Plans (77) - s - 6a)-7.7 ) a 2 S i 77-u7gq/i( ,f- RECEIVED APR 1 4 2016 *'y'•`i*`` OICY h TIGARD lYA r ir• jr r ■ i �."t -�- ING DIVISION FIRE PROTECTION, INC. 9095 S.W. Burnham Tigard, OR 97223 SOUTHVIEW HEIGHTS LOT 32 12052 SW TURNAGAIN DRIVE TIGARD, OREGON 97224 FIRE PROTECTION HYDRAULIC CALCULATIONS HYDRANT FLOW REQUEST FORM PROJECT: Southview ADDRESS: none available CROSS STREET: 120th and Beef Bend Rd Tigard Or FLOW HYDRANT LOCATION: highest hydrant in new development lot 4 STATIC: 60 RESIDUAL: 54 GPM: 1230 @ 20 PSI = 2362 DATED: 12.15.14 MONITOR HYDRANT LOCATION: 12012 Aspen Ridge STATIC: 60 RESIDUAL: 48 GPM: DATED: 12.15.14 WITNESS WITNESSED BY: TITLE: ORGANIZATION: SIGNATURE: t. HYDRAULIC CALCULATIONS for Job Information Project Name:Southview Lot 32 Contract No.:C16-985 City: Tigard, OR 97224 Project Location: 12052 SW Tumagain Dr Date:4/14/2016 Contractor Information Name of Contractor. Wyatt Fire Protection Address: 9095 SW Bumham St City: Tigard, OR 97223 Phone Number: 503-684-2928 E-mail:a.nishihara@wyattfirecom Name of Designer Ashley Nishihara Authority Having Jurisdiction: City of Tigard Design Remote Area Name Den&Entry Remote Area Location Occupancy Classification Density(gpm/ft2) 0.052 Area of Application(ft2) 648 Coverage per Sprinkler(ft2) 324 Number of Calculated Sprinklers 2 In-Rack Demand(gpm) 0 Special Heads Hose Streams(gpm) 0 Total Water Required(incl.Hose Streams)(gpm) 34 Required Pressure at Source(psi) 36.3 Type of System Wet Volume-Entire System (gal) 3.6 gal Water Supply Information Date 12/15/2014 Location Highest Hydrant in Development Source Public Water Notes File:W:ISOUTHVIEW\Southview 3215V32 Calc.tyc3 Date 4/14/2016 Copyright©2002-2012 Tyco Fire Protection Products Page 1 ..e. Job:Southview Lot 32 Node Labels: Off Pipe Labels: Off Diagram for Design Area: Den&Entry ....------- ..,,,..,.„ ....------- . --....., _,..- ,. ------- .... _.-------- ....... ... ------- .....----. ------- --.. _._.----------- _. -• . . File:W:\SOUTHV1EWSOUthVieW 32\SV32 Calc.tyc3 Date 4/14/2016 Copyright©2002-2012 Tyco Fire Protection Products Page 2 Job:Southview Lot 32 Hydraulic Analysis for : Den & Entry Calculation Info Calculation Mode Demand Hydraulic Model Fluid Name Hazen-Williams Fluid Weight, (Ib/ft3) Water @ 60F(15.6C) Fluid Dynamic Viscosity, (Ib•s/ft2) N/A for Hazen-Williams calculation. N/A for Hazen-Williams calculation. Water Supply Parameters Supply 1 :src1 Flow(qpm) Pressure(psi) 0 60 1230 54 Hoses Inside Hose Flow/Standpipe Demand(gpm) Outside Hose Flow(gpm) Additional Outside Hose Flow(gpm) Other(custom defined) Hose Flow(gpm) Total Hose Flow(gpm) Sprinklers Ovehead Sprinkler Flow(gpm) 34 InRack Sprinkler Flow(gpm) 0 Other(custom defined)Sprinkler Flow(gpm) 0 Total Sprinkler Flow(gpm) 34 Other Required Margin of Safety(psi) 0 Base of Riser-Pressure(psi) 36.3 Base of Riser-Flow(gpm) 34 Demand w/o System Pump(s) N/A File:W:\SOUTHVIEW\Southview 32\SV32 Calc.tyc3 Date 4/14/2016 Copyright©2002-2012 Tyco Fire Protection Products Page 3 Job:Southview Lot 32 Hydraulic Calculations/Fluid Delivery Time Analysis Node Data Node# Type K-Fact. Discharge Coverage Tot. Pres. Req. Pres. Elev Hgroup Open/Closed Overdischarge Density Elev. Pres. Req. Discharge gpm ft2 psi psi ft gpm/Psi/z gpm gpm/ft2 psi gpm srci Supply34 36.3 3 SUPPLY 0 n1 Node 35.6 4 NODE -0.4 n2 Node 30.4 5 NODE -0.9 n3 Node 26 10.67 NODE -3.3 n4 Node 24.4 10.67 NODE -3.3 n5 Node 17.4 10.67 NODE -3.3 n6 Node 12.6 10.67 NODE -3.3 n7 Node 12.2 10.67 NODE -3.3 n8 Node 12.1 10.67 NODE -3.3 hl Overhead Sprinkler 4.9 17 324 12.1 12 10.17 HEAD Open 0.0 0.053 -3.1 17 h2 Overhead Sprinkler 4.9 17 324 12 12 10.17 HEAD Open 0 0.052 -3.1 17 File:W:\SOUTHVIEW\Southview 32\SV32 Calc.tyc3 Date 4/14/2016 Copyright 02002-2012 Tyco Fire Protection Products Page 4 • Job name:Southview Lot 32 Sheet number: PIPE INFORMATION Node 1 Elev 1 K-Factor 1 Flow added(q)* Nominal ID Fittings g L C Factor total (Pt) Node 2 Elev 2 K-Factor 2 Total flow (Q) Actual ID quantity x (name) = length F Pf per ft elev(Pe) NOTES T frict (Pf) (ft) (gpm/psi'/2) (gpm) (in) (ft) (ft) (psi) (psi) h2 10.17 4.9 17 1 lx(BM.90)=5 0.5 150 12 n8 10.67 17 1.101 5 0.0502 -0.2 5.5 n8 10.67 0.3 0 1 lx(BM.Tee-Br)=5 5.83 150 12.1 n6 10.67 17 1.101 5 0.0502 0 10.83 0.5 - n6 10.67 17 1 2x(fm.Tee-Run)=3.82 17.5 150 12.6 n5 10.67 34 1.101 lx(BM.Tee-Br)=5 8.82 0.1815 0 26.32 4.8 n5 10.67 0 1 3x(fm.Tee-Run)=5.73 27.67 150 17.4 n4 10.67 34 1.101 lx(BM.90)=5 10.73 0.1815 0 38.4 7 n4 10.67 0 1 1x(us.90)=3.82 4.83 150 24.4 n3 10.67 34 1.101 3.82 0.1815 0 8.65 1.6 n3 10.67 0 1 1x(coupling)=1.19 5.67 120 26 n2 5 34 1.087 1.19 0.292 2.5 n2 5 6.86 2 0 1 1 0 30.4 Ames2000B nl 4 34 0 0 4.7666 0.4 1 4.8 nl 4 0 1 srcl n13 1 120 35.6 34 1.087 0 0.292 0.4 hi 10.17 4.9 1 0.3 17 1 1x(BM.90)=5 0.5 150 12.1 n7 10.67 17 1.101 5 0.0504 -0.2 5.5 0.3 n7 10.67 0 1 lx(BM.Tee-Run)=1 8.5 150 12.2 n6 10.67 17 1.101 1 0.0504 0 9.5 0.5 * Discharge shown for flowing nodes only ©2006 National Fire Protection Association Page 5 RECEI VED �e APR 142016 +i i�a t'�`w� CITY OF T3 `A f ,rt i � i i !� � t ' i .-41.,\:."-Algr WFIRE YAT 1S1 �PROTECTION 1NC. 9095 S.W. Burnham Tigard, OR 97223 SOUTH VIEWLW3HEIGHTs HEIGHTS OT 2 12052 SW TURNAGAIN DRIVE TIGARD, OREGON 97224 FIRE PROTECTION EQUIPMENT SUBMITTAL tz,co Worldwide Fire Protection www.tyco-fire.com Contacts Products RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Flat-Plate Concealed Pendent Wet Pipe and Dry Pipe Systems General proven to help in the control of residen- tial fires and to improve the chance for Description occupants to escape or be evacuated. The TYCO RAPID RESPONSE Series The Series LFII Residential Flat-Plate LFII Residential Flat-Plate Concealed Concealed Pendent Sprinklers are shipped with a Disposable Protective Pendent Sprinklers(TY2524)are decora- Cap.The Protective Cap protects the tive,fast response,fusible solder sprin- sprinkler during ceiling installation or klers designed for use in residential oc- finish.After ceiling installation is corn- cupancies such as homes,apartments, plete, the Protective Cap is removed dormitories,and hotels. and the Cover Plate/Retainer Assem The Cover Plate/Retainer Assembly con- bly is installed. Removing the Protec- tive Cap is required for proper sprinkler ceals the sprinkler operating compo- nents above the ceiling.The flat profile performance. of the Cover Plate provides the optimum The owner is responsible for maintaining of the Cover ppeprov sprinkler design. Dry Pipe System Application their fire protection system and devic- aeshscall the concealed design f the The Series LFII Residential Flat-Plate es in proper operating condition. Con- Additionally,Series LFII Residential Flat-Plate Con Concealed Pendent Sprinkler offers a tact the installing contractor or sprinkler cealed Pendent Sprinklers provides 1/2 laboratory approved option for design- manufacturer with any questions. sys- inch d ,7 rint adjmedt.This ing dry pipe residential sprinkler adjustment provides a measure of flex- terns,whereas,ebmost residentialppovedsprin- Sprinkler ibility when cutting fixed sprinkler drops. klers are laboratory approved for wet systems only. Identification The Series LFII Residential Flat-Plate Through extensive testing,it has been Concealed Pendent Sprinklers are in- determined that the number of desi n tended for use in the following systems: g Number (SIN) sprinklers(hydraulic design area)for the •wet and dry pipe residential sprin- Series LFII Residential Flat-Plate Con- TY2524 kler systems for one- and two-fam- cealed Sprinklers(TY2524)need not be ily dwellings and mobile homes per increased over the number of design NFPA 13D sprinklers(hydraulic design area)speci- •wet and dry pipe residential sprin- fied for wet pipe sprinkler systems, as kler systems for residential occu is customary for density/area sprinkler pancies up to and including four sto- systems designed per NFPA 13, 13D, ries in height per NFPA 13R or 13R. •wet and dry pipe sprinkler systems Consequently,the Series LFII Resided for the residential portions of any tial Flat-Plate Concealed Sprinklers occupancy per NFPA 13 (TY2524)offer the features of non-wa- n addition to not having to The Series LFII Residential Sprinklers increase the ter filled ienumber of design sprinklers have been designed with heat sensitiv- (hydraulic design area)for systems de- ity and water distribution characteristics signed to NFPA 13, 13D,or 13R. NOTICE IMPORTANT The Series LFII Residential Rat-Plate Always refer Technical Data Concealed Pendent Sprinklers(TY2524) Sheet t refer for the Technical Data described herein must be installed and WARNING'that provides cautions maintained in compliance with this doc- ument and the applicable standards of with respect to handling and instal- the National Fire Protection Association, lation of sprinkler systems and corn- in addition to the standards of any au- ponents.Improper handling and in- thorities having jurisdiction. Failure to stallation can permanently damage do so may impair the performance of a sprinkler system or its compo- these devices. nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 6 FEBRUARY 2014 TFP443 TFP443 Page 2 of 6 BODY SEALING WRENCH (1/2"NPT) f ASSEMBLY RECESS CAP AL �� ,,,r= 1, /', SPRINKLERi r WRENCHING SADDLE \ PUSH WRENCH SUPPORT i ; L I� COMPRESSION INTO ENSURE CUP WITH ) 5 SCREW ENGAGEMENT ROLL FORMED 1 WITH SPRINKLER THREADS11 WRENCHING AREA IL- A LEVER FIGURE2 GUIDE I W-TYPE 18 PIN 'l_S ,, ) ,�'�,I SPRINKLER WRENCH SOLDER LINK ELEMENT GUIDE PIN HOUSING , DEFLECTOR DEFLECTOR I C,-,-ti-- s- _�3 (OPERATED , POSITION) SPRINKLER/SUPPORT CUP ASSEMBLY _ S , THREAD INTO j RETAINER SUPPORT WITH THREAD CUP UNTIL MOUNTING O O DIMPLES SURFACE IS ) FLUSH WITH CEILING EJECTION SPRING SOLDER J �-- COVER PLATE/RETAINER COVER TAB ASSEMBLY PLATE FIGURE 1 RAPID RESPONSE SERIES LFII RESIDENTIAL FLAT-PLATE CONCEALED PENDENT SPRINKLER(TY2524) " SPRINKLER- (632-1/2,5 mmDIA.) _y 1/2"(12,7 mm) FACE OF SUPPORT CUP 1/2" THREADED SPRINKLER ASSEMBLY NPT ADJUSTMENT FITTING I OPERATED im.