Report (10) Po'rr� VANE TYPE WATERFLOW VS R �- 6 The Symbol of Protection ALARM SWITCH WITH RETARD Installation (see Fig. 1) These devices may be mounted on horizontal or vertical pipe. On horizontal pipe they shall be installed on the top side of the pipe where they will be accessible. The device should not be installed within 6"(15 cm)of a fitting which changes the direction of the waterflow or within 24" (60 cm)of a valve or drain. NOTE:Do not leave cover off for an extended period of time. Drain the system and drill a hole in the pipe using a hole saw in a slow speed drill(see Fig. 1). Clean the inside pipe of all growth or other material for a distance equal to the pipe diameter on either side of the hole.Roll the vane so that it may be inserted into the hole; do not bend or crease it.Insert the vane so that the arrow on the saddle points in the direction of the waterflow.Take care not to damage the non-corrosive bushing in the saddle.The bushing should fit inside the hole in the pipe.Install the saddle strap and tighten nuts alternately to required torque (see the chart in Fig. 1).The vane must not rub the inside of the pipe or bind in any way. A CAUTION r Do not trim the paddle.Failure to follow these instructions may prevent the device from operating and will void the warranty. Fig.1 Retard Adjustment DO NOT LEAVE COVER OFF FOR \'�� ANEXTENDED PERIOD OF The delay can be adjusted by rotating the retard adjustment knob from 11 0 to the max setting(60-90 seconds).The time delay should be set at ...-111,11....0.1.0....;.,.4,14%41,.. ` the minimum required to prevent false alarms llk 1. 1\0 4� ' TIGHTEN NUTS _. _ _ ... \,`J I�1� ALTERNATELY ��;;�j�' chew/ CAUTIO ,.�► ' Hole must be drilled perpendicular to the pipe and vertically centered. , /` Refer to the Compatible Pipe/Installation Requirements chart for size. Correct Incorrect /, MOUNT ON PIPE SO 1111140 ARROW ON SADDLE `J �-I POINTS IN DIRECTION --( ) O-4.00001! OF WATERFLOW 11 /v/ (3 ÷ .., _ 0 Ii 111=111 ROLL PADDLE IN 50mm kr V/ OPPOSITE DIRECTION ADAPTER \\ //fI ADAPTER DIRECTION OF OF WATERFLOW \\\ / WATERFLOW I W 20mm±2mm MAX. (Flowing water activates device in one direction only.) DN50 ONLY '4......) USE(2)5180162 ADAPTERS AS SHOWN ABOVE DWG.D46-11 DWG#114E-1F Compatible Pipe/Installation Requirements Model Nominal Pipe Nominal Pipe Pipe Wall Thickness Hole Size U-Bolt Nuts Size O.D. Schedule 10(UL) Schedule 40(UL) BS-1387(LPC) DN(VDS) Torque inch mm inch mm inch mm inch mm inch mm inch mm inch mm ft-lb n-m VSR-2 2 DN50 2.375 60.3 0.109 2.77 0.154 3.91 0.142 3.6 0.091 2.3 VSR-2 1/2 2.5 - 2.875 73.0 0.120 3.05 0.203 5.16 - - - - 1.25+.1251-.062 33.0±2.0 . VSR-2 1/2 - DN65 3.000 76.1 - - - - 0.142 3.6 0.102 2.6 VSR-3 3 DN80 3.500 88.9 0.120 3.05 0.216 5.49 0.157 4.0 0.114 2.9 VSR-3 1/2 3.5 - 4.000 101.6 0.120 3.05 0.226 5.74 - - - - 20 27 • VSR-4 4 DN100 4.500 114.3 0.120 3.05 0.237 6.02 0.177 4.5 0.126 3.2 2.00±.125 50.8±2.0 . VSR-5 5 - 5.563 141.3 0.134 3.40 0.258 6.55 - - - - VSR-6 6 DN150 6.625 168.3 0.134 3.40 0.280 7.11 0.197 5.0 0.157 4.0 VSR-8 8 DN200 8.625 219.1 0.148 3.76 0.322 8.18 0.248 6.3 0.177 4.5 NOTE:For copper or plastic pipe use Model VSR-CF. PRINTED IN USA MFG.#5401146-REV L PAGE 2 OF 4 3/09 VSR. P j3fffJ? VANE TYPE WATERFLOW The Symbol of Protection ALARM SWITCH WITH RETARD Fig.2 Fig.3 Fig.4 Switch Terminal Connections Clamping To remove knockouts:Place screwdriver at Break out thin section of cover when Plate Terminal, inside edge of knockouts,not in the center. wiring both switches from one conduit 111 entrance. 1i, At i 0 tic° �/`i ,%, ,A, I �/ DO owe 11,48-15 lit � , ,/� An uninsulated section of a single conductor should not be looped %WV ��g' <-f'igal J' I1� around the terminal and serve as two separate connections. The wire must be severed,thereby providing supervision of the \ , l` connection in the event that the wire become dislodged from under NOTICE \ /, the terminal. Failure to sever the wire may render the device Do not drill into the base as this creates /`.!/i1 OWE.1146-13 inoperable risking severe property damage and loss of life. metal shavings which can create �. Do not strip wire beyond 3/8"of length or expose an uninsulated electrical hazards and damage the P> \\ � conductor beyond the edge of the terminal block.When using device.Drilling voids the warranty. stranded wire,capture all strands under the clamping plate. Fig.5 Typical Electrical Connections , BEL -gal f Notes: ®� +2 I +, li POWER SOURCE 1. The Model VSR has two switches,one can be used to operate a central - g- �-` SUITABLE FOR BELL station,proprietary or remote signaling unit,while the other contact = I-1 is used to operate a local audible or visual annunciator. I' Ammo _..ii i., �..-u 2. A condition of LPC Approval of this• product is that the electrical 1- . . • entry must be sealed to exclude moisture. _ N. p '! 1\ I ! WATERFLOW ZONE 3. For supervised circuits,see"Switch Terminal Connections" _ .4 6�4 t+ ll EOLR ON FIRE PANEL drawing and warning note(Fig.4). 44101 ,• +, I CMG.114[42 Testing The frequency of inspection and testing for the Model VSR and its associated protective monitoring system shall be in accordance with applicable NFPA Codes and Standards and/or the authority having jurisdiction(manufacturer recommends quarterly or more frequently). If provided,the inspector's test valve shall always be used for test purposes.If there are no provisions for testing the operation of the flow detection device on the system,application of the VSR is not recommended or advisable. A minimum flow of 10 GPM(38 LPM)is required to activate this device. NOTICE Advise the person responsible for testing of the fire protection system that this system must be tested in accordance with the testing instructions. Fig.7 Mounting Dimensions 5.56 in Fig 8 3.50 in (141.2 mm) (89.0 mm) 2.00 in GREEN GROUND (50.8 mm) A SCREWS (2.34 i!)111111 '������ A. rI:Iri1I U-BOLT NUT PPEDIA. MP +5.25inU-BOLT WASHER mA \/■I (+133.4mm) �I■lPIPE SADDLE , I ■\O `PIPE1N �'�( � i TPLASTIC PADDLE all °w I "u Ivi I Q U-BOLT NOMINAL PIPE DIA.+1.75 in(+44.5 MM)FOR DN 50--DN 65 2-2.5 in -��••• 2W0 wale NOMINAL PIPE DIA.+2.125 in(+54.0 MM)FOR DN 80-DN 200 3-8 in PRINTED IN USA MFG.#5401146-REV L PAGE 3 OF 4 3/09 1 VSR • VANE TYPE WATERFLOW The Symbol of Protection ALARM SWITCH WITH RETARD • Maintenance Inspect detectors monthly. If leaks are found,replace the detector. The VSR waterflow switch should provide years of trouble-free service. The retard and switch assembly are easily field replaceable.In the unlikely event that either component does not perform properly,please order replacement retard switch assembly stock#1029030(see Fig.6).There is no maintenance required,only periodic testing and inspection. Retard/Switch Assembly Replacement(See Fig.6) NOTICE The Retard/Switch Assembly is field-replaceable without draining the system or removing the waterflow switch from the pipe I. Make sure the fire alarm zone or circuit connected to the waterflow switch is bypassed or otherwise taken out of service. 