinkler should be lation is completed by removing the protective cap and installed into a fitting to allow protrusion into the fitting in ac- inserting the coverplate. Coverplate assemblies provide cordance with the diagrams. The "A" dimension of the dry '/" (13mm) of adjustment. Final adjustment is made by sprinkler,which extends into a freezing zone from wet pipe turning the coverplate clockwise until the skirt flange systems, should be selected to provide,as a minimum,the makes full contact with the wall surface. Cover removal specified lengths in inches shown in Fig. 1. requires turning in the counter-clockwise direction. Caution; Concealed coverplate assemblies are listed only for Do not install Model DH56 HSW Dry sprinklers into CPVC use with specific sprinklers. The use of any other con- adapter fittings or tees that have an internal obstruction. cealed wall sprinkler or the use of the SWC coverplate This will damage the sprinkler and /or the fitting. Refer to on any sprinkler with which it is not specifically listed will Fig. 8 void all guarantees, warranties, listings and approvals. Note: DH56 and DH56 Recessed Sprinklers have or- DH56 HSW ange bulb protectors to minimize bulb damage during To install the DH56 HSW dry sprinkler cut a 21/8" diameter shipping, handling, and installation. REMOVE THIS PRO- hole in the wall as shown in Fig. 4. Use the Model G3 instal- TECTION AT THE TIME THE SPRINKLER SYSTEM IS lation wrench (see Fig. 3) to tighten the sprinkler until it is PLACED IN SERVICE FOR FIRE PROTECTION. Remov- secured in the sprinkler fitting. Apply a Teflon* based seal- al of the protectors before this time may leave the bulb ant to the sprinkler threads before installing in the sprinkler. vulnerable to damage. RASCO wrenches are designed Wrench only on the square boss. DO NOT WRENCH ON to install sprinklers when covers are in place. REMOVE ANY OTHER PART OF THE SPRINKLER. Installation is com- PROTECTORS BY UNDOING THE CLASP BY HAND. DO pleted by removing the orange glass bulb-protector and as- NOT USE TOOLS TO REMOVE THE PROTECTORS. sembling the slip-on escutcheon to the sprinkler's can. DH56 HSW Recessed with FP Escutcheon To install the DH56 HSW dry sprinkler with the FP Escutch- eon as a recessed sprinkler cut a 25/8" diameter hole in the wall as shown in Fig.5. Temporarily remove the plastic pro- tective cap,and then use the Model XLO2 wrench(see Fig. 2) to tighten the sprinkler until it is secured in the sprinkler fitting. Note: The Model XLO2 wrench has a notch in it to accommodate the deflector top. This wrench can only be inserted one way. Care must be taken not to damage the deflector during tightening. Apply a Teflon** based seal- ant to the sprinkler threads before installing in the sprinkler. Wrench only on the square boss. DO NOT WRENCH ON ANY OTHER PART OF THE SPRINKLER. It is recommended that the sprinkler be protected during plastering and paint- ing operations by reinstalling the plastic protective cap. In- stallation is completed by removing the protective cap and inserting the push-on escutcheon.Turn clockwise to adjust the escutcheon against the wall. *DuPont Registered Trademark 2. 8u1/ L I u L u LI k'• 8 (STANDARD DH56 HSW DRY SPRINKLER SHOWN) ammo BARREL TENDET&tAT*LIRE ADDHEir TD1 OF PROTECTED 407/KC 180'F/10'C 18VF/1FC AREA•AZT DIOCTIARGEEND EXPOSED IAN1I4HM BARREL LENGTH•• OF THE SPRINKLER (FACE OF TEE TO TOP OF CEDJNo) TN.WO I11.(MM) N.(MM) 407(KC) 0 0 0 30F(-1'C) 0 0 0 20F(—TC) 4(101) 0 0 10F(-12,C) 8(203) 1 (28.1) 0 A• DIMENSIONOF(-18T) 12(306) 3(75) 0 NDANWEXPOSED CLEARANCE —10F(-23BAR C) 14(368) 4(101) 1 (28.1) REL HOLE LEN-20F(2IFC) 14(368) 8(152) 3(78) 'TM —30F(-34'C) 16(406) 8(203) 4(101) \:':;:; :; ':;:;:; ;:::;:;:; ;\ ESCUTCHE7??1 —IGF —IOC 18 \•i:ii 7':iM:' ''.' \ ( ) (467) 8 4(101) (HEATED AREA) \' ti:i:i:i\ —60'F(—ICC) 20(608) 10(264) 8(152) \:::: :::::::::::::::::::::::\ \' ii:i:iiiiiiii:i::iiiii —80F(-61C) 20 808) 10( ) a Ha2J \i is i:i:i:i i:i:i:i:i :i ::::::\ •THE PROTECTED AREA REFERS TO THE AREA BE1.0(THE CEILING. I mle_ 3' THE AI,IBIENT TEMPERATURE IS THE TEMPO AZURE AT THE DISCHARGE END OF THE SPRINKLER. __J'! �•ii L1A. FOR PROTECTED AREA713 THAT OCCUR BETWEEN THE VALUES LISTED.USE 711E NEM GOOIER TE)APERATURE, // c'[;i;Lji K; ;'; i;i; ::rdi;i; ••RE IAN.REQUIRED BARREL LENGTH IS NOT THE SAME AS THEW DIMENSION. \ NOTE:EXPOSED MEVMUM BARREL LENGTHS ARE INCLUSIVE OR TO 300H 'PE \ :•i•: i ii:i:•: ii:i::i:\ WIND VELOCRIES IN THE PROTECTED AREA \;:i:ii•i:;• :i:i:iii:;:;:::i;isi:::\ �OTECTED AREA) INSTALL i BICE NPT THREADED \ '' '. ''. � END OF DRY PENDENT SPRINKLER :'I'i'':::::': : ?:i:i:ia:i INTO IS OF A 1 INCH IpRNpM�'SIDgE FITTING . PER B 18.3(CIA35 160) WAIy OR CAST IRON THREADED TEE MING PER ANSI 18.4(CLASS 126)ONLY. INSULATED FREUERU�IURE IF HLA�ITY AND TEMPERATURE DIFFERD(TIAL OR EXIQIWR FRAMING CAUSES CIRIDENSATION 71E DPOSED DRY SPRINKLER,C011S/DERXPOSED BARREL WITH?�LLAApT�� TAPE OR EQUIVALENT. SEAL THE CLEARANCE SPACE AROUND THE SPRDKLER TO AVOID LEAKAGE OF AIR INTO TFE PROTECTED AREA AND caNsEnuENT FTRNATIoN OF CO♦mE%TE ITAAOR rum RON ATHE�FRRAJ�C WHOCH IE TH®S.SEE BELOW FOR RECOMMENDED DRY SPRINKLER SEAL ARRANGEMENTS (STANDARD DH56 HSW DRY SPRINKLER SHOWN) WOLN EXPOSED CLEARANCE MIN/MUN DAENRREL HOLE EXPOSED DARREL CSEE ADOVD LENGTH 1SEE ABOVE) INSIDE INSIDE FACE I 1IN COLD MEAOEATED AREA) 1 .•.•:•:':"7.:.:.:::.:.:.:.:.:".:.1 IN COLD AREAOEATED AREN � :::::::::::::1 � 1::::::i:iiiiiiii i i i2 iii�i�11111 1� Iii r iiii��1 Iii l�lil II IIIIII -_-_ 1,1.w.,-, 1 � !, � ,{I,IIIIII�IIII ,1_,...„; 4i::::: ::i:::::::::::::::::::N SEAL 6 .. . ......:...._..... A D�FLASHI Q ; : 1 / .. i 1 PRDTEcteD AREN (�DAIEND ) INSULATED FREEZER, OR COOLERUCTURE OR EKTERIORSI AMI 018,008A Fig. 1 3. • I Technical Data: Maintenance K Factor Temperature Sprinkler Model DH56 Quick Response Dry Sprinklers should be Thread Rating Maximum Identification inspected quarterly and the sprinkler system maintained in Size SWC Ambient Number accordance with NFPA 25. Do not remove the factorya US Metric Sprinkler Cover Temperature (SIN) plied thermally sensitive wax fillet between the bulb support- 155°F 135°F 100°F ing cup and the wrenching boss. Do not replace this wax with (68°C) (57°C) (38°C) a substitute substance. An alternate substance may interfere 5.6 80 1 175°F 165°F 150°F with proper operation of the sprinkler. Do not clean sprinklers (79°C) (74°C) (66°C) RA1664 with soap and water, ammonia or any other cleaning fluids. 200°F 165°F 150°F Remove dust by using a soft brush or gentle vacuuming. Re- (93°C) (74°C) (66°C) move any sprinkler which has been painted(other than factory applied)or damaged in any way. A stock of spare sprinklers should be maintained to allow quick replacement of dam- Coverage Area aged or operated sprinklers. Prior to installation, sprinklers Maximum Coverage Flow Rate Pressure should be maintained in their original cartons and packaging Area Width x Length psi(bar) g p g g n x ft(m x m) gpm(L/min) until used to minimize the potential for damage to sprinklers 28 x 8(8,5 x 2,4) 23(87,1) 16.9(1,2) that would cause improper operation or non-operation. 28 x 10(8,5 x 3) 28(106) 25(1,7) Model DH56 Quick Response Approval Type: Extended Coverage Horizontal • Quick Response, Extended Coverage. Sidewall Dry Sprinkler Specification • Approved for installation in accordance with NFPA 13 Sprinklers shall be a [quick response —cULus Listed] ex- for light hazard occupancies. tended coverage horizontal sidewall sprinkler for light hazard occupancies. Sprinklers to be of bronze frame construction Step 1 with a special deflector capable of providing a discharge over a coverage area of 28 ft. (8,5m) wide, and 10 ft. (3m) long horizontal throw.Water seal assembly shall consist of a Teflon- coated Belleville spring washer. Installation shall permit sprin- 4 kler deflectors to be positioned 4" (102mm)to 12" (305mm) below the ceiling. Sprinklers shall have a nominal K-factor Step 2 of 5.6 (80), and 1" NPT thread. Sprinkler temperature rating - - shall be [155°F(68° C)] and [200°F(93°C)]. Rated working Ammo-` "'' pressure shall be 250 psi (17.2 bar). Standard finish: [whit e][chrome][bronze][Special finish—specify]. Quick response t extended coverage horizontal sidewall dry sprinklers shall be Reliable Model DH56,SIN RA1664(Bulletin 016). Step 3 For recessed EC horizontal sidewall sprinklers: Replace ti. ( . y "horizontal sidewall"with"recessed horizontal sidewall." Add: (1)Recessed escutcheon assembly shall be a two-piece es- +{ cutcheon of push on and thread off design with 'h" (13mm) adjustment.Standard finish shall be chrome,white and brass. Quick response recessed horizontal sidewall sprinklers shall Fig.2-XL02 Wrench be Reliable Model DH56,SIN RA1664(Bulletin 016). For concealed EC horizontal sidewall sprinklers: Replace "horizontal sidewall" with "concealed horizontal sidewall." Add: Cover plate assembly shall consist of a brass cover tr plate and copper alloy retainer flange. Method of attaching the cover plate to the sprinkler cup shall be a push-on and thread-off design allowing a 1/2" (13mm) cover plate adjust- ment. Cover plate temperature rating shall be 135°F(57°C) for 155°F (68°C) dry sprinkler and 165°F (74°C) for 200°F (93°C)dry sprinkler. A bulb protector shall be provided and factory installed inside the sprinkler cup to protect the glass bulb from damage, which could occur during construction before the cover plate is installed.Standard cover plate finish: Ag.3-G3 Wrench [white] [Custom Color— specify]. Quick response extended coverage concealed horizontal sidewall dry sprinklers shall be Reliable Model DH56,SIN RA1664(Bulletin 016). 4. • DH56 HSW DRY SPRINKLER 1 1/2" [38.10mm] Total Adjustment rPE Ceiling c LA 1. I 1 1/4" [31.75mm] 4" [101.60mm] Min. Escutcheon Adjustment 12" [304.80mm] Max. ' j- 1/4' [6.35mm] System Tee � Escutcheon Adjustment 1" NPT I 1"Y. -11; „ 1 15/16" _rte f iiia _ ^ IVIIIIIIII I I i� I I I Eib' ', 3" Dia. ��.``; 0111111111111111 I I �i�' [76.20mm] --1- -1J - .- 2 1/8" Dia. [53.98mm] 1...1 iL Hole in Wall 1/4" [6.35mm] Protrusion Sprinkler Can "A" Dimension Nominal Position Range + 1/4" (+6.3bmm] Adjustmentof Escutcheon 01eF003A - 1 1/4 [-31.75mm] Available "A" Dim. is 2"to 48" (51 mm to 1219mm)in 1/4" (6mm) increments Note: The Sprinkler Can protrudes 1/4°when escutcheon is in nominal position. Escutcheon adjustment provides + 1/4"(+6mm) to -11/4" (-32mm) "A" dimension adjustment range. Fig. 4 DH56 HSW RECESSED DRY SPRINKLER Ceiling /4"Es1 1/TI- Escutcheon cutcheon �-^� [31.75mm] I_; 4" [101.6mm]Min. System Tee Cup 13 1 12" [304.8mm]Max.* 1" NPT - ` INIMINI )jIlllLlII _r� fle�` i . 3 7/32" Dia. IIIIIIIII �__rV [81.8mm] `S.-f __-1J I I J 1 2 5/8" Dia. [66.68mm] Hole in Wall 131 Nominal Position of Escutcheon 2 9/32" Dia. I.-.A [57.94mm] 1/4" [6.35] Escutcheon Adjustment "A" Dimension 1/2" [12.7mm] Adjustment Range Escutcheon Adjustment OfoF002B r t1/4~ 1/4" [6.36] [±6.35mm] Escutcheon Adjustment Available "A" Dim. is 3-1/2" to 48" (89mm to 1219mm) in 1/4" (6mm) increments Note: Do not install the Model DH56 Dry EC Horizontal Recessed Sidewall Sprinkler in walls which have positive pressure in their side space. Fig. 5 5. DH56 HSW CONCEALED DRY SPRINKLER iii:r-t 1Wing I I i I ....-:_i_7411"' .�. r» ` LL _ IIIIIIIIIIII _—_—_ _ �II,I i..-.� d�d .�. .. new ���'' w 01111111 �, ___�� mi ' -__ , r i 1 i VZ ���� L._. ,, of Carphie• oferooM Dl6rarWs w mows A $4ILM7 is MO a„ 7°""f Izmir Available "A" Dim. is 3-1/2" to 48" (89mm to 1219mm) in 1/4" (6mm) increments Fig. 6 I \ 13' [4m] Minimum Spacing I 28' [8.5m] Maximum Spacing \ MODEL DH56 DRY SPRINKLER I \ r \ WALL F0� Ii 4. '1°61°' , + 4" [100mm] min.From Ceiling [305mm] max.From Ceiling 28' [8.5m] /, 12" 10' [3m] 016FGO4A \rte Fig.7 6. *CAUTION* DO NOT INSTALL MODEL F3, MODEL F3QR OR MODEL DH56 HSW DRY SPRINKLERS INTO CPVC ADAPTER FITTINGS OR TEES THAT HAVE AN INTERNAL OBSTRUCTION. THIS WILL DAMAGE THE SPRINKLER AND/OR THE FITTING. CPVC ADAPTER FITTINGS AND TEES WITH INTERNAL OBSTRUCTIONS ARE ALSO COMMONLY FOUND DURING THE RETROFITTING PROCESS OF RELIABLE'S OLDER MODEL G3 DRY SPRINKLERS. INTERNAL NO INTERNAL OBSTRUCTION OBSTRUCTION TIE FEMALE 0` �� FEMALE 0 PIPE %� 4PIPE . ;` � THREAD THREAD � INCORRECT CORRECT CPVC ADAPTER CPVC ADAPTER FITTING OR TEE FITTING OR TEE RELIABLE MANUFACTURES A FULL—LINE OF MODEL F3—PL. MODEL F3QR—PL. AND MODEL DH56 HSW—PL DRY SPRINKLERS THAT HAVE A SHORTER INLET FOR THESE APPLICATIONS. SHORTER LONGERINLET INLET -- -- MALE RI MALE PIPE PIPE THREAD THREAD MODEL F3—PL, STANDARD MODEL F3QR—PL OR MODEL F3, MODEL DH56 HSW—PL MODEL F3QR OR DRY SPRINKLER MODEL DH56 HSW DRY SPRINKLER BE SURE TO ORDER THE CORRECT SPRINKLERS FOR YOUR APPLICATION 016fgo8 Fig.8 7. 1 • Ordering Information Installation Wrench Specify: Model XLO2 Sprinkler Wrench (Recessed &Concealed) 1. Sprinkler Type (select one): Model G3 Sprinkler Wrench (a)Model DH56 Dry EC HSW Note: A leak tight 1" NPT sprinkler joint can be obtained (b)Model DH56 Dry Recessed EC HSW/FP with a torque of 20-30 ft-lbs (27.1 - 40.7 N-m). Do not (c)Model DH56 Dry Concealed EC HSW tighten sprinklers over maximum recommended torque. 2. Sprinkler Temperature Rating. It may cause leakage or impairment of the sprinklers. 3. Sprinkler Finish. 4. Cover Plate/Escutcheon Finish. Escutcheon Data: 5. Length: "A"Dimension(face of tee to face of ceiling or FP cup/escutcheon assembly-1/2"(13mm) adjustment wall) in 1/4" (6mm) increments. Finishes (1) Note: Standard Finishes(1) 1. The "A" dimension is based on a nominally gauged Sprinkler Escutcheon Cover Plate pipe thread "make-up" of 0.600" (15mm) per ANSI White Polyester(2) B2.1 [71/2 threads approximately]. /Chrome/Bronze White/Chrome White 2. All platings and paintings are decorative and intend- 11) Other colors and finishes are available. Consult factory for details. ed for interior use. (2)cULus Listed as Corrosion Resistant Sprinkler in standard Black or White. UL Listing Category Note:Paint or any other coatings applied over the factory finish will void Sprinklers, Automatic and Open. Quick Response Sprinklers. all approvals and warranties. The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association,Factory Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Productsmanufactured and distributed by Reliable have been protecting life and property for over 90 years,and are installed and se " -.by the most highly qualified and reputable sprinkler contractors located throughout the United States,Canada and foreign countries. *It %O. Manufactured b The Reliable Automatic Sprinkler Co.,Inc. Recycled ® (800)431 1588 Sales Offices Paper IiabI (800)848-6051 Sales Fax (914)829 2042 Corporate Offices Revision lines indicate updated or new data. www.reliablesprinkler.com Internet Address EG.Printed in U.S.A 05/10 P/N 9999970308 FlameGuard® PEARS ICPVC FIRE SPRINKLER PRODUCTS ) FG-2-0312 Complete System of Pipe, Fittings & Solvent Cement Corrosion Resistant • Superior Flow • Ease of Installation . <.a, a. Spears® FlameGuard® CPVC Fire Sprinkler Products provide a cost effective alternative to metal systems with advantages of high corrosion fftresistance, improved system hydraulics, ease of installation and quick ,'` .'=i' �d, ; assembly with readily available tools. CPVC Fire Sprinkler Systems are 11""''F— ,1' 1 # u1Jf: based on proven CPVC Ma VIM=PROMO'S products that ! . have been in continuous service for over 40 years. Spears®Fla meGuard® � — E ii products are approved by UL®, FM® 1 .. Global, LPCB and Certified by NSF ' II 110 International for potable water use. N Check local codes for restrictions and limitations. Corrosion Resistant CPVC Material Does Not Easy Installation for Lower Costs Sustain Biological Growth FlameGuard®CPVC system installations significantly Unlike metal systems, FlameGuard®CPVC products never reduce costs over conventional metal piping by virtually rust,scale or pit and do not sustain biological growth-a cause eliminating prefabrication. Systems can be fully installed of Microbiologically Influenced Corrosion(MIC)which can on site using solvent cement joining methods. destroy metal fire sprinkler systems from the inside out. UL®Listed for U.S. and Canada in Superior Flow Characteristics for Lower NFPA 13, 1FlameGuard® & 13D Systems Friction Losses FlameGuard CPVC Fire Sprinkler Products are UL® The smooth-wall interior surfaces of FlameGuard® CPVC listed for U.S.and Canada applications for Light Hazard systems result in reduced friction loss over metal systems. occupancies as defined in NFPA 13,Residential occupancies The design flow characteristics remain constant throughout up to and including 4-stories as defined in NFPA 13R, the life of the product because there is no interior corrosion and Residential occupancies for one and two family dwellings and manufactured homes as defined in NFPA in the system due to microbiological activity. 13D.Consult Spears®FlameGuard®CPVC Fire Sprinkler Pressure Rated to 175 psi (1200kpa) @ 150°F Products Installation Instructions and NFPA Standards for (65°C) additional applications including air plenum,system risers, FlameGuard®CPVC Products are produced in combinations concealed, exposed, underground, combustable attic, of Schedule 40 and Schedule 80 Fitting configurations con- garage,basement and low pressure dry piping installations. forming to ASTM F 438 or F 439 standards and FlameGuard® Full Limited Lifetime Warranty SDR 13.5 CPVC Fire Sprinkler Pipe conforming to ASTM F FlameGuard® CPVC Fire Sprinkler Products carry a 442 standards. UL® Rated working pressure is 175 psi limited lifetime warranty against defects in material or (1200kpa)@ 150°F(65°C)(LPCB rated to 120°F)(49°C). workmanship.Consult Spears®warranty for additional details. . PROGRESSIVE PRODUCTS FROM (:,,<,:.,„,-,-,.....„,,,, 1;:;)/ SPEARS®INNOVATION& LPCB 4,1109,---- TECHNOLOGY o UK AS s a MANAGEMENT O� °-L SYSTEMS � ' Visit our web site: www.spearsmfg.com 007 Spears® FlameGuard®. . . The Leader in Innovative CPVC Fire Sprinkler System Products Pioneer in Molded-in Metal Insert Head Adapters Spears® pioneered the development of the FlameGuard® molded-in-place metal thread insert for connection of sprinkler heads to CPVC fire sprinkler systems, plus Metal FIPT threaded female adapters for metal-to-plastic ,4- transitions. Developed the Special Reinforced (SR) Head Adapters Spears® FlameGuard® continuous improvement program developed the technology to produce a superior patented plastic threaded fitting - the Special Reinforced(SR)Design.This unique design incorporates a patented v4,,,,42!" - thermoplastic compression process that equalizes stresses generated by tapered thread joint make-up. All CPVC plastic body and threads provide a more uniform construction and improved corrosion resistance. Now, the Revolutionary TorqueSafeTM Gasket Sealed Head Adapter • Requires NO Thread Sealants • Eliminates Stress P • Prevents Over Tightening • Provides Easy Frame Alignment Spears® revolutionary design features a special molded-in-place Brass Thread Insert fitted with an elastomer gasket seal at the base of the threads. The gasket seal allows a modified thread design that eliminates radial stress and associated problems typical with tapered thread joint make up.The insert is designed to rotate for easy sprinkler frame alignment without over tightening. Patent Pending. Full Assortment of Specialty Products & Fitting Configurations Spears® FlameGuard® provides the specialty fittings needed in today's fire sprinkler systems. Like the adjustable drop nipple for fine-tuning to finished ceiling height,and ringed head adapter for ease of locating during installation. Plus, Spears®FlameGuard®line offers a full assortment of CPVC fire sprinkler fitting configurations including Tees, Elbows, Flanges, Couplings, Caps, Male Adapters, Grooved Coupling Adapters and Unions, sizes 3/4" through 3"; with new 3/4" and 1" Repair Couplings. Complete Size Range of CPVC Pipe (1111111111 Spears®FlameGuard®CPVC Fire Sprinkler Pipe is available in sizes 3/4" to 3". Conforms to ASTM F 442 standard for SDR 13.5 CPVC pipe. Spears® Solvent Cements & Thread Sealant FlameGuard®products should be installed using Spears® FS-5 One-Step Solvent Cement. For threaded joints, use Spears® BLUE 75'"Thread Sealant that has been tested for compatibility with FlameGuard® CPVC Fire Sprinkler Products. Spears®TorqueSafeTM Gasket Sealed Adapter requires no sealant. Consult sprinkler head manufacturer prior to use. Installation Training Available - Contact Spears® Technical Services for Details FlameGuard®Products must be installed in accordance with Spears®CPVC Fire Sprinkler Piping Products Installation Instructions,National Fire Protection Association Standards 13, 13R, 13D,and in accordance with local codes.Code requirements and field conditions may differ. It is the responsibility of the installing contractor to insure that the product is suitable to meet these requirements. SPEARS® MANUFACTURING COMPANY CORPORATE OFFICE . 15853 Olden St., Sylmar,CA 91342• PO Box 9203,Sylmar, CA 91392 (818)364-1611 •www.spearsmfg.com ©Copyright 2012 Spears®Manufacturing Company. All Rights Reserved.Printed in the United States of America 03/12. FG-2-0312 Ili: 7bll From BOO B2S"42BB•www.plan.erpips.eotn Scope Bending Teat CCoId3 ' Covers black and hot-dipped galvanized furnace butt-welded For NPS 2"and under (continuous welded)Grade A pipe. Pipe Is intended Degree of Bend Diameter of Mandrel (. for mechanical and pressure applications and is acceptable Standard 90' . 12 x outside pipe • for ordinary uses bi steam,water,gas and air lines. Pips diameterClose Coiling 90' 8 x outside pipe is sukable for welding,threading,grooving and bending. diameter Flattening Test Hot"Dipped Dalvanized As a test for quality of the weld for pipe 2W NPS and larger, The average weight of zinc coating shall be not less than position the weld at 90'from the direction of force and flatten until the 1.8 oz.per sq.ft.of surface(inside and outside). OD is 3/4 of the original outside diameter. No cracks shall occur along When galvanized pipe is bent or otherwise fabricated the Inside or outside surface of the weld. to a degree which causes zinc coating to stretch or compress beyond the lknit of elasticity,some flaking'of the coating Frequency of Tests may occur. Tensile teats are required on each lot of 25 tons or fraction thereof of pipe NPS 1W and smaller and horn each lot of 50 tons or fraction Hydroatatio Testing thereof of pipe NPS 2 and larger. Hydrostatic lest pressures for plain-end pipe are For NPS 2W and larger,a flattening test is also required on each lot of 60 tone. NPS Std.Weight Extra Strong 16'through 1" 700 psi 850 psi Dimensions and Weights 1W through 3" 1000 psi 1300 psi The dimensions and weights furnished under this specification are in • agreement with the standardized dimensions and weights specified in End Finish ASME B 36.10. Plain End: Black Plain End NPS 1W and smaller:unless otherwise specified on order, PermleeUale • end finish shall be at the option of the manufacturer. Variations Soh 40 Soh 80 In Wall Nominal OD Weight Weight NPS 2'and larger,STD and XS weights:ends beveled Size Inches Wall LbJFt. Wall Lbs/Ft. to angle of 30',a5°,-0'with a root face of *%x". Thickness y: .406 .068 .24 .096 .31 Minimum wall thick- '/.' .540 .088 .43 .118 .54 • • Threaded:To ANSI Standard B 1.20.1 ness at any point shall +/,"y, .840 . 