--mumi SPRINKLER II1-7/8"±1/4" - COVER ' - (47,6 mm PLATE �� � = I RETAINER � 1/8"GAP ±6,4 mm) (3,2 mm) COVER- SPRINKLER- MOUNTING 7/8 (22,2 mm) I I RETAINER SUPPORT CUP 3/16" SURFACE 1-1/8"(28,6 mm) ASSEMBLY ASSEMBLY �� �� (4,8 mm) 'W \ 3-3/16" DIA. DISPOSABLE DEFLECTOR IN (81,0 mm) TIP PROTECTIVE CAP OPERATED POSITION FIGURE 3 RAPID RESPONSE SERIES LFII RESIDENTIAL FLAT-PLATE(TY2524) INSTALLATION DIMENSIONS/PROTECTIVE CAP/ACTIVATED DEFLECTOR TFP443 Page 3 of 6 Technical Design Criteria Dry Pipe System Water Delivery When using the Series LFII Residential Data The TYCO RAPID RESPONSE Series Flat-Plate Concealed Pendent Sprinklers LFII Residential Flat-Plate Concealed (TY2524)in dry pipe sprinkler systems, Approvals Pendent Sprinklers (TY2524) are UL the time for water delivery must not ex- UL and C-UL Listed and C-UL Listed for installation in ac- ceed 15 seconds for the most remote The TYCO RAPID RESPONSE Series cordance with this section: operating sprinkler. LFII Residential Flat-Plate Concealed Residential Sprinkler Design Guide Obstruction to Water Distribution Pendent Sprinklers are only listed with When conditions exist that are outside Sprinklers are to be located in accor- the Series LFII Concealed Cover Plates the scope of the provided criteria, re- dance with the obstruction rules of having a factory-applied finish. fer to the Residential Sprinkler Design NFPA 13D, 13R, and 13 as applicable These Cover Plates and their part num- Guide TFP490 for the manufacturer's for residential sprinklers as well as with bers can be found in the Ordering Pro- recommendations that may be accept- the obstruction criteria described within cedure section at the end of this data able to the authority having jurisdiction. the Technical Data Sheet TFP490. sheet. System Type Operational Sensitivity For details on approvals,refer to the De- Per the UL Listing,wet pipe and dry pipe Install sprinklers relative to the ceiling sign Criteria section. systems may be utilized. Per the C-UL mounting surface as shown in Figure 3. Listing,only wet pipe systems may be The Series LFII Residential Flat-Plate Maximum Working Pressure utilized. 175 psi(12,1 bar) Concealed Pendent Sprinklers must Refer to Technical Data Sheet TFP485 not be used in applications where the Discharge Coefficient about the use of Residential Sprinklers air pressure above the ceiling is greater K=4.9 GPM/psi12(70,6 LPM/bar12) in residential dry pipe systems. than that below. Down drafts through Temperature Rating Ceiling Types the Support Cup can delay sprinkler op- Sprinkler: 160°F(71°C) Smooth flat horizontal, or beamed, or eration in a fire situation. Cover Plate: 139°F(59°C) sloped, in accordance with the 2013 Sprinkler Spacing Edition of NFPA 13D, 13R or 13 as The minimum spacing between sprin- Vertical Adjustment applicable. klers is 8 feet (2,4 m). The maximum 1/2 inch(12,7 mm) Design spacing between sprinklers cannot ex- Hydraulicand 13R) ceed the length of the coverage area Finishes (NFPA Refer to the Ordering Procedure section. For systems designed to NFPA 13D or (Table A)being hydraulically calculated Physical Characteristics NFPA 13R,the minimum required sprin- 12 ft a maximum of 12 feet for a 12 ft.x kler flow rate are givenp 12 ft. coverage areagor feet for a 20 Cover Plate/Retainer Assembly: in Tables A and ft.x 20 ft.coverage area.) Cover Plate Copper B as a function of temperature rating Ejection Spring Stainless Steel and the maximum allowable coverage Retainer Brass areas.The sprinkler flow rate is the mini- Sprinkler/Support Cup Assembly: mum required discharge from each of Body Brass the total number of"design sprinklers" Cap Bronze as specified in NFPA 13D or NFPA 13R. Saddle Brass The number of"design sprinklers"spec- Sealing Assembly Beryllium ified in NFPA 13D and 13R for wet pipe Soldered Link Halves Nickel w/TEVLcON systems is to be applied when designing kel dry pipe systems. Lever Bronze Compression Screw Brass Hydraulic Design Deflector Bronze (NFPA 13) Guide Pin Housing Bronze Guide Pins Bronze For systems designed to NFPA 13,the Support Cup Steel number of design sprinklers is to be the four most hydraulically demanding Operation sprinklers.The minimum required dis- charge from each of the four sprinklers is to be the greater of the following: When exposed to heat from a fire, the Cover Plate,which is normally soldered •The flow rates given in Tables A and to the Retainer at three points,falls away B as a function of temperature rating to expose the Sprinkler/Support Cup As- and the maximum allowable cover- sembly.At this point,the Deflector,sup- age area ported by the Guide Pins, drops down •A minimum discharge of 0.1 gpm/ft2. to its operated position. over the"design area"comprised of The Solder Link Element of the Sprinkler/ the four most hydraulically demand- Support Cup Assembly is comprised of ing sprinklers for the actual coverage two link halves that are soldered togeth- areas being protected by the four er with a thin layer of solder.When the sprinklers rated temperature is reached,the sol- The number of "design sprinklers" der melts and the two link halves sepa- specified in NFPA 13 for wet pipe sys- rate, allowing the sprinkler to activate tems is to be applied when designing and flow water. dry pipe systems. TFP443 Page 4 of 6 WET PIPE SYSTEM Maximum Minimum Flow and Residual Pressure') Coverage Maximum Area fai Spacing Ordinary Temp Rating Ft. 160°F(71°C) Ft.x Ft. (m x m) (m) t. Deflector to Installation Minimum Flow Pressure Ceiling Type Spacing GPM PSI Ft. (L/min) (bar) (m) 12 x 12 12 13 7.0 Smooth (3,7 x 3,7) (3,7) (49,2) (0,48) Ceilings 7/8 to 14 x 14 14 13 7.0 1-1/8 inches. (4,3 x 4,3) (4,3) 49,2) (0,48) Beamed 16 x 1616 13 7.0 Ceilings per 8 (4,9 x 4,9) (4,9) (49,2) (0,48) NFPA 13D Concealed 13R,or 13 (2,4) 18 x 18 18 17 12.0 Installed in (5,5 x 5,5) (5,5) (64,3) (0,83) beam 7/8 to x 20 20 1-1/8 inches 20 (6, x 20) 20 16.7 below bottom (6,1) (75,7) (1,15) of beam (a) For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage area for which Hydraulic Design section under the Design Criteria are stated. (b) The Minimum Flow requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pres- sures are calculated using the nominal K-factor.Refer to"Hydraulic Design"in the Design Criteria section for details. (c) For NFPA 13 residential applications,the greater of 0.1 gpm/ft.2 over the design area or the flow in accordance with the criteria in this table must be used. TABLE A WET PIPE SYSTEM SERIES LFII RESIDENTIAL FLAT-PLATE CONCEALED PENDENT SPRINKLER(TY2524) NFPA 13D, 13R,AND 13 HYDRAULIC DESIGN CRITERIA DRY PIPE SYSTEM Maximum Maximum Minimum Flow and Residual Pressure) Coverage Area i° Spacing Ordinary Temp Rating Ft.x Ft. Ft. 160°F(71°C) Deflector to Installation Minimum (m x m) (m) Flow Pressure Ceiling Type Spacing GPM PSI Ft. (L/min) (bar) (m) 12 x 12 12 15 9.4 Smooth (3,7 x 3,7) (3,7) (56,8) (0,65) Ceilings 7/8 to 14 x 14 14 15 1-1/8 inches. (4,3 x 4,3) (4,3) (56,8) 96 (0,65) Beamed 16 x 16 16 16 10,7 Ceilings per (4,9 x 4,9) (4,9) (60,6) (0,74) 1i3FPA 13 R or 13 Concealed (2,4) 18 x 18 18 17 12.0 Installed in (5,5 x 5,5) (5,5) (64,3) (0,83) beam 7/8 to 20 x 20 20 1-1/8 inches 20 21 18,4 below bottom (6,1x 20) (6,1) (79,5) (1,27) of beam (a) For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage area for which Hydraulic Design section under the Design Criteria are stated. (b) The Minimum Flow requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using the nominal K-factor.Refer to"Hydraulic Design"in the Design Criteria section for details. (c) For NFPA 13 residential applications,the greater of 0.1 gpm/ft 2 over the design area or the flow in accordance with the criteria in this table must be used. TABLE B DRY PIPE SYSTEM SERIES LFII RESIDENTIAL FLAT-PLATE CONCEALED PENDENT SPRINKLER(TY2524) NFPA 13D, 13R,AND 13 HYDRAULIC DESIGN CRITERIA TFP443 Page 5 of 6 Installation Step 6.Screw on the Cover Plate/Re- Automatic sprinklers must never be tainer Assembly until its flange contacts painted, plated,coated,or otherwise The TYCO RAPID RESPONSE Series the ceiling. Do not continue to screw altered after leaving the factory.Modi- LFII Residential Flat-Plate Concealed on the Cover Plate/Retainer Assembly fied or overheated sprinklers must be Pendent Sprinklers must be installed in such that it lifts a ceiling panel out of replaced. accordance with this section: its normal position. If the Cover Plate/Retainer AssemblyCare must be exercised to avoid dam- Instructions age to the sprinklers-before,during, DGeneraletoIthe dur- cannot be engaged with the Mounting and after installation.Sprinklers dam- g installation Solder be LinknElement by h - Cup or the Cover Plate/Retainer Assem- aged by dropping,striking,wrench twist/ ing he tin can by the Support a bly cannot be engaged sufficiently to slippage,or the like,must be replaced. Cup contact the ceiling,the Sprinkler Fitting only;that is,do not apply pressure to the must be repositioned. The owner is responsible for the in- Solder Link Element(Figure 1). spection,testing,and maintenance of A leak tight 1/2 inch NPT sprinkler joint Care and their fire protection system and devices in compliance with this document, as should be obtained by applying a min - well urn-to-maximum torque of 7 to 14 well as with the applicable standards of ft.