2. Disconnect the power source for local bell(if applicable). 3. Identify and remove all wires from the waterflow switch. 4. Remove the(2)mounting screws holding retard/switch assembly to the base.Do not remove the(2)retard housing screws. 5. Remove the retard assembly by lifting it straight up over the tripstem. 6. Install the new retard assembly.Make sure the locating pins on the retard/switch assembly fit into the locating pin bosses on the base. 7. Re-install the(2)original mounting screws. 8. Reconnect all wires.Perform a flow test and place the system back in service. Fig,6 REMOVE(2)ORIGINAL MOUNTING SCREWS HOLDING RETARD/SWITCH ASSEMBLY TO BASE BREAKOUTTHIN SECTIONOF COVER WHEN WIRING BOTH SWITCHES FROM ONE CONDUIT ENTRANCE. (2)ORIGINAL MOUNTING ICREWS IRETARD/SWITCH ASSEMBLY 4:01111111,7121 1���. ' \ / -/1 1 II � 1 r �IF ,�_!-- 1 �.. rid i (2)LOCATING PINS I Ill (2)LOCATING PIN I ' DO NOT REMOVE I '1 BOSSES IN BASE (2)RETARD HOUSING I ",j I I,. SCREWS ,�H � _ -117M td l T f�!I ' 14BASE .■. vans!co II o No DWG#1146-10 Removal of Waterflow Switch • To prevent accidental water damage,all control valves should be shut tight and the system completely drained before waterflow detectors are removed or replaced. • Turn off electrical power to the detector,then disconnect wiring. • Loosen nuts and remove U-bolts. • Gently lift the saddle far enough to get your fingers under it. With your fingers,roll the vane so it will fit through the hole while continuing to lift the waterflow detector saddle. • Lift detector clear of pipe. PRINTED IN USA MFG.#5401146-REV L PAGE 4 OF 4 3/09 t 1 APPROVALS PIPE HANGER -:‘:', SAMMYS® FOR WOOD Pipe Hanger • 1) Rod Mount (IL Max UL Test UL Min Wood FM Max FM Test FM Min Wood art Na. Mod& Size Direction Pipe Size Load(lbs) Thickness Pipe Size Load(lbs) Thickness 8007957 GST 10 3/8" Vertical CPVC 1-1/2" 300 1-1/2" 8020957 SWG 10 3/8" Horizontal CPVC 1-1/2" 300 1-1/2" 8008957 GST 20 3/8" Vertical 2-1/2" 850 1-1/2' 4' 1475 1-1/2" 8068925 GST 20-SS 3/8" Vertical 2-1/2" 850 1-1/2" 8010957 GST 30 3/8' Vertical 4" 1500 1-1/2" 4" 1475 1-1/2' 8009925 GST 25-380 3/8" Vertical 4° 1500 1-1/2" 8022925 SWG 25-380 3/8" Horizontal 3-1/2"-4"* 1500 . 1-1/2" -. 8021957 SWG 20 3/8" Horizontal 2-1/2"-3"** 1050 1-1/2" 8073925 SWG 20-SS 3/8" Horizontal 2-1/2" 850 1-1/2" 8139957 SH-GST 20 3/8" 17*Angle off Vertical 3" 1050 1-1/2" 4" 1475 1-1/2" 8141957 SH-GST 30 3/8" 17°Angle off Vertical 4° 1500 1-1/2" 4" 1475 1-1/2" SAMMYS'') FOR STEEL Pipe Hanger ,440t.No,,,, , Model '1,! ,..4:" ,;:t4:47, ,..-.!-• ,',.P.,, -,,? ,t- , 4:';',' "9''' ' , ',P, l'i","," , '' " '''',g,;'"/ ' '4" •:',..5-- ' ' —,-,',...,,,:;:' " 8038957 DSTR 1 3/8' Vertical 4" 1500 , .035" 4' 1475 .105" 8037957 DSTR 1-1/2 3/8" Vertical 4" 1500 .035" 4" 1475 .105" 8039957 DSTR 516 3/8" Vertical 4' 1500 , .037" 4' 1475 .105" 8045957 DST 516 3/8" Vertical 4" 1500 .188" 4" 1475 .188" 8046957 TEK 50 3/8" Vertical 4" 1500 .250" 4" 1475 .188" 8055957 SWDR 1 3/8" Horizontal 4" 1500 .037" 4" 1475 .060" ' 8056957 SWOR 516 '3/8" Horizontal 4" 1500 , .037' 4" 1475 .060" - 8054957 SWDR 1-1/2 3/8" Horizontal 4" 1500 .037" 4" 1475 .060" 8137957 SH-DSTR 1 3/8" 17"Angle off Vertical 4" 1500 .035" 4" ', 1475 .105" 2" 940 .029" 8150922 XP 20 3/8" Vertical 2-1/2" 850 .027" 4" 1475 .105" 8153922 XP 35 3(8" Vertical 3-1/2" 1250 .060" 4" 1475 105" • , 8294922 SXP 20 3/8" Vertical or up to 45° 2" 750 .027° 2" 635 .029" 8295922 SXP 35 3/8" Vertical or up to 89' 3-1/2' 1250 .060" 2" 635 .029" . , 8293957 SWXP 35 3/8" Horizontal 3-1/2" 1250 .060" Pipe Hanger 8059957 CST 20 3/8" Vertical ' 4' 1475 3000 ' 8061957 SWC 20 3/8" Horizontal 4" 1475 3000 8150922 XP 20 3/8" Vertical 2-1/2" 850 Pre-Pour Structural @3000psi ... „ 8150922 XP 20 3/8" Vertical 2-1/2" 850 Post-Pour Range II LWC 5 35 PCF(lbs/ft3) TRUSS-T HANGER® Pipe Hanger Rod Mount UL Load UL Test Part No. Model Listed Application Size Direction Rating (lbs) Load(lbs) 8296900 HD38TC 3/8" Top Chord 1200 6075 Maximum 4"Schedule 40 pipe 8297900 HD38BC 3/8" Bottom Chord 1200 6075 Maximum 4"Schedule 40 pipe 8198900 HD12CZP 1/2" Bottom aord * 1200 6075 Maximum 8"Schedule 40 Pipe 8298900 HD12TC 1/2" Top Chord 1200 6075 Maximum 8"Schedule 40 Pipe 8299900 HD12BC 1/2" Bottom Chord 1200 6075 ,Maximum 8"Schedule 40 Pipe ' .. *SWG 25-380 Maximum pipe size in composite wood joist allowed by UL is 3-1/2" UL compliance with NEC Standards. 'SWG 25-380 Maximum pipe size in wood timber or joist allowed by UL is 4" UL and FM tests were performed in compliance with NFPA 13 Standards. ""SWG 20 Maximum pipe size in composite wood joist allowed by UL is 2-1/2" Fastening requirement:5 times weight of water-filled schedule 40 pipe plus 250 pounds. ""SWG 20 Maximum pipe size in wood timber or joist allowed by UL is 3" Os 4> ' - LISTED PPE HANGER ALSO LISTED AS CONDUIT'AND CABLE HARDWARE APPROVED ALSO LISTED AS ANCHOR FOR LUMPARE RV For the most up to date information,visit www.sammysuperscrew.com 14 LUMINAIRE, CONDUIT, TUBING, & CABLE APPROVALS SAMMYS''' FOR STEEL Luminaire Fitting SteelrY 185 .027" 8150922 XP 20 3/8" Vertical ' 250 .035' 185 .027" 8153922 XP 35 3/8" Vertical 250 .035" 185 .027' 8181922 XP 200 1/4" Vertical 250 ,035" .027" 8294922 SXP 20 3/8" Vertical 170 45° 80 .027" 8295922 SXP 35 3/8' Vertical 250 .060" 90° 80 .060" 8293957 SWXP 35 3/8" Horizontal 80 .060" TRUSS-T HANGER® Luminaire Fitting Rod Mount UL Load UL Test Part No. Model Listed Application Size Direction Rating (lbs) Load(lbs) 8296900 H038TC 3/8" Top Chord 1200 6075 Overhead Lighting&Luminaire Fittings 8297900 HD38BC 3/8" Bottom Chord 1200 6075 Overhead Lighting&Luminaire Fittings 8198900 HD12CZP yr Bottom Chord 1200 6075 Overhead Lighting&Luminaire Fittings 8298900 HD12TC 1/2" Top Chord 1200 6075 Overhead Lighting&Luminaire Fittings 8299900 HD12BC 1/2" Bottom Chord 1200 607$ Overhead Lighting&Luminaire Fittings SAMPAYS" FOR STEEL Conduit,Tubing,and Cable - „,- - , - 8150922 XP 20 3/8" Vertical 283 .027" Max 4 trade size EMT.RMC,and IMC&5 trade size rigid PVC conduit - 8153922 XP 35 3/8' Vertical 500 .060° Max 4 trade size EMT&6 trade sze RMC,IMC,and rigid PVC conduit 8294922 SXP 20 3/8" Vertical 283 .027" Max 4 trade size EMT,RMC,and IMC&5 trade size rigid PVC conduit 8295922 SXP 35 3/8" Vertical 500 .060" Max 4 trade size EMT&6 trade sze RMC,IMC,and rigid PVC conduit 8293957 SWXP 35 3/8" Horizontal 500 .060" Max 4 trade size EMT&6 trade sze RMC,IMC,and rigid PVC conduit Sheet Steel Sizes ," Gauge No. 22 ga. 20 ga. 18 ga. 16 ga. 14 ga. 12 ga. 3/16" 1/4" Nominal Decimal Equivalent .030" .036" .048" .060" .075" .105° .188" .250" TRUSS-T HANGER" Conduit,Tubing, and Cable Rod Mount UL Load UL Test Part No. Model Listed Application Size Direction Rating (lbs) Load(ibs) 8296900 HD38TC 3/8' Top Chord 1200 6075 Up to 6"Trade Size EMT,IMC,and Rigid PVC conduit 8297900 HD38BC 3/8" Bottom Chord 1200 6075 Up to 6"Trade Size EMT,IMC,and Rigid PVC conduit 8198900 HDI2CZP 1/2" Bottom Chord 1200 6075 Up to 6"-Trade Size EMT,IMC,and Rigid PVC conduit 8298900 HD12TC 1/2° Top Chord 1200 6075 Up to 6"Trade Size EMT,IMC,and Rigid PVC conduit 8299900 FID12BC 1/2" Bottom Chord 1200 6075 Up to 6"Trade Size EMT,IMC,and Rigid PVC conduit UL compliance with NEC Standards. • • (1) s LISTED PPE HANGER ALSO LISTED AS CONDUIT AND CABLE HARDWARE APPROVED ALSO LISTED AS ANCHOR FOR LUMINAIRE ma 15 To find a distributor near you,call 800-BUILDEX Model 1011 T AN G T E T DRAIN FSectional Floor Control Test and Drain Valve for Systems Requiring Pressure Relief Valve and Pressure Gauge Assembly C3%" 1" 11/11 11/2" 2" •The AGF Manufacturing Inc. Model = , 1011T TESTANDRAIN®matches all the features and benefits of our ,);;fi,, Model 1000 byprovidingboth the i`` �.=` "s' test function and the express drain ft • _ { function in a multistory installation *' "; , for a wet fire sprinkler system,with .F, , the added features of an integral ' � Model 7000 Pressure Relief Valve with drainage piping, Model 7500 300 PSI 31/2" Pressure Gauge, and Model 76001/4" 3-Way Globe Valve. t, ,a,-,; •The Model 1011T complies with the requirements of NFPA-13 that 7- stipulate a pressure relief valve be ..- i. _- " �, fli. . installed on all gridded systems and - e ' downstream of all pressure reducing • valves(see reverse). • •The Model 1011T TESTANDRAIN® ,+ � �N'� `,, ��. C �, is a compact single handle ball , ' ,:, "a `a_. valve which includes a tamper resis- tant test orifice and integral tamper resistant sight glasses, and is 300 PSI rated. •Available in a full range of sizes from 3/4"to 2" NPT and BSPT,with all specifiable orifice sizes%" (2.8K), 7A6" (4.2K), 1/2" (5.6K), 17/32" (8.0K),5/a" (11.2K, ELO), 3/a" (14.0K, ESFR), and K25 as required by NFPA 13,2007 (see reverse). •The included UL/FM Model 7000 Pressure Relief Valve features a flushing handle and is factory rated for 175 PSI. Other pressure settings are available and may be substituted. • Designed to relieve excess system pressure caused by surges or temperature changes as well as solve the dif- ficult problem of providing the relief valve with a convenient drainage-piping outlet. •The Model 1011T is shipped complete with all necessary components including the UL/FM Model 7500 Pres- sure Gauge and UL/FM Model 7600 Globe Valve. • Shipped with relief valve and bypass drain ports plugged to expedite pressure testing the system. •A locking kit is available and can be ordered with the valve to provide vandal resistance or prevent uninten- tional alarm activation. • Repair kits including (1)adapter gasket, (1)ball, (2)valve seats, (1)stem packing, and(1)stem washer are avail- able for all TESTANDRAIN®valves.Valve and orifice size must be specified when ordering. NOTE:It is important to note that the pressure rating of the relief valve indicates an operating range of pressure for both opening and closing of the valve.Standard relief valves are required to OPEN in a range of pressure between 90%and 105%of their rating.The valves • are required to CLOSE at a pressure above 80%of that rating.The relief valve should be installed where it is easily accessible for main- tenance.Care should be taken that the relief valve CANNOT be isolated from the system when the system is operational.A relief valve • should NEVER have a shutoff valve or a plug downstream of its outlet. Reliability, Versatility, icodecompatibilityVv h TESTANDRAIN is a registered trademark of AGF Manufacturing Inc. CS1011T 10/09 Model 1011T ; P. cos us - r 400. DRAIN® APPROVED Model 1011T 300 PSI Bronze Ball Valve,Model 7000 Pressure Relief Valve, Model 7500 Pressure Gauge, and Model 76001/4"3-Way Globe Valve DIMENSIONS MODEL 1011T - FRONT VIEW Orifice Size Available:3/8",7A&',1/2",17/32", ELO(%")*, ESFR(3/4")*,&K25** , SIZE A B C D E F - 101/4" 33/8" 11M6" 4466" 63/8" 83/4" 6 .- -: I 3� (256 mm) (86 mm) (46 mm) (117 mm) (162.5 mm) (119 mm) 4 e e e� 1 101/4" 31/4" 11M6" 4V16" 634" 83/4" F INLET A (256 mm) (86 mm) (46 mm) (117 mm) (162.5 mm) (119 mm) 'I ;o. . 101/2" 35/8" 11W16" 59/16" 51/2" 9" --B-+I o O al 11/a° o��, (263 mm) (91 mm) (51 mm) (141 mm) (192 mm) (225 mm) ri oOp°�O1%z.. 111/2" 37/4" 2�4" 81/4" 107/4" 911 6" DTO RAIN c _\� •(288 mm) (99 mm) (67 mm) (207 mm) (274 mm) (242 mm) E •� I,I �;����; 1 O G 1� 2" 111/2" 37/8" 26/8' 81/4" 107/8" 911/16" ID • �J (288 mm) (99 mm) (67 mm) (207 mm) (274 mm) (242 mm) I lb ,�•••.,...,,.�•,,,,.;�., *Available on 11/4"to 2"size units only LI **Available on 11/2"and 2" size units only THE MODEL 1011T PROVIDES ALL OF THE FOLLOWING... MATERIALS From the 2007 Edition of NFPA 13 Handle:Steel Chapter 8.16.2.4.1* Provisions shall be made to properly drain all parts of the system. Stem:Rod Brass Chapter 8.16.2.4.2 Drain connections,interior sectional o floor control valve(s)—shall be provided Ball:C.P.Brass &8.16.2.4.3 with a drain connection having a minimum size as shown in Table 8.16.2.4.2. Body: Bronze . Chapter 8.16.2.4.4 Drains shall discharge outside or to a drain capable of handling the flow of the Valve Seat: Impregnated drain. Teflon® Chapter A.8.17.4.2 (Wet Pipe System)test connection is permitted to terminate into a drain capable Indicator Plate:Steel of accepting full flow... using an approved sight test connection containing a Relief Valve: Bronze smooth bore corrosion-resistant orifice giving a flow equivalent to one sprinkler... Bypass Fittings: Brass Chapter 8.17.4.2.2 The test connection valve shall be readily accessible. Bypass Tubing: Nylobraid Chapter 8.17.4.2.4 shall be permitted to be installed in any location...downstream of the waterflow APPROVALS alarm. Chapter 8.17.4.3.1 (Dry Pipe System)a trip test connection not less than 1" in diameter,terminating UL and ULC Listed: in a smooth bore corrosion-resistant orifice,to provide a flow equivalent to one (EX4019&EX4533) sprinkler... FM Approved Chapter 8.17.4.3.2 The trip test connection...with a shutoff valve and plug not less than 1",at least NYC BSA No.720-87-SM one of which shall be brass. Chapter 7.1.2 -a gridded wet pipe system shall be provided with a relief valve set to operate at 175 PSI or 10 PSI in excess of the maximum system pressure,whichever is greater. Chapter 8.16.1.2.3* A relief valve of not less than 1/2" in size shall be provided on the discharge side of . ., the pressure-reducing valve set to operate at a pressure not exceeding 175 PSI. 4%4' Chapter A.8.16.1.2.3 -consideration should be given to piping the discharge from the(pressure relief) :;:** 000,00 valve " Chapter 8.16.1.2.2 Pressure gauges shall be installed on the inlet and outlet sides of each pressure- MADE IN D.S.A. reducing valve. USA Patent # 4741361 and Other Patents Pending AGF Manufacturing Inc. Job Name: 100 Quaker Lane,Malvern,PA 19355 Phone:610-240-4900 Architect: Fax:610-240-4906 Engineer: www.testandrain.com Contractor: • ': �. ��� � - -.. - - _ tat EDOYTHREit A LIGHTWEIGHT SCHEDULE 140 REPLACEMENT PIPE • ull Moose Tube's®Eddythread 40 40° ADVANTAGES BULL MOO f D TH is a lightweight replacement for • Has a Corrosion Resistance Ratio of 1.0. Schedule 40 that has a Corrosion • Has a pressure rating of 300 psi. Resistance Ratio of 1. • Is lighter weight than Schedule 40. • Is approved by Factory Mutual and listed by Underwriters Laboratories. • Is produced in accordance to ASTM A135 and A795 Type E,Grade A. •Can be used with standard Schedule 40 threaded fittings,couplings,and valves. • Is produced from steel with excellent properties of strength and threadability. •Can be used in wet,preaction,and deluge type sprinkler systems. ' •Can be hot dipped galvanized to meet FM's requirement for dry systems. F1 F •Offers lower freight costs. •Supplied with EDDY GUARD II'°MIC preventative coating. ----- -_',zi 4' . IMI'-IRE I i Ti N a a NOMINAL PIPE 0.0. I.D. WEIGHT WATER FILLED BUNDLE 0 r SIZE(IN) (IN) (IN) CRR* LB./FT WEIGHT SIZE 1 1.295 1.083 1.00 ' 1.461 1.860 70 1-1/4 1-650 1.418 1.00 2.070 2.754 51 1-1/2 1.900 1.654 1.00 2.547 3.468 44 2 2.375 '' 2.123 1.00 3.308 4.842 30 'Corrosion Resistance Ratio per latest UL Directory Listing PIPE PRIEPARAT1ON For proper operation,all pipe surfaces should be cleaned prior to installation.In order to provide a leak-tight seat for the gasket,pipe surfaces should be free from indentations and projections from the end of the pipe to the groove.All loose paint,scale,dirt,chips, grease,and rust must be removed prior to installation.Failure to take these important steps may result in improper coupling assembly, c us LISTED causing leakage.Also,check the manufacturer's instructions for the specific fitting used. APPROVED For Additional Information Contact(800)325-4467 www.bullmoosetube.com [7.034?).. C3s26)ONFSAOr From Canada Call:(800)882-4666 sales@bullmoosetube.com '. n,waawr...mraroirr . NFPA" Am:4,- �°""oAso"'.°" 1819 Clarkson Road cl Chesterfield,MO Gerald,MO Kent,WA Casa Grande,AZ Dallas,TX Masury,OH s 9ULL MOOEN TUBE COMPANY 63017 •DDY FLt.*°' THE COST EFFECTIVE ik PI SCHEDULE '1! ...« ..x.«.. ,..�,.w- ". � ". Lull Moose Tube's®EddyFlow° MOOSET S OF BULLTUBE('- EDDY FLOW. is a specially engineered •Certified to ASTM A135 and A795 Type E,Grade A. replacement for Schedule 10, •FM approved for roll grooving and welding for use in wet systems. offering better flow characteristics • UL Listed(for U.S.and Canada)for joining by welding or by listed rubber gasketed fittings for use in wet,dry,preaction,and deluge type while providing design flexibility sprinkler systems. This product is FM approved,as well • Lightweight—saves shipping costs and offers easier handling. as UL Listed(for U.S.and Canada) •Can be used with roll grooved couplings or welded outlets for pressures up to 300 psi. for roll grooving and welding. •Can be supplied roll grooved or plain end. •Can be hot dipped galvanized to meet FM's&UL requirement for dry systems. As an added benefit,it is more •Supplied with EDDY GUARD II®MIC preventative coating. economical to use than Schedule 10 due to reduced delivery costs and ease of handling.Furthermore, NPS O.D. EDDY FLOW® EDDY FLOW® WEIGHT WATER FILLED BUNDLE Eddy Flow's®larger ID provides SIZE(IN) (IN) (ID) CRR* PER FT. WT. SIZE an opportunity far downsizing 1-1/4 1.660 1.530 1.98 1.222 2.019 61 and further cost savings. 1-1/2 1.900 1728 3.44 1.844 2.86061, 2 2.375 2.203 2.78 2.330 3.982 37 2-1/2 22.'837755 2.705 1.66 . 2.809 5.299'' 30 3 3.500 3.334 1.00 3.361 7.144 19 4 4.500 4.310 1.00 4.968 11.290 19 "Corrosion Resistance Ratio per latest UL Directory Listing PIP?. ; ,t-REPARAT1ON For proper operation,all pipe surfaces should be cleaned prior to installation.In order to provide a leak-tight seat for the gasket,pipe surfaces should be free from indentations and projections from the end of the pipe to the groove.All loose paint,scale,dirt,chips, grease,and rust must be removed prior to installation.Failure to take these important steps may result in improper coupling assembly,causing leakage.Also,check the manufacturer's instructions for the specific fitting used. c us LISTED 'fir , APPROVED o] ® For Additional Information Contact(800)325-4467 www.bullmoosetube.com Lex ONFSA ( c..„?e) Or From Canada Call:(800)882-4666 sales@bullmoosetube.com NFPA' ARSA _. .°""`r""°"°"°" 1819 Clarkson Road Lii Chesterfield,MO Gerald,MO Kent,WA Casa Grande,AZ Dallas,TX Masury,OH A BULL M0082 MOE COMPANY 63017 7 _. . tqco ''''. f, =, -1 ' '' Worldwide Fire Protection , LU i G Contacts www.tyco-fire.com ' Products Series TY-FRB, 5.6 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General NOTICE The TYCO Series TY-FRB Sprinklers ''' 'm" Description described herein must be installed and TYCO TY-FRB,5.6 K-factor, maintained in compliance with this doc- The �. UprightYT (TYCO Series3)and Pendent, .6 (TY323)toument, as well as with the applicable i , standards of the National Fire Protec- ' 41- Sprinklers described in this data sheet are quick response,standard coverage, tion Association,in addition to the scan- � � -, g dards of any other authorities having . decorative 3 mm glass bulb-type spray jurisdiction.Failure to do so may impair ` sprinklers designed for use in light or the performance of these devices. -" ordinary hazard,commercial occupan- te:. cies such as banks,hotels,and shop- The owner is responsible for maintain- ping malls. ing their fire protection system and The recessed version of the Series TY devices in proper operating condition. The installing contractor or sprinkler FRB Pendent Sprinkler,where applica- manufacturer should be contacted with ble, is intended for use in areas with a finished ceiling.This recessed pendent any questions. sprinkler uses one of the following: S rinkler • A two-piece Style 15 Recessed p �K Escutcheon with recessed adjust- Identification „ m ment up to 5/8 inch (15,9 mm)from the flush pendent position. Number (SIN) e • A two-piece Style 20 Recessed Escutcheon with recessed adjust- TY313 Upright 5.6K, 1/2"NPT ,d ment up to 1/2 inch (12,7 mm)from TY323 Pendent 5.6K, 1/2"NPT ;. the flush pendent position. ,r The adjustment provided by the Technical Recessed Escutcheon reduces the Temperature Rating accuracy to which the fixed pipe drops Data 135°F(57°C) to the sprinklers must be cut. 155°F(68°C) Intermediate level versions of Series Approvals 175°F(79°C) TY-FRB Sprinklers are described in UL and C-UL Listed 200°F(93°C) Technical Data Sheet TFP357. Sprin- FM,LPCB,and VdS Approved 286°F(141°C) kler guards and shields are described CE Certified Finishes in Technical Data Sheet TFP780. Sprinklers with Polyester Finish are UL Sprinkler:Refer to Table A and C-UL Listed as Corrosion-Resis- Recessed Escutcheon:White Coated, tant Sprinklers. Chrome Plated,or Brass Plated Maximum Working Pressure Physical Characteristics 175 psi(12.1 bar) Frame Bronze 250 psi(17.2 bar)* Button Brass/Copper *The maximum working pressure of 250 psi Sealing Assembly Stainless IMPORTANT (17.2 bar)only applies to the listing by Un- Steel w/TEFLON Always refer to Technical Data derwriters Laboratories,Inc.