9 .86 .148 .09 ,840 .11008 .86 .147 1.09 not be more than l.* 1.050 .113 1.13 .154 1.48 ' • Couplings:To ASTM Standard A 865 1" 1.915 .133 1.88 .179 2.17 12.5%under nominal 1'/: 1.880 .140 2.27 .191 8.00 1W 1.800 .145 2.72 .200 3.83 . Chemical Requirements wall thickness 2" 2.676 .154 3,86 .218 5.03 specified. 2'/a" 2.375 .203 6.80 278 7.67 Composition,max.% 3" 3.600 .218 7.58 .300 10.26 Dothan Manganese Phosphorus ' $uifur, ' 30 120 05 .045 Permissible Variations In Outside Diameter NPS 1'!e and under: ±.016" *Copper *NIdrel •Chromium "Molybdenum "Vanadium NPS 2"and over: *1% .40 .40 .40 .15 .013 *The combination of these five elements shall not exceed 1.00%. Permissible Variations Weight Per Foot Pipe shall not vary more than*10%from the standard specified. Tenet's Requirements Tensile Strength,min. 48,000 psi Product Marking Each length of pipe 1/1"NPS and larger is continuously stenciled to Yield Strength,min. 30,000 psi show the manufacturer,the grade of pipe(ASTM A53),the kind of pipe Elongation in 2" Refer to A53 Table X4.1 (F for continuous weld,A for Grade A),the size,XS for extra strong, and length. Legal Notice:This brochure is Intended for general information only. Pioneer makes no warranty or representation,expressed or hnpiied,of any kind with respect to the information contained herehr and shall In no event assume liability or responsibility for any loss,damage or Injury whatsoever resulting from the use of this Information. In all rimes,the customer is therefore requested to use this information Mks own risk and responsibility. North Amerlcon Pipe&Steel www.napsteel.com PAP$teel FIRE SPRINKLER PIPE �.. _. ,E, North American Pipe & Steel has been a trusted source for steel piping products since 1981. With strong ties to mills in the U.S. and abroad, we are certain to supply "What you need when you need it". Our fire sprinkler line of pipe is another example of our commitment to meeting the needs of our increasing customer base. NAP SuperFlow and NAP Schedule 10 Pipe is: manufactured to ASTM A135,A795 and A53A. UL listed and FM approved for fire sprinkler applications including roll grooved, plain end and welded joints. fully traceable. V ANIMA IWO NAP SuperFlow L' 1-1/4" 1.660 1.494 1.400 61 300 3.70/0.26 ear 2 185 2.320 ® 300 3.58/0.30 3" 3.500 3.320 3.280 19 300 1.27/0.09 i-tait14; 64;1' /TA NAP Schedule 10 7,f 7 e rtr aM ` 6 e s k fi , t 1-1/4" 1.660 1.442 1.400 61 300 — fit177' St,, .. '.� 2" 2.320 37 300 — 0 .:, ®s'49/+,n �„x ¢ s£;..* e„,` h .F ® 3.500 3.260 3.280 19 300 1.111.11111111 4Y7s '.a � . {" , 19 • s .. x ,. ., ¢. NAP Super Flow Pipe and NAP Schedule 10 Pipe are manufactured by MS Pipe Co.,LTD, South Korea Surrey,BC Longview,WA Auburn,WA Nampa, ID 11933 Tannery Road,V3V 3X1 7 International Way,98632 3136 B Street NW,98001 2114 Delta Drive,83687 1-800-665-7473 1-877-735-0275 1-877-735-0275 1-877-735-0275 Ductile Iron Threaded Fittings < j f2i itcar Ductile Iron Threaded Fittings • 4 branded fittings are UL Listed and FM Approved at 500 psi • Rated to 300 psi WSP cus • Ductile iron castings conform to ASTM A536 liSTED • Fitting dimensions conform to ASME B16.3 • Bushings and plugs conform to ASME B16.14 411;;X°P' • All fittings are 100% air tested APPROVED • NPT threads on all fittings conform to ASME B1.20.1 • Independent lab verification that fittings meet applicable chemical&mechanical properties • Manufacturing facilities are ISO 9001:2008 and ISO 14001 • ProPakTM Packaging 'e €stature t Norm PreSiu ren-S t ps�g } ees >;*; Class 300 Threaded f rigs -20 to 100 500 h � W 200 480 300 440 a 400 400 t w• - , yi yy ",e 45 1.� .F Ar.-x•Sg... Aktf.,y Y±3060 500 360 . *0 34 600 320 SCI ProPakT"i System • I Ductile Iron Threaded Fittings- Class 300 UL/FM calus APPROVED LISTED Fig. 35E 3 90°Elbow A aCkif i if! 1/2 35E 3004 1 13 100 200 0 2 /i ' ) A 1 35E3010 1.50 40 80 05 l 1-1/2 35E 3014 1.94 18 36 1.1 rc 2-1/2 35E 3024 2.70 4 8 3.2 111/1 B T Fig. 35RE3-90°Reducing Elbow ( ) I I� � Ca I 3/4 x 1/2 35RE3006004 ,,,,,,,,,,,,,,1;20, 1.22 80 160 0.3 v- 1 x 3/4 35RE3010006 1 38 1.45 50 100 0.4 1-1/4 x 3/4 35RE3012006 1.45 1.63 35 70 0.6 1-1/2 x 1/2 35RE3014004 1.52 1.75 30 60 0.6 1-1/2 x 1 35RE3014010 1.65 1.80 20 40 0.8 a . !° ° 2 x 1/2 35RE3020004 1.60 1.97 18 36 1.0 w.. , ,}. w °r.' <6 i ILI, . '.:46:1:!.':!:.:i!".? , 2 x 1 35RE3020010 1.73 2.02 16 32 1.2 :m 2 x 1-1/2 35RE3020014 2.02 2.16 10 20 . .:M 1 5 �¢¢ �yx� M�xe:: 5 �y��y 3 d�.� 7? .B '^s.I- .. s 1,� `y' �,,, mtDd.di�"k:.�, x i, EI'�M w' �a .,.. Rie 2-1/2 x 2 35RE3024020 2.39 2.60 6 12 2.5 Fig. 35F 3-45°Elbow ... ""'-'''''-"'''''' -wilf-• .,i,...,-,,,,,t,iz A � � A e ! 1/2 35F 3004 0.88 150 300 0.2 35F 3010 1.1,3 40 .: 80. 0.5 ,,im�� 1A [,,, .,,1,-[-11/2 . 3 3011 r ,1;44, 20. . 40 n 1:0,,,, 0 T 2-1/2 35F 3024 1.95 4 8 2.7 Fig. 35T 3- Tee Sized tt �mber w�. ' P f, g +,._ 1 a� ` � : ,. v ..,,r„.,,t ? x....1'..;I: 7 6,,,- F este.. , ',., 1110/ `!z�,c_` 1/2 35T 3004 1 13 80 160 0.3 1 35T3010 1.50 25'' 41' 50 ''''''''''''11:7S ,--�� i.. .' , ,. ., ... ,,x 41: ,. . ..x,.. ' . 11.1,11 A I A 1 1/2 35T 3014 �{#5§s 1 94 10 20 1 5 P,;['[:[['[[;,...2 . 3 tt '-'-1[1,[0‘,:[1,- "„+,9a: *'ex3. '",,I..:../- : 30.11;;;..,Ir , s ' c 2-1/2 35T 3024 2.70 4 8 4.3 201 SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com (.. „ I Ductile Iron Threaded Fittings - Class 300 UL/FM • c 43 us Fig. 35RT3-Reducin8' Tee LISTED APPROVED . . P.� IU ller . a^ h 11V ht:. " I I \`�� C 3/4 x r11�//2 35RT3006004 1.20 1.20 1.22 60 120 0.4 -`= I 'M+� 7 d3'raJPI a 1 a 3 � vsgiw S. a s i x 1/2 x 1 35RT3010004010 1 50 1 36 1.50 30 60 0 6 DB '( A ) 1x3/4x3/4 35RT3010006006 1.38 1.31 J.45 35 70,B 0.6 ,, ' � ; 0.`. n' i s _, < ' A . i U 1-1/4 x 1/2 35RT3012004 1.34 1.34 1.53 20 40 0.8 ::-. 4:41: �k rrs.0 ("L`u.sX.lt wteJ .',.'41;701... . A x � ''fiki'� Y," '7444 1-1/4 x 3/4 35RT3012006 1.45 1.45 1.62 15 30 0.9 y . 71110 LL y416 1-1/4 x 1 35RT.�3012010 yy,g1(.58 1.58 y1..66y7�lSj 15 30 1.0 1-1/4 x 1 x 3/4 35RT3012010006 1.45 1.38 1.63 20 40 0.8 1-1/4 x 1 x 1-1/4 35RT3012010012 1.75 1.69 1.75 15 30 1.0 .s 1-1/2x1/2x1-1/4 35RT3014004012 1.81 1.56 1.88 24 48 1.1 rfifItW 1-1/2x3/4 35RT3014006 • 1.52 1.52. . AI 1 75 •16 • 32 1.1 ' j . M +a i 1, /2x3/4 -1/2. 35ART3014006014 11.94 . 1.751 1.94 18 r36. 1.2 ' 1-1/2 x 1 x 1/2 35RT3014010004 1.44 1.25 1.69 20 40 0.8 ''1'1/2 x 1,C„�4 ^ , `m '.r�: rJ: ' ,,..-00,..4401C-. '`P70 1-1/2 x 1 x 1 35RT3014010010 1.65 1.50 1.80 16 32 1.0 1`1I Ci�if4' ,'4� � � a 0_ IIiC Olt;': F H, 1-1/2 x 1 x 1-1/2 35R13014010014 1.94 j 1.80 1.94 12 24 1.3 < ;'it• tel `r 7 r, ? W ' tt# > r: , •'"01:,.. ;. nt477. 1-1/2 x 1-1/4 x 1/2 35RT3014012004 1.41 1.34 1.66 16 32 0.9 ti)74i /4 ';Y. 4 r 4ICK410, N.a itt O,7, 1-1/2 x 1-1/4 x 1 35RT3014012010 1.65 1.58 1.80 16 32 1.1 1-1/2 � l���x �/235��114 �,���94 1.88 1.94 14 28 1.4 2 x 3/4 35RT3020006 1.60 i 1.60 1.97 10 20 1.6 2 x 1 x 2 35RT3020010020 2.25 2.02 2.25 8 16 1.9 2 x 1-1/4 x 2 35RT3020012020 2.25 2.10 2.25 8 16 2.0 2 x 1-1/2 x 1/2 35RT3020014004 1.49 1.41 1.88 10 20 1.3 i2''f> x ( .0 L }d fftr:414 • Yf illtii 4 2 x 1-1/2 x 1 35RT3020014010 1.73 1.65 2.02 8 16 1.5 2t 1.it*44, .. T40Jk 1 ?-. ,:2: >1. :` -,s::144.71 '1,, 1 2 x 1-1/2 x 1-1/2 35RT3020014014 2.02 1.94 2.16 8 16 1.8 Fig. 35BT3-Bull Head Tee S.ige < A B. C Pa P. : Wei ht: C in } 1n . in ' in Inner .aster:',- Ib :-. la' .1 3/4x 1 35BT3006010 1.45 1 45 1 37 30 60 0.6': 1.�<�-114 '° 1'',3CI 1 '4 t'`, 1'�7�:- 1•.. 40'�t,� flw9 ';Y�IIIIIIII � ----- ...i • 1 x 1-1/2 35BT3010014 1.80 1.80• 1.65 15 • 30 1.0 • (---)1(---9 1-1/4 x 1-1/2 35BT3012014• 1.88 1.88 1.82 15 30 1.3 1? ., 1-1/2��-1�/4 x 2,. 3530 O'L�:t oU;� 1�' .'10 44�' ,.40.:,,:',,,]';1t°r>1;2QA ;� ; 0 2.16 2.10 2.02 1 20 1.8 1 1/tic 5 `r3bj4026 2: =E ft:.-f aM 2,62`., ' 'f r 202 SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com . i Ductile Iron Threaded Fittings- Class 300 UL/FM < ..H-. ! 1 c0us APPROVED Fig. 35CP3 -Straight Coupling with Ribs LISTED 0 A rr. u ` IMIUTg. 71:Wi tim. 1/2 35CP3004 200 400 0.1 t! ie ee, _ is �� 1 35CP3010 1.754 60 120 0.4 t" ... .ia . a. .... `:. S; `. 113:& :: .. .. �^k'�". , r... :.!,: 1-1/2 35CP3014 2.19 25 50 0.7 2-1/2Ogn1 " 35CP3024 3.00 9 18 2.2 T Fig. 35RC3 -Hex Reducing Coupling ry 11 iik 1 x 1/2 35RC3010004 1.69 80 160 0.3 4; I 1 1-1/4x3/4 35RC3012006 2.06 40 80 0.6 M1, 1 7` `4;:;, f;g 4 h .-, 'A., a tw'{ -. '. 6 _ 'bC ..+'~.at?Pz.=' p :.., . Fig. 35HB3 -Hex Bushing . f kA 1;. 1 x 1/2 35HB3010004 1.06 1.40 180 360 0.2 ��1111111111/1 I I IA 1 1/4 x 1 35HB3012010 1.19 1.80 90 180 0.2 1-1/2 x 1-1/4 35HB3014012 1.25 1.95 75 150 0.3 ;r' ic; i".` i -i1FIV.Zilitt. ;,i 5i771; ads . iT 7.A. z.. 2 x 1-1/4 35HB3020012 1.38 2.55 40 80 0.6 ,iiEti r fi 4µi Fig. 35SP3 -Square Head Plug S �� 1/2 35SP3004 0.94 600 1200 0.07 1\ i °1 1 35SP3010 1.25 200 400 0.1 1-1/2 35SP3014 1.44 80 160 0.4 Fig. 35U 3-Union with Brass Seat A , ,biZeFh P. i } �i,.: ���.�.,wAn. � � :4,e, �1�t ;;;; B� It= a �. / 1�� - 1 35U 3010 2.19 20 40 1.0 1-1/2 35U 3014 2.62 10 20 1.7 777�kOKG i .e. . ;i':4r ¢.id,'''.. M..*`zs....:;-"l .,.f t,r. - .. . _ 1%xt ...:4--. s1-1 .. .... 203 SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • wwwsmithcooper.com I Ductile Iron Threaded Fittings - Class 300 UL/FM c us Fig. 35X 3 Cross LISTED APPROVED $ia . _ a V; �n ;��� " � umbel� �, � � ,IU( A � .�.x� �� P . . r . � I •i% 1 35X 3010 1.50 20 40 0 9 I I 7_ • rr ici ---I 11 1-:1/2 5X 3014 1 94 8 16 1.8 U` C Li B Fig. 35RX3—Reducing Cross B � e art 1 r i1 F sfght m. '""1—''47Z. IA in _ in in m41. inner a o- 1 1/4 x 1 35RX3012010 1 67 ,1;58, 111 15 30 1 2 TA 2 x 1 35RX3020010 2.02 1.73 8 16 2.0 "`1 I JI m A Fig. 35C 3—Cap ht h a A 1/2 35C 3004 '''0.87 300 600 0.1 . . • r' Tr. ° 4, 1...M - 1 35C 3010 1.16 110 220 0.2 1-1/2 35C 3014 1.33 50 100 0.5 2-1/2 35C 3024 1.70 18 36 1.6 Fig. 35BC3—Beam Clamp 1 =; � • I .. 0 it �.� in inner : aster Io A. :;$ NEI 3/8 35BC3003 0.75 100 200 0.3 204 SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • wwwsmithcooper.com FireLock® Fittings ✓ataulid 10.03 Material Specifications: r Fitting: Ductile iron conforming to ASTM A-536,grade 65-45-12. 111 Fitting Coating: ❑ Orange enamel ❑ Red enamel in Europe, Middle East, Africa, and India ❑ Optional: Hot dipped galvanized Approvals/Listings: C®Us FM LPCB] VdSMED l tT_P Product Description: FireLock®products comprise a unique system specifically designed for fire protection services. FireLock full-flow elbows and tees feature CAD- developed, hydrodynamic design, affording a shorter center-to-end dimension than standard fittings. A noticeable bulge allows the water to make a smoother turn to maintain similar flow characteristics as standard full flow fittings. FireLock fittings are designed for use exclusively with Victaulic couplings that have been Listed or Approved for Fire Protection Services. Use of other couplings or flange adapters may result in bolt pad interference. Refer to the appropriate listing agency or approval body for pressure ratings. Pressure ratings vary by agency. Job/Owner Engineer System No. Spec Section Location Paragraph Contractor Approved Submitted By Date Date victaulic.com I FireLock®Fittings I Publication 10.03 10.03 1539 Rev M Updated 12/2014 ©2014 Victaulic Company.All rights reserved. 1 iCtaUliC" victaulic.com I FireLock®Fittings I Publication 10.03 Dimensions: -CtoEy C 1 I ,>\ i to E II C to ^) C---4-#1 .ani 1- C O p °I II II C I ^T tj" �✓ J '' j_ E e e 1 NO.001 NO.003 NO.002 No.006 No.001 No.003 No.002 No.006 90°Elbow 45°Elbow Straight Tee Cap Actual Approx. Approx. Approx. Approx. Nominal Outside Weight Weight Weight Weight Size Diameter C to E Each C to E Each C to E Each C to E Each inches inches inches Lbs. inches Lbs. inches Lbs. inches Lbs. mm mm mm kg mm kg mm kg mm kg 1�'A 1.660 0.82 0.3 32 42.4 - - - - - - 21 0.1 1 Y3 1.900 - - - - - - 0.82 0.4 40 48.3 - - - - - - 21 0.2 2 2.375 2.75 1.7 2.00 1.8 2.75 2.4 0.88 0.6 50 60.3 70 0.8 51 0.8 70 1.1 22 0.3 21/4 2.875 3.00 3.1 2.25 2.2 3.00 3.6 0.88 1.0 65 73.0 76 1.4 57 1.0 76 1.6 22 0.5 76.1 mm 3.000 3.00 330 2.25 2.4 3.00 3.8 76.1 76 1.5 57 1.1 76.2 1.7 - - 3 3500 3.38 4.0 250 3.1 3.38 5.3 0.88 1.2 80 88.9 86 1.8 64 1.4 86 2.4 22 0.5 108 mm 4.250 4.00 5.7 3.00 5.1 4.00 7.5 - 108.0 102 2.6 76 2.3 102 3.4 - 4 4.500 4.00 6.7 3.00 5.6 4.00 8.7 1.00 2.4 100 114.3 102 3.0 76 2.5 102 3.9 25 1.1 5 5563 4.88 12.6 3.25 83 4.88 15.7 1.00 4.1 125 141.3 124 5.7 83 3.8 124 7.1 25 1.9 139.7 mm 5.500 4.88 12.4 3.25 8.2 4.88 15.4 139.7 124.0 5.6 82.6 3.7 124.0 6.9 - - 159 mm 6.250 550 12.6 3.50 9.2 550 17.9 158.8 140 5.7 89 4.2 140 8.0 - - 6 6.625 550 18.3 3.50 11.7 5.50 22.7 1.00 5.9 150 168.3 140 8.3 89 53 140 103 25 2.7 165.1 mm 6500 5.43 17.6 3.50 11.4 5.50 22.0 - 165.1 139.7 7.9 88.9 5.2 139.7 9.9 - 8 8.625 6.81 25.5 4.25 20.4 6.94 38.7 1.13 12.7 200 219.1 173 11.6 108 93 176 17.6 29 5.8 10.03 1539 Rev M Updated 12/2014 0 2014 Victaulic Company.All rights reserved. victaulic.com 2 ✓Ctaulic victaulic.com I FireLock® Fittings I Publication 10.03 Flow Data: Frictional Resistance Actual Equivalent Feet/meters of Straight Pipe' Nominal Outside No.002 Size Diameter Elbows Straight Tee inches inches No.001 No.003 mm mm 90°Elbow 45°Elbow Branch Run 11/4 1.660 - - - - 32 42.4 - - - - 11h 1.900 - - - - 40 48.3 - - - - 2 2.375 3.5 1.8 8.5 3.5 50 60.3 1.1 05 2.6 1.1 21 2.875 4.3 2.2 10.8 4.3 65 73.0 13 0.7 3.3 1.3 76.1 mm 3.000 4.5 2.3 11.0 4.5 76.1 1.4 0.7 3.4 1.4 3 3.500 5.0 2.6 13.0 5.0 80 88.9 1.5 0.8 4.0 1.5 108 mm 4.250 6.4 3.2 153 6.4 108.0 2.0 0.9 4.7 2.0 4 4.500 6.8 3.4 16.0 6.8 100 1143 2.1 1.0 4.9 2.1 5 5.563 8.5 4.2 21.0 8.5 125 1413 2.6 1.3 6.4 2.6 139.7mm 5.500 8.3 4.1 20.6 83 139.7 2.5 1.3 63 2.5 159 mm 6.250 9.4 4.9 25.0 9.6 158.8 2.9 1.5 7.6 2.9 6 6.625 10.0 5.0 25.0 10.0 150 1683 3.0 1.5 7.6 3.0 165.1 mm 6.500 9.8 4.9 24.5 9.8 165.1 3.0 1.5 7.5 3.0 8 8.625 13.0 5.0 33.0 13.0 200 219.1 4.0 1.5 10.1 4.0 ' The flow data listed is based upon the pressure drop of Schedule 40 pipe. General Notes: NOTE:When assembling FireLock EZ couplings onto end caps,take additional care to make certain the end cap is fully seated against the gasket end stop. For FireLock EZ Style 009N/009H couplings, use FireLock No.006 end caps containing the"EZ" marking on the inside face or No. 60 end caps containing the "QV EZ" marking on the inside face. Non-Victaulic end cap products shall not be used with Style 009/009V/009H couplings. Installation Note Reference should always be made to the 1-100 Victaulic Field Installation Handbook for This product shall be manufactured by Victaulic or to Victaulic specifications.All products the product you are installing.Handbooks are included with each shipment of Victaulic to be installed in accordance with current Victaulic installation/assembly instructions. products for complete installation and assembly data,and are available in PDF format Victaulic reserves the right to change product specifications,designs and standard on our website at www.victaulic.com. equipment without notice and without incurring obligations. Warranty Trademarks Refer to the Warranty section of the current Price List or contact Victaulic for details. Victaulic®is a registered trademark of Victaulic Company. 10.03 1539 Rev M Updated 12/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 3 ictauliC Victaulic® FirelockTM Rigid Coupling jctaulie Style 009N 10.64 • Patented 1.0 CERTIFICATION/LISTINGS u� FM LPCB v ds C104-1a/36 2.0 PRODUCT DESCRIPTION • The FireLock EZTM Style 009N Installation-ReadyTM Rigid Coupling is for use in the fire protection market. • The coupling's unique design eliminates loose parts, promotes consistent installation and provides substantial gains in productivity. • IMPORTANT: FireLock EZTM Style 009N couplings are recommended for use ONLY on fire protection systems. 3.0 MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A 536, Grade 65-45-12. Ductile iron conforming to ASTM A 395, Grade 65-45-15, is available upon special request. Housing Coating: (specify choice) O Orange enamel (North America,Asia Pacific) ❑ Red enamel (Europe) O Hot dipped galvanized Gasket: (specify choice') ❑ Grade"E" EPDM (Type A) FireLock EZ products have been Listed by Underwriters Laboratories Inc., Underwriters Laboratories of Canada Limited, and Approved by Factory Mutual Research for wet and dry(oil free air)sprinkler services within the rated working pressure. 1 Services listed are General Service Guidelines only.It should be noted that there are services for which these gaskets are not compatible.Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service guidelines and for a listing of services which are not compatible. Bolts/Nuts: Zinc electroplated carbon steel,trackhead meeting the physical and chemical requirements of ASTM A 449 and physical requirements of ASTM A 183. System No. Location Spec Section Paragraph Submitted By Date Approved Date • victaulic.com I Couplings I FireLock I Rigid I Style 009N I Publication 10.64 10.64 7072 Rev G Updated 10/2014 ©2014 Victaulic Company.All rights reserved. 1 jataUlie victaulic.com I Couplings I FireLock I Rigid I Style 009N I Publication 10.64 4.0 LISTINGS/APPROVAL 2 The information provided below is based on the latest listing and approval data at the time of publication. Listings/Approvals are subject to change and/or additions by the approvals agencies. Contact Victaulic for performance on other pipe and the latest listings and approvals. Nominal Size cULus FM Vds LPCB Sch.5 Sch. 10 Sch.40 Sch.5 Sch.10 Sch.40 inches psi psi psi psi psi psi psi psi mm kPa kPa kPa kPa kPa kPa kPa kPa 11/4 232 365 365 175 363 363 363 363 32 1600 2517 2517 1205 2502 2502 2500 2500 11 232 365 365 175 363 363 363 363 40 1600 2517 2517 1205 2502 2502 2500 2500 2 363 365 365 175 363 363 363 363 50 2502 2517 2517 1205 2502 2502 2500 2500 21/2 N/A 365 365 175 363 363 363 363 65 2517 2517 1205 2502 2502 2500 2500 76.1 mm N/A 3653 N/A N/A 3634 N/A 363 363 25173 25024 2500 2500 3 N/A 365 365 175 363 363 363 363 80 2517 2517 1205 2502 2502 2500 2500 4N/A 365 365 175 363 363 363 363 100 2517 2517 1205 2502 2502 2500 2500 175 363 363 108.0 mm N/A N/A N/A 1205 2502 2502 N/A N/A 5 290 365 363 363 232 125 N/A 2000 2517 N/A 2502 2502 1600 N/A 133.0 mm N/A N/A N/A N/A 25024 N/A N/A N/A 363 4 232 139.7 mm N/A 200055 N/A N/A 2 02 4 N/A 600 N/A 159.0 mm N/A N/A N/A N/A 25024 N/A N/A N/A 165.1 mm N/A 2000 a N/A N/A 2290 6 5024 N/A N/A N/A 6 290 365 363 363 232 150 N/A 2000 2517 N/A 2502 2502 1600 N/A 216.0 mm N/A N/A N/A N/A 25024 N/A N/A N/A 8 290 365 363 363 232 200 N/A 2000 2517 N/A 2502 2502 1600 N/A 2 Listed/Approved for wet and dry pipe systems(>—40°F/-40°C)for continuous use in freezing conditions,use of Style 005H Coupling with Silicone Gasket is recommended. Please see the Victaulic Installation Manual I-009N/009H for details concerning when supplemental lubrication is required. 3 cULus listed for DIN 2458 2.6 mm pipe wall. 4 FM approved for BS 1387 Medium 3.6 mm pipe wall. 5 cULus listed for EN 10220 4.0 mm pipe wall. 6 cULus listed for EN 10255 4.5 mm pipe wall. 10.64 7072 Rev G Updated 10/2014 C 2014 Victaulic Company.All rights reserved. victaulic.com 2 ✓ctaulic victaulic.com I Couplings I FireLock I Rigid I Style 009N I Publication 10.64 4.1 LISTINGS/APPROVAL Speciality Pipe Pipe Size Pressure Rating Pipe Size Pressure Rating Pipe Size Pressure Rating cULus FM cULus FM cULus FM inches psi psi inches psi psi inches psi psi kPa kPa kPa kPa kPa kPa BLT 1 y+—2 300 365EZT 1�/+ 2 300 365 300 365 2068 2517 2068 2517 MT 1/+ 2 2068 2517 300 365 300 365 DF 1�/+—4 2068 2517 FF 1 1/+—4 2068 2517 MLT 11/4—2 N/A 365 2517 300 DT 1 1/+—2 2068 256 7 FLF 11/4—4 N/A 2517 ST 1 1/+—2 N/A 365 365 2517 175 175 EF 11/+—4 1 06 1 06 FLT 1 1/+—2 N/A 365 STF 1 1/+—4 N/A 365 2517 2517 EL 11/4—2 2068 3651 FLTL 1 1/+—2 N/A 365 TF 21b—4 N/A 365 , 2517 2517 ET40 114—2 300 365 300 365 , 300 365 2068 2517 2068 2517�L 1,/+_2 WLS 1/+—2 2068 2517 300 365 300 365 EZF 3—4 2068 2517 MF 1 1/+—4 2068 2517 WST 11/+—2 N/A 365 2517 XL 11/+—2 300 2517 NOTES • BLT=BLT steel pipe manufactured by Allied Tube&Conduit Corp. • DF=DYNA-FLOW steel pipe manufactured by Allied Tube&Conduit Corp. • DT=DYNA-FLOW steel pipe manufactured by Allied Tube&Conduit Corp. • EF=EDDY FLOW steel pipe manufactured by Bull Moose Tube Co. • EL=EDDYLITE steel pipe manufactured by Bull Moose Tube Co. • ET40=Eddythread 40 steel pipe manufactured by Bull Moose Tube Co. • EZF=EZ-Flow steel pipe manufactured by Northwest Pipe Co. • EZT=EZ-Thread steel pipe manufactured by Youngstown Tube Co. • FF=Fire-Flo steel pipe manufactured by Youngstown Tube Co. • FLF=Fire-Line Flow steel pipe manufactured by Western International Forest Products Inc. • FLT=Fire-Line Threadable steel pipe manufactured by Western International Forest Products Inc. • FLTL=Fire-Line Threadable Light steel pipe manufactured by Western International Forest Products Inc. • GL=GL steel pipe manufactured by Wheatland Tube Co. • MF=Mega-Flow steel pipe manufactured by Wheatland Tube Co. • MT=Mega-Thread steel pipe manufactured by Wheatland Tube Co. • MLT=MLT steel pipe manufactured by Wheatland Tube Co • ST=STD wall pipe in accordance with ASTM A53. • STF=Steady Flow steel pipe manufactured by AMS Tube Corp. • TF=Tex-Flow steel pipe manufactured by Tex-Tube Co. • WLS=WLS steel pipe manufactured by Wheatland Tube Co. • WST=WST steel pipe manufactured by Wheatland Tube Company. • XL=XL steel pipe manufactured by Allied Tube&Conduit Corp. • • 10.64 7072 Rev G Updated 10/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 3 ✓ctaulic victaulic.com I Couplings I FireLock I Rigid I Style 009N I Publication 10.64 5.0 DIMENSIONS Style 009N Y ...