-lbs. (9,5 to 19,0 Nm). H igher levels Maintenance the National Fire Protection Association n- o t torque can distortthe sprsprinkler The TYCO RAPID RESPONSE Series dads of any o, NFPA ther authorriities havingn to the aju- q leakageimpairmentLFII Residential Flat-Plate Concealed risdiction.Contact the installing contrac- of the sprinkler. Pendent Sprinkler(TY2524) must be Do not attempt to compensate for insuf- maintained and serviced in accordance tor qr estions.nkler manufacturer regarding ficient adjustment in the Cover Plate/ with the section: any questions. rec- Retainer Assembly by under-or over- Before closing a fire protection system Automatic sprinkler systems are tightening the sprinkler. Re-adjust the main control valve for maintenance work ommended maintained aim i to be inspected,uaied tested, position of the sprinkler fitting to suit. on the fire protection system that it con- and Service accordanceby a qualified with local Step 1. Install pendent sprinklers in trols,obtain permission to shut down the tion Service in olocal the pendent position,with the center- affected fire protection system from the requirements and/or national codes. line of the sprinkler perpendicular to the proper authorities and notify all person- mounting surface. nel who may be affected by this action. Step 2. Remove the Protective Cap. Absence of a Cover Plate may delay the Step3.With sprinkler operation in a fire situation. pipe-thread sealant ap- plied to the pipe threads,and using the The owner must assure that the sprin- W-Type 18 Wrench shown in Figure 2, klers are not used for hanging any ob- install and tighten the Sprinkler/Sup- jects and that the sprinklers are only port Cup Assembly into the fitting.The cleaned by means of gently dusting with W-Type 18 Wrench accepts a 1/2 inch a feather duster;otherwise,non-opera- ratchet drive. tion in the event of a fire or inadvertent Step 4. Replace the Protective Cap by operation may result. pushing it upwards until it bottoms out When properly installed,there is a nomi- against the Support Cup.The Protec- nal 1/8 inch(3,2 mm)air gap between tive Cap helps prevent damage to the the lip of the Cover Plate and the ceil- Deflector and Guide Pins during ceiling ing,as shown in Figure 3.This air gap installation and/or during application of is necessary for proper operation of the the finish coating of the ceiling. sprinkler by allowing heat flow from a fire to pass below and above the Cover NOTICE Plate to help assure appropriate release of the Cover Plate in a fire situation.If the As long as the protective Cap remains ceiling needs repainting after sprinkler in place, the system is considered"Out installation,exercise care to ensure that Of Service" the new paint does not seal off any of Step 5.After the ceiling has been corn- the air gap.Failure to do so may impair pleted with the 2-1/2 inch(63 mm)diam- sprinkler operation. eter hole and in preparation for install- Factory painted Cover Plates must not ing the Cover Plate/Retainer Assembly, be repainted.They should be replaced, remove and discard the Protective Cap, if necessary,by factory painted units. and verify that the Deflector moves up Non-factory applied paint may adversely and down freely. delay or prevent sprinkler operation in If the sprinkler has been damaged and the event of a fire. the deflector does not move up and Do not pull the Cover Plate relative to the down freely,replace the entire sprinkler Retainer.Separation may result. assembly. Do not attempt to modify or repair a damaged sprinkler. Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced. TFP443 Page 6 of 6 Limited Warranty For warranty terms and conditions,visit www.tyco-fire.com. Ordering Procedure Contact your local distributor for avail- ability.When placing an order, indicate the full product description and Part Number(P/N). Sprinkler/Support Cup Assembly Specify:Series LFII(TY2524), K=4.9 (70,6),Residential Flat-Plate Concealed Pendent Sprinkler without Cover Plate/ Retainer Assembly,P/N 51-114-1-160 Cover Plate/Retainer Assembly Specify:Series LFII(TY2524), K=4.9 (70,6),Residential Flat-Plate Concealed Pendent Sprinkler Cover Plate/Retain- er Assembly with(specify)finish, P/N (specify): Ivory(RAL 1015) P/N 56-202-0-135 Beige(RAL 1001) P/N 56-202-2-135 Pure White(b)(RAL 9010) P/N 56-202-3-135 Signal White(a)(RAL 9003) P/N 56-202-4-135 Grey White(RAL 9002) P/N 56-202-5-135 Brown(RAL 8028) P/N 56-202-6-135 Black(RAL 9005) P/N 56-202-7-135 Brushed Brass P/N 56-202-8-135 Brushed Chrome P/N 56-202-9-135 Custom Paint P/N 56-202-X-135 (a)Previously known as Bright White. (b)Eastern Hemisphere sales only. Note: All Custom Cover Plates are painted using Sherwin Williams Interior Latex Paint. Contact TYCO Customer Service with any questions related to custom orders. Sprinkler Wrench Specify:W-Type 18 Sprinkler Wrench, P/N 56-000-1-265 GLOBAL HEADQUARTERS 11400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright©2014 Tyco Fire Products,LP. All rights reserved. t co TEFLON is trademark of The DuPont Corporation. Fire Protection Products tqco /Fire & Building Products rapid response Technical Services:Tel:(800)381-9312/Fax:(800)791-5500 HOME FIRE SPRINKLER SYSTEM 4. ,t,:" BlazeMaster CPVC Fire Sprinkler Pipe & Fittings Submittal Sheet General Technical Description Data Tyco Fire& Building Products (TFBP) Sizes BlazeMaster CPVC Pipe and Fittings 3/4"to 3" are designed exclusively for use in wet .r pipe automatic fire sprinkler systems. Maximum Working Pressure They are made from a specially Bevel- 175 psi oped thermoplastic compound com- Approvals posed of post chlorinated polyvinyl UL, FM, CUL, NSF, Dade County, . r* chloride(CPVC)resin and state of the LPCB,MEA,and the City of Los Ange- u ' art additives. TFBP BlazeMaster les. (Refer to IH-1900, Rev. 0, Janu- CPVC products are easier to install ary 2005 "Installation Instruction & than traditional steel pipe systems, Technical Handbook" for exact list- and at the same time, provide superior ing/approval information.) , , �w5 heat resistance and strength as com- pared to traditional CPVC and PVC Manufacture Source piping materials used in the plumbing U.S.A. trade. Various adapters are available Material to connect CPVC pipe to metallic pip- ing. All female pipe thread adapters . Pipe:ASTM F442, SDR 13.5 have brass inserts for durability. • Fittings: ASTM F438 (Sc-- 40) and Grooved adapters connect directly to ASTM F439(Sch.80),ASTM Fl970 grooved end valves and metallic pipe, with flexible grooved end couplings. Color Orange WARNING Tyco Fire&Building Products(TFBP) BlazeMaster CPVC Pipe and Fittings described herein must be installed and maintained in compliance with this document,as well as with the applica- ble standards of the National Fire pro - document, Association, in addition to the standards of any other authorities ha v- ing jurisdiction. Failure to do so may impair the performance of these de- vices. The owner is responsible for mainta/n- ing their fire protection system and de- vices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. BIazeMaste�is a registered trademark of Nov IP Holding Corp. Page 1 of 6 JANUARY, 2006 TFP1915 Page 2 of 6 TFPI915 NOMINAL AVERAGE AVERAGE WEIGHT WATER SIZE O.D. I.D. lbs./ft. FILLED WEIGHT FT.OF PIPE WEIGHT PER LIFT lbs./ft. PER LIFT lbs. 3/4" 1.050" 0.874" 0.18 0.44 7875 1339 1" 1.315" 1.101' 0.26 0.67 5040 1320 1-1/4" 1.660" 1.394" 0.42 1.08 2835 1191 1-1/2" 1.900" 1.598" 0.54 1.41 2205 1213 2" 2.375" 2.003" 0.84 2.20 1260 1084 2-1/2" 2.875" 2.423" 1.26 3.26 1215 1531 3" 3.500" 2.952" 1.87 4.83 720 1344 FIGURE 1—PIPE DIMENSIONS Installation Care and Tyco Fire and Building Products Maintenance (TFBP) BlazeMaster CPVC Pipe and Fittings are to be installed in accord- The owner is responsible for the fin- ance with IH-1900, Rev. 0, January spection, testing, and maintenance of 2005"Installation Instruction&Techni- their fire protection system and de- cal Handbook". vices in compliance with this docu- ment, as well as with the applicable standards of the National Fire Protec- tion Association (e.g., NFPA 25), in addition to the standards of any authority having jurisdiction. The in- stalling contractor or product manufac- turer should be contacted relative to any questions. It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspection Service in accordance with local requirements and/or national codes. NOTES Before closing a fire protection system control valve for inspection or mainte- nance work on the fire protection sys- tem that it controls,permission to shut down the affected fire protection sys- tem must first be obtained from the proper authorities and all personnel who may be affected by this action must be notified. After placing a fire protection system in service,notify the proper authorities and advise those responsible formoni- toring proprietary and/or central sta- tion alarms. TFP1915 Page 3 of 6 FITTING PART NOMINAL SIZE NOMINAL TAKE-OUT WEIGHT TYPE NUMBER (TIO) SCHD. (lb.) TEE 80000 3/4" 5/8" 40 0.11 T/O 80001 1" 11/16" 40 40 0.19 J f-- 80002 1-1/4" 7/8" 0.26 INIIIIIII 80003 1-1/2" 1-1/16" 80 0.51 ..11.