(UL). Bulb Glass Sheet TFP700 for the`INSTALLER Discharge Coefficient Compression Screw Bronze WARNING"that provides cautions K=5.6 GPM/psis/2(80,6 LPM/bar1/2) Deflector Bronze with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and installation can permanently dam- age a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 4 FEBRUARY 2014 TFP172 TFP172 Page 2 of 4 Components: *Temperature rating is **Pipe thread connections per ISO 7-1 1 - Frame 4 - Bulb indicated on Deflector. can be provided on special request. 2 - Button 5 - Compression STYLE 15 or 20 3 - Sealing Screw ESCUTCHEON PLATE 1/2" 7/16"(11,1 mm) RECESSED Assembly 6 - Deflector* DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE-IN ESCUTCHEON \ i 5 �A 7/16" ESE M-- (11,1 mm) tF 4 NOMINAL j 2" MAKE-IN 6_ (50,8 mm) 1 I 1 44r 2 - IMME 1-3/8" 3 �� (50,8 mm) (34,9 mm) _ , WRENCH 1 f / I FLATS } 1/2"NPT** DEFLECTOR* I--*— 2-7/8"(73,0 mm)DIA. -- CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT FIGURE 1 SERIES TY-FRB UPRIGHT(TY313)AND PENDENT(TY323)SPRINKLERS 5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE �, Operation Installation The glass bulb contains a fluid which The TYCO Series TY-FRB,5.6 K-factor, WRENCH RECESS expands when exposed to heat.When Upright(TY313)and Pendent(TY323) (USE ONLY the rated temperature is reached,the Sprinklers must be installed in accor- END0.37/ "A") fluid expands sufficiently to shatter the dance with this section. ,../ glass bulb, allowing the sprinkler to General Instructions FIGURE 2 activate and water to flow. Do not install any bulb-type sprinkler if W-TYPE 6 the bulb is cracked or there is a loss SPRINKLER WRENCH Design of liquid from the bulb.With the sprin- kler held horizontally, a small air bub- WRENCH Criteria ble should be present. The diameter RECESS of the air bubble is approximately 1/16 The TYCO Series TY-FRB,5.6 K-factor, inch(1,6 mm)for the 135°F(57°C)and Upright(TY313)and Pendent(TY323) 3/32 inch(2,4 mm)for the 286°F(141°C) rte, Sprinklers are intended for fire protec- temperature ratings. tion systems designed in accordance with the standard installation rules rec- leak-tight 1/2 inch NPT sprinkler joint ognized by the applicable Listing or should be obtained by applying a min- Approval agency(such as, UL Listing imum to maximum torque of 7 to 14 `r is based on the requirements of NFPA ft.-lbs. (9,5 to 19,0 Nm). Higher levels �•� 13, and FM Approval is based on the of torque can distort the sprinkler Inlet requirements of FM's Loss Prevention with consequent leakage or impairment PUSH WRENCH Data Sheets). the Style 15 or Style of the sprinkler. Only IN TO ENSURE ) Y tY ENGAGEMENT 20 Recessed Escutcheon is to be used Do not attempt to compensate for WITH SPRINKLER for recessed pendent installations. insufficient adjustment in the Escutch- WRENCHING AREA eon Plate by under-or over-tightening FIGURE 3 the sprinkler. Re-adjust the position of W-TYPE 7 RECESSED the sprinkler fitting to suit. SPRINKLER WRENCH Upright and Pendent Sprinklers The Series TY-FRB Upright and Pen- dent Sprinklers must be installed in accordance with the following instructions. Step 1.Install Pendent sprinklers in the pendent position.Install upright sprin- klers in the upright position. Step 2. With pipe-thread sealant applied to the pipe threads, hand- tighten the sprinkler into the sprinkler fitting. TFP172 Page 3 of 4 Step 3.Tighten the sprinkler into the 2-7/8"DIA. sprinkler fitting using only the W-Type (73,0 mm) 6 Sprinkler Wrench(Figure 2).With ref- erence to Figure 1,apply the W-Type 6 2-1/4"DIA. Sprinkler Wrench to the wrench flats. FACE OF — (57,2 mm) Torque sprinklers 7 to 14 ft.-lbs.(9,5 to SPRINKLER 19,0 Nm). FITTING 5/8"(15,9 mm) Recessed Pendent Sprinklers 4 \ Ns FLUSH The Series TY-FRB Recessed Pendent 3/8±5/16" 1 Sprinklers must be installed in accor- (9,5±7,9 mm) , j '/ /dance with the following instructions. f /Step A.After installing the Style 15 or MOUNTING 1/8" J Style 20 Mounting Plate over the sprin- SURFACE (3,2 mm) kler threads, and with pipe-thread -------— sealant applied to the pipe threads, CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) hand-tighten the sprinkler into the TY-FRB PLATE 3/4" sprinkler fitting. (19,1 mm) Step B.Tighten the sprinkler into the FIGURE 4 Step B. fittingghtusing onin the into Wthe SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323) 7spriRecessed Sprinkler Wrench (Figure WITH TWO PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15 3).With reference to Figure 1,apply the RECESSED ESCUTCHEON W-Type 7 Recessed Sprinkler Wrench to the sprinkler wrench flats. Torque _ 2-7/8"DIA. sprinklers 7 to 14 ft.-lbs. (9,5 to 19,0 (73,0 mm) Nm). FACE OF Step C.After ceiling installation and fin- SPRINKLER 2-1/4"DIA. ishing,slide on the Style 15 or Style 20 FITTING (57,2 mm) Closure over the Series TY-FRB Sprin- 5/16±1/4" kler and push the Closure over the (7,9±6,4 mm) 1/2"(12,7 mm) Mounting Plate until its flange comes in + NsFLUSH contact with the ceiling. _....