---•. y r-IIZ-r 011 ...,-----\...., IN /TM& 1Tji 11 tar ca ni .11- e. Style 009N Pre-Assembled Style 009N Joint Assembled (Push On Condition) Dimensions Actual Maximum Maximum Allow. Pre-assembled Approx. Nominal Outside Working End Pipe End Bolt/Nut a (Push On Condition) Joint Assembled Weight Size Diameter Pressure' Load ' Separations Size X Y X Y Z Each inches inches psi lbs. inches inches inches inches inches inches inches lbs. mm mm kPa N mm No. mm mm mm mm mm mm kg 11/4 1.660 365 790 0.102 %x 2 3.13 5.00 2.75 5.00 2.00 1.4 32 42.4 2517 3514 2.54 M10 x 2 79 127 70 127 51 0.6 11 1.900 365 1035 0.10 2 3/e x 2 3.38 5.13 3.00 5.13 2.00 1.5 • 40 48.3 2517 4604 2.54 M10 x 2 86 130 76 130 51 0.7 2 2375 365 1616 0.122 %x21 4.00 5.63 3.50 5.63 2.00 1.9 50 60.3 2517 7193 3.05 M10 x 21/2 102 143 89 143 51 0.9 2% 2.875 365 2370 0.122 3/e x 21h 4.50 6.13 4.00 6.13 2.00 2.1 65 73.0 2517 10542 3.05 M10 x 21/2 114 156 102 156 51 1.0 76.1 mm 3.000 365 2580 0.12 2 3/e x 21/2 4.63 6.00 4.13 6.13 2.00 2.1 76.1 2517 11476 3.05 M10 x 21h 118 152 105 156 51 1.0 3 3.500 365 3512 0.122 3/e x 21h23 5.13 6.75 4.63 6.75 2.00 80 88.9 2517 15622 3.05 M10 x 21h 130 171 117 171 51 1.0 4 4.500 365 5805 0.17 2 3/4 x 21/2 6.00 7.88 5.63 7.50 2.13 2.9 100 114.3 2517 25822 4.32 M10 x21/2 152 200 143 191 54 1.3 4.250 365 5175 0.17 2 3/e X 2% 5.63 7.38 5.38 738 2.13 3.1 108.0 mm 108.0 2517 23020 4.32 M10 x 21h 152 1.87 137 187 54 1.4 5 5.563 365 8870 0.172 1h x 3 725 9.25 6.75 9.13 2.25 5.0 125 141.3 2000 39456 4.32 M12 x 3 184 235 171 232 57 2.3 133.0 mm 5.250 365 7897 0.17 2 %x 3 6.63 9.00 638 9.00 225 4.8 133.0 2517 35106 432 M12 x 3 168 229 162 229 57 2.2 139.7 mm 5.500 365 8667 0.17 2 %x 3 6.88 9.25 6.75 9.13 2.25 4.9 139.7 2517 38529 4.32 M12 x 3 175 235 171 232 57 2.2 159.0 mm 6.250 365 11192 0.17 2 1h x 31/4 7.88 10.00 7.38 9.88 2.25 5.6 159.0 2517 49753 432 M12 x 31/4 200 254 187 251 57 2.5 165.1 mm 6.500 365 12105 0.17 2 1h x 31/4 8.00 10.25 7.75 10.13 2.25 6.0 165.1 2517 53813 432 M12 x3 Vs 203 260 197 257 57 2.7 6 6.625 365 12582 0.17 1h x 31/4 8.38 10.38 7.88 10.13 2.25 6.0 150 168.3 2000 44469 4.32 2 M12 x314 213 264 200 257 57 2.7 216.0 mm 8.500 365 20712 0.17 2 %x 4 10.63 13.25 10.25 10.13 2.63 11.4 216.0 2517 55968 4.32 M16 x4 270 337 260 257 67 5.2 8 8.625 365 21326 0.172 %x4 10.88 1338 10.25 13.13 250 11.4 200 219.1 1620 94863 432 M16 x 4 276 340 260 333 64 5.2 7 Working Pressure and End Load are total,from all internal and external loads,based on standard weight(ANSI)steel pipe,standard roll or cut grooved in accordance with Victaulic specifications.See the Listings/Approvals section of this publication for ratings on other pipe. 8 The allowable pipe separation dimension shown is for system layout purposes only.FireLock EZTh1 couplings are considered rigid connections and will not accommodate expansion or contraction of the piping system. 9 Number of bolts required equals number of housing segments. NOTES • When assembling FireLock EZTM couplings onto end caps,take additional care to make certain the end cap is fully seated against the gasket end stop.For FireLock EZT1 Style 009N couplings,use FireLock No.006 end caps containing the"EZ"marking on the inside face or No.60 end caps containing the"QV EZ"marking on the inside face.Non-Victaulic end cap products shall not be used with Style 009N couplings.IMPORTANT:Gaskets intended for the Style 009 or Style 009V couplings cannot be used with the Style 009N coupling.There is no interchanging of gaskets or housings between coupling styles. • Use Of Flushseal Gaskets For Dry Pipe Systems FireLock EZTM couplings are supplied with FireLock EZT4 Grade"E"Type A gaskets.These gaskets include an integral pipe stop,that once installed provides the similar benefits as a FlushSeal gasket for dry pipe systems.It should be noted that standard Victaulic Flush-SealTM gaskets are not compatible and cannot be used with the FireLock EZT"couplings. 10.64 7072 Rev G Updated 10/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 4 ✓otaulic' victaulic.com I Couplings I FireLock I Rigid I Style 009N I Publication 10.64 • • 6.0 REFERENCE MATERIALS Publication 05.01:Seal Selection Guide I-009N/009H:Installation Instructions FireLock Er"Rigid Coupling • • User Responsibility for Product Selection and Suitability Note Each user bears final responsibility for making a determination as to the suitability of This product shall be manufactured by Victaulic or to Victaulic specifications.All products Victaulic products for a particular end-use application,in accordance with industry to be installed in accordance with current Victaulic installation/assembly instructions. standards and project specifications,as well as Victaulic performance,maintenance, Victaulic reserves the right to change product specifications,designs and standard safety,and warning instructions.Nothing in this or any other document,nor any verbal equipment without notice and without incurring obligations. recommendation,advice,or opinion from any Victaulic employee,shall be deemed to Installation alter,vary,supersede,or waive any provision of Victaulic Company's standard conditions Reference should always be made to the l-009N/I-009H Firelock EZ Rigid Coupling of sale,installation guide,or this disclaimer. Installation Instructions for the product you are installing.Handbooks are included with Intellectual Property Rights each shipment of Victaulic products,providing complete installation and assembly data, No statement contained herein concerning a possible or suggested use of any material, and are available in PDF format on our website at www.victaulic.com. product,service,or design is intended,or should be constructed,to grant any license Warranty under any patent or other intellectual property right of Victaulic or any of its subsidiaries Refer to the Warranty section of the current Price List or contact Victaulic for details. or affiliates covering such use or design,or as a recommendation for the use of such material,product,service,or design in the infringement of any patent or other intellectual Trademarks property right.The terms"Patented"or"Patent Pending"refer to design or utility patents Victaulic,FireLock EZT"',Flush-SealT'^,and Installation-Ready'"'are trademarks or or patent applications for articles and/or methods of use in the United States and/or other registered trademarks of Victaulic Company,and/or its affiliated entities,in the U.S.and/ countries. or other countries. • 10.64 7072 Rev G Updated 10/2014 ©2014 Victaulic Company.All rights reserved. • victaulic.com 5 4tauiicr CARBON STEEL PIPE-GROOVED COUPLINGS 06.08 Reducing Coupling c uM V$ s [LPCB V, SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS STYLE 750 The Style 750 Reducing Coupling permits direct reduction on the piping run.Designed to replace two couplings and a reducing fitting,the Style 750 features a special reducing % St gasket for pressure responsive sealing.A steel washer which prevents telescoping of the smaller pipe inside the larger pipe during vertical systems assembly is available upon request. luAu La IEI MATERIAL SPECIFICATIONS Housing:Ductile iron conforming to ASTM A-536,grade 65-45-12.Ductile iron conforming to ASTM A-395,grade 65-45-15,is available upon special request. Housing Coating:Orange enamel • Optional:Hot dipped galvanized and others Gasket:(Specify choice*): • Grade"E"EPDM(All other sizes) I EPDM(Green color code).Temperature range-30°F to+230°F/-34°C to+110°C. Recommended for cold and hot water service within the specified temperature range plus a variety of dilute acids,oil-free air and many chemical services.UL classified in accordance with ANSI/NSF 61 for cold+86°F/+30°C and hot+180°F/+82°C potable water service.NOT RECOMMENDED FOR PETROLEUM SERVICES. • Grade"T"nitrile Nitrile(Orange color code).Temperature range-20°F to+180°F/-29°C to+82°C. Recommended for petroleum products,air with oil vapors,vegetable and mineral oils within the specified temperature range.Not recommended for hot water services over+150°F/+66°C or for hot dry air over+140°F/+60°C. * Services listed are General Service Recommendations only. It should be noted that there are services for which these gaskets are not recommended.Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service recommendations and for a listing of services which are not recommended. • Optional:Assembly Washer:Galvanized,carbon steel Bolts/Nuts:Heat-treated plated carbon steel,trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date Approved Date www.victaulic.com VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2012 VICTAULIC COMPANY.ALL RIGHTS RESERVED. IICt'aul,c REV_J 06.08_1 • CARBON STEEL PIPE-GROOVED COUPLINGS 06.08 Reducing Coupling STYLE 750 DIMENSIONS Max.Work Allow.Pipe Bolt/Nut@ Approx. Size Pressure' Max.End Load' End Sep.t Deflect.Fr.C,i No-Size Dimensions-Inches/mm Wgt.Each Nominal Per Pipe Size psi Lbs. Cplg. In./Ft. Lbs. Inches/mm kPa N Inches/mm Deg. mm/m Inches - 8 Y Z kg 2 1 350 500 ' 0-0.07 ' 0.20 2-3/8x2 338 I 528 ' 1,88 2.7 -5T l, 50 x 25 2410 2225 0 0 18 17 • 85 € 134 i 48 • 12 ,11/2 350 1000 1 0.0.07 a5T 0.20 , ' 3.38 528 1.88 2.0 ' 0'-57' 2-3/8x2 ' 40 , . 2410.... 4450 0 1.8 17 f = 85 134 48 1.0 21/2 2 500 2215 0 0.07 ' ° 016 4.00 5.93 , 1.88 3.1 65 x 50 3450 ,, .._,. 9850 0 1.8 , 0 47 14 i.. 2 3/8 x 2 102 ' 151 48 1.4 w-761. », _, ._ _,- ... ._. _.,_. ... €€ I mm x 2 350 1550 0 007 0 47 016 !I 2 ,/ax23/a g 438 663 1.88 4.6 50 ' 2410 6900 , 0 12 14 , t 111 168 48 • 21 3 2 350 1550 0-0.07 0° 39' 0.13 2-1/2x 23/, 4.75 7.13 1.88 ? 4.9 80 x' 50 2410 6900 I 0-18 11 121 181 = 48 I 22 21 500 3250 1 0 097 0 39 013 2 �x 214 4.75 713 188 4.3 65x 3450 14460 0 1.8 11 121 181 48 2,0 350 2475 0 0 07 0.13 6 4.75 7.13 1.88s 4.2 88.9mm x 76.1mm l € t 0°-39 2 'kx23/a t 2410 ' 11010 0 1.8 11 121 181 48 1 1.9 4x 2 350 1550 I 0 0.13 1°-19' 0.28 2-5/8 x 3'A 625 890 225 8.1 100 50 2410 6900 ;, 0 3.2 25 159 226 ' 57 3.7 2'h 350 2275 0-0.13 1.-19 0 28 •h 2_5/8 x 3'/a � 625 8.90 225 I 8.6 652410 10125 0 3.2 25 159 ' 226 57 3.9 80 3450 400 0 03 2 1.-19 �58 ; 2 5/ 8 x 3 Ya 152 226 575 3.0 114.3 mm x ` 76.1 mm - 350 2475 0-0.13 ' 1° 19 0 285 4 2 5/8 x 3%a i 6 25 8.90 i 225 69 2410 11014 I 0 3 2 25 159 226 57 3.1 350 5565 � 0.22 761'521985 .18 10.70 2.13 i 112 x 0 0.13 1'-3' 2-'/ax4'/a 125 100 2410 24765 =.. 0 3.2 19 - 182 - 272 54 I 5.1 64 350 5565 0 013 018 2 3/ax4%a 863 1190 225 167 x t 0°-52 150 100 2410 24765 r 0 3.2 15 181 302 57 76 5 1 350 8500 • 0 0.13 I0°-52, 018 2 3/a x 41/48.31 11.90 2.25 12.9 I 125 2410 37825 0 3.2 15 • 211 302 57 s 59 1165.1 mm x 4 { 350 5565 0 0.13 _ 019 8 63 I 1190 225 15,2 100 2410 24765 0 3,2 0 55 _. 16 I 2 3,4x4%a 219 302 57 • 69 re I 8 6 t 350 12060 0 0.13P 013 10.81Y 14.88 250 224 Itt ra200 x 150 l 2410 53645 0 3.2 0 -38' 11 2 7/8 x 5 275 378 64 1 102 350 11610 t 0-0.13 013 10.75 " 14.88 2.50 • 232 219.1 mm x 1651 mm j 2410 x g 0° 38' 11 ' 2 7/8 x 5 273 I 378 64 10.5 51645 0-3.2 It 10 x 8 350 20450 0-0.13 . V-25, 0.9 i 2-1 x 51/2 I 13.12 1226 2.62 31.4 273 2191 2410 90970 0-3.2 8 333 438 67 14.2 Style 750 Reducing couplings should not be used with end caps(#60)in systems where a vacuum may be developed.Contact Victaulic for details. *Working Pressure and End Load are total,from all internal and external loads,based on standard weight(ANSI)steel pipe,standard roll or cut grooved in accordance with Victaulic specifications.Contact Victaulic for performance on other pipe.Maximum working pressure rating based on larger pipe size. Maximum End Load rating based on smaller pipe size.WARNING:FOR ONE TIME FIELD TEST ONLY,the Maximum Joint Working Pressure may be increased to 11/2 times the figures shown. t Allowable Pipe End Separation and Deflection figures show the maximum nominal range of movement available at each joint for standard roll grooved pipe.Figures for standard cut grooved pipe may be doubled.These figures are maximums;for design and installation purposes these figures should be reduced by:50%for 3/4-3W/20-90 mm;25%for 4'1100 mm and larger. @ Number of bolts required equals number of housing segments. Metric thread size bolts are available(color coded gold)for all coupling sizes upon request.Contact Victaulic for details. WARNING:Depressurize and drain the piping system before attempting to install,remove,or adjust any Victaulic piping products. 1 r___,__I ,...,_, , ...,_z_. .,../0-4.4„,, ,,u Ipl, cáo 'IN.....-?. - la www.victaulic.com jCtelUli[: VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2012 VICTAULIC COMPANY.ALL RIGHTS RESERVED. 06.08_2 REV_J s CARBON STEEL PIPE-GROOVED COUPLINGS 06.08 Reducing Coupling STYLE 750 FLOW DATA HEAD LOSS The head loss across Style 750 Reducing coupling is very small and is essentially the same as for standard short body reducing pipe fittings. Equivalent lengths of standard weight steel pipe are shown in the tables.All data is based on water flowing at ambient temperature. FLOW REDUCING FLOW EXPANDING Equiv.Pipe Equiv.Pipe Size Length Size Length Nominal Nominal Size Sm.Dia. Size Sm.Dia. Inchesfmm Feet/m Inches/mm Feettm 2 1 5.9 1 2 2.7 50 x 25 18 25 x 50 i 0.8 11/2 2.0 11/2x 1.9 40 0.6 40 x 50 0.6 21/22 19 2 2,1 1D 65 x 50 06 50 x 65 03 761mm x 50 )6 76,1mm , �� 32 ! 55 3 I 35 80 x 50 1 17 80 1.1 2 3.8 4 30 65 I 12 100 j 0.9 88.9mm x 761m 3.8 21/2 x 3 2.5 1.2 65 i'80 0.8 100 x 50 18 100 0.9 65 b,g 76.1 mm x 88.9mm 0.8 3 6.0 114.3mm 3.0 1143mm x 76.1mm : 6.8 80 X 100 0.8 .,.max r w. ...m�. .......,. ...,........_...... ,..._,. _ .,_ __,,. ......�....._..__,..,. 54 3.0 4 5 3.3 125 x 100 0.9 100 x 125 1.0 64 6.0 6 4.6 150 x 100 18 150 1.4 125 1,4 165.1 mm 4.6', 1.4 46.0 5 6 23 1651 mm x 100 18 125 x 150 07 8 6 7.3 6 8 6.0 200 X 150 22 150 x 200 1.8 219.1mm x 1651mmi Z23 1651mm x 219.1 mm 165 10 8 i 8.7 810 6.3 I 273 X 2191 2.65 2191 x 273 i 192 www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2012 VICTAULIC COMPANY.ALL RIGHTS RESERVED. IICtauI,C REV_J 06.08_3 CARBON STEEL PIPE-GROOVED COUPLINGS 06.08 Reducing Coupling STYLE 750 INSTALLATION Reference should always be made to the 1-100 Victaulic Field Installation Handbook for the product you are installing.Handbooks are included with each shipment of Victaulic products for complete installation and assembly data,and are available in PDF format on our website at www.victaulic.com. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. For complete contact information,visit www.victaulic.com 06.08 1536 REV J UPDATED 08/2012 ictauliid VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2012 VICTAULIC COMPANY.ALL RIGHTS RESERVED. 06.08 Victaulic® Flexible Coupling Style 75 �ctaul�� 06.05 zi • Victaulic RX roll sets must be used when grooving light-wall/thin-wall stainless steel pipe for use with kr 1/ Victaulic Couplings. U I U I V Failure to use Victaulic RX roll sets when grooving light-wall/thin-wall stainless steel pipe may cause joint failure, resulting in serious personal injury and/or Exaggerated for clarity property damage. Approvals/Listings FM LPCB (yds) NOTICE • Victaulic RX grooving rolls must be ordered See Victaulic publication 10.01 for details separately.They are identified by a silver color and See Victaulic publication 02.06 for portable water approvals if applicable. the designation RX on the front of the roll sets. Product Description Style 75 is available where moderate pressures are expected or weight considerations are a factor. Up to 50% lighter in weight than the Style 77,the Style 75 coupling is recommended for service up to 500 psi/3450 kPa depending on size. Housings are cast in two identical pieces in all sizes. Hot-dip galvanized and special coatings are available for all sizes. The Victaulic standard flexible coupling offering for grade "EHP" or"T"gaskets is the Style 177 installation-ready flexible coupling. For all available sizes,the Style 177 is the standard flexible coupling Victaulic supplies in North America for piping systems using Grade "EHP" or "T" gaskets. Contact Victaulic for further details. Performance data presented in this document is based on use with standard wall, carbon steel pipe. For use with stainless steel pipe, please reference publication 17.09 for pressure ratings and end loads.When used on light wall stainless steel pipe, the Victaulic RX roll set must be used to roll groove the pipe. For further information regarding roll grooving stainless steel, refer to publication 17.01. Job/Owner Engineer System No. Spec Section Location Paragraph Contractor Approved Submitted By Date Date victaulic.com I Couplings I Flexible I Style 75 I Publication 06.05 06.05 1470 Rev 0 Updated 09/2014 ©2014 Victaulic Company.All rights reserved. 1 ✓ctauli victaulic.com I Couplings I Flexible I Style 75 I Publication 06.05 Material Specifications Housing: Bolts/Nuts: Ductile iron conforming to ASTM A-536,grade 65-45-12. Heat-treated plated carbon steel,trackhead meeting the Ductile iron conforming to ASTM A-395, grade 65-45-15, physical and chemical requirements of ASTM A-449 and is available upon special request. physical requirements of ASTM A-183 Housing Coating: (specify choice) ❑ Standard: Orange enamel. ❑ Optional: Hot dipped galvanized and others. Gasket: (specify choice') NOTE:Additional gasket styles are available.Contact Victaulic for details. ❑ Grade"E"EPDM EPDM (Green stripe color code). Temperature range—30°F to+230°F/-34°C to+110°C. May be specified for cold and hot water service within the specified temperature range plus a variety of dilute acids, oil-free air and many chemical services. UL Classified in accordance with ANSI/NSF 61 for cold +73°F/+23°C and hot+180°F/+82°C potable water service and ANSI/NSF 372. NOT COMPATIBLE FOR PETROLEUM SERVICES. ❑ Grade"T"Nitrile Nitrile(Orange stripe color code). Temperature range 20°F to+180°F/29°C to+82°C. May be specified for petroleum products, air with oil vapors,vegetable and mineral oils within the specified temperature range. Not compatible for hot water services over +150°F/+66°C or for hot dry air over+140°F/+60°C. 1 Services listed are General Service Guidelines only.It should be noted that there are services for which these gaskets are not compatible.Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service guidelines and for a listing of services which are not compatible. 06.05 1470 Rev 0 Updated 09/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 2 ✓Ctaulie victaulic.com I Couplings I Flexible I Style 75 I Publication 06.05 Dimensions Style 75 I-Y- ,I t r:r�� :, I. IV 4111 � Irl Actual Maximum Maximum Allow. Dimensions Approx. Nominal Outside Working End Pipe End Deflection from Weight Size Diameter Pressure 2 Load 2 Separations Centerline' Bolt/Nuta X Y Z Each Pipe inches inches psi lbs. inches Per Cplg. inches/ft. inches inches inches lbs. mm mm kPa N mm Degrees mm/m (No.)size inches mm mm mm kg 1 1.315 500 680 0-0.060 0.57 2.38 4.27 1.77 1.3 25 33.4 3450 3025 0-1.6 2-43 48 2-3/4x 2 61 108 45 0.6 11/a 1.660 500 1080 0-0.06 ° 0.45 2.68 4.61 1.77 1.4 32 42.2 3450 4805 0-1.6 2-10 38 2-%x 2 68 117 45 0.6 1% 1.900 500 1420 0-0.061.-56' 0.40 2-%x 2 2.91 4.82 1.77 1.5 40 483 3450 6320 0-1.6 33 74 122 45 0.6 2 2.375 500 2215 0-0.06 , 0.32 3.43 522 1.88 1.7 50 60.3 3450 9860 0-1.6 1 -31 26 2-%x 2 87 133 48 0.8 2% 2.875 500 3245 0-0.06 , 0.26 3.88 5.68 1.88 1.9 65 73.0 3450 14440 0-1.6 1 -15' 22 2-3/e x 2 98 144 48 0.9 76.1 mm 3.000 500 3535 0-0.06 1°_12, 0.26 2-�ex2 4.00 5.90 1.88 1.9 76.1 3450 15730 0-1.6 22 102 150 48 0.9 3 3.500 500 4800 0-0.060 0.22 , 4.50 7.00 1.88 2.9 80 88.9 3450 21360 0-1.6 1 -2 18 2-h x 2 1/4 114 178 48 1.3 3 1/2 4.000 500 6300 0-0.060.19 5.00 7.50 1.88 2.9 90 101.6 3450 28035 0-1.6 0°-54 16 2-1/2x 23/4 127 191 48 1.3 4 4.500 500 7950 0-0.13034 5.80 8.03 2.13 4.1 100 1143 3450 35380 0-32 1.-36' 28 2-1/4x21/4 147 204 54 1.9 4.250 450 6380 0-0.130.35 5.55 7.79 2.13 3.7 108.0 mm 108.0 3100 28395 0-32 1.-41' 29 2-12 x 70 141 198 54 1.7 41/4 5.000 450 8820 0-0.130.25 6.13 9.43 2.13 5.5 120 127.0 3100 39250 0-32 1°-26 21 2-%x 31/4 156 240 54 2.5 5 5.563 450 10935 0-0.131.-18' 0.27 2-5,4)(31/4 6.88 10.07 2.13 5.8 125 1413 3100 48660 0-32 23 175 256 54 2.6 133.0 mm 5.250 450 9735 0-0.13 10-21' 0.28 2-16 x825 6.55 9.37 2.13 6.0 133.0 3100 43325 0-32 24 166 238 54 2.7 5.500 450 10665 0-0.130.28 6.80 9.59 2.13 6.3 139.7 mm 139.7 3100 47460 0-3.2 10-18' 24 2-5/e x 3 1/4 173 244 54 2.9 152.4 mm 6.000 450 12735 0-0.13 1.-12' 0.21 2-s/s x 3,/a 7.38 10.48 1.88 62 152.4 3100 56670 0-32 18 187 266 48 2.8 6 6.625 450 15525 0-0.1310-5' 0 23 2-Sex 3 1/48.00 11.07 2.13 7.0 150 168.3 3100 69085 0-3.2 18 203 281 54 32 6.250 450 13800 0-0.13 1°_9, 0.24 2-16 x 82.5 7.63 10.49 2.13 6.8 159.0 mm 159.0 3100 61405 0-3.2 20 194 266 54 3.1 8 8.625 450 26280 0-0.130°-50' 0.18 2-3/4x41/4 10.34 13.97 2.13 12.4 200 219.1 3100 116945 0-32 14 263 355 59 5.6 2 Working Pressure and End Load are total,from all internal and external loads,based on standard weight(ANSI)steel pipe,standard roll or cut grooved in accordance with Victaulic specifications.Contact Victaulic for performance on other pipe. 3 Allowable Pipe End Separation and Deflection figures show the maximum nominal range of movement available at each joint for standard roll grooved pipe. Figures for standard cut grooved pipe may be doubled.These figures are maximums;for design and installation purposes these figures should be reduced by: 50%for 3-3 1/2'720-90 mm;25%for 4'7100 mm and larger. 4 Number of bolts required equals number of housing segments. General Notes Metric thread size bolts are available(color coded gold)for all coupling sizes upon request.Contact Victaulic for details. WARNING:FOR ONE TIME FIELD TEST ONLY,the Maximum Joint Working Pressure may be increased to 11/2 times the figures shown. 06.05 1470 Rev 0 Updated 09/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 3ictaulic° victaulic.com I Couplings I Flexible I Style 75 I Publication 06.05 • Installation Note Reference should always be made to the I-100 Victaulic Field Installation Handbook for This product shall be manufactured by Victaulic or to Victaulic specifications.All products the product you are installing.Handbooks are included with each shipment of Victaulic to be installed in accordance with current Victaulic installation/assembly instructions. products for complete installation and assembly data,and are available in PDF format Victaulic reserves the right to change product specifications,designs and standard on our website at www.victaulic.com. equipment without notice and without incurring obligations. Warranty Trademarks Refer to the Warranty section of the current Price List or contact Victaulic for details. Victaulica is a registered trademark of Victaulic Company. 