- 80004 2" 1-3/8" 80 0.90 T/O ■■ T/0 80005 2-1/2" 1-9/16" 80 1.59 80006 3" 1-13/16" 80 2.41 XxYxZ X Y Z 80132 3/4"x 3/4"x 1" 3/4" 3/4" 5/8" 40 0.14 80133 1"x 3/4"x 3/4" 9/16" 9/16" 3/4" 40 0.14 80134 1"x 3/4"x 1" 3/4" 11/16" 3/4" 40 0.17 80260 1"x 1"x 3/4" 5/8" 5/8" 13/16" 40 0.16 80135 1-1/4"x 1"x 3/4" 5/8" 5/8" 15/16" 40 0.21 80136 1-1/4"x 1"x 1" 3/4" 3/4" 15/16" 40 0.22 80137 1-1/4"x 1"x 1-1/4" 15/16" 15/16" 7/8" 40 0.26 REDUCING TEE 80261 1-1/4"x 1-1/4"x 3/4" 5/8" 5/8" 7/8" 40 0.23 80262 1-1/4"x 1-1/4"x 1" 3/4" 3/4" 7/8" 40 0.26 Z 80138 1-1/4"x 1-1/4"x 1-1/2" 1" 1" -0 T/0 1" 80 0.43 I I 80140 1-1/2"x 1-1/4"x 3/4" 9/16" 9/16" 1" 80 0.36 .me80141 1-1/2"x 1-1/4"x 1" 9/16" 9/16" 1-1/16" 80 0.38 III 80263 1-1/2"x 1-1/2"x 3/4" 9/16" 9/16" 1" 80 0.36 X-111111-Y I 80264 1-1/2"x 1-1/2"x 1" 9/16" 9/16" 1-1/16" 80 0.38 - J.. � 80275 1-1/2"x 1-1/2"x 1-1/4" 7/8" 7/8" 1" 80 0.45 T/0 T/0 80265 2"x 2"x 3/4" 3/4" 3/4" 1-3/8" 80 0.61 80266 2"x 2"x 1" 7/8" 7/8" 1-3/8" 80 0.66 80274 2"x 2"x 1-1/4" 1-1/16" 1-1/16" 1-3/8" 80 0.74 80267 2"x 2"x 1-1/2" 1-1/8" 1-1/8" 1-3/8" 80 0.78 80271 2-1/2"x 2-1/2"x 1" 1-9/16" 1-9/16" 1-9/16" 80 1.43 80272 2-1/2"x 2-1/2"x 1-1/4" 1-9/16" 1-9/16" 1-9/16" 80 1.46 80273 2-1/2"x 2-1/2"x 1-1/2" 1-9/16" 1-9/16" 1-9/16" 80 1.48 80276 2-1/2"x 2-1/2"x 2" 1-9/16" 1-9/16" 1-9/16" 80 1.50 80270 3"x 3"x 1-1/2" 1-13/16" 1-13/16" 1-13/16" 80 2.28 80268 3"x 3"x 2" 1-13/16" 1-13/16" 1-3/4" 80 2.25 80269 3"x 3"x 2-1/2" 1-13/16" 1-13/16" 1-13/16" 80 2.44 CROSS&REDUCING CROSS 80009 3/4" 9/16" 40 0.13 80010 1" 11/16" 40 0.23 )MI T/0 80011 1-1/4" 15/16" 40 0.34 -. --In 80012 1-1/2" 1-1/16" 80 0.67 -101-■ 80013 2" 1-5/16" 80 1.00 d41qIl�- 80014 2-1/2" 1-9/16" 80 1.91 U T/0 80008 3" 1-13/16" 80 2.89 T/0 ■■ T/0 80015 1"x 1"x 3/4"x 3/4" 7/8" 40 0.28 90°ELBOW& 80025 3/4" 5/8" 40 0.09 REDUCING ELBOW 80026 1" 3/4" 40 0.14 80027 1-1/4" 7/8" 40 0.21 X 80028 1-1/2" 1-1/16" 80 0.40 �„/ T/0 80029 2" 1-5/16" 80 0.79 O . - 80030 2-1/2" 1-9/16" 80 1.14 MEM .4Y 80031 3" 1-13/16" 80 1.82 XxY X Y - -T/0 80032 1"x 3/4" 11/16" 13/16" 40 0.16 FIGURE 2-FITTING DIMENSIONS(Part I of 4) Page 4 of.6 TFPI915 FITTING PART NOMINAL TAKE-OUT TYPE NUMBER NOMINAL SIZE SCHD. WEIGHT (T/O) (lb.) 45°ELBOW 80050 3/4" 3/8" 40 0.08 T/O 80051 1" 3/8" Q� 80052 1-1/4" 3/4" 40 0.110 40 0.20 ,�r 80053 1-1/2" 1/2" 80 0.31 T/O'S = 80054 2" 3/4" 80 0.56 80055 2-1/2" 13/16" 80 0.89 80056 3" 1" 80 1.19 80075 3/4" 1/8" 40 0.07 COUPLING& 80076 1" 1/8" 40 0.11 REDUCING COUPLING 80077 1-1/4" 3/16" 40 0.12 '<'' 80078 1-1/2" 3/16" 80 0.25 80079 2" 3/16" 80 0.38 ,r7. 1 80080 2-1/2" 1/4" 80 0.67 -I-T/O 80081 3" 3/16" 80 0.91 80220 1"x 3/4" 1/8" 40 0.08 80200 1"x3/4" 7/16" 40 0.04 80201 1-1/4"x 3/4" 1/2" 40 0.11 80202 1-1/4"x 1" 5/16" 40 0.12 80203 1-1/2"x 3/4" 5/8" 80 0.16 80204 1-1/2"x 1" 1/2" 80 0.14 REDUCER BUSHING 80205 1-1/2"x 1-1/4" 3/8" 80 0.17 80206 2"x 3/4" 13/16" li i 80207 80 0.27 2"x 1" 11/16" 80 0.26 80208 2"x 1-1/4" 9/16" 80 0.24 -'r',L 80209 2"x 1-1/2" 7/16" 80 0.19 F-T/O 80215 2-1/2"x 1" 15/16" 80 0.42 80214 2-1/2"x 1-1/4" 13/16" 80 0.45 80213 2-1/2"x 1-1/2" 11/16" 80 0.46 80211 2-1/2"x 2" 5/8" 80 0.29 80210 3"x 2" 3/4" 80 0.72 80212 3"x 2-1/2" 1/2" 80 0.47 Cpp 80100 3/4" 5/16" 40 0.04 80101 1" 3/8" 40 0.06 80102 1-1/4" 7/16" 40 0.10 80103 1-1/2" 11/16" 80 0.20 e'.,• 1 80104 2" 5/8" 80 0.31 T/O-I 80105 2-1/2" 7/8" 80 0.58 80106 3" 1" 80 0.88 GROOVED T/0 PIPE O.D. COUPLING ADAPTER 80160 1-1/4"x 1-1/4"Groove 2-5/16" 1-1/4"(1.660") 40 0.78 80161 1-1/2"x 1-1/2"Groove 2-5/16" 1-1/2"(1.900") 80 0.95 PIPE 80162 2"x 2"Groove 2-5/16" O 2"(2.375") 80 1.42 .D. `i`,,`\" 80163 2-1/2"x 2-1/2"Groove 2-5/16" 2-1/2"(2.875") 80 2.28 80164 3"x 3"Groove 2-1/4" 3"(3.500") 80 3.00 -T/O-I 80169 2-1/2"x 76,1 mm Groove 2-5/16" 76,1 mm(3.000") 80 2.28 FIGURE 2-FITTING DIMENSIONS(Part 2 of 4) TFP1915 Page 5 of 6 FITTING PART NOMINAL SIZE NOMINAL TAKE-OUT WEIGHT TYPE NUMBER (I/O) SCHD. (lb.) SPRINKLER HEAD ADAPTER 80175E 3/4"x 1/2"NPT 7/16" 80 0.20 80176E 1"x 1/2"NPT 7/16" 80 0.22 F""` 80175WL 3/4"x 1/2"NPT 7/16" 40 0.16 ''' 80179 1"x 3/4"NPT 13/16" 40 0.43 T/O SPRINKLER HEAD ADAPTER fr-`x 80175W 3/4"x1/2"NPT 1/2" 40 0.19 80176W 1"x 1/2"NPT 1/2" 40 0.18 — I/O SPRINKLER HEAD ADAPTER(SPIGOT) _J �� 80177L 3/4"x 1/2"NPT 1/2" 40 0.16 �11gg 80178 1"x 1/2"NPT 9/16" 40 0.20 �j��„ 80180 1"x3/4"NPT 7/8" 40 0.40 —I —I/O FEMALE ADAPTER ,,,,, 80142 3/4"x 314"NPT �.\\\\\ 13/16" 40 0.41 80145 1'x 1"NPT 7!8" 40 0.63 80146 1-1/4"x 1-1/4"NPT 1-1/8" 40 1.03 ,,,, \\\\ 80147 1-1/2"x 1-1/2"NPT 1-3/8" 80 1.42 80148 2"x 2"NPT 1-11/16" 80 2.66 — —T/O MALE ADAPTER iii, 80157 3/4"x 3/4"NPT 1-5/16" 40 0.33 80158 1'x 1"NPT 1-3/8" 40 0.56 T/O__I XxYxZ X Y Z SPRINKLER HEAD ADAPTER TEE 80250 3/4"x 3/4"x 1/2"NPT 9/16" 9/16" 1" 40 0.22 Z 80251 1"x 1"x 1/2"NPT 11/16" 11/16" 1-3/16" 40 0.29 ;_=i T/O 80249 1"x 1"x 1"NPT 15/16" 15/16" 1-9/16" 40 0.73 . si .......A11114.......... - 80256 1-1/4"x 1"x 1/2"NPT 7/16" 9/16" 1-5/16" 40 0.30 - 80252 1-1/4"x 1-1/4"x 1/2"NPT 7/16" 7/16" 1-5/16" 40 0.31 X -■■-Y 80257 1-1/2"x 1-1/4"x 1/2"NPT 1/2" 11/16" 1-7/16" 80 0.43 '4wAI,.,. 80254 1-1/2"x 1-1/2"x 1/2"NPT 1/2" 1/2" 1-7/16" 80 0.46 I/O 'III T/O 80258 2"x 1-1/2"x 1/2"NPT 1/2" 5/8" 1-11/16" 80 0.56 80253 2"x 2"x 1/2"NPT 1/2" 1/2" 1-11/16" 80 0.62 FIGURE 2—FITTING DIMENSIONS(Part 3 of 4) Page 6 of 6 TFPI915 FITTING PART NOMINAL SIZE NOMINAL TAKE-OUT WEIGHT TYPE NUMBER (TIO) SCHD. (lb.) BACK-TO-BACK TEE X x Y x Z X Y,Z X / e T/O I y' 4 80459 1"x 1/2"NPT x 1/2"NPT 5/8" 1-5/16" 40 0.48 �"III Z} 80460 1"x 1/2"NPTx 1/2"NPT 5/8" 1-3/16" 40 0.46 T/0 T/0 BACK-TO-BACK CROSS X x Y x Z x W X,Y W x TIO Z J!kfIII HIE I !!!W 80462 1"x 1"x 1/2"NPT x 1/2"NPT 5/8" 1-3/16" 40 0.46 ♦�— 80463 1"x 1"x 1/2"NPT x 1/2"NPT 5/8" 1-5/16" 40 0.47 T/O �� II T/O T/O SPRINKLER HEAD X x Y X Y ADAPTER 90°ELBOW Y =� T/0 t i 80199 or 80198 3/4"x 1/2"NPT 9/16" 1" 40 0.20 . - 1"x 1/2"NPT 3/4" 1-1/4" 40 0.26 ...gm x 1 80196 1"x 3/4"NPT 1-1/16" 1-7/16" 40 0.26 — —T/O FIGURE 2—FITTING DIMENSIONS(Part 4 of 4) by TFBP to be defective shall be either of merchantability and fitness for a par- Limited repaired or replaced, at TFBP's sole ticular purpose. Warranty option. TFBP neither assumes, nor authorizes any person to assume for it, This limited warranty sets forth the ex- any other obligation in connection with failure remedy for claims based on Products manufactured by Tyco Fire& the sale of products or parts of prod- failure of or defect in products, materi- Building Products (TFBP) are war- ucts.TFBP shall not be responsible for als or components, whether the claim ranted solely to the original Buyer for sprinkler system design errors or inac- is made in contract, tort, strict liability ten(10)years against defects in mate- curate or incomplete information sup- or any other legal theory. rial and workmanship when paid for plied by Buyer or Buyer's repre- This warranty will apply to the full ex- and properly installed and maintained sentatives. tent permitted by law.The invalidity, in under normal use and service. This whole orpart, of warranty will expire ten (10) years In no event shall TFBP be liable, in any portion of this from date of shipment by TFBP. No contract, tort, strict liability or under warranty will not affect the remainder. warranty is given for products or com any other legal theory, for incidental, ponents manufactured by companies indirect,special or consequential dam not affiliated by ownership with TFBP ages,including but not limited to labor or for products and components which charges, regardless of whether TFBP have been subject to misuse,improper was informed about the possibility of installation, corrosion, or which have such damages, and in no event shall not been installed, maintained, modi- TFBP's liability exceed an amount fied or repaired in accordance with ap- equal to the sales price. plicable Standards of the National Fire The foregoing warranty is made in lieu Protection Association, and/or the of any and all other warranties. ex- standards of any other Authorities press or implied. including warranties Having Jurisdiction. Materials found TYCO FIRE&BUILDING PRODUCTS,451 North Cannon Avenue,Lansdale, Pennsylvania 19446 tqco PrOre„&„Bsui Fldingft rapid response Technical Services:Tel:(800)381-9312/Fax:(800)791-5500 HOME FIRE SPRINKLER SYSTEM BlazeMaster CPVC Fire Sprinkler Pipe & Fittings Submittal Sheet General Technical Description Data Tyco Fire& Building Products (TFBP) Sizes BlazeMaster CPVC Pipe and