- ----1 ' ' 7 i� Care and f I — MOUNTING 011 1/8" J Maintenance SURFACE (3,2 mm) The TYCO Series TY-FRB,5.6 K-factor, "--" Upright(TY313)and Pendent(TY323) CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) Sprinklers must be maintained and ser- TY-FRB PLATE 7/8"(22,2 mm) viced in accordance with this section. FIGURE 5 Before closing a fire protection system SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323) main control valve for maintenance WITH TWO PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 work on the fire protection system RECESSED ESCUTCHEON that it controls, obtain permission to shut down the affected fire protection Modified sprinklers must be replaced. standards of any other authorities hav- systems from the proper authorities Sprinklers that have been exposed to ing jurisdiction. Contact the installing and notify all personnel who may be corrosive products of combustion,but contractor or sprinkler manufacturer affected by this action. have not operated,should be replaced regarding any questions. Absence of the outerpiece of an if they cannot be completely cleaned by wiping the sprinkler with a cloth or Automatic sprinkler systems are rec- escutcheon, which is used to cover by brushing it with a soft bristle brush. ommended to be inspected, tested, ii a clearance hole, can delay sprinkler and maintained by a qualified Inspec- operation in a fire situation. Care must be exercised to avoid dam- tion Service in accordance with local The owner must assure that the sprin- age to the sprinklers before,during,and requirements and/or national codes. klers are not used for hanging any after installation.Sprinklers damaged objects and that the sprinklers are only by dropping, striking, wrench twist/ • cleaned by means of gently dusting slippage,or the like,must be replaced. with a feather duster;otherwise, non- Also, replace any sprinkler that has a operation in the event of a fire or inad cracked bulb or that has lost liquid from vertent operation may result. its bulb.(Ref. Installation Section.) Sprinklers which are found to be leak- The owner is responsible for the ing or exhibiting visible signs of corro- inspection,testing,and maintenance of sion must be replaced. their fire protection system and devices in compliance with this document,as Automatic sprinklers must never be well as with the applicable standards painted, plated, coated, or other- of the National Fire Protection Associa- wise altered after leaving the factory. tion (e.g., NFPA 25), in addition to the TFP172 Page 4 of 4 P/N* 77 - XXX X XXX SPRINKLER TEMPERATURE FINISH RATINGS SIN 1 NATURAL BRASS 135 135°F(57°C) 370 5.6K UPRIGHT(1/2"NPT) TY313 g PURE WHITE(RAL9010)" 155 155°F(68°C) POLYESTER 371 5.6K PENDENT(1/2"NPT) TY323 q SIGNAL WHITE(RAL9003) POLYESTER 175 175°F(79°C) Use suffix 1"for ISO 7-1 connection; 9 CHROME PLATED 200 200°F(93°C) for example,77-370-4-175-I "Eastern Hemisphere sales only 286 286°F(141°C) TABLE A SERIES TY-FRB UPRIGHT AND PENDENT SPRINKLERS PART NUMBER SELECTION Limited Ordering Warranty Procedure For warranty terms and conditions,visit Contact your local distributor for avail- www.tyco-fire.com. ability.When placing an order, indicate the full product name and Part Num- ber(P/N). Sprinkler Assemblies with NPT Thread Connections Specify:Series TY-FRB Upright or Pen- dent(specify)Sprinkler,SIN (specify), K=5.6,Quick Response,(specify)tem- perature rating, (specify) finish, P/N (specify,refer to Table A). Recessed Escutcheon Specify:Style 15 Recessed Escutcheon • with(specify*)finish,P/N(specify*) Specify: Style 20 Recessed Escutch- eon with(specify*)finish,P/N(specify*) *Refer to Technical Data Sheet TFP770 Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387 Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001 • GLOBAL HEADQUARTERS 11400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright®2014 Tyco Fire Products,LP. All rights reserved. two TEFLON is trademark of The DuPont Corporation. Fire Protection Products w .. tqco Worldwide Fire Protection Contacts www.tyco-fire.com . Products J £U16 Series TY-FRB — 5.6 K-factor Horizontal and Vertical Sidewall Sprinklers Quick Response, Standard Coverage General tained when exposed to corrosive at- mospheres. Although corrosion resis Description tant coated sprinklers have passed the standard corrosion tests of the appli- 7 The Series TY FRB, 5.6 K-factor, Hor cable approval agencies,the testing is -m � �,, izontal and Vertical Sidewall Sprin- not representative of all possible cor- klers described in this data sheet rosive atmospheres. Consequently, it are quick response -standard cover- is recommended that the end user be � � consulted with resect to the suitabil i _ ` age, decorative 3 mm glass bulb type p spray sprinklers designed for use in ity of these coatings for any given cor1 - rosive environment.The effects of am- light and ordinary hazard, commer- ' cial occupancies such as banks, ho- bient temperature, concentration of tels,shoppingmalls,etc.Theyare de chemicals, and gas/chemical velocity, signed forinstallationalong wall ar should be considered, as a minimum, the side of a beam and just beneath a along with the corrosive nature of the smooth ceiling.Sidewall sprinklers are chemical to which the sprinklers will commonly used instead of pendent or be exposed. upright sprinklers due to aesthetics or building construction considerations, NOTICE where piping across the ceiling is not The Series TY-FRB Sprinklers de- desirable. scribed herein must be installed and " maintained in compliance with this The recessed version of the Series p TY-FRB Horizontal Sidewall Sprin- document, as well as with the appli- kler is intended for use in areas with cable standards of the National Fire ' a finished wall. It uses a two-piece Protection Association, in addition to Style 10 Recessed Escutcheon with the standards of any other authorities , 1/2 inch(12,7 mm)of recessed adjust- having jurisdiction. Failure to do so - ment or up to 3/4 inch(19,1 mm)of to- may impair the performance of these •tal adjustment from the flush sidewall devices. ° position, or a two-piece Style 20 Re- The owner is responsible for main- x . cessed Escutcheon with 1/4 inch (6,4 taining their fire protection system mm) of recessed adjustment or up to and devices in proper operating con ;� .?.` 1/2 inch (12,7 mm)of total adjustment dition. Contact the installing contrac- from the flush sidewall position. The tor or sprinkler manufacturer with any adjustment provided by the Recessed questions. Technical Escutcheon reduces the accuracy to which the fixed pipe nipples to the Sprinkler Data sprinklers must be cut. p Corrosion resistant coatings, where Identification Approvals applicable, are utilized to extend the UL and C-UL Listed. • life of copper alloy sprinklers beyond Numbers FM,LPCB,and NYC Approved. that which would otherwise be ob- (Refer to Table A for complete approv- TY3331 Horizontal al information including corrosion re- TY3431 Vertical sistant status.) IMPORTANT Always refer to Technical Data Maximum Working Pressure Sheet TFP700 for the "INSTALLER Refer to Table B. WARNING" that provides cau- Discharge Coefficient tions with respect to handling K=5.6 GPM/psi1i2(80,6 LPM/bar1/2) and installation of sprinkler sys- tems and components. Improp- Temperature Ratings er handling and installation can Refer to Table A. permanently damage a sprin- Finishes kler system or its components Sprinkler: Refer to Table C. and cause the sprinkler to fail Recessed Escutcheon:Signal or Pure to operate in a fire situation or cause White,Jet Black,Chrome Plated,or it to operate prematurely. Brass Plated. Page 1 of 6 FEBRUARY 2014 TFP176 y TFP176 Page 2 of 6 1 Frame DEFLECTOR Installation 2 Button HAT 5 �4�.ei 10% The Series TY-FRB,5.6 K-factor, Hori- 3 - Sealing _� zontal and Vertical Sidewall Sprinklers Assembly must be installed in accordance with 4 - Bulb /`y. ,�,�� this section. 