06.05 1470 Rev 0 Updated 09/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 4 ictauliic M11 A ll3 ® SIDEWINDER° FOR WOOD -Horizontal Application Application Product Features Not less than 2"nominal width •No pre-drilling required. (1-1/2")up to 3-1/2"pipe;not less than 3"(2-112")nominal width 4"&5"pipe •Quick to install using the Sammy 4— Floor Joist Nut Driver with an 18V cordless drill/driver. Minimum 2-1/2"from bottom for branch lines.Minimum 3"from bot- tom for main lines.Exception:ThisSaves time from traditional methods. requirement shall not apply to 2"or thicker nailing strips resting on top of steel beams. ,. x •Reduces installation costs. - •Made in the U.S.A. i J; ! Composite/Truss i C.oesj [u5 e J.?.c urer for cr.:m ntled r(112b;n point r oli,g tray- required tar Model S L5 a'c T .+varacle on pago 11. i Watch a video demonstration at www.itwbulldex.com Approvals Rod Part Model Screw Ultimate UL Test Box Case Size Number Descriptions Pullout(lbs) Load(lbs) Qty Qty HORIZONTAL MOUNT 1/4" 8019957 SWG 200 1/4 x 2" 1725(Fir) 25 125 81.' 'x cs 'ii, / 422 fRr) i.E 1:-....‘t, i.,'` .4 12. ° ; 3/8" 8021957 SWG 20 1/4 x 2 1725(Fir) 1050 25 125 — .. .11 n`°" t -( e,2 SS% „:'.',''!,1,4%;,2' ��5=�. rh, 'r: .h � ..w 25 �x ` 3/8"" 8022925 SWG 25-380 3/8x2-1/2" 2249(Fir) 1500 25 125 #14 SW Red _ rte i4.,,, x = i 11tS2392s ' .? .- "'W:;:' � s~::',:4H '...1,. W Nut Driver 1� Part#8114910 *May require pre-drilling;consult joist manufacturer, W Et SAMMYS SWIVEL HEADTM FOR WOOD -Swivel Application v a Application0 Product Features V } NAM=20 r •Eliminates distortion of threaded rod. N. ••Accommodates up to 3 Y2'x 12 pitch roof. •Allows 17°deflection from vertical. y i ROD •Saves time from traditional methods. W ► •Reduces installation costs. IX '"'®—' I j •Made in the U.S.A. 0 MANGER A wAxmxuEW h ¢iib ,,ww Rod Part Screw Ultimate UL Test Load FM Test Min Box Case la Approvals Size Number Model Descriptions Pullout(lbs) (lbs) Load(lbs) Thickness Qty Qty SWIVEL MOUNT ( #14 BlackV _ ` Nut Drier 3/8" 8139957 SH GST 20 1/4 x 2" 1257(Fir) 1050 1475 25 125 . Part#8113v910 .: K +411J57= :'R,..r S0 ; 114• ".. ,172{1 ,. . :.r r$ t ". „,-'-'--°:--4.;°,,,,e. . t1 , r 1903 Dim.Lumber 1500 Q.,p 3/8"" 8269957 SH-GST/CST 20 5/16 x 1-3/4” 1406 @ 45°off vertical 850 @ 45° 25 125 II Dim Lumber /w r * ...;':',1V" �+ — �„x .0: a. Di I.canber; 1 " c J �" �0-1-3957 T/CST2. 5i 1-3/4”-:.?,t, t @ 45 off vei11'1 ' 25 "125 Q 'May require pre-drilling;consultjoist manufactures 0 #14 SH Orange Nut Driver Ct O.Part#8273910 a % 5 To find a distributor near you,call 800-BUILDEX r Y $ �u W ar , F"35"82' F.. F ..SA , an ., e R ; sx SAMMYS° FOR WOOD - Vertical Application Application Product Features Not less than Wood Flooring 2'nominal width •No pre-drilling required. (—� •Quick to install using the Sammy Not less than Nut Driver with an 18V cordless 3"nominal drill/driver. thickness(2-1/2") (depth or side Wood Joist •Saves time from traditional of vertical member) _ -, `� methods. x a. Double Sheetrock F-vertic a.use- Ceiling •Reduces installation costs. i i�st 9 it centero�o ier ince- 1. rinmum 2"emb cm nt into base •Made in the U.S.A. r.ateri'I for NFPA 13 compliance. ' Composite/Truss f, Cs o ilr,�,mart lot W'erfor 4 - rc Cvrr-n.I..c. ir14.a d:�Ur.p,lrl(. ( 'f'r, . rFmeyfen-IrmdforCSr + r 25-f on,r. ahle •,.page 77. 1"b, Watch a video demonstration at www.ifwbuildexcom Approvals Rod Part Model Screw Ultimate UL Test FM Test Box Case Size Number Descriptions Pullout(lbs) Load(lbs) Load(lbs) Qty Qty _ VERTICAL MOUNT 1/4" 8002957 GST 100 1/4 x 1" 210 (7/16"OSB) 25 125 670 (3/4"Ply) 1 M' ;„;, i 1/4 x2”' 1760 II r�„ 26 =a,1 { 1. 114" 8004957 GST 300 1/4 x 3" 2060(Fir) 25 125 Qa7 ivti* a o'54 #, S1/ ,t; 1/4X.1* 67© 6 '$e t3) DO 125 —ii ''t 3/8" 8008957 GST 20 1/4 x 2" 1760(Fir) 850 1475 25 125 ack ;>a+� .``'.�e �r . . r,'I/4X2 , 1 tRts ��'4:„ .x x 25 318" 8009925 GST 2‘5t3.,8,(.) 5-380 318x2-1/2" 2113 (Fir) 1500 25 125 #14 Black �s�. . ,r $ . r i3ST30 .` I .,< . #"r`r ttl. . .. r�500 .. 1- ,, 12$; Nut Driver 3/8" 8069925 GST 30-SS 1/4 x 3" 2060 (Fir) 25 125 Part#8113910 . i4 �' 14ix4" -' . 0 ( . T? '',./14i,,, .712i ,,, , , # 1/2" 8013925 GST2 1/4x2" 1760 (Fir) 25 125 ( )C . ' : °ir'"'� d"�. .�. < "r.w<. 21'1`3. t2rr ' �,„ . -.2 .4 5 tax 1/2" 8015925 GST 3 1/4 x 3" 2275 (Fir) 25 125 #14 SW Red Nut Driver Part#8114910 U MV\ITF/ SPECIAL NUT DRIVER SYSTEM:The nut drivers were designed with a unique spin-off feature which provides a fast and safe installation each time.When the face of the driver comes into contact with the material you are installing into,continue drilling until nut driver spins free.Installation is then complete.Warranty requires the use of the appropriate nut driver for installations. For the most up to date information,visit www.itwbuildex.com 4 .ZS:grg§0 P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www.Afcon.org 514 CPVC — COPPER ns05 #906 STEEL ° 1 OFFSET HANGER r 3W M , 1 - - Y Ill SIZE-SYSTEM PIPE: 3/4"thru 2" )11 MATERIAL-Carbon Steel. FINISH-Mil.Galvanized. LISTING/APPROVAL- Hanger/Restrainer eus�Ea�203-EX 4231,EX 2551 PATENT-No.6,648,278. MIIII■' FUNCTION- Support horizontal piping: CPVC,Copper or Steel. I.l Provides listed vertical/horizontal restraint and prevents upward movement of pipe from pendent sprinkler discharge. Stabilize vertical piping. Hanger/ i)- INSTALLATION- Per these instructions Restrainer 1)- Stabilize including NFPA 13, 13R, 13D and CPVC manufacturers instructions. ■ Install on horizontal or vertical mounting surface. Snap over pipe then squeeze strap back allowing pipe to slide freely. When #905 threads are exposed in wood,install#906 backing nut. �� FASTENERS-UL Listed per NFPA 13 III) WOOD- CPVC pipe-#905 screw-no pre-drill. Copper and Steel pipe-#14 SMS or 1/4"xl 1/2"lag screw- no pre-drill. Thru 5/8"gypsum board- 1/4"x 2"lag screw. STEEL-min. 18 GA.-CPVC,Copper and Steel pipe- 1/4"or#14 Tek Screw. . CONCRETE:Required minimum load each fastener= 5(wt)+2501bs. o 2 4 4 FEATURES 'c - * * 1 1/2"Offset-loose fit allows pipe to slide. • o • a • *Common center-line for 3/4"and 1". . *Offset edge eliminates abrasion. Ilif *AFCON#905 screw included-5/16"hex head. git ORDERING-Part#and pipe size. AFCON#906 backing nut sold separately. VP Specific AFCON products are exclusively designed to be compatible ONLY with other AFCON products including parts and fasteners,resulting in a listed sway brace,restrainer or hanger assembly. Be advised the following warranty restriction will apply.DISCLAIMER-AFCON will NOT warrant against the failure of its products when used in combination with other products,parts or systems not manufactured or sold by AFCON.AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect,incidental or consequential damages of any kind,including but not limited to loss of business or profit,when non-AFCON products have been,or are used. 11/13 . 7:g'1§00 P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www.Afcon.org 515 CPVC DOUBLE OFFSET HANGER Hanger/Restrainer \ allER /o e 0 SIZE-SYSTEM PIPE:3/4"and 1" MATERIAL-Carbon Steel. FINISH-Mil.Galvanized. LISTING/APPROVAL- chaos 203-EX 4231 PATENT-No.6,702,236 FUNCTION-Support horizontal CPVC pipe. Provides listed vertical/horizontal restraint and prevents Hanger/Restrainer upward movement of pipe from pendent sprinkler discharge. INSTALLATION- Per these instructions / including NPFA 13, 13R, 13D and CPVC manufacturers instructions. A Install on horizontal or vertical mounting surface. FASTENERS-UL Listed per NFPA 13. #904 screw in wood-no pre-drill. FEATURES *Double 1 1/2"offset *Common center-line for 3/4"and 1". *Offset edge eliminates abrasion. *Required AFCON#904 screw included-3/8"hex head. ORDERING-Part#and pipe size. Specific AFCONproducts are exclusively designed to be compatible ONLY with other AFCONproducts including parts and fasteners,resulting in a listed sway brace,restrainer or hanger assembly. Be advised the following warranty restriction will apply.DISCLAIMER-AFCON will NOT warrant against the failure of its products when used in combination with other products,parts or systems not manufactured or sold by AFCON.AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect,incidental or consequential damages of any kind,including but not Eluded to loss of business or profit,when non-AFCONproducts have been,or are used. IOW 11/13 • log) P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www.Afcon.org 510 CPVC - COPPER - STEEL HANGER o 510 Fastener SIZE Dim. 3/4 2.12.12 5 J O 1 2.312 1 1/4 3.170_ 1 1/2 3.400 2 4010 2 1/2 4.320 3 5.320 SIZE-SYSTEM PIPE:3/4"thru 3" MATERIAL-Carbon Steel. FINISH-Mil.Galvanized. LISTING/APPROVAL- r� 4L '"203-EX 4231,EX 2551 daiEs FUNCTION-Support horizontal piping: CPVC,Copper or Steel. Size 3/4"-2"Prevents upward movement of pipe from pendent sprinkler discharge. Stabilize vertical piping. INSTALLATION- Per these instructions t t� including NFPA 13, 13R, 13D and CPVC manufacturers instructions. Install on horizontal or vertical mounting surface. FASTENERS- UL Listed per NFPA 13 in WOOD: 3/4"-3"CPVC pipe-#905 screw-no pre-drill. 3/4"-3"Steel and Copper pipe-#14 x 1 1/2"SMS or 1/4"x11/2"lag bolt-no pre-drill. Restraint in STEEL-min. 18 GA. 3/4"-3"CPVC,Copper and Steel pipe- 1/4"or#14 Tek Screw. U FEATURES ' *Offset edge eliminates abrasion. *Retainer dimples secure hanger to pipe during installation. *Required AFCON#905 screw included-5/16"hex head. Hanger r Stabilize ORDERING-Part#and pipe size. / 1 1 CAN ALSO BE USED TO REPLACE-#500 Pipe Strap #520 Tin Strap Specific AFCON products are exclusively designed to be compatible ONLY with other AFCON products including parts and fasteners,resulting in a listed sway brace,restrainer or hanger assembly. Be advised the following warranty restriction will apply.DISCLAIMER-AFCON will NOT warrant against the failure of its products when used in combination with other products,parts or systems not manufactured or sold by AFCON.AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect,incidental or consequential damages of any kind,including but not limited to loss of business or profit,when non-AFCON products have been,or are used. 5/14 # _ 7ffig P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www.Afcon.org 300 RING HANGER 1 thru 4 Inch pipe 1/2&3/4 Inch pipe LISTED FOR STEEL/CPVC 5 thru 8 inch pipe NFPA 13 UL 1 WT. 5 WT.+250 TEST PIPE ROD LOAD 1 3/8 30.75 403.75 750 11/4 3/8 43.95 469.75 750 11/2 3/8 54.15 520.75 750 SIZE-ROD-3/8"or 1/2" 2 3/8 76.95 634.75 750 SIZE-SYSTEM PIPE- 1/2"thru 8" 21/2 318 118.35 841.75 850 MATERIAL-Carbon Steel,Mil.Galvanized to G-90 spec. 3 3/8 162.30 1061.50 . 1050 LISTING/APPROVAL- 4 3/8 246.00 1480.00 1500 COUS 5 1/2 349.45 1996.75 2000 IISTED 203-EX 2551 1"-8" 6 1/2 476.35 2631.75 2650 FM Approval guide-1"-8" 8 1/2 711.00 3805.00 4050 OSHPD OPA-0601 See Website. CONFORMS WITH:Federal Specification WW-H-171E,Type 10. Manufacturers Standardization Society ANSI/MSS-SP-58 Type 10. MAXIMUM TEMPERATURE-650°F. FUNCTION-Pipe hanger component of an AFCON hanger. To support steel,CPVC or copper pipe. INSTALLATION-Per NFPA 13, 13R, 13D,these instructions and PIPE A B T the CPVC or copper pipe manufacturers instructions. 1 1.8793 2s2s9 FEATURES- 11/4 2.1382 2.7850 * ' Sized and listed exclusively for use with#310 Surge Restrainer. 1 1/2 2.2673 2.9140 1 B 2 2.6048 3.2516 * Band edge is offset for EASY pipe insertion. A 21/2 3.4920 4.1150 * Custom fit swivel nut for better retention in ring. 3 3.7845 4.4311 ORDERING-Part#,pipe size. 4.3562 '.9992 6 6.0668 6.8180 8 7.5768 8.3290 11/09 P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www.Afcon.org 077 ATTACHMENT FITTING LOCKING 17/32" 17/32" (D4 ves 077D DUCTILE BASE PLATE 077S STEEL BASE PLATE SIZE-BRACE PIPE: 1"and 1 1/4"Sch.40 MATERIAL-Carbon Steel,Ductile Iron or S.S.(Type 304). FINISH-Plain or E.G. LISTING/APPROVAL- Os LISTED 4 s 203A-EX2625 0 FM Approved-1950 OSHPD See Website. FUNCTION-Structure attachment fitting of an AFCON sway brace assembly. cq�aas Max. Horizontal Load Sway brace assemblies are intended to be installed in accordance with NFPA 13 and the manufacturer's installation instructions. Size 1-1 1/4 2015 INSTALLATION-Per these instructions including NFPA 13 or FM 2-8. Load rating-see chart. ASSEMBLY Combine with proper AFCON components-see disclaimer below. Insert brace pipe thru fitting near pivot bolt. FM Max.Horizontal Load Tighten set bolt until head contacts bracket. 0 FEATURES *Swivel allows attachment at any angle. 30-44° 45-59°60-74°75-90° *Visual inspection,verifies proper installation. Size 1-1 1/4 630 870 1620 1810 *Larger fastener hole available.-Consult factory. ORDERING-Part#,size-brace pipe and finish. Specific AFCONproducts are exclusively designed to be compatible ONLY with other AFCON products including parts and fasteners,resulting in a listed sway brace,restrainer or hanger assembly. Be advised the following warranty restriction will apply.DISCLAIMER-AFCON Will NOT warrant against the failure of its products when used in combination with other products,parts or systems not manufactured or sold by AFCON.AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect,incidental or consequential damages of any kind,including but not limited to loss of business or profit,when non-AFCON products have been,or are used. 9/14 tajIll . 77.,g'Ig 100 P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www.Afcon.org 411 SWAY BRACE FITTING Part#077-, " .\' 41 Part#078 SIPt/ it at •-7* G G RI SIZE-SYSTEM PIPE:Nominal Pipe Size IL r Sch.40 Steel 1"- 12" `iti -' Sch. 10 Steel 1 1/4"- 12" Sch.7 Steel 2"-6" MATERIAL-Carbon Steel or S.S.(Type 304) FINISH-Plain or E.G. PATENT-No.7,140,579 ®Listed Max.Horizontal Load LISTING/APPROVAL 1"-10" 2765 'Gs as 203A-EX 2625 © FM Approved-1950 12" 3740 USTS APPROVED FUNCTION-Longitudinal fitting of an AFCON sway brace assembly. Sway brace assemblies are intended to be installed in accordance with NFPA 13 and the manufacturer's installation instructions. ©certified Max.ASD Horizontal Load INSTALLATION- Per these instructions System Sch. 30°-44° 45°-59° 60°-74° 75°-90° NPS including NFPA 13 or FM 2-8 1"-1 1/2" 10-40 420 510 570 Load rating-see chart. 2"-3" 7-ao 860 1030 1150 4" 7-40 860 1030 1150 ASSEMBLY-See drawing. 5" 7-40 950 1150 1280 Combine with proper AFCON components-see disclaimer below. s" 7-40 2220 2220 3040 Align brace member parallel to face of 411 fastener flanges. s" 10-40 1340 1620 1810 Tighten 1/2"bolts until fastener flanges connect. FEATURES * Patented-design eliminates bending of fastener flanges during installation. * Patented-design prevents over tightening on system pipe. * Improved assembly-fastener flanges connect for superior strength. * Visual inspection-proper installation when 411 fastener flanges connect. ORDERING-Part#,size-system pipe and finish. Specific AFCON products are exclusively designed to be compatible ONLY with other AFCON products including parts and fasteners,resulting in a listed sway brace,restrainer or hanger assembly. Be advised the following warranty restriction will apply.DISCLAIMER-AFCON will NOT warrant against the failure of its products when used in combination with other products,parts or systems not manufactured or sold by AFCON.AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect,incidental or consequential damages of any kind,including but not limited to loss of business or profit,when non-AFCONproducts have been,or are used. 11, 5/14 ., 4f 5'#` . 7, j1§01,aD P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www.Afcon.org 078 ATTACHMENT FITTING LOCKING 9/16 Dia. Part#077 N43 O #078 41 Part 410/411— SIZE-BRACE PIPE: 1"and 1 1/4"Sch.40 MATERIAL-Carbon Steel or S.S.(Type 304). FINISH-Plain or E.G. !-1 LISTING/APPROVAL- 'On 203A-EX 2625 FM FM Approved-1950 OSHPD See Website. FUNCTION-Structure attachment fitting of an AFCON sway brace assembly. Common transition component with 411 sway brace fitting-see drawing Sway brace assemblies are intended to be installed in accordance with NFPA 13 and the manufacturer's installation instructions. INSTALLATION- Per these instructions including NFPA 13 or FM 2-8. 41 Max. Horizontal Load Load rating-see chart. 30°-44° 45°-59° 60°-89° 90° DO NOT BEND-If angle required use part 070,075,076 or 077. 1008 1425 1745 2015 ASSEMBLY Combine with proper AFCON components-see disclaimer below. Insert brace pipe thru fitting near pivot bolt. Tighten set bolt until head contacts bracket. € Max. Horizontal Load FEATURES 30°-44° 450-59° 60°-74° 75°-90° *Visual inspection,verifies proper installation. 430 620 760 940 *Bolt hole fits 410/411 sway brace fitting. ORDERING-Part#,size-brace pipe and finish. Specific AFCON products are exclusively designed to be compatible ONLY with other AFCON products including parts and fasteners,resulting in a listed sway brace,restrainer or hanger assembly. Be advised the following warranty restriction will apply.DISCLAIMER-AFCON will NOT warrant against the failure of its products when used in combination with other products,parts or systems not manufactured or sold by AFCON.AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect,incidental or consequential damages of any kind,including but not limited to loss of business or profit,when non-AFCONproducts have been,or are used. 4/14 P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www.Afcon.org 400 RISER CLAMP IRON PIPE A PIPE STOCK MAX.REC. C C ....4 SIZE A B C SIZE LOAD LBS. 1 1/2" 10 3/8" 3/8" 1 1/2" 3/16"x1 1/4" 255 2" 10 3/4" 3/8" 2" 3/16"x1 1/4" 255 o ®_ 2 1/2" 11" 3/8" 2 1/8" 1/4"x1 1/4" 390 411 1r1 3" 12" 3/8" 3 1/4"x11/4" 530 3 1/2" 13" 1/2" 3 5/16" 1/4"x1 1/4" 670 B B 4" 13 1/2" 1/2" 3 3/8" 1/4"x1 1/4" 810 5" 14 1/2" 1/2" 4" 1/4"x1 1/2" 1160 6" 15 1/8" 1/2" 4 1/2" 1/4"x2" 1570 8" 18 1/2" 5/8" 5 13/16" 318x2" 2500 NOTE:MAXIMUM TEMPERATURE:650°F SIZE- 1/2 thru 20 inch pipe. *oli MATERIAL-Carbon Steel. FINISH-Plai> G.,H.D.G.and S.S. LISTING/APPROVAL- EX 2551 11/2"-8"pipe. OSHPD OPA-0601 See Website. CONFORMS WITH: Federal Specification W W-H-171 E ,type 8,3/4 thru 20 inch,and Manufacturers Standardization Society SP-69,type 8. FUNCTION-Used for supporting vertical piping. ORDERING-Part#,pipe size and finish. r ,: 1/08 IPS CARBON STEEL PIPE-FIRE PROTECTION)PRODUCTS 10.96. FireLock® Zone Control Riser Module ® €) <> SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS SERIES 747Mi lk Designed for NFPA 13 commercial requirements,the Victaulic Series 747M Zone Control Riser Module features a cast body,and is compact and easy to install in zoned wet sprinkler systems. ( ` The integrated module body consists of a shut off valve,test and drain valve combination and different orifice sizes(K factors),a UL Listed and FM Approved Flow Switch,and a Pressure Gauge.The Series 747M FireLock Zone Control Riser Module is available in sizes from 1 LY4 through 6732mm-150mm with grooved ends on the main pipe for installation in the horizontal or vertical up-flow positions with UL Listed,FM Approved Victaulic grooved couplings.1Y4-2"modules have an NPT drain port.2 Y2-6"modules have a grooved drain port. „ The Series 747M FireLock Zone Control Riser Module is FM Approved and UL and ULC Listed for working pressures up to 365psi/2517kPa.An optional pressure relief valve kit is available STYLE 747M for all sizes.The Pressure Relief Valve is FM Approved and UL and ULC Listed for working PATENT PENDING pressures up to 175psi/12OOkPa. DIMENSIONS Aprx Weight 1Module Body Size Dimensions Inches/mm Each "inr I s' ° .' .`r t' a ' .x . �` ual r r i Inc A . v ooveel Lbl ikteh I x.h .0Im.2.ta, !R } 1,A, 1660 1 I 11.45 7.20 5.77 3.50 10.05 7.48 2.54 r 15.2 D Le 32. 42.2 i 33.4 1 290.8 182.9 146.5 88.9, , 255.3 190.0 645 « 6.9 F r •�;� ''� C F 1'1/2 1.900 1 11.45 , 7.32 I 577 3.50 10.05 7.48 2.54 15.5 +I 40 48.3 33.4 290 8 , 185.9 . 146 5 88.9 255.3 190.0 64.5 7.0 2 2.375 I 1 ; 11.45 7.55 . 5.77; 3.50 ' 10.05 7.48 I 2.54 g 19.9 50 60 3 33.4 290.8 191.8 146.5 i 88.9 255.3 190.0 64.5 9.0 2 r 2.875 1 Ya 12.00 « 8.41 I 6.18 ' 4.25 9.76 11.87 s 4.25 22.7 L, . E G 65 I 73.0 42 305 s 214 157 108 248 302 108 10.3 A 3 , 3.500 1 1/, i 12.00 9.42 6.18 I 4.25 9.76 11.87 I 4 25 i 23.2 80 88.9 42 1 305 C 239 157 108 248 302 108 I 10.6 11/4-2"/32-50 mm Nominal Sizes 4 : 4.500 2 12.00 , 9.90 7.25 5.00 ; 10.15 12.62 4.21 30.3 100 « 114.3 60 305 S 252 184 127 258 321 107 13 8 .a,,. and 6 6.625 2 , 12.00 10 85 : 8.31 I 6.00 10.15 13 62 « 4.24 I 36.7 B 150 168.3 60 305 „ 276 ' 211 « 154 . 258 346 1077 16.7 c,I Irr Orifices 1 tr;::..• tir, , l...' Nominal Size D qis- inches ' F G - 1.25 K5.6 t I ,a 1-111444-A- '. 1.5 K5.6 F -, .�� f 2 K5.6 I Il 2.5 K5.6 K6.9 KB.O K11.2 3 K5.6 K6.9 K8.0 K11.2 E 4 K5.6 K6.9 K8.0 K11.2 K14.0 K16.8 6 K5.6 K6.9 K8.0 K11.2 K14.0 K16.8 A 21-6165.0-150 mm Nominal Sizes (Valves shown above in the"test"position. Nominal Size Drain Type Drain Size Shown with optional Pressure Relief Valve Kit inches installed) 1.25 NPT 1 Hose Clamp 1.5 NPT 1 2 NPT 1 25 Grooved 1 r/4 Pressure Relief Valve 711(,...,,,, - � 3 Grooved 1 Ya Barbed Fitting 4 Grooved 2. Hose Clamp II 6 Grooved 2" Close Nipple I)-4-Drain Tubing lieElbow Barbed Fitting Optional Pressure Relief Valve Kit Detail JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date Approved Date www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2010 VICTAULIC COMPANY.ALL RIGHTS RESERVED. ICtaUll� REV_I 10.96_1 FIRE PROTECTION PRODUCTS—DEVICES 10.96 FireLock® Zone Control Riser Module SERIES 747M MATERIAL SPECIFICATIONS Module Body:Cast from ductile iron conforming to ASTM A-536,grade 65-45-12 with integral Victaulic grooved ends.Finish:orange enamel. Shut-off and Test/Drain Valve:Chrome plated brass ball,S 37700 brass clapper,416SS or 410SS shafts,Delrin orifice,virgin Teflon*,enhanced Teflon and EPDM rubber seals. *Teflon is a registered trademark of Dupont Coupling:Any UL Listed,FM Approved Victaulic IPS-sized coupling may also be used.Note: Couplings not included with product. Waterflow Detector:System Sensor Model WFD/WFDTH vane type waterflow detector with sealed retard,visual switch activation,and mechanical delay adjustment.Cover includes tamper resistant security screws and tool.Note:ULC models WFDA/WFDTHA include cover tamper switch. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. WARNING A • This product must be installed by an experienced,trained installer, in accordance with the instructions provided with each valve.These instructions contain important information. c.17Failure to follow these instructions may result in serious personal injury, property damage,or valve leakage. If you need additional copies of this product literature or the valve installation instructions,or if you have any questions about the safe installation and use of this device,contact Victaulic Company,P.O. Box 31,Easton,PA 18044-0031 USA,Telephone:001-610-559-3300. For complete contact information,visit www.victaulic.com 10.96 3089 REV I UPDATED 7/2010 iCtcaUliC VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2010 VICTAULIC COMPANY.ALL RIGHTS RESERVED. 10.96 FireLock® Check Valves \Otaulicr Series 717 & 717H 10.08 Grooved ends allow fast, easy installation with just two Victaulic couplings or the valve may be mounted .: to flanged (ANSI CL.150)equipment using either to IIPI Victaulic Style 741 Vic-Flange®or Style 744 FireLock flange adapters on either end. Series 717 Series 717 (21 —3'/65—80 mm) (4—127100—300 mm) Series 717H High Pressure Check Valve (2—3750—80 mm) Approvals/Listings: cO us <> vds LPCB LISTED See Victaulic Publication 10.01 for more details. The FireLock Series 717 Check Valve and Series 717H High Pressure Check Valves are CAD designed for hydrodynamic efficiency and available in 2 750 mm—3780 mm (Series 717H)and 2 1/2765 mm— 127300 mm (Series 717)sizes. Series 717H valves are cULus Listed and FM Approved for service up to 365 psi/2517 kPa. See chart below for approved services for the Series 717 valves. In both valve designs,the single-disc mechanism incorporates a spring-assisted feature for nonslamming operation.This spring-assisted,single-disc design achieves a leak-free seal with as little as 5ft/1.5m of head.Series 717 and 717H FireLock Check Valves can be installed either vertically(flow upwards only)or horizontally.A cast flow arrow indicator is provided to assist with proper valve orientation. Both valves include upstream and downstream pressure taps. Each valve is factory-tested to the rated working pressure. For systems requiring a Riser Check option, refer to publication 10.09. Job/Owner Engineer System No. Spec Section Location Paragraph Contractor Approved Submitted By Date Date Check Valve I Firelock®I Series 717&717H I Publication 10.08 victaulic.com 1 xictaulie Check Valve I Firelock'I Series 717&717H I Publication 10.08 Material Specifications: Spring:All sizes Type 302/403 Stainless Steel Housing: Shaft Plug: Ductile iron conforming to ASTM A-536, grade • Series 717H (2—3750—80 mm): Type 416 Stainless 65-45-12. Ductile iron conforming to ASTM A-395, Steel grade 65-45-15, is available upon special request. • Series 717 (2 '/z— 12765—300 mm): Carbon steel Body Coating: zinc plated Series 717H Body: Black Paint Pipe Plug: Series 717H Endface: Electroless Nickel • Series 717H (2—3750—80 mm):carbon steel zinc Series 717 (2 1—3"): PPS Coating plated Series 717(4— 12"): Black Paint • Series 717 (4— 127100—300 mm): Carbon steel zinc Body Seat: plated Series 717H—Nitrile 0-ring installed into an electroless nickel plated endface Series 717(2 1—3"): PPS Coated ductile iron Series 717 (4— 12"): Electroless Nickel plated Disc Seal or Coating: (specify choice') 111 Grade "T" nitrile (Series 717H Only) Nitrile(Orange color code).Temperature range—20°F to +180°F/-29°C to+82°C.Recommended for petroleum products,air with oil vapors,vegetable and mineral oils within the specified temperature range;except hot,dry air over+140°F/+60°C and water over+150°F/+66°C. NOT RECOMMENDED FOR HOT WATER SERVICES. ❑ Grade "E" EPDM (Series 717 Only) EPDM(green color code).Temperature range-30°F to +230°F/-34°C to+110°C.Recommended for cold and hot water service within the specified temperature range plus a variety of dilute acids,oil-free air and many chemical services. NOT RECOMMENDED FOR PETROLUEM SERVICES. ' Services listed are General Service Recommendations only.It should be noted that there are services for which these gaskets are not recommended.Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service recommendations and for a listing of services which are not recommended. Discs: • Series 717H (2—3750—80 mm): CF8M Cast Stainless Steel • Series 717(2 V2—3°):Aluminum bronze with elastomer seal • Series 717 (4—127100—300 mm): Elastomer encapsulated disc with electroless nickel plated seat Shaft: • Series 717H (2—3750-80 mm): Brass • Series 717(2 ' —3"): Type 416 Stainless Steel • Series 717(4—127100—300 mm)Type 316 Stainless Steel victaulic.com 2 ✓ctaulicc Check Valve I Firelock I Series 717&717H I Publication 10.08 Approval/Listing: Approval/Listing Service Pressures Series 717H Size cULus FM LPCB Vds 2750 mm up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa 21/2765 mm up to 365 psi/2517 kPa up to 365 ps1/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa 76.1 mm up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa 3780 mm up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa 4'/100 mm n/a n/a n/a n/a 57125 mm n/a n/a n/a n/a 139.7 mm n/a n/a n/a n/a 6/150 mm n/a n/a n/a n/a 165.1 mm n/a n/a n/a n/a 8"/200 mm n/a n/a n/a n/a 10"/250 mm n/a n/a n/a n/a 127300 mm n/a n/a n/a n/a Approval/Listing Service Pressures Series 717 Size cULus FM LPCB Vds 2"/50 mm n/a n/a n/a n/a 21765 mm up to 250 psi/1725 kPa n/a up to 365 psi/2517 kPa n/a 76.1 mm up to 250 psi/1725 kPa n/a up to 365 psi/2517 kPa up to 16bar/232 psi 3"/80 mm up to 250 psi/1725 kPa n/a up to 365 psi/2517 kPa up to 16bar/232 psi 4"/100 mm up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 16bar/232 psi 57125 mm up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa n/a 139.7 mm up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 16bar/232 psi 6"/150 mm up to 365 ps1/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 16bar/232 psi 165.1 mm up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa n/a 8"/200 mm up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 348 psi/2400 kPa up to 16bar/232 psi 107250 mm up to 250 psi/1725 kPa up to 250 psi/1725 kPa up to 1725 kPa/250 psi n/a 12"/300 mm up to 250 psi/1725 kPa up to 250 psi/1725 kPa up to 1725 kPa/250 psi n/a victaulic.com 3 ✓ataulic Check Valve I Firelock®I Series 717&717H I Publication 10.08 Dimensions-Series 717: A pool la vie `.��J .0 1ilIDEL...g.) L `_,_ _DEE. 14-A--.1 B 71 F4-B 19I K t)• i p B -N J N- B -�!J,4- go 071 0 'h"NPT Upstream Drain ©/z"NPT Upstream Drain m h"NPT Downstream Drain ®1W NPT Downstream Drain 0 2"NPT(Drain Optional) Typical 2 1/-3765-80 mm Typical 4-87100-200 mm Typical 10-12'/250-300 mm Actual Dimensions Approx. Nominal Outside E to E Weight Size Diameter A B C D E J K P R Each inches inches inches inches inches inches inches inches inches inches inches lbs. mm mm mm mm mm mm mm mm mm mm mm kg 21/4 2.875 3.88 4.26 337 _ _ _ _ 3.6 65 73.0 99 108 91 1.6 76.1 mm 3.000 3.88 4.26 337 - - - - - - 3.6 76.1 99 108 91 1.6 3 3.500 425 5.06 4.174.5 80 88.9 108 129 106 - - - - - 2.0 4 4.500 9.63 6.00 3.88 2.75 3.50 2.00 4.50 350 3.35 20.0 100 114.3 245 152 99 70 89 51 114 89 85 9.1 5 5.563 1030 6.80 430 _ 4.17 2.15 5.88 4.08 3.98 27.0 125 1413 267 173 114 106 55 149 104 101 12.3 5.500 10.50 6.80 4.50 - 4.17 2.15 5.88 4.08 3.98 27.0 139.7mm 139.7 267 173 114 106 55 149 104 101 12.3 6 6.625 11.50 8.00 5.00 _ 4.50 2.38 6.67 4.73 3.89 38.0 150 168.3 292 203 127 114 61 169 120 99 17.2 6.500 1130 8.00 5.00 - 4.50 2.38 6.67 4.73 3.89 38.0 165.1 mm 165.1 292 203 127 114 61 169 120 99 17.2 8 8.625 14.00 9.88 6.06 5.05 5.65 2.15 8.85 5.65 5.75 64.0 200 219.1 356 251 154 128 144 55 225 144 146 29.0 10 10.750 17.00 12.00 7.09 5.96 6.69 2.15 10.92 6.73 _ 100.0 250 273.0 432 305 180 151 170 55 277 171 45.4 12 12.750 19.50 14.00 8.06 6.91 7.64 2.51 12.81 7.73 _ 140.0 300 323.9 495 356 205 176 194 64 925 196 63.5 Dimensions-Series 717H: A .-B_.. a � 1111 II. I II E 0 R J Typical 2"/50 mm-3780 mm Dimensions Approx. Nominal E to E Weight Size A B C D E J K P R Each inches inches inches inches inches inches inches inches inches inches lbs. mm mm mm mm mm mm mm mm mm mm kg 2 8.66 6.46 323 1.48 3.02 2.80 _ _ 425 10.7 50 219.8 164.1 82.1 375 76.7 71.0 108.0 4.9 21 9.37 6.94 331 1.66 3.40 3.38 _ - 438 13.8 65 238.0 176.3 84.1 422 86.4 85.9 111.3 6.3 76.1 mm 9.37 6.94 3.31 1.66 3.40 338 - - 4.38 13.8 238.0 176.3 84.1 422 86.4 85.9 1113 6.3 3 9.62 7.44 353 1.91 3.65 3.38 _ _ 4.63 20.0 80 244.3 189.0 89.7 48.5 92.7 85.9 117.6 9.1 victaulic.com 4 ✓ctaulic Check Valve I Firelock®I Series 717&717H I Publication 10.08 - Flow Characteristics The charts below express the flow of water at 60°F/16°C through valve. 5717H/717HR 10 - w. l kk y _ ...._... _ ...,.,. .4a,—4- F �F t 0 1 I 1 .t' 4.A 1 �CCs y F� J 1 b5 y d a: i ' "1" ':#0°1°14101 10 100 1000 Flow—GPM 5717H/717HR Y .... _ n y q I : I . FF i o & ro, ,\b ,FR k. ��cR J 10.00 1 x ,' 4b s 'y a 1 6�` R ,$t .c ^,v o ,:• N ,.y... ,..., ,. .Mme-.-o. l " ! € F I t # 1.00 2, 1 t 10 100 1000 110 100000 Flow Rate—Litres/min. victaulic.com 5 ✓ctaulic Check Valve I Firelock®I Series 717&717H I Publication 10.08 Flow Characteristics The charts below express the flow of water at 60°F/16°C through valve. 5717/717R s yFei > C ` i..., i1b F ' ,& I ,.x. -. .,s. /. F .,„..-4, r 1 i , . .\ FF F o . ?1 t. , n ( t l S p £ ' ;I I t 8 ! I 1< r 1 ( I' i l 5 I5 10 100 1000 10000 10 000 Flow-GPM 5717/717R 10 ,« 1 � 4 —1 I .y t 'r 1,. 6 Fe 1 .;:, 4, F I I a ,r ,.d4.t. ,moo. ;�$ ,_., �F 4 pow i.., s i I II;,,,,,4- M �. ,\'y of \\o: \' '`,V ;{:.. „,„ J 1 le „- r 'V� c- ,,, - I l I I Ili S i n } , nw t E va- .. .. ` II i til 3 i I I 5. ' b i . 0.1 - AR `_ ia 1 rte. 10 100 1000 10000 100000 Flow-GPM • Installation Note Reference should always be made to the 1-100 Victaulic Field Installation Handbook for This product shall be manufactured by Victaulic or to Victaulic specifications.All products the product you are installing.Handbooks are included with each shipment of Victaulic to be installed in accordance with current Victaulic installation/assembly instructions. products for complete installation and assembly data,and are available in PDF format Victaulic reserves the right to change product specifications,designs and standard on our website at www.victaulic.com. equipment without notice and without incurring obligations. Warranty Trademarks Refer to the Warranty section of the current Price List or contact Victaulic for details. Victaulic and FireLock are registered trademarks of Victaulic Company. 10.08 1479 Rev.R Updated 05/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 6 jetaulie FireLock® Buterfly Valve ✓Ctauiic Style 705 with Weatherproof Actuator 10.81 Material Specifications: Body: Ductile iron conforming to ASTM A-536,grade } .F 65-45-12 End Face, 2—6750— 150 mm: Ductile iron conforming to ASTM A-536, grade 65-45-12 Seal Retainer, 8— 12"/200—300 mm: Ductile iron conforming to ASTM A-536, grade 65-45-12 Approvals/Listings: Coating: Black alkyd enamel s LPCB Fnn Disc: Ductile iron conforming to ASTM A-536, grade USTE0 #G410001 104j/04 65-45-12,with electroless nickel coating conforming to See Victaulic Publication 10.01 for more details. ASTM B-733 Seat: Product Description: ❑ Grade "E" EPDM The Series 705 Butterfly Valve features a weatherproof actuator housing Approved for indoor or outdoor use,a Stems:416 stainless steel conforming to ASTM A-582 ductile iron body and disc with EPDM seats. Designed for fire protection services only.Victaulic FireLock Stem Seal Cartridge: C36000 brass Series 705 Butterfly Valve is cULus Listed, LPCB Listed, FM and VdS Approved for 300 psi/2068 kPa service. Bearings: Stainless Steel with TFE lining Contact Victaulic for details of agency approvals. Stem Seals: EPDM Stem Retaining Ring: Carbon steel Actuator: 0 2—8750—200mm: Brass or bronze traveling nut on a steel lead screw, in a ductile iron housing ❑ 10—127250—300mm: Steel worm and cast iron quadrant gear, in a cast iron housing Job/Owner Engineer System No. Spec Section Location Paragraph Contractor Approved Submitted By Date Date victaulic.com I Butterfly Valve I Series 705 I Publication 10.81 10.81 5662 Rev F Updated 11/2014 ©2014 Victaulic Company.All rights reserved. 1 iCtaUIic" victaulic.com I Butterfly Valve I Series 705 I Publication 10.81 Approvals and Listings: Approval/Listing Service Pressures Series 705 Butterfly Valve Size cULus FM Vds LPCB 2"/50 mm up to 300psi/2068kPa n/a up to 300psi/2068kPa up to 300psi/2068kPa 2 1/2"/65 mm up to 300psi/2068kPa up to 300psi/2068kPa n/a up to 300psi/2068kPa 76.1 mm up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa 3"/80 mm up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa 4'/100 mm up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa 5"/125 mm up to 300psi/2068kPa up to 300psi/2068kPa n/a up to 300psi/2068kPa 139.7 mm up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa 6/150 mm up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa 165.1 mm up to 300psi/2068kPa up to 300psi/2068kPa n/a up to 300psi/2068kPa 8"/200 mm up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa 10"/250 mm up to 300psi/2068kPa up to 300psi/2068kPa n/a up to 300psi/2068kPa 12"/300 mm up to 300psi/2068kPa up to 300psi/2068kPa n/a up to 300psi/2068kPa 10.81 5662 Rev F Updated 11/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 2 ictaulid victaulic.com I Butterfly Valve I Series 705 I Publication 10.81 Dimensions: ��'' Alli" I I dAL' ,_.( Cl". .---\ F G E-ba 1-D NOTE:OPTIONAL'"/15MM TAP AVAILABLE. CONTACT VICTAULIC FOR DETAILS. Actual Dimensions Nominal Outside E to E Size Diameter A B C D E F G DIA H J inches inches inches inches inches inches inches inches inches inches inches mm mm mm mm mm mm mm mm mm mm mm 2 2.375 4.25 2.28 6.41 _ _ 4.00 4.22 4.50 2.12 60.3 60.3 108.0 57.9 162.8 101.6 107.2 114.3 53.8 21/2 2.875 3.77 2.28 7.54 _ 4.00 4.22 4.50 1.77 73 73.0 95.8 57.9 191.5 - 101.6 107.2 114.3 45.0 3.000 3.77 2.28 7.54 _ 4.00 4.22 4.50 1.77 76.1 mm 76.1 95.8 57.9 191.5 101.6 107.2 114.3 45.0 3 3.500 3.77 2.53 7.79 _ _ 4.50 4.22 4.50 1.77 88.9 88.9 95.8 643 197.9 114.3 107.2 114.3 45.0 108 mm 4.250 4.63 2.88 8.81 - - 5.50 4.22 4.50 2.20 108.0 117.6 73.2 223.8 139.7 107.2 114.3 55.9 4 4.500 4.63 2.88 8.81 _ _ 5.50 4.22 4.50 2.20 114.3 114.3 117.6 73.2 223.8 139.7 107.2 114.3 55.9 5.250 5.88 3.35 10.88 _ _ 6.56 6.19 630 2.58 133 mm 133.0 149.4 85.1 276.4 166.6 157.2 160.0 65.5 5.500 5.88 3.35 10.88 - - 6.56 6.19 630 2.58 139.7 mm 139.7 149.4 85.1 276.4 166.6 157.2 160.0 65.6 5 5.563 5.88 3.35 10.88 _ _ 6.56 6.19 630 2.58 141.3 1413 149.4 85.1 276.4 166.6 157.2 160.0 65.5 159 mm 6.250 5.88 3.84 11.38 - 0.41 7.52 6.19 6.30 2.58 159.0 149.4 97.5 289.1 10.4 191.0 157.2 160.0 655 165.1 mm 6.500 5.88 3.84 11.38 - 0.41 7.52 6.19 630 2.58 165.1 149.4 97.5 289.1 10.4 191.0 157.2 160.0 65.5 6 6.625 5.88 3.84 11.38 0.41 7.52 6.19 6.30 1.90 1683 168.3 149.4 97.5 289.1 10.4 191.0 157.2 160.0 483 8 8.625 533 5.07 13.53 0.80 1.47 10.00 6.19 8.10 2.33 219.1 219.1 135.4 128.8 343.6 203 37.3 254.0 157.2 205.7 59.2 10 10.750 6.40 637 15.64 1.41 1.81 12.25 8.10 9.00 _ 273 273.0 162.6 161.8 3973 35.8 46.0 311.2 205.7 228.6 12 12.750 650 7.36 16.64 230 2.80 14.25 8.10 9.00 - 323.9 323.9 165.1 186.9 422.7 58.4 71.1 362.0 205.7 228.6 10.81 5662 Rev F Updated 11/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 3 ictaulic victaulic.com I Butterfly Valve I Series 705 I Publication 10.81 Performance: The chart expresses the frictional resistance of Victaulic Series 705 Butterfly Valve in equivalent feet/ meters of straight pipe. Nominal Outside Equivalent Size Diameter mm mm Feet/m inches inches of pipe 2 2.375 6 50 60.3 1.8 21/2 2.875 6 65 73.0 1.8 76.1 mm 3.000 6 76.1 1.8 3 3.500 7 80 88.9 2.1 4 4.500 8 100 114.3 2.4 108 mm 108 mm 8 2.4 5 5.563 12 125 1413 3.7 133 mm 133 mm 12 3.7 139.7 mm 5.500 12 139.7 3.7 6 6.625 14 150 1683 4.2 159 mm 159 mm 14 4.3 165.1 mm 6.500 14 165.1 4.2 8 8.625 16 200 219.1 4.9 10 10.750 18 250 273.0 5.5 12 12.750 19 300 323.9 5.8 10.81 5662 Rev F Updated 11/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 4 ✓ctaulic victaulic.com I Butterfly Valve I Series 705 I Publication 10.81 Performance: C„values for flow of water at+60°F/+16°C through a fully open valve are shown in the table below. For additional details,contact Victaulic. Formulas for C„values Formulas for K„values Where: z Where: AP=QZ/K AP=o2/C52 v Flow Coefficient c, Q=K�x SAP Flow Factor K Q=c XJAP Q(Flow) EMI Q(Flow) ms/hr AP(Pressure Drop) psi AP(Pressure) bar Valve Size Full Open Valve Size Full Open Actual Actual Nominal Outside Nominal Outside Size Diameter Flow Coefficient Size Diameter Flow Coefficient inches inches c inches inches K,, mm mm mm mm 2 2375 2 2.375 147 50 60.3 170 50 60.3 21 2.875 260 2' 2.875 65 73.0 65 73.0 225 76.1 mm 3.000 260 76.1 mm 3.000 225 76.1 76.1 3 3.500 3 3.500 380 80 88.9 440 80 88.9 4 4.500 4 4.500 710 100 114.3 820 100 1143 108mm 108mm 820 108mm 108mm 710 5 5.563 1200 5 5.563 1040 125 1413 125 1413 133mm 133 mm 1200 133mm 133 mm 1040 139.7 mm 5.500 1200 139. mm 5. 7 500 1040 139.7 139.7 6 6.625 1800 6 6.625 1560 150 1683 150 168.3 159 mm 159 mm 1800 159 mm 159 mm 1560 165.1 mm 6.500 1800 165.1 mm 6.500 1560 165.1 165.1 8 8.625 3400 8 8.625 2940 200 219.1 200 219.1 10 10.750 5800 10 10.750 5020 250 273.0 250 273.0 12 12.750 12 12.750 7790 300 323.9 9000300 323.9 10.81 5662 Rev F Updated 11/2014 ®2014 Victaulic Company.All rights reserved. victaulic.com 5 ictaulic victaulic.com I Butterfly Valve I Series 705 I Publication 10.81 Switch and Wiring: ULDSTED iuNrnoN eox • CONDUIT ,4./ 1. The supervisory switch contains two single pole, L .�:�4Iv._ double throw, pre-wired switches. ��' `.14, a m N'NRi - coNDUlrcoNNECTau 2. Switches are rated: 1 r IMRE NUTS 10 amps @ 125 or 250 VAC/60 Hz 0.50 amps CO 125 VDC FIRE ALARM TO END-OF-LINE RESISTOR, 0.25 amps CP 250 VDC CONnIOL FANEL OR NEXT INDICATOR SUPERVISORY CIRCUIT 3. Switches supervise the valve in the "OPEN" position. SACH CONTACT RATING: _. M .19 5. One switch has two#18 insulated wires per terminal, 1RA "° 'SOSACAT 125 EN No W24 025 AT 125 250VDC, _ 025 AT ' which permit complete supervision of leads (refer � oRL to diagrams and notes below). The second switch VOLTAGE SOURCE HORN has one#18 insulated wire per terminal. This double Swl"hl:',leaa.pereeemtli Swech 2:1 bA pe,,.n,tsl circuit provides flexibility to operate two electrical devices at separate locations, such as an indicating light and an audible alarm, in the area that the valve NOTE:The above diagram shows a connection between is installed. the common terminal (yellow—51 and yellow-with- orange stripe—S2)and the normally closed terminal 6. A#14 insulated ground lead (green) is provided. (blue—51 and blue-with-orange stripe—S2). In this Switch#1 =S1 example,the indicator light and alarm will stay on until the valve is fully open.When the valve is fully open, the For connection to the supervisory circuit of a UL indicator light and alarm will go out. Cap off any unused Listed alarm control panel wires(e.g. brown with orange stripe). Switch#2=S2 Only 51 (two leads per terminal) may be connected to Auxiliary switch that may be connected to auxiliary the fire alarm control panel. devices, per the authority having jurisdiction The connection of the alarm switch wiring shall be in accordance with NFPA 72 and the auxiliary switch per Normally Closed: (2) Blue Si NFPA 70(NEC). Common: (2)Yellow Normally Closed: Blue with Orange Stripe S2 Normally Open: Brown with Orange Stripe Common: Yellow with Orange Stripe Installation Note Reference should always be made to the 1-100 Victaulic Field Installation Handbook tor This product shall be manufactured by Victaulic or to Victaulic specifications.All products the product you are installing.Handbooks are included with each shipment of Victaulic to be installed in accordance with current Victaulic installation/assembly instructions. products for complete installation and assembly data,and are available in PDF format Victaulic reserves the right to change product specifications,designs and standard on our website at www.victaulic.com. equipment without notice and without incurring obligations. Warranty Trademarks Refer to the Warranty section of the current Price List or contact Victaulic for details. Victaulic®is a registered trademark of Victaulic Company. 10.81 5662 Rev F Updated 11/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 6 jctaulic° FireLock NXTTM Dry Valve 4tauiicr Series 768 30.80 Patent Pending Certifications/Listings: C 4.21 US .C> LPCB C L vis t (T_P 104f/O1 0832 �.. `� MEA:248-98-E See Victaulic Publication 10.01 for more details. Product Description: The patent-pending Victaulic Series 768 FireLock NXT Dry Valve is a low differential, latched clapper valve that uses a unique direct acting diaphragm to separate system water supplies from dry-pipe sprinkler systems. see page 12 for European trim Job/Owner Engineer System No. Spec Section Location Paragraph Contractor Approved Submitted By Date Date victaulic.com I NXT Dry Valve I Series 768 I Publication 30.80 30.80 4219 Rev G Updated 01/2015 ©2015 Victaulic Company.All rights reserved. 1 jctaulie victaulic.com I NXT Dry Valve I Series 768 I Publication 30.80 Features: The low differential, unique latch and actuator design of the valve allows the valve to be reset without opening the valve. The low differential design is not subject to water columns. The valve allows the water to operate a water • motor alarm and/or electric pressure alarms,which Clapper continue until the flow of water stops. With the optional �.' "S0 �"h accelerator,the valve can be configured to respond `�, faster for use in larger systems, or where faster response times are required. \ '�_ , /`� ' Diaphragm The valve is rated to 300 psi/2065 kPa water working (" ♦\���yit,"&;. . Assembly l? �J- �� pressure and is factory tested hydrostatically to 600 psi/ M'��,r— 4135 kPa for sizes 1 %2—8740—200 mm. VdS trim ON)i Clapper Seal configurations are approved to 16 BAR (see page 12). $ 0 seat Required air pressure for all trim variations is 13 psi/ 90 kPa. The Series 768 is available grooved x grooved. Exaggerated for clarity Standard grooved dimensions conform to ANSI/AWWA Note:Valve is shown in the"set"position C606. The Victaulic Series 768 FireLock NXT Dry Valve is made of high-strength, low-weight ductile iron, and it offers easy access to all internal parts. All internal parts are replaceable. Maintenance and service can be performed without removing the valve from its installed position. The rubber clapper seal is replaced easily without removing the clapper from the valve. The valve is painted inside and out to increase corrosion resistance. The body is tapped for main drain and all available trim configurations. Installation Options The Victaulic Series 768 FireLock NXT Dry Valve is available bare, or in the following configurations: Pre-trimmed The pre-trimmed valve comes completely assembled with all necessary trim components. Vic-Quick Riser The Vic-Quick Riser comes completely pre-trimmed and includes a shut off valve(uses a Series 705W FireLock Butterfly valve—request publication 10.18;for 1 1/2 and 2'/40 and 50 mm sizes,the Vic-Quick Riser comes with a Series 728 Ball Valve—request publication 10.17)for system shut off, pre-set pressure switches,and a drain kit for ease of installation. For complete Vic-Quick Riser information request publication 30.20. Series 745 FireLock Fire-Pac(Available in North America only) The Fire-Pac is a completely pre-assembled fire protection valve that provides maximum service in a minimal enclosed space. The unit includes a water supply shutoff valve,the sprinkler system fire protection valve, alarm line pressure switches, air supervisory pressure switches,supervisory pump switches, and digital pressure gauges that are easily viewed through a window in the cabinet door. For complete Fire-Pac information request publication 30.23. Optional accessories ship separately. 