Fittings 3/4"to 3" are designed exclusively for use in wet si pipe automatic fire sprinkler systems. Maximum Working Pressure They are made from a speciallyBevel- 175 psi oped thermoplastic compound corn Approvals posed of post chlorinated polyvinyl UL, FM, CUL, NSF, Dade County, '.4s:44.11":7,'-, : chloride(CPVC)resin and state of the LPCB,MEA,and the City of Los Ange- art additives. TFBP BlazeMaster les. (Refer to IH-1900, Rev. 0, Janu- CPVC products are easier to install ary 2005 "Installation Instruction & than traditional steel pipe systems, Technical Handbook" for exact list- and at the same time,provide superior ing/approval information.) , heat resistance and strength as com- pared to traditional CPVC and PVC Manufacture Source piping materials used in the plumbing U.S.A. trade. Various adapters are available Material to connect CPVC pipe to metallic pip- ing. All female pipe thread adapters • Pipe:ASTM F442, SDR 13.5 have brass inserts for durability. • Fittings: ASTM F438 (Sch. 40) and Grooved adapters connect directly to ASTM F439(Sch.80),ASTM Fl970 grooved end valves and metallic pipe, with flexible grooved end couplings. Color Orange WARNING Tyco Fire&Building Products(TFBP) BlazeMaster CPVC Pipe and Fittings described herein must be installed and maintained in compliance with this document,as well as with the applica- ble standards of the National Fire Pro- tection Association, in addition to the standards of any other authorities hav- ing jurisdiction. Failure to do so may impair the performance of these de- vices. The owner is responsible for maintain- ing their fire protection system and de- vices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. BlazeMaster®is a registered trademark of Noveon IP Holding Corp. Page 1 of 6 JANUARY, 2006 TFP1915 Page 2 of 6 TFP1915 NOMINAL AVERAGE AVERAGE WEIGHT WATER FILLED WEIGHT FT.OF PIPE WEIGHT PER LIFT SIZE O.D. I.D. lbs./ft. lbs./ft. PER LIFT lbs. 3/4" 1.050" 0.874" 0.18 0.44 7875 1339 1" 1.315" 1.101' 0.26 0.67 5040 1320 1-1/4" 1.660" 1.394" 0.42 1.08 2835 1191 1-1/2" 1.900" 1.598" 0.54 1.41 2205 1213 2" 2.375" 2.003" 0.84 2.20 1260 1084 2-1/2" 2.875" 2.423" 1.26 3.26 1215 1531 3" 3.500" 2.952" 1.87 4.83 720 1344 FIGURE 1—PIPE DIMENSIONS Installation Care and Tyco Fire and Building Products Maintenance (TFBP) BlazeMaster CPVC Pipe and Fittings are to be installed in accord- The owner is responsible for the fin- ance with IH-1900, Rev. 0, January spection, testing, and maintenance of 2005"Installation Instruction&Techni- their fire protection system and de- cal Handbook". vices in compliance with this docu- ment, as well as with the applicable standards of the National Fire Protec- tion Association (e.g., NFPA 25), in addition to the standards of any authority having jurisdiction. The in- stalling contractor or product manufac- turer should be contacted relative to any questions. It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspection Service in accordance with local requirements and/or national codes. NOTES Before closing a fire protection system control valve for inspection or mainte- nance work on the fire protection sys- tem that it controls,permission to shut down the affected fire protection sys- tem must first be obtained from the proper authorities and all personnel who may be affected by this action must be notified. • After placing a fire protection system in service,notify the proper authorities and advise those responsible for moni- toring proprietary and/or central sta- tion alarms. TFP191 S Page 3 of 6 FITTING PART NOMINAL TAKE-OUT TYPE NUMBER NOMINAL SIZE SCHD. WEIGHT (T/0) (lb.) TEE 80000 3/4" 5/8" ' J 80001 1" 11/16^ 40 0.11 ( T/W0 _ 40 0.19 MIMEj- 80002 1-1/a" 7/8" 40 0.26 80003 1-1/2" 1-1/16" 80 0.51 WJ�N 80004 2" 1-3/8" 80 0.90 T/O ■■ T/O 80005 2-1/2" 1-9/16" 80 1.59 80006 3" 1-13/16" 80 2.41 XxYxZ X Y Z 80132 3/4"x 3/4"x 1" 3/4" 3/4" 5/8" 40 0.14 • 80133 1"x 3/4"x 3/4" 9/16" 9/16" 3/4" 40 0.14 80134 1"x 3/4"x 1" 3/4" 11/16" 3/4" 40 0.17 80260 1"x 1"x 3/4" 5/8" 5/8" 13/16" 40 0.16 80135 1-1/4"x 1"x 3/4" 5/8" 5/8" 15/16" 40 0.21 80136 1-1/4"x 1"x 1" 3/4" 3/4" 15/16" 40 0.22 80137 1-1/4"x 1"x 1-1/4" 15/16" 15/16" 7/8" 40 0.26 REDUCING TEE 80261 1-1/4"x 1-1/4"x 3/4" 5/8" 5/8" 7/8" 40 0.23 Z 80262 1-1/4"x 1-1/4"x 1" 3/4" 3/4" 7/8" 40 0.26 T/O 80138 1-1/4"x 1-1/4"x 1-1/2" 1" 1" 1" 80 0.43 aaIfr- ., 80140 1-1/2"x 1-1/4"x 3/4" 9/16" 9/16" 1" 80 0.36 80141 1-1/2"x 1-1/4"x 1" 9/16" 9/16" 1-1/16" 80 0.38 80263 1-1/2"x 1-1/2"x 3/4" 9/16" 9/16" 1" 80 0.36 X.1111111._Y 1 80264 1-1/2"x 1-1/2"x 1" J.. 9/16" 9/16" 1-1/16" 80 0.38 80275 1-1/2"x 1-1/2"x 1-1/4" 7/8" 7/8" 1" 80 0.45 T/O T/0 80265 2"x 2"x 3/4" 3/4" 3/4" 1-3/8" 80 0.61 80266 2"x 2"x 1" 7/8" 7/8" 1-3/8" 80 0.66 80274 2"x 2"x 1-1/4" 1-1/16" 1-1/16" 1-3/8" 80 0.74 80267 2"x 2"x 1-1/2" 1-1/8" 1-1/8" 1-3/8" 80 0.78 80271 2-1/2"x 2-1/2"x 1" 1-9/16" 1-9/16" 1-9/16" 80 1.43 80272 2-1/2"x 2-1/2"x 1-1/4" 1-9/16" 1-9/16" 1-9/16" 80 1.46 80273 2-1/2"x 2-1/2"x 1-1/2" 1-9/16" 1-9/16" 1-9/16" 80 1.48 80276 2-1/2"x 2-1/2"x 2" 1-9/16" 1-9/16" 1-9/16" 80 1.50 80270 3"x 3"x 1-1/2" 1-13/16" 1-13/16" 1-13/16" 80 2.28 80268 3"x 3"x 2" 1-13/16" 1-13/16" 1-3/4" 80 2.25 80269 3"x 3"x 2-1/2" 1-13/16" 1-13/16" 1-13/16" 80 2.44 CROSS&REDUCING CROSS 80009 3/4" 9/16" 40 0.13 80010 �.. -� T/0 80011 - 1-1/4" 15/16" 40 0.34 -. -- 80012 1-1/2" 1-1/16" 80 0.67 '.11111111T '!.■ 80013 2" 1-5/16" 80 1.00 II 80014 2-1/2" 80 1.91 Il.,il T/0 80008 3" 1-9/16" 1-13/16" 80 2.89 T/0 ■■ T/0 80015 1"x 1"x 3/4"x 3/4" 7/8" 40 0.28 90°ELBOW& 80025 3/4" 5/8" 40 0.09 REDUCING ELBOW 80026 1" 3/4" 40 0.14 80027 1-1/4" X 7B" 40 0.21 j../ T/0 80029 1-2"2„80 0.49 1-1/16"1-5/16" 80 0.79 j 80030 2-1/2" 1-9/16" it 80 1.14 vimY 80031 3" 1-13/16" 80 1.82 4'IN XxY X Y - -T/0 80032 1"x 3/4" 11/16" 13/16" 40 0.16 FIGURE 2-FITTING DIMENSIONS(Part 1 of 4) Page 4 of 6 TFP1915 FITTING PART NOMINAL TAKE-OUT TYPE NUMBER NOMINAL SIZE (T/O) SCHD. WEIGHT (lb.) 45°ELBOW 80050 3/4" 3/8" 40 0.08 T/O3/8" 80051 1" 40 0.11 80052 1-1/4" 3/4" 40 0.20 MIMII 80053 1-1/2" 1/2" 80 0.31 T/O trill. 80054 2" 3/4" 80 0.56 ��Ii� 80055 2-1/2" 13/16" 80 0.89 80056 3" 1" 80 1.19 80075 3/4" 1/8" 40 0.07 COUPLING& 80076 1" 1/8" 40 0.11 REDUCING COUPLING 80077 1-1/4" 3/16" 40 0.12 •"s," 80078 1-1/2" 3/16" 80 0.25 80079 2" 3/16" 80 0.38 •-rr'r 80080 2-1/2" 1/4" 80 0.67 -F-T/O 80081 3" 3/16" 80 0.91 80220 1"x 3/4" 1/8" 40 0.08 80200 1"x 3/4" 7/16" 40 0.04 80201 1-1/4"x 3/4" 1/2" 40 0.11 80202 1-1/4"x 1" 5/16" 40 0.12 80203 1-1/2"x 3/4" 5/8" 80 0.16 80204 1-1/2"x1" 1/2" 80 0.14 REDUCER BUSHING 80205 1-1/2"x 1-1/4" 3/8" 80 0.17 80206 2"x 3/4" 13/16" 80 0.27 li i 80207 2"x 1" 11/16" 80 0.26 80208 2"x 1-1/4" 9/16" 80 0.24 ",(z,L 80209 2"x 1-1/2" 7/16" 80 0.19 ---I I---T/O 80215 2-1/2"x 1" 15/16" 80 0.42 80214 2-1/2"x 1-1/4" 13/16" 80 0.45 80213 2-1/2"x 1-1/2" 11/16" 80 0.46 80211 2-1/2"x 2" 5/8" 80 0.29 80210 3"x 2" 3/4" 80 0.72 80212 3"x2-1/2" 1/2" 80 0.47 CAP 80100 3/4" 5/16" 40 0.04 80101 1" 3/8" 40 0.06 i, 80102 1-1/4" 7/16" 40 0.10 80103 1-1/2" 11/16" 80 0.20 ///��/ 80104 2" 5/8" 80 0.31 T/O--I L 80105 2-1/2" 7/8" 80 0.58 80106 3" 1" 80 0.88 GROOVED T/O PIPE O.D. COUPLING ADAPTER `�" "`� 80160 1-1/4"x 1-1/4"Groove 2-5/16" 1-1/4"(1.660") 40 0.78 I I 80161 1-1/2"x 1-1/2"Groove 2-5/16" 1-1/2"(1.900") 80 0.95 PIPE 80162 2"x 2"Groove 2-5/16" O.D. 2"(2.375") 80 1.42 "`„"` 80163 2-1/2"x 2-1/2"Groove 2-5/16" 2-1/2"(2.875") 80 2.28 80164 3"x 3"Groove 2-1/4" 3"(3.500") 80 3.00 -T/O-I 80169 2-1/2"x 76,1 mm Groove 2-5/16" 76,1 mm(3.000") 80 2.28 FIGURE 2-FITTING DIMENSIONS(Part 2 of 4) TFP1915 Page 5 of 6 FITTING PART NOMINAL SIZE NOMINAL TAKE-OUT WEIGHT TYPE NUMBER (TIO) SCHD. (lb.) SPRINKLER HEAD ADAPTER 80175E 3/4"x 1/2"NPT 7/16" 80 0.20 80176E 1"x 1/2"NPT 7/16" 80 0.22 h``\ 80175WL 3/4"x 1/2"NPT 7/16" 40 0.16 '" 80179 1"x 3/4"NPT 13/16" 40 0.43 T/O SPRINKLER HEAD ADAPTER Arimu 80175W 3/4"x 1/2"NPT 112" 40 0.19 =\ 80176W 1"x 1/2"NPT 1/2" 40 0.18 — T/O SPRINKLER HEAD ADAPTER(SPIGOT) � ��, 80177L 3/4"x 1/2"NPT 1/2" 40 0.16 MjOM 80178 1"x 1/2"NPT 9/16" 40 0.20 ���• 80180 1"x3/4"NPT 7/8" 40 0.40 —I T/O FEMALE ADAPTER 'z r / \\ 80142 3/4"x 3/4"NPT 13/16" 40 0.41 80145 80146 1'x 1"NPT 7/8" 40 0.63 1-1/4"x 1-1/4"NPT 1-1/8" 40 1.03 80147 1-1/2"x 1-1/2"NPT 1-3/8" 80 1.42 ,,,..,./ "\\\\\ 80148 2"x 2"NPT1-11/16" 80 2.66 — —T/O MALE ADAPTER .... 80157 3/4"x 3/4"NPT 1-5/16" 40 0.33 zrzz 80158 1'x 1"NPT 1-3/8" 40 0.56 T/O XxYxZ X Y Z SPRINKLER HEAD 80250 3/4"x 3/4"x 1/2"NPT 9/16" 9/16" 1" 40 0.22 ADAPTER TEE Z 80251 1"x 1"x 1/2"NPT 11/16" 11/16" 1-3/16" 40 0.29 ` 15/16" 15/16" 1-9/16" 40 0.73 ;_=i T/O 80249 1"x 1"x 1"NPT ... ...:411111110.. . 80256 1-1/4"x 1"x 1/2"NPT 7/16" 9/16" 1-5/16" 40 0.30 -`+_ 80252 1-1/4"x 1-1/4"x 1/2"NPT 7/16" 7/16" 1-5/16" 40 0.31 X =En=Y 80257 1-1/2"x 1-1/4"x 1/2"NPT 1/2" 11/16" 1-7/16" 80 0.43 Apr .rAmr.VIMIII 80254 1-1/2"x 1-1/2"x 1/2"NPT 1/2" 1/2" 1-7/16" 80 0.46 T/0 •• T/O 80258 2"x 1-1/2"x 1/2"NPT 1/2" 5/8" 1-11/16" 80 0.56 80253 2"x 2"x 1/2"NPT 1/2" 1/2" 1-11/16" 80 0.62 FIGURE 2—FITTING DIMENSIONS(Part 3 of 4) Page 6 of 6 TFP1915 FITTING PART WEIGHT NOMINAL SIZE NOMINAL TAKE-OUT TYPE NUMBER (T/O) SCHD. (lb.) BACK-TO-BACK TEE X x Y x Z X Y Z X T/O i Y' .4 '�,I 80459 1"x 1/2"NPT x 1/T NPT 5/8" 1-5/16" 40 0.48 I! z I 80460 1"x 1/2"NPTx 1/2"NPT 5/8" 1-3/16" 40 0.46 T/O T/O BACK-TO-BACK CROSS XxYxZxW X,Y Z W x T/O IIIIIIMEMMIIIii i��ra` � . 