5 - Compression - Screw General Instructions 6 - Deflector* 6*/ 4 2 3 1 Do not install any bulb type sprin- kler if the bulb is cracked or there is a loss of liquid from the bulb.With the • 9/16" WRENCH 1/2"** sprinkler held horizontally, a small air (14,3 mm) FLATS NPT bubble should be present. The diam- eter of the air bubble is approximately i ---1.A.--.\ / 1/16 inch(1,6 mm)for the 135°F(57°C) ik �� ` "7 / ���r to 3/32 inch (2,4 mm) for the 286°F iw-.1111" = 111114il � � 1111 (141°C)temperature ratings. ' A leak tight 1/2 inch NPT sprinkler joint • `moi should be obtained with a torque of 7 1-13/16" to 14 ft-lbs. (9,5 to 19,0 Nm). Higher - . 7/16 levels of torque maydistort the sprin- (46,0 mm) (11,1 mm) kler and cause leaage or impairment CENTERLINE NOMINAL of the sprinkler. OF SPRINKLER MAKE-IN p WATERWAY Do not attempt to make-up for insuf- 1-1/2" ficient adjustment in the escutcheon (38,1 mm)~ plate by under-or over-tightening the *Temperature rating sprinkler. Readjust the position of the is indicated on 2-3/16" - sprinkler fitting to suit. Deflector. (55,6 mm) V ESCUTCHEON ** SerieserticaTY-FRB dewall HorizontalSrinkler and STYLE Pipe thread 10 or 20 — PLATE SEATING p connections per RECESSED I SURFACE Installation ISO 7-1 can be ESCUTCHEONThe Series TY-FRB Horizontal and provided on gm Vertical Sidewall Sprinklers must be special request. �1� installed in accordance with the fol- lowing instructions. 2-7/8"DIA. (73,0 mm) 1■arlitiIIIIIIIIIl Step 1. Horizontal sidewall sprinklers are to be installed in the horizontal po- sition with their centerline of waterway perpendicular to the back wall and parallel to the ceiling.The word "TOP" on the Deflector is to face towards the ceiling. Vertical sidewall sprinklers are to be FIGURE 1 installed in the pendent or upright po- 5.6 K-FACTOR QUICK RESPONSE sition with the arrow on the Deflector SERIES TY-FRB HORIZONTAL SIDEWALL(TY3331)SPRINKLERS pointing away from the wall. Characteristics Step 2. With pipe thread sealant ap- PhysicalDesign plied to the pipe threads, hand tighten Frame Bronze the sprinkler into the sprinkler fitting. Button Brass/Copper Sealing Assembly Beryllium Nickel w/ Criteria Step 3. Tighten the sprinkler into the • TEFLON The Series TY-FRB,5.6 K-factor, Hi sprinkler fitting using only the W-Type acor, or Bulb Glass6 Sprinkler Wrench (Ref. Figure 5), Compression Screw Bronze zontal and Vertical Sidewall Sprinklers With reference to Figure 1 or 2,the W- HSW Deflector Bronze are intended for fire protection sys- Type 6 Sprinkler Wrench is to be ap- VSW Deflector Copper tems designed in accordance with the standard installation rules recognized plied to the wrench flats. Operation by the applicable Listing or Approval agency (e.g., UL Listing is based on The glass bulb contains a fluid which the requirements of NFPA 13, and FM expands when exposed to heat.When Approval is based on the requirements the rated temperature is reached, the of FM's Loss Prevention Data Sheets). fluid expands sufficiently to shatter Only the Style 10 or 20 Recessed Es- the glass bulb, allowing the sprinkler cutcheon,as applicable, is to be used to activate and water to flow. for recessed horizontal installations. TFP176 Page 3 of 6 Series TY-FRB Recessed *Temperature ** Pipe thread 1 - Frame 4 - Bulb 7 - Ejection Horizontal Sidewall Sprinkler rating is connections 2 - Button 5 - Compression Spring . Installation indicated on per ISO 7-1 can 3 - Sealing Screw The Series TY-FRB Recessed Hori- Deflector. be provided on Assembly 6 - Deflector* zontal Sidewall Sprinklers must be special request. installed in accordance with this section. ARROW MUST POINT AWAY �— ij Step A. Recessed horizontal sidewall 7/16" FROM AND BE sprinklers are to be installed in the ESCUTCHEON (11,1 mm) PERPENDICULAR O horizontal position with their center- PLATE SEATING NOMINAL TO THE BACK . line of waterway perpendicular to the SURFACE 1/2"** MAKE-IN WALL SURFACE4 back wall and parallel to the ceiling. NPT The word "TOP"on the Deflector is to 6* face towards the ceiling. I _� f-` �-� r• Step B.After installing the Style 10 or 71 FOV 1'r V._5 20 Mounting Plate over the sprinkler ,c threads,hand tighten the sprinkler into 2-3/16" dl IItb 2-3/16" 4 the sprinkler fitting. (55,6 mm) 1 (55,6 mm) li Step C. Tighten the sprinkler into the 1-1/2" \ I ;y 2 sprinkler fitting using only the W-Type (38,1 mm) WRENCH'-- -.-- --. FLATS -m—Ii" PA i 7 Recessed Sprinkler Wrench (Ref. 73 Figure 6). With reference to Figure ��A 1, the W-Type 7 Recessed Sprinkler ������ , Y 1 Wrench is to be applied to the sprin SHOWN SHOWN CROSS kler wrench flats. PENDENT UPRIGHT SECTION Step D.After the ceiling has been in- FIGURE2 stalled or the finish coat has been ap- 5.6 K-FACTOR QUICK RESPONSE plied, slide on the Style 10 or 20 Clo- SERIES TY-FRB VERTICAL SIDEWALL sure over the Series TY-FRB Sprinkler (T Y3431)SPRINKLERS and push the Closure over the Mount- ing Plate until its flange comes in con- if they cannot be completely cleaned The owner is responsible for the in- tact with the ceiling. by wiping the sprinkler with a cloth or spection, testing, and maintenance by brushing it with a soft bristle brush. of their fire protection system and de- Care and Care must be exercised to avoid dam- vices in compliance with this docu- age to the sprinklers before, during, ment, as well as with the applicable Maintenance and after installation. Sprinklers darn- standards of the National Fire Pro- aged by dropping, striking, wrench addion Association (e.g., NFPA 25), in The Series TY-FRB,5.6 K-factor, Hori- twist/slippage, or the like, must be addition to the standards of any oth- zontal and Vertical Sidewall Sprinklers replaced. Also, replace any sprinkler er authorities having jurisdiction. The must be maintained and serviced in that has a cracked bulb or that has installing contractor or sprinkler man- accordance with this section. lost liquid from its bulb. (Ref. Installa- ufacturer should be contacted relative tion Section to any questions. Before closing a fire protection sys- )• tem main control valve for mainte- The owner must assure that the sprin- It is recommended that automatic nance work on the fire protection sys- klers are not used for hanging any ob- sprinkler systems be inspected, test- tem that it controls,permission to shut jects and that the sprinklers are only ed, and maintained by a qualified In- down tern musthe be obtained fed fire om then s- cleaned by means of gently dusting slocaltion requiirrvice in rements and/orance with national prop- with a feather duster; otherwise, non- er authorities and all personnel who