30.80 4219 Rev G Updated 01/2015 ©2015 Victaulic Company.All rights reserved. victaulic.com 2 ictaulid victaulic.com I NXT Dry Valve I Series 768 I Publication 30.80 Dimensions: The 4 Inch/114.3 Mm UI Listed,FM Approved Configuration Is Shown Below 11/2-2748.3-60.3 mm Configurations Contain 3/<'/19 mm Drain Valves. 21/2-3"/73.0-88.9 mm Configurations Contain 11/4"/31 mm Drain Valves. 4-8"/114.3-219.1 mm Configurations Contain 2"/50 mm Drain Valves. r-I I I i'ev��is �y.. ' _ h--4 iti 1 G Yi CI -� 4:.11.1 A rr-T . I u He. it ��r.167 a r-+I .Inl._j I II ..�;li\�1. LL-1" F J II II ir�i _ In -I_a_Y ❑I III �',�'1 ® I D *Dl �� �� IL J1 i 1 O J -II I' TI •FOII' \ "Alrail SI eot . % � I lief II €', 'I -t� 1 1O II J cm--pp.> •I.� I4 i y lit_ aT is - II 4 El EllpIli Ill"L 14--- K C >4 "El Full Open Approx. Weight Dimensions Each Actual Nominal Outside Without With Size Diameter A Al B Bl C D Dl E El F G H J K Trim Trim inches inches inches inches inches inches inches inches inches inches inches inches inches inches inches inches lbs. lbs. mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm kg kg 1'h 1.900 9.00 16.35 27.25 39.50 13.75 16.00 _ 5.25 8.50 9.50 21.25 3.04 9.17 6.98 16.7 43.0 40 48.3 228.60 415.29 692 1003 349 406 133 215 241 539 77.21 232.91 177.29 7.6 19.5 2 2.375 9.00 13.37 27.25 39.50 13.75 16.00 _ 5.25 8.50 9.50 21.25 3.04 9.17 6.98 17.0 43.0 50 603 228.60 339.60 692 1003 349 406 133 215 241 539 77.21 232.91 177.29 7.7 19.5 2'h 2.875 12.61 16.50 32.25 44.25 13.50 16.00 17.50 5.25 9.00 9.25 21.25 3.90 10.50 6.93 41.0 65.0 65 73.0 320.29 419.10 819 1123 342 406 444 133 228 234 539 99.06 266.70 176.02 18.7 29.5 76.1 mm 3.000 12.61 16.50 32.25 44.25 13.50 16.00 17.50 5.25 9.00 9.25 21.25 3.90 10.50 6.93 41.0 65.0 76.1 320.29 419.10 819 1123 342 406 444 133 228 234 539 99.06 266.70 176.02 18.7 29.5 3 3.500 12.61 16.50 32.25 44.25 13.50 16.00 17.50 5.25 9.00 9.25 21.25 3.90 10.50 6.93 41.0 65.0 80 88.9 320.29 419.10 819 1123 342 406 444 133 228 234 539 99.06 266.70 176.02 18.7 29.5 4 4.500 15.03 19.83 33.50 45.50 15.00 15.75 20.50 5.25 9.00 10.75 21.00 6.25 9.62 8.46 59.0 95.0 100 114.3 381.76 503.68 850 1155 381 400 520 133 228 273 533 158.75 244.34 214.88 26.7 43.0 165.1 mm 6.500 16.00 22.00 34.00 46.00 15.50 17.00 22.00 5.25 8.50 11.50 20.50 6.20 9.62 8.84 80.0 116.0 165.1 406.40 558.80 863 1168 393 431 558 133 215 292 520 157.48 244.34 224.53 36.2 52.6 6 6.625 16.00 22.05 34.00 46.00 15.50 17.00 22.00 5.25 8.50 11.50 2030 6.20 9.62 8.84 80.0 116.0 150 168.3 406.40 560.07 863 1168 393 431 558 133 215 292 520 157.48 244.34 224.53 36.2 52.6 8 8.625 17.50 23.00 3350 45.50 16.75 20.00 25.25 6.25 8.75 12.75 18.50 6.05 9.40 10.21 122.0 158.0 200 219.1 444.50 584.20 850 1155 425 508 641 158 222 323 469 153.67 238.76 259.33 55.3 71.6 NOTES: The"A"dimension coupling is not shown in order to clarify dimensional callouts. Components shown as dotted lines denote optional equipment. *Measurements denoted with an asterisk take optional equipment into account. Optional drain connection kit is shown for reference and takeout dimensions. 30.80 4219 Rev G Updated 01/2015 ©2015 Victaulic Company.All rights reserved. victaulic.com 3 ictauliic victaulic.com I NXT Dry Valve I Series 768 I Publication 30.80 Performance: Hydraulic Friction Loss The chart below expresses the flow of water at 65°F/18°C through a full open valve. 5.0 4 :,r,.,, ..4 40 I ' I, t tf �, 0 I , I 20 -i, - _ ,,,e• .7a of i -i • 0 0.9 C n 05 ! = 1 ! " CO CC d 03 r..., Ei j -r s M ;, ' P i i 0.1 . x {_1..,x _A.i_ ,..W!,,..•,. .... .v 1.1 LL _ 10 20 30 40 60 80 100 200 300 400 600 1,000 2,000 4,000 6,000 10,000 20,000 800 3,000 8,000 FLOW RATE-GPM Frictional Resistance The chart below expresses the frictional resistance of Victaulic Series 768 FireLock NXT. Dry Valve in equivalent feet of straight pipe. Actual Equivalent Nominal Outside Length of Size Diameter Pipe inches inches feet mm mm meters 1 Y2 1.900 3.00 40 48.3 0.914 2 2.375 9.00 50 60.3 2.743 21 2.875 8.00 65 73.0 2.438 3.000 8.00 76.1 mm 76.1 2.439 3 3.500 17.00 80 88.9 5.182 ' 4 4.500 21.00 100 114.3 6.401 6.500 22.00 165.1 mm 165.1 6.706 6 6.625 22.00 150 168.3 6.706 8 8.625 50.00 200 219.1 15.240 30.80 4219 Rev G Updated 01/2015 ©2015 Victaulic Company.All rights reserved. victaulic.com 4 xictaulie victaulic.com I NXT Dry Valve I Series 768 I Publication 30.80 ;Values: Operation: Cv values for flow of water at+60°F/+16°C through a fully The Series 768 Dry Valve contains a clapper,which has open valve are shown in the table below. a replaceable rubber seal.The clapper makes contact with the valve's seat ring,which has access Formulas for C,values Where: holes leading into an intermediate chamber in the valve. AP=Q2/C„2 Flow Coefficient C, The diaphragm contacts the latch, and the latch holds Q=C,x VAP Q(Flow) GPM the clapper closed. AP(Pressure Drop) psi In the closed position,the valve diaphragm is maintained in the extended position by the water supply pressure from upstream of the water supply control valve. The diaphragm latch holds the clapper in the closed position. The Series 776 Low Pressure Actuator(LPA) maintains Valve Size Full Open the water,and the system's air pressure controls the Actual LPA. Required air pressure is 13 psi/90 kPa. The design Nominal Outside of the 776 actuator does not require the traditional air Size Diameter Flow Coefficient cushion of 10—20 psi/69— 138 kPa. Excess air inches inches pressure above 13psi/90 kPa will cause a delayin valve mm mm K, 1'h 1.900 60 operation. 40 48.3 52.0 Once the system's air pressure reduces to the trip point, 50 60.32375 95 110 the LPA opens and allows the water supply pressure in 21/2 2.875 180 the diaphragm to release(i.e.an open sprinkler). This 65 73.0 156.0 release allows the latch to move to its open position, 76.1 mm 7600 156.0permitting the clapper to pivot freely,thus allowing water into the system. 3 3.500 200 80 88.9 173.0 Water enters the intermediate chamber of the valve 4 4.500 350 through the holes in the seat ring. The water flows from 100 114.3 302.8 the intermediate chamber to the alarm line,which 165.1 mm 6.500 1000 activates the s stem's alarms. The alarms continue to 165.1 865.0 y 6 6.625 1000 sound until the flow of water stops. 150 1683 865.0 When the flow of water stops,the spring-assisted valve 280 28.625 11590 clapper returns to the closed position.The valve acts as an alarm check valve until the system is back in service as a dry system, according to the proper procedure. 30.80 4219 Rev G Updated 01/2015 ©2015 Victaulic Company.All rights reserved. victaulic.com 5 tctauliC' victaulic.com I NXT Dry Valve I Series 768 I Publication 30.80 Material Specifications: Body: Ductile iron conforming to ASTM A-536,grade 65-45-12. Ductile iron conforming to ASTM A-395, grade 65-45-15, is available upon special request. Clapper:Aluminum bronze UNS-C95500 Latch:Aluminum bronze UNS-C95500 Shaft: Stainless 17-4 Clapper Seal: Peroxide cured EPDM, ASTM D2000 Bushings/Seat 0-rings: Nitrile Springs:Stainless Steel (300 Series) Diaphragm: Peroxide cured EPDM with fabric reinforcement Bill of Materials 1 Valve Body 12 Cover Plate 2 Clapper 13 Cover Plate Gasket 3 Clapper Seal 14 Cover Plate Bolts* 4 Seal Ring 15 Latch 5 Seal Washer 16 Latch Spring 6 Seal Retaining Ring 17 Latch Spring Bushing and 0-ring(Qty.2) 7 Seal Assembly Bolt 18 Diaphragm 8 Bolt Seal 19 Diaphragm Cover 9 Clapper Spring 20 Diaphragm Cover Cap Screws(Qty.8) 10 Clapper Shaft 21 Latch Shaft 11 Clapper Shaft Bushing and 0-ring(Qty.2) 0 • • 0 „(-401.1.1* m m . NodCIO : 0 ..i 0 N t1 0 O 0 4110 11110) 0 v'..• . 0 *NOTE:The 11/2-inch/48.3-mm and 2-inch/60.3-mm valve sizes contain washers under the heads of the cover plate bolts. 30.80 4219 Rev G Updated 01/2015 ©2015 Victaulic Company.All rights reserved. victaulic.com 6ictauliC victaulic.com I NXT Dry Valve I Series 768 I Publication 30.80 Trim Package Details: • Air Compressor(See page 8 for more on the Trim Packages: Victaulic Series 7C7 Compressor Package) • NOTE: See page 11 for details of trim and page 12 for Air Maintenance Trim Assembly details of European trim. • Alarm Panels 1 Galvanized components. • Drain Connection Kit 2 Series 776 Low-Pressure Actuator—The Series 776 Low-Pressure Actuator is pneumatically actuated and requires only 13 psi/90 kPa minimum air Air Supply Requirements: pressure, regardless of the system supply pressure. This actuator allows the system to operate with a low The required air pressure for Series 768 FireLock NXT air or gas pressure of 7 psi/48 kPa. Dry Valves is 13 psi/90 kPa minimum, regardless of the system supply water pressure.Air pressures should be 3 All Required Pipe and Fittings. kept below 18 psi/124 kPa, unless a Series 746-LPA 4 All Standard Trim Accessories. Dry Accelerator is installed.Systems with air pressures higher than 18 psi/124 kPa may require the addition of a 5 All Required Gauges Series 746-LPA Dry Accelerator. Optional Trim Package: If multiple Series 768 FireLock NXT Dry Valves are 1 Black Trim for Foam Systems—If the valve is installed with a common air supply, isolate the systems intended for use in a foam system, black trim must with a spring-loaded, soft-seated ball check valve to be ordered, per NFPA requirements.Specify this ensure air integrity for each system. Good practice is requirement on the order. to include a ball valve for isolation and service of each individual system. The engineer/system designer is responsible for sizing Optional Accessories: the compressor so that the entire system is charged to • Series 746-LPA Dry Accelerator—The Series the required air pressure within 30 minutes. DO NOT 746-LPA Dry Accelerator is required when the oversize the compressor to provide more airflow.An Series 768 Dry Valve is installed in large systems to oversized compressor will slow down or possibly prevent improve response time. Request submittal 30.64. valve operation. • Series 760 Water Motor Alarm—The Series 760 If the compressor fills the system too fast, it may be Water Motor Alarm is a mechanical device that necessary to restrict the air supply. Restricting the air sounds when a sustained flow of water occurs(such supply will ensure that air being exhausted from an open as with an open sprinkler). Request submittal 30.32. sprinkler or manual release valve is not replaced by the air supply system as fast as it is being exhausted. • Series 75B Supplemental Alarm Device—The Series 75B Supplemental Alarm Device is designed to provide a continuous alarm for systems equipped with a mechanical device. Request submittal 30.33. • Series 75D Water Column Kit—The Series 75D Water Column Kit is designed to minimize residual water in the riser from collecting above the clapper. Request submittal 30.34. • Alarm Pressure Switch—Alarm Pressure Switches are designed to activate electrical alarms and control panels when a sustained flow of water occurs(such as with an open sprinkler). • Air Supervisory Pressure Switch—Air Pressure Supervisory Switches are used to monitor low system air pressure and are factory pre-set. • Air Supply System—The air supply system contains all components for establishing and maintaining air in the system. The compressor, low-pressure alarms, ball valves, and required trim are included in the air supply system. 30.80 4219 Rev G Updated 01/2015 ©2015 Victaulic Company.All rights reserved. victaulic.com 7 jataulic victaulic.com I NXT Dry Valve I Series 768 I Publication 30.80 Compressor Sizing: COMPRESSOR REQUIREMENTS 12 20 psi/138 kPa 13 psi/90 kPa 10 I C k t G • I E V N " 7 4 � �,.. ••• • 4 � ' I W 0 O � O O O O 8 SYSTEM CAPACITY(in gallons) Base or Riser-Mounted Compressors: Shop Air or Tank-Mounted Air Compressors: For base or riser-mounted compressors,the recom- In the event a compressor becomes inoperative, a mended air pressure of 13 psi/90 kPa is the "on" or properly sized tank-mounted air compressor provides "low" pressure setting for the compressor. The "off" the greatest protection for systems. or"high" pressure setting should be 18 psi/124 kPa. When shop air or a tank-mounted air compressor is Victaulic offers the Series 7C7 Compressor package used,the Series 757 Regulated AMTA must be installed. for FireLock NXT devices which is riser-mounted and The Series 757 Regulated AMTA provides proper air pre-set for the FireLock NXT pressure requirements as regulation from the air reservoir to the sprinkler system. stated above. For information on the Series 7C7 package, consult publication 30.22.The Series 7C7 For tank-mounted air compressors,the recommended Compressor package is only available in North America. air pressure of 13 psi/90 kPa should be used as the When a base or riser mounted air compressor supplies set point for the air regulator. The "on" pressure of the air to a Series 768 FireLock NXT Dry Valve, it is not compressor should be at least 5 psi/34 kPa above the set point of the air regulator. necessary to install the Victaulic Series 757 Regulated Air Maintenance Trim Assembly(AMTA). In this case, the airline of the compressor connects to the trim at the fitting where the Series 757 Regulated AMTA is normally installed (refer to the applicable trim drawing). If the compressor is not equipped with a pressure switch,the Series 757P Air Maintenance Trim Assembly with Pressure Switch should be installed. For information on the Series 757 Regulated Air Maintenance Trim Assembly, see publication 30.35. For information on the Series 757P Air Maintenance Trim Assembly, see publication 30.36. 30.80 4219 Rev G Updated 01/2015 ©2015 Victaulic Company.All rights reserved. victaulic.com 8 ictaulic' victaulic.com I NXT Dry Valve I Series 768 I Publication 30.80 Series 757 Regulated Air Maintenance Trim Assembly: • Victaulic recommends a maximum of two Series 768 FireLock NXT Dry Valves per Series 757 Regulated AMTA Bill of Materials 1 1/2"/3.2 mm Restrictor 2 Slow Fill Ball Valve(Normally Open) 3 Air Regulator '1? 4 Strainer(100 Mesh) .70 5 Spring-Loaded,Soft-Seated j jj Ball Check Valve 0 0 6 Fast Fill Ball Valve(Normally Closed) ui © e z;✓ 0 Weir rq Exaggerated for clarity Series 757P Air Maintenance Trim Assembly With Pressure Switch: . • Victaulic recommends a maximum of two Series 768 FireLock NXT Dry Valves per Series 757P AMTA with Pressure Switch ; I0 Bill of Materials 0 I; �/ Item Qty. Description I \% 1 1 Restrictor(1h-inch NPT) 2 1 Strainer(1/2-inch NPT) O 3 1 Swing Check(1/-inch NPT) 4 1 Slow-Fill Ball Valve m (Normally Open) 5 1 Spring-Loaded,Soft-Seated O Check Valve ' 6 1 Pressure Switch 7 2 Compression Fitting,Straight (1/4-inch NPTx 1/4-inch Tube) 5 V 8 1 Copper Tubing(1/4-inch OD) 9 11 Close Nipple ® ice. (1/2-inch NPTx 1.13) ' 10 1 Nipple(1h-inch NPTx4.00) \ rie, ® 11 1 90°Female Elbow(1/-inch NPT) 12 4 Female Tee(h-inch NPT) 13 3 Union(1/2-inch NPT) Y� 14 2 Reducing Bushing ® (4 (1/2-inch NPT x 1A-inch NPT) q �•. 15 1 Fast-Fill Ball Valve (Normally Closed) © `�t , 16 1 Pressure Switch Isolation Ball 7 m' • 'i:• Valve(Normally Open- i '® Lockable) FROM COMPRESSOR ® /�/.• SYSTEM Exaggerated for clarity 30.80 4219 Rev G Updated 01/2015 ©2015 Victaulic Company.All rights reserved. victaulic.com 9 jctaulid victaulic.com I NXT Dry Valve I Series 768 I Publication 30.80 Compressor Requirements: Remote System Test Valve Requirements Compressor Requirements and Settings for Series 768 The remote system test valve(inspector's test connection) FireLock NXT Dry Valves Installed with Series 746-LPA should contain a UL Listed and/or FM Approved valve Dry Accelerators (normally closed),which can be opened to simulate the Set the air regulator of the Series 757 Regulated AMTA operation of a sprinkler. to 13 psi/90 kPa. The remote system test valve(inspector's test connection) THE SERIES 757P AIR MAINTENANCE TRIM should be located at the most hydraulically ASSEMBLY WITH PRESSURE SWITCH MUST NOT BE demanding location in the release system. USED ON A SERIES 768 FIRELOCK NXT DRY VALVE NOTE: Multiple restrictions on the remote system test INSTALLED WITH A SERIES 746-LPA DRY valve (inspector's test connection) may slow the air ACCELERATOR. decay rate and cause the system to respond slower than required. When a Series 768 FireLock NXT Dry Valve is installed with a Series 746-LPA Dry Accelerator,the Series 757 The remote system test valve(inspector's test connection) Regulated AMTA must be used. NOTE: The use of an air should terminate with an orifice equal to the regulator with a base or risermounted compressor could smallest orifice in the releasing system. cause short cycling, resulting in premature wear of the The remote system test valve(inspector's test connection) compressor. is used to ensure that water reaches the most remote In the event a compressor becomes inoperative, a part of the system within 60 seconds. properly sized tank-mounted air compressor provides the greatest protection for systems installed with a Series 746-LPA Dry Accelerator. In this situation, air can be supplied continuously to the sprinkler system for an extended time period. NOTE: The Series 757 Regulated AMTA must be used with a tank-mounted air compressor or shop air system that continually supplies air to a Series 768 FireLock NXT Dry Valve installed with a Series 746-LPA Dry Accelerator. The air regulator of the Series 757 Regulated AMTA is a relief-type design.Any pressure in the system that is above the set point of the air regulator will be released. Therefore,charging the air regulator above the set point could cause premature operation of a valve installed with a Series 746-LPA Dry Accelerator. NOTE:The series 746-LPA should not be used above 30 psi. If higher pressures are required,the series 746 should be used. Settings for Air Supervisory Pressure Switches and Alarm Pressure Switches Air supervisory pressure switches are required for dry systems and must be set according to the following instructions. NOTE: Switches for Vic-Quick Risers are pre-set at the factory. Wire the air supervisory pressure switches to activate a low-pressure alarm signal. NOTE: In addition,the local authority having jurisdiction may require a high-pressure alarm. Contact the local authority having jurisdiction for this requirement. Set the air supervisory pressure switches to activate at 2—4 psi/14—28 kPa below the minimum air pressure required, but not lower than 10 psi/69 kPa. Wire the alarm pressure switch to activate a water flow alarm. Set the alarm pressure switch to activate on a pressure rise of 4—8 psi/28—55 kPa. 30.80 4219 Rev G Updated 01/2015 ©2015 Victaulic Company.All rights reserved. victaulic.com 10 iCtaulie victaulic.com I NXT Dry Valve I Series 768 I Publication 30.80 Exploded View Drawing- Trim Components (c a us <> Trim) LISTED Series 768 FireLock NXT Dry Valve (Optional Accessories Also Shown) Bill of Materials 1 Series 768 FireLock NXT Dry Valve Ol 2 FireLock Rigid Coupling(OptionaV Sold Separately-Comes Standard I OW when VQR Assembly is Ordered) I m 3 Water Supply Main Control Valve From System \s/ i (OptionaVSold Separately-Comes Al,feed -'I I 0 j Standard when VQR Assembly is Ordered) 4 Drain Swing Check Valve 5 Drip Cup with Cap m 7 `i 6 Alarm Pressure Switch(Optional/Sold .'1 / - Separately-Comes Standard when VQR ' Assembly is Ordered) e ® li- L«atma 7 Series 729 Drip Check Valve 0 __ 0 8 Diaphragm-Charge-Line Ball Valve , r (Normally Open) i- %l M l ill . 9 3-in-1 Strainer/ChecWRestrictor - i' / \� O Assembly l 1� l I �, CD f. 0,,%.' 10 Series 760 Water Motor Alarm za I f ���/, ; (Optional/Sold Separately) ® �' A> 3�\` 11 Alarm Test Ball Valve 0 J `_ 12 Diaphragm-Charge-Line Pressure s " 'Mr To Drlpap Gauge(0-300 psi/0-2068 kPa/0-20.7 Bar) ` e -.. a To Drip Crcoanoo �l � , �«atwa p 13 Series 749 Auto Drain ®o - i- •%1 O O 14 Series 746-LPA Dry Accelerator �,L Assembly(Optional/Sold Separately) b 0� 15 Series 776 Low-Pressure Actuator f 16 Air Manifold Note -\• ® syn.m a..,. ... / 17 Air Supervisory Pressure Switch \••\ (Optional/Sold Separately-Comes h--- Standard when VQR Assembly is Ordered) m . ' \• \• 1 , / F. 18 System Pressure Gauge ;� \•\ \• � � 1<�o (0-80 psi/0-552 kPa/0-5.5 Bar with Retard) ♦�� •\• I 19 Water Supply Main Drain Valve- ® O� f J 9,0 • to "� �1Flow Test tl� ip 20 Water Supply Pressure Gauge J ��.. L' . 0 7 ',ihi (0-300psi/0-2068kPa/0 20.7 Bar) ;:its\,\ O �j,\,n` -� 21 Drain Connection Kit(Optional/Sold ,r `----_-J Separately-Comes Standard when VQR Assembly is Ordered) '\ — -te--�ice`'' j r 22 Gauge Valve \ILIj\ 23 System Main Drain Valve �` 24 Series 748 Ball Check Valve I�' - © kil ' \TLDritronpt 1,„. o�uO ii'I (047k .11 ,-p,.i �l © q‘ �4r 4111/ From Water Supply Exaggerated for clarity Optional devices include the Series 75D Water Column Device Kit and the Series 75B Supplemental Alarm Kit. NOTE 1:Connection point for the Series 75D Water Column Device Kit. For installation of the Series 75B Supplemental Alarm Device,refer to the instructions supplied with the product. 