11 w 80462 1"x 1"x 1/2"NPTx 1/2"NPT 5/8" 1-3/16" 40 0.46 .._. �j 80463 1"x 1"x 1/2"NPT x 1/2"NPT 5/8" 1-5/16" 40 0.47 T/O i„1 T/O T/O SPRINKLER HEAD X x Y X Y ADAPTER 90°ELBOW Y ,;'0 T/0 I 0 r m 80199 3/4"x 1/2"NPT 9/16" 1" 40 0.20 .� _ 80198 1"x 1/2"NPT 3/4" 1-1/4" 40 0.26 ����'-X I 80196 1"x 3/4"NPT 1-1/16" 1-7/16" 40 0.26 - -T/O FIGURE 2—FITTING DIMENSIONS(Part 4 of 4) Limited by TFBP to be defective shall be either of merchantability and fitness for a par- repaired or replaced, at TFBP's sole ticular purpose. Warranty option. TFBP neither assumes, nor authorizes any person to assume for it, warranty This limited sets forth the ex- clusive remedy for claims based on any other obligation in connection with failure of or defect in products, materi- Products manufactured by Tyco Fire& the sale of products or parts of prod- Building Products (TFBP) are war- ucts.TFBP shall not be responsible for als or components, whether the claim ranted solely to the original Buyer for sprinkler system design errors or inac- is made in contract, tort, strict liability ten(10)years against defects in mate- curate or incomplete information sup- or any other legal theory. rial and workmanship when paid for plied by Buyer or Buyer's repre- This warranty will apply to the full ex- and properly installed and maintained sentatives. tent permitted by law.The invalidity, in under normal use and service. This whole or part, of any portion of this warranty will expire ten (10) years In no event shall TFBP be liable, in warranty will not affect the remainder. from date of shipment by TFBP. No contract, tort, strict liability or under warranty is given for products or com- any other legal theory, for incidental, ponents manufactured by companies indirect,special or consequential dam- not affiliated by ownership with TFBP ages, including but not limited to labor or for products and components which charges, regardless of whether TFBP have been subject to misuse,improper was informed about the possibility of installation, corrosion, or which have such damages, and in no event shall not been installed, maintained, modi- TFBP's liability exceed an amount fied or repaired in accordance with ap- equal to the sales price. plicable Standards of the National Fire The foregoing warranty is made in lieu Protection Association, and/or the of any and all other warranties. ex- standards of any other Authorities press or implied. including warranties Having Jurisdiction. Materials found TYCO FIRE&BUILDING PRODUCTS,451 North Cannon Avenue,Lansdale,Pennsylvania 19446 Eddythread 40 AT Lige40 R That Hashtwa ight Corrosion Resistance Ratioeplacement ofPipe 1.0 Bull Moose Tube Company has been making pipe for a long time and is recognized as a producer of quality pipe products. Eddythread 40 is designed with the same thoroughness as our other fine pipe products and now our customers have an option to buy a carefully designed replacement for Schedule 40 that: • Has a Corrosion Resistance Ratio of 1.0 • Has a Pressure Rating of 300 psi • Is Lighter Weight Than Schedule 40 • Is Approved by Factory Mutual and Listed by Underwriters Laboratories • Is Produced in Accordance to ASTM A-135 and A-795 • Can be Used With Standard Schedule 40 Threaded Fittings, Couplings and Valves • Is Produced From Steel With Excellent Properties of Strength and Threadability • Can be Used in Wet, Dry, Preaction, and Deluge Type Sprinkler Systems* • Offers Lower Freight Costs EDDYTHREAD 40 SPECIFICATIONS NOMINALSIZE(in) (l (in) BUNDLESIZE 1 1.461 1.083 70 1 1/4 2.070 - ; 1.418 51 2.547 .,1.654' 44 2 3.308 2.123 30 CORROSION RESISTANCE RATIOS MNL PIPE SIZE(in) SCHEDULE 40 2 EDDYTHREAD 1 1.00 1.00 1 .1/4 1.00 1.00 1 1/2 , 1.00 1.00 .. 2 1.00 1.00 *Eddythread 40 can be hot dipped galvanized to meet FM's requirement for dry systems ell 1819 Clarkson Road For additional information, Chesterfield,MO 63017 contact your salesperson today at Ceuse II BULL MOOSE Tl IOC ComPANY (800)325-4467 (800)325-4467 or(636)537-2600 LISTED - FAX: .bull 537-2645 oosetu inthe USA,o2 466froCanada A�� www.bullmoosetube.com call(800)882-4666 company e-mail:sales a,bullmoosetube.com APPROVED All information contained herein is accurate as known at the tune of publication. Bull Moose Tube reserves the right to change product specifications without notice and without incurring obligation. 8/08 ES-A-20008 Series 2000B �l Valve S Double Check `] heck v Cave Assemblies FIRE&WATERWORKS Sizes: 1/2" —2" (15—50mm) Features �. • Ease of maintenance with only one cover 2"20006 HC • • Top entry (50mm) • Replaceable seats and seat discs • Modular construction = • Compact design • 1/2"—2"(15—50mm)Cast bronze #'^`+ ) body construction • Top mounted ball valve test cocks 3/a"20006 • Low pressure drop (20mm) • No special tools required • 1/2"—1"(15—25 mm)have Series 2000B Double Check Valve Assemblies are designed to protect drinking water sup- plies for dangerous cross-connections in accordance with national plumbing codes and tee handles water authority requirements for non-health-hazard non-potable service applications such as irrigation,fire line,or industrial processing. Available Models These valves meet the requirements of ASSE Std.1015 and AWWA Std.C510 and are Suffix: approved by the Foundation for Cross-Connection Control and Hydraulic Research at the B- Quarter turn ball valves University of Southern California. LBV- less ball valves Specifications SH- stainless steel ball valve handles A Double Check Valve Assembly shall be installed at each noted location.The assembly HC- 21/2"inlet/outlet fire hydrant fitting shall consist of two positive seating check modules with captured springs and rubber seat (2" valve) discs.The check module seats and seat discs shall be replaceable.Service of all internal components shall be through a single access cover secured with stainless steel bolts. Pressure — Temperature The assembly shall also include two resilient seated isolation valves and four top mounted, Temperature Range:33°F—140°F resilient seated test cocks.The assembly shall meet the requirements of ASSE Std. 1015 (0.5°C—60°C) and AWWA Std.C510.Approved by the Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California.Assembly shall be an Ames Maximum Working Pressure: 175psi Company Series 2000B. (12.1 bar) Approvals Standardsfi�r_r G�osip o AWWA Std.C510, IAPMO PS31 055E et C V� uS cus 1015 B64.5 '/o"-2" A WARNING (LBV Models Only) It is illegal to use this product in any plumbing Approved by the Foundation for Cross-Connection Control and Hydraulic Research at system providing water for human consumption, the University of Southern California. • such as drinking or dishwashing,in the United LBV models not listed. States.Before installing standard material prod Horizontal and vertical "flow up"approval on all sizes. uct,consult your local water authority,building pp and plumbing codes. Job Name Contractor Job Location Approval Engineer Contractor's P.O.No. Approval Representative Ames product specifications in U.S.customary units and metric are approximate and are provided for reference only.For precise measurements,please contact Ames Technical Service.Ames reserves the right to change or modify product design,construction,specifications,or materials without prior notice and without incurring any obligation to make such changes and modifications on Ames products previously or subsequently sold. amesfirewater.com Dimensions - Weights 4 - A :� o, .� =tri -1® nit -0-1■ 0 • 0 ,.----If_ N '-- ����� 11 -.I■ , 1I F - `/)i Suffix HC- Fire Hydrant Fittings dimension"A"=23W (594mm) .4- -4-1-4. G > SIZE(DN) DIMENSIONS WEIGHT A B C F G H I in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm lbs. kgs. 1/ 15 10 254 4% 117 27/16 62 5 127 33/6 85 25/16 59 21A6 52 4.5 2 3/4 20 11% 282 4 102 3% 79 63/6 157 37/6 87 2% 54 16/6 33 5 2.3 1 25 131/4 337 5% 130 4 102 7%z 191 3% 85 11'/6 43 11%6 43 12 5.4 11/4 32 16% 416 5 127 35/6 84 9%z 241 5 127 3 76 2 50 15 6.8 1% 40 16% 425 4% 124 3% 89 9% 248 513/6 148 3% 79 211/16 68 15.86 7.2 2 50 19% 495 61 159 4 102 13% 340 6% 156 37/6 87 21%6 68 25.75 11.7 Strainer sold separately Capacities kPa si As compiled from documented Foundation for Cross-Connection Control 96 1q A 11/4" (32mm) and Hydraulic Research at the University of Southern California lab tests. H 83 12 ATypical maximum system flow rate(7.5 feet/sec.,2.3 meters/sec.) 0 69 10 J kPa psi 1/2" (15mm) L 55„co 68 83 12 A H 41 6 0 69 10 0)• 28 4 . 55 8 14 z �� 41 6 A-... 0 0 CA 2 AP 0 10 20 30 40 50 60 70 80 90 100 110 120 gpm 0 28 a` 0 0 0 38 76 114 152 190 228 266 304 342 380 418 456 Ipm 5 7.5 10 15 fps 0 2 4 6 8 10 12 gpm 1.5 2.3 3.0 4.6 mps AP 0 7.6 15.2 22.8 30.4 38 45.6 1pm Flow Rate 5 7.5 10 fps 1.5 2.3 Flow Rate 3 U mps kPa psi 11/2"(40mm) kPa psi 83 12 a " (20mm) • 69 10 3/a o 152 22 co 055 8 3 124 18 m 41 6 2 96 14 28 4 ��� y 69 10ca 14 2 a 41 6 a 0 Apo 10 20 0 40 50 60 70 80 90 100 110 120 gpm 14 2 �~ 0 38 76 114 152 190 228 266 304 342 380 418 456 Ipm AP 0 5 10 15 Ze 25 30 35 40 46 50 5 7.5 10 15 fps gpm 1.5 2.3 3.0 4.6 mps 0 19 31 51 Z M 114 133 152 171 197Ipm 7.5 15 fps Flow Rate 2.3 4.6 mps kPa psi e 2"(50mm) Flow Rate 83 12 kPa psi co 110 16 A 1"(25mm) 0 69 10 J 83 12 m 55 8 m 69 10 L 41 6 3 6 H 28 4 1� N LD 41 4 a 14 2 0. 