operation in the event of a fire or inad- codes. may be affected by this action must vertent operation may result. be notified. Frequent visual inspections are rec- Absence of an escutcheon, which is ommended to be initially performed - used to cover a clearance hole, may for corrosion resistant coated sprin- delay the time to sprinkler operation in klers, after the installation has been a fire situation. completed,to verify the integrity of the Sprinklers that are found to be leaking corrosion resistant coating. Thereaf- - or exhibiting visible signs of corrosion ter, annual inspections per NFPA 25 must be replaced. should suffice; however, instead of in- specting from the floor level,a random Automatic sprinklers must never be sampling of close-up visual inspec- painted, plated, coated or other- tions should be made, so as to better wise altered after leaving the factory. determine the exact sprinkler condi- Modified sprinklers must be replaced. tion and the long term integrity of the Sprinklers that have been exposed to corrosion resistant coating, as it may corrosive products of combustion,but be affected by the corrosive condi- have not operated,should be replaced tions present. TFP176 Page 4 of 6 5/8±1/4" (15,916,4 mm) MOUNTING FACE OF WRENCH RECESS SURFACE —-- SPRINKLER (END"A"USED FOR FITTING 1/2"NPT MODELS) A CLOSURE - FIGURE 5 W-TYPE 6 SPRINKLER WRENCH • 2-7/8"DIA. SERIES rigrA (73,0 mm) TY-FRB `quit II (57,2 57 2 miTo WRENCH RECESS MOUNTING PLATE '% �,TW A 1/8" (3,2 mm) 1-1/4"(31,8 mm) 3/4"(19,1 mm) PUSH WRENCH 3/4"(19,1 mm) 1/4"(6,4 mm) IN TO ENSURE ENGAGEMENT FIGURE 3 WITH SPRINKLER SERIES TY-FRB RECESSED HORIZONTAL SIDEWALL SPRINKLER WRENCHING AREA WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT FIGURE 6 STYLE 10 RECESSED ESCUTCHEON W-TYPE 7 RECESSED SPRINKLER WRENCH 1/211/8" (12,7/3,2 mm) MOUNTING FACE OF SURFACE __— SPRINKLER FITTING A CLOSURE 4 2-7/8"DIA. SERIES !WM (73,0 mm) TY-FRB ■.1�', IIIA (57,2 mDm) MOUNTING 11.11 PLATE I i 1/8" (3,2 mm) 1-1/4"(31,8 mm) 1/2"(12,7 mm) 1"(25,4 mm) 1/4"(6,4 mm) FIGURE 4 SERIES TY-FRB RECESSED HORIZONTAL SIDEWALL SPRINKLER WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 RECESSED ESCUTCHEON TFP176 Page 5 of 6 SPRINKLER FINISH(See Note 11) K TYPE TEMP. BULB NATURAL CHROME LIQUID BRASS PLATED POLYESTER*** LEAD COATED 135°F(57°C) Orange HORIZ. 155°F(68°C) Red SIDEWALL 175°F(79°C) Yellow 1,2,3,4,9,10 1,2,3,9 1,2,3,9 (TY3331) 200°F(93°C) Green 286°F(141°C) Blue 5.6 RECESSED 135°F(57°C) Orange 1/2" HORIZ. 155°F(68°C) Red NPT SIDEWALL 1,2,4,9,10 1,2,9 N/A (TY3331)* 175°F(79°C) Yellow Figure 3 200°F(93°C) Green RECESSED 135°F(57°C) Orange HORIZ. 155°F(68°C) Red SIDEWALL 1,2,3,4,9 N/A (TY3331)** 175°F(79°C) Yellow Figure 4 200°F(93°C) Green VERTICAL 135°F(57°C) Orange SIDEWALL 155°F(68°C) Red 5.6 (TY3431) 1/2" Installed 175°F(79°C) Yellow 5,6,7,8,9 5,6,7,9 NPT Pendent or 200°F(93°C) Green Upright P86°F(141°C) Blue NOTES: 1. Listed by Underwriters Laboratories,Inc.(UL)as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies at a 4 to 12 inch(100 to 300 mm)top of deflector to ceiling distance. 2. Listed by Underwriters Laboratories Inc.for use in Canada(C-UL)as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies at a 4 to 12 inch(100 to 300 mm)top of deflector to ceiling distance. 3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers for use in Light Hazard Occupancies at a 4 to 12 inch(100 to 300 mm)top of deflector to ceiling distance. 4. Approved by the Loss Prevention Certification Board(LPCB Ref.No.007a/04)at a 4 to 6 inch(100 to 150 mm)top of deflector to ceiling distance.The LPC does not rate the thermal sensitivity of horizontal sidewall sprinklers. 5. Listed by Underwriters Laboratories,Inc.as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies. 6. Listed by Underwriters Laboratories for use in Canada(C-UL)as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies. 7. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers for use in Light Hazard Occupancies. 8. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/06&007a/04)as Quick Response Sprinklers. 9. Approved by the City of New York under MEA 354-01-E. 10. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/06)at a 4 to 6 inch(100 to 150 mm)top of deflector to ceiling distance.The LPC does not rate the thermal sensitivity of horizontal sidewall sprinklers. 11. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion Resis- tant Sprinklers.Where Lead Coated Sprinklers are noted to be FM Approved,the sprinklers are FM Approved as Corrosion Resistant Sprinklers. *Installed with Style 10(1/2"NPT)3/4"Total Adjustment Recessed Escutcheon. **Installed with Style 20(1/2"NPT)1/2"Total Adjustment Recessed Escutcheon. ***Frame and deflector only. TABLE A • LABORATORY LISTINGS AND APPROVALS TFP176 Page 6 of 6 SPRINKLER FINISH K TYPE NATURAL BRASS CHROME PLATED POLYESTER LEAD COATED HORIZONTAL SIDEWALL 250 PSI(17,2 BAR) (TY3331) or 175PSI(12,1 BAR) 5.6 RECESSED HORIZ. 1/2" SIDEWALL(TY3331) (SEE NOTE 1) NPT VERTICAL SIDEWALL 175 PSI(12,1 BAR • (TY3431) ) NOTES: 1. The maximum working pressure of 250 psi(17,2 bar)only applies to the Listing by Underwriters Laboratories,Inc.(UL);the Listing by Underwriters Laboratories,Inc.for use in Canada(C-UL);and,the Approval by the City of New York. TABLE B MAXIMUM WORKING PRESSURE P/N 57 - XXX - X - XXX � I SIN SPRINKLER TEMPERATURE FINISH RATINGS 378 HORIZONTAL SIDEWALL TY3331 1 NATURAL BRASS 135 135°F(57°C) 375 VERTICAL SIDEWALL TY3431 3 PURE WHITE(RAL9010)* 155 155°F(68°C) POLYESTER 4 SIGNAL WHITE(RAL9003) 175 175°F(79°C) POLYESTER 5 JET BLACK(RAL9005)** 200 200°F(93°C) POLYESTER 7 LEAD COATED 286 286°F(141°C) 9 CHROME PLATED *Eastern Hemisphere sales only. **Available in 155°F(68°C)or 200°F (93°C)temperature rating only. TABLE C PART NUMBER SELECTION SERIES TY-FRB HORIZONTAL AND VERTICAL SIDEWALL SPRINKLERS Orderin Sprinkler Assemblies with NPT Recessed Escutcheon 7 Thread Connections: Specify:Style(10 or 20)Recessed Es- Procedure Specify: Series TY-FRB (specify SIN), cutcheon with (specify*) finish, P/N (specify K-factor), (specify) Horizontal (specify*). Contact your local distributor for avail- Sidewall or Vertical Sidewall Sprinkler, *Refer to Technical Data Sheet TFP770 ability. When placing an order, indi- Standard Response, Standard Cov- cate the full product name and Part erage, (specify) temperature rating, Sprinkler Wrench Number(P/N). (specify)finish or coating, P/N (spec- Specify: W-Type 6 Sprinkler Wrench, ify from Table C) P/N 56-000-6-387 Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001 GLOBAL HEADQUARTERS 11400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright®2013 Tyco Fire Products,LP. All rights reserved. NCO TEFLON is trademark of The DuPont Corporation. Fire Protection Products