30.80 4219 Rev G Updated 01/2015 ©2015 Victaulic Company.All rights reserved. victaulic.com 11 ictaulilc victaulic.com I NXT Dry Valve I Series 768 I Publication 30.80 Exploded View Drawing— Trim Components: ( (European Trim: C 0 us FM ILKBI « VdS p) 104f/01 0832 MEA:248-98-E Series 768 FireLock NXT Dry Valve (Optional Accessories Also Shown) Bill of Materials 1 Series 768 FireLock NXT Dry Valve Ol i 0 2 FireLock Rigid Coupling(Optional/Sold 1 Separately-Comes Standard when VQR V Assembly is Ordered) From System Ilito 1 m 3 Water Supply Main Control Valve(Optional/ lay Feed� .1 =, i it? ,/ Sold Separately-Comes Standard when VQR 1 Assembly is Ordered) , J 4 Drain Swing Check Valve fig•: I,- 5 Drip Cup with Cap ;% 6 Alarm Pressure Switch(Optional/Sold _T 'ILocation Separately-Comes Standard when VQR 0 Assembly is Ordered) 21 7 Series 729 Drip Check Valve i �>, 8 Diaphragm-Charge-Line Ball Valve 1.' I O (Normally Open) i :1 I ,t .„..., ` , 9 3-in-1 Strainer/Check/Restrictor , 04111,... I4) Assembly m ® I r ToOlpCup�, 10 Series 760 Water Motor Alarm J r. .,, TVie Drip notion '04, (OptionaVSold Separately) i1 1 �%1�, (�4 cup I0 11 Alarm Test Ball Valve ® z,t.- .. /- Location e 1 12 Diaphragm-Charge-Line Pressure -� �,` Q., 0 ® o Gauge(0-300 psi/0-2068 kPa/0-20.7 Bar) b �- 13 Series 749 Auto Drain �� t '\• ® sysrem ,.I,. .;i:� 14 Series 746-LPA Dry Accelerator Note 1 •\•, / I Assembly(Optional/Sold Separately) \- T N. 15 Series 776 Low-Pressure Actuator \, \-\ �. T 49 r16 Air Man fold ?i I \•, uf ' 17 Air Supervisory Pressure Switch(Optional/Sold • r i \- :.s Separately-Comes Standard when VQR ® 0 v \1� JI Assembly is Ordered) ,r ' ff(f J \•�`�)"`i 18 System Pressure Gauge • all.(0-80psi/0-552kPa/0-5.5 Bar with Retard) ;.,� 19' 0i''' ''s,<...),..:.'611' l ''19 Water Supply Main Drain Valve- IFlow Test I I - • r 25 20 Water Supply Pressure Gauge -- i (0_300 psi/0-2068 kPa/0-20.7 Bar) �- ® 1''�� 1J 1 21 Drain Connection Kit(Optional/Sold © � `� I'roori O r l�/" I Separately-Comes Standard when VQR tl), - Location Assembly is Ordered) 22 Gauge Valve c, 23 System Main Drain Valve .0"-k) 24 Series 748 Ball Check Valve .� i>/ll \'J © 1.�, 25 Water Motor Alarm Shutoff Valve -if r (Normally Open)' Item 25,water motor alarm shutoff valve,can be closed to prevent water horn flowing into the Series 760 Water Motor alarm during conditions that are not favorable for the alarm to sound(Le during a tnp test). From Water wppb 30.80 4219 Rev G Updated 01/2015 ©2015 Victaulic Company.All rights reserved. victaulic.com 12 ictaul,dr victaulic.com I NXT Dry Valve I Series 768 I Publication 30.80 • This product must be installed by an experienced,trained installer, in accordance with the instructions provided with each valve.These instructions contain important information. Failure to follow these instructions may result in serious personal injury, property damage,or valve leakage. If you need additional copies of this product literature or the valve installation instructions,or if you have any questions about the safe installation and use of this device,contact Victaulic Company, P.O. Box 31, Easton, PA 18044-0031 USA, Telephone:001-610-559-3300. Installation Note Reference should always be made to the appropriate Installation,Maintenance,and This product shall be manufactured by Victaulic or to Victaulic specifications.All products Testing Manual included with each shipment of Victaulic products.These manuals are also to be installed in accordance with current Victaulic installation/assembly instructions. available in PDF format on our website at victaulic.com Victaulic reserves the right to change product specifications,designs and standard Warranty equipment without notice and without incurring obligations. Refer to the Warranty section of the current Price List or contact Victaulic for details. Trademarks Victaulic®and FireLock®are registered trademarks of Victaulic Company. 30.80 4219 Rev G Updated 01/2015 ©2015 Victaulic Company.All rights reserved. victaulic.com 13 ictaul,c IPS CARBON STEEL PIPE-FIRE PROTECTION PRODUCTS 30.35 FireLock® Devices Air Maintenance Trim Assembly SERIES 757 PROPER AIR SUPPLIES FOR SERIES 1.When a riser or base mounted air compressor is being used to supply air to a dry valve or preac- 756/SERIES 758/SERIES 768/SERIES769 tion system it is not necessary to use the air maintenance trim assembly with the air regulator. In this ACTUATED VALVES: circumstance the air line of the compressor is connected to the valve trim at the fitting into which the Air Maintenance Trim is normally installed. When the valve is used with this setup it is the engineer/system designer's responsibility to size the compressor so that the compressor brings the entire system to the required pressure in 30 minutes. The compressor must not be oversized to provide more air flow as this will slow down or possibly prevent the operation of the valve. It must further be emphasized that the base mounted compressor does not provide any backup air to the system and that continuous service(24 hours per day,7 days per week)must be maintained in order to prevent the potential of false tripping of the valve due to loss of air pressure. Additionally,due to the large on/off differential available on pressure switches that control base mounted compressors,the compressor pressure switch must be adjusted so that the"ON"contact of the pressure switch is set a minimum of 5 psi higher than the set point of the regulator. 2.When shop air or a tank mounted air compressor is being used,the Air Maintenance Trim Assembly(AMTA)must be used.The AMTA is designed to provide the proper air regulation to the sprinkler system which will assure the proper operation of the Fire Safety Valve. In the event of a compressor becoming inoperative the tank mounted air compressor provides the greatest protection.With a properly sized tank,air can be continuously supplied to the sprinkler sys- tem for an extended period of time even with a loss of compressor. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. II III 1111111111111111111111 WCAS-7MYM68 For complete contact information,visit www.victaulic.com 30.35 2515 REV D UPDATED 1/2009 ictauliC VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. 30.35 , I'm also available In a BASEPLATE UNIT J frq c_AII:zE . . r � ��ld.1r � ' ' lWi'ik r mpg COMPRESSORS �.. ��",II ► ,. X300 ,1 } . -.... PRODUCT NUMBERING SYSTEM S300H - SD, 1 -1115„ , 1.5 HP ll SYSTEM CAPACITY MOUNTING OPTIONS SERIES PHASE VOLTAGE ADDITIONAL OPTION 3.8 CFM HD SD B.Baseplate HD.Heavy Duty 1:Single Phase t t 5 on,mane<"Seee P:Prewired Power Cord r 175 300 H:Horizontal Tank SD:Standard Duty 3:Three Phase 230rzosose S:Prewired Magnetic Starter 255 2000 Y:Vertical Tank 460 U:30-40psi Pressure Switch 325 m�0oassmannia,ca0 500 (also arailabk in PU and SUr 750 �00 300 GAL. MAX CAP. 3300 1700 'Greyed out nylons do not apply to this unit 'S300H-SP1-115 is a stocked iters 27" x12" x22" n SPECIAL ORDER OPTIONS: SINGLE PHASE 1 Phase:115v/200v/230v v®AMPS 70-100 PSI I -3 Phase:200v/230v/460v zoa 11131 1.0 -Power Cord 230 rEl 1.0 3 Phase Starter THREE PHASE 35 LBS -30-40 PSI Pressure Switch VOLTS AMPS S.F. • -Horizontal or Baseplate Mount 208 En® 230 ME® 1/2" 1 ■ DON'T FORGET YOUR INSTALLATION KIT! aso ®® 'C' The Advantage 26549 FallbrookAvenue,Wyoming,MN 55092//800.762.2247//651.462.3440//www.c-aireinc.com • Spare Sprinkler Head Storage Cabinet Description Fire Protection Products, Inc. Spare Sprinkler Head Cabinets are designed to allow for spare sprinkler head storage as required by NFPA guidelines. The Spare Sprinkler Head Cabinets are available SpeCifiCationS in six configurations. Three head, six head, six head ESFR, twelve head, twenty-four head and thirty-six head. All six styles are Material: manufactured with "knockouts"to accommodate the most common Painted plain steel size sprinklers. The shelf is located to allow for the storage of a typical sprinkler head wrench. Each cabinet is finished with a red Finish: enamel fi nish. Each spare head cabinet comes with a hinged Red enamel door which remains closed to protect the spare sprinklers from the Sales: elements and features two holes on the back panel to allow for 3 Spare sprinklers, attachment to most surfaces utilizing the appropriate fasteners. 1/2 or 3/4 Not intended for exposed or harsh environments. 6 Spare sprinklers, 1/2 or 3/4 Installation 6spare, ESFR, Select the correct Spare Once the correct Spare Sprinkler 1/2 , 3/4 or 1" Sprinkler Head Cabinet in Head Cabinet has been select- 12 Spare sprinklers accordance with the Automatic ed, installation is accomplished 1/2 or 3/4 Sprinkler Systems Handbook. by inserting the correct fastener 24 Spare sprinklers As per the 1989 Edition the in each of the two holes inside 36 Spare sprinklers correct number of spare the cabinet, securing the cabinet sprinkler is as follows: securely to the wall. The insert the correct number and type of "0-300 sprinklers, not less than 6 sprinklers in accordance with the 300-1000, not less than 12 "handbook". 1000 or more, not less than 24. *Final determination is subject to approval Stock of spare sprinklers shall by the AHJ. include all types and ratings installed."* 1111 FPPr Fire Protection Products, Inc 6241 Yarrow Dr.,Suite A,Carlsbad,CA 92011-1541 ©2000-2007 Fire Protection Products,Inc(FPPI) For questions: 1 800 344-1822.1 800 344-3775 fax•www.fppi.com • P POTTER BELLS The Symbol of Protection PBA-AC &MBA-DC UL,ULC,and FM Approved Sizes Available: 6"(150mm),8"(200mm)and 10"(250mm) Voltages Available: 24VAC 120VAC 12VDC(10.2 to 15.6)Polarized 24VDC(20.4 to 31.2)Polarized Service Use: Fire Alarm General Signaling Burglar Alarm Environment: Indoor or outdoor use(See Note 1) -40°to 150°F(-40°to 66°C) (Outdoor use requires weatherproof backbox.) ® Termination: AC Bells-4 No. 18 AWG stranded wires DC Bells-Terminal strip Finish: Red powder coating Optional: Model BBK-1 weatherproof backbox Model BBX-1 deep weatherproof backbox These vibrating type bells are designed for use as fire,burglar or general Notes: signaling devices. They have low power consumption and high decibel 1. Minimum dB ratings are calculated from integrated sound pressure ratings.The unit mounts on a standard 4"(101mm)square electrical box measurements made at Underwriters Laboratories as specified in UL for indoor use or on a model BBK-1 weatherproof backbox or BBX-1 Standard 464. UL temperature range is-30°to 150°F(-34°to 66°C). deep weatherproof backbox for outdoor applications. Weatherproof 2. Typical dB ratings are calculated from measurements made with a backbox model BBK-1,Stock No. 1500001. conventional sound level meter and are indicative of output levels in an actual installation. 3. ULC only applies to MBA DC bells. Size inches Voltage Model Stock Current Typical dB at Minimum dB at (mm) Number Number (Max.) 10 ft.(3m)(2) 10 ft.(3m)(1) 6(150) 12VDC MBA-6-12 1750070 .12A 85 76 8(200) 12VDC MBA-8-12 1750080 .12A 90 77 10(250) 12VDC MBA-10-12 1750060 .12A 92 78 6(150) 24VDC MBA-6-24 1750100 .06A 87 77 8(200) 24VDC MBA-8-24 1750110 .06A 91 79 10(250) 24VDC MBA-10-24 1750090 .06A 94 80 6(150) 24VAC PBA246 1806024* .17A 91 78 8(200) 24VAC PBA248 1808024* .17A 94 77 10(250) 24VAC PBA2410 1810024* .17A 94 78 6(150) 120VAC PBA1206 1806120* .05A 92 83 8(200) 120VAC PBA1208 1808120* .05A 99 84 10(250) 120VAC PBA12010 1810120* .05A 99 86 All DC bells are polarized and have built-in transient protection. *Does not have ULC listing. O. z In outdoor or wet installations,bell must be mounted with weatherproof backbox,BBK-1 or BBX-1.Standard electrical boxes will not provide a weatherproof enclosure.If the bell and/or assembly is exposed to moisture,it may fail or create an electrical hazard. Potter Electric Signal Company, LLC • St. Louis, MO, • Phone: 866-572-3005/Canada 888-882-1833 • www.pottersignal.com PRINTED IN USA MFG.#5400776-REV Y-1 PAGE 1 OF 2 01/13 ES-A-I n Bu ilding Riser For Fire Protection Applications Job Name Contractor Job Location Approval Engineer Contractor's P.O. No. Approval Representative LEAD FREE* Series IBR In-Building Risers Customizable Sizes: 4"-10" (100-250mm) Building Floor Building perimeter wall QSA ' ��p 9r O P` .1 x 1 c NV TC 'r w ■■■S. C 6'x6'standard length d' --- (custom lengths from 3'-20'available) • ar;c�:or t — Flow Features Series IBR In-Building Risers are used to connect the main fire supply to the building overhead fire system.The fitting passes under the foundation without joints and ex- •Cost savings tends up through the floor. Provided with installation tabs,the unit has a CIPS(Cast •Corrosion resistant stainless steel Iron Pipe Size)coupler for easy connection to the underground supply(AWWA C900 construction,type 304 PVC and Ductile Iron Pipe)and industry standard grooved-end connection(AWWA •Ease of installation and light weight allows C606)on the building side for easy connection to the overhead fire sprinkler system. one person to position and handle the riser The IBR features Lead Free*construction to comply with Lead Free*installation requirements. •Minimal site preparation;joint restraint one Ames In-Building Risers are precision engineered and manufactured to provide piece construction reduces time and labor; no missing parts, no leaks; easily identifiable exceptional reliability and reduce installation time&labor costs associated with field for approvals assembly. In accordance with NFPA 24,the UUFM approved In-Building Risers replace numerous fittings,elbows&spools and reduces the possibility of leaks or •Includes Test Cap and Coupler failure in comparison to traditional installation methods and materials. Factorytested •UUFM approved integrity ensures the highest quality installation.The use of stainless steel significantly •Sizes:available in 4"-10" (100-250mm) increases the reliability and life of the riser. with various lengths to meet local require- ments *The wetted surface of this product contacted by consumable water contains less •Designed to meet NFPA 24 than 0.25%of lead by weight. •AWWA C900 Inlet/DIP •AWWA C606 Outlet Ames Fire&Waterworks product specifications in U.S.customary units and metric are approximateand are provided for reference only.For precise measure- ments,please contact Ames Fire&Waterworks Technical Service.Ames Fre&Waterworks reserves the right to change or modify product design,consbuction, specifications,or materials without prior notice and without incuning any obligation to make such changes and modifications on Ames Fre&Waterworks products A M E S previously or subsequently sold. FIRE&WATERWORKS Specifications Standards In-Building Riser shall be installed as indicated on the plans. NFPA— Designed to allow the contractor to conform to NFPA Riser shall be composed of a single extended 90 degree fitting 24 of fabricated 304 stainless steel tubing, maximum working Where a riser is close to building foundations, underground pressure 200psi(14 bar).The fitting shall have a grooved-end fittings of proper design and type shall be used to avoid pipe joints connection on the outlet(building)side and a CIPS coupler on being located under the foundations. the inlet(underground)side.The grooved end shall include a coupler and cap to facilitate testing of the underground pip End Connections ing.The In-Building Riser shall be an Ames Fire&Waterworks Series IBR. Horizontal End:Mates with Ductile Iron Pipe and AWWA 0900 Pipe(PVC Pipe with Ductile Iron Pipe Equivalent OD's) Utilizes Gasket conforming to UL 157 with"Lock in" gasket configuration Approvals Fittings FM class 1920 SIZE(DN) MATING PIPE OD UL HKQA(4"-10") in. mm in. mm ® 4 100 4.8 122 6 150 6.9 175 8 200 9.1 230 10 250 11.1 282 Dimensions-Weights A I Vertical End: Lim Meets AWWA C-606 dimensions for roll grooved pipe Grooved End Meets AWWA C-207 class D for flanges (Flange Optional) Ratings Meets AWWA C-900 pressure class 200, DR 14 Pipe B Testing Welds are 100%leak tested at the factory CIPS Coupling Tie Rod Bracket % ---— -- SIZE DESIGN PROOF PRESSURE in. mm psi bar 4 100 1000 70 14 C 01 6 150 1000 70 8 200 800 56 10 250 800 56 SIZE(DN) WEIGHT A(OD) B G in. mm in. mm ft cm ft cm lbs. kg NOTICE 4 100 41/2 114 6 183 6 183 71 32 Inquire with governing authorities for local installation 6 150 65/e 168 6 183 6 183 98 44 requirements 8 200 85/s 219 6 183 6 183 129 59 10 250 103/4 273 6 183 6 183 202 92 **Each B(vertical)and C(horizontal)leg is customizable from 3'to 20'with UUFM NOTICE approvals.Consult with your factory representative for details. The information contained herein is not intended to replace the full product installation and safety information available or the experience of a trained product installer.You are required to thoroughly read all installation instructions and product safety information before beginning the installation of this product. AMES FIRE&WATERWORKS A Watts Water Technologies Company USA:Backflow Tel:(978)689-6066•Fax:(978)975-8350•AmesFireWater.com USA:Control Valves Tel:(713)943-0688•Fax:(713)944-9445•AmesFireWater.com Canada: Tel:(905)332-4090•Fax:(905)332-7068•AmesFireWater.ca Latin America: Tel:(52)81-1001-8600•Fax:(52)81-8000-7091 •AmesFireWater.com ES-A-InBuildingRiser 1540 ©2015 Ames Fire&Waterworks • . , P POTTER BELLS e The Symbol of Protection PBA-AC &MBA-DC Bells Dimensions Inches(mm) Wiring(rear view) Fig. 1 Fig.3 A.C.BELLS nil', [ ]), WH TE(MA11111WHITE(OUT) (250) 8" 1 —ct1—_ (200) FROM CONTROL rei6" PANEL CEDINGB (ISO) �7 PRECEDING BELL �' --77, _ BLACK(IN) BLACK(OUT) ��r-- SII CAUTION: 2 11/I6" WHEN ELECTRICAL SUPERVISION IS REQUIRED USE IN AND OUT LEADS AS SHOWN. (68) DWGM 7761 NOTES: 1.WHEN USING AC BELLS,TERMINATE EACH EXTRA WIRE SEPARATELY AFTER LAST BELL. 2.END-OF-LINE RESISTOR IS NOT REQUIRED ON AC BELLS. DWOS 776-3 Weatherproof Backbox Dimensions Inches(mm) Fig.2 FACP ii Box has one threaded 1/2"conduit entrance --9-- il� 0 LiliiiiiuiiiiiiiPJ 53/4" O _ 33/8° s^ To Next (146) (86) (127) III Device or — — End-of-Lineesistr Ili i �_/ Resistor e 3 3/8" 1 5/8" (86) _I.j (41) -F 4 1/4" (108) Installation DWG/1776-2 1. The bell shall be installed in accordance with NFPA 13,72,or local AHJ.The top of the device shall be no less than 90"AFF and not less than 6"below the ceiling. .'IP, 2. Remove the gong. 3. Connect wiring(see Fig.3). 4. Mount bell mechanism to backbox(bell mechanism must be a mounted with the striker pointing down). OD / 5. Reinstall the gong(be sure that the gong positioning pin,in the mechanism housing,is in the hole in the gong). S�> 6. Test all bells for proper operation and observe that they can BBX-1 ti be heard where required(bells must be heard in all areas as designated by the authority having jurisdiction). Failure to install striker down will prevent bell from operating. PRINTED IN USA MFG.#5400776-REV Y-1 PAGE 2 OF 2 01/13 Product Information MLTs FS-ONE High Performance Intumescent w.fir. Firestop Sealant Product description • Intumescent(expands when exposed to fire)firestop sealant that helps protect combustible and non-combustible penetrations for up to 4 hours fire rating ' . `, Product features . �� ■ Smoke,gas and water resistant after material has cured = "° s. r. ■ Contains no halogen,solvents or asbestos e ■ High fire rating properties • Water based,easy to clean -- ■ Protects most typical firestop penetration applications rt ¢{ • Paintable cal Da#a .. �. ,, FSO E ' • Single component systems available Chemical basisWater-basedWater-based intumescent acrylic ■ Meets LEEDTm requirements for indoor environmental quality credit dispersion 4.1 Low Emitting Materials,Sealants and Adhesives and 4.2 Paints Color Red and Coatings Application temperature 40°F to 104°F(5°C to 40°C) Skin forming time Approx.20-30 min. Areas of application Curing time Approx.2 mm/3 days • Steel,copper and EMT pipes Movement capability Approx.5% • Insulated steel and copper pipes Expansion rate(unrestricted) Up to 3-5 times original volume • Cable bundles Temperature resistance(cured) -40°F to 212°F(-40°C to 100°C) • Closed or vented plastic pipes Surface burning characteristics Flame Spread:0 • HVAC penetrations (ASTM E 84-96) Smoke Development:5 Sound transmission classification 56(Relates to specific construction) For use with (ASTM E 90-99) • Concrete,masonry,drywall and wood floor assemblies Approvals ■ Wall and floor assemblies rated up to 4 hours •California State Fire Marshal- No.4485-1200:108 •City of New York-MEA 326-96-M Vol.IV Examples Tested in accordance with ■ Sealing around combustible pipe penetrations in fire rated •UL 1479 •ASTM E 814 •ASTM E 84 construction *At 73°F(23°C)and 50%relative humidity • Sealing around non-combustible penetrations in fire rated construction 4�FsQo FILL,VOID oR CAVITY MATERIAL +.r..* FOR USE IN THROUGH-PENETRATION FIRESTOP SYSTEMS ® *V$TEY CCYPATYf1E C USSEE UL FIRE RESISTANCE DIRECTORY APPROVED 66Y7 Installation instructions for FS-ONE Notice 4. Smoothing of firestop sealant:To complete the • On materials where oil,plasticizers or solvents may • Before handling,read Material Safety Data Sheet seal,tool immediately to give a smooth appearance. bleed i.e.impregnated wood,oil based seals,green and product label for safe usage and health Excess sealant,prior to curing,can be cleaned away or partially vulcanized rubber information. from adjacent surfaces and tools with water. • In any penetration other than those specifically • Instructions below are general guidelines—always 5. Leave completed seal undisturbed for 48 hours. described in this manual or the test reports refer to the applicable drawing in the UL Fire 6. For maintenance reasons,a penetration seal could Storage Resistance Directory or Hilti Firestop Systems Guide be permanently marked with an identification plate. for complete installation information Store only in fromthe original packaging in a locationb p In such a case,mark the identification plate and protected moisture at temperatures between Opening fasten it in a visible position next to the seal. 40°F(5°C)and 86°F(30°C) 1. Clean the opening.Surfaces to which FS-ONE will Not for use • Observe expiration date on the packag be applied should be cleaned of loose debris,dirt, • High movement expansion joints oil,moisture,frost and wax.Structures supporting • Underwater penetrating items must be installed in compliance with local building and electrical standards. Wr Application of firestop sealant -I 'r i, , .r 2. Install the prescribed backfilling material type and . , ........ , --. Q ! depth to obtain the desired rating(if required).Leave V Cie:sufficient depth for applying FS-ONE. 3. Application of firestop sealant:Apply FS-ONE to the 1.Clean opening. 2.Pack mineral wool. 3.Apply FS-ONE. 4.Smooth 5.Leave completed 6.Fasten identification (If required) FS-ONE. seal undisturbed for plate(f required). H required depth in order to obtain the desired fire rating. 