14 2 ...... 0 0 0 25 50 75 100 125 150 175 200 gpm AP 05 0 5 20 25 AP 0 95 190 285 380 475 570 665 760 1pm 9 10 15 76 95 30 133 35 40 45 190 50 55 2601 gpmm 5 7.5 . 15 fps 5 7.5 10 15 1.5 2.3 3.0 4.6 mps 1.5 2.3 3.0 4.6 fps Flow Rate mps AFlow Rate AMES FIRE&WATERWORKS A Watts Water Technologies Company USA:Backflow Tel:(978)689-6066•Fax: 978 ( )975-8350•AmesFireWater.com USA:Control Valves Tel:(713)943-0688•Fax:(713)944-9445•AmesFireWater.com Canada: Tel:(905)332-4090•Fax:(905)332-7068•AmesFireWater.ca Latin America: Tel:(52)81-1001-8600•Fax:(52)81-8000-7091 •AmesFireWater.corn ES-A-2000B 1410 ©2014 Ames Fire&Waterworks PFOR SMALL PIPE VSR_S PcJTTE.R VANE TYPE WATERFLOW The Symbol of Protection ALARM SWITCH WITH RETARD UL,ULC,CSFM Listed and NYMEA Accepted Service Pressure: Up to 300 PSI(20,7 BAR) Flow Sensitivity Range for Signal: 4-10 GPM(15-38 LPM)UL Maximum Surge: 18 FPS(5,5 m/s) Enclosure: Die-cast,red enamel finish Cover held in place with tamper resistant screws Contact Ratings: Two sets of SPDT(Form C) 10.0 Amps at 125/250 VAC 2.0 Amps at 30 VDC Resistive 10mAmps min.at 24 VDC Conduit Entrances:Two openings provided for 1/2"conduit. Individual switch compartments suitable for dissimilar voltages. Usage: Listed plastic,copper and schedule 40 iron pipe. Fits pipe sizes-1"(25mm), 1 1/4"(32mm),1 1/2"(38mm) and 2"(50mm) Stock No. 1144440 Note: 12 paddles are furnished with each unit,one for each pipe size of threaded and sweat TEE,one for 1"(25mm)CPVC, one for 1"(25mm)CPVC(Central),one for 1"threaded Nibco j CPVC,and one for 1 1/2"(38mm)threaded(Japan). Environmental Specifications: • � • NEMA-4/IP54 Rated enclosure suitable for indoor or outdoor Installation must be perfomed by qualified personnel and in use with factory installed gasket and die-cast housing when used accordance with all national and local codes and ordinances. with appropriate conduit fitting. Shock hazard. Disconnect power source before servicing. • Temperature range:40°F to 120°F,(4,5°C to 49°C)UL Serious injury or death could result. Service Use: Risk of explosion. Not for use in hazardous locations. Serious Automatic Sprinkler injury or death could result. NFPA-13 One or two family dwelling NEPA-13D Residential occupancy up to four stories NFPA-13R National Fire Alarm Code NFPA-72 Optional:Cover Tamper Switch Kit,Stock No.0090148 (See Fig.7 for terminations) Replaceable Components:Retard/Switch Assembly,stock no. 1029030 The Model VSR-S is a vane type waterfiow switch for use on wet Installation sprinkler systems that use 1"(25mm),11/4"(32mm),1'A"(38mm)or 2" These devices may be mounted in horizontal or vertical pipe. On (50mm)pipe size.The unit may also be used as a sectional waterflow horizontal pipe they should be installed on the top side of the pipe where detector on large systems. they will be accessible.The units should not be installed within 6"(15cm) The unit contains two single pole double throw snap action switches and of a valve,drain or fitting which changes the direction of the waterftow. Select the proper paddle for the pipe size and type of TEE used see Fig. an adjustable, instantly recycling pneumatic retard. The switches are actuated when a flow of 10 gallons per minute(38 LPM)or more occurs 1 for instructions on changing paddle.The unit has a 1"NPT bushing downstream of the device.The flow condition must exist for a period of for threading into a non-corrosive TEE.See Fig.2 for proper TEE size, type and installation.Use no more than three wraps of teflon tape. time necessary to overcome the selected retard period. Enclosure Screw the device into the TEE fitting as shown in.Fig.2.Care must be The VSR-S switches and retard device are enclosed in a general purpose, taken to properly orient the device for the direction of waterfiow. die-cast housing.The cover is held in place with two tamper resistant The vane must not rub the inside of the TEE or bind in any way.The screws which require a special key for removal.Afield installable cover stem should move freely when operated by hand. tamper switch is available as an option which may be used to indicate The device can also be used in copper or plastic pipe installations with unauthorized removal of the cover. See bulletin number 5401103 for installation instructions of this switch. the proper adapters so that the specified TEE fitting may be installed on the pipe run. Note:Do not leave cover off for an extended period of time. Potter Electric Signal Company,LLC•2081 Craig Road,St.Louis,MO,63146-4161•Phone:800-325-3936/Canada 888-882-1833•www.pottersignal.com PRINTED IN USA MFG.#5401206-REV G 12/08 PAGE 1 OF 3 Pi POfTER FOR SMALL PIPE V S R_S VANE TYPE WATERFLOW The Symbol of Protection ALARM SWITCH WITH RETARD Fig. I Fig.2 Retard Adjustment DO NOT LEAVE COVER OFF FOR EXTENDED PERIOD OF TIME IIII Thetimedelay is factory set at30±10 seconds. � °°�°x COVER TAMPER SWITCH The delay can be adjusted by rotating the retard — adjustment knob from 0 to the max setting(60- �' ��1'', mel :,.r,a 90 seconds).The time delay should beset at the ,��,+4 .Ii II II minimum required to prevent false alarms. #' _L 11141 4/11k 1. ,N <-r Screw the device into the tee fitting as shown. DIRECF1oN of I ,, '...,,-;;Al Care must be taken to properly orient the warER FLOW / ntowTso ���' f/`• P l� Y ARRowoN -.>J�rdevice for the direction of waterHow.On sweat �1 EUSHLNG POINTS \`, tees,no threaded bushings,inserts,or adapters L N DIRECTION OF WATERFLow 1 ,� are permitted,unless they comply with the OW.737.11 1"NET .� dimensions listed in the chart below. THREADED I a c ov ` Important-The depth to the inside bottom of ALL SIZES the tee should have the following dimensions: RUN OF MAY BE el,,,,,,..-- ) Approximate Depth Requvement There are 12 paddles furnished with each unit. THREADED OR Tee Sne Threaded Sweat CPVC One for each size of threaded,sweat or plastic SWEAT PIPE /1) P'x 1"x 1" 2 1/16" L 3/4" 2 7/16" TEE as described in Fig.2.These paddles have DIRECTION OF F (((«� i 1/4"x 1 1/4"x 1" 2 7/16" 2 7/16" N/A raised lettering that shows the pipe size and type4Ft UWen�7 .a of TEE that they are to be used with.Theproper paddlemustbeused.Thepaddlemustbeproperly 2"x 2"x 1" 3 3/16" 2 3/4" N/A Shown with optional Cover Tamper Switch Kit attached(see drawing)and the screw that holds "' i 1 the paddle must be securely tightened. Do not use more than three wraps of teflon tape. Fig.3 Switch Terminal Connections Clamping Plate Terminal Fig.7 Cover Tamper Switch Wiring `-.•-:P" 1`ro a jPP Y „� (Shown with cover in place) ��' j An uninsulated section of a single conductor should not be looped • i. around the terminal and serve as two separate connections.The wire O OV,„;,, ,,,,„„„ must be severed,thereby providing supervision of the connection in the event that the wire become dislodged from under the terminal. N.O. N.C. Failure to sever the wire may render the device inoperable risking (WI-IT) (RED) (BLK) severe property damage and loss of life. OWO#881oo1X-2 Fig.4 Typical Electrical Connections Fig.5 Fig.6 SII To remove knockouts: Breakoutthinsectionofcoverwhenwiring f E BELL 1 cOR Place screwdriver at edge of both switches from one conduit entrance. ' i, knockouts,not in the center. � POSITIVE DC OR 'I — �- HOT AC' ' IC)_it -II I.. , ci)' r 1 t!1 �:�':, WATERFLO W ZONE ON �\I. � FIRE PANEL I I `� ° SII +_ �j1 i. y. , �`\r te Notes: =\� '/ ���j �` thiA,0 1. The Model VSR-S has two switches,one can be used to operate a 1y — central station,proprietary or remote signaling unit,while the other is used to operate a local audible or visual annunciator. 2. For supervised circuits see"Switch Terminal Connections"drawing a and caution note(Fig.3). PRINTED IN USA MFG.#5401206-REV G PAGE 20F3 12/08 P POTTER FOR SMALL PIPE VSR-S VANE TYPE WATERFLOW ® The Symbol of Protection ALARM SWITCH WITH RETARD Testing Removal The frequency of inspection and testing for the Model VSR-S and its • To prevent accidental water damage,all control valves should associated protective monitoring system should be in accordance with be shut tight and the system completely drained before waterflow applicable NFPA Codes and Standards and/or the authority having detectors are removed or replaced. jurisdiction(manufacturer recommends quarterly or more frequently.) • Turn off electrical power to the detector,then disconnect wiring. An inspector's test valve(usually located at the end ofthemost remote branch • Use a wrench on the flats of the bushing.Turn the switch line)should always be used for test purposes.If there are no provisions for counterclockwise to disengage the pipe threads. testing the operation of the flow detection device on the system,application • Gently lift with your fingers,roll the vane so it will fit through the of the VSR-S is not recommended or advisable. hole while continuing to lift the waterflow detector. A minimum flow of 10 gpm(38 Lpm)is required to activate this device. • Lift detector clear of pipe. NOTICE Please advise the person responsible for testing of the A CAUTION fire protection system that this system must be tested in accordance with the testing instructions. Waterflow switches that are monitoring wet pipe sprinkler systems Maintenance shall not be used as the sole initiating device to discharge AFFF, Inspect detectors monthly for leaks. If leaks are found, replace the deluge,or chemical suppression systems.Waterfl ow switches used detector.The VSR-S waterflow switch should provide years of trouble- for this application may result in unintended discharges caused free service.The retard and switch assembly are easily field replaceable. by surges,trapped air,or short retard times. In the unlikely event that either component does not perform properly, please order replacement retard switch assembly stock#1029030.There is no maintenance required,only periodic testing and inspection. Mounting Dimensions 3.50" . 5.56" ft- GROUND SCREWS (89.0 mm) (141.2 mm) 1,01 2.00"O , A?p (50.8 mm �t : AC I_i_LI _I _d f 2.34" .......a lira (59.4 mm) IS- 4.89" � _ l - -. 1�[��C4_ h0 _ (52.3 mm) Clr '. I ' 1191 _ ___ ___ .,. O 1"-111/2 NPT a. DWG#1206-5 PRINTED IN USA MFG. 5 #401206-REV G PAGE 3 OF 3 12!08 Sprinkler Gauge 4, a 1 !► FPPI• Description ,- ""206 •.� � FPPI pressure gauges feature an impact and corrosion resistant case made from o ABS (plastic). Features phosphor bronze bourdon tube movement with white ti°° �u°° 1 °O \ enameled brass dial face with large numbers for easy reading. Dual scale to 300 �f PSI/2000Kpa. UL/ULc Listed (Sprinkler Gauge Model 111.10SP, UL Listed file � EX5232)and FM Approved. °° 4 S� ,®. // 0 - 74 Applications Standard FeaturesSpecifications • Fire sprinkler systems Design •Suitable for all media that will not EN 837-1 &ASME B40.100 Bourdon Tube Material:copper alloy C-type obstruct the pressure system or Sizes ,a, attack copper alloy parts 4" (100 mm) Pressure Connection Accuracy class Material:copper alloy Special Features t 3%% of span Vs"NPT lower mount(LM) • UL-listed (UL-393), United States (ASME B40.100 Grade B) Movement and Canada(Sprinkler Gauge Ranges Copper alloy Model 111.10SP, UL Listed file 0/80 psi, retard to 250 psi (air) Dial EX5232) 0/300 psi (air, water, air/water) White aluminum with stop pin; • Factory Mutual (FM)approved Working Pressure black and red lettering 3 • Reliable and economical Steady: 3A of full scale value P Pointer Fluctuating:%of full scale value Black aluminum Short time: full scale value Operating Temperature Case u- Ambient: -40°F to 140°F Black polycarbonate (-40°C to 60°C) Window Media: 140°F(+60°C)maximum Snap-in clear polycarbonate Temperature Error Additional error when temperature changes from reference temperature of 68°F(20°C)+0.4% for every 18°F (10°C)rising or falling. Percentage of span. 3198 LIONSHEAD AVE CARLSBAD, CA 92010 TEL+1 760 599-1168 +1 800 344-1822 FAX+1 800 344-3775 ©2012 Fire Protection Products,Inc. 11 11 11. . . . IT Model 1000 APAN DRAIN® Sectional Floor Control Test and Drain Valve c us APPROVED R 3/" 1 ii 11411 11 2" 2t' 1". " 'Y-777- 1:i,..,Wi ; 10,--4f. -, -,ta,:iii, '177; ,-777- ::„.*;,.rs:— - - '''.- — a£ 5 � , E } f- ;'ems > _ M t — PUSH , '� ,' • } TESTANDRAIN k� j y c DRAIN f4TTlac Mils AC TYPE ,4;‘,„ ® e'"> ", • i e A AGf Mt l MMlluzrN.;'A .>..r.,.,»..i.7 '.w f y 1dr U.:; S ... r l • The AGF Manufacturing Inc. Model 1000 TESTANDRAIN® MODEL 1000- FRONT VIEW,VERTICAL INSTALLATION provides both the test function and the express drain function for a wet fire sprinkler system. • The Model 1000 complies with the requirements of l FROM BRANCH NFPA-13, NFPA-13R, and NFPA-13D. trii • The Model 1000 TESTANDRAIN®is a compact single SYST'E`M ACCESS PORT handle ball valve which includes a tamper resistant test ;�, orifice and integral tamper resistant sight glasses, and is 300 PSI rated. li •i •Available in a full range of sizes from 3/a"to 2" NPT and Ail, �[O' BSPT, with all specifiable orifice sizes 3/e" (2.8K),7A5" (4.2K), STREET EL will[` 1/2" (5.6K), 17/32" (8.0K),5/a" (11.2K, ELO), 3A" (14.0K, ESFR), L))�i and K25 as required by NFPA 13,2007 Edition(see reverse). 1.x;11 • The orifice size is noted on the indicator plate and the valve features a tapped and plugged port for system access. STREET EL �� In • •A locking kit is available and can be ordered OR PIPE �� I TO DRAIN de ed with the valve I I to provide vandal resistance or prevent unintentional alarm ` activation. TO DRAIN j • Repair kits including (1) adapter gasket, (1) ball, (2)valve seats, (1)stem packing, and(1)stem washer are available for all TESTANDRAIN®valves.Valve and orifice size must RIGHT HAND/STRAIGHT INSTALLATION be specified when ordering. Reliability, Versatility, Code Compatibility TESTANDRAIN is a registered trademark of AGF Manufacturing Inc. CS1000 10/09 Model 1000 Ala c ® us F .,› TESTAN D RAI No APPROVED 300 PSI Bronze Ball Valve MODEL 1000 - PLAN VIEW FRONT VIEW - HORIZONTAL INSTALL A ► * E--0.1 II ��� I 1, 1/ACNPT CESSYSTEM ��-e � li I ACCESS PORTTO DRAIN I _:r , iI! 4TO DRAIN .116.Thsal 1 • G l 1 —�— ' 1 .- DIMENSIONS MATERIALS Orifice Size Available:3/8",7/16", 1/2", 17/32", ELO(5/8")*, ESFR(3/a")*,&K25** Handle:Steel SIZE A B C D E F G H Stem: Rod Brass Ball:C.P. Brass 3�,. 51/46" 11/2" 23/46" 35/8" 3W' 113/16" 4 '46" 6W Body: Bronze (128 mm) (37.5 mm) (57 mm) (93 mm) (86 mm) (46 mm) (117 mm) (162.5 mm) Valve Seat: Impregnated Teflon® 1" 51/16" 11/2" 23/46" 34" 3V8" 113/16" 4/16" 64" Indicator Plate:Steel (128 mm) (37.5 mm) (57 mm) (93 mm) (86 mm) (46 mm) (117 mm) (162.5 mm) Handle Stop:Steel 11/4" 57/16" 111/46" 29/46" 41/4" 35/16" 115/16" 5V16" 51/2" APPROVALS (163 mm) (43 mm) (65 mm) (108 mm) (83 mm) (51 mm) (141 mm) (192 mm) 1%z" 67/16" 113/46" 31/a" 51/16" 37/8" 25/s" 81/4" 107/8" UL and ULC Listed(EX4019) FM Approved (163 mm) (45 mm) (81.5 mm) (127 mm) (99 mm) (67 mm) (207 mm) (274 mm) NYC-BSA No. 720-87-SM 2" 67/16" 113/16" 31/4" 51/16" 37/8" 24" 81/4" 104" (163 mm) (45 mm) (81.5 mm) (127 mm) (99 mm) (67 mm) (207 mm) (274 mm) .x,'''':*Available on 11/4"to 2"size units only *+ ** **Available on 11/2"and 2"size units only *`**** THE MODEL 1000 PROVIDES ALL OF THE FOLLOWING... 401.1- MADE IN U.S.A. From the 2007 Edition of NFPA 13 Chapter 8.16.2.4.1* Provisions shall be made to properly drain all parts of the system. Chapter 8.16.2.4.2 Drain connections, interior sectional or floor control valve(s)—shall be provided with a drain &8.16.2.4.3 connection having a minimum size as shown in Table 8.16.2.4.2. Chapter 8.16.2.4.4 Drains shall discharge outside or to a drain capable of handling the flow of the drain. Chapter A.8.17.4.2 (Wet Pipe System)test connection is permitted to terminate into a drain capable of accepting full flow... using an approved sight test connection containing a smooth bore corrosion-resistant orifice giving a flow equivalent to one sprinkler... Chapter 8.17.4.2.2 The test connection valve shall be readily accessible. Chapter 8.17.4.2.4 shall be permitted to be installed in any location...downstream of the waterflow alarm. Chapter 8.17.4.3.1 (Dry Pipe System)a trip test connection not less than 1" in diameter,terminating in a smooth bore corrosion-resistant orifice,to provide a flow equivalent to one sprinkler... Chapter 8.17.4.3.2 The trip test connection...with a shutoff valve and plug not less than 1",at least one of which shall be brass. USA Patent # 4741361 and Other Patents Pending AGF Manufacturing Inc. Job Name: G 100 Quaker Lane,Malvern,PA 19355 Phone:610-240-4900 Architect: Fl Fax:610-240-4906 Engineer: www.testandrain.com Contractor: .447ffig§.0 P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org 510 CPVC - COPPER - STEEL HANGER 0 Fastener SIZE Q E Dim -Q, J 3/4 2.125 0 1 2.312 1 1/4 3.170 1 1/2 3.400 2 4.010 2 1/2 4.320 3 5.320 SIZE-SYSTEM PIPE: 3/4"thru 3" MATERIAL-Carbon Steel. FINISH-Mil. Galvanized. LISTING/APPROVAL- `Ous 203-EX 4231,EX 2551 FUNCTION-Support horizontal piping: CPVC,Copper or Steel. Size 3/4"-2"Prevents upward movement of pipe from pendent sprinkler discharge. Stabilize vertical piping. INSTALLATION- Per these instructions including NFPA 13, 13R, 13D and CPVC manufacturers instructions. Install on horizontal or vertical mounting surface. FASTENERS- UL Listed per NFPA 13 in WOOD: 3/4" -3"CPVC pipe-#905 screw-no pre-drill. 3/4"-3"Steel and Copper pipe-#14 x 1 1/2" SMS or 1/4"x11/2"lag bolt-no pre-drill. Restraint in STEEL-min. 18 GA. 3/4"-3"CPVC,Copper and Steel pipe- 1/4"or#14 Tek Screw. FEATURES -1 J *Offset edge eliminates abrasion. *Retainer dimples secure hanger to pipe during installation. *Required AFCON#905 screw included 5/16"hex head. Hanger Stabilize ORDERING-Part#and pipe size. 1 � 1 I � CAN ALSO BE USED TO REPLACE -#500 Pipe Strap #520 Tin Strap Specific AFCON products are exclusively designed to be compatible ONLY with other AFCON products including parts and fasteners,resulting in a listed sway brace,restrainer or hanger assembly. Be advised the following warranty restriction will apply. DISCLAIMER-AFCON will NOT warrant against the failure of its products when used in combination with other products,parts or systems not manufactured or sold by AFCON.AFCON shall NOT be liable under any circumstances whatsoever for any director indirect,incidental or consequential damages of any kind,including but not limited to loss of business or profit,when non-AFCON products have been,or are used. 5/14