48 hours. Make sure FS-ONE contacts all surfaces to provide maximum adhesion.For application of FS-ONE use a E ,standard caulking gun,foil pack gun,bulk loader and111bulk gun.With FS-ONE buckets,Graco type sealantt*lpumps may be used.(Contact pump manufacturer for IE.EiII proper selection). ; 1.Clean opening. 2.Pack mineral wool. 3.Apply FS-ONE. 4.Smooth 5.Leave completed 6.Fasten identlication (If required) FS-ONE. seal undisturbed for plate(if requirecfj. 48 hours. Hilti. Outperform. Outlast. Hilti,Inc.(U.S.)1-800-879-8000•www.us.hilti.com•en espanol 1-800-879-5000•Hilti Firestop Systems Guide a N Material S,ifoty D it,i'Thppt MSDS No.: 259 Revision No.: 010 Revision Date: 08/17/04 Page: 1 of 2 Product name: FS-ONE High Performance Intumescent Firestop Sealant Description: One-part acrylic-based sealant Supplier: Hilti,Inc. P.O.Box 21148,Tulsa,OK 74121 Emergency#(Chem-Trec.): 1 800 424 9300(USA,PR,Virgin Islands,Canada);001 703 527 3887(other countries) INGREDIENTS AND EXPOSURE LIMITS Ingredients: CAS Number: PEL: TLV: STEL: Polyacrylate dispersion Mixture NE NE NE Calcium carbonate 001317-65-3 5 mg/ma(1) 10 mg/ma(T) NE Zinc borate 138265-88-0 NE NE NE Ammonium polyphosphate 068333-79-9 NE NE NE Talc 014807-96-6 20 mppcf 2 mg/ma NE Expandable graphite 012777-87-6 5 mg/ma m 2 mg/ma M NE Ethylene glycol 000107-21-1 NE C:100 mg/ma(A) NE Polybutene 009003-29-6 NE NE NE Iron oxide 001309-37-1 10 mg/ma 5 mg/ma NE Glass filament 065997-17-3 NE 5 mg/m3(T) NE Silicon dioxide 014808-60-7 0.05 mg/ma(1) 0.1 mg/m3(T) NE Water 007732-18-5 NE NE NE Abbreviations: PEL=OSHA Permissible Exposure Limit TLV=ACGIH Threshold Limit Value. C=Ceiling. STEL=Short Term Exposure Limit. NE=None Established. NA=Not Applicable. (T) indicates"as total dust". (A)indicates"as respirable fraction". (A)indicates"as an aerosol". mppcf=million particles per cubic foot. PHYSICAL DATA Appearance: Red paste. Odor: Odorless. Vapor Density: (air=1) Not determined. Vapor Pressure: 23mbar 0 20C/68F Boiling Point: Not applicable. VOC Content: 75.0 g/L. Evaporation Rate: Not applicable. Solubility in Water: Soluble. Specific Gravity: 1.5 pH: Not determined. FIRE AND EXPLOSION HAZARD DATA Flash Point: Non-flammable. Flammable Umits: Not applicable. Extinguishing Media: Not applicable. Use extinguishing media as appropriate for surrounding fire. Special Fire Fighting Procedures: None known.Use a self-contained breathing apparatus when fighting fires involving chemicals. Unusual Fire and Explosion Hazards: None known. Thermal decomposition products can be formed such as oxides of carbon, sulfur and phosphorous. REACTIVITY DATA Stability: Stable. Hazardous Polymerization: Will not occur. Incompatibility: Strong acids, peroxides,and oxidizing agents. Decomposition Products: Thermal decomposition can yield CO and CO2. Conditions to Avoid: None known. HEALTH HAZARD DATA Known Hazards: None known. Signs and Symptoms of Exposure: Possibly irritating upon contact with the eyes or upon repeated contact with the skin. Medical Conditions Eye and skin conditions. Aggravated by Exposure: Routes of Exposure: Dermal. p Hilti Firestop 9 ..., Saving Lives 111. through innovation L and education Hilti. Outperform. Outlast. Hill,, Inc (115.)1-800-879-8000•www.us.hilti.con•en espanol 1-800-879-5000•HMI(Canada)Corp,1-800-383-4458 www.hiltLca M ,t,11a1 Safety Lata Sheet MSDS No.: 259 Revision No.: 010 Revision Date: 08/17/04 Page: 2 of 2 Carcinogenicity: IARC classifies crystalline silica(quartz sand)as Group I based upon evidence among workers in industries where there has been long-term and chronic exposure(via inhalation)to silica dust;e.g.mining,quarry,stone crushing,refractory brick and pottery workers. This product does not pose a dust hazard;therefore,this classification is not relevant. Based upon the nature and intended use of this product,it does not pose an increased cancer risk to workers. EMERGENCY AND FIRST AID PROCEDURES Eyes: Immediately flush with plenty of water. Call a physician if symptoms occur. Skin: immediately wipe off material and wash with soap and water. Material can adhere to the skin. If material has adhered to the skin,use an abrasive containing hand cleaner. If material does not come off,buff with a pumice stone. Inhalation: Move victim to fresh air if discomfort develops. Call a physician if symptoms persist. ingestion: Seek medical attention. Do not induce vomiting unless directed by a physician.If a large quantity was ingested,give 1 to 2 glasses of water to dilute. Never give anything by mouth to an unconscious person. Other: Referral to a physician is recommended if there is any question about the seriousness of the injury/exposure. CONTROL MEASURES AND PERSONAL PROTECTIVE EQUIPMENT Ventilation: General(natural or mechanically induced fresh air movements). Eye Protection: Not required,however,safety glasses should be worn in most industrial settings. Skin Protection: Avoid skin contact.Cloth gloves are suitable for hand protection. Respiratory Protection: None normally required. Where ventilation is inadequate to control vapors,use a NIOSH- approved respirator with organic vapor cartridges. Never enter a confined space without an appropriate air-supplied respirator. PRECAUTIONS FOR SAFE HANDLING AND USE Handling and Storing Precautions: Store in a cool,dry area preferably between 40o and 77o F. Keep from freezing. Do not store in direct sunlight. Avoid contact with the eyes or skin. Practice good hygiene;i.e. always wash thoroughly after handling and before eating or smoking. For industrial use only. Keep out of reach of children. Follow label/use instructions. Spill Procedures: Immediately wipe away spilled material before it hardens. Place in a container for proper disposal in accordance with all applicable local,state,or federal requirements. REGULATORY INFORMATION Hazard Communication: This MSDS has been prepared in accordance with the federal OSHA Hazard Communication Standard 29 CFR 1910.1200. HMIS Codes: Health 1, Flammability 0, Reactivity 0, PPE B DOT Shipping Name: Not regulated. IATA/ICAO Shipping Name: Not regulated. TSCA Inventory Status: Chemical components listed on TSCA inventory.SARA Title III,Section 313:This product contains<3%ethylene glycol(CAS 107-21-1)and<15%zinc borate(re:zinc compounds)which are subject to reporting under Section 313 of SARA Title III(40 CFR Part 372). EPA Waste Code(s): Not regulated by EPA as a hazardous waste. Waste Disposal Methods: Consult with regulatory agencies or your corporate personnel for disposal methods that comply with local,state,and federal safety,health and environmental regulations. CONTACTS Customer Service: 1 800 879 8000 Technical Service:1 800 879 8000 Health/Safety: 1 800 879 6000 Jerry Metcalf(x6704) Emergency# (Chem-Trec): 1 800 424 9300(USA,PR,Virgin Islands,Canada); 001 703 527 3887(other countries) The information and recommendations contained herein are based upon data believed to be correct;however,no guarantee or warranty of any kind expressed or implied is made with respect to the information provided. Hitti Firestop Saving roves ■ through innovation L and education HMI. Outperform. Outlast. Hitti,Inc,(U.S.1 1-800-879-8000•www.ts.hiltI.ccm•en espanol 1-800-879-5000•Hilo(Canada!Corp.1-800-363-445B w www.hlNLce • - h C ortitica of Cam jiance Certificate Number 20100512-R13240 Page 1 of 1 Report Reference 2010 May 12 Issue Date 2010 May 12 Underwriters 1181Um Laboratories Inc.. Issued to: Hilti, Inc • 54 S 122ND East AVe Tulsa,OK 74146 USA This is to certify that Fill, Void or Cavity Materials representative samplesof FS-ONE Have been investigated by Underwriters Laboratories Inc.®(UL)or any authorized licensee of UL in accordance with the Standard(s)indicated on this Certificate. Standard(s)for Safety: ANSI/UL 1479,ANSUUL 2079,CAN/ULC-5115-05 Third Edition,revised March 1,2010 • Additional Information: FS-ONE Sealant for use in Joint`Systems and FS-ONE for use in Through-Penetration Firestop Systems as currently described in the UL Fire Resistance Directory. Only those products bearing the UL Classification Mark should be considered as being covered by UL's Classification and Follow-Up Service. . The UL Classification Mark includes:UL in a circle symbol Itt with the word"CLASSWTED"(as shown);a control number (may be alphanumeric)assigned by UL;a statement to indicate the extent of UL s evaluation of the product,and,the product category name(product identity)as indicated in the appropriate;UL Directory • Look for the UL Classification Mark on the product - Issued L% e31F Co ° ,Reviewed -( 4L dOute . • •,J { ' t 4 .1 �. ..4".111c " . ' a 9 .. and to k UL Matt"stiiiteaarsp,u did F iii#t t tL 11. 3'': -a s do • • • ", y Certificate of Corn i fiance Certificate Number 20060214-R13240E Page 1 of 1 Report Reference 2006 February 14 Issue Date 2006 February 14 !Underwriters < Laboratories Inc..: Issued to: Hilti, Inc. 5400 S 122ND East Ave Tulsa,OK 74146 USA This is to cert fy that Fill, Void or Cavity Materials representative samples of FS_ONE Have been investigated by Underwriters Laboratories Inc.®in accordance with the Standard(s) indicated on this Certificate. Standard(s)for Safety: ANSI/UL 1479,ANSI/UL 2079,CAN/ULC-S 115-05 Additional Information: FS-ONE Sealant for use in Joint Systems and FS-ONE for use in Through- Penetration Firestop Systems as currently described in the UL Fire Resistance Directory. Only those products bearing the UL Classification Mark should be considered as being covered by UL's Classification and Follow-Up Service. The UL Classification Mark includes: UL in a circle symbol: 441 with the word "CLASSIFIED" (as shown); a control number (may be alphanumeric) assigned by UL; a statement to indicate the extent of UL's evaluation of the product;and,the product category name(product identity)as indicated in the appropriate UL Directory. Look for the UL Classification Mark on the product Issued by: Reviewed by: //,, iG .r A�ouloute Christopher 11 in Underwriters Laboratories Inc. Underwriters L...ratories Inc. 1101,11.:11', Hilti North America 5400 South 122nd East Avenue Tulsa,OK 74146 P.O.Box 21148 I Tulsa,OK 74121-1148 T 1-800-879-8000 I F 918-252-6742 www.hilti.com June 27, 2008 To Whom It May Concern: Re: Hilti FS-ONE Intumescent Firestop The Hilti FS-ONE Intumescent Firestop is manufactured in Kaufering, Germany. The FS-ONE pail is made of polyethylene and can be completely recycled. There is no post- consumer or post-industrial content in FS-ONE and it cannot be recycled. The VOC content for FS-ONE is 75 grams/liter. FS-ONE is not regulated as a hazardous waste by the Federal EPA Standards. The regulations for the disposal of non-regulated industrial waste can vary from state to state and even city to city. For this reason, you should consult your local and state regulatory agencies for direction on disposal. Please feel free to contact me at (918) 252-6704 if you have questions. Sincerely, Jerry Metcalf MPH, CHMM Safety/Environmental Manager Hilti Inc (918) 252 6704 ierrv.metcalf c(. hilti.com NOTES/DEFINITIONS: 1. Post-Consumer Recycled Content: Portion of material or product derived from discarded consumer waste that has been recovered for use as a raw material[e.g.,plastic bottles, newspaper] 2. Post Industrial Recycled Content: Portion of material or product derived from recovered industrial and mfg.materials that are diverted from municipal solid waste for use in a different mfg.process,prior to use by a consumer[e.g.,fly-ash in concrete or synthetic gypsum board,both of which are by-products of coal-burning power plants].Spills and scraps from the original manufacturing process that are combined with other constituents after a minimal amount of reprocessing for use in further production of the same product do not qualify. 3. Manufactured: Final assembly of components into building product that is furnished and installed by trades[e.g.,if the hardware comes from Dallas,TX,the lumber from Keene, NH,and the joist is assembled in Kent,WA;then the location of final assembly is Kent,WA]. www.upsvisualizer.com/calculators can be used to calculate straight-line distance between project site/New York,NY and location of manufacture and raw material source. Note:location noted on material data sheets is often corporate location;need manufacturer to verify actual manufacture location. 4. Raw Materials: Virgin or recovered resources from which the product's components are made[i.e.,before processing or manufacturing]. 5. Rapidly Renewable: Materials and products made from raw materials that are harvested within a 10-year cycle[e.g.,bamboo,cork,linoleum,fast-growing poplar,wheatboard,wool carpet]. 6. FSC Certified: Wood-based products that are certified by the Forest Stewardship Council and carry a Chain-of-Custody certificate number from the vendor or manufacturer. 7. VOC Content: The quantity of volatile organic compounds contained in products such as adhesives,sealants and architectural coatings.VOC content is to be reported in grams/liter or lbs/gallon,less water and any exempt compounds/solvents. CONTRACTOR CERTIFICATION: I, a duly authorized representative of hereby certify that the information contained herein accurately represents the listed"green building"characteristics of the material to be provided by our company as components of the building construction.Furthermore, I understand that any change in such"green building"material characteristics during the purchasing and/or installation period will require prior written approval from the Construction Manager and Owner. SIGNATURE OF AUTHORIZED REPRESENTATIVE: DATE: P. of MSDS No.: 259 11.41111..'"111"11 Revision No.: 010 Revision Date: 08/17/04 Page: 1 of 2 MATERIAL SAFETY DATA SHEET Product name: FS-ONE High Performance Intumescent Firestop Sealant Description: One-part acrylic-based sealant Supplier: Hilti, Inc. P.O.Box 21148,Tulsa,OK 74121 Emergency#(Chem-Trec.): 1 800 424 9300(USA, PR,Virgin Islands,Canada);001 703 527 3887(other countries) INGREDIENTS AND EXPOSURE LIMITS Polyacrylate dispersion Mixture NE NE NE Calcium carbonate 001317-65-3 5 mg/m3(T) 10 mg/m3(T) NE Zinc borate 138265-88-0 NE NE NE Ammonium polyphosphate 068333-79-9 NE NE NE Talc 014807-96-6 20 mppcf 2 mg/m3 NE Expandable graphite 012777-87-6 5 mg/m3(T) 2 mg/m3(T) NE Ethylene glycol 000107-21-1 NE C:100 mg/m3(A) NE Polybutene 009003-29-6 NE NE NE Iron oxide 001309-37-1 10 mg/m3 5 mg/m3 NE Glass filament 065997-17-3 NE 5 mg/m3(T) NE Silicon dioxide 014808-60-7 0.05 mg/m3(T) 0.1 mg/m3(T) NE Water 007732-18-5 NE NE NE Abbreviations: PEL=OSHA Permissible Exposure Limit. TLV=ACGIH Threshold Limit Value. C=Ceiling. STEL=Short Term Exposure Limit. NE=None Established. NA=Not Applicable. (T)indicates"as total dust". (R)indicates"as respirable fraction". (A) indicates"as an aerosol". mppcf=million particles per cubic foot. PHYSICAL DATA Appearance: ' Red paste. Odor: Odorless. Vapor Density: (air=1)" Not determined. Vapor Pressure: 23mbar @ 20C/68F Boiling Point: Not applicable. VQC Content 75.0 g/L. Evaporation Rate: Not applicable. Solubility in Water: Soluble. Specific Gravity: 1.5 pH; Not determined. FIRE AND EXPLOSION HAZARD.1'ATA Flash Point: Non-flammable. l=lammableLimits: Not applicable. Extinguishing Media: Not applicable. Use extinguishing media as appropriate for surrounding fire. Special Fire Fighting None known.Use a self-contained breathing apparatus when fighting fires involving chemicals. Procedures: Unusual Fire and Explosion None known. Thermal decomposition products can be formed such as oxides of carbon, sulfur Hazards: and phosphorous. REACTIVITY DATA Stability: Stable. ;Hazardous Polymerization: Will not occur. Incompatibility: Strong acids,peroxides,and oxidizing agents. Decomposition Products: Thermal decomposition can yield CO and CO2. Conditions to Avoid: .' None known. HEAL`11°HAZARD DATA Known Hazards: None known. Signs and Symptoms of Possibly irritating upon contact with the eyes or upon repeated contact with the skin. Exposure: Medical Conditions Eye and skin conditions. Aggravated by Exposure: Routes of Exposure: Dermal. HILTI®is a registered trademark of Hilti Corp. j Carcinogenicity: IARC classifies crystalline silica.,(qua rtz„..s,,„.a nd)as Group I based upon evidence among workers in industries where there has been long-term and chronic exposure (via inhalation)to silica dust; e.g. mining, quarry, stone crushing, refractory brick and pottery workers. This product does not pose a dust hazard; therefore, this classification is not relevant. Based upon the nature and intended use of this product,it oes not pose an increased cancer risk to workers. EMER NCY AND FIRST AID)i tOCEDUR $r lies: Immediately flush with plenty of water. Call a physician if symptoms occur. Sluri 3 Immediately wipe off material and wash with soap and water. Material can adhere to the skin. If material has adhered to the skin, use an abrasive containing hand cleaner. If material does not ▪ come off,buff with a pumice stone. in alation` , Move victim to fresh air if discomfort develops. Call a physician if symptoms persist. ingi stion: Seek medical attention. Do not induce vomiting unless directed by a physician. If a large quantity was ingested, give 1 to 2 glasses of water to dilute. Never give anything by mouth to an • unconscious person. Other, Referral to a physician is recommended if there is any question about the seriousness of the n ; injury/exposure ▪ ONTROI..MEASURES AND PERSONAL PROTECTIVE EQUIPMENT t Ventilation ' . General(natural or mechanically induced fresh air movements). Eye Protection: Not required,however,safety glasses should be worn in most industrial settings. Skin Prote On. Avoid skin contact.Cloth gloves are suitable for hand protection. Respiratory"Picatection None normally required. Where ventilation is inadequate to control vapors, use a NIOSH approved respirator with orsanic vapor cartridges. Never enter a confined space without an . appropriate air supplied respirator PRECAUTIONS:FOR SAI ANDLM1G AND USE ry r .� n ti x Handling and Storing Store in a cool,dry area preferably between 40°and 77°F. Keep from freezing. Do not store in Precautionsi direct sunlight. Avoid contact with the eyes or skin. Practice good hygiene; i.e. always wash thoroughly after handling and before eating or smoking. For industrial use only. Keep out of reach of children. Follow label/use instructions. Spill Procedures Immediately wipe away spilled material before it hardens. Place in a container for proper disposal = in accordance with all applicable local,state,or federal requirements. REGI 1TATORY INFORMATION: j" " hazard communication This MSDS has been prepared in accordance with the federal OSHA Hazard Communication Standard 29 CFR 1910.1200. HMISodes. : Health 1, Flammability 0, Reactivity 0, PPE B DOT:,aipping Name: Not regulated. IATA/ICAO Shipping Name: Not regulated. LSCA Inver ory Status". Chemical components listed on TSCA inventory. SARA Title on II;SectiThis product contains < 3% ethylene glycol (CAS 107-21-1) and <A1 5% zinc borate (re: zinc compounds) which are subject to reporting under Section 313 of SRA Title Ill (40 CFR Part 372). EPA Waste Codes Not regulated by EPA as a hazardous waste. waste}Disposal Methods Consult with regulatory agencies or your corporate personnel for disposal methods that comply with local,state,and federal safety,health and environmental regulations. f n w. CONTACTS Customer Ser ce 1 800 879 8000 Techr i 'Service: 1 800 879 8000 Heap 1 Safety• 1 800 879 6000 Jerry Metcalf (x6704) Emergency (Chem Tref): 1 800 424 9300(USA,P. Virgin Islands,Canada); 001 703 527 3887(other countries) The information and recommendations contained herein are based upon data believed to be correct; however, no guarantee or warranty of any kind expressed or implied is made with respect to the information provided. MSDS 259, Page 2 of 2 CALIFORNIA DEPARTMENT OF FORESTRY&FIRE PROTECTION !- ' OFFICE OF THE STATE FIRE MARSHAL CAL F RE FIRE ENGINEERING- BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 4485-1200:108 Page 1 of 1 CATEGORY: Opening Protection (Firestopping) LISTEE: Hilti, Inc., 5400 S. 122nd East Ave,Tulsa, OK 74146 Contact: *Clay Hensley(918)252-6216 Fax(918)254-1679 DESIGN: Model FS-ONE Firestop Sealant. Refer to listee's printed data sheet and UL Fire Resistance Directory for additional detailed product description and operational considerations. INSTALLATION: In accordance with listee's printed installation instructions, applicable codes&ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name,type identification and UL label. APPROVAL: Listed as firestop devices for use in through-penetration firestop system up to 3 hour rating. For indoor use only. Approved under Through-Penetration Fire Stop Systems: CAJ1155, CAJ2091, CAJ2118, CAJ3095, CAJ5044, CAJ8041, F-C-2025, WL1085, WL1056, WL3047, WL5029, WL8004. Refer to UL Fire Resistance Directory for detailed constructions. *Rev.06-20-2006 (4° � [ ( This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources. Date Issued: JUNE 10, 2008 Listing Expires June 30, 2009 Authorized By: BEN HO, Chief Fire Engineering Division Report of Materials and gBUILDINGS Equipment Acceptance Division NYC Department of Buildings 280 Broadway, New York, NY 10007 Patricia Lancaster, FAIA, Commissioner (212)566-5000,TTY: (212)566-4769 Pursuant to Administrative Code Section 27-131, the following equipment or material has been found acceptable for use subject to the terms and conditions contained herein. MEA 326-96-M Vol. 5 Manufacturer: Hilti, Inc., 5400 S. 122 East Avenue, Tulsa, OK 74146 Trade Name(s): Hilti, Inc. Product: Fill,void or cavity material for fire protection Pertinent Code Section(s): 27-345 Prescribed Test(s): RS 5-19 (ASTM E814), UL 2079 Laboratory: Underwriters Laboratories, Inc. Test Report(s): File R13240, dated July 16, 1993, July 21, 1993, July 13, 1993, July 22, 1993, April 1, 1993, March 25, 1994, March 3 and 6, 1995, September 4, 1996, September 27,1997; File R13644, dated April 12, 1993 and May 3, 1993; File R12232, dated August 2, 1993; UL-design listings. Description: Fill, void or cavity material for through-penetrations in fire-rated wall and/or floor/ceiling construction. The Hilti FS-ONE Firestop Sealant shall be applied in accordance with Underwriters Laboratories `Inc.'system numbers, listed on following pages, in achieving the required fire-resistance ratings. MEA 326-96